LCI Install Guide
LCI Install Guide
Installers Guide
LonTalk® Communications Interface with Space
Comfort Control for ReliaTel™ controls
October 2005
Contents
General Information .......................................................................................... 3
LCI-R Shipment and Inspection ........................................................................ 3
Storage ............................................................................................................. 3
Mounting and Wiring ......................................................................................... 3
LonTalk Communication Link ............................................................................ 4
Status/Power/Wink/Test LED ............................................................................ 7
Service Switch .................................................................................................. 8
Modbus STATUS ............................................................................................... 8
Network Interface .............................................................................................. 8
Configuration Properties ................................................................................... 9
Send Heartbeat ................................................................................................. 9
Occupancy Temperature Setpoint ..................................................................... 9
Minimum Send Time ......................................................................................... 9
Receive Heartbeat ............................................................................................ 9
Location Label .................................................................................................. 9
Local Bypass Time ............................................................................................ 9
Outdoor Air Damper Minimum Position ........................................................... 10
Space Humidity Set Point ................................................................................ 10
Space CO2 Limit .............................................................................................. 10
Node Object ..................................................................................................... 10
Self-Documentation ......................................................................................... 10
Network Variable Descriptions: ........................................................................ 10
NV#1 Space Temperature Input ...................................................................... 11
NV#2 Temperature Setpoint Input (absolute) .................................................. 11
NV#3 Setpoint Offset Input ............................................................................. 11
NV#5 Occupancy Scheduler Input .................................................................. 11
NV#6 Occupancy Override Input .................................................................... 12
NV#7 Occupancy Sensor Input ....................................................................... 12
NV# 8 Application Mode Input ........................................................................ 12
NV#9 Heat/Cool Mode Input ........................................................................... 12
NV#11 Compressor Enable Input ................................................................... 13
NV#12 Auxiliary Heat Enable Input ................................................................ 14
NV#13 Economizer Enable Input .................................................................... 14
NV#17 Emergency Override Input .................................................................. 14
NV#22 Space CO2 Input ................................................................................ 15
NV#59 Outdoor Air Damper Minimum Position Input ...................................... 15
NV#21 Outdoor Relative Humidity Input .......................................................... 15
NV#19 Outdoor Temperature Input ................................................................. 15
NV#20 Space Relative Humidity Input ............................................................. 15
NV#26 Effective Space Temperature Output .................................................. 15
NV#28 Effective Setpoint Output .................................................................... 16
NV#27 Unit Status Output ............................................................................... 17
NV#29 Effective Occupancy Output ................................................................ 19
NV#30 Effective Heat/Cool Output ................................................................. 19
NV#31 Local Setpoint Output ......................................................................... 20
NV#33 Fan Speed Output ............................................................................... 21
NV#34 Discharge Air Temperature Output ..................................................... 21
NV#36 Absolute Power Consumption Output .................................................. 21
NV#37 Terminal Load Output ........................................................................... 22
NV#42 Outdoor Air Damper Output ................................................................. 22
NV#43 Space Humidity Output ....................................................................... 22
NV#44 Outdoor Air Humidity Output ............................................................... 22
NV#45 Outdoor Air Temperature Output ......................................................... 22
NV#46 Space CO2 Output .............................................................................. 23
Mixed Air Temperature Output ......................................................................... 23
Return Air Temperature Output ........................................................................ 23
NV#64 Mixed Air Temperature Output ............................................................. 23
2 ACC-SVN19B-EN
Installation
NOTICE: Storage
Warnings and Cautions appear at When the LCI-R board must be stored
appropriate sections throughout this for a period of time prior to being
installed, it must be protected from the
manual. Read these carefully. elements. The temperature of the
storage location should be between -
40C and 65.6C (-40 F and 150 F) and
WARNING– Indicates a the relative humidity should be 10 to 90
potentially hazardous situation percent, non-condensing.
which, if not avoided, could result in
death or serious injury. Mounting and Wiring
The LCI-R board mounts directly in the
Unit Control Box. The following proce-
CAUTION – Indicates a dure explains how to mount and wire
potentially hazardous situation the LCI-R board. See Figure 1, 2, 3, 4
which, if not avoided, may result in or 5 for LCI-R board mounting location
minor or moderate injury. It may also and wire bundle placement.
be used to alert against unsafe
practices. Note: Skip steps 1 – 8 if the
LonTalk® Communication
Interface board is already factory
CAUTION – Indicates a situation installed.
that may result in equipment or
property-damage-only accidents.
WARNING
General Information Hazardous Voltage!
The Communication Interface board Hazardous Voltage w/Capacitors!
allows ReliaTel™ controls to Disconnect all electric power, includ-
communicate on a LonTalk Network at ing remote disconnects and dis-
the unit level. This product is intended charge all motor start/run capacitors
to be installed by a qualified System before servicing. Follow proper lock-
Integrator properly trained and out/tagout procedures to ensure the
experienced in LonTalk networks. power cannot be inadvertently ener-
Network variables are based on the gized. Verify with an appropriate volt-
LonMark® Space Comfort Controller meter that all capacitors have dis-
Functional Profile Template. The LCI-R charged. Failure to disconnect power
utilizes a Free Topology transceiver and discharge capacitors before ser-
FTT-10A. The FTT-10A transceiver vicing could result in death or seri-
supports non-polarity sensitive, free ous injury.
topology wiring, allowing the system
installer to utilize star, bus, and loop 1. Disconnect the power source to the
architecture. unit and remove the Access Panel
to gain access to the electronic con-
trols.
LCI-R Shipment and Inspec-
tion 2. Select proper installation depending
The Kit (BAYLTCI002B or on tonnage:
BAYLTCI003B) includes: a ReliaTel™
LCI-R communications board, a wiring 3 - 5 ton Packaged Rooftop
harness and the mounting hardware (except WSC060E) and
needed for installation on a Packaged 7½ - 10 ton Split System units:
Rooftop Unit with ReliaTel™ Mount the LonTalk® Communication
Communications Module. Interface board to the rear side of
the ReliaTel™ Refrigeration Module
LCI-R kits include the following items: mounting panel by sliding the
1 - LCI-R communications board LonTalk® Communication Interface
1 - Wire harness mounting feet into the mounting ex-
4 - LCI-R board mounting screws trusions on the ReliaTel™ Refrigera-
1 - Pop-in wire tie (BAYLTCI002B) tion Module mounting panel. Secure
with 1 screw. See Figure 1.
ACC-SVN19B-EN 3
Installation
15 - 20 ton Split System units: 7. Route the twisted pair communica-
Mount the LonTalk® Communica- tions wire from the BMS or CCP,
tion Interface board above the through the hole located below TB1
Reliatel™ Refrigeration Module on on the LonTalk® Communication In-
the control box mounting panel. Se- terface board and connect these
cure with 2 screws. See Figure2. wires to TB1. Refer to the ICS Com-
munications Link Wiring Require-
6 through 10 Ton Packaged Roof- ments section for wire information.
top Units (and WSC060E):
Mount the LonTalk® Communication 8. Secure the wires connected to TB1
Interface board to the right side of using the pop-in wire tie under the
the ReliaTel™ Refrigeration Module control box.
mounting panel by sliding the
LonTalk® Communication Interface LonTalk Communication Link
mounting feet into the mounting ex- Wiring Requirements
trusions on the control box mounting The LonTalk communications link is for
panel. Secure with 1 screw. See Fig- connection to a Building LonTalk Net-
ure 3. work.
12 1/2 through 25 Ton Packaged The Communications link wiring is de-
Rooftop Units: pendent on the network architecture. It
Mount the LonTalk® Communication is recommended that a System Integra-
Interface board to the right side of tor refer to "LonWorks FTT-10A Free
the ReliaTel™ Refrigeration Module Topology Transceiver User's Guide" by
by sliding the LonTalk® Communica- the Echelon Corporation for proper wire
tion Interface mounting feet into the selection. The physical limits are de-
mounting extrusions on the control fined in Chapter 4, Network Cabling
box bottom panel. Secure with 2 And Connection. This User's Guide is
screws. See Figure 4. available on the Echelon Web page. A
typical wire recommendation is Belden
27 1/2 through 50 Ton Packaged 85102, single twisted pair, stranded 19/
Rooftop Units: 29, unshielded, 150 C.
Mount the LonTalk® Communication
Interface board to the right side of
the ReliaTel™ Refrigeration Module
on the control box back panel. Se-
cure with 4 screws. See Figure 5.
4 ACC-SVN19B-EN
Installation
Figure 1
LonTalk® Communication Interface Board Mounting and Wiring
Figure 2
LonTalk® Communication Interface Board Mounting and Wiring
ACC-SVN19B-EN 5
Installation
Figure 3
LonTalk® Communication Interface Board Mounting and Wiring
Figure 4
LonTalk® Communication Interface Board Mounting and Wiring
6 ACC-SVN19B-EN
Installation
Figure 5
LonTalk® Communication Interface Board Mounting and Wiring
+ ON - Power is applied and the LCI-R is normal. + Flickering - When communication activity is detected
+ OFF - There is either no power applied or the LCI-R is on the network. (This LED is not effected by
unconfigured or offline. transmitting data from the LCI-R.)
+ Blinking twice per second for 10 seconds - The LCI-R + OFF - No current activity on the Network.
has been commanded to WINK.
+ Continuous Blinking ; ON for 2.25 seconds , OFF for
.25 seconds - The unit is in a TEST mode.
Wink Response
The LCI-R responds to a network "Wink Request". Upon re-
ceipt of a Wink request the LCI-R will blink (0.25 second ON,
0.25 second OFF, 0.25 second ON, etc...) the STATUS LED
continuously for 10 seconds. This Wink response is available
both when the LCI-R node is configured and when it is
unconfigured.
ACC-SVN19B-EN 7
Installation
8 ACC-SVN19B-EN
Installation
Typical Range and Default Values
Configuration Properties Minimum Maximum Default
unoccupied_cool 4.44 C 43.33 C 29.44 C
The network management read and write messages can be
used to modify 7 configuration parameters. 40.00 F 110.00 F 85.00 F
standby_cool 4.44 C 43.33 C 25.55 C
Rooftop Object Configuration Property 40.00 F 110.00 F 78.00 F
SCC nci SNVT Type SCPT NV Name occupied_cool 4.44 C 43.33 C 23.33 C
Index Index 40.00 F 110.00 F 74.00 F
1 SNVT_time_sec 49 nciSndHrtBt occupied_heat 4.44 C 40.55 C 21.67 C
2 SNVT_temp_setpt 60 nciSetpoints 40.00 F 105.00 F 71.00 F
3 SNVT_time_sec 52 nciMinOutTm standby_heat 4.44 C 40.55 C 19.44 C
4 SNVT_time_sec 48 nciRcvHrtBt 40.00 F 105.00 F 67.00 F
5 SNVT_str_asc 17 nciLocation unoccupied_heat 4.44 C 40.55 C 15.55 C
6 SNVT_time_min 34 nciBypassTime 40.00 F 105.00 F 60.00 F
8 SNVT_lev_percent 23 nciOAMinPos
9 SNVT_ppm 42 nciSpaceCO2Lim Minimum Send Time
10 SNVT_lev_percent 36 nciSpaceRHSetpt Network input config SNVT_time_sec nciMinOutTm
20 SNVT_hvac_type 169 nciHvacType
This parameter defines the minimum period of time which
must elapse between updates of bound output network vari-
Send Heartbeat ables. The default is 0.2 seconds. An invalid value (0xFFFF)
Network input config SNVT_time_sec nciSndHrtBt is considered the same as zero.
This parameter defines the amount of time that expires be- Setting nciMinOutTm = 0.0 disables the Minimum Send
fore all bound output network variables associated with the Time, allowing the LCI-R to send multiple network variable
Rooftop object are automatically updated. Network variable updates as fast as it can.
update messages are sent at periodic intervals. The default
is 5 minutes and invalid (0xFFFF) is interpreted as zero. Receive Heartbeat
Network input config SNVT_time_sec nciRcvHrtBt
Setting nciSndHrtBt =0.0 disables the Send Heartbeat.
This parameter specifies the maximum period of time which
Occupancy Temperature Setpoint can elapse between updates to an input network variable
Network input config SNVT_temp_setpt nciSetpoints before the LCI-R begins to use the default value. Each input
network variable is monitored for updates individually. The
This configuration parameter defines the space temperature default is 15 minutes and invalid (0xFFFF) is interpreted as
setpoints for the various heat, cool and occupancy modes. zero.
The occupied and standby setpoints are defaults which can
be modified by various input variables such as nviSetpoint Setting nciRcvHrtBt = 0.0 disables the Receive Heartbeat.
and nviSetpointOffset. The unoccupied setpoints are always The following input network variables DO NOT revert back
valid. to their defaults, they are based on Receive Heartbeat:
If any setpoint is out of range or they are not in the proper or- nviSetpoint
der the LCI-R reverts to default values. The values of the indi- nviOccManCmd
vidual setpoints within nciSetpoints must be kept in descend- nviEmergOverride
ing order as follows: unoccupied_cool, standby_cool,
occupied_cool, occupied_heat, standby_heat and Location Label
unoccupied_heat. Network input config SNVT_str_asc nciLocation
RQ_UPDATE_STATUS
The Rooftop object supports the following 2 optional status
flags in SNVT_obj_status.
10 ACC-SVN19B-EN
Installation
Network Variable Descriptions: adjustment. All occupied and standby setpoints will be
shifted upward (+) or downward (-) by the value of
Network Variable description NV refers to the SCC NV #. An nviSetptOffset. Refer to Effective Setpoint Output
example would be NV#1 is SCC NV#1 as referenced on the (nvoEffectSetpt) for more information.
Rooftop Object Network Variables table on page 4.
Valid Range
The valid range is -10C to +10C. The value 0x7FFF (inter-
NV#1 Space Temperature Input preted as 0) will be handled as an invalid value.
Network input SNVT_temp_p nviSpaceTemp;
ACC-SVN19B-EN 11
Installation
NV#6 Occupancy Override Input Default Value
Network input SNVT_occupancy nviOccManCmd; The default value is OC_OCCUPIED = 0.
This value will be adopted at power-up and in case of not re-
This input network variable is used to command the ReliaTel ceiving an update within the specified Receive Heartbeat
Control into different occupancy modes. It is typically sent time.
by an externally mounted occupant-interface module or a
supervisory node, to manually control occupancy modes, or NV# 8 Application Mode Input
to override the scheduled occupancy. Network input SNVT_hvac_mode nviApplicMode;
The bypass timer is started when an update to This network variable input is used to coordinate the ReliaTel
nviOccManCmd occurs in which nviOccManCmd = Control with any supervisory controller. If a mode is re-
OC_BYPASS. There is no Receive Heartbeat associated quested that is not supported by the ReliaTel Control, the
with nviOccManCmd, so any update in which nviOccManCmd ReliaTel Control will ignore the request.
= OC_BYPASS will restart the bypass timer. Any other up-
date will clear the bypass timer. When the timer expires, The nviApplicMode overrides nviHeatCool, unless
nviOccManCmd reverts to OC_NUL. nviApplicMode is HVAC_AUTO, HVAC_TEST, or HVAC_NUL.
If nviApplicMode is HVAC_AUTO, HVAC_TEST or
This input is used in conjunction with nviOccSchedule and HVAC_NUL, then nviHeatCool determines the effective mode
nviOccSensor (if provided) to determine the effective occu- of the unit. Refer to Effective Heat/Cool Output
pancy mode. Refer to Effective Occupancy Output (nvoHeatCool) for more information.
(nvoEffectOccup) for more information.
Valid Range
Valid Range 0 = HVAC_AUTO (Mode determined by Reliatel Control)
0 = OC_OCCUPIED: The ReliaTel Control should operate in 1 = HVAC_HEAT (Use heat setpoints)
the occupied mode (e.g. occupied setpoint). 2 = HVAC_MRNG_WRMUP (Morning warmup)
3 = HVAC_COOL (Use cool setpoints)
1 = OC_UNOCCUPIED: The ReliaTel Control should operate 4 = HVAC_NIGHT_PURGE (Free cooling)
in the unoccupied mode (e.g. unoccupied setpoint and fan 5 = HVAC_PRE_COOL (Morning cooldown)
mode in AUTO). 6 = HVAC_OFF (No unit operation allowed)
7 = HVAC_TEST (same as HVAC_NUL)
2 = OC_BYPASS: The ReliaTel Control should operate in the 8 = HVAC_EMERG_HEAT (Emergency heat)
occupied mode for a period of time defined by 9 = HVAC_FAN_ONLY (No heating or cooling allowed)
nciBypassTime. 12 = HVAC_MAX_HEAT (Same as HVAC_HEAT)
14 = HVAC_DEHUMID (Same as HVAC_AUTO)
3 = OC_STANDBY: The ReliaTel Control should operate in 0xFF = HVAC_NUL (same as HVAC_AUTO)
the standby mode (e.g. standby setpoint). All other enumerations will be ignored.
0xFF = OC_NUL: This is the initial value after power-up and Default Value
it remains until another value is received. It is used to indi- The default value is HVAC_AUTO.
cate that this network variable input is invalid or unused, or to This value will be adopted at power-up and in case of not re-
cancel a previous command. ceiving an update within the specified Receive Heartbeat
time.
Default Value
The default value OC_NUL = 0xFF. NV#9 Heat/Cool Mode Input
This value will be adopted at power-up. This network vari- Network input SNVT_hvac_mode nviHeatCool;
able input does not use the Receive Heartbeat function.
This network variable input is used to coordinate the ReliaTel
NV#7 Occupancy Sensor Input Control with any node that may need to control the heat/cool
Network input SNVT_occupancy nviOccSensor; changeover of the unit. For example, one node may coordi-
nate it’s heat/cool mode with another node serving the
This input network variable is used to indicate the presence same area, or the heat/cool mode could be manually se-
of occupants in the controlled space. It is typically sent by an lected from a human interface device. If a mode is re-
occupancy sensor. quested that is not supported by the ReliaTel Control, the
ReliaTel Control will ignore the request.
This input is used in conjunction with nviOccSchedule and This input is overridden by nviApplicMode, unless
nviOccManCmd (if provided) to determine the effective occu- nviApplicMode is HVAC_AUTO, HVAC_TEST, or
pancy mode. Refer to Effective Occupancy Output HVAC_NUL. If nviApplicMode is HVAC_AUTO or
(nvoEffectOccup) for more information. HVAC_NUL or HVAC_TEST, then nviHeatCool determines
the effective mode of the unit. Refer to Effective Heat/Cool
Output (nvoHeatCool) for more information.
Valid Range
0 = OC_OCCUPIED: The occupancy sensor is indicating
that there ARE occupants in the space.
12 ACC-SVN19B-EN
Installation
Valid Range
0 = HVAC_AUTO (Mode determined by Reliatel Default Value
Control) Default value is ON (state = 0xFF) for Occupied Mode.
1 = HVAC_HEAT (Use heat setpoints) The value is AUTO for Unoccupied Mode.
2 = HVAC_MRNG_WRMUP (Morning warmup)
3 = HVAC_COOL (Use cool setpoints) NV#11 Compressor Enable Input
4 = HVAC_NIGHT_PURGE (Free cooling) Network input SNVT_switch nviComprEnable;
5 = HVAC_PRE_COOL (Morning cooldown)
6 = HVAC_OFF (No unit operation allowed) This input is used to disable compressor operation. The in-
7 = HVAC_TEST (Same as HVAC_NUL) put is typically sent from a supervisory controller.
8 = HVAC_EMERG_HEAT (Emergency heat)
9 = HVAC_FAN_ONLY (No heating or cooling allowed) This input can be used for simple enable/disable functions,
12 = HVAC_MAX_HEAT (same as HVAC_HEAT) or can be used to enable a portion of the unit’s compressor
14 = HVAC_DEHUMID (same as HVAC_AUTO) capacity. For example, if a unit has 2 compressors, a value
0xFF = HVAC_NUL (same as HVAC_AUTO) of 100 (50.0%) could indicate that only one compressor is
All other enumerations will be ignored. enabled.
This input is used to change the fan mode of the unit. The in- 2* 0 n/a n/a 0
put is typically sent from a supervisory controller. This vari- 1 0 0% 0
able does not use Receive Heartbeat. 1 01 to 100 .05% to 50% 1
nvoEffectOccup nvoHeatCool nviFanModeCmd Voyager 1 101 to 200 50.5% to 100% 2
Fan Mode 1 201 to 255 100% 2
State Value Equiv. %
0xFF n/a n/a 2
X HVAC_OFF X X AUTO
X HVAC_FAN_ONLY X X ON
OC_UNOCCUPIED X X X AUTO Default Value
* X 0 n/a n/a AUTO
Default Value is ENABLED (state = 0xFF).
* X 1 0 0% AUTO
* X 1 1 to 255 0.5% to 100% ON
This value will be adopted at power-up and in case of not
* X 0xFF n/a n/a ON receiving an update within the specified Receive Heartbeat
time.
* OC_OCCUPIED, OC_STANDBY, OC_BYPASS, or
OC_NUL.
ACC-SVN19B-EN 13
Installation
NV#12 Auxiliary Heat Enable Input NV#13 Economizer Enable Input
Network input SNVT_switch nviAuxHeatEnable; Network input SNVT_switch nviEconEnable;
This input is used to disavle auxiliary heat operation. This in- This input is used to enable and disable economizer opera-
put is typically sent from a system supervisor panel. For ex- tion. This input is typically sent from a system supervisor
ample, during peak electrical demand periods, electric heat panel to override the local economizer enable/disable deci-
operation could be disbled. sion. For this input, economizer Auto means that the ReliaTel
Control determines economizer operation. Enabled or Dis-
This input can be used for simple enable/disable functions, abled means that economizer operation is allowed or not al-
or can be used to enable a portion of the unit’s auxiliary heat lowed (respectively), overriding the local decision.
capacity. For example, if a unit has 2 stages of electric heat,
a value of 100 (50.0%) could indicate that only one stage is Valid Range
enabled. nvoHeatCool nviEconEnable Economizer
State
State Value Equiv. %
Heat nviAuxHeatEnable Number HVAC_MRNG_WRMUP X X Disabled
Type of Heating HVAC_NIGHT_PURGE X X Enabled
Default Value
The default value is EMERG_NORMAL.
This value will be adopted at power-up, until an update is re-
ceived. This network variable input does not use the Receive
Heartbeat function.
14 ACC-SVN19B-EN
Installation
NV#22 Space CO2 Input Valid Range
Network input SNVT_ppm nviSpaceIAQ; The valid range is -40C to 70C (-40F to 158F). The value
0x7FFF=+327.67C will be handled as an invalid value.
This input network variable is used to connect an external
space CO2 sensor to the LCI-R. It does not have to be Default Value
bound to a sensor node if the unit has a locally wired space Default Value is 0x7FFF (=+327.67C). This value will be
CO2 sensor. In any case, the nviSpaceIAQ has priority if a adopted at power-up and in case of not receiving an update
valid value is present. within the specified receive heartbeat time.
Valid Range
NV#59 Outdoor Air Damper Minimum Position The valid range is 0 to 100%. The value 0x7FFF will be
Input handled as an invalid value.
Network input SNVT_lev_percent nviOAMinPos;
Default Value
This input network variable is used to connect an external The default Value is 0x7FFFThis value will be adopted at
damper minimum position to the LCI-R. It does not have to power-up and in case of not receiving an update within the
be bound to a sensor node if the unit has a local minimum specified receive heartbeat time.
position potentiometer. In any case, the nviOAMinPos has
priority if a valid value is present.
NV#26 Effective Space Temperature Output
Valid Range Network output SNVT_temp_p nvoSpaceTemp;
The valid range is 0 to 50 %. The value 0x7FFF will be
handled as an invalid value. This output network variable is used to monitor the effective
space temperature that ReliaTel Control is using for control.
If the input nviSpaceTemp has a valid value, this output will
Default Value echo the value of the input. If a valid value for nviSpaceTemp
The default Value is 0x7FFF. This value will be adopted at does not exist, the locally wired sensor value is used. If nei-
power-up and in case of not receiving an update within the ther value is available, the output will send the INVALID
specified receive heartbeat time. value.
NV#21 Outdoor Relative Humidity Input Range
Network input SNVT_lev_percent nviOutdoorRH; The range is -10C to 50C (14F to 122F). The value
0x7FFF=+327.67C will be used as an invalid value in case of
This input network variable is used to connect an external a sensor failure.
outdoor RH sensor to the LCI-R. It does not have to be
bound to a sensor node if the unit has a locally wired space When Transmitted
RH sensor. In any case, the nviOutdoorRH has priority if a The variable is transmitted immediately when its value has
valid value is present. changed significantly. Additionally, this network variable will
also be transmitted as a heartbeat output on a regular basis
Valid Range as dictated by the Maximum Send Time (nciSndHrtBt) con-
The valid range is 0 to 100%. The value 0x7FFF will be figuration value.
handled as an invalid value.
Update Rate
Default Value This value will be updated no faster than the Minimum Send
The default Value is 0x7FFFThis value will be adopted at Time (nciMinOutTm) configuration value.
power-up and in case of not receiving an update within the
specified receive heartbeat time. Default Service Type
NV#19 Outdoor Temperature Input The default service type is unacknowledged.
Network input SNVT_temp_p nviOutdoorTemp;
ACC-SVN19B-EN 15
Installation
NV#28 Effective Setpoint Output If nviSetpoint is valid:
Network output SNVT_temp_p nvoEffectSetpt; effective_occupied_cool = nciSepoints.occupied_cool
+ abs_setpoint_offset + nviSetptOffset
This output network variable is used to monitor the effective
temperature setpoint currently used by the ReliaTel Control, effective_standby_cool = nciSetpoints.standby_cool
which may depend on nciSetpoints, nviSetpoint, + abs_setpoint_offset + nviSetptOffset
nviSetpointOffset, nvoEffectOccup, nvoHeatCool, and any
local setpoint adjustment. For example, if the occupancy effective_occupied_heat = nciSetpoints.occupied_heat
state is unoccupied and the heat/cool state is heat, then the + abs_setpoint_offset + nviSetptOffset
effective setpoint would be equal to the unoccupied heating
setpoint defined in nciSetpoints. effective_standby_heat = nciSetpoints.standby_heat
+ abs_setpoint_offset + nviSetptOffset
Definitions: If nviSetpoint is not valid there are 4 cases to consider:
abs_setpoint_offset = LCS = Local Zone Cooling Setpoint Input
nviSetpoint-(nciSetpoints.occupied_cool+ LHS = Local Zone Heating Setpoint Input
nciSetpoints.occupied_heat)/2
Case 1: LCS is valid & LHS is valid
deadband_occupied =
nciSetpoints.occupied_cool - nciSetpoints.occupied_heat effective_occupied_cool = LCS + nviSetptOffset
effective_standby_cool = LCS +
heat_standby_offset = cool_standby_offset + nviSetptOffset
nciSetpoints.occupied_heat - nciSetpoints.standby_heat
effective_occupied_heat = LHS + nviSetptOffset
cool_standby_offset = effective_standby_heat = LHS – heat_standby_offset
nciSetpoints.standby_cool - nciSetpoints.occupied_cool + nviSetptOffset
effective_occupied_cool = nciSetpoints.occupied_cool
+ nviSetptOffset
effective_standby_cool = nciSetpoints.standby_cool
+ nviSetptOffset
effective_occupied_heat = nciSetpoints.occupied_heat
+ nviSetptOffset
effective_standby_heat = nciSetpoints.standby_heat
+ nviSetptOffset
16 ACC-SVN19B-EN
Installation
The effective setpoint is then defined as follows: NV#27 Unit Status Output
Network output SNVT_hvac_status nvoUnitStatus;
Occupancy Status Mode nvoEffectSetpoint
nvoEffectOccup nvoHeatCool This output network variable is used to report the ReliaTel
OCCUPIED OR Cool** effective_occupied_cool Control status. It combines the operating mode, the capacity
BYPASS Heat* effective_occupied_heat of heating and cooling used and an indication if any alarms
are present in the unit. SNVT_hvac_status allows this infor-
UNOCCUPIED Cool** effective_unoccupied_cool mation to be provided in one network variable.
Heat* effective_unoccupied_heat
STANDBY Cool** effective_standby_cool Mode:
Heat* effective_standby_heat Refer to Effective Heat/Cool Output (nvoHeatCool) for addi-
tional information regarding the value reported in the mode
*Heat Modes: field. The value in the mode field is the same value as the
HVAC_HEAT Effective Heat/Cool Output.
HVAC_EMERG_HEAT
**Cool Modes: Valid Range
HVAC_COOL Mode: same as nvoHeatCool
HVAC_OFF heat_output_primary: 0-100%, 0xFFFF (Invalid)
HVAC_TEST heat_output_secondary: 0-100%, 0xFFFF (Invalid)
HVAC_FAN_ONLY cool_output: 0-100%, 0xFFFF (Invalid)
econ_output: 0-100%, 0xFFFF (Invalid)
There are 2 exceptions to the table above. The occupied fan_output: 0-100%, 0xFFFF (Invalid)
setpoint is used in the following cases: in_alarm: 0 Means there is no alarm.
1 Means there is an alarm.
1. If nvoHeatCool = HVAC_MRNG_WRMUP
Then nvoEffectSetpt = effective_occupied_heat
Heat Output Primary:
2. If nvoHeatCool = HVAC_NIGHT_PURGE or Heat Output Primary is compatible with SNVT_lev_percent
HVAC_PRE_COOL This value indicates the capacity of heat that is currently op-
Then nvoEffectSetpt = effective_occupied_cool erating in the Unit, for the following unit types:
+Gas Heat: Capacity of Gas Heat stages
Range +Electric Heat (not Heat Pump) : Capacity of Electric Heat
The range is 10C to 32.22C (50F to 90F). If the stages.
nvoEffectSetpt calculates to a lower valve than 10C (50F), +Heat Pump: Capacity of Compressor Heat stages
the LCI-R will clamp the nvoEffectSetpt to 10C (50F). If the +Cooling Only: A value of 0xFFFF (Invalid) is sent.
nvoEffectSetpt calculates to a higher valve than 32.22C
(90F), the LCI will clamp the nvoEffectSetpt to 32.22C (90F). Unit Type # of Stages Heat Output
Operating Secondary
When Transmitted Heat Pump with 0 0%
The variable is transmitted immediately when its value has
changed significantly. Additionally, this network variable will Single Stage 1 100%
also be transmitted as a heartbeat output on a regular basis Aux. Heat
as dictated by the Maximum Send Time (nciSndHrtBt) con- Heat Pump with 0 0%
figuration value. Two Stage 1 50%
Update Rate Aux. Heat 2 100%
This value will be updated no faster than the Minimum Send Non Heat Pump Unit - 0xFFFF (Invalid)
Time (nciMinOutTm) configuration value.
Heat Output Secondary:
Default Service Type Heat Output Secondary is compatible with
The default service type is unacknowledged. SNVT_lev_percent
This value indicates the capacity of auxiliary electric heat
that is currently operating in Heat Pump units. If the unit is
not a Heat Pump, a value of 0xFFFF (Invalid) is sent.
ACC-SVN19B-EN 17
Installation
Cool Output : Maintenance Required
Cool Output is compatible with SNVT_lev_percent
This value indicates the capacity of mechanical cooling that Space Temp Sensor Fail
is currently operating in the unit. If the unit has no mechani- Outdoor Temp Sensor Fail
cal cooling, a value of 0xFFFF (Invalid ) is sent. Compressor 1 HPC Lockout
Compressor 1 LPC Lockout
Unit Type # of Stages Cool Output Comp 1 Disable Input/LPC
Operating Compressor 2 HPC Lockout
Single Stage 0 0% Compressor 2 LPC Lockout
Cooling 1 100% Comp 2 Disable Input/LPC
Two Stage 0 0% Smoke Detector
Cooling 1 50% Heat Fail
2 100% Dirty Filter
Three Stage 0 0% Supply Fan Fail
Cooling 1 33% Emergency Stop Input
2 66% FroStat™ Trip
3 100% Unit Comm Fail
Heating Only - 0xFFFF (Invalid) Mixed Air Temp Sensor Fail (Optional)
OA Rel Humidity Fail (Optional)
Econ Output RA Temp Sensor Fail (Optional)
Econ Output is compatible with SNVT_lev_percent.
This value indicates the position (percent open) of the unit's RA Rel Humidity Fail (Optional)
Outdoor Air Damper (economizer). If the unit does not have Coil Temperature Sensor Fail (Heat Pump only)
an Outdoor Air Damper, a value of 0xFFFF (Invalid) is sent. Demand Defrost Fault A (Heat Pump only)
Demand Defrost Fault B (Heat Pump only)
Fan Output
Fan Output is compatible with SNVT_lev_percent. Demand Defrost Fault C (Heat Pump only)
This value indicates the status of the unit's Supply Fan. If the Demand Defrost Fault D (Heat Pump only)
fan is off, the value is 0%. If the fan is on, the value is 100%. Defrost Default Mode (Heat Pump only)
In Alarm Local Cooling Setpt Failure (Optional)
This value indicates whether an alarm condition currently ex- Local Heating Setpt Failure (Optional)
ists in the unit. A value of 0 = No alarm exists, while a value Vent Override – Purge (Optional)
of 1 = an alarm exists. The following alarm conditions in the Vent Override – Exhaust (Optional)
ReliaTel Control will indicate an alarm:
Vent Override – Pressurize (Optional)
External Auto / Stop(Optional)
Freeze Stat Tripped (Optional)
Discharge Temperature Sensor Fail (Optional)
CO2 Sensor Fail (Optional)
CO2 Setpoint Fail (Optional)
Dehumid Sensor Failure (Optional)
Dehumid Setpt Failure (Optional)
Outdoor Air CFM Sensor Failure (Option)
Outdoor Air CFM Setpt Failure (Option)
Space Pressure Setpt Failure (Option)
Space Pressure Sensor Failure (Optional)
Heating High Limit Open
Inducer Proving Switch Fail
No Flame Sensed on Heat Call
Flame Rollout Switch Open
Flame Sensed w/ Gas valve Off
Gas Heat Module Failure
Economizer Actuator Fault
Comp 1 Disable Input/HPC
Comp 2 Disable Input/HPC
18 ACC-SVN19B-EN
Installation
When Transmitted Effective Occupancy Output
This variable is transmitted immediately when its value has nviOccManCmd nviOccSchedule³ nviOccSensor² nvoEffectOccup
changed significantly. Additionally, this network variable will OC_OCCUPIED X X OC_OCCUPIED
also be transmitted as a heartbeat output on a regular basis OC_UNOCCUPIED X X OC_UNOCCUPIED
as dictated by the Maximum Send Time (nciSndHrtBt) con- OC_BYPASS¹ OC_OCCUPIED X OC_OCCUPIED
figuration value. OC_UNOCCUPIED X OC_BYPASS¹
OC_STANDBY X OC_BYPASS¹
Update Rate OC_NUL OC_OCCUPIED² OC_OCCUPIED
This value will be updated no faster than the Minimum Send OC_UNOCCUPIED OC_BYPASS¹
OC_STANDBY X X OC_STANDBY
Time (nciMinOutTm) configuration value.
OC_NUL OC_OCCUPIED OC_OCCUPIED² OC_OCCUPIED
OC_UNOCCUPIED OC_STANDBY
Default Service Type
OC_UNOCCUPIED X OC_UNOCCUPIED
The default service type is unacknowledged. OC_STANDBY X OC_STANDBY
OC_NUL OC_OCCUPIED² OC_OCCUPIED
NV#29 Effective Occupancy Output OC_UNOCCUPIED OC_UNOCCUPIED
Network output SNVT_occupancy nvoEffectOccup; Notes:
1. OC_BYPASS can be initiated by the nviOccManCmd or local sensor mounted switch.
This output network variable is used to indicate the actual oc- nvoEffectOccup w ill only be OC_BYPASS for the duration of the Local Bypass
cupancy mode of the unit. This information is typically re- Time (nciBypassTime), until reinitiated by an update to nviOccManCmd or local switch.
ported to a supervisory controller, or provided to another unit 2 For the occupancy sensor, OC_NUL is interpreted as OC_OCCUPIED.
to coordinate the operation of multiple units. The occupancy 3 For nviOccSchedule, this refers to the “current state” field.
mode is determined by a combination of optional input net- 4. “X” = Any State
ACC-SVN19B-EN 19
Installation
1 The “mode” field of nvoUnitStatus will typically report the same value as HVAC_OFF LCS
nvoHeatCool. HVAC_FAN_ONLY LCS
2 nvoHeatCool will report HVAC_TEST if the Reliatel Control is put into the
Service Test Mode locally. HVAC_TEST is not supported as an input.
Range
3 If nviApplicMode = HVAC_MRNG_WRMUP and nviHeatCool =
The range is 10C to 35C (50F to 95F). The value
0x7FFF=+327.67°C will be sent as an invalid value in case of
HVAC_EMERG_HEAT, then nvoHeatCool = HVAC_EMERG_HEAT.
a setpoint device failure.
4 nvoHeatCool will report HVAC_DEHUMID if the Reliatel Control determines it
is okay to perform dehumidification. HVAC_DEHUMID is not supported as an input.
When Transmitted
The variable is transmitted immediately when its value has
The nvoHeatCool is also used to help determine other oper- changed significantly. Additionally, this network variable will
ating parameters in the unit, including the Fan Mode, the be transmitted as a heartbeat output on a regular basis as
Economizer Enable/Disable state and Economizer Minimum dictated by the Maximum Send Time (nciSndHrtBt) configu-
Position. In certain states, nvoHeatCool overrides the normal ration value.
decisions for these parameters as shown in the table below:
nvoHeatCool Fan Mode Economizer Economizer Minimum Update Rate
Position This value will be updated no faster than the Minimum Send
HVAC_HEAT nviFanModeCmd nviEconEnable nciOAMinPos Time (nciMinOutTm) configuration value.
HVAC_COOL nviFanModeCmd nviEconEnable nciOAMinPos
HVAC_MRNG_WRMUP nviFanModeCmd DISABLE 0 Default Service Type
*HVAC_NIGHT_PURGE nviFanModeCmd ENABLE 0
The default service type is unacknowledged.
HVAC_PRE_COOL nviFanModeCmd nviEconEnable 0
HVAC_OFF AUTO nviEconEnable nciOAMinPos
HVAC_EMERG_HEAT nviFanModeCmd nviEconEnable nciOAMinPos
HVAC_FAN_ONLY ON nviEconEnable nciOAMinPos
*HVAC_NIGHT_PURGE disables compressors allowing for free cooling
Note: Whenever the Fan is OFF the Outdoor Air Damper (Economizer) will be closed.
When Transmitted
This variable is transmitted immediately when its value has
changed significantly. Additionally, this network variable will
also be transmitted as a heartbeat output on a regular basis
as dictated by the Maximum Send Time (nciSndHrtBt) con-
figuration value.
Update Rate
This value will be updated no faster than the Minimum Send
Time (nciMinOutTm) configuration value.
20 ACC-SVN19B-EN
Installation
Range
The range is 0C to 100C (32F to 212F). The value
0x7FFF=+327.67C will be sent as an invalid value in case of
a sensor failure.
When Transmitted
This variable is transmitted immediately when its value has
changed significantly. Additionally, this network variable will
also be transmitted as a heartbeat output on a regular basis
as dictated by the Maximum Send Time (nciSndHrtBt) con-
figuration value.
Update Rate
This value will be updated no faster than the Minimum Send
Time (nciMinOutTm) configuration value.
ACC-SVN19B-EN 21
Installation
NV#37 Terminal Load Output Range
Network output SNVT_lev_percent nvoTerminalLoad; The range is 0 % to 100 %. The value 0x7FFF = +163.835 %
will be sent as an invalid value to indicate that the locally
This output reports the current heat/cool demand of the unit. wired humidity sensor is failed.
Positive implies cooling. Negative implies heating. This value
is estimated from the current space temp and active When Transmitted
setpoints. This variable is transmitted immediately when its value has
changed significantly. Additionally, this network variable will
Range also be transmitted as a heartbeat output on a regular basis
There are 4 valid values for nvoTerminalLoad: +100%, 0, - as dictated by the Maximum Send Time (nciSndHrtBt) con-
100%, -150%. The value is determined by comparing the figuration value.
space temp with CSP and HSP.
Update Rate
This value will be updated no faster than the Minimum Send
When Transmitted Time (nciMinOutTm) configuration value.
This variable is transmitted immediately when its value has
changed significantly. Additionally, this network variable will Default Service Type
also be transmitted as a heartbeat output on a regular basis The default service type is unacknowledged.
as dictated by the Maximum Send Time (nciSndHrtBt) con-
figuration value.
NV#44 Outdoor Air Humidity Output
Update Rate Network output SNVT_lev_percent nvoOutdoorRH;
This value will be updated no faster than the Minimum Send
Time (nciMinOutTm) configuration value. This output network variable is used to monitor the effective
outdoor relative humidity that the ReliaTel control is using. If
Default Service Type the input nviOutdoorRH has a valid value, this output will
The default service type is unacknowledged. echo the value of the input. If a valid value for nviOutdoorRH
does not exist, the locally wired sensor value is used. If nei-
ther value is available, the output will send the INVALID
NV#42 Outdoor Air Damper Output value.
Network output SNVT_lev_percent nvoOADamper;
Range
This output network variable indicates the outdoor air The range is 0 % to 100 %. The value 0x7FFF = +163.835 %
damper position in percent, if the unit has an economizer. will be sent as an invalid value to indicate that the locally
wired humidity sensor is failed.
Range
The range is 0 % to 100 %. The value 0xFFFF will be sent When Transmitted
as an invalid value to indicate that the unit does not have an This variable is transmitted immediately when its value has
economizer. changed significantly. Additionally, this network variable will
also be transmitted as a heartbeat output on a regular basis
When Transmitted as dictated by the Maximum Send Time (nciSndHrtBt) con-
This variable is transmitted immediately when its value has figuration value.
changed significantly. Additionally, this network variable will
also be transmitted as a heartbeat output on a regular basis Update Rate
as dictated by the Maximum Send Time (nciSndHrtBt) con- This value will be updated no faster than the Minimum Send
figuration value. Time (nciMinOutTm) configuration value.
22 ACC-SVN19B-EN
Installation
When Transmitted Update Rate
This variable is transmitted immediately when its value has This value will be updated no faster than the Minimum Send
changed significantly. Additionally, this network variable will Time (nciMinOutTm) configuration value.
also be transmitted as a heartbeat output on a regular basis
as dictated by the Maximum Send Time (nciSndHrtBt) con- Default Service Type
figuration value. The default service type is unacknowledged.
Update Rate
This value will be updated no faster than the Minimum Send Return Air Temperature Output
Time (nciMinOutTm) configuration value. Network output SNVT_temp_p nvoRATemp;
Default Service Type This network variable does not follow the Space Comfort
The default service type is unacknowledged. Controller Functional ProfileTemplate, so it does not have a
SCC NV number.
NV#46 Space CO2 Output
Network output SNVT_ppm nvoSpaceCO2; This output network variable is used to monitor the return air
temperature of the unit, if the temperature sensor is installed.
This output network variable indicates the space CO2 in
ppm, if the unit has a locally wired CO2 sensor. Range
The range is 0C to 100C (32F to 212F). The value 0x7FFF =
Range +327.67C will be handled as an invalid value in case of a
The range is 0 ppm to 2000 ppm. The value 0xFFFF will be sensor failure.
sent as an invalid value to indicate that the locally wired CO2
sensor is failed. When Transmitted
This variable is transmitted immediately when its value has
When Transmitted changed significantly. Additionally, this network variable will
This variable is transmitted immediately when its value has also be transmitted as a heartbeat output on a regular basis
changed significantly. Additionally, this network variable will as dictated by the Maximum Send Time (nciSndHrtBt) con-
also be transmitted as a heartbeat output on a regular basis figuration value.
as dictated by the Maximum Send Time (nciSndHrtBt) con-
figuration value. Update Rate
This value will be updated no faster than the Minimum Send
Update Rate Time (nciMinOutTm) configuration value.
This value will be updated no faster than the Minimum Send
Time (nciMinOutTm) configuration value. Default Service Type
The default service type is unacknowledged.
Default Service Type
The default service type is unacknowledged. NV#64 Mixed Air Temperature Output
Network output SNVT_temp_p nvoMixedAirTemp;
Mixed Air Temperature Output
Network output SNVT_temp_p nvoMATemp; This output network variable is used to monitor the mixed air
temperature of the unit, if the temperature sensor is installed.
This network variable does not follow the Space Comfort
Controller Functional ProfileTemplate, so it does not have a Range
SCC NV number. The range is 0C to 100C (32F to 212F). The value 0x7FFF =
+327.67C will be handled as an invalid value in case of a
This output network variable is used to monitor the mixed air sensor failure.
temperature of the unit, if the temperature sensor is installed.
When Transmitted
Range This variable is transmitted immediately when its value has
The range is 0C to 100C (32F to 212F). The value 0x7FFF = changed significantly. Additionally, this network variable will
+327.67C will be handled as an invalid value in case of a also be transmitted as a heartbeat output on a regular basis
sensor failure. as dictated by the Maximum Send Time (nciSndHrtBt) con-
figuration value.
When Transmitted
This variable is transmitted immediately when its value has Update Rate
changed significantly. Additionally, this network variable will This value will be updated no faster than the Minimum Send
also be transmitted as a heartbeat output on a regular basis Time (nciMinOutTm) configuration value.
as dictated by the Maximum Send Time (nciSndHrtBt) con-
figuration value. Default Service Type
The default service type is unacknowledged.
ACC-SVN19B-EN 23
Literature Order Number ACC-SVN19B-EN
File Number SV-UN-ACC-ACC-SVN19B-EN 10/05
Supersedes ACC-SVN19A-EN
Stocking Location Webb Mason
The manufacturer has a policy of continuous product and product data improvement and reserves the right
to change design and specifications without notice.
24 ACC-SVN19B-EN