Energy Procedia 24 (2012) 123 – 130

Invited paper

Modeling and control of Multi-terminal VSC HVDC systems


Jef Beerten, Ronnie Belmans
University of Leuven (KU Leuven), Dept. Electrical Engineering (ESAT), Division ELECTA
Kasteelpark Arenberg 10 (bus 2445)
3001 Heverlee, Belgium

Abstract
This paper discusses the modeling and control of Voltage Source Converter High Voltage Direct Current (VSC HVDC)
systems in a multi-terminal configuration (MTDC). Both steady-state interactions, as well as transient stability modeling
and control are addressed. Simulation results show that adequately modelling the DC voltage droop characteristics or a
distributed voltage control in both the power flow algorithm and in the transient stability models allows to simulate the
steady-state results of the dynamic simulation by means of power flow software algorithms.

©
c 2012
2011 Published by Elsevier
Published by Ltd. Selection and/or peer-review under responsibility of SINTEF Energi AS.
ElsevierLtd.
Open access under CC BY-NC-ND license.
Keywords: VSC HVDC, Multi-terminal HVDC, converter control, DC voltage droop.

1. Introduction

In recent years, the power industry in Europe is showing ever increasing interests in transmission
schemes based on High Voltage Direct Current (HVDC) systems. Especially the Voltage Source Converter
(VSC) HVDC technology has good prospects for an extension to so-called multi-terminal configurations.
The DC side behaves as a voltage source, making power reversal quite straightforward when compared to
the Current Source Converter (CSC) technology. Although current day VSC HVDC schemes are all point-
to-point connections, the operation principles can be extended to a multi-terminal HVDC (MTDC) system.
In recent years, significant research efforts has been put on the modeling and control of VSC MTDC systems
as well as interactions with the AC power systems, addressing steady-state interactions using power flow
software [1, 2], as well as dynamic interactions by means of simulations in the time domain [3, 4, 5].
This paper discusses the modeling and control of VSC MTDC systems and provides a link between
power flow models and the steady-state operation points of transient stability models. Emphasis is put on
the interactions in the DC system. Section 2 discusses the operation principles of VSC HVDC converters,
as well as recent trends in converter topologies. Sections 3 and 4 respectively discus the steady-state and
transient stability models. Finally, section 5 discusses both the steady-state and dynamic interactions by
means of simulation results.

1876-6102 © 2012 Published by Elsevier Ltd. Selection and/or peer-review under responsibility of SINTEF Energi AS.
Open access under CC BY-NC-ND license. doi:10.1016/j.egypro.2012.06.093
124 Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130

Pdc
Phase
Ss reactor S c

Filter
Converter

Fig. 1: VSC HVDC converter station.

2. VSC Converter operation and control

In a interconnected AC/DC system, the converters form the connections between the DC systems on the
one hand and the AC systems on the other hand. Fig. 1 shows the main components of a converter station
connected to a symmetrically grounded monopolar transmission scheme. Contrary to the thyristors used
in CSC HVDC technology, the IGBTs in the VSC converters are self-commutated and do not rely on the
AC system for commutation. It is therefore possible to connect the VSC converters to existing networks
or to start up a remote grid, e.g. in a wind farm, whereas CSC HVDC can only be connected to strong
AC networks or need an external voltage source for communication when a connection to a wind farm is
considered.
The VSC converters synthesize an AC voltage waveform using a two-level or a multi-level approach.
Commercially, these products are available as HVDC Light [6], HVDC PLUS [7] and HVDC MaxSine [8].
The first generations of the HVDC Light technology have been using Pulse Width Modulation (PWM) and
a two-level or neutral-point-clamped three-level converter topology, whereas the new converters use a so-
called Cascaded Two-Level Converters (CLT) topology [9]. The HVDC PLUS technology uses multilevel
switching and is based on the Multi-modular Converter (MMC) approach. The HVDC MaxSine technology
uses a hybrid converter concept, with multi-level full H-bridge switching circuits in series with a large num-
ber of IGBTs, comparable to the two-level topology. The series cascaded multi-level converter provides a
wave shaping function.
Contrary to the two-level topology, all recent developed converter schemes have distributed DC capaci-
tances in the submodules. Dependent on the topology used in the submodules, the converters can either
block DC fault currents or rely on an external DC or AC breaker to disconnect in case of a fault on the
DC side. Whereas the two-level and three-level topologies can be accurately represented by grouping the
cascaded IGBT switches, research on how to accurately model the new multi-level topologies in EMTP-
software is ongoing [10].
The earlier two- or three-level schemes use AC filters to remove the high frequency content in the AC voltage
waveforms due to the PWM scheme (Fig. 1). In the more recent multilevel schemes, the filter requirements
are heavily reduced or even eliminated. When addressing the majority of AC/DC system interactions, in
steady-state or dynamically, and under the assumption that the switching behavior is not of particular inter-
est to the problem, the converters can be modeled as a controllable voltage behind a phase reactor.
With respect to the AC or DC grid, each VSC can exhibit a number of different control functions. Due to
the decoupled current control, further discussed in section 4, the active and reactive power can be controlled
independently since the two orthogonal dq-current components can be controlled independently.
With respect to the current component linked with the active power, different control functions can be
implemented:
1. Pac constant: The converter has a constant active power injection into the AC grid.
2. Pdc constant: The converter has a constant active power injection into the DC grid.
3. Udc constant: The current order is changed to control the DC bus voltage Udc at the converter terminal
to a constant value.
4. Udc droop: Dependent on the actual value of the DC bus voltage Udc , the current order is changed.
Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130 125

U s1,1 PQ PV U s2,1
AC 2
AC 1 U s1,2 PV DC PQ U s2,2

U s1,n PV
PQ U s3,1 AC 3

Fig. 2: AC/DC power flow: Representation of converters in the AC power flow.

Dependent on the variable chosen, a linear droop relation can be defined between DC bus voltage and
the following quantities:
a) Udc − Idc droop: The DC current reference is changed.
b) Udc − Pdc droop: The DC power reference is changed.
c) Udc − Pac droop: The AC power reference is changed.
Using existing control concepts from two-terminal schemes, the Udc − Pac droop option seems the most
straight-forward option. From a system’s point of view, the Udc − Idc droop relation is the one that is directly
linked to the voltage dynamics in the DC system.

With respect to the reactive current component, the following control options can be implemented.
1. Constant Q: The converter has a constant reactive power injection Q s into the AC grid.
2. Constant U: The converter adapts the reactive power injection to obtain a constant AC bus voltage
magnitude U s .
When the converter is connected to a remote offshore wind farm, where no external voltage source is
available, the converter controls the AC grid voltage magnitude and frequency.

3. Steady-state modeling

Depending on the outer control function implemented in the converter control loop, the steady-state
interaction with the AC and DC system has to be modeled differently. This section primarily focuses on
the representation of the converters and the resulting model of the DC grid power flow algorithm. More
information on the interaction with the AC system and details on the power flow implementation can be
found in [2, 11].
With respect to the AC power flow, the VSC stations can be modeled by including them as PV or PQ
nodes, as graphically depicted in Fig. 2. When under constant Pac control, the active power P s injected or
withdrawn from the AC grid is known. For the other three control options, an initial estimate is needed to
start the iteration process. The initial estimate P(0)
si can be formulated as:




⎪ P∗si Pac constant



⎨ −P∗dci Pdc constant
P(0) =⎪
⎪  , (1)
si ⎪

⎪ − nj=2 P(0) Udc constant

⎩−P
sj
or P
dc,0i s,0i Udc droop

with the DC slack bus (Udc constant) the first bus, assuming a DC slack bus to be present. The actual value
of P0i used, depends on whether the droop is implemented as a power-voltage or current-voltage droop, as
126 Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130

defined in the previous section.


After solving the AC grid power flow, the DC powers can be found using

Pdci = −Pci − Plossi , (2)

with Pci the converter side power (behind the converter reactor).

The different control strategies implemented can be mathematically represented in the DC grid power
flow algorithm by striving to achieve convergence of the controlled quantities to their reference values. The
DC grid power flow equations in a monopolar symmetrically grounded scheme can be written as

n
Idci = Ydci j · (Udci − Udc j ), (3)
j=1
ji

n
Pdci = 2 Udci Ydci j · (Udci − Udc j ). (4)
j=1
ji

with Ydci j equal to 1/Rdci j . In case of a Udc − Idc droop, the current injected by the voltage droop controlled
buses, can be written as
1
Idci = Idc,0i − (Udci − Udc,0i ). (5)
ki
Similarly, In case of a Udc − Pdc droop, the DC power injected, can be written as
1
Pdci = Pdc,0i − (Udci − Udc,0i ). (6)
ki
In case of an AC power based droop, the expression becomes similar to (6), but the losses in the converter
station have to be taken into account.
In its most general format, in case of both U − I and U − P droop controls implemented on different
converters, a vector with unknowns X dc can be defined,

X dc = [ Pdc1 , Pdc2 . . . Pdck , Idc,0k+1 . . . Idc,0l , Pdc,0l+1 . . . Pdc,0m , 0 . . . 0 ]T , (7)




 
 
 

slack P−control U − I droop U − P droop outage

with the first converter set to DC voltage control (slack), the subsequent k − 1 converters set to active power
control (either constant Pac or Pdc ) and the remaining operating converters controlling the DC voltage by
means of a droop control.
Using this vector of unknowns X dc , the DC power flow problem can respectively be rewritten as (8) to
be solved with a Newton-Raphson method:
( j)
∂X dc ΔU dc ( j)
U dc · = ΔX dc ( j) . (8)
∂U dc U dc

with the mismatch vector ΔX dc ( j) defined as


⎧ (k)


⎪ Pdci − Pdci (U dc ( j) ) ∀i : 2<i≤k



( j) ⎨ Idc,0i − Idc,0i (U dc ( j) ) ∀i : k≤i≤l
ΔXdc =⎪
⎪ . (9)
i ⎪

⎪ Pdc,0i − Pdc,0i (U dc ( j) ) ∀i : l≤i≤m

⎩ −P (U ( j) ) dci dc ∀i : m<i≤n

Idc,0i (U dc ( j) ) and Pdc,0i (U dc ( j) ) can be expressed by rewriting (5) and (6) in terms of respectively Idc,0i and
Pdc,0i .
Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130 127

u sq
u∗cq ucq + − icq
1 1
1+τσ ·s Rc +Lc ·s

Δuq
ωL

−ωL
Δud
u∗cd −
1 ucd + 1
icd
1+τσ ·s Rc +Lc ·s

Fig. 3: Transient stability converter model.

AWU AWU
u sq
i∗cq   + u∗cq i∗cd   u∗cd
+ + + +
Ki 1 + 1
τi ·s Ki 1 + 1
τi ·s
− + − +
icq Δucq |ucq |∗ ≤ ucqlim icd Δucd |ucd |∗ ≤ ucdlim

(a) icq current controller (b) icd current controller

Fig. 4: Decoupled inner current controllers.

4. Transient stability modeling

Accurately EMTP models of the converters as addressed in section 1 are especially of interest when
detailed studies of the DC system dynamics and interactions have to be undertaken. When addressing
interactions with large scale AC power system, a transient stability model captures the events of interests
in AC power system dynamics while still revealing the necessary details with respect to the DC system
interactions. These details of the models form a well balanced trade-off between modeling complexity and
computational burden.
From a transient stability point of view, the converter can be modeled in a dq-reference frame as depicted in
Fig. 3. The first order system with time constant τσ in Fig. 3 represents the time required for the conversion
of the reference voltage to the output voltage of the converter due to the converter power electronics [5]. The
dynamics of the phase-locked loop (PLL) have been neglected and the grid voltage is oriented according to
the q-axis.
Fig. 4 depicts the inner current control loops of the controller. The values of the voltage limits ucdlim and
ucqlim and the limits in the anti windup (AWU) scheme depend on the value of the DC voltage udc on the bus.
Priority has to be given to the components in uc formed by the voltage decoupling terms Δucd and Δucq and
the contribution due to the grid voltage u sq .
Fig 5 depicts different control structures for the outer q-control loop. As the grid voltage U s is oriented
according to the q-axis, the q-component is related to the active component of the converter current. It is
either possible to control the active power injection (Fig. 4(a)), to control the DC voltage to a constant
value using a PI-controller (Fig. 4(b)) or to control the DC voltage by means of a voltage droop (Fig. 4(c)),
either using a power or current based voltage droop. The current limits ±icdlim and ±icqlim are related to the
maximum current capability of the converter. The d and q-limits are therefore dependent on each other and
128 Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130

icqlim icqlim

P∗s +   i∗cq u∗dc +   i∗cq


KP 1 + 1
τP ·s Kdc 1 + 1
τdc ·s
− −
Ps udc
−icqlim −icqlim
(a) Constant P s controller (b) ConstantUdc controller

udc

Udc droop ΔP s icqlim


+   i∗cq
P∗s +
KP 1 + 1
τP ·s

Ps
−icqlim

(c) Udc droop controller

Fig. 5: Outer active power controllers.

priority can be given to active power or reactive power. Alternatively, the converter can keep working with
the same power factor when the current is activated.
With respect to the d-control loop, the converter can either control the reactive power injected into the AC
grid or keep up the AC grid voltage. Similar control structures to Figs. 4(a) - 4(b) can thus be depicted for the
reactive power component of the converter current. The steady-state behavior of the converters with respect
to the AC and DC system depends on the outer set-points and/or limits hit during the dynamic simulations.
When using the steady-state behavior of the DC voltage control in e.g. contingency analysis, the converter
limits and droop characteristics have to be implemented in line with the actual implementation in the control
loops discussed in this section.

5. Simulation results

When properly modeled, the results from power flow studies are in line with those that result from the
dynamic converter control, as discussed in this section. Both steady-state and transient simulations have
been carried out on a 4-terminal test system. A MATPOWER implementation using the approach from [2]
and the model presented in this paper has been used to obtain the power flow solution. The transient model-
ing has been performed with MatDyn [12], an open-source toolbox for power system dynamic simulations,
using the models described in the previous section. A DC current based droop as addressed in section 3 has
been implemented in the power flow package. Converter filters and losses are not included.
All outer q-controllers in the transient simulation are based on the droop implementation shown in 5(c),
using a current based droop. The converter model and inner current controllers are based on Figs. 3 and 4.
The DC lines have been modeled as PI-equivalent cable models, with the inductance of the cable neglected.
All AC grids have been modeled as infinite bus systems.
Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130 129

1.000 0.995 1.010 1.009


0.880 0.480 0.478 0.875 0.717 0.073 0.073

0.277

0.524
1 2 1 2

0.397

0.073
3 4 3 4

0.399

0.073
0.276

0.521
0.417 0.417 0.961 0.248

0.140 0.141 0.440 0.441

0.998 0.999 1.006 1.009


(a) Normal operation (b) Outage of converter 2

Fig. 6: Power flow results before and after outage of converter 2. Legend: → Active power (p.u.) and
voltage (bold) (p.u.).

1 1 1-2
2 1-3
3 0.2
1-4
Active power P s (p.u.)

Line currents icc (p.u.)

0.5 4 2-4
3-4

0 0

−0.5
−0.2
−1
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.00 0.05 0.10 0.15 0.20 0.25 0.30
Time t (s) Time t (s)

(a) (b)

1.02
DC Voltage udc (p.u.)

1.01

1 1
2
3
4
0.99
0.00 0.05 0.10 0.15 0.20 0.25 0.30
Time t (s)
(c)

Fig. 7: Dynamic interactions of converters in the DC grid after outage of converter 2: (a) Active power P s
injected into the AC grid, (b) Currents in the DC lines icc and (c) DC voltage udc .
130 Jef Beerten and Ronnie Belmans / Energy Procedia 24 (2012) 123 – 130

Fig. 6 shows the results of the steady-state analysis before and after a outage of converter 2 in the
4-terminal, monopolar symmetrically grounded MTDC system. As expected, the DC voltage and current
droop operation points change, as reflected by the results. Fig. 7 shows the results of the dynamic analysis.
Due to the selection of power and voltage base, the DC line currents in the symmetrically grounded system
are about half of the line powers in Fig. 6. With droop settings and an implementation similar in the power
flow and transient model, the results of the power flow analysis are in line with the steady-state results of
the dynamic simulations.
It is clear from the results that, when properly modeled, the AC/DC power flow algorithm can be used
to analyze the steady-state interactions of the droop-controlled converters. As addressed in [11], this also
impacts the power flows in the AC systems.

6. Conclusion

In this paper, the steady-state and dynamic modeling of VSC MTDC systems has been discussed. The
implementation of the voltage droop characteristics in steady-state power flow algorithms allows to extend
contingency analyses to DC grids and to study the effects of the droop control and the individual droop
values of each converter on the post-disturbance power flows in both the AC and DC system. The transient
model allows to study the dynamic interactions of the converters and the effect of the individual droop
values. Similarly, the transient model can be included in an AC transient stability program, allowing to
study the dynamic interaction of the AC and DC system.

Acknowledgement

Jef Beerten is funded by a research grant from the Research Foundation – Flanders (FWO).

References
[1] A. Pizano-Martinez, C. R. Fuerte-Esquivel, H. Ambriz-Perez, E. Acha, Modeling of VSC-based HVDC systems for a Newton-
Raphson OPF algorithm, IEEE Transactions on Power Systems 22 (4) (2007) 1794–1803.
[2] J. Beerten, S. Cole, R. Belmans, Generalized steady-state VSC MTDC model for sequential AC/DC power flow algorithms, IEEE
Transactions on Power SystemsAccepted for publication.
[3] L. Zhang, L. Harnefors, H.-P. Nee, Modeling and control of VSC-HVDC links connected to island systems, IEEE Transactions
on Power Systems 26 (2) (2011) 783–793.
[4] T. M. Haileselassie, K. Uhlen, J. O. Tande, O. Anaya-Lara, Connection scheme for north sea offshore wind integration to UK and
Norway: Power balancing and transient stability analysis, in: Proc. IEEE Trondheim PowerTech, 2011, pp. 1–5.
[5] S. Cole, J. Beerten, R. Belmans, Generalized dynamic VSC MTDC model for power system stability studies, IEEE Transactions
on Power Systems 25 (3) (2010) 1655–1662.
[6] P. Haugland, It’s time to connect - technical description of HVDC Light technology, Tech. rep., ABB (March 2008).
[7] K. Friedrich, Modern HVDC PLUS application of VSC in modular multilevel converter topology, in: Proc. IEEE Int Industrial
Electronics (ISIE) Symp, 2010, pp. 3807–3810. doi:10.1109/ISIE.2010.5637505.
[8] N. M. MacLeod, C. D. Barker, A. J. Totterdell, From concept to reality; the development of a multi-level VSC HVDC converter,
in: CIGRE 2011 Bologna Symposium, Bologna, Italy, 2011.
[9] B. Jacobson, P. Karlsson, G. Asplund, L. Harnefors, T. Jonsson, VSC-HVDC transmission with cascaded two-level converters,
in: Proc. CIGRE 2010, Paris, France, 2010.
[10] U. N. Gnanarathna, A. M. Gole, R. P. Jayasinghe, Efficient modeling of modular multilevel hvdc converters (mmc)
on electromagnetic transient simulation programs, IEEE Transactions on Power Delivery 26 (1) (2011) 316–324.
doi:10.1109/TPWRD.2010.2060737.
[11] J. Beerten, D. Van Hertem, R. Belmans, VSC MTDC systems with a distributed DC voltage control – a power flow approach, in:
Proc. IEEE PowerTech ’11, Trondheim, Norway, 2011.
[12] S. Cole, R. Belmans, Matdyn, a new matlab-based toolbox for power system dynamic simulation, IEEE Transactions on Power
Systems 26 (3) (2011) 1129–1136.