18 J Paraggio on 06 Aug 2008. t user personal user cence only. Stocage, eistibuton or use on network prohibited
Licensed to
AS/NZS 4284:2008
Australian/New Zealand Standard™
Testing of building facades
Fit published as ASINZS 4224 1005,
‘Second adton 2008
COPYRIGHT
© Standards Australia/Standards New Zealand
All rights are reserved. No part of this work may be reproduced or copied in any form or by
‘any means, electronic or mechanical, including photocoaying, without the written
permission ofthe publisher
Jointly published by Standards Australia, GPO Box 476, Sydney, NSW 2001 and Standards
New Zealand, Private Bag 2429, Wellington 6020
ISBN 0 7937 8619 7Licensed to Melinda J Paraggio on 06 Aug 2008, 1 user personal user licence only. Storage, dstibuton or use on network proibite.
ASINZS 428422008 2
PREFACE,
This Standard was prepared by the Joint Australia/New Zealand Standards Committee
BD-080 on Curtain Walls to supersede AS/NZS 4284:1995
The Standard is based on “Specification for the performance testing of building facades by
the SIROWET method” published by CSIRO, Division of Building, Construction and
Engineering now it is known as Manufacturing and Infrastructure Technology.
This Standards is derived from publication by the CSIRO on the method of facade testing
developed by the CSIRO and known as SIROWET. These publications are the following:
() ‘The SIROWET Rig, for testing weatherproofess of building facades’ by
N.G. Brown and E.R. Ballantyne, CSIRO Division of Building Research 1975,
(ii) ‘Specification for the performance Testing of Building Facade by the SIROWET
Method’, January 1990, Division of Building, Construction & Engineering, CSIRO—
Australia,
(iii) ‘The SIROWET Method; Specification for the Performance Testing of Building
Facades by the SIROWET Method’, June 1992 ISBN 0643 050930. This
specification (TR92/6) is effective from 30 June 1992 and supersedes (TR 90/2) dated
February 1990.
Consideration has been given to maintaining compatibility with NZS 4211:1985,
Specification for performance of windows and with Amendment No. 3 which converts the
carlicr working stress basis to limit state design requirements. It should be noted that the
water test pressure calculated in NZS 4211 Amendment No 3 is based on an alternative
serviceability wind pressure definition and not equivalent to serviceability pressure
determined in AS/NZS 1170.2.
‘The objective of this Standard is to provide those persons or organizations involved with
the specification, design, purchasing and construction of building facades with a method for
determining the performance of a building facade under wind and other optional loadings.
This test method is applicable to complete facades and is intended to assess the overall
system performance and interaction of the various facade components,
The Committee has made a number of significant changes and additions to the original
SIROWET method and these include the following:
(a) Change to limit state principles from working stress.
(b) Addition of optional seal degradation, seismic and building maintenance unit (BMU)
restraint tests,
(©) Aditi
‘Test pressures nominated in the Standard represent minimum default values that should be
applied to the test sample; however, selection of pressure values should be based on the
proposed usage of the structure, its exposure conditions and of the expected performance of
the facade.
n of several appendices, including a pro forma for test loads and limits‘Storage, distibution or use on network prohibited.
Licensed to Melinda J Paraggio on 06 Aug 2008. 1 user personal user lence on
3 ASINZS 4284:2008
For high rise residential and commercial building facades (buildings typically greater than
25 m) or at particularly exposed sites that incorporate curtain wall, strip windows, opening
window sashes, sliding doors, bifolding doors and the like, the methods of test described in
this Standard are applicable to prove performance of the system. Facade elements in these
situations can be subjected to the same environmental factors such as a continuous facade
on an office building—particularly wind-driven rain. The non-uniform nature of wind-
driven rain has led to the adoption in this Standard of the cyclic pressure water test and the
SIROWET method before it. Appropriate additional testing parameters, such as those
described in Table 2.2 of AS 2047—1999, Windows in buildings—Selection and
installation and AS 4420.3—1996, Windows—Methods of test, Method 3: Operating force
test as well as the torsional rigidity of building elements as covered in Clause 13 of
NZS 4211:1985 Specification for performance of windows, should also be considered for
relevant elements.
The term ‘informative’ has been used in this Standard to define the application of the
appendix to which it applies, An appendix is only for information and
guidance,ieence only. Storage, distibuion or use on network prohibited
Licensed to Melinda J Paregglo on 05 Aug 2008. 1 user personal us
ASINZS 428422008 4
1 SGOPBsasissassse
2 REFERENCED DOCUMENTS.
3. DEFINITIONS.
4 NOTATIONS...
S PRINCIPLE
6 APPARATUS...
7 SAMPLE PREPARATION
8 PROCEDURE... a
9 PERFORMANCE REQUIREMENTS:
10 TEST REPORT.
APPENDICES
A INFORMATION TO BE SUPPLIED BY SPECIFIER,
B SAMPLE PREPARATION........
C STRENGTH TEST AT ULTIMATE LIMIT STATE LOADING. 00.
D AIR INFILTRATION TESTING...
E WATER PENETRATION TESTING wc.
F SEISMIC TESTING wren
CONTENTS.Licensed to Melinda J Paragglo on 06 Aug 2008.1 user personal user licence ony. Storage, distribution or use Gn network prohibited
s ASINZS 4284:2008
STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND
Australian/New Zealand Standard
Testing of building facades
1 SCOPE
‘This Standard sets out a method for determining the performance of a representative
building facade under simulated conditions of loading. This Standard may be applied to all
types of facades including low- and high-rise, commercial, industrial and residential
buildings. Tests include displacement of the facade or prototype, water penetration and
structural integrity at ultimate limit state as well as optional tests, including BMU restraint,
seismic loading and seal degradation, This test method is applicable to prototype testing in
a test facility and on-site testing.
2 REFERENCED DOCUMENTS
The following documents are referred to in this Standard:
AS
1170 Structural design actions
1170.4 Part 4: Earthquake loads
ASINZS
1170 Structural design actions
1170.0 Part 0: General principles
1170.1 Part I: Permanent, imposed and other actions
1170.2 Part 2: Wind actions
NZS
1170 Structural design actions
1170.5 Part 5: Barthquake actions—New Zealand
aun Specification for performance of windows
ISO/IEC
17025 General requirements for the competence of testing and calibration
laboratories
3. DEFINITIONS
For the purpose of this Standard, the de!
3.1 BMU
ions below apply.
Building maintenance unit,
3.2, Framing members
The elements, such as mullions and transoms that support facade panels
3.3. Specifier
The person or party responsible for the facade Specification, nominating the use of this
Standard, the test sample, sequence, pressures and performance criteria.
3.4 Test facility
Bither a laboratory or any other facility registered by an accredited-testing agency in
accordance with ISOMEC 17025.
copyRIGHTLicenses to Melinda J Paraggio on 06 Aug 2008, 1 user personal user licence only. Storage, cistron or use on network prohibited
ASINZS 4284:2008 6
3.3. Uncontrolled water
Any leakage that is not contained and drained away during the water spray operation and
for $ min after the water spray has stopped during which time there is zero air pressure
differential on the facade,
4 NOTATION
The following symbols are used in this Standard
Dz = average of net end displacements, in millimetres
Dy = maximum displacement of member (generally at midspan), in millimetres
d, _ ~ seismic test displacement amplitude at the serviceability limit state, in millimetres,
4d, = seismic test displacement amplitude at the ultimate limit state, in millimetres
K, = deflection amplification factor, in millimetres
M = overturning moment, in kilonewton metres
n= number of cycles in the seismic test
Ry = structural response factor
S-_= span of member between points of support (transducers), in millimetres
T = period of the seismic cycle, in seconds
positive serviceability test pressure, in millimetres
5 PRINCIPLE
A sample of the building facade forms one face of an externally mounted chamber and is
sealed at its perimeter and then successively subjected to a structural test, a water
penetration test and a strength test.
NOTES:
1 Additional tests requested by the Specifier may include an air infiltration test, seismic loading
by in-plane displacements, a simulated seal degradation test and a BMU restraint load test,
2. For information on sample preparation, see Appendix B.
6 APPARATUS
‘The following apparatus is require
(@) An externally mounted chamber of a size to fit to the test sample of the building
facade. The fit shall be such as to seal the perimeter of the test sample against air and
water penetration.
NOTE: The use of an internally mounted pressure box is suitable for all static pressure tests
but may not adequately demonstrate water penetration in pressure-equalized systems in the
eyelie pressure test.
(b) A reversible air pump with controls to pressurize and depressurize the chamber
(©) Water sprays positioned so that when the sprays are in operation, the extemal face of
the test sample is covered with water.
(@) Displacement transducers capable of measuring deflections to an accuracy of
40.2 mm,
(@) An orifice plate or laminar flow elements or other airflow measuring device
calibrated to a traceable standard,
coPyRIGHTLicensed to Metinda J Paraggia on 06 Aug 2008.1 user personal user oan only. Storage, cisbutlon or use on rtwork prohibited
() A manometer capable of measuring air pressure to an accuracy of 2% of measuring
range. The manometer used during the cyclic water test shall have a fast response
time of at least 0.05 s.
7 SAMPLE PREPARATION
7.1 Test sample
The sample, with components, shall be representative both in size and shape of the facade
of the building. Vertical and horizontal movement joints shall be included in the test
sample, The joints shall be set on the sample within the design joint width including
tolerances.
‘The materials of the test sample (glass, aluminium, stone, reinforced concrete, sealants,
gaskets, etc.) shall be of the same type and size, have undergone the same method of
construction, and have the same details, flashing and anchorage as the building facade,
If not an actual on-site representative sample of the wall of the building, the test sample
shall be mounted and sealed into a simulated building frame in the same manner and by the
same fixings that are intended to attach the facade to the building structure. The support
frame shall be of similar stiffness to the supporting building structure
NOTE: For discussion of the supporting structure, refer to Appendix B.
Simulated floor slabs and spandrel beams shall be to actual depth if, for example, in curtain
walls, the air seal is connected to the slab. The internal finishes and linings shall be
installed where they contribute to the air seal, The air seal of the test sample shall be
continued to the air seal of the test chamber.
All framing members and other interconnected joints in the facade shall be sealed at the
sample boundaries.
NOTE: This is to minimize the effects that the surrounding construction will have on the test
performance of the sample.
All pressure equalization and drainage openings in the test sample shall be left open for the
duration of testing
‘NOTE: Transparent viewing panels (or other means of observation, such as an optical fibre probe)
should be provided so that the performance of the test sample in areas that are not readily seen
can he observed. They should be sized and sited to have a negligible minimal effect on the water
and structural performance of the test sample
7.2 Drawings
Shop drawings shall be supplied to the test facility before installation of the test sample.
These drawings shall include the following:
(a) Test sample elevation and vertical and horizontal sections.
(>) Typical details of framing members and facade panels (including intersections of
members).
(©) All fixing brackets and support details.
(@)_ Extent and type of sealants.
(e) _ Size, position and number of pressure equalization and drainage openings,
® Complete building in and blanking off details around the perimeter of the sample,
including the chamber details where significant to sample performance.
(2) Location of transparent viewing panels if used.
(bh) Method of installation,
(Location of displacement transducers.
COPYRIGHT
ASINZS 4284:2008Licensed to Melinda J Paraggio on 06 Aug 2008. 1 user personal user licence ony, Storage, distribution or use on network prohibited
ASINZS 42842008 8
8 PROCEDURE
8.1 Test sequence
BALL General
‘The sample shall be subjected to the tests in Items (a), (b), (d) and (g). The other tests shall
be carried out only if specified. The test sequence shall be as follows:
{a) Preliminary tests,
(b) Structural test at serviceability limit state.
(c) Air infiltration test.
(d) Water penetration test by static pressure followed by cyclic pressure test.
(2) Seismic test at serviceability limit state displacement (includes subsequent water
penetration test)
(f) BMU restraint test.
(g) Strength test at ultimate limit state
{h) Sein
ic test at ultimate limit state displacement.
(i) Seal degradation test.
B.L.2 Variation of test sequence or retesting
Where a variation of the test sequence is required, or if the test sample requires
modification to gaskets, joint seals or drainage details to enable it to pass either the air
infiltration ot the water penetration test, both tests shall be repeated in full. Before
retesting, the full positive and negative structural-test pressures (JV,) shall be applied to the
test sample for 2 min each.
8.2. Prelit
8.2.1 General
The tests in Clauses 8.2.2 and 8.2.3 shall be conducted before the structural test. Before
prototype testing the information required in Appendix A shall be submitted by the
Specifier.
inary tests
8.2.2 Static pressure
The test sample shall be subjected to the positive and negative SLS design wind pressures.
‘These pressures shall be maintained for 10 s at the positive requirement followed by 10's at
the negative requirement
8.2.3 Water
Preliminary water tests shall be conducted under static and cyclic pressures in accordance
with Clauses 8.5 and 8.6,
8.3. Structural test at serviceability limit state
8.3.1 Structural-iest pressures
The structural-test pressures (I¥,) are the positive and negative SLS design wind pressures.
They shall be calculated in accordance with AS/NZS 1170.0 and AS/NZS 1170.2. and
include all local pressure factors and internal pressures relevant to the location of the
sample on the building,
The minimum serviceability requirements shall be for an annual probability of exceedance
of 1/20 (0.05).
NOTE: Information on structural and strength test at ultimate limit state loading is given in
Appendix C.
COPYRIGHT9 ASINZS 4284:2008
8.3.2 Location of the displacement transducers
The framework to support the displacement transducers shall be rigidly fixed independent
of the test sample.
NOTE: The building frame (actual or simulated) is not part of the test sample,
Displacement readings shall be taken on the test sample at designated framing members,
facade panels and window locations that would represent actual structural movement
Displacements shall be taken, at least, at the ends of the framing member or between fixings
and at midspan, and also below and above (or to the left or right of) movement joints of
framing members and across the shortest span of the largest panel or glass pane included in
the test sample.
NOTE: Where members of facade framing systems are not simply supported over a single span,
the points of maximum defleetion are unlikely 10 fall midway between the support brackets
connecting the facade to the building. In these cases the points of maximum deflection should be
identified by structural analysis and displacement readings taken at these points
Sufficient displacement transducers shall be located at the fixing brackets so that any
differential movement between the various components and the support structure will be
identified.
The location of all displacement transducers shall be nominated or approved by the
Specifier
8.3.3 Pressure loading sequence
Displacements shall be measured at all pressure (positive) and suetion (negative) sequence
steps by calibrated displacement transducers.
The loading sequence during test (as shown in Figure 1) consists of three modes and shall
be as follows:
:
g
:
5
5
g
5
(2) An initial pressure differential equivalent to either the positive or the negative
structural-test pressure shall be applied against the external face of the test sample for
a period of 2 min which shall be taken as a settling/take-up period,
() The differential pressure shall be removed and the zero position of the transducers
recorded after 2 min of zero pressure (see Figure 1, zero stage Z1).
(©) Differential pressures in the same direction as in Item (a) shall then be applied to the
external face of the test sample in not less than five approximately equal steps, until
the pressure reaches the structural test loading. The pressure shall be held at each step
for at least | min before the displacements are recorded.
(4) ‘The differential pressure shall be removed and the zero position of transducers
recorded after 2 min of zero pressure (sce Figure 1, zero stage 22).
(c) The structural-test loading shall be applied again to the external face of the test
sample and maintained for at least I min, The differential pressure shall then be
reduced in the same number of steps as the increasing pressure regime ((see Item (c)).
The pressure shall be held at each step for at least | min before the displacements are
recorded. Also, the zero position of the transducers shall be recorded after 2 min of
zero pressure (see Figure 1, zero stage Z3).
(8 The procedure in Items (a) 10 (c), inclusive, shall be repeated using the opposite
structural test design loading,
(g) The procedure in Items (a) and (b) shall be repeated using the initial differential
pressure.
NOTE: Items (b) to (¢) are referred to as Mode 1, Item (f) as Mode 2 and Item (g) as Mode 3
Licensed te Melinda J Paraggio on 06 Aug 2008.1 user personal user ence ony. Si
COPYRIGHTLicensed to Melinda J Paraggla on 06 Aug 2008. 1 user personal user cence only. Storage, cstbuton or use on rework prohibited
ASINES 4284:2008 10
imal Ava
Asoo
Ra (4) A
: |
oe Avo
iz Fal z2| za 24 zs ze|_|zz
TIME, minutes
NOTE; The displacements used for deflectiom/span ratios are based on zer0 deflections at the reference stages
2) and 74. The reducing pressure steps fom 72 10 73 and from Z5 10 Z6 are optional
FIGURE 1 TYPICAL STRUCTURAL TEST SEQUENCE
8.3.4 Displacement measurement of spandrel panels
If the facade specification requires displacement measurements of spandrel panels which
form the exterior face of a spandrel box and the spandrel box is a pressure-equalizing
design, a separate test is required.
Deflection measurements taken of the spandrel panels during the structural test sequence
indicated above shall not be accepted as true readings of spandrel panel deflection, as the
spandrel panels may not be under full test load, due to the extent of pressure equalization of
the spandrel box chamber.
‘The spandre] panel measurement may be carried out immediately after the structural test
sequence has been completed, or any other time before the strength test at ultimate limit,
state pressure.
Holes shall be installed in the prototype in a location agreed with the testing officer (usually
in the back-pan), so that, when the test pressure is applied, the pressure difference will be
across the spandrel panel. These holes may be installed before testing and covered for other
tests,
Deflection transducers may be installed through the holes in the back-pan, to the internal
surface of the spandrel panel or to the external surface of the spandrel panel.
The loading sequence of structural loadings shall be repeated as shown in Figure 1, taking
deflection measurements of the spandrel panels. The test pressure for the spandrel panels,
may be reduced in accordance with the porosity provisions of AS/NZS 1170.2. During this
test, pressure readings shall be taken both inboard and outboard of the spandrel panel(s) for
Which deflection measurements are being taken, to ensure that the pressure differential
across the spandrel panel(s) is equal to the agreed spandrel test pressure
When the spandrel deflection measurements have been taken and this test is complete, the
holes shall be covered, so that the pressure difference in the spandrel box is applied across
the back-pan and the prototype is effectively restored to the in-service condition. The hole
covers shall be structurally contimuous with the member to which they are attached and any
sealant used in the covers is adequately cured before testing is resumed.
COPYRIGHTUcensed to Melinda J Paragsio on 06 Aug 2008.1 user personal ser licence ony. Storage, distbution oF use on network prohibited
u ASINZS 4284:2008
Calculation of deflection/span ratio
Where a framing member of the test sample is effectively supported at its ends only, its
midspan deflection and resultant deflection/span ratio under load shall be calculated. The
displacement for each transducer at the ends and midspan of the member and cach mode
(positive and negative) shall be reduced to a deflection and deflection/span ratio using the
relationship—
Deflection / span ratio is 1
where
S = span of member between points of support (transducers)
Dz = maximum displacement of member (generally at midspan)
Dz = average of net end displacements
The greater of the two deflections in positive and negative modes shall be used in the
calculation of the deflection/span ratio for the members and panels. Significant variations in
the ratios at the design pressure steps (that is either side of mid-mode steps) shall be noted
in the final report.
Mode | deflection readings shall be referenced to Z1 and Mode 2 deflection readings shall
be referenced to Z4
NOTE: When stack joints are involved in the case of unitized curtain wall mullions, the maximuin
displacement may vary from the midspan between the support and the stack joint, In such
instances it is recommended the transducer location for maximum displacement be checked with
the aid of structural analysis software or design charts (see Figures C1 and C2).
8.3.6 Calculation of successive member displacement
The successive displacement of a member is the zero air pressure displacement (relative to
the reading after initial take-up) measured during the structural performance test (refer to
Figure 1)—
(a) between maximum pressures in Mode 1 (stage 22);
(b) before take-up in Mode 2 (stage 23);
(©) after take-up in Mode 2 (stage 74);
(4) between maximum pressures in Mode 2 (stage 25);
(©) before take-up in Mode 3 (stage 26); and
(0) after take-up in Mode 3 (stage 27),
8.3.7 Calculation of maximum displacement
The maximum displacement in Mode! shall be referenced to Z1 and maximum
displacement in Mode 2 shall be referenced to Z4.
NOTE: Referencing of the made of displacement to the Z4 zero values provides the equivalent
member displacement as determined for Mode 1 while maintaining the successive member
displacement values ZI to 27.
8.4 Air infiltration test
8.4.1 Test pressure
‘The air infiltration test pressure shall be as specified or taken as +150 Pa and —150 Pa,
coPYRIGHTASINZS 428422008 2
8.4.2 Procedure
The total air infiltration rates through the test sample and the test enclosure shall be
determined by applying both positive and negative test pressures, No further testing shall be
required if the air infiltration rates determined on the combined test specimen and test
enclosure are less than the purchaser-specified air infiltration rate or the value in
Clause 9.3, and there is no requirement for actual infiltration rates through the test
specimen.
Where the total air infiltration rate is greater than the purchaser-specified air infiltration
rates or the value in Clause 9.3, or the purchaser/specifier requires actual air infiltration
rates, the face of the test sample shall be sealed airtight by covering it with an impervious
film. If this is not practicable, all joints, weepholes and glazing or sealant lines of the test
facade shall be sealed with air-impervious tape and the air infiltration rates for the
enclosure only determined. The air infiltration rates through the test sample shall be the
difference between the total and sealed airflow meter readings at both positive and negative
test pressures
NOTE: Air infiltration testing is described in Appendix D,
8.5 Water penetration test by statie pressure
8.5.1 Test pressure
The water penetration test pressure shall be nominated by the Specifier, or taken as the
greater of 300 Pa or 0.3
85.2 Procedure
oF use on network profited.
The test facade shall be subjected to water sprayed completely and continuously over the
exterior face of the test sample at a rate not less than 0.05 L/m’ s (3 L/m? min).
‘At the start of the test, the water spray shall operate for 5 min with zero air pressure
differential on the facade. This shall be followed by a further period of 15 min at the test
pressure. Observations of the internal surface of the facade shall be carried out during the
water spray operation and for 5 min after the water spray has stopped and there is zero air
pressure differential on the facade.
‘Any water appearing on the inside surfaces of the facade shall be recorded, with the extent
and, if possible, the source of leakage indicated.
8.6 Water penetration test by eyelic pressure
8.6.1 Test pressure
‘The water penetration test using cyclic pressure shall be carried out in three stages and shall
take into account the geographical location and exposure of the building and shall be
specified by the Specifier, or taken as the following:
(a) Stage Lesson 0,15 > W, 100.3 x W,
(b) Stage 2 oe sueunananeitatiininnnen D2 Wyt0 0.4 x Ws
(©) Stage 3 0.3 W, 10 0.6 * W
where
W, = positive serviceability test pressure. (Should I, pressure be less than
1000 Pa, use 1000 Pa instead of F, in this Clause.)
NOTE: Where buildings are located in Wind Regions B, C and D as defined in AS/NZSI170.2,
the test pressures as a function of the serviceability wind pressures (and velocities) should be
inereased in line with historic data for wind driven rain at the local area in question,
Licensed to Melinda J Paraggio on 06 Aug 2008.1 user personal user cence only. Storage, distibut
copyRiGHTLicensed to Melinda J Paraggio on 06 Aug 2008, 1 user personal user lence only. Storage, distrbution o use on network proibites
6 ASINZS 4284:2008
8.6.2. Procedure
This test shall be performed upon completion of the test for water penetration test by statie
pressure
Should the cyclic water penetration test not commence within 30 min of the static water
penetration test then immediately before the start of the cyclic test the exterior face of the
test sample shall be completely sprayed with water at a rate not less than 0.05 L/m’ s for
5 min with zero air pressure differential on the facade.
Water shall be applied continuously and completely cover the exterior face of the test
sample at a rate not less than 0.05 L/m’ s while a eyclic positive air pressure is applied to
the exterior face for a duration of not less than 5 min. The applied test pressure shall be
varied between the specified limits with a cycle time of 3 s to 3s
‘The cyclic pressure shall be recorded on a device capable of recording and graphically
displaying the variations in pressure.
NOTE: Water gauge manometers and other slow response pressure indicators are unsuitable for
this purpose
The air pressure differential shall be reduced to zero for 2 min between each stage with the
‘water spray still in operation. Observation of the internal surfaces of the facade shall be
carried out during the water spray operation and for $ min after the water spray has stopped
during which time there is zero air pressure differential on the facade.
‘The appearance of any water on the inside surfaces of the facade shall be recorded, with the
extent and, if possible, the source of leakage indicated.
NOTE: Further information on water penetration testing is given in Appendix E.
8.7 BMU restraint test
8.7.1 Test load
‘The load designated in this test shall be ultimate limit state and shall be specified by the
Specifier, taking into account the size and operation of the BMU,
NOTE: There may be regulatory requirements that will determine the magnitude of the test load
8.7.2. Procedure
The BMU restraint unit shall be fitted to a specified restraint point. A lanyard and clip or
other restraint system as specified for use shall be attached to the restraint and the other end
attached to a cable attached to a load cell reading device and this in turn attached to a cable
which is attached to a tensile loading device applying the required load. The load shall be
applied in three stages, as follows:
(a) The restraint shall be subjected to a tensile load applied orthogonally and horizontally.
to the sample, and applied for a minimum of 10 s.
(b) The restraint shall be subjected to a tensile load applied horizontally to the left of the
anchorage point in the plane of the sample, This load shall be applied for a minimum
of 10s.
(c) Stage (b) shall be repeated with the load directed to the right of the anchorage point.
8.8 Structural test at wl
sate limit state
8.8.1 Test pressures
The strength test pressures shall be the facade positive and negative ultimate limit state
wind pressures calculated in accordance with AS/NZS 1170.0 and AS/NZS 1170.2 and shall
include all local pressure factors and internal pressures relevant to the location of the
sample on the building.
coPYRIGHTance ony, Storage, dierbution or use on network prohibit,
Licensed to Melinda J Peragaio on 06 Aug 2008, 1 user personal user
ASINZS 4284:2008 u
8.8.2 Procedure
The test sample shall be subjected to positive and negative strength test pressures. Each
strength test pressure shall be maintained on the test sample for a period of 10 s.
The load period from zero to ultimate limit state pressure shall be 50 5 to 60 s.
‘The sample shall be inspected at the end of each of the positive and negative pressure
stages. Record all incidences of non-linear deflection and/or collapse
8.8.3 Spandrel panel
If the facade specification requires a structural test at ultimate limit state spandrel panels
shall be tested in a repeat structural test at ultimate limit state procedure. Follow the set-up
requirements indicated in Clause 8.3.4. Repeat the procedure indicated in Clause 8.8.2 with
pressure transducers which measure the pressure difference inboard and outboard of the
spandrel panels. The number of spandrel panels instrumented is to be agreed with the
involved parties before the test.
The structural test at ultimate limit state for the spandrel panels may be carried out either
before or after the structural test at ultimate limit state for the other prototype members and
components.
8.9 Seis
test
8.9.1 Test displacement
The sample shall be displaced in the plane of the facade sample for n eyeles at a period T,
for distance of 4d, or td, mm from the original setting position. ‘The values of n, 7 and d, ot
d, shall be specified and based on the serviceability and ultimate limit states appropriate to
the geographical region.
The appropriate values of d, at serviceability and dy at the ultimate limit state seismic
displacements shall be determined by the building structural designer.
8.9.2 Procedure
One of the reaction beams shall be selected by the Specifier as a seismic loading floor. This
beam shall be capable of sliding back and forth to simulate lateral seismic motion, The
facade support brackets shall be attached to the moveable beam.
Lateral displacements of the sample shall be measured as the relative displacement between
the lateral fixed support and moveable beam. The mechanism to move the beam shall be of
sufficient strength to react to the required test period.
Inspect and report the condition of the prototype after the completion of all the cycles.
Serviceability limit state displacement test is first carried out, followed by a eyclic water
penetration test, in accordance to Clause 8.6.
‘The ultimate limit state displacement test may be carried out before or after the ultimate
limit state structural test
NOTES
1 No water testis required after the seismic test at ultimate limit state displacements.
2 Further information on seismic testing is given in Appendix F
Seal degradation test
‘The Specifier shall designate areas of the sample where seals are to be removed or cut by
Knife to simulate long-term degradation of the sample. All changes to the sample shall be
reported, A cyclic water penetration test shall be carried out in accordance with Clause 8.6.
copyRiGHTLicensed to Melinda J Paraggio on 06 Aug 2008. 1 user personal user cence only. Storage, dstrbuton or use on network prohibited.
18 ASINZS 4284:2008
9 PERFORMANCE REQUIREMENTS
9.1 General
The performance requirements listed in the remaini
the absence of alternative performance requirements provided by the Specifier
12 sections of Clause 9 shall be used in
All components of the sample are required to remain structurally intact as detailed on test
sample drawings with no signs of visible damage or distortion following the structural
performance, air infiltration and water penetration tests,
9.2 Structural test at serviceability limit state
9.2.1 Deflection/span ratios
When tested to serviceability wind pressures and using the method of ealeulation described
in Clause 8.3.5, no framing members shall deflect by an amount greater than span/250 mm.
For mullions, the span shall be taken to be the distance between fixing positions, in
millimetres,
9.2.2 Successive member displacement
The successive member displacement calculated from Clause 8.3.6 shall not exceed
3.0 mm.
9.2.3 Maximum displacement
The maximum displacement of a framing member calculated from Clause 8.3.7 shall not
exceed 20 mm, or a lower figure specified in the facade specification
For frames greater than Sm between supports, the maximum frame displacement shall be
agreed with the Specifier, but not more than the limit described in Clause 9.2.1 (see
Figure C2, Appendix C).
9.3. Air infiltration test
Air infiltration for airconditioned buildings shall not exceed 1,6 Lim's.
NOTE: Ifthe total air infiltration of the sample and the test apparatus is less than the value given,
the sealing of the test sample may be omitted and the test report should quote the total air
infiltration reading of the sample and system, (Refer Appendix D.)
9.4 Water penetration test
Under static and cyclic pressures there shall be no leaks.
For both the static and cyclic water tests, a leak is considered to occur when one or more of
the following occur:
(a) Water appears on any inside Surface of the facade and is visible from an dccupied
space.
(b) Uncontrolled water appears on any inside surface of the facade.
(c)__ Water appears that is likely to wet insulation, fixtures and finishes.
(4) Water appears in other locations specified as unacceptable by the Specifier.
9.5. Seismic test at serviceability limit state displacement
The sample shall pass the eriteria set for the cyclic water penetration test (see Clause 8.6)
after the seismie test at the SLS displacements.
9.6 BMU rest
int test
After the load is released in cach step, any deformation of the sample at or near the loading
point shall be recorded, A failure shall be recorded if the BMU restraint becomes
unserviceable or separates from the sample,
‘COPYRIGHTLicensed to Melinda J Paraggio.on 06 Aug 2008, 1 user personal user licence nly. Storage, dstibutio or use on network prohibited
ASINZS 428422008, 16
9.7 Structural test at ultimate limit state
Under structural test at ultimate limit state there shall be no collapse of the test sample.
Collapse shal] mean any one or any combination of the following:
(a) Disengagement or partial disengagement of any framing member, facade panel or any
part thereof.
() Failure of any fixings that connect the facade to the building structure.
(©) Failure of any stop, locking device, fastener or support which eould allow an opening,
light to come open.
(4) Repeated breakage of glass resulting in loss of chamber pressure. Glass may only be
replaced once before the sample is deemed to have collapsed.
(©) Repeated cracking of glass which does not result in loss of chamber pressure. Glass.
may only be replaced twice before the sample is deemed to have collapsed.
‘Any permanent distortion of a panel shall be noted and documented in the report.
NOTE: At the ultimate limit state load the sample may suffer permanent deformation and might
not remain operational. This Clause is intended to protect people in the vicinity of the building
should a window collapse under extreme conditions
9.8 Seismic test at ultimate limit state displacement
The sample shall not collapse during or after the seismic test at ultimate limit state
displacements. Any damage to the seals, members or panels shall be recorded and noted in
the report. Collapse shall mean any one or any combination of the occurrences described in
Clause 9.1(a) to (4).
9.9 Seal degradation test
The sample shall be observed for water penetration after the nominated seals have been
altered,
‘NOTE: For domestic buildings in New Zealand it has been found that the removal of 10% of the
air seal is appropriate,
10 TEST REPORT
10.1, Preliminary test report
‘The test report can be a separate report from the official test report, or incorporated as part
of the official test report. All details of preliminary test(s) shall be included in the
preliminary test report, including full details of all modifications/rectifications carried out
‘on the facade test sample prior to the official test
10.2. Official test report
‘The report shall include the following:
(a) The name of the project, client and Specifier, sample designer/manufacturer and
installer as appropriate, as well as the time and date of the test, the test schedule, the
identification of official persons observing the testing, name, location and
accreditation of the testing facility and the testing officer with responsibility of
measuring and recording data and producing the test report, and reference to
preliminary test report(s) issued separately. Completed Appendix A form from the
Specifier and a summary of results
(b) A Certificate of Identification from the facade designer and manufacturer stating that
the facade test sample is a true representation of the facade to be erected on the
building and it incorporates identical materials and construction methods. The
Certificate shall also include the comprehensive list of drawings, which shall describe
the facade test sample, and included in the report.
COPYRIGHTsensed to Melinda J Paraggio on 06 Aug 2006. 1 user personal user lence only Storage, distribution or use on network prohibited.
©
@
(e)
(
(®
(hy
(i)
G)
()
a
(mn)
@)
" ASINZS 4284:2008
A general description of the facade test sample.
Drawings of the test sample showing modifications, if any.
Test sequence with pressures used in all test.
For the structural test, provide for each member—
(i) location of all transducers:
(ii) _ spans of relevant members, given as measured distances between transducers;
(iii) deflection/span ratios;
(iv) maximum displacement;
(v) a separate zero table, giving readings for Z1 to 27;
(vi) successive member displacement; and
(vii) a full set of readings in an appendix.
For the air infiltration test—
(i) the air infiltration through the test sample and the system for each of the air
infiltration test pressures; and
(ii) an estimation of the test accuracy, based on good laboratory practice.
For each of the static and eyclic water penetration tests full details of all leakages,
including position extent and timing,
Seismic test SLS displacements; the location of the moving support beam, damage to
seals, members or panels and changes in movement joint positions and/or sizes,
Ultimate limit state test; details of all permanent distortion and collapse.
Seal deyradation test; drawings and description of seals altered and observations
made during the test.
Details of the BMU restrai
after loading
its position on the sample and observations during and
Seismic test ultimate limit state; report as per seismic test SLS.
Reference to this Joint Australian/New Zealand Standard, i.e., AS/NZS 4284.
COPYRIGHTLicensed to Malinda J Paragglo on 06 Aug 2008. 1 user personal user leance only. Storage, dsinbuon or use on network prohibited
ASINZS 42842008 18
APPENDIX. A
INFORMATION TO BE SUPPLIED BY SPECIFIER
(Normative)
‘The Specifier shall complete this test request form for specific test pressures and limits
NOTE: Values specified in the Standard are defaults and the Specifier should refer to
Appendices B to F for discussion of the basis of some limits
COPYRIGHTnce ony. Storage, cstbution or use on network probed
Licensed to Metinds J Paragsio on 06 Aug 2008.1 user personal us
9 ASINZS 428422008
TEST REQUEST FORM
Project,
Client
Specifier
Sample designer/manufacturer:
Installer
Date of test requested
Test schedule required: (Cross out those Sections not required—a, b, ©, d and g are
mandatory to claim compliance with this Standard, AS/NZS 4284}
a—Preliminary b—Structural at SLS c—Air infiltration
d—Water at static and cyclic e—Seismic at SLS with water
‘—BMU restraint test
9—Strength at ULS Seismic at ULS |-Seal degradation
General description of test sample
Drawings of the test sample attached? Y/N
Certificate of Identification attached? Y/N
Position of any viewing panels for water test noted Y/N
COPYRIGHTLicensed! to Meknda J Paraggio on 06 Aug 2008.1 user personal user licence only. Storage, cstbuton or use on network prohibited
ASINZS 4284:2008, 20
SPECIFIC TEST REQUIREMENTS
Section Test Name Clause Required parameters
a Preliminary test 24
SLS pressure 82.2183
Sis) = a
Water static 82.3/8.5 | Static water test pressure Pa
Water—Cyclic 82.3/8.6 | Cyclic test pressure Stage Pa
8.2.3/8.6 _ | Cyclic test pressure Stage Pa
82.3186 | Cyclic test pressure Stage Pa
b Structural test at SLS | 8.3.2 Location of transducers noted on’
drawings? _YIN
23.3 Pressure steps?
Max. displacement? = mm
| Members or panels
Deflection/span limit ratio
© Air infitration test. | Test Pa
| pressure Pa
I Air infiltration limit = (ims)
d Waier test (static and | Pressure | Duration | Duration and spray intensity
cyclic) Pa) (mins)
Static 15 min, 0.05 Lim? s
Cyclic 1 5 min, 0.05 Lin? s
Gyclic 2 5 min, 0.05 Lim? s
Cyclic 3 5 min, 0.05 lms
‘Additional water penetration requirements?
e Seismic at SLS (Water test repeated after)
‘Support beam movement allowed =
Number of cycles =
Frequency of movemeni
f BMU restraint Test load across face of sample = __kN
Test load perpendicular to sample = _kN
a Strength at ULS Test Pa
pressure Pa
h Seismic at ULS
Support beam movement allowed = mm
Number of cycles =
Frequency of movement =
Hz
i Seal degradation
10% air seal removal? YIN
Describe seals to be altered
COPYRIGHT:
<
3
E
g
5
i
3
5
5
i
i
e
3
ASINZS 428822008 2
For a panelized or stick curtain wall system it is recommended that a sample width include
at least three adjoining wall panels, This will simulate two typical mullions and two edge
conditions. At the boundary of the prototype the restraint system used should be
representative of the actual restraint system of the sample being tested. Variation in the
degree of fixing of these restraints will influence the results of the test, Similarly, the
sealing and flashing details should be representative of actual conditions,
For curtain walls for multistorey buildings, it is recommended that two expansionistack
joints be tested (See Figure Bl),
The stiffness of the support system for the sample should be representative of the actual
support system, Acceptance of the stiffness of the support system proposed should form
part of the review by the Specifier.
Test rig
support
beam |
Storey
Expansion or height
paul slack joint 5
support Test rig -xpansion
bracket support joint
Mullion beam (at
|
Mullion Storey
Expansion or height
stack joint ante
support
brackets
Expansion
joint
(2) Panelized facade (b) Stick system facade
FIGURE B1 ATYPICAL CROSS-SECTION OF A BUILDING FACADE
INDICATING TWO INTERMEDIATE EXPANSION/STACK JOINTS.
Often no single panel of a building facade is representative of all the areas of the facade
that the Specifier requires to have tested. The test sample can be designed specifically to
include different areas of the facade within the test sample, such as comers, overhangs.
column junctions, and changes to materials.
‘The stiffness of the curtain wall mullions in the test sample will almost never be identical 1
the typical curtain wall on the actual building. The actual curtain wall mullion will have
different stiffness in the bottom and top two or three floors due to different start and end
(boundary) conditions. There will often also be floors of different heights and longer
mullions with extra added stiffeners and/or fixings.
COPYRIGHTLicensed to Malinda J Paraggio.on 06 Aug 2008, 1 user personal user cence aly. Storage, dstibution or use on network prohibited,
a ASINZS 4284:2008
APPENDIX B
SAMPLE PREPARATION
(Informative)
BL INTRODUCTION
The test is a method of assessment of a facade system that has been designed by a
competent person to meet the specified requirements of the Specifier. It is not an alternative
method of proving a facade system. This Appendix relates to the preparation of a prototype
test sample of the building facade. The two most important objectives in testing building
facades are to evaluate the performance of the sample under exposure to simulated
environmental conditions before production commences and to use the sample as an
opportunity for the manufacturer to evaluate the fabrication and installation of the sample
These objectives are based on the premise that the sample is a faithful representation of the
proposed design (ie., from drawings and design calculations) and, with the test
amendments, a sample of the wall that will be constructed on to the building within the
construction tolerances of the structural elements of the building.
This facade-testing Standard provides the method for testing the facade, using a full-scale
prototype of the wall under actual design conditions.
A prototype has the advantage that performance of actual materials in the facade,
interaction at joints and fixing points, and visual appearance, can be critically assessed.
It is possible that as part of the testing procedure some modification will be required to
each the acceptance criteria successfully. The modifications will usually be related to
penetration of water, but could also include deflection performance of the building facade
frame or glass, or slippage at the joints or fixing points.
Modifications are permitted as part of the design development: however, it is important the
modifications be documented in the test report. These modifications must then be
incorporated in the ‘as-manufactured’ and ‘as-built’ facade, so that defects noted in testing
do not recur on the actual project.
‘There have been instances where several tests were required before the facade met the
required criteria to pass the test which can raise doubts with the specifying Specifier as to
whether the wall is satisfactory. It is recommended, therefore that, if after four tests,
modifications are still required, the designer should carry out a detailed review of the
design. Further testing should only proceed when the problem has been identified and
agreement has been reached with the specifying Specifier.
B2 TEST SAMPLE
For reasons given in Paragraph Al the sample of facade selected for testing should be
representative in size and shape of the facade of the building, taking into account number of
storeys and extent in plan,
‘The aim is to simulate actual conditions so that the assumed design criteria relating to air
infiltration, waterproofing and structural aspects, including deflection, performance at
joints, and structural behaviour of the elements, can be assessed with confidence,
Where a facade is designed with a jockey sash or internal sash, not an integral part of the
weatherproofing or structural performance of the facade, it is, nevertheless, recommended
that this element be included in the prototype test sample. Removal of the sash may
adversely influence air infiltration through penetrations for fixings and locks,
COPYRIGHTFy ASINZS 428422008
The curtain wall designer should choose a representative part of the curtain wall for the test
sample. Sometimes the structural test is run twice; once with one bracket per floor and a
second time at higher building comer wind pressures with double fixings. The actual chosen
test sample mullion set-up should be analyzed to determine its expected structural
performance (deflection) during the structural test, The analysis must take account of the
actual fixings of the curtain wall members to the structure: in particular, the fixity of the
flashing at the top of the curtain wall must be correctly assessed. The deflection
should then be re-assessed in accordance with this analysis. The expected deflection for the
test sample may be more or less than the listed nominal requirement in this Standard. ‘The
expected value should be a pointer to adequate performance on-site and that the system
satisfies the specified criteria. Similarly, the maximum deflection point may not be at the
middle point between supports and the transducer position should be chosen accordingly. It
may also be appropriate to position one transducer at the middle point between supports and
one at the expected maximum deflection point
The final test sample configuration and its analysis should be agreed with the Specifier on
the project. Selection of the test sample configuration is often made before the facade
contract is awarded, so it may be necessary to modify the test sample configuration during
the design development to suit the contractor's final design and the test rig size and
capability.
‘Test rigs are available where multiple test samples can be tested within the one rig, such as
side by side or back to back. This provides greater scope for testing elements of the facade.
Where design loadings vary for the different samples, the rig should be able to be blocked
off for each sample or one of the samples modified to accept the higher loading without
distress
The Standard has not included any provisions to test louvres; however, louvres may form
part of the sample to simulate the boundary effeets of adjacent facade panels, provided the
inside face of the unit is sealed
B3_ REQUIREMENTS
Materials selected for the test sample are to be actual materials used for the facade.
However, where these materials do not directly influence the performance of the sample
under test, such as glass selection or special coatings, it is possible to test the sample with
substituted materials, Use of substitute materials requires careful assessment by the
designers and the Specifier, Such substitutes should be documented and included on test
sample drawings and noted in the test report
Where pressure equalization is specified by the Specifier, it means that the pressure in the
cavities of the facade are similar to the outside pressure in service. Under this condition the
rear or inner seal of the facade provides the air and watertightness
In some instances the facade designer may detail the spandrel cavity as a pressure-equalized
zone to the external air pressure, to prevent water entry through a pressure drop and a
failure in the external seal. The manufacturers have generally used thin metal sheets, known
as back-pans, to contain the air pressure, and in some instances these sheets are not
stiffened. As traditional engineering analysis of these sheets and their fixings (especially
fixing spacing) tend to give conservative results it is essential that a less conservative
design be adequately tested and that the test sample contain at least four back-pans, if the
design is to be confirmed by the performance test. Generally the test facility will measure
the pressure in the pressurized spandrel cavity and plot it against the external pressure. The
Specifier may require this test data reported in the final report,
1a J Paraggio on 06 Aug 2008. 1 user personal use cence only. Storage, dstnbution or use on network prohibited
In order to monitor the sample under test conditions, transparent viewing panels (or other
means of observation, such as optical fibre probe) should be provided, so that water
performance in the cavities, in areas not readily seen, can be observed during the static and
cyclic water tests
Licensed to Mi
copyRIGHTASINZS 428422008 a
The Specifier determining the sample shape and size should also take into account the worst
specified project construction tolerances. This will generally entail a maximum distance
between the structure and the building facade and the distance between horizontal structural
elements (simulated floor edge beams) to be at or near maximum tolerance, so that
‘movement joints are set in their most open position. If the sample is to be subjected to
forced racking (seismic tests) and/or vertical movements (i.e., column shortening test)
special consideration should be given to movement joint setting positions, so that the joint
full open and full closed positions are tested, but not exceeded.
B4 INCLINED GLAZING
The SIROWET method upon which this Standard is based was originally developed to test
the performance of vertical facades.
If inclined or overhead glazing systems are to be included in the test it may be necessary to
vary test pressures to simulate the design wind pressures on these surfaces. This needs to be
assessed by the Specifier:
The application rate of water as specified in Clauses 7.5 and 7.6 for the water penetration
test has been chosen to provide complete coverage of the vertical test samples to ensure that
any opening or erack in the facade system is wetted
This may be considered too severe for inclined surfaces and a rate representative of peak
rainfall conditions at the building location may be more appropriate, This needs to be
assessed by the Specifier:
nes oely. Skrote| distin use oe neksiik pmo,
Licensed to Melinda J Paraggia on 06 Aug 2008, 1 user personal user
COPYRIGHT+ user personal user licence only. Storage, distribution or use on network prohibited
Lcensed te Melinda J Paragaio on 06 Aug 2008,
as AS/NZS 4284:2008,
APPENDIX ©
STRENGTH TEST AT ULTIMATE LIMIT STATE LOADING
(nformative)
Structural elements of a building facade are designed and detailed by limiting stress, strain
and deflections. During the design process, stresses and strains are easily interchanged in
the calculations; however, on the prototype facade stresses are only determined by
measuring strains, The most common method of determining strain is by strain gauges
meticulously attached to the accessible aluminium surfaces. Strain gauging metal surfaces
is cumbersome, difficult and costly in comparison to deflection measurements. Also, when
measuring strains the test engineer has to assume maximum strain locations and these
locations may be at areas where sealant is applied. Further assumptions on the structural
behaviour of a component consisting of two parts may lead to results that are no better than
data based on deflection measurements. These shortcomings of strain measurements have
given rise to the use of a deflection limiting criterion for the struetural performance test.
The limiting deflection span ratio has been based on empirical data, and the limits stated in
the SIROWET Standard were satisfactory for the Australian construction experience. As
noted in Appendix B, a compromise is made in regard to the selection of the size of the
sample and the location of the support brackets to mullions, and the deflections on the
prototype may not be truly representative of the final building facade, The building facade
consultant should always compare the sample deflections with the theoretical calculations
and establish reasons for significant variations,
The deflection of a member is determined by a minimum of three displacement transducers.
Support deflections are measured to allow for slippage and end member deflections. For
example, a transom attached to the midspan of a mullion will have end span deflections that
usually exceed the midspan elastic deflection of the transom. Also the span of the member
should be based on the distance between the transducers, measuring the deflection of the
member
For panelized curtain wall systems the mullion span is the distance between the bottom of
the unit to the mullion bracket (see Figure C1). The definition of mullion span is based on
the curvature of the framing members under lateral loading as shown in Figure C2 for a
continuous panelized or stick system.
‘The only default deflection/span ratio listed in the Standard (see Clause 9.2.1) is for
framing members. This value has been derived linearly from the average decrease in wind
pressure from permissible to SLS. No default deflection/span ratios are given for the
elements as a direct function of the fixing system, and the Specifier should establish limits
from other Standards and guidelines.
In the caleulation of the positive and negative pressure deflection/span ratios, the
deflections either side of the mid-mode zero stages (i.e., 22 and Z5) are used. It is
uncommon for the deflection/span ratios to be equal for a similar positive or negative
structural test pressure, due 10 the effects of slippage in the elements of the framing
members,
coPyRIGHTLicensed to Melinda J Paraggia 0n 06 Aug 2008.1 user personal user licence only Storage, distribution or use on network prohdited
AS/NZS 4284:2008 26
Expansion or
stack joint
Mullion
Mullion
bracket
FIGURE C1 ATYPICAL CROSS-SECTION OF A PANELIZED BUILDING FACADE
INDICATING THE FLOOR TO FLOOR HEIGHT (A), THE PANEL HEIGHT (B)
THE VISION MULLION SPAN (C1) AND THE SPANDREL MULLION SPAN (C2),
SOMETIMES NOTED BY MANUFACTURERS
The test facilities will also generally interpolate or extrapolate from the actual calibrated
pressure to the nominated test pressure as the air-handling system cannot be held constant at
the nominated pressure due to chamber leakages and the precision of the pressure flow
devices. In these cases it is considered that linear interpolation or extrapolation is
acceptable when the difference in pressure from the nominated to the measured is within
+2% and 45% for test facilities and field sites respeetively.
With the structural performance test pressure changing from a working stress pressure (i.e,
permissible stress limit) to a SLS pressure, the accumulated damage to the glass panels has
been reduced and the probability of glass failing during testing of the sample is lowered.
Some regions may have lower ratios of serviceability to permissible limit state pressure, so
the ultimate load may become critical in these arcas.
‘The maximum displacement limit (see Clauses 8.3.7 and 9.2.3) om the sample that was
specified in the SIROWET Standard was based on research findings. This limit has also
been confirmed by testing at CSIRO Manufacturing and Infrastructure Technology to be
satisfactory and prudent in terms of user comfort, With the change from permissible to SLS
pressures the deflection limit has changed to the default of 20 mm and applied to the
framing members. The architect and building owner should be aware that the centre lateral
deflection on large glazing units may be high in strong winds and cause concern among,
COPYRIGHTLicensed fo Melinda J Paraggio on 06 Aug 2008, 1 user personal user cence only. Storage, cistrbutlon or use on network prohibited
Panol joint
/-Flxing
i
Detlected facade
under loading
Panel joint
Fixing
i
(a) Single fixing
ASINZS 4288:2008
Panel joint
Lo
Fixing
Deflected
facade
under
loading:
Panel joint
£
Fixing
(b) Double fixing
FIGURE C2 TYPICAL DEFLECTED SHAPES OF A CONTINUOUS PANELIZED
OR STICK SYSTEM FRAME UNDER LATERAL LOADING WITH SINGLE
AND DOUBLE FIXING SYSTEMS.
COPYRIGHTsence ony. Storage, dition or use on network prohibited
Licensed to Melinda J Paraggto on 06 Aug 2008. 1 user personal usar
ASINZS 4284:2008 2
During the calculations of the maximum displacement it is also acceptable to interpolate or
extrapolate the deflection based on the small difference between the measured and
nominated test pressure. The small difference noted previously (i.e., +2% and +5% for test
facility and field sites respectively) can occur, due to difficulties in testing large samples in
externally mounted and internally mounted chambers,
Another limit adopted from the SIROWET Standard is the slippage of members at the ‘at
rest” pressures. The Committee has considered that there is no apparent reason to change
these values even though some criticisms have been expressed by manufacturers that the
3 mm limit should be increased for large panels with an area exceeding 10 m*. Currently
there is no research data to indicate that the 3 mm limit should be increased and, in
addition, it may not be appropriate to change the limit as the wind loading induced on to the
test sample is lower, due to the lower test pressures (i.¢., permissible to SLS). Therefore,
this Standard has maintained the default 3. mm limit,
‘The 1 mm support slippage limit in the SIROWET Standard has been deleted as experience
has shown that a sample not meeting the 3 mm limit is usually a result of slippage at the
support. For large panels the Specifier may wish to limit the deflection at the top of the
support bracket to avoid excessive rotation of the support.
When testing samples with corer units, the horizontal slotted holes in support brackets
connected to the main sample face should be avoided, due to the lateral in-plane loads
applied from the comer unit. Alternatively, a locking device may be used in the facade
support bracket at the corner unit,
Multiple structural tests may be carried out if there is a requirement for many displacement
measurements or if the sample consists of multiple loading zones. The test procedure for
each test shall consist of that outlined in Clause 8.3.3(a) to (z) (see Figure B3.)
Should the sample or the data collection system fail during one of the three modes in the
structural test, the additional structural test shall commence at Clause 8.3.3(a). The
intermediate steps of Modes | and 2 are not required if the transducer layout has not
changed or one mode with all intermediate pressure steps has been completed before to the
partial completion of the structural test (see Figure B4),
This Standard allows for a glass unit to break during the structural test at ultimate limit
state load as it is statistically unreasonable for glass to maintain integrity when subjected to
the ultimate limit state pressures. The intent of accepting the failure of an additional glass
unit is based on the same strength premise; however, the replacement glass in the same unit
ona sample should not fail. The failure should always be investigated as it may be caused
by excessive frame deflections. Where the cause of breakage of a glass unit has been
identified as handling damage by the test engineer or the Specifier, it is common in the
industry for a replacement timber panel to be attached to the sample and the structural test
at ultimate limit state test restarted if'a similar glass unit is on the sample.
copyRiGHTistibulon or use on neon prohibited
[Licensed to Melinda J Paraggio on 08 Aug 2008. 1 user personal user licence only, Stor
2» ASINZS 4284:2008
Pressure
Mode + Mode 3! Moda 1 Mode 3
Mode 2 Mode 2
———— test 1. ———+=—_ test 2. ——_+
NOTE: The take-up forthe second test not nasessay.
FIGURE C3. TEST PROCEDURE FOR MULTIPLE STRUCTURAL
PERFORMANCE TESTS
Pressure
Mods + [Moda 4 Mode 9
'
fy ill
'
| Time
est fault
a |
—— Tost 1 et Tost 1 repeat
‘NOTE: In this ease the intermediate steps of Mode I are not neces
FIGURE C4 TEST PROCEDURE FOR STRUCTURAL PERFORMANCE TESTS.
WHERE EQUIPMENT OR SAMPLE FAILURE PREVENTS
THE COMPLETION OF MODE 2
REFERENCE,
1 ROONAN, B. and VOROBIEFF, G. The Structural Performance of High Rise
Building Facades, Second National Structural Engineering Conference 1990, LE.
Aust.
COPYRIGHTLicensed to Melinda J Paraggia on 08 Aug 2008, 1 user personal user lcance only. Storage, cstrbution or use on network prohibited
ASINZS 4284-2008 30
APPENDIX D.
AIR INFILTRATION TESTING
(Informative)
The air infiltration and exfiltration test results (commonly referred to as air infiltration) are
used by mechanical service engineers to design air-handling and stair-pressurization
systems, This test may also refleet on the water resistance performance as a ‘leaky’ sample
may have a large air infiltration result.
The air infiltration test is a measure of the air leakage of the whole sample, and it has
always been difficult to ensure that the sample elements are representative in size in
relation to the typical building floor. If openable windows are inchided in the sample, the
area or length of the openings should be included in the report for information. In
ASTM E283 the leakage rate is sometimes reported in terms of the area and volume per
‘crack’ length. The Specifier may wish to specify limits according to the number of
openable windows per floor rather than rely on area-based air leakage rates. This condition
may apply when the major area of the sample consists of an openable window.
The air infiltration test is one of the most difficult tests to perform with a great degree of
accuracy and the testing Specifier should take this into consideration when reviewing the
results. It has been generally accepted in the industry that airflow measurements below
0.1 Lim? s are difficult to obtain using an orifice plate. However, the technique to determine
air infiltration and exfiltration detailed in Clause 8.4.2 is simple and cost-effective, and
assuines that the sample and chamber leakage rates do not change during the test procedure
This assumption appears to hold true for most samples provided sufficient care is taken to
ensure that the sample is constructed with a suitable and continuous flashing.
In some situations, the air infiltration rate specified in the tests is used in the design
calculation of the air-handling and stair-pressurization systems. Clause 9.3 allows the test
facility 10 forego the sealing of the sample of the test if the total air loss through the sample
is less than the limit, In some situations in an ‘airtight’ building, facades can make it
difficult for occupants to open stair exit doors, and the Specifier may insist on a full
procedure air infiltration test to establish the actual air loss through the sample.
Testing has shown that the air infiltration and exfiltration rates are not necessarily similar
as the stiffness of the building facade varies according to the wind loading direction. If
openable windows are included in the test sample these can give different results,
depending on the window seal design.
This Standard has provided a default value for the air infiltration limit at a specified
chamber pressure, and it is noted that the increase in the chamber pressure from the adopted
value in the SIROWET Standard is indicative of the quality building facade installed on
buildings. However, it is strongly suggested that the Specifier seeks to apply more suitable
limits matching the needs of the building owner (see Table D1). The Specifier should note
that by reducing the air infiltration rate substantially below 1.6 Lim’s this may inerease the
cost of the building facade
Where a sample consists of a large area of openable windows or doors in relation to the
total sample (generally greater than 50%), a combined air infiltration limit may be stated in
terms of area and length of ‘crack’, For instance, in NZS 4211, an additional allowable air
loss of 0.6 L/m’s is provided for openable fixtures at 150 Pa chamber pressure. Note that
two openable parts meet, such as the interlocking stiles of a sliding door, the common
length is normally counted once.
COPYRIGHT‘Storage, disbution or use on network prohibited
Licensed to Melinda J Paraggio on 06 Aug 2008. 1 user personal user
3 ASINZS 428422008
TABLE D1
SUGGESTED AIR INFILTRATION RATES,
(Chamber Pressure [Air rate limit Building Type
ray (Limt.s)
=150 16 All airconditioned buildings
=150 80 All non-sirsonditioned buildings
In view of the accuracy of the test method described in this Standard, it is an acceptable
practice in the industry to report the leakage rate of the sample as the sample and chamber
leakage rate (ie., when there is no seal over the sample) if the air infiltration rate is less
than the limit stated by the Specifier or the default value. Should the Specifier wish to seck
greater accuracy in the air infiltration measurements or if the results are near the limit, the
method of determining the air leakage error noted in ASTM E283 may be used.
REFERENCE,
1 ASTM £283 Test method for determining rate of air leakage through exterior
windows, curtain walls, and doors under specified pressure differences
across the specimen
COPYRIGHTLicensed fo Melina J Paraggio on 06 Aug 2008. 1 user personal user licence any. Storage, dsiibution ar use on network prohibited.
AS(VZS 428422008 2
APPENDIX. E
WATER PENETRATION TE!
TING
(Informative)
Most building facades for multistorey buildings in Australia and New Zealand are currently
designed in accordance with the drained-joint and pressure-equalization principles. Water is
likely to penetrate these building facades when essential parts of the wall (for instance,
rain-sereen, drip edges, air seal) are not functioning, Some recent attempts to computer
model this interaction by computational fluid dynamics and the physical entities have yet to
create sufficient evidence to eliminate prototype testing. Inrespective of the tools used to
evaluate the building facade, there are three environmental factors relating to the water test.
‘These are—
(a) _ static versus eyelic applied air pressure:
(b) the duration of the water test; and
(©) the intensity of water sprayed on the sample,
The technology for applying eyclie air pressure to simulating wind gusts on a 9 m high by
8 m wide sample, and maintaining low test costs, have frustrated engineers for decades. It is
recognized that the static air chamber test is simple and reproducible, but far from reality.
In an externally mounted chamber the cycling of air pressure about some mean pressure
provides a nearer solution to simulate wind gust effects. Also, the cyclic air pressure can be
applied to the whole sample whereas the aeroplane engine test has a limited area of
simulated wind gust
Air pressure values measured on unitized curtain wall samples with connecting spandrel,
mullion and transom cavities and successfully designed to pressure-equalization principles
indicate, in both static and cyelic pressure modes, that the internal chambers are near full
pressure-equalization to the chamber pressure. Therefore, probable water penetration during
a static test is by capillary suction, kinetic energy and surface tension, and these methods
are the least common mechanisms for water penetration experienced today, More
commonly, water penetration failure in a static test is due to out-of-plane deflections and
rotations at junctions of the sample high enough to form breaks in the air seal,
In Australia, the dynamic water test commenced in the 1960s using a wind generator, such
‘as an aircraft engine with a 4 m diameter propeller. The wind generator was also adopted by
American engineers with the test procedure detailed in AAMA 501.183. The test wind
speed is SS km/h and produces a minimum pressure of 137 Pa, Along with the low external
pressure the positive airflow coverage applied on the sample is generally limited to one
floor.
‘The cyclic water test using an externally mounted chamber does not provide a close
approximation to natural conditions as the frequency and pressure range during a storm are
rnot uniform and consistent in time. However, the eyclic action over the whole sample is,
stringent and repeatable, and therefore it becomes a reliable and cost-effective method of,
performance evaluation.
Brown and Ballantyne (Ref. 1) recognized in the 1970s that the water penetration test
pressure for both the static and cyclic tests was a function of the building height and
associated with the positive wind pressure. Also, the frequency of occurrence of wind-
driven rain on a building face was considered ‘somewhat less’ than the wind speeds listed
in the wind code.
COPYRIGHTLicensed fo Melinda J Paraggio on 08 Aug 2008. 1 user personal user iene only. Storage, cstbutlon or use on network prohibited
Fe) ASINZS 428422008,
Research efforts for the determination of the joint wind and rain probability commenced in
the 1990s at CSIRO-DBCE (Ref. 2). One of the difficulties faced in using the data at
meteorological stations was that the wind records were hourly mean wind speeds recorded
at 3h time intervals averaged over the 10 min period before the hour. It was well known
that the duration of many wind-driven storms lasted for 10 to 30 min. The published data
did establish that
(wind speeds increased for increasing return periods at a constant rainfall intensity;
and
Gi) for the same return period the extreme wind speeds decreased with increasing rainfall
intensity
In the Tate 1980s industry experts had decided to maintain the 300 Pa SIROWET test
pressure for the static test and nominate the eyelie water penetration test pressure in three
stages, as follows
(A) Stage 1a... oe “ tS: 300 Pa to 600 Pa.
(B) Stage 2 0 30% We t0 60% M,,
(©) Stage 3
In Stage 2, W, refers to the structural design (i.e., positive SLS) pressure. The 300 Pa value
nominated in Clause 8.5.1 is a default value, and the building facade designer should select
an appropriate pressure based on the building exposure,
..on instructions from Specifier.
The third component in the establishment of suitable test requirement to assess the water
resistance of building facade systems is the water spray intensity at the sample, Currently
the SIROWET Standard specifies 0.05 L/s m’ (or 3.0 L/min m’) whereas ASTM E547 and
ASTM E331 specifies 0.057 L/s m’ (or 3.4 L/min m’), The ASTM Standard has been
converted from imperial units (i.e., 4 gals/h ft’) and the water spray quantity is equivalent to
the direct impingement of rain on the wall at the rate of 203 mm/h (ASTM E547)
The default test duration and water spray contents have not changed from the SIROWET
method; however, the proforma test sheet in Appendix A allows the Specifier to change
these values, based on regional weather data
In both this Standard and ASTM Standards, the water spray pattern is uniform, covers the
whole sample, and is calibrated using a *catch-box’ test in accordance with ASTM E547.
More importantly, the upper half of the sample has little run-off and the quantity of run-off
increases down the sample. If the external dynamic air pressure is generated by propeller
the water flow across the sample appears to be radial and downwards, and this provides
additional kinetic energy to water.
REFERENCES,
1 BROWN, N.G. and BALLANTYNE, E.R. The SIROWET Rig for Testing the
Weatherproofness of Building Facades, CSIRO Division of Building Research, 1975.
CHO, E.C.C. Extreme Wind Speeds During Rainfall—Proceedings of Second
Workshop on Wind Engineering, Australian Wind Engineering Society, Melbourne,
February 1992.
3 ASTM Test method for water penetration of exterior windows, skylights, doors,
E331 and curtain walls by uniform static air pressure difference
4 ASTM Test method for water penetration of exterior windows, skylights, doors and
E547 curtain walls, and doors by eyclie static air pressure difference
5 AAMA Quality assurance and diagnostic water leakage field check of installed
501.2 storefronts, curtain walls, and sloped glazing systems
coPyRiGHTLicensed to Melinda J Peragolo on 06 Aug 2008.1 user personal user icence only. Slorage, cistibuion or use on network prohitited
ASINZS 42842008 4
APPENDIX F
SEISMIC TESTING
(Informative)
Designing a building facade for earthquake resistance requires a full understanding of the
behaviour of the building when subjected to seismic ground motions, In most instances the
building structure will vibrate to its first mode of vibration and this may be calculated using
the approximation in AS 1170.4 and NZS 1170.5. The structure vibration is generally much
lower than the natural frequency of vibration of the building facade components
It is costly to design and construct a building to withstand the maximum probable
earthquake and therefore the designer and the building owner are required to establish an
acceptable level of damage at an appropriate risk level. The acceptable level of risk should
include the degree of glazing unit collapse, the reduction in air and water penetration
resistance, and other performance indicators relevant to the type of facade.
It is common to allow for post-elastic building response during ultimate limit state
earthquakes. This is implied in the building response factor (Rj), and deflection
amplification factor (Ka) of AS 1170.4, and in Section 7 of NZS 1170.5. The calculated
elastic deformation should be amplified by Ky or in accordance with Section 7 of
NZS 1170.5 to determine the maximum post-elastic response at roof level. This maximum
response is then applied as an ultimate limit state drift
In “shear-walled” buildings the maximum drift can usually be assumed to be linear up to
building height. In *framed’ buildings 75% of the maximum drift is likely to oceur over the
lower six storeys and the ultimate drift limit specified in the test should make allowance for
this effect. It is common for post-elastic drift to be factored by 1.3 to allow for secondary
effects, such as plastic hinge elongation and “floor growth’ (i.e., known to occur during
extreme response)
Because the forces for displacement of shear-wall facades are generally greater than those
that can be achieved in a prototype test enclosure and the likelihood of glazing components
set in these shear-walls are not dimensionally stressed during seismic events, it is
recommended that seismic testing within the scope of this Standard should only be
undertaken with flexible framed systems, such as stick and panelized curtain walls and light
frame construction.
This appropriate value of d, at serviceability and d, at the ultimate limit state seismic
displacement should be determined by the building structural designer,
‘The seismic test program has been developed for in-plane displacements only and typical of
the building racking initiated by the movement of one floor relative to adjacent floors (i.e.,
inter-storey drift), At the SLS, the structural system and building facade should remain in
the elastic state and it is anticipated that the building owner would expect the building to be
functional after this seismic loading
In Clause 7.9 of this Standard, a water penetration test by cyclic pressure is recommended
after a seismic test at the SLS displacement to observe the change in performance of the
sample. In some test specifications the consultant has specified an additional air infiltration
test, However, it is difficult to get significant results, due to the damage to the surrounding,
flashing during the seismic loading,
Temporary repair techniques to the building facade may be examined after seismic loading
and these repair techniques may be tested and compared against a water penetration
criterion,
COPYRIGHTLicensed to Nietnda J Paraggio on 06 Aug 2008, 1 user personal user ioence only. Storage, dlsnbution or use on network prohitite
ASINZS 4284:2008
Test displacements and application have been detailed as sinusoidal as it is the building
response rather than the ground response which is likely to be applied to the prototype. The
period of cycling (1) should be sufficiently rapid to ensure a realistic slip of gaskets and
seals if used in the building facade components. The New Zealand experience and research
(BRANZ report) indicates that the period of displacement should be expressed as a peak
. typically greater than 10 mm/s. In addition, BRANZ notes that the minimum
number of cycles (n) is 10 and additional repeated cycling may be required where a dry-
glaze gasket system is used.
REFERENCE
1 THORNTON, SJ and KING, B.B BRANZ Technical Recommendation No. 15
(1993), Proposed test and evaluation procedure for external curtain wall glazing
systems to simulate seismic loading,
COPYRIGHT36
ASINZS 428422008,
NoTEs
‘ayaiyoud omiou vo asm 40 uoMnquip ‘aBeIaNg “Kun 20U809 Jo5n
98190 1889 "9002 BnY 99 Uo CIBBeIe, ¢ epUEEYY OF pOSUBOHition o use on network prof
+ user personal user licence only, Storage, i
Licensed to Melinda J Paraggio on 06 Aug 2008,
Standards Australia
Standards Australia is an independent company. limited by guarantee, which prepares and publishes
‘most of the voluntary technical and commercial standards used in Australia. These standards are
developed through an open process of consultation and consensus, in which all interested parties are
invited to participate. Through a Memorandum of Understanding with the Commonwealth
government, Standards Australia is recognized as Australia's peak national standards body.
Standards New Zealand
‘The first national Standards organization was created in New Zealand in 1932. The Standards
Council of New Zealand is the netionsl authority responsible for the production of Standards,
Standards New Zealand is the trading arm of the Standards Council established under the Standards
Act 1988,
AustralianiNow Zealand Standards
Under a Memorandum of Understanding between Standards Australia and Standards New Zealand,
Australian/New Zealand Standards are prepared by committees of experts from industry,
governments, consumers and other sectors, The requirements or recommendations contained
in published Standards are @ consensus of the views of representative interests and also take
account of comments received trom other sources, They reflect the latest scientific and industry
experience. Australian/New Zealand Standards are kept under continuous review after publication
and are updated regularly to take account of changing technology,
International Involvement
Standards Australia and Standards New Zealand are responsible for ensuring that the Australian
and New Zealand viewpoints are considered in the formulation of international Standards and that
the latest international experience is incorporated in national and Joint Standards. This role is vital
in assisting local industry to compete in international markets. Both organizations are the national
‘members af ISO (the International Organization for Standardization) and IEC (the International
Electrotechnical Commission).
Visit our web sites
www.standards.org.au
www.standards.co.nz
www.standards.com.auLicensed to Melinda J Paraggio en 06 Aug 2008, 1 user personal user cence only. Storage, dstbutio or use on network prohibited.
SBN 0 7337 86197
{GPO Box 478 Syiney NSW 2001
Aaiministrtion
Phone 02 9237 6000
Fax (02) 9257 e010
Emel misiandrds or a0
Customer Service
Phone 1500854645
ax 12008549 49
Email
[email protected]
Internet uv standards. org
eros
Level 10 Ris New Zealand House
165 The Tevace Wangan 6001
(Prats Bog 2430 Wengen 6020)
Phone (0) 498 S880
Fax (04 408 5058
(Customer Series (04 408 £001
Information Service (04 458 5862
mall
[email protected]
Internet nn standards 0.02
Printed in Australia