Power System Operation and Control-3
Power System Operation and Control-3
Blooms
Course
S. No Question Taxonomy
Outcome
Level
UNIT - I
Rs./h
Rs./h
Rs./h
The total load that these units supply varies between 90 MW and 1250 MW.
Assuming that all the three units are operational all the time, we have to
compute the economic operating settings as the load changes.
5 Consider two generating plant with same fuel cost and generation limits. These Analyze 1
are given by
For a particular time of a year, the total load in a day varies as shown in Fig.
5.2. Also an additional cost of Rs. 5,000 is incurred by switching of a unit
during the off peak hours and switching it back on during the during the peak
hours. We have to determine whether it is economical to have both units
operational all the time
6 The fuel inserts per all of plants I and II are given as Apply 1
F1= 0.1P21 + 40 P1+120 Rs/Hr
F2= 0.25P 22+30P2+150 Rs/Hr. Determine the economic operating schedule
and corresponding cost of generation if the max and min loading on each unit
is 100 MW and 25 MW and the demand is 180 MW and transmission losses
are neglected. If the load is equally shared by the both the units, determine the
saving obtained by loading the units as per equal incremental products and
cost.
7 A power system network with a thermal power plant is operating by four Apply 1
generating units. Determine the most economical unit to be committed to a
load demand of 8 MW. Also prepare the UC table for the load. The min and
max generating capacities and cost curve parameters of the units listed in a
tabular form are given.
8 A power system network with a thermal power plant is operating by four Analyze 1
generating units Determine the most economical unit to be committed to a
load demand of 10 MW. Also prepare the UC table for the load changes in
steps of 1 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
9 A power system network with a thermal power plant is operating by four Analyze 1
generating units Determine the most economical unit to be committed to a
load demand of 20 MW. Also prepare the UC table for the load changes in
steps of 4 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
A power system network with a thermal power plant is operating by four Apply 1
generating units Determine the most economical unit to be committed to a
10 load demand of 30 MW. Also prepare the UC table for the load changes in
steps of 8 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
11 For the system shown in figure, with bus 1 as reference bus with a voltage of Analyze 2
1.0V<00 pu, find the loss formula co-efficient if the branch currents and
impedances are: Ia=1.00+j0.15 p.u; Za=0.02+j0.15 p.u Ic =0.20-j0.05pu; Zc
=0.02+0.25pu If the base is 100 MVA, what will be the magnitudes of B –
coefficients in reciprocal MW?
12 (i) A generating station has a maximum demand of 50,000 kW. Calculate the Analyze 2
cost per unit generated from the following data.
Interest and
Depreciation = 12%.
(ii) (1) Define ‘‘diversity factor’’.
(2) Define ‘‘Plant use factor’’
13 The fuel cost functions in Rs/hr for two thermal plants are given by Apply 2
C1 =420+9.2P1+0.004P22 ; C2=350+8.5P2+0.0029P22
Where P1, P2 are in MW. Determine the optimal scheduling of generation if
the load is 640.82 MW. Estimate value of ʎ=12 Rs/MWhr. The transmission
power loss is given by the expression PL(p.u) =0.0346P21(p.u) +0.00643P22(p.u)
14 The fuel cost functions in Rs/hr for two thermal plants are given by Apply 2
C1 =420+9.2P1+0.004P22, 100<P2<200 ; C2=350+8.5P2+0.0029P22,
150<P3<500 Where P1, P2 are in MW. Determine the optimal scheduling of
generation if the load is 640.82 MW. Estimate value of ʎ=12 Rs/MWhr. The
transmission power loss is given by the expression P L(p.u) =0.0346P21(p.u)
+0.00643P22(p.u)
15 The IFC for two plants are dC1/dPG1=0.075 Pg1+18 Rs/hr ; Analyze 2
dC2/dPG2=0.08PG2+16 Rs/hr The loss coefficients are given as
B11=0.0015/MW, B12= -0.00004/ MW, B22 = 0.0032/ MW for ʎ=25 Rs/MWhr.
Find the real power generations, total load demand, and the transmission
power loss.
16 A system consists of two power plants connected by a transmission line. The Analyze 2
total load located at a plant-2 is as shown in below. Data of evaluating loss
coefficients consists of information that a power transfer of 100 MW from
station-1 to station-2 results in a total loss of 8 MW. Find the required
generation at each station and power received by the load when ʎ of the
system is Rs. 100/MWhr. The IFCs of the two plants are given by
dC1/dPG1=0.12PG1+65 Rs/MWhr ; dC2/dPG2=0.25PG2+75 Rs/MWhr
17 For above problem with 212.5 MW received by the load, find the savings in Analyze 2
Rs/hr obtained by co-coordinating the transmission losses rather than
neglecting in determining the load division between the plants
18 Determine the incremental cost of received power and the penalty factor of the Apply 2
plant shown, if the incremental cost of production is dC 1/dPG1=0.1PG1+3.0
Rs/MWhr.
19 Assume that the fuel input in Btu per hour for units 1 and 2 are given by Apply 2
C1 =(8PG1+0.024P2G2+80)10^6 ; C2=6PG!+0.04P2G2+120)10^6
The maximum and min loads on the units are 100 and 10 MW, respectively.
Determine the min cost of generation when the following load is supplied. The
cost of fuel is Rs.2 per million Btu.
20 Two power plants are connected together by a transmission line and load at Apply 2
plant-2. When 100 MW is transmitted from plant-1, the transmission loss is
100 MW. The cost characteristics of two plants are
C1 =0.05P\2G1+13PG1; C2=0.06P2G2+12PG2
Find the optimum generation for ʎ=22,ʎ=25 and ʎ=30.
UNIT - II
Rs./h
Rs./h
Rs./h
The generation limits of the units are
The total load that these units supply varies between 90 MW and 1250 MW.
Assuming that all the three units are operational all the time, we have to
compute the economic operating settings as the load changes.
5 Consider two generating plant with same fuel cost and generation limits. These Analyze 1
are given by
For a particular time of a year, the total load in a day varies as shown in Fig.
5.2. Also an additional cost of Rs. 5,000 is incurred by switching of a unit
during the off peak hours and switching it back on during the during the peak
hours. We have to determine whether it is economical to have both units
operational all the time
6 The fuel inserts per all of plants I and II are given as Apply 1
F1= 0.1P21 + 40 P1+120 Rs/Hr
F2= 0.25P 22+30P2+150 Rs/Hr. Determine the economic operating schedule
and corresponding cost of generation if the max and min loading on each unit
is 100 MW and 25 MW and the demand is 180 MW and transmission losses
are neglected. If the load is equally shared by the both the units, determine the
saving obtained by loading the units as per equal incremental products and
cost.
7 A power system network with a thermal power plant is operating by four Apply 1
generating units. Determine the most economical unit to be committed to a
load demand of 8 MW. Also prepare the UC table for the load. The min and
max generating capacities and cost curve parameters of the units listed in a
tabular form are given.
8 A power system network with a thermal power plant is operating by four Analyze 1
generating units Determine the most economical unit to be committed to a
load demand of 10 MW. Also prepare the UC table for the load changes in
steps of 1 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
9 A power system network with a thermal power plant is operating by four Analyze 1
generating units Determine the most economical unit to be committed to a
load demand of 20 MW. Also prepare the UC table for the load changes in
steps of 4 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
10 A power system network with a thermal power plant is operating by four Apply 1
generating units Determine the most economical unit to be committed to a
load demand of 30 MW. Also prepare the UC table for the load changes in
steps of 8 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
11 Let us consider a generating station that contains a total number of three Analyze 1
generating units. The fuel costs of these units are given by
Rs./h
Rs./h
Rs./h
The total load that these units supply varies between 80 MW and 1260 MW.
Assuming that all the three units are operational all the time, we have to
compute the economic operating settings as the load changes.
12 Consider two generating plant with same fuel cost and generation limits. These Analyze 1
are given by
For a particular time of a year, the total load in a day varies. Also an additional
cost of Rs. 6,000 is incurred by switching of a unit during the off peak hours
and switching it back on during the during the peak hours. We have to
determine whether it is economical to have both units operational all the time
13 The fuel inserts per all of plants I and II are given as Apply 1
F1= 0.21P21 + 30 P1+122 Rs/Hr
F2= 0.28P 22+20P2+155 Rs/Hr. Determine the economic operating schedule
and corresponding cost of generation if the max and min loading on each unit
is 100 MW and 25 MW and the demand is 180 MW and transmission losses
are neglected. If the load is equally shared by the both the units, determine the
saving obtained by loading the units as per equal incremental products and
cost.
14 A power system network with a thermal power plant is operating by four Apply 1
generating units. Determine the most economical unit to be committed to a
load demand of 9 MW. Also prepare the UC table for the load. The min and
max generating capacities and cost curve parameters of the units listed in a
tabular form are given.
15 A power system network with a thermal power plant is operating by four Analyze 1
generating units Determine the most economical unit to be committed to a
load demand of 12 MW. Also prepare the UC table for the load changes in
steps of 2 MW starting from the min and max generating capacities and cost
curve parameters of the units listed in a tabular form are given.
UNIT - III
2 500 4%
characteristics. The units are operating in parallel, sharing 900 MW at a
nominal frequency. Unit 1 supplies 500 MW and unit 2 supplies 400 MW at
60 Hz. The load is increased by 90 MW.
(a) Assume there is no frequency dependent load i,e., B=0. Find the steady
state frequency deviation and new generation on each unit.
(b) The load varies 1.5 % for every 1 % change in frequency i.e., B= 1.5. Find
the steady state frequency deviation and new generation on each unit.
5 A Generator in single area load frequency control has the following Analyze 4
parameters: Total generation capacity = 2500 MW Normal operating load
=1500 MW Inertia constant=5 kW-seconds per kVA; Load damping constant,
B=1 %; frequency, f=50 Hz; and Speed regulation, R=2.5 Hz / p.u MW. If
there is a 1.5 % increase in the load, find the frequency drop
(a) without governor control
(b) With governor control.
6 A250MVA synchronous generator is operating at 1500 rpm, 50 Hz. A load of Apply 4
50 MW is suddenly applied to the machine and the station valve to the turbine
opens only after 0.35 sec due to the time lag in the generator action. Calculate
the frequency at which the generated voltage drops before the steam flow
commences to increase to meet the new load. Given that the valve of H of the
generator is 3.5 KW-s per KVA of the generator energy.
7 Two Generating Stations A And B have full load capacities of 250 and Analyze 4
100MW, respectively. The interconnector connecting the two stations has an
induction motor/synchronous generator of full load capacity 30 MW;
percentage changes of speeds of A, B and C are 4, 3 and 2 respectively.
Determine the load taken by plant C and indicate the direction of the power
flow.
8 A 750 MW generator has a speed regulation of 3.5%. If the frequency drops Analyze 4
by 0.1Hz with an Unchanged reference, determine the increase in turbine
power. And also find by how much the reference power setting should be
changed if the turbine power remains unchanged
9 A500MVA synchronous generator is operating at 1500 rpm, 50 Hz. A load of Apply 4
100 MW is suddenly applied to the machine and the station valve to the
turbine opens only after 0.5 sec due to the time lag in the generator action.
Calculate the frequency at which the generated voltage drops before the steam
flow commences to increase to meet the new load. Given that the valve of H
of the generator is 5 KW-s per KVA of the generator energy.
10 Two Generating Stations A And B have full load capacities of 350 and Apply 4
500MW, respectively. The interconnector connecting the two stations has an
induction motor/synchronous generator of full load capacity 40 MW;
percentage changes of speeds of A, B and C are 5, 4 and 2 respectively.
Determine the load taken by plant C and indicate the direction of the power
flow
11 Two areas A and D are interconnected. The generating capacity of area A is Apply 4
36000 MW and its regulating characteristic is 1.5% of capacity per 0.1 Hz.
Area D has a generating capacity of 400 MW and its regulating characteristic
is 1% of capacity per 0.1 Hz. Find each area's share of a +400 MW disturbance
(increase in load) occurring in area D and the resulting tie- line flow.
12 Find the static frequency drop if the load is suddenly increased by 25 MW on a Analyze 4
system having the following data:
Rated capacity Pr=500MW ; operating load P D=250 MW
Inertia constant H=5s ; Governor regulation R=2 Hz p.u.MW
Frequency f= 50 Hz. Also find the additional generation.
13 Two areas of a power system network are interconnected by a tie-line, whose Analyze 4
capacity is 250MW, operating at a power angle of 450. If each area has a
capacity of 2000 MW and the equal speed regulation of 3 Hz/P.u MW,
determine the frequency of oscillation of the power for step change in load.
Assume that both areas have the same inertia constants of H = 5 sec. If a step
load change of 100MW occurs in one of the areas determine the change in tie-
line power.
14 Two power systems, A and B, having capacities of 3000 and 2000 MW, Analyze
Apply 4
respectively, are interconnected through a tie-line and both operate with
frequency-bias-tie-line control. The frequency bias for each area is 3 % of the
system capacity per 0.1 Hz frequency deviation. If the tie-line interchange for
A is set at 100 MW and for B is set (incorrectly) at 200 MW, calculate the
steady state change in frequency.
15 Two control areas have the following characteristics: Apply 4
Area-1: Speed regulation = 0.2 p.u ,Damping coefficient = 0.8 p.u ,Rated
MVA = 1500
Area-2: Speed regulation = 0.25 p.u, Damping co-efficient = 0.9 p.u, Rated
MVA = 500
Determine the steady state frequency change and the changed frequency
following a load change of 120MW occurs in area-1. Also find the tie-line
power flow change.
16 The two area system has the following data: Analyze 4
Capacity of area 1, Pr1 =1000 MW,
Capacity of area 2, Pr2 =2000 MW,
Nominal load of area 1, PD1=500 MW
Nominal load of area 1, PD1=1500 MW
Speed regulation of area 1=4%
Speed regulation of area 2=3%
Find the new steady state frequency and change in the line ow for a load
change of area 2 by 125 MW. For both the areas each percent change in
frequency causes 1 percent change in load. Find also the amount of additional
frequency drop if the interconnection is lost due to certain reasons.
17 Explain the state variable model of two area load frequency controller with Analyze 4
integral action. Two control areas connected by a tie line have the following
characteristics.
Area 1 Area 2
R=0.01 p.u R=0.02 p.u
D=0.8 p.u D=1.0 p.u
Base MVA=2000 Base MVA=500
A load change of 100 MW (0.2 p.u) occurs in area 1. What is the new steady
state frequency and what is the change in the tie own? Assume both areas were
at nominal frequency (60 Hz) to begin.
18 Two generators rated 250 MW and 500 MW are operating in parallel. The Apply 4
droop characteristics are 4% and 6% respectively. Assuming that the
generators are operating at 50 HZ at no load, how a load of 750 MW would be
shared. What is the system frequency? Assume free governor action
19 Two control areas have the following characteristics: Apply 4
Area-1: Speed regulation = 0.04 p.u ,Damping coefficient = 0.6 p.u ,Rated
MVA = 1300
Area-2: Speed regulation = 0.03 p.u, Damping co-efficient = 0.85 p.u, Rated
MVA = 500
Determine the steady state frequency change and the changed frequency
following a load change of 150MW occurs in area-1. Also find the tie-line
power flow change.
20 Two areas of a power system network are interconnected by a tie-line, whose Apply 4
capacity is 350MW, operating at a power angle of 450. If each area has a
capacity of 3000 MW and the equal speed regulation of 6Hz/P.u MW,
determine the frequency of oscillation of the power for step change in load.
Assume that both areas have the same inertia constants of H = 5 sec. If a step
load change of 120MW occurs in one of the areas determine the change in tie-
line power.
UNIT - V
2 Find the rating of synchronous compensator connected to the tertiary winding Analyze 5
of a 132 kV star connected, 33 kV star connected, 11 kV delta connected three
winding transformer to supply a load of 66 MW at 0.8 p.f. lagging at 33 kV
across the secondary. The equivalent primary and secondary winding
reactances are 32 ohms and 0.16 ohms respectively while the secondary
winding reactance is negligible. Assume that the primary side voltage is
essentially constant at 132 kV and maximum of nominal setting between
transformer primary and secondary is1.1.
A 3-phase single circuit, 220kV, line runs at no load. Voltage at the receiving Apply 5
end of the line is 205kV. Find the sending end voltage, if the line has
3 resistance of 21.7ohms, reactance of 85.2ohms and the total susceptance of
5.32X10-4 mho. The transmission line is to be represented by Pie-model.
4 Design a static VAR compensator for a low voltage distribution system with Apply 5
the following specifications:
System voltage = 440 V
System frequency = 50 Hz
Coil inductance, L=5.37 mH
The inductor saturates at 950 A and settles to a value of 1.8 mH at 1800 A.
Compensation is required over a range of -80 kVAR to +30 kVAR per phase.
5 The load at receiving end of a three-phase, over head line is 25.5 MW, power Analyze 5
factor 0.8 lagging, at a line voltage of 33 kV. A synchronous compensator is
situated at receiving end and the voltage at both the ends of the line is
maintained at 33 kV. Calculate the MVAR of the compensator. The line has a
resistance of 4.5 ohms per phase and inductive reactance (line to neutral) of 20
ohms per phase.
6 A 3-ph transmission line has resistance and inductive reactance of 25 and 90 Analyze 5
respectively. With no load at the receiving end a synchronous compensator
there takes a current lagging by 900, the voltage at the sending end is 145 kV
and 132 kV at the receiving end. Calculate the value of the current taken by the
compensator. When the load at the receiving end is 50 MW, it is found that the
line can operate with unchanged voltages at sending and receiving ends,
provided that the compensator takes the same current as before but now
leading by 900. Calculate the reactive power of the load.
7 A 440V, 3-Ø distribution feeder has a load of 100 KW at lagging p.f. with the Apply 5
load current of 200A. If the pf. is to be improved, determine the following:
i) Uncorrected pf. and reactive load
ii) New corrected pf. after installing a shunt capacitor of 75 KVAR.
8 A synchronous motor having a power consumption of 50 KW is connected in Apply 5
parallel with a load of 200KW having a lagging pf. of 0.8. If the combined
load has a pf. of 0.9, what is the value of leading reactive KVA supplied by the
motor and at what pf. is it working?
9 A 400V, 50Hz, 3-Ø supply delivers 200KW at 0.7 pf. lagging. It is desired to Apply 5
bring the line pf. to 0.9 by installing shunt capacitors. Calculate the
capacitance if they are (a) Star connected and (b) Delta connected.
10 A 3-Ø, 500HP, 50Hz, 11KV star connected induction motor has a full load Analyze 5
efficiency of 85% at lagging pf. of 0.75 and is connected to a feeder. If the p.f.
of load is desired to be corrected to 0.9 lagging, determine the following:
(a) Size of the capacitor bank in KVAR and
(b) Capacitance of each unit if the capacitors are connected in delta as
well as in star.
11 Find the rating of synchronous compensator connected to the tertiary winding Analyze 5
of a 132 kV star connected, 66 kV star connected, 11 kV delta connected three
winding transformer to supply a load of 33 MW at 0.8 pf. lagging at 33 kV
across the secondary. The equivalent primary and secondary winding reactance
are 32 ohms and 0.16 ohms respectively while the secondary winding
reactance is negligible. Assume that the primary side voltage is essentially
constant at 132 kV and maximum of nominal setting between transformer
primary and secondary is1.1.
12 A 3-phase single circuit, 230kV, line runs at no load. Voltage at the receiving Apply 5
end of the line is 210kV. Find the sending end voltage, if the line has
resistance of 21.7ohms, reactance of 85.25ohms and the total susceptance of
5.32X10-5 mho. The transmission line is to be represented by Pie-model.
13 Design a static VAR compensator for a low voltage distribution system with Apply 5
the following specifications:
System voltage = 420 V
System frequency = 50 Hz
Coil inductance, L=5.4 mH
The inductor saturates at 950 A and settles to a value of 1.8 mH at 1800 A.
Compensation is required over a range of -80 kVAR to +30 kVAR per phase.
14 The load at receiving end of a three-phase, over head line is 25.6 MW, power Analyze 5
factor 0.85 lagging, at a line voltage of 33 kV. A synchronous compensator is
situated at receiving end and the voltage at both the ends of the line is
maintained at 33 kV. Calculate the MVAR of the compensator. The line has a
resistance of 4.35ohms per phase and inductive reactance (line to neutral) of 22
ohms per phase.
15 A 3-ph transmission line has resistance and inductive reactance of 26 and 91 Analyze 5
respectively. With no load at the receiving end a synchronous compensator
there takes a current lagging by 900, the voltage at the sending end is 144 kV
and 133 kV at the receiving end. Calculate the value of the current taken by the
compensator. When the load at the receiving end is 50 MW, it is found that the
line can operate with unchanged voltages at sending and receiving ends,
provided that the compensator takes the same current as before but now
leading by 940. Calculate the reactive power of the load.