ON-SITE GUIDE
BS 7671 : 2001 (2004)
Wiring Regulations
16th Edition
Including Amendments
No 1 : 2002 and No 2 : 2004
oe
a
a
—_
an
'?
=
O
PriPublished by: The IEE, LONDON, UK
©2004 The Institution of Electrical Engineers
Printed February 1992
Reprinted May 1993, with amendments
Reprinted July 1993, with amendment (Appendix 9)
Reprinted February 1994, with amendments
Revised February 1995 to incorporate Amendment No 1 to BS 7671
Revised June 1996, new cover only
Revised June 1998 to incorporate Amendment No 2 to BS 7671
Revised Feb 2002 to incorporate BS 7671 : 2001, inc Amd No 1: 2002
Reprinted July 2003, new cover only
Revised April 2004 to incorporate BS 7671 : 2001, inc Amd No 2: 2004
This publication is copyright under the Berne Convention 2003 and the Universal
Copyright Convention. All rights reserved. Apart from any fair dealing for the purposes
of research or private study, or criticism or review, as permitted under the Copyright,
Designs and Patents Act, 1988, this publication may be reproduced, stored or
transmitted, in any form or by any means, only with the prior permission in writing of
the publishers, or in the case of reprographic reproduction in accordance with the terms
of licences issued by the Copyright Licensing Agency. Inquiries concerning reproduction
outside those terms should be sent to the publishers at the undermentioned address:
The IEE, Michael Faraday House, Six Hills Way, STEVENAGE, SG1 2AY, United Kingdom
Copies may be obtained from The IEE:
The IEE
P.O. Box 96
Stevenage
SG1 2SD, UK
Tel: +44 (0)1438 767 328
Email:
[email protected]
http:/www.iee.org/Publish/Books/WireAssod’
While the publisher and contributors believe that the information and
guidance given in this work is correct, all parties must rely upon their
own skill and judgement when making use of it. Neither the publisher
nor any contributor assume any liability to anyone for any loss or
damage caused by any error or omission in the work, whether such
error or omission is the result of negligence or any other cause. Where
reference is made to | lation it is not to be considered as legal
advice. Any and all such liability is disclaimed.
ISBN 0 86341 3749
2PREFACE
FOREWORD
SECTION 1.
11
1.2
SECTION 2.
2.1
2.2
SECTION 3.
SECTION 4.
41
4.2
43
44
45
4.6
47
48
49
CONTENTS
INTRODUCTION
Scope
Basic Information Required
THE SERVICE POSITION
General Layout of Equipment
Function of Components:
PROTECTION
Types of Protective Device(s)
Overload Protection
Fault Current Protection
Protection Against Electric Shock
Disconnection Times
Residual Current Devices (RCD)
BONDING AND EARTHING
Main Equipotential Bonding of Metal
Services (Figs 4a, 4b, 4c)
Main Earthing and Main Equipotential
Bonding Conductor Cross-sectional Areas
Main Equipotential Bonding - Plastic Services
Earthing
Supplementary Equipotential Bonding in
Locations of Increased Shock Risk - Metal
Pipework
Supplementary Bonding in other Locations -
Metal Pipework
Supplementary Bonding of Plastic Pipe
Installations
Earth Electrode (Fig 4c)
Types of Earth Electrode
4.10 Typical Earthing Arrangements
24
24
25
2
2
26
26
32
32
33SECTION 5.
SECTION 6.
6.1
SECTION 7.
71
72
73
74
SECTION 8.
8.1
8.2
8.3
84
‘SECTION 9.
9.1
9.2
9.3
SECTION 10. GUIDANCE NOTES ON INITIAL TESTING OF
ISOLATION AND SWITCHING
Isolation
Functional Switching
Switching Off for Mechanical Maintenance
Emergency Switching
LABELLING
Labels to be Provided
FINAL CIRCUITS
Final Circuits
Using the Tabulated Final Circuits
Installation Considerations
Smoke Alarms and Emergency Lighting
SPECIAL LOCATIONS GIVING RISE TO
INCREASED RISK OF ELECTRIC SHOCK
Locations Containing a Bath or Shower
Shower Cubicles in a Room used for Other
Purposes
Temporary and Garden Buildings, Domestic
Garages, Buildings of Lightweight
Construction etc
Earthing requirements of Equipment
having High Protective Conductor Current
INSPECTION AND TESTING
inspection and Testing
Inspection
Testing
INSTALLATIONS
10.1 Safety and equipment
10.2 Sequence of Tests
10.3 Test Procedures
60
60
62
62
65
66
67SECTION 11. OPERATION OF RESIDUAL CURRENT
OPERATED DEVICES(RCDs) AND
RESIDUAL CURRENT BREAKERS WITH
OVERCURRENT PROTECTION (RCBOs)
11.1 General Test Procedure
11,2 General purpose RCDs to BS 4293
11.3 General purpose RCCBs to BS EN 61008 or
RCBOs to BS EN 61009
11.4 RCD protected socket-outlets to BS 7288
11.5 Additional Requirement for Supplementary
Protection
11.6 Integral Test Device
81
81
81
81
81
82
82APPENDICES
Maximum demand and diversity
2. Maximum permissible measured earth
fault loop impedance
3 Notes on the selection of types of
cable and flexible cord for particular
uses and external influences
4 Notes on methods of support for
cables, conductors and wiring systems
5 Cable capacities of conduit and
trunking
6 Current-carrying capacities and
voltage drop for copper conductors
7 Certification and reporting
8 Standard circuit arrangement for
household and similar installations
9 Resistance of copper and aluminium
conductors
10 Protective conductor sizing
11 Identification of conductors
INDEXES
(i) The installation
(ii) Bonding and earthing
(iii) Special locations and RCDs
(iv)
w)
Inspection and testing
Alphabetical
Page
88
94
100
109
115
127
150
157
161
164
170
173
174
176
178Co-operating Organisations
The IEE acknowledges the contribution made by the following organisations
in the preparation of this guide.
Association of Manufacturers of Domestic Electrical Appliances
§ A MacConnacher BSc CEng MIEE
BEAMA Installation Ltd
Eur Ing M H Mullins BA CEng FIEE FIIE
British Cables Association
CK Reed | Eng MIIE
British Electrotechnical & Allied Manufacturers Association Ltd
R F B Lewington MIEE
British Electrotechnical Approvals Board
P D Stokes MA CEng MRAeS.
British Standards Institution
MR Danvers
City & Guilds of London Institute
HR Lovegrove IEng FIIE
Electrical Contractors’ Association
D Locke IEng MIIE ACIBSE
Electrical Contractors’ Association of Scotland t/a SELECT
D Millar IEng MIIE MILE
Electricity Association Limited
DJ Start BSc CEng MIEE
ERA Technology Ltd
M W Coates BEng
Federation of the Electronics Industry
F W Pearson CEng MIIE
The GAMBICA Association Ltd
K A Morriss BSc CEng MIEE
Health & Safety Executive
Eur Ing J A McLean BSc CEng FIEE FIOSH
Institution of Incorporated Engineers
P Tootill IEng MIIE
Lighting Association
K R Kearney IEng MIIE
National Inspection Council for Electrical Installation Contracting
Safety Assessment Federation Limited
J Gorman BSc (Hons) CEng MIEE
Society of Electrical and Mechanical Engineers serving Local Government
CJ Tanswell CEng MIEE MCIBSE
Editor PR L Cook CEng FIEE MCIBSEPREFACE
The On-Site Guide is one of a number of publications prepared by
the IEE to simplify some aspects of BS 7671 : 2001 (2004) Requirements
for Electrical Installations (IEE Wiring Regulations Sixteenth Edition).
BS 7671 is a joint publication of the British Standards Institution and
the Institution of Electrical Engineers.
The scope generally follows that of BS 7671. It includes material not
included in BS 7671, provides background to the intentions of BS 7671,
and gives other sources of information.
However, this guide does not ensure compliance with BS 7671. It is a
simple guide to the requirements of BS 7671, and electricians should
always consult BS 7671 to satisfy themselves of compliance.
It is expected that persons carrying out work in accordance with this
guide will be competent to do so.
Electrical installations in the United Kingdom which comply with the
IEE Wiring Regulations, BS 7671, should also comply with the
Statutory Regulations such as the Electricity at Work Regulations 110-01-01
1989. It cannot be guaranteed that BS 7671 complies with all
relevant Regulations and it is stressed that it is essential to establish
what statutory and other Regulations apply and to _ install
accordingly. For example, an installation in Licensed Premises may App 2(vi)
have requirements different from or additional to BS 7671 and these
will take precedence over BS 7671.FOREWORD
This Guide is concerned with limited application of BS 7671 in
accordance with para 1.1 Scope. Part 1
BS 7671 and the On-Site Guide are not design guides. It is essential to
prepare a schedule of the work to be done prior to commencement
or alteration of an electrical installation and to provide all necessary
information and operational manuals of any equipment supplied to
the user on completion.
Any specification should set out the detailed design and provide
sufficient information to enable competent persons to carry out the
installation and to commission it. The specification must include a
description of how the system is to operate and all of the design and
operational parameters.
The specification must provide for all the commissioning procedures
that will be required and for the production of any operational
manual.
It must be noted that it is a matter of contract as to which person
or organisation is responsible for the production of the parts of the
design, specification and any operational manual.
The persons or organisations who may be concerned in the
preparation of the specification include:
The Designer(s)
The Installer(s)
The Electricity Distributor
The Installation Owner and/or User
The Architect
The Fire Prevention Officer
The Planning Supervisor
All Regulatory Authorities
Any Licensing Authority
The Health and Safety ExecutiveIn producing the specification advice should be sought from the
installation owner and/or user as to the intended use. Often, such
as in a speculative building, the detailed intended use is unknown. In
those circumstances the specification and/or the operational manual
must set out the basis of use for which the installation is suitable.
Precise details of each item of equipment should be obtained from
the manufacturer and/or supplier and compliance with appropriate
standards confirmed.
The operational manual must include a description of how the
system as installed is to operate and all commissioning records. The
manual should also include manufacturers’ technical data for all
items of switchgear, luminaires, accessories, etc and any special
instructions that may be needed. The Health and Safety at Work etc
Act 1974 Section 6 and the Construction (Design and Management)
Regulations 1994 are concerned with the provision of information.
Guidance on the preparation of technical manuals is given in BS 4884
(Specification for technical manuals) and BS 4949 (Recommendations
for the presentation of technical information about products and
services in the construction industry). The size and complexity of the
installation will dictate the nature and extent of the manual.
10SECTION 1.
11
ON-SITE GUIDE
INTRODUCTION
Scope
This Guide is for electricians (skilled persons). It covers the
following installations:
(a)
(b)
domestic installations generally, including off-peak
supplies, and supplies to associated garages,
out-buildings and the like
industrial and commercial single- and three-phase
installations where the distribution board(s) or
consumer unit is located at or near the distributor's
cut-out.
Note: Special Installations or Locations (Part 6 of BS 7671) are generally Part 6
excluded from this Guide. Advice is given on installations in locations
containing a bath or shower (8.1), temporary and garden buildings etc (8.3)
and personal computer circuits in office locations (8.4).
This Guide is restricted to installations : 313-01-01
@
(i)
(iii)
tiv)
at a supply frequency of 50 Hertz
at a nominal single-phase voltage of 230 V a.c.
single-phase and 230/400 V a.c. three-phase
fed through a distributor's cut-out having a fuse or
fuses to BS 1361 Type !! or through fuses to BS 88-2 or
BS 88-6
with a maximum value of the earth fault loop
impedance outside the consumer's installation as
follows:
Earth return via sheath (TN-S system): 0.8 ohm
Earth return via combined neutral and earth conductor
(TN-C-S system): 0.35 ohm
TT systems: 21 ohms excluding consumer's earth
electrode
11
Sect12
Sec1
This Guide contains information which may be required in
general installation work, e.g. conduit and trunking capacities,
bending radii of cables.
This Guide introduces the use of conventional circuits, which
are discussed in Section 7.
Because of simplification this Guide may not give the most
economical result.
This Guide is not a replacement for BS 7671, which should always
be consulted. Defined terms according to Part 2 of BS 7671 are
used in this Guide.
In conformance with the definitions of BS 7671, throughout
this Guide the term ‘live part’ is used to refer to a conductor or
conductive part intended to be energised in normal use,
including a neutral conductor. For convenience in use, and in
accordance with current UK manufacturing practice, the Part 2
terminals of electrical equipment shown in Figs 10.1 to 10.5 figs 3to7
have been identified by the letters L, N and E.
Further information is available in the series of Guidance Notes
published by the Institution.
For new domestic installations and major refurbishments
account should be taken of the recomrnendations in Approved
Document B, issued as guidance on the Building Regulations
1991. Part B1, Section 1 advises that, if dwellings are not
protected by an automatic fire detection and alarm system to
Part 6 of BS 5839, a suitable number of mains operated
self-contained smoke alarms to BS 5446 be installed.
In Scotland the Building Standards (Scotland) Regulations 1990
apply and installations must comply with The Scottish Office
Technical Standards .1.2 Basic Information Required Part 3
Before starting work on an installation that requires a new
supply, the electrician should obtain the following information
from the distributor:
w
(i)
(iii)
(iv)
(v)
(vi)
(vii)
the number of phases to be provided 312-02-01
the distributor's requirement for cross-sectional area 313.01-014i)
and length of meter tails
the maximum prospective fault current (pfc) at the 313.01-01(i)
supply terminals
the maximum earth loop impedance (Ze) of the earth —_313.01-01()
fault path outside the consumer's installation
the type and rating of the distributor's fusible cut-out — 313.01-01(v)
or protective device
the distributor's requirement regarding the size of main 547-0201
equipotential bonding
the earthing arrangement and type of system 312-03-01
(viii) the arrangements for the incoming cable and metering. 31301010)
For existing installations, electricians should satisfy themselves
as to the suitability of the supply including the earthing
arrangement.
13
Sec1SECTION 2. THE SERVICE POSITION
2.1 General Layout of Equipment
The general layout of the equipment at the service position is
shown in Figs 2a and 2b.
2.2 Function of Components:
(i) Distributor’s Cut-out
This will be sealed to prevent the fuse being withdrawn 31301-01()
by unauthorised persons. When the meter tails and
consumer unit are installed in accordance with the
requirements of the distributor the cut-out may be
assumed to provide fault current protection up to the
consumer's main switch.
(ii) Supplier's Meter
This will be sealed by the supplier to prevent
interference by unauthorised persons.
(iii) Meter Tails
These are part of the consumer's installation. They 4730204)
should be insulated and sheathed or insulated and 521-0703
enclosed in conduit or trunking.
Polarity should be indicated by the colour of the 514-06
insulation and the minimum cable size should be
25 mmé. The distributor may specify the maximum length
and the minimum cross-sectional area (see 1.2(ii)).
Where the meter tails are protected against fault current 473-0204)
by the distributor's cut-out the method of installation,
maximum length and minimum cross-sectional area
must comply with the requirements of the distributor.
14
Sec2Fig 2a: Layout when the supplier does not provide a main switch
Note: Earthing arrangements have been omitted for clarity. Tails between the
meter and the consumer's installation are provided by the consumer
meter
~~ supplier's
terminals
consumer's meter tails
istributor’s
cut-out
Fig 2b: Layout when the supplier does provide a main switch
Note: Earthing arrangements have been omitted for clarity. Tails between any
main switch provided by the supplier and the consumer's installation are
provided by the consumer
consumer's
tails
Pe supplier’s
main switch terminals
15
Sec216
Sec2
(iv)
Ww)
Supplier’s Switch
Some suppliers may provide and install a suitable switch
between the meter and the consumer unit. This permits 476-01-01
the supply to the installation to be interrupted without
withdrawing the distributor's fuse in the cut-out.
Consumer's Controlgear
A consumer unit is for use on single-phase installations. part 2
It contains a double-pole main switch and fuses or
circuit-breakers (cbs) and perhaps residual current
devices (RCDs) or residual current breakers with integral
overcurrent protection (RCBOs) for the protection of
each final circuit. Alternatively, a separate main switch
and distribution board may be provided.SECTION 3. PROTECTION
3.1 Types of Protective Device(s)
The consumer unit (or distribution board) contains devices for ch 43
the protection of the final circuits against:
(i) overload 433
(ii) short-circuit 434
(iii) earth fault. 434
Functions (i) and (ii) are carried out usually by one device, a fuse
or circuit-breaker,
Function (iii) may be carried out by the fuse or circuit-breaker 413-02-04
provided for functions (i) and (ii), or by an RCD.
An RCBO being a combined circuit-breaker and RCD will carry
out functions (i), (ii) and (iii).
3.2 Overload Protection
Overload protection is given by the following devices:
Fuses to BS 88-2.1 or BS 88-6; BS 1361 and BS 3036; App3
miniature circuit-breakers to BS 3871-1 Types 1, 2 and 3;
circuit-breakers to BS EN 60898 types B, C and D; and
residual current circuit-breakers with integral
overcurrent protection (RCBOs) to BS EN 61009-1.
3.3 Fault Current Protection
When a consumer unit to BS EN 60439-3 or BS 5486 : Part 13, 473-02-04
or a fuseboard having fuselinks to BS 88-2.1 or BS 88-6 or BS 1361
is used, then fault current protection will be given by the
overload protective device.
For other protective devices the breaking capacity must be
adequate for the prospective fault current at that point.
3.4 Protection Against Electric Shock
(i) Direct Contact 412
Electrical insulation and enclosures and barriers give 412-01-01
protection against direct contact. Non-sheathed
insulated conductors must be protected by conduit or 521-07-03
17
Sec318
Sec3
(i)
(ii)
trunking or be within a suitable enclosure. A 30 mA
RCD may be provided to give supplementary protection 412.06
against direct contact, but must not be relied upon for
primary protection.
Indirect Contact a3
Protection against indirect contact is given by limiting
to safe values the magnitude and duration of voltages
that may appear under earth fault conditions between
simultaneously accessible exposed-conductive-parts of
equipment, and between them and _ extraneous-
conductive-parts or earth. This may be effected by the:
(a) co-ordination of protective devices and circuit 4113-02-04
impedances, or
(b) use of RCDs to limit the disconnection time, or 413-02-07
(©) __ use of Class Il equipment or equivalent insulation. 413-03
SELV and PELV
SELV 411-02
Separated extra-low voltage (SELV) systems
(a) are supplied from isolated safety sources such as 411-02-02
a safety isolating transformer to BS 3535
(b) have no live part connected to earth or the 411-02-05
protective conductor of another system
(are enclosed in an insulating sheath additional to 411-02-06
their basic insulation
(d) have no exposed-conductive-parts connected to 411-02-07
earth, to exposed-conductive-parts or protective
conductors of other systems or to extraneous-
conductive-parts.
PELV A71-14-01
Protective extra-low (PELV) systems must meet all the 471-14-02
requirements for SELV, except that the circuits are not
electrically separated from earth.For SELV and PELV systems protection against direct 411-02-09
contact need not be provided if voltages do not exceed 471-14-02
the following:
Location SELV
Dry areas 25 V a.c. or 60 Vd.c. 25 Vac. or 60V dc. 411-02-09
Bathrooms, swimming _| Protection required at__| Protection required at | 601-03-02
pools, saunas all voltages all voltages 6602-03-01
6603-03-01
Other areas 12V ac. or 30Vd.c. 6Va.c.or 15Vd.c. 471-01-01
471-14-02
3.5 Disconnection Times
3.5.1 Conventional Circuits
For the conventional circuits given in Section 7, the correct
disconnection time in seconds (0.4 s or 5s) is obtained by using
the protective devices and related maximum circuit lengths in
Table 7.1.
3.5.2 Special Circuits
A disconnection time of not more than 0.4 s is required for final
circuits supplying:
(i) portable equipment intended to be moved by hand 413-02-09
while in use
(ii) hand-held metal-cased equipment requiring an earth, —413-02-09
and supplied directly or through a socket-outlet
(iii) fixed equipment outside the equipotential zone with —_471-08-03
accessible exposed-conductive-parts
3.6 Residual Current Devices (RCD)
Note: Residual current device (RCD) is a device type that includes residual current
circuit-breakers (RCCBs) and residual current circuit-breakers with integral
overcurrent protection (RCBOs).
3.6.1 Protection by an RCD
There are a number of instances where an installation is
required to incorporate one or more RCDs (RCCB or RCBO).
These instances include:
19
Sec320
Sec3
(i) where the earth fault loop impedance is too high to
provide the required disconnection time e.g. where the
distributor does not provide an earth - TT systems
(ii) onsocket-outlet circuits in TT systems
(iii) on all socket-outlets that may reasonably be expected
to supply portable equipment used outdoors
(iv) circuits supplying portable equipment for use outdoors
by means of a flexible cable.
(v) on socket-outlets in a room, other than a bathroom or
shower room, containing a shower cubical.
3.6.2 Applications of RCDs
Installations are required to be divided into circuits to avoid
danger and minimise inconvenience in the event of a fault and
to take account of hazards that might arise from the failure of
a single circuit, e.g. a lighting circuit.
30 mA RCDs installed to provide protection to socket-outlets
likely to feed portable equipment outdoors should protect only
those sockets, see Fig 3b.
Where an RCD is fitted only because the earth loop impedance
is too high for shock protection to be provided by an
overcurrent device, for example in a TT system, the rated
residual operating current should not be less than 100 mA.
If two RCDs are installed they should preferably control
separate circuits, see Fig 3a(i), or a time delay 100 mA or
greater RCD (S type) should be installed, see Fig 3a(ii).
The use of RCBOs, see Fig 3a(iii), will minimise inconvenience
in the event of a fault.
The enclosures of RCDs or consumer units incorporating RCDs
in TT installations should be of an all-insulated or Class I!
construction. Otherwise, additional precautions recommended
by the manufacturer need to be taken to prevent faults to
earth on the supply side of the RCD.
413-02-19
471-08-06
471-16-01
471-16-02
6601-08-02
314-01-01
314-01-02Fig 3a: Installing RCDs in a TT installation
i} consumer unit with separate isolator
ii) consumer unit using time delayed RCD as main switch
Rote 1 circuits to lights, cooker, water heater, smoke alarms
(labelled) as the main switch for the installation
consumer unit with insulated enclosure or
additional protection to meter and isolator tails
consumer unit with insulated enclosure or
additional protection to meter tails
note 1
2 circuits to portable equipment outdoors and socket-outlets that may reasonably supply
portable equipment outdoors (ground floor socket-outlets)
3 time delay (S-type) double-pole RCD to BS EN 61008. This RCD must be clearly identified
21
Sec3Fig 3a cont'd: Installing RCDs in a TT installation
22
Sec3
HD consumer unit with RCBOs consumer unit with insulated enclosure or
additional protection to meter tails
lan 2 100 mA,
note 4 Circuits to lights, cooker, water heating, smoke alarms
5 Circuits to portable equipment outdoors and socket-outlets that may reasonably supply
equipment outdoors, and certain equipment in bathrooms - see Table 8.1
3.6.3 Applications of residual current circuit-breakers with
overload current protection (RCBOs)
In TN systems it is preferable for reliable operation for indirect 413-02-04
shock protection to be provided by overcurrent devices,
including RCBOs operating as overcurrent devices; that is, with
loop impedances complying with Table 2D of Appendix 2. RCBOs
are then providing indirect shock protection as overcurrent
devices and supplementary protection against direct contact as 471-16
residual current circuit-breakers (RCCBs).
When the designer intends that indirect shock protection is to 413-02-16
be provided by a residual current circuit-breaker (RCCB) or the
residual current element of an RCBO, loop impedances are as
for an RCD, that is appropriate to the rated residual operating
current (Zs < 50 V/ lan), and not more than 200 ohms.Fig 3b: Installing RCDs in a TN-S or TN-C-S installation
note 1 The 30 mA RCD and associated cbs may be replaced by residual current breakers with
‘overcurrent protection (RCBOs) on the main switch busbar rail
2 Circuits to lights, cooker, water heating, smoke alarms
3 Circuits to portable equipment outdoors and socket-outlets that may reasonably supply
equipment outdoors
23
Sec3SECTION 4. BONDING AND EARTHING
4.1 Main Equipotential Bonding of Metal Services (Figs 4a,
4b, 4c)
Main equipotential bonding conductors are required to 413-02-02
connect the following metallic parts to the main earthing
terminal, where they are extraneous-conductive-parts:
i) metal water service pipes
(ii) _ metal gas installation pipes
(iii) other metal service pipes (including oil and gas supply
pipes) and ducting
(iv) metal central heating and air conditioning systems
(v) exposed metallic structural parts of the building
(vi) lightning protection systems.
4.2 Main Earthing and Main Equipotential Bonding
Conductor Cross-Sectional Areas
The minimum cross-sectional area (csa) of the main equipotential 547-02-01
bonding conductor is half that of the main earthing
conductor. For 100 A TN installations, the main earthing
conductor csa needs to be 16 mm2 and that of the main
bonding conductors 10 mm2 where the size of the supply Table 54H
neutral conductor is not more than 35 mm2. However, local
public electricity distribution network conditions may require
larger conductors. For other conditions see Table 10A of
Appendix 10. For TT installations see Fig 4c.
Note that:
(i) only copper conductors should be used; copper covered 542-03-03
aluminium conductors or aluminium conductors or
structural steel can only be used if special precautions
outside the scope of this Guide are taken
(ii) bonding connections to incoming metal services should 547-02-02
be as near as possible to the point of entry of the
services to the premises, but on the consumer's side of
any insulating section
(iii) the connection to the gas, water, oil, etc service should 47-02-02
be within 600 mm of the service meter, or at the point
of entry to the building if the service meter is external,and must be on the consumer's side before any branch
pipework and after any insulating section in the service.
The connection must be made to hard pipe, not to soft
or flexible meter connections
{iv) the connection must be made using clamps (to BS 951) 542-03-03
which will not be subject to corrosion at the point of
contact
() if incoming gas and water services are of plastic, main
bonding connections are to be made to metal
installation pipes only.
4.3 Main Equipotential Bonding - Plastic Services
There is no requirement to main bond an incoming service
where both the incoming service pipe and the pipework
within the installation are both of plastic. Where there is a
plastic incoming service and a metal installation within the
premises, main bonding must be carried out, the bonding
being applied on the customer's side of any meter, main stop
cock or insulating insert.
44 — Earthing
Every exposed-conductive-part (a conductive part of equipment 413-02-06
which can be touched and which is not a live part but which 413-02-18
may become live under earth fault conditions) shall be
connected by a protective conductor to the main earthing
terminal.
4.5 Supplementary Equipotential Bonding in Locations of
Increased Shock Risk - Metal Pipework
Supplementary equipotential bonding is required only in
locations of increased shock risk such as some of those in Part 6
of BS 7671 (471-08-01). In domestic premises, the locations 471-08-01
identified as having increased shock risks are rooms containing
a bath or shower (bathrooms) and around swimming pools.
In a bathroom or shower room, local supplementary equipotential 601-04-01
bonding is required to be provided connecting together the
terminal of protective conductors of each circuit supplying
Class | and Class II equipment in zones 1, 2 or 3, and extraneous-
conductive-parts in these zones including the following:
(i) metal pipes supplying services and metallic waste pipes
(e.g. water, gas)
25
Seca26
Seca
(ii) metal central heating pipes and air conditioning systems
(iii) accessible metal structural parts of the building (metal
door architraves, metal handrails, window frames and
similar parts are not considered to be extraneous-
conductive-parts unless they are connected to metallic
structural parts of the building)
(iv) metal baths and metal shower basins.
Circuit protective conductors may be used as supplementary
bonding conductors.
The supplementary equipotential bonding may be provided in
close proximity to the location.
See Section 8.1 for locations containing a bath or shower,
A typical installation is shown in Figure 4d. 601-04-01
4.6 Supplementary Bonding in other Locations - Metal 471-08-01
Pipework
There is no specific requirement in BS 7671 to supplementary
bond the following
kitchen pipes, sinks or draining boards
metal furniture in kitchens
metal pipes and wash hand basins in domestic locations
other than bathrooms.
Note: Metal waste pipes in contact with earth should be main bonded back to
the main earthing terminal.
4.7 Supplementary Bonding of Plastic Pipe Installations
Supplementary bonding is not required to metal parts
supplied by plastic pipes, such as metal hot and cold water taps
supplied from plastic pipes. A metal bath not connected to
extraneous-conductive-parts (such as structural steelwork) with
plastic hot and cold water pipes and plastic waste pipes does
not require supplementary bonding. Supplementary bonding
in a bathroom or shower room will still be required between
the protective conductors of circuits supplying Class 1 and Class II
equipment in the zones e.g. heaters, showers and accessible
luminaires, see Figure 4e.Fig 4a: Typical earthing arrangements and protective conductor csa - TN-S
meter
LABE|
yes
Lz
meter tails 25 mm2
consumer unit
or distribution board
2
16 mm earthing bar
LABEL |
gb 10 mm? [apet]| | 40 mm2
intake 7 ope [rape]
int LABEI
main
earthing metal metal
terminal water gas
16 mm2 pipe Pipe
main earthing main equipotential
conductor bonding conductors
supply earth
TN-S: Earthed to armour or metallic sheath
Note: i) Main equipotential bonding conductors may be separate (as shown) or looped with unbroken conductors.
ji) [LABEL J - Safety Electrical Connection - Do Not Remove.
LABEL
other
extraneous-
conductive-
partsy22s
8z
Fig 4b: Typical earthing arrangements and protective conductor csa - TN-C-S
meter
meter tails 25 mm?
16 mm? consumer unit
or distribution board
; (TaBeL] earthing bar
intake LABEL | LABEL
9 000
7 10mm? f LABEL |
i 16mm — tomm T | other
T na main equipotential ee
earthing bonding conductors best aboard
supply earth terminal : Parts
pme metal metal
connection water gas
pipe pipe
iii) LABEL }- Safety Electrical Connection - Do Not Remove.
i) Main equipotential bonding conductors may be separate (as shown) or looped with unbroken conductors.
ii) Local electricity distribution network conditions may require larger conductors.Fig 4c: Typical earthing arrangements and protective conductor csa - TT
meter
meter tails 25 mm?
RCDs
consumer unit
or distribution board
earthing bar
main earthing 6 mm2
conductor
6mm2 [ABEL]
BEL.
see Table 10C 6 mm2 LABEL [ABEL
00 O00
main
earthing metal metal
—— earth terminal water a
electrode pipe pipe other
. extraneous-
TT: Earth return via earth electrode conductive-
Note: i) Main equipotential bonding conductors may be separate (as shown) or looped with unbroken conductors. parts
i) [LABEL |- Safety Electrical Connection - Do Not Remove.
£3 iii) An earth electrode resistance exceeding 192 is presumed, see paragraph 4.10.
©
5Bw
ao
Outside Zones:
~ Radiant fire
1.
metal waste
* Zone | if the space is accessible without the use of a tool.
Spaces under the bath, accessible only with the use of a tool, are outside the zones.
2.25m | Outside Zones
7 ' Notes:
The protective conductors
of all power and lighting
points within the zones
must be supplementary
bonded to all extraneous-
conductive-parts in the
zones, including metal
waste, water and central
heating pipes, and metal
baths and metal shower
basins.
. Circuit protective
conductors may be used as
supplementary bonding
conductors.Fig 4e: Supplementary bonding in a bathroom - plastic pipe installation
Ceiling
Outside Zones
225m : Outside Zones
: Notes:
1. The protective conductors
of all power and lighting
points within the zones
must be supplementary
bonded. The bonding
connection may be to the
earth terminal of a switch
or accessory supplying
equipment.
. Circuit protective
conductors may be used as
supplementary bonding
conductors.
plastic pipes ?
plastic waste
** Zone 1 if the space is accessible without the use of a tool.
Spaces under the bath, accessible only with the use of a tool, are outside the zones.
yes
Le4.8 — Earth Electrode (Fig 4c)
This is connected to the main earthing terminal by the earthing 542-01-04
conductor and provides part of the earth fault loop for a TT
installation.
It is recommended that the earth fault loop impedance for TT 542-02-02
installations does not exceed 200 ohms.
Metal gas or water or other metal service pipes are not to be 542-02-04
used as the earth electrode, although they must be bonded as
Paragraph 4.1.
49 — Types of Earth Electrode
The following types of earth electrode are recognised:
) earth rods or pipes 542-02-01
(ii) earth tapes or wires 542-02-01
(ji) earth plates 542-02-01
(iv) underground structural metalwork embedded in 542-02-01
foundations
(v) welded metal reinforcement of concrete embedded in 542-02-01
the earth (excluding pre-stressed concrete)
(vi) lead sheaths and metal coverings of cables, which must 542-02-05
meet the following conditions:
(a) _ the sheath or covering shall be in effective contact sa202.05(i)
with earth,
(b) the consent of the owner of the cable shall be 54202-0514)
obtained, and
(Q arrangements shall be made for the owner of 542-02-05(N)
the cable to warn the owner of the electrical
installation of any proposed change to the cable
or its method of installation which might affect
its suitability as an earth electrode.
32
Sec44.10 Typical Earthing Arrangements
for Various Types of Earthing System (Figs 4a, 4b, 4c)
Figs 4a, 4b and 4c show the single-phase arrangements, but three-
phase arrangements are similar.
The protective conductor sizes shown in Figures refer to copper Table 54G
conductors and are related to 25 mm? supply tails from the Table 54H
meter. 547-02-01
For TT systems protected by an RCD with an earth electrode 542-03-01
resistance 1 ohm or greater, the earthing conductor size need 543-01-03
not exceed 2.5 mm? if protected against corrosion by a sheath
and if also protected against mechanical damage; otherwise,
see Table 10C of Appendix 10.
The earthing bar is sometimes used as the main earthing
terminal; however, means must be provided in an accessible
position for disconnecting the earthing conductor to facilitate 542-04-02
testing of the earthing.
Note: For TN-S and TN-C-S installations, advice about the availability of an
earthing facility and the precise arrangements for connection should be
obtained from the distributor or supplier.
33
Sec4SECTION 5. ISOLATION AND SWITCHING
34
Sec5
5.1 Isolation
A means of isolation must be provided to enable electrically 460-01-01
skilled persons to carry out work on, or near, parts which
would otherwise normally be energised. Isolating devices must
comply with the isolation requirements of BS 1363-4, BS 3676, 511
BS EN 60669-2-4, BS EN 60898, BS EN 60947-2, BS EN 60947-3, 537-02-02
BS EN 61008-1 or BS EN 61009-1. The position of the contacts 537-02-04
must either be externally visible or be clearly, positively and 476-02-02
reliably indicated. If it is installed remotely from the
equipment to be isolated, the device must be capable of being
secured in the OPEN position.
Means of isolation should be provided as follows:
(i) at the origin of the installation, a main linked switch or 460-01-02
circuit-breaker should be provided as a means of
isolation and of interrupting the supply on load. For
single-phase household and similar supplies that may —_476-01-03
be operated by unskilled persons, a double-pole device
must be used for both TT and TN systems. For
three-phase supplies an isolator must interrupt the phase 460-01-04
and neutral conductors in a TT system; in a TN-S or TN-C-S
system only phase conductors need be interrupted.
Provision shall be made for disconnecting the neutral —_460-01-06
conductor. Where this is a joint it shall be such that it is
accessible, can only be disconnected by means of a tool,
is mechanically strong and will reliably maintain
electrical continuity
(ii) other than at the origin of the installation every circuit, 476-01-02
or group of circuits, which may have to be isolated
without interrupting the supply to other circuits should
be provided with its own isolating device, which must —_537-02-01
switch all live conductors in a TT system and all phase
conductors in a TN system
Every motor circuit should be provided with a readily accessible 131-14-02
device to switch off the motor and all associated equipment
including any automatic circuit-breaker.5.2 Functional Switching 537-05
A means of switching for interrupting the supply on load is 476-01-02
required for every circuit and final circuit.
One common switch may be used to interrupt the supply to a 476-01-01
group of circuits. Additionally, a separate switch must be
provided for every circuit which, for safety reasons, has to be 476-01-02
switched independently.
5.3 Switching Off for Mechanical Maintenance 462
A means of switching off for mechanical maintenance is 462-01-01
required where mechanical maintenance may involve a risk of
burns or of injury from mechanical movement, and may be
required for lamp replacement.
Each device for switching off for mechanical maintenance
must:
i) be capable of switching full load current 537-03-04
(ii) be suitably located in a readily accessible position 462-01-02
(ii) be identified with a permanent label unless its purpose 462-01-02
is obvious
(iv) _ have either an externally visible contact gap or a 537-03-02
clearly and reliably indicated OFF position. An
indicating light should not be relied upon
(v) be selected and installed to prevent unintentional 537-03-03
reclosure, such as might be caused by mechanical
shock or vibration.
5.4 Emergency Switching 463
An emergency switch is to be provided for every part of an 476-01-01
installation which may have to be disconnected rapidly from 476-03-04
the supply to prevent or remove danger. Where there is a risk
of electric shock the emergency switch is to disconnect all live 463-01-01
conductors, except in three-phase TN-S and TN-C-S systems 460-01-04
where the neutral need not be switched.
A means of emergency stopping is also to be provided where 463-01-05
mechanical movement of electrically actuated equipment may 476-03-02
give rise to danger.
35
Sec536
Sec5
A plug and socket-outlet or similar device shall not be selected 537-04-02
as a device for emergency switching.
An emergency switch must be:
i) readily accessible from the place where the danger 537-04-04
may occur
(ii) marked, preferably with a red handle or pushbutton —_537-04-04
(iii) capable of cutting off the full load current 537-04-01
(iv) _ of the latching type or capable of being restrained in 537-04-05
the ‘OFF’ or ‘STOP’ position
(vy) double-pole for single-phase systems. 463-01-01
(vi) if operated via a relay or contactor, of adesign which —_537-04-03
has fail-safe characteristics.
A fireman's switch must be provided to disconnect the supply to 476-03-05
a high voltage installation, e.g. a neon sign, but such installations
are outside the scope of this Guide (see Regulations 476-03-05
to 07 and 537-04-06 of BS 7671). 537-04-06SECTION 6. LABELLING
6.1 Labels to be Provided
The following durable labels are to be securely fixed on or
adjacent to equipment installed in final circuits.
(i) Unexpected presence of nominal voltage (U or Uo) 514-10-01
exceeding 230 V
Where the nominal voltage (U or Uo) exceeds 230 V,
e.g. 400 V phase-to-phase, and it would not normally be
expected to be so high, a warning label stating the
maximum voltage present shall be provided where it
can be seen before gaining access to live parts.
(ii) | Nominal voltage exceeding 230 volts (U or Uo) 514-10-01
between simultaneously accessible equipment
For simultaneously accessible equipment with terminals
or other fixed live parts having a nominal voltage (U or Uo)
exceeding 230 volts between them, e.g. 400 V phase-to-
phase, a warning label shall be provided where it can
be seen before gaining access to live parts.
(iii) Presence of different nominal voltages in the same 514-10-01
equipment
Where equipment contains different nominal voltages,
e.g. both low and extra-low, a warning label stating the
voltages present shall be provided so that it can be seen
before gaining access to simultaneously accessible live parts.
(iv) Connection of earthing and bonding conductors 514.13,
A label to BS 951 durably marked with the words as follows 514-13-01
SAFETY ELECTRICAL CONNECTION - DO NOT REMOVE
shall be permanently fixed in a visible position at or near
the point of connection of
(1) every earthing conductor to an earth
electrode or other means of earthing, and
(2) every bonding conductor to extraneous-
conductive-parts, and
(3) at the main earth terminal, where it is not part
of the main switchgear.
37
Sec638
Sec6
Ww
(vi)
(vii)
(viii)
(ix)
Purpose of switchgear and controlgear 514-01-01
Unless there is no possibility of confusion, a label
indicating the purpose of each item of switchgear and
controlgear shall be fixed on or adjacent to the gear. It
may be necessary to label the item controlled, as well as
its controlgear.
Identification of protective devices 514-08-01
A protective device, e.g. fuse or circuit-breaker, shall be
arranged and labelled so that the circuit protected may
be easily recognised.
Identification of isolators 461-01-05
537-02-09
All isolating devices shall be clearly and durably marked
to indicate the circuit or circuits which they isolate.
Isolation requiring more than one device 514-11-01
A durable warning notice must be permanently fixed in
a clearly visible position to identify the appropriate
isolating devices, where equipment or an enclosure
contains live parts which cannot be isolated by a single
device.
Periodic inspection and testing 514-12-01
A notice of durable material indelibly marked with the
words as follows, and no smaller than the example
shown in BS 7671,
IMPORTANT
This installation should be periodically inspected and
tested and a report on its condition obtained, as
prescribed in BS 7671 Requirements for Electrical
Installations published by the Institution of Electrical
Engineers.
Date of last inspection
Recommended date of next inspection ...
shall be fixed in a prominent position at the origin of
every installation. The electrician carrying out the initial(x)
The
verification must complete the notice, and it must be
updated after each periodic inspection.
Diagrams 514.09
A diagram, chart or schedule shall be provided showing:
(a) the number of points, size and type of cables for
each circuit
(b) the method of providing protection against
indirect contact
(©) any circuit vulnerable to an insulation test.
schedules of test results (Form F4) of Appendix 7 meets the
above requirement for a schedule.
(xi)
(xii)
Residual current devices 514-12-02
Where an installation incorporates an RCD a notice
with the words as follows, and no smaller than the
example shown in BS 7671,
This installation, or part of it, is protected by a device
which automatically switches off the supply if an earth
fault develops. Test quarterly by pressing the button
marked 'T' or ‘Test’. The device should switch off the
supply and should then be switched on to restore the
supply. if the device does not switch off the supply
when the button is pressed, seek expert advice.
shall be fixed in a prominent position at or near the origin
of the installation.
Warning notice - non-standard colours 514-14-01
if alterations or additions are made to an installation so that
some of the wiring complies with the harmonized
colours of Table 11A and there is also wiring in the old
colours, a warning notice shall be affixed at or near the
appropriate distribution board with the following
wording:
CAUTION
This installation has wiring colours to two versions of BS 7671.
Great care should be taken before undertaking extension,
alteration or repair that all conductors are correctly identified.
39
Sec6SECTION 7. FINAL CIRCUITS
7.1 Final Circuits 413-02-08
413-02-12
Table 7.1 has been designed to enable a radial or ring final 525-01-02
circuit to be installed without calculation where the supply is 543-01-03
at 230 V single-phase or 400 V three-phase. For other voltages, App 4
the maximum circuit length given in the table must be Table 4D2A
corrected by the application of the formula Table 4D2B
Lix Uo
Lp= asa
7 230
where:
Lp is the permitted length for voltage Uo,
Lt is the tabulated length for 230 V
Uo is the supply voltage.
The conditions assumed are that:
(i) the installation is supplied
(a) bya TN-C-S system with a maximum external earth
fault loop impedance, Ze, of 0.35 ohm, or
(b) bya TN-S system with a maximum Ze of 0.8 ohm, or
() a TT system with RCDs installed as described in
Section 3.6.
(ii) the final circuit is connected to a distribution board or
consumer unit at the origin of the installation
(iii) the method of installation complies with Reference App 4
Methods 1, 3 or 6 of Appendix 4 of BS 7671:
(a) Reference Method 1 (M1)
Sheathed cables, armoured or unarmoured
clipped direct or embedded in plaster
(b) Reference Method 3 (M3)
Cables run in conduit or trunking
Single-core or insulated and sheathed
(c) Reference Method 6 (M6)
Multicore thermoplastic (pvc) insulated and sheathed — Table 4D54
flat twin cable with protective conductor in conduit in
an insulating wall and also direct in a thermally(iv)
w)
(vi)
7.2
7.21
(i)
i)
(ii)
insulating wall, or single-core thermoplastic (pvc)
insulated cables enclosed in conduit in a thermally
insulating wall (Method 15).
the ambient temperature throughout the length of the Table 4¢1
circuit does not exceed 30 °C
the characteristics of protective devices are in App 3
accordance with Appendix 3 of BS 7671, with a fault
current tripping time for circuit-breakers of 0.1 s or less
the cable conductors are of copper.
Using the Tabulated Final Circuits
Grouping of Cables
In domestic premises, except for heating cables, the Table 4B1
conventional circuit design permits any number of
single-layer circuits when the spacing between
adjacent surfaces of the cables exceeds one cable
diameter, and, for other than semi-enclosed fuses,
(BS 3036) up to 5 touching, single-layer, circuits, when
clipped to a non-metallic surface (Installation Method 1)
up to four, 5 Aor 6 A circuits of enclosed or bunched Table 481
cables (Methods 3 and 6) are allowed for circuits
protected by semi-enclosed fuses to BS 3036 and up to
6 circuits when protected by BS 88 or BS 1361 fuses or
by circuit-breakers to BS 3871-1 or BS EN 60898 or
RCBOs to BS EN 61009
for other groupings and/or high ambient temperatures
and/or enclosure in thermal insulation cable sizes will
need to be increased per Appendix 6 of this Guide.
41
Sec?£225
TABLE 7.1 Conventional Circuits
Device | Cablesize | Protective Cable Maximum length in metres
rating | mm? device type Installation
a Phase/cpe | (note v) method Ze <0.8 ohm Ze $0.35 ohm
(note i) TNS TN-C-S
Ithermo- | thermo- 04s 5s 04s 5s
plastic(pvd| setting | disconnection] disconnection] disconnection] disconnection
cable cable
Ring
Circuits
30 251.5 BS 1361 M6 M6 90(ii) Nt 90 Ni
BS 3036 M1 M3 uv) Nt 91 Ni
ch Type 2 M6 M6 5a(ii) Nt 88 Ni
cb/RCBO Type 1 &B M6 M6 88 Nt 88 Nt
cb/RCBO Type 3 & C M6 M6 N2 Nt Tei) Ni
32 251.5 BS 88 M6 M6 66(vi) Nt 6 Nt
cb/RCBO Type 1 &B M6 M6 a4 NI 84 Nt
cb Type M6 M6 46(ii) Nt 84 Nt
cb/RCBO Type 3 & C M6 M6 N2 NI 68tii) Nt
Radial
Gircuits
5 1.0/1.0 BS 1361, BS 3036 M6 M6 46 46 46 46
bRCBO Type 1, 2,3,B&C | M6 Me 46 46 6 46
5 1.5/1.0 BS 1361, BS 3036 M6 M6 71 71 7 7m
cb/RCBO Type 1, 2,3,B&C | M6 M6 n n nm n
6 1.0/1.0 BS 88 M6 Me 38 38 38 38
Cb/RCBO Type 1, 2,3,B&C | M6 M6 38 38 38 38
cb/RCBO Type D M6 M6 27(ii) 27) 3a(il) 3a(ii)£295
TABLE 7.1 continued Conventional Circuits
Cable size | Protective Cable Maximum length in metres
rating | mm? device type Installation
7 Phase/cpe | (note v) method Ze<0.8ohm Ze $0.35 ohm
(note i) TNS TN-CS
Ithermo- | thermo- 04s 5s 04s 5s
plastic (pve)| setting | disconnection] disconnection] disconnection] disconnection
cable cable
Radial
Circuits
6 1.5/1.0 BS 88 Ms Ms 59 59 59 59
cb/RCBO Type 1, 2, 3,B&C | M6 M6 59 59 59 59
cb/RCBO Type D M6 Ms fi 45tii)
10 1.0/1.0 BS 88 M6 M6 a
cb/RCBO Type 1, 2, 3,B &C | M6 Ms 21
cb/RCBO Type D M6 M6 200i)
10 1.5/1.0 BS 88 Ms M6 33
cb/RCBO Type 1, 2, 3,B&C | M6 M6 33
cb/RCBO Type D M6 M6 23(ii)
15 25/15 BS 3036 M3 M6 35
cb/RCBO Type 1, 2 &B M6 M6 35
cb/RCBO Type 3 & C M6 M6 35
5 4.015 Bs 3036 ms Ms 61
BS 1361 cb/RCBO Type 1, 2 & B 61
cb/RCBO Type 3 & C 61(ii)
16 2.5/1.5 BS 88 33
BS 1361 cb/RCBO Type 1, 2 & 33
cb/RCBO Type 3. & C 33
cb/RCBO Type D 171)nal Circuits
Device | Cablesize | Protective Cable Maximum length in metres
rating | mm? device type Installation
a Phase/cpe | (note v) method Ze< 0.8 ohm Ze 0.35 ohm
(note i) TNS TN-CS
thermo- | thermo- 04s 5s 04s 5s
plastic (pvo)] setting —_| disconnection| disconnection| disconnection] disconnection
cable cable
Radial
Greuits
16 40.5 BS 88 M6 M6 56 56 56 56
cb/RCBO Type 1, 2 &B M6 M6 56 56 56 56
cb/RCBO Type 3 & C M6 M6 34(ii) 34Gii) 56(ii) 46(i1)
cb/RCBO Type D M6 M6 N2 N2 20(ii) 20)
20 251.5 BS 88, BS 1361 M3 M6 27 27 27 27
BS 3036 M3 M3 NB NB NB NB
cb/RCBO Type 1, 2&B M3 M6 7 27 27 27
cb/RCBO Type 3 & C M3 M6 174i) 174i) 27 27
cb/RCBO Type D M6 M6 N2 2 to(il) 10(ii)
20 4.01.5 BS 3036 m3 M6 43 43 43 43
BS 88, BS 1361 M6 M6 43 43 43 43
cb/RCBO Type 1& B M6 M6 43 43 43 43
ch Type 2 M6 M6 4B 4B 43 43
cbIRCBO Type 3 & C M6 M6 19 19 434i) 42{ii)
cb/RCBO Type D M6 M6 N2 N2 12 12
25 4025 BS 88 M6 M6 33 33 33
cb/RCBO Type 1, 2&B M6 M6 33 33 33
cb/RCBO Type 3 & C M6 M6 110i) 11) 33
cb/RCBO Type D M6 Me N2 N2 sui)£25
sv
TABLE 7.1 continued Conventional Circuits
Device | Cable size | Protective Cable Maximum length in metres
rating | mm’ device type Installation
A Phase/cpe | (note v) method Ze $0.8 ohm Ze < 0.35 ohm
(note i) ‘TN-S TN-C-S
thermo- | thermo- 0.45 5s 0.45 55
plastic (pvc)| setting | disconnection] disconnection] disconnection} disconnection
cable cable
Radial
Circuits
25 401.5 BS 88 M6 Me 33 33 33
cb/RCBO Type 1 &B M6 M6 33 33 33
cb Type 2 M6 M6 2a(ii) 33 33
cb/RCBO Type 3 & C M6 Me ati’) 30(ii) 30(ii)
cb/RCBO Type D M6 M6 N2 N2 N2
30 6.02.5 BS 3036 M1 M6 27(ii) 45 45 45
BS 1361 M6 M6 31(ii) 42 42 42
cb/RCBO Type 1 &B M6 M6 42 42 42 42
cb Type 2 M6 M6 2x) 27K) 42 “2
cb/RCBO Type 3 & C M6 M6 N2 N2 35(ii) 35(ii)
30 10.0/4.0 | BS 3036 M6 Me ati) 74 14 74
BS 1361 M6 M6 51(ii) 74 74 74
cb/RCBO Type 1 &B M6 M6 74 74 74 74
cb Type 2 M6 M6 alii) 4a(ii) 74 74
cb/RCBO Type 3 & C M6 Me N2 N2 saci) 5a(ii)
32 6.025 BS 88 M6 Me 23(ii) 39 39 39
cb/RCBO Type 1 &B M6 M6 39 39 39 39
cb Type 2 M6 M6 214i) 21) 39 39
cb/RCBO Type 3 & C M6 M6 N2 N2 31(ii) 31Gii)
cb/RCBO Type D M6 Me N2 N2 2Gii) ati)£20s
TABLE 7.1 continued Conventional Circuits
Cable size | Protective Cable Maximum length in metres
mm? device type installation
Phase/cpc | (note v) method Ze<0.8 ohm Ze< 0.35 ohm
(note) TN-S TN-CS
thermo- | thermo- 0.45 5s 045 5s
plastic (pvc)| setting | disconnection] disconnection] disconnection] disconnection
cable cable
Radial
Circuits
32 10.0/4.0 | BS 88 M6 M6 37(ii) 69 69 69
cb/RCBO Type 1 &B M6 M6 69 69 69 69
cb Type 2 M6 M6 35(il) 35(ii) 69 69
cb/RCBO Type 3 &C M6 M6 N2 N2 51(ii) 51Gii)
40 10.0/4.0 | BS8B M6 M6 7Gi) 53 53 53
cb Type 1 M6 M6 53 53 53 53
cb/RCBO Type B M6 M6 51(ii) 51(ii) 53 53
cb Type 2 M6 M6 Ei) 7Gi) 53 53
cbIRCBO Type 3 &C M6 M6 N2 N2 232(ii) 32(ii)
40 16.0/6.0 | BS 88 M6 M6 11(ii) 88 88 88
cb Type 1 M6 M6 88 88 88 88
cb/RCBO Type B M6 M6 7a(ii) 78(ii) 88 88
ch Type 2 M6 M6 11) 114i) 88 88
cb/RCBO Type 3 & C M6 M6 N2 2 49(ii) 49(ii)
45 10/4.0 BS 1361 M3 M6 N2 104i) 32tii) 49
BS 3036 M1 M3 N2 49 34(ii) 49
cb/RCBO Type 1 &B M3 M6 49 49 49 49
cb/RCBO Type B MB M6 35(i) 35(i) 49 49
cb Type 2 M3 M6 N2 N2 49 49
cbIRCBO Type 3 & C M3 M6 N2 N2 23(i) 23(i)Notes to Table 7.1
(i) _ Installation reference method
M6 indicates methods of cable installation M1, M3 and M6
may be used
M3 indicates methods of cable installation M1 and M3 may
be used
M1 indicates method of cable installation M1 only may be
used
All the circuits are limited by voltage drop other than those marked
as below:
(ii) Length is limited by earth fault loop impedance
(iii) Alternative method of Regulation 413-02-12 applied, 413-02-12
R2 +4 to be less than 0.30 ohm
(iv) Alternative method of Regulation 413-02-12 applied, 413-02-12
R2 +4 to be less than 0.36 ohm
(vy) Application of RCBOs, see 3.6.3
(vi) Alternative method of Regulation 413-02-12 applied, 413-02-12
R2 +4 to be less than 0.28 ohm
N1 NOT PERMISSIBLE as 0.4 s disconnection required for
socket-outlet circuits
N2 NOT PERMISSIBLE as earth fault loop impedance too high
N3 NOT PERMISSIBLE cable overloaded
If the alternative method ((iii) or (iv)) is used, R2 must be recorded on
the installation schedule.
Reference to BS 88 fuses is to BS 88-2.1 or BS 88-6
BS 88 fuses are not available in Consumer Units.
47
Sec77.2.2. Thermosetting cables (e.g. to BS 5467 or BS 7211) Table 4A2
Cable sizes must not be reduced when cables with
thermosetting insulation are used, as the cable operating
temperature may exceed the maximum tolerated by the
accessory to which it is connected.
7.2.3 Checklist
Before installing a conventional final circuit the following
questions must be answered:
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)
(x)
what is the load current and can the distribution board
and supply arrangements accommodate it? (See
Appendix 1 for guidance on assessing load currents)
which kind of protective device is to be used?
what cable type and installation method are to be used?
what rating of the protective device is equal to or next
higher than the load current of the circuit?
which type of earthing arrangement is employed?
is the maximum required disconnection time 0.4 s or 5 s?
Maximum 0.4 s disconnection time is required for circuits 413-02-09
feeding socket-outlets and circuits feeding fixed 471-08-03
equipment outside the equipotential zone.
what are the isolation and switching requirements?
(See Section 5)
what labels are required? (See Section 6)
is the earth loop impedance value below the values
given in 7.1(i) or 7.2.4(ii)?
is an RCD or RCBO required? All socket-outlets on a TT 471-08-06
system must be protected by an RCD or RCBO.
Socket-outlets in all systems, that may reasonably be 471-16-01
expected to supply equipment outdoors need to be
protected by an RCD or RCBO with a rated residual
operating current of 30 mA (all RCDs or RCBOs to comply
with BS 4293, BS 7288, BS EN 61008 or BS EN 61009).
Certain equipment in bathrooms requires RCD protection. 601-09-02
601-09-037.2.4 TT Systems
For TT systems the figures for TN-C-S systems, with 5 s disconnection
time, may be used provided that:
10)
(ii)
iii)
the circuit is controlled by an RCD to BS 4293,
BS EN 61008 or BS EN 61009 with a rated residual
operating current not exceeding 200 mA, and
the total earth fault loop impedance is verified as being
less than 200 ohms, and
a device giving both overload and short-circuit
protection is installed in the circuit. This may be an
RCBO.
7.2.5 Choice of Protective Device
The selection of protective device depends upon:
(i)
(ii)
(ii)
(iv)
prospective fault current
circuit load characteristics
cable current-carrying capacity
disconnection time limit.
Whilst these factors have generally been allowed for in the
conventional final circuits in Table 7.1, the following additional
guidance is given:
(i)
prospective fault current
If a protective device is to operate safely its rated short- 434-03-01
circuit capacity must exceed the prospective fault
current at the point it is installed.
At the origin of the installation the distributor needs to 313-01-01
be consulted as to the prospective fault current. Except
for London and some other major city centres, the
maximum fault current for 230 V single-phase supplies
up to 100 A will not exceed 16 kA.
Consumer units including protective devices complying
as a whole assembly with BS 5486-13 or BS EN 60439-3
are suitable for locations with fault currents up to 16 kA.
when supplied through a type II fuse to BS 1361 : 1971
(1992) rated at no more than 100 A.
49
Sec750
Sec7
TABLE 7.2A
Rated Short-Circuit Capacities
Device type Device Rated
designation | short-circuit
capacity kA
Semi-enclosed fuse to BS 3036 sia 1
with category of duty S2A, 2
saa, 4
Cartridge fuse to BS 1361 type! 16.5
type Il 33.0
General purpose fuse to BS 88-2.1 50 at 415V
General purpose fuse to BS 88-6 16.5 at 240 V
80 at 415V
Circuit-breakers to BS 3871 M1 1
(replaced by BS EN 60898) M15 15
M3 3
M45, 45
M6 6
M9 9
Circuit-breakers to BS EN 60898* and In kes
RCBOs to BS EN 61009 (15)
* Two rated short-circuit rating are defined in BS EN 60898 and BS EN 61009
@ en the rated short-circuit capacity (marked on the device).
(b) ——cs_the service short-circuit capacity.
The difference between the two is the condition of the circuit -breaker after manufacturer's testing.
len is the maximum fault current the breaker can interrupt safely, although the breaker may no
longer be usable.
Ics is the maximum fault current the breaker can interrupt safely without loss of performance.
The Icn value is normally marked on the device ina rectangle e. and for the majority of
applications the prospective fault current at the terminals of the circut-breaker should not
exceed this value.
For domestic installations the prospective fault currents unlikely to exceed 6 kA up to which
value the lon and Ics values are the same.
‘The short-circuit capacity of devices to BS EN 60947-2 is as specified by the manufacturer.(i) circuit load characteristics
(a) _ semi-enclosed fuses - fuses should preferably be of the 533-01-04
cartridge type. Semi-enclosed fuses are still commonly
used in domestic and similar premises only
(b) cartridge fuses to BS 1361 - these are for use in
domestic and similar premises
© cartridge fuses to BS 88 - three types are specified:
gG_ fuse links with a full-range breaking capacity for
general application
gM __ fuse links with a full-range breaking capacity for
the protection of motor circuits
aM fuse links with partial range breaking capacity for
the protection of motor circuits.
(d) __circuit-breakers to BS 3871-1 or BS EN 60898 and RCBOs
to BS EN 61009 - guidance on the selection is given in
Table 7.2B below.
TABLE 7.2B
Instantaneous Application
trip current
2.7 t0 4 In domestic and commercial installations
3to5In having little or no switching surge
4.0 to7.0 In general use in commercial/industrial
5to 10 I, installations where the use of fluorescent
7 to 10 In lighting, small motors etc can produce
switching surges that would operate a Type
1 or B circuit-breaker. Type C or 3 may be
necessary in highly inductive circuits such as
banks of fluorescent lighting
10 to 50 In suitable for transformers X-ray machines,
10 to 20 In, industrial welding equipment etc where
high inrush currents may occur
Where In is the nominal rating of the device.
51
Sec752
Sec7
(ii) cable current-carrying capacities
For guidance on the co-ordination of device and cable App 3
ratings see Appendix 6 App 4
(iv) disconnection times 413-02-09
413-02-13
The protective device must operate within 0.4 or 5 seconds
as appropriate for the circuit. Appendix 2 provides
maximum permissible measured earth fault loop
impedances for fuses, circuit-breakers and RCBOs.
7.3 Installation Considerations
7.3.1 Floors and ceilings
When a cable is installed under a floor or above a ceiling it shall be 522-06-05
run in such a position that it is not liable to damage by contact with
the floor or ceiling or their fixings. Unarmoured cables passing
‘through a joist shall be at least 50 mm from the top or bottom as
appropriate or enclosed in earthed steel conduit. Alternatively, the
cables can be provided with mechanical protection sufficient to
prevent penetration of the cable by nails, screws and the like. (Note,
‘the requirement to prevent penetration is difficult to meet.)
Fig 7.3.1: Cables through joists
cable in earthed insulated
steel conduit and
sheathed
¥ cable
greater than
50 mm
Notes:
Maximum diameter of hole should be 0.25 x joist depth.
Holes on centre line in a zone between 0.25 and 0.4 x span.
Maximum depth of notch should be 0.125 x joist depth.
Notches on top in a zone between 0.1 and 0.25 x span.
pe wn sn
Holes in the same joist should be at least 3 diameters apart.73.2 Walls
Where a cable is concealed in a wall or partition at a depth of less 522-06-06
than 50 mm from any surface it must be enclosed in earthed metal
conduit (trunking or ducting) or installed either horizontally within
150 mm of the top of the wall or partition or vertically within 150
mm of the angle formed by two walls, or run horizontally or
vertically to an accessory or consumer unit (see Fig 7.3.2).
Fig 7.3.2: Permitted cable routes
no protection
required
150mm wall
<4— protection required
unless depth greater
than 50 mm
Note:
A Zone formed on one side of a partition wall of 100 mm or less thickness 5 22-06-06
extends to the reverse side only if the location of the accessory can be
determined from the reverse side.
7.3.3 Telecommunication Circuits 528-01-02
528-01-04
An adequate separation between telecommunication wiring
(Band |) and electric power and lighting (Band II) circuits must
be maintained. This is to prevent mains voltage appearing in
telecommunication circuits with consequent danger to personnel.
BS 6701: 1994 recommends that the minimum separation
distances given in Tables 7.3A and 7.3B should be maintained:
53
Sec754
Sec7
TABLE 7.3A External Cables
Minimum separation distances between external low voltage
electricity supply cables operating in excess of 50 V a.c. or 120 V d.
to earth, but not exceeding 600 V a.c. or 900 V d.c. to earth (Band Il),
and Telecommunications cables (Band 1).
Voltage to earth Normal
separation
distances
Exceeding 50 V a.c. or
120 V d.c., but not 50mm
Exceptions to normal separation
distances, plus conditions to
exception
Below this figure a non-conducting
divider should be inserted between
exceeding 600 V a.c.
or 900 V d.c.
the cables,
TABLE 7.3B Internal Cables
Minimum separation distances between internal low voltage
electricity supply cables operating in excess of 50 V a.c. or 120 V dic.
to earth, but not exceeding 600 V a.c. or 900 V d.c. to earth (Band II)
and Telecommunications cables (Band I).
Voltage to earth Normal
separation
distances
Exceptions to normal separation
distances, plus conditions to
exception
Exceeding 50 V ac, or
120 V d.c., but not
exceeding 600 V a.c.
or 900 V dic.
50 mm separation need not be
maintained, provided that
()_ the LV cables are enclosed in
separate conduit which if metallic
is earthed in accordance with
BS 7671, OR
the LV cables are enclosed in
separate trunking which if
metallic is earthed in accordance
with BS 7671, OR
ii) the LV cable is of the mineral
insulated type or is of earthed
armoured construction
1. Where the LV cables share the same tray then the normal
separation should be met.
2. Where LV and telecommunications cables are obliged to cross
additional insulation should be provided at the crossing point;
this is not necessary if either cable is armoured.7.3.4 Proximity to Other Systems 528-02
Electrical and all other services must be protected from any
harmful mutual effects foreseen as likely under conditions of
normal service. For example, cables should not be in contact 528-02-02
with or run alongside hot pipes.
The installation must comply with BS 7671, Chapter 52 and
Chapter 54, regarding separation and bonding.
A particular form of harmful effect may occur when an
electrical installation shares the space occupied by a hearing
aid induction loop.
Under these circumstances, if phase(s) and neutral or switch
feeds and switch wires are not close together, there may be
interference with the induction loop.
This can occur when a conventional two-way circuit is installed.
This effect can be reduced by connecting as shown in Fig 7.3.4.
Fig 7.3.4: Circuit for reducing interference with induction loop
neutral
a witch wire light
point
A 2 way switch
‘common
cores
q grouped
together
|
strappers
2 way switch
circuit shown switched
of
55
Sec756
Sec?
7.3.5 Height of switches, sockets etc
Accessories for general use, such as light switches and socket-
outlets, are required by the Building Regulations to be
located so that they can be used by people whose reach is
limited. A way of satisfying this requirement is to install
switches for lights and similar equipment and socket-outlets 553-01-06
at a height of between 450 mm and 1200 mm from finished
floor level. See Figure 8A in Appendix 8.
7.4 Smoke Alarms and Emergency Lighting
7.4.1. Smoke alarms in single dwellings
The Building Regulations 1991 and the Building Standards
(Scotland) Regulations 1990 require all new and refurbished
dwellings to be fitted with mains operated smoke alarms, The
requirements for single family dwellings of not more than two
storeys are that self-contained smoke alarms should be
installed as follows:
1) at least one on each floor
2) within 7 m of kitchens and living rooms or other areas
where fires may start e.g. integral garages
3) within 3 m of all bedroom doors.
The smoke alarm must be installed in accordance with the
manufacturer's instructions, generally on ceilings and at least
300 mm from any wall or ceiling luminaire.
The alarms are required to:-
- be interconnected so that detection of smoke by one
unit operates the alarm in all units
- be permanently wired to a separate way in the
distribution board (consumer unit), or supplied from a
local, regularly used lighting circuit.
- have battery backup
Except for TT supplies, the circuit supplying a smoke alarm
should not be protected by an RCD. For TT supplies the smoke
alarm must be supplied from the fixed equipment section, that
is not through a 30 mA RCD, see Figure 3a.The cable for the power supply to each self-contained unit and
for the interconnections need have no fire retardant
properties, and needs no special segregation. Otherwise, fire 528-01-04
alarm system cables generally are required to be segregated as
per BS 5839-1 and BS 5839-6, see Table 7.4.
TABLE 7.4 Segregation requirements of fire alarm and emergency
lighting standards
Fire alarms Emergency lighting
BS 5839 BS 5266,
a _ installation in conduit, ducting, trunking or achannel_ a _physical segregation by a
reserved for fire alarms, or minimum distance of 300 mm,
or
b amechanically strong, rigid and continuous partition
of non-combustible material, or use of mineral cables, or
¢ mounting at a distance of at least 300 mm from ¢ cables to BS 6387 Cat B
conductors of other systems, or
d__ wiring in cables complying with BS 7629, or
wiring in mineral insulated copper sheathed cable
with an insulating sheath or barrier. The exposed-to- Table 1A
touch rating of the IEE Wiring Regulations should not
he exceeded.
7.4.2 Emergency lighting
The wiring to self-contained emergency lighting luminaires is
not considered part of the emergency lighting installation and
needs no special segregation. Otherwise, emergency lighting 528-01-04
and fire alarm circuits must be separated from other cables
and from each other, in compliance with BS 5266,
see Table 7.4.
57
Sec7SECTION 8. SPECIAL LOCATIONS GIVING RISE TO INCREASED
58
Secs
RISK OF ELECTRIC SHOCK
8.1 Locations Containing a Bath or Shower
8.1.1 Because of the presence of water these locations are
onerous for equipment and there is an increased danger of
electric shock because of immersion of the body in water.
The additional requirements can be summarised as follows:
(i) No socket-outlets are allowed other than SELV and
shaver supply units - see Table 8.1.
(ii) Supplementary bonding of the terminals of the
protective conductors of circuits to Class | and Class II
equipment in the zones (see Figure 4d) to exposed-
conductive-parts in the zones is required, including:
- metal pipes both water and central heating
- metal baths and shower basins
- accessible metal structural parts of the building.
The supplementary bonding must be carried out in or in
close proximity to the zones. See Figures 4d and 4e.
(iii) Protection against ingress of moisture is specified for
equipment installed in the zones — see figure 4d and
Table 8.1. The requirements apply to appliances,
switchgear and wiring accessories.
(iv) There are restrictions as to where appliances,
switchgear and wiring accessories may be installed - see 601-09
Table 8.1.
8.1.2 Underfloor heating installations in these areas should 601-09-04
have an overall earthed metallic grid or the heating cable
should have an earthed metallic sheath, which must be
supplementary bonded.TABLE 8.1
Requirements for equipment (current using and accessories) in locations containing a bath or shower
Zone Requirements for equipment in the zones
note2 | Minimum Current Using (Appliances) Switchgear and Accessories
degree of
protection
0 1PX7__| Only SELV fixed equipment that cannot be located elsewhere, |None allowed.
7 1PX4___|SELV equipment allowed. Only 12 Va.c. and 30 V dc. switches of SELV circuits
Water heaters, showers, shower pumps, allowed. allowed, the source being outside zones 0, 1 and 2.
Other fixed equipment that cannot reasonably be located
elsewhere allowed if protected by a 30 mA RCD.
2 1PX4__|SELV equipment allowed. ISELV switches and sockets allowed, the source being
Water heaters, showers, shower pumps, luminaires, fans, | OUtside zones 0, 1 and 2, and shaver supply units to
heating appliances, units for whirlpool baths allowed. bay om ia 2 i 1 allowed only if fixed where
m ;
Other fixed equipment that cannot reasonably be located Fee eee
elsewhere allowed.
3 No |SELV equipment allowed. Accessories allowed except for socket-outlets. There is
requirement. | appliances allowed and, unless fixed, must be protected _|t© be no provision for connecting portable equipment.
by a 30 mA ROD. SELV sockets and shaver supply units to BS EN 60742
Chap 2 Sect 1 allowed.
Outside|__No_ [Appliances allowed ‘Accessories allowed except for socket-outlets.
Zones | requirement. SELV sockets and shaver supply units to BS EN 60742
Chap 2 Sect 1 allowed.
6S
820s
Note 1: Where a shower cubicle is installed in a room other than a bathroom or shower room, outside zones 0, 1, 2 or 3 a socket-
outlet, other than a SELV socket-outlet or shaver supply unit, shall be protected by a residual current device with rated
residual operating current (Ign) not exceeding 30 mA in accordance with Regulation 412-06.
Note 2: See Figures 4d and 4e for zones.
601-08-01
601-09-01
601-08-01
601-09-01
601-08-01
601-09-03
601-08-01
601-09-03
601-08-01
6601-08-02
412-0660
Sec8
8.2 Shower Cubicles in a Room used for Other Purposes —_601-08-02
Where a shower cubicle is installed in a room other than a
bathroom or shower room the requirements for bathrooms
and shower rooms are generally to be complied with, except
that socket-outlets are allowed outside zones 0, 1, 2 and 3
provided they are protected by a 30 mA RCD, and no
supplementary bonding is required in zone 3. 601-04-02
8.3 Temporary and Garden Buildings, Domestic Garages, 300-01
Buildings of Lightweight Construction etc
The use of a temporary building does not permit a lower
standard of electrical installation. The standards of installation
and maintenance need to be higher to cope with the more
onerous conditions. Particular attention must be paid to:
i) suitability of the equipment for the environment
(ii) earthing and bonding
(iii) connection to the supply
(iv) _ use of accessories of the appropriate Degree of
Protection (IP code) to suit the particular external
influences.
84 — Earthing requirements of Equipment having High 607
Protective Conductor Current
Equipment
Equipment having a protective conductor current exceeding 607-02-02
3.5 mA shall be either permanently connected to the fixed
wiring or connected by means of an industrial plug and socket
to BS EN 60309-2.
Equipment having a protective conductor current exceeding 6907-02-03
10 mA shall be connected preferably by a permanent connection,
or an industrial plug and socket to BS EN 60309-2 with a protective
conductor csa of at least 2.5 mm? for plugs up to 16 A and at
least 4 mm? for plugs rated above to 16 A.
Circuits
The wiring of every final circuit and distribution circuit having 607-02-04
a protective conductor current likely to exceed 10 mA shall
have high integrity protective conductor connections
comprising either:
(i) a single protective conductor complying with Section 543
and of csa not less than 10 mm2, or(ii) a single copper protective conductor complying with
Section 543 and of csa not less than 4 mm? enclosed in
conduit, or
(iii) duplicate protective conductors, each complying with
Section 543.
Socket-outlet final circuits
For socket-outlet final circuits requiring a high integrity protective 607-03-01
conductor connection, the following arrangements are acceptable:
(i) aring circuit with a ring protective conductor (Fig 8.4a), or
(ii) a radial circuit with a single protective conductor (Fig 8.4b)
connected as a ring or an additional protective conductor
provided by conduit, trunking or ducting.
When the two protective conductors are provided the ends
must be terminated independently of each other at all
connection points e.g. distribution board and socket-outlet.
Accessories are required to have two separate earth terminals.
Fig 8.4a: Ring final circuit supplying socket-outlets
DISTRIBUTION BOARD
(total protective conductor current exceeding 10 mA)
separate
connections
0,
Socket-outlets must have two
terminals for protective conductor,
One terminal to be used for each
protective conductor, of a minimum
size of 15 mm?
Fig 8.4b: Radial circuit supplying socket-outlets
with duplicate protective conductor
DISTRIBUTION BOARD| «(total protective conductor current exceeding 10 mA)
separate
connections
Socket-outlets must have two
terminals for protective conductors.
Duplicate protective conductor. (One terminal to be used for each
Keep close to circuit conductors protective conductor, of a minimum
to reduce eme effects. Size of 15 mm?62
Sec9
SECTION 9. INSPECTION AND TESTING Part 7
9.1 Inspection and Testing
Every installation must be inspected and tested during erection 711-01-01
and on completion before being put into service.
Precautions shall be taken to avoid danger to persons and to 711-01-01
avoid damage to property and installed equipment during
inspection and testing.
If the inspection and tests are satisfactory, a signed Electrical 741
Installation Certificate together with a Schedule of Inspections
and a Schedule of Test Results (as in Appendix 7) are to be
given to the person ordering the work.
9.2 Inspection
9.2.1 Procedure and Purpose
Inspection shall precede testing and shall normally be done 712-01-01
with that part of the installation under inspection disconnected
from the supply.
The purpose of the inspection is to verify that equipment is: 712-01-02
(i) correctly selected and erected in accordance with
BS 7671 (and if appropriate its own standard)
(ii) not visibly damaged or defective so as to impair safety.
9.2.2 Inspection Checklist 712-01-03
The inspection shall include at least the checking of relevant
items from the following checklist:
i) connection of conductors
(i) identification of conductors
(iii) routing of cables in safe zones or protected against
mechanical damage
(iv) _ selection of conductors for current-carrying capacity
and voltage drop, in accordance with the design
(v) connection of single-pole devices for protection or
switching in phase conductors only(vi)
(vii)
(iii)
(ix)
correct connection of accessories and equipment
(including polarity)
presence of fire barriers, suitable seals and protection
against thermal effects
methods of protection against electric shock
(a) protection against both direct contact and indirect
contact, i-e.:
- SELV
- limitation of discharge of energy
(b) protection against direct contact (including
measurement of distances where appropriate),
Le:
- protection by insulation of live parts
- protection by barriers or enclosure
- protection by PELV
(c) _ protection against indirect contact:
+ earthed equipotential bonding and automatic
disconnection of supply
presence of earthing conductor
presence of protective conductors
presence of main equipotential bonding
conductors
presence of supplementary equipotential
bonding conductors
- _ use of Class Il equipment or equivalent
insulation
- electrical separation
prevention of mutual detrimental influence 515
Account must be taken of the proximity of other 528
electrical services of a different voltage band and of
non-electrical services and influences.
Fire alarm and emergency lighting circuits must be 528-01-04
separated from other cables and from each other, in
compliance with BS 5839 and BS 5266, see 7.4.1 and
74.2.
63
Sec9Sec
()
(xi)
(xii)
(xiii)
(xiv)
(xv)
(xvi)
Band | and Band II circuit cables may not be present in
the same enclosure or wiring system unless they are
either separated by an effective barrier or wired with
cables suited to the highest voltage present. Where
common boxes are used for Band | and Band II circuits,
the circuits must be segregated by an insulating or
earthed partition.
Mixed categories of circuits may be contained in
multicore cables, subject to specific requirements.
Definitions of voltage bands
Band | circuit:
Circuits that are nominally extra-low ie. not exceeding 50 V
ac or 120 V dc e.g. SELV, PELV, telecommunications, data
and signalling.
Band If circuit:
Circuits that are nominally low voltage, that is 51 to
1000 V ac and 120 to 1500 V dc. Telecommunication
cables that are generally ELV but have ringing voltages
exceeding 50 V are Band |.
presence of appropriate devices for isolation and
switching correctly located
presence of undervoltage protective devices (where
appropriate)
choice and setting of protective and monitoring devices
(for protection against indirect contact and/or
protection against overcurrent)
labelling of circuits, cbs, RCDs, fuses, switches and
terminals, main earthing and bonding connections
selection of equipment and protective measures
appropriate to external influences
adequacy of access to switchgear and equipment
presence of danger notices and other warning signs
(see Section 6)
528-01-02
528-01-07
528-01-02
Part 2
131-14-01
451
514
522(xvii) presence of diagrams, instructions and similar 514-09
information
(xviii) erection methods 522
(xix) requirements for special locations. 600
9.3 Testing 713
Testing must include the relevant tests from the following
checklist.
When a test shows a failure to comply, the installation must be 713-01-01
corrected. The test must then be repeated, as must any earlier
test that could have been influenced by the failure.
9.3.1 Testing Checklist
(i) continuity of protective conductors {including main and 713-02-01
supplementary equipotential bonding conductors)
(ii) continuity of ring final circuit conductors including 713-03-01
protective conductors
(iii) insulation resistance (between live conductors and 713-04
between each live conductor and earth)
(iv) __ polarity; this includes checks that single-pole control 713-09
and protective devices (e.g. switches, circuit-breakers,
fuses) are connected in the phase conductor only, that
bayonet and Edison-screw lampholders (except for E14
and E27 to BS EN 60238) have their outer contacts
connected to the neutral conductor and that wiring has
been correctly connected to socket-outlets and other
accessories
(v) earth electrode resistance 713-10
(vi) earth fault loop impedance 713-11
(vii) prospective fault current, if not determined by enquiry 713-12
of the distributor
(viii) functional testing (including RCDs and RCBOs). 713-13
65
Sec9SECTION 10. GUIDANCE NOTES ON INITIAL TESTING OF
INSTALLATIONS
10.1 Safety and equipment 71-01-01
Electrical testing involves danger. It is the tester's duty to
ensure his or her own safety, and the safety of others, in the
performance of the test procedures. When using test
instruments, this is best achieved by precautions such as:
(i) an understanding of the correct application and use of
the test instrumentation, leads, probes and accessories
to be employed
(ii) checking that the test instrumentation is made in
accordance with the appropriate safety standards such
as BS EN 61243-3 for two-pole voltage detectors and
BS EN 61010 or BS EN 61557 for instruments
(iii) checking before use that all leads, probes, accessories
(including all devices such as crocodile clips used to
attach conductors) and instruments are clean,
undamaged and functioning
(iv) observing the safety measures and procedures set out in
HSE Guidance Note GS 38 for all instruments, leads, probes
and accessories. It should be noted that some test
instrument manufacturers advise that their instruments
be used in conjunction with fused test leads and probes.
Other manufacturers advise the use of non-fused leads
and probes when the instrument has in-built electrical
protection, but it should be noted that such electrical
protection does not extend to the probes and leads.
10.2 Sequence of Tests 73-01-01
Note: The advice given does not preclude other test methods.
Tests should be carried out in the following sequence:
10.2.1 Before the supply is connected
(i) continuity of protective conductors, induding main and
supplementary bonding
(ii) continuity of ring final circuit conductors, including
protective conductors
insulation resistance
(iv) __ polarity (by continuity methods)
66
Sec 10(v) earth electrode resistance, when using an earth
electrode resistance tester (see also vii).
10.2.2 With the supply connected
(vi) re-check of polarity
(vii) earth electrode resistance, when using a loop
impedance tester
(viii) earth fault loop impedance
(ix) prospective fault current measurement, if not
determined by enquiry of the distributor
(x) functional testing.
Results obtained during various tests should be recorded in the 741-01-01
Schedule of Test Results (Appendix 7) for future reference.
10.3 Test Procedures
10.3.1 Continuity of protective and bonding conductors
(except ring final circuits, see Para 10.3.2)
Test Methods 1 and 2 are alternative ways of testing the continuity
of protective conductors.
Every protective conductor including the earthing conductor,
main and supplementary bonding conductors should be tested
to verify that the conductors are electrically sound and correctly
connected.
Test Method 1 detailed below, as well as checking the continuity
of the protective conductor, also measures (Ri + R2) which,
when added to the external impedance (Ze), enables the earth-
fault loop impedance (Zs) to be checked against the design, see
Section 10.3.6. Note: (R1 + R2) is the sum of the resistances of the
phase conductor (R1) and the circuit protective conductor (R2)
between the point of utilisation and origin of the installation.
Use an ohmmeter capable of measuring a low resistance for
these tests.
Test Method 1 can only be used to measure (Ri + R2) for an ‘all
insulated’ installation. Installations incorporating steel conduit,
steel trunking, micc and pvc/swa cables will produce parallel
paths to protective conductors. Such installations should be
inspected for soundness of construction and Test Method 1 or
2 used to prove continuity.
7413-02-01
67
Sec 10OL 285
89
Fig 10.1: Connections for testing
continuity of protective conductors Method 1
ceiling rose
atend of ——>
circuit
temporary
link
lamps
removed
switch on
test
instrument
main switch off distribution board
all fuses out or
all breakers off10.3.1(i) To test the continuity of protective conductors
Test Method 1
Bridge the phase conductor to the protective conductor at the
distribution board so as to include all the circuit. Then test
between phase and earth terminals at each point in the circuit.
The measurement at the circuit’s extremity should be recorded
and is the value of (Ri + R2) for the circuit under test (see Fig 10.1).
If the instrument does not include an “auto-null” facility, or
this is not used, the resistance of the test leads should be
measured and deducted from the resistance readings obtained.
Test Method 2
Connect one terminal of the continuity test instrument to a
long test lead and connect this to the consumer's main earthing
terminal.
Connect the other terminal of the instrument to another test
lead and use this to make contact with the protective
conductor at various points on the circuit, such as luminaires,
switches, spur outlets etc.
The resistance of the protective conductor R2 is recorded on
the Schedule of Test Results, form F4.
10.3.1(ii) To test the continuity of bonding conductors
Use Test Method 2
10.3.2 Continuity of ring final circuit conductors
A three step test is required to verify the continuity of the
phase, neutral and protective conductors and correct wiring of
every ring final circuit. The test results show if the ring has
been inter-connected to create an apparently continuous ring
circuit which is in fact broken, or wrongly wired.
Step 1:
The phase, neutral and protective conductors are identified
and the end-to-end resistance of each is measured separately
(see Fig10.2a). These resistances are r1, rn and r2 respectively. A
finite reading confirms that there is no open circuit on the ring
conductors under test. The resistance values obtained should
be the same (within 0.05 ohm) if the conductors are the same
713-02-01
713-02-01
713-03-01
69
Sec 1070
Sec 10
size. If the protective conductor has a reduced csa the
resistance +2 of the protective conductor loop will be
proportionally higher than that of the phase and neutral loops
e.g. 1.67 times for 2.5/1.5 mm? cable. If these relationships are
not achieved then either the conductors are incorrectly
identified or there is something wrong at one or more of the
accessories.
Step 2:
The phase and neutral conductors are then connected together
so that the outgoing phase conductor is connected to the
returning neutral conductor and vice-versa (see Fig 10.2b). The
resistance between phase and neutral conductors is measured
at each socket-outlet. The readings at each of the sockets
wired into the ring will be substantially the same and the value
will be approximately one quarter of the resistance of the
phase plus the neutral loop resistances, i.e. (r1 + Mm)/4. Any
sockets wired as spurs will have a higher resistance value due
to the resistance of the spur conductors.
Note: Where single-core cables are used, care should be taken to verify that the phase and
neutral conductors of opposite ends of the ring circuit are connected together. An error
in this respect will be apparent from the readings taken at the socket-outlets,
progressively increasing in value as readings are taken towards the midpoint of the
ring, then decreasing again towards the other end of the ring.
Step 3:
The above step is then repeated, this time with the phase and
cpc cross-connected (see Fig 10.2c). The resistance between
phase and earth is measured at each socket. The readings
obtained at each of the sockets wired into the ring will be
substantially the same and the value will be approximately one
quarter of the resistance of the phase plus cpc loop resistances,
ie. (ry + r2)/4. As before, a higher resistance value will be
recorded at any sockets wired as spurs. The highest value
recorded represents the maximum (Rj + R2) of the circuit and is
recorded on Form F4, The value can be used to determine the
earth loop impedance (Zs) of the circuit to verify compliance with
the loop impedance requirements of BS 7671 (see Appendix 9).
This sequence of tests also verifies the polarity of each socket,
except that if the testing has been carried out at the terminals
on the reverse of the accessories, a visual inspection is required
to confirm correct polarity connections, and dispenses with the
need for a separate polarity test.Fig 10.2: Connections for testing continuity of ring final circuit conductors
10.2a
initial check for
continuity at
ends of ring
test
instrument
10.2¢
10.2b
N LON L
connection for
taking readings of Ri + R2
at sockets
71
Sec 1072
Sec 10
10.3.3 Insulation resistance
Pre-test checks
10.3.3(i)
(a) _ pilot or indicator lamps, and capacitors are
disconnected from circuits to avoid misleading test
values being obtained
(b) if a circuit includes voltage-sensitive electronic devices
such as dimmer switches, touch switches, delay timers,
power controllers, electronic starters or controlgear for
fluorescent lamps etc either:
(1) _ the devices must be temporarily disconnected, or
(2) ameasurement should be made between live
conductors (phase and neutral) connected
together and the protective earth only
It should also be confirmed that there are no RCDs
incorporating electronic amplifiers, before the test is made.
10.3.3(ii)
Tests should be carried out using the appropriate d.c. test
voltage specified in Table 10.1.
The tests should be made at each distribution with the main
switch off, all fuses in place, switches and circuit-breakers
closed, lamps removed and other current-using equipment
disconnected. Where the removal of lamps and/or the
disconnection of current-using equipment is impracticable, the
local switches controlling such lamps and/or equipment should
be open.Where any circuits contain two-way switching the two-way
switches must be operated one at a time and further
insulation resistance tests carried out to ensure that all the
circuit wiring is tested.
TABLE 10.1 TABLE 71A
Minimum values of insulation resistance
Circuit nominal Minimum
voltage voltage insulation
Vdc. resistance
(M ohms)
SELV and PELV 0.25
Up to and including 500 V with the
exception of SELV and PELV, but
including FELV
Although an insulation resistance value of not less than 0.5
megohm complies with BS 7671, where an insulation resistance
of less than 2 megohms is recorded the possibility of a latent
defect exists. Each circuit should then be tested separately, and
its insulation resistance should be greater than 2 megohms.
Where electronic devices are disconnected for the purpose of 713-04-04
the tests on the installation wiring (and the devices have
exposed-conductive-parts required by BS 7671 to be connected
to the protective conductors) the insulation resistance between
the exposed-conductive-parts and all live parts of the device
(phase and neutral connected together) should be measured
separately and should not be less than the values stated in
Table 10.1.
10.3.3(iii) Insulation resistance between live conductors 713-04
Single-phase and three-phase
Test between all the live (phase and neutral) conductors at the
distribution board (see Fig 10.3).
73
Sec 10OL 285
Fig 10.3: Insulation resistance tests between live conductors of a circuit
switch on lamps
removed
main switch off
circuit-fuse out
or breakers off
note 1: protective conductors to switches have
been omitted for clarity
note 2: the test should initially be carried out on
the complete installation
test
instrumentResistance readings obtained should be not less than the
minimum values referred to in Table 10.1.
10.3.3(iv) Insulation resistance to Earth 713-04
Single-phase
Test between the live conductors (phase and neutral) and the
circuit protective conductors at the distribution board
(see Fig 10.4).
For circuits containing two-way switching or two-way and
intermediate switching the switches must be operated one at a
time and the circuit subjected to additional insulation resistance
tests.
Three-phase
Test to earth from all live conductors (including the neutral)
connected together. Where a low reading is obtained it is
necessary to test each conductor separately to earth, after
disconnecting all equipment.
Resistance readings obtained should be not less than the
minimum values referred to in Table 10.1.
10.3.3(v) SELV and PELV circuits Table 714
Test between SELV and PELV circuits and live parts of other
circuits at 500 V dic.
Test between SELV or PELV conductors at 250 V d.c. and between
PELV conductors and protective conductors of the PELV circuit
at 250 V d.c.
10.3.3(vi) FELV circuits 471-14-03
FELV circuits are tested as LV circuits at 500 V d.c.
75
Sec 10OL es
9L
Fig 10.4: Insulation resistance tests to earth
ceiling ceiling
foPe tl rose
\ ge
lamps
removed = a IT) i LBS d
two-way switches a switch on lamps
la removed
eee distribution board
note 1: protective conductors to switches have
been omitted for clarity
note 2: the test should initially be carried out on
the complete installation
test
instrumentFig 10.5: Polarity test on a lighting circuit
R2
i a ae a a ee eee 1
I
|
Note: |
Protective conductor 1
{| to switch has been temporary
‘| omitted for clarity link 1
i Edison screw
i lampholder switch if]
as
oo
wee aE EEL
loo)
main switch off
all fuses out or
all breakers off
distribution
board
note: the polarity of E14 and E27 Edison
screw lampholders to BS EN 60238
does not have to be verified.
test
instrument
Ob 28S
ae78
Sec 10
10.3.4 Polarity
See Figure 10.5.
The method of test prior to connecting the supply is the same
as Test Method 1 for checking the continuity of protective
conductors which should have already been carried out (see
10.3.1, 10.3.2 and Figs 10.1 and 10.2). For ring circuits a visual
check may be required (see 10.3.2 following step 3).
It is important to confirm that:
(i) overcurrent devices and single-pole controls are in the
phase conductor
(ii) except for E14 and E27 lampholders to BS EN 60238,
centre contact screw lampholders have the outer
threaded contact connected to the neutral and
(iii) socket polarities are correct.
After connection of the supply polarity must be checked using
a voltmeter or a test lamp (both with leads complying with
HSE Guidance Note GS 38).
10.3.5 Earth Electrode Resistance
If the electrode under test is being used in conjunction with an
RCD protecting an installation, the following method of test
may be applied.
A loop impedance tester is connected between the phase
conductor at the origin of the installation and the earth
electrode with the test link open, and a test performed. This
impedance reading is treated as the electrode resistance and is
then added to the resistance of the protective conductor for
the protected circuits. The test should be carried out before
energising the remainder of the installation.
The measured resistance should meet the following criteria and
those of 10.3.6 but in any case should not exceed 200 ohms:
For TT systems, the value of the earth electrode resistance Ra in
ohms multiplied by the operating current in amperes of the
protective device IAn shall not exceed 50 V e.g. if Ra = 200 Q, then
the maximum RCD operating current should not exceed 250 mA.
Remember to replace the test link.
713-09
713-09-01
7713-09-01
713-09-01
713-10
542-02-02
413-02-2010.3.6 Earth Fault Loop Impedance 713-11
The earth fault loop impedance (Z;) is required to be 413-02-10
determined for the furthest point of each circuit. It may be 413-02-11
determined 413-02-14
- by direct measurement of Zs.
- by direct measurement of Ze at the origin and adding
(R1 + R2) measured during the continuity tests (10.3.1
and 10.3.2) (Zs = Ze + (Ri + R2))
- by adding (R1 + R2) measured during the continuity
tests to the value of Ze declared by the distributor,
(see 7.1(i)). The effectiveness of the distributor's earth
must be confirmed by a test.
The external impedance (Z.) may be measured using a phase-
earth loop impedance tester.
The main switch is opened and made secure to disconnect the
installation from the source of supply. The earthing conductor
is disconnected from the main earthing terminal and the
measurement made between phase and earth of the supply.
Remember to reconnect the earthing conductor to the
earth terminal after the tests.
Direct measurement of Z, can only be made on a live
installation. Neither the connection with earth nor bonding
conductors are disconnected. The reading given by the loop
impedance tester will usually be less than Z. + (Ri + R2) because
of parallel earth return paths provided by any bonded
extraneous-conductive-parts. This must be taken into account
when comparing the results with design data.
Care should be taken to avoid any shock hazard to the testing
personnel and to other persons on site during the tests.
The values of Z; determined should be less than the value given 413-02-08
in Appendix 2 for the particular overcurrent device and cable. 543-01-03
For TN systems, when protection is afforded by an rcd, the 413-02-16
rated residual operating current in amperes times the earth
fault loop impedance in ohms should not exceed 50 V. This test
should be carried out before energising other parts of the
system.
Note: For further information on the measurement of earth fault loop
impedance, refer to Guidance Note No 3 — Inspection and Testing.
79
Sec 1080
Sec 10
10.3.7 Measurement of prospective fault current 713-12-01
lt is not recommended that installation designs are based on 434-02-01
measured values of prospective fault current, as changes to the
distribution network subsequent to the completion of the
installation may increase fault levels.
Designs should be based on the maximum fault current 313-01-01
provided by the distributor (see 7.2.5(i)).
If it is desired to measure prospective fault levels this should be
done with all main bonding in place. Measurements are made
at the distribution board between live conductors and between
phase conductors and earth.
For three-phase supplies the maximum possible fault level will
be approximately twice the single-phase to neutral value. (For
three-phase to earth faults, neutral and earth path impedances
have no influence.)
10.3.8 Functional testing 713-13
RCDs should be tested as described in Section 11. All assemblies 713-13-02
including switchgear, controls, and interlocks should be
functionally tested; that is, operated to check that they work
and are properly fixed etc.SECTION 11. OPERATION OF RESIDUAL CURRENT OPERATED DEVICES
11.7
(RCDs) AND RESIDUAL CURRENT BREAKERS WITH
OVERCURRENT PROTECTION (RCBOs)
General Test Procedure
The tests are made on the load side of the RCD, as near as
practicable to its point of installation, and between the phase
conductor of the protected circuit and the associated circuit
protective conductor. The load supplied should be disconnected
during the test.
11.2
i)
(ii)
(i)
a)
(i)
(ii)
General purpose RCDs to BS 4293
with a leakage current flowing equivalent to 50 % of
the rated tripping current, the device should not open.
with a leakage current flowing equivalent to 100 % of
the rated tripping current of the RCD, the device should
open in less than 200 ms. Where the RCD incorporates
an intentional time delay it should trip within a time
range from ‘50 % of the rated time delay plus 200 ms’ to
‘100 % of the rated time delay plus 200 ms’.
General purpose RCCBs to BS EN 61008 or RCBOs to
BS EN 61009
with a leakage current flowing equivalent to 50 % of
the rated tripping current of the RCD the device should
not open.
with a leakage current flowing equivalent to 100 % of
the rated tripping current of the RCD, the device should
open in less than 300 ms unless it is of ‘Type S’ (or
selective) which incorporates an intentional time delay.
In this case, it should trip within a time range from 130 ms
to 500 ms
RCD protected socket-outlets to BS 7288
with a leakage current flowing equivalent to 50 % of
the rated tripping current of the RCD the device should
not open
with a leakage current flowing equivalent to 100 % of
the rated tripping current of the RCD, the device should
open in less than 200 ms
713-13-01
81
sec1182
Sec11
11.5 Additional Requirement for Supplementary Protection 412-06-02
Where an RCD or RCBO with a rated residual operating
current lan not exceeding 30 mA is used to provide
supplementary protection against direct contact, with a test
current of 5lan the device should open in less than 40 ms. The
maximum test time must not be longer than 40 ms, unless the
protective conductor potential rises by less than 50 V. (The
instrument supplier will advise on compliance).
11.6 Integral Test Device 713-13-02
An integral test device is incorporated in each RCD. This device
enables the electrical and mechanical parts of the RCD to be
verified, by pressing the button marked ‘T’ or ‘Test’.
Operation of the integral test device does not provide a means
of checking:
(a) _ the continuity of the earthing conductor or the
associated circuit protective conductors, or
(b) any earth electrode or other means of earthing, or
(any other part of the associated installation earthing.
The test button will only operate the RCD if the RCD is
energised.
Confirm that the notice to test RCDs quarterly (by pressing the 514-12-02
test button) is fixed in a prominent position ((see 6.1(xi)).APPENDICES
CONTENTS
Appendix Page
1 Maximum demand and diversity 84
2. Maximum permissible measured earth
fault loop impedance 88
3 Notes on the selection of types of cable
and flexible cord for particular uses and
external influences 94
4 Notes on methods of support for cables,
conductors and wiring systems 100
5 Cable capacities of conduit and trunking 109
6 Current-carrying capacities and voltage
drop for copper conductors 115
7 Certification and reporting 127
8 — Standard circuit arrangement for household
and similar installations 150
9 Resistance of copper and aluminium
conductors 157
10 Protective conductor sizing 161
11 Identification of conductors 164
83APPENDIX 1
MAXIMUM DEMAND AND DIVERSITY
Appx 1
This Appendix gives some information on the determination of
the maximum demand for an installation and includes the
current demand to be assumed for commonly used equipment.
It also includes some notes on the application of allowances for
diversity.
The information and values given in this Appendix are intended
only for guidance because it is impossible to specify the
appropriate allowances for diversity for every type of
installation and such allowances call for special knowledge and
experience. The figures given in Table 1B, therefore, may be
increased or decreased as decided by the engineer responsible
for the design of the installation concerned. For blocks of
residential dwellings, large hotels, industrial and large
commercial premises, the allowances are to be assessed by a
competent person.
The current demand of a final circuit is determined by
summating the current demands of all points of utilisation and
equipment in the circuit and, where appropriate, making an
allowance for diversity. Typical current demands to be used for
this summation are given in Table 1A.
The current demand of a circuit supplying a number of final
circuits may be assessed by using the allowances for diversity
given in Table 1B which are applied to the total current demand
of all the equipment supplied by that circuit and not by
summating the current demands of the individual final circuits
obtained as outlined above. In Table 1B the allowances are
expressed either as percentages of the current demand or,
where followed by the letters f.l., as percentages of the rated
full load current of the current-using equipment. The current
demand for any final circuit which is a conventional circuit
arrangement complying with Appendix 8 is the rated current
of the overcurrent protective device of that circuit.
An alternative method of assessing the current demand of a
circuit supplying a number of final circuits is to summate the
diversified current demands of the individual circuits and then
apply a further allowance for diversity. In this method the
allowances given in Table 1B are not to be used, the values to
311be chosen being the responsibility of the designer of the
installation.
The use of other methods of determining maximum demand is
not precluded where specified by a suitably qualified electrical
engineer. After the design currents for all the circuits have been
determined, enabling the conductor sizes to be chosen, it is
necessary to check that the limitation on voltage drop is met.
TABLE 1A
Current demand to be assumed for points of utilisation and
current-usit jipment
Point of utilisation or current-using | Current demand to be assumed
equipment
Socket-outlets other than Rated current
2 A socket-outlets and other than
13 A socket-outlets see note 1
2A socket-outlets At least 0.54
Lighting outlet see note 2 Current equivalent to the connected
load, with a minimum of 100 W per
lampholder
Electric clock, shaver supply unit May be neglected
(complying with BS 3535), shaver
socket-outlet (complying with
BS 4573), bell transformer, and
current-using equipment of a rating
not greater than 5 VA
Household cooking appliance The first 10 A of the rated current
plus 30 % of the remainder of the
rated current plus 5 A if a
socket-outlet is incorporated in the
control unit
British Standard rated current, or
normal current
All other stationary equipment
Note 1; See Appendix 8 for the design of standard circuits using socket-
outlets to BS 1363-2 and BS 4343.
Note 2: Final circuits for discharge lighting must be arranged so as to be
capable of carrying the total steady current, viz. that of the lamp(s)
and any associated gear and also their harmonic currents. Where
more exact information is not available, the demand in volt-amperes
is taken as the rated lamp watts multiplied by not less than 1.8. This
multiplier is based upon the assumption that the circuit is corrected
toa power factor of not less than 0.85 lagging, and takes into
account control gear losses and harmonic current.
85
Appx 1Appx 1
TABLE 1B
Allowances for diversity
Purpose of Type of premises
final circuit
fed from
conductors or Individual household | Small shops, ‘Small hotels,
switchgear to installations stores, offices boarding houses,
which diversity | including individual | and business guest houses, etc
applies dwellings of a block | premises
1. Lighting 66 % of total current} 90 % of total 75 % of total
demand current demand | current demand
2. Heating and | 100 % of total 100 % f.l. of 100 % f.l. of
power (but see | current demand up _! largest appliance | largest appliance
3 to 8 below) to 10 amperes +50 %| +75 % fil. of +80 % f.l. of
of any current remaining second largest
demand in excess of | appliances appliance +60 %
10 amperes f. of remaining
appliances
3. Cooking 10 amperes +30 % f.l] 100 % f.l. of 100 % f.l. of
appliances of connected cooking largest appliance | largest appliance
appliances in excess | +80 % fl. of +80 % f.l. of
of 10amperes+5 | secondlargest | second largest
amperes if appliance +60 % | appliance +60 %
socket-outlet f.l of remaining | f.l. of remaining
incorporated in appliances appliances
control unit
4. Motors not applicable 100 % f.l. of 100 % f.l. of
(other than lift largest motor | largest motor
motors which +80 % fil. of +50 % fl. of
are subject to second largest | remaining motors
special motor +60 % f.l.
consideration of remaining
motors
5, Water-heaters| 100 % f.l. of largest | 100 % f.l. of 100 % f.. of
(instantaneous | appliance +100 % f.l.| largest appliance} largest appliance
type)* of second largest +100 % f.l. of +100 % f.l. of
appliance +25 % f.1. | second largest | second largest
‘of remaining appliance +25 % | appliance +25 %
appliances f.1. of remaining | f.l. of remaining
appliances
appliancesTABLE 1B continued Allowances for diversity
Purpose of
final circuit
fed from
conductors or
switchgear to
which diversity
applies
Individual household
installations
including individual
dwellings of a block
Type of premises
Small shops, Small hotels,
stores, offices | boarding houses,
and business guest houses, etc
premises
6. Water-heaters|
(thermostatically
controlled)
no diversity allowablet
7. Floor warming}
installations no diversity allowablet
8. Thermal
storage space no diversity allowablet
heating
installations
9. Standard 100 % of current 100 % of current demand of largest
arrangement of
final circuits in
accordance with
Appendix 8
demand of
largest circuit
+40 % of current
demand of every
other circuit
circuit +50 % of current demand of
every other circuit
10. Socket-outlets
other than those
included in 9
above and
stationary
equipment other
than those listed
above
100 % of current
demand of
largest point of
utilisation
+40 % of current
demand of every
other point of
utilisation
100 % of current} 100 % of current
demand of demand of
largest point of | largest point of
utilisation utilisation
+70 % of current] +75 % of current
demand of every | demand of every
‘other point of || other point in
utilisation main rooms
(dining rooms,
etd) +40 % of
current demand
of every other
point of
Utilisation
For the purpose of this Table an instantaneous water-heater is deemed to
be a water-heater of any loading which heats water only while the tap is
turned on and therefore uses electricity intermittently.
+ It is important to ensure that the distribution boards and consumer units
are of sufficient rating to take the total load connected to them without.
the appli
ion of any diversity.
87
Appx 1APPENDIX 2
MAXIMUM PERMISSIBLE MEASURED EARTH FAULT LOOP
IMPEDANCE
388
Appx 2
The tables in this Appendix provide maximum permissible 713-11
measured earth fault loop impedances (Zs) for compliance with 413-02-05
BS 7671 where the conventional final circuits of Table 7.1 are 413-02-10
used. The values are those that must not be exceeded in the 413-02-11
tests carried out under Para 10.3.6 at an ambient temperature 413-02-14
of 10°C to 20°C. Table 2E provides correction factors for other 543-01-03
ambient temperatures.
Where the cables to be used are to Tables 4, 7 or 8 of BS 6004 or
Tables 3, 5, 6 or 7 of BS 7211 or are other thermoplastic (pvc) or
thermosetting (Isf) cables to these British Standards, and the
cable loading is such that the maximum operating
temperature is 70 °C, then Tables 2A, 2B and 2C give the
maximum earth loop impedances for circuits with:
(a) protective conductors of copper and having from
1mm? to 16 mm? cross-sectional area,
(b) _ where the overcurrent protective device is a fuse to
BS 88 Part 2 or Part 6, BS 1361 or BS 3036.
For each type of fuse, two tables are given:
- where the circuit concerned feeds socket-outlets and the
disconnection time for compliance with Regulation
413-02-09 is 0.4s, and 13-02-09
- where the circuit concerned feeds fixed equipment only
and the disconnection time for compliance with Regulation
413-02-13 is 5s. 413-02-13
In each table the earth fault loop impedances given correspond
to the appropriate disconnection time from a comparison of
the time/current characteristic of the device concerned and the
equation given in Regulation 543-01-03. 543-01-03
The tabulated values apply only when the nominal voltage to
Earth (Up) is 230 V.
Table 2D gives the maximum measured Zs for circuits protected
by circuit-breakers to BS 3871-1 and BS EN 60898, and RCBOs
to BS EN 61009.Note: The impedances tabulated in this Appendix are lower than those in
Table 41B1, Table 41B2 and Table 41D of BS 7671 as these are measured
values at an assumed conductor temperature of 10 °C, whilst those in
BS 7671 are design figures at the conductor normal operating temperature.
TABLE 2A Semi enclosed fuses
Maximum measured earth fault loop impedance (in ohms) when
overcurrent protective device is a semi-enclosed fuse to BS 3036 (see Note)
() 0.4 second disconnection 413-02-05
Table 4181
Protective Fuse rating (amperes) Peete
conductor
(mm?)
5 15 20 30 45
1.0 8.00
15 8.00
2.5 to 16.0
1.48 NP NP
1.48 0.91 NP
1.48
5 seconds disconnection rere
Table 41D
Protective Fuse rating (amperes) 5343-01-03
conductor
(mm?)
5 15 20 30 45
1.0 14.80 4.46 NP
15 14.80 4.46 NP
25 14.80 4.46 1.20
4.0 to 16.0
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for Table 54C
insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
i insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211. The k
value is based on both the thermoplastic (pvc) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.
NP protective conductor, fuse combination NOT PERMITTED.
89
Appx2TABLE 2B BS 88 fuses
Maximum measured earth fault loop impedance (in ohms) when
‘avercurrent protective device is a fuse to BS 88
wa 0.4 second disconnection
(see Note)
413-02-05
Table 4181
Protective Fuse rating (amperes) ees
conductor
(mm?)
6 50
1.0 7 NP
15 7 NP
25 to 16.0
5 seconds disconnection 413-02-05
Table 41D
Protective Fuse rating (amperes) 9543-01-03
conductor
(mm?)
6 | 10 | 16 | 20 | 25 | 32 | 40 | so
1.0 +4.28| 6.19] 3.20] 1.75] 1.24) 0.69] NP] NP
15 11.28| 6.19) 3.49) 2.43| 1.60] 1.12] 0.67] NP
25 11.28] 6.19] 3.49] 2.43] 1.92) 152| 1.13] 0.56
40 11.28] 6.19] 3.49] 2.43] 1.92] 1:52] 1.13) 081
6.0t016.0 | 11.28] 6.19] 3.49] 243] 1.92] 1.52) 1.13] 087
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for Table 54C
pvc insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
\sf insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211. The k
value is based on both the thermoplastic (pvc) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.
NP protective conductor, fuse combination NOT PERMITTED.
Appx 2TABLE 2C
Maximum measured earth fault loop impedance (in ohms) when
overcurrent protective device is a fuse to BS 1361
() 04 second disconnection one
Protective Fuse rating (amperes)
conductor
(mm?)
5 15 20 30 45
10 8.72 0.80 NP
15 8.72 0.96 .
2.5 to 16.0
(ii) 5 seconds disconnection
Protective Fuse rating (amperes)
conductor
(mm?)
5 15 20 30 45
1.0 13.68 4.18 1.75 0.80 NP.
15 13.68 4.18 2.24 1.20 0.34
25 13.68 4.18 2.34 1.54 0.53
4.0 13.68 4.18 2.34 1.54 0.70
6.0 to 16.0 13.68 4.18 2.34 1.54 0.80
413-02-05
Table 41B1
5543-01-03
Table 41D
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for Table 54c
pvc insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
Isf insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211, The k
value is based on both the thermoplastic (pve) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.
NP protective conductor, fuse combination NOT PERMITTED.
91
Appx 2zwxddy
8
TABLE 2D Table 41B2
Maximum measured earth fault loop impedance (in ohms) when overcurrent protective device is a circuit-breaker to 413-02-05
BS 3871-1 or BS EN 60898 or a RCBO to BS EN 61009
(i) both 0.4 and 5 seconds disconnection times
Circuit- Circuit-breaker (amperes)
breaker
type
5 6 10 15 16 20 25 30 50 63
1 9.60 2.40 096 | 0.76
2 5.49 0.55 0.43
B _ 0.77 | 0.61
3aC 3.84 0.96 0.38 | 0.30
D 0.48
Note: A value of k of 115 from Table 54C of BS 7671 is used. This is suitable for pvc insulated and sheathed cables to Tables 4, 7 or 8 of BS 6004 and for
\sf insulated and sheathed cables to Tables 3, 5, 6 or 7 of BS 7211. The k value is based on both the thermoplastic (pvc) and thermosetting (Isf)
cables operating at a maximum temperature of 70 °C.TABLE 2E
Ambient temperature correction factors
Ambient Correction factors (from
temperature °C 10 °C) notes 1,2
Notes:
1 - The correction factor is given by: {1 + 0.004 (Ambient temp - 10} where
0.004 is the simplified resistance coefficient per °C at 20 °C given by BS 6360
for both copper and aluminium conductors
2 - The factors are different to those of Table 9B because Table 2E corrects
from 10 °C and Table 9B from 20 °C. The values in Tables 2A to 2D are for a 10°C
ambient.
The ambient correction factor of Table 2E is applied to the
earth fault loop impedances of Tables 2A to 2D if the ambient
temperature is not within the range 10 °C, to 20 °C. For
example, if the ambient temperature is 25 °C the measured
earth fault loop impedance of a circuit protected by a 32 A
type 1 mcb should not exceed 1.50 x 1,06 = 1.59 Q.
93
Appx2APPENDIX 3
NOTES ON THE SELECTION OF TYPES OF CABLE AND
FLEXIBLE CORD FOR PARTICULAR USES AND EXTERNAL
INFLUENCES
For compliance with the requirements of Chapter 52 for the ch52
selection and erection of wiring systems in relation to risks of
mechanical damage and corrosion, this Appendix lists in two
tables types of cable and flexible cord suitable for the uses
intended. These tables are not intended to be exhaustive and
other limitations may be imposed by the relevant Regulation
of BS 7671, in particular those concerning maximum permissible
operating temperatures.
Information is also included in this Appendix on protection
against corrosion of exposed metalwork of wiring systems.
TABLE 3A
Applications of cables for fixed wiring
Type of cable Uses Comments
Thermoplastic (pvc) | In conduits, cable ducting or| (i) intermediate support may be
‘or thermosetting | trunking required on long vertical runs
ee eae (i) 70°C maximum conductor
non-sheathed temperature for normal wiring
grades — including thermosetting
types (4)
Gii)cables run in pvc conduit shall not
operate with a conductor
temperature greater than 70 °C (4)
Flat thermoplastic | (i) general indoor use in dry] (i) additional protection may be
(pvo) or or damp locations. May necessary where exposed to
thermosetting, be embedded in plaster | _ mechanical stresses
insulated and (ii) on exterior surface walls,| (ji) protection from direct sunlight may
sheathed boundary walls and the be necessary. Black sheath colour is
like better for cables in sunlight
(iii)overhead wiring {iii)see Note (4)
between buildings (6) | (iv)unsuitable for embedding directly
(v)underground in conduits) in concrete
or pipes (v) may need to be hard drawn (HD)
(W) in building voids or ducts) copper conductors for overhead
formed in situ wiring (Note 6)
94
Appx 3