Op Inst - Erlymd-2-1-S8-1co-24v Op566

This document provides information about an ERLYMD-2-1-S8-1CO-24V module that is used with PLCs for communication. The module has 8 channels, relay contacts, and connects via RS485. It can be configured with different slave IDs, baud rates, and LEDs indicate communication status. The module mounts on a DIN rail and specifications include voltage ratings, contact ratings, and environmental limits.

Uploaded by

Sudipto Majumder
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views2 pages

Op Inst - Erlymd-2-1-S8-1co-24v Op566

This document provides information about an ERLYMD-2-1-S8-1CO-24V module that is used with PLCs for communication. The module has 8 channels, relay contacts, and connects via RS485. It can be configured with different slave IDs, baud rates, and LEDs indicate communication status. The module mounts on a DIN rail and specifications include voltage ratings, contact ratings, and environmental limits.

Uploaded by

Sudipto Majumder
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ERLYMD-2-1-S8-1CO-24V

OP566-V01

1. PRODUCT PROFILE 2. DESCRIPTION


Ø ERLYMD-2-1-S8-1CO-24V is a module for use in conjunction with any PLC
(With RS 485 master communication)
Ø Up to 7 number of such modules can be connected to a master PLC
Ø Four baud rate selections 9600, 19200, 38400, 57600 (User configurable)
Ø Seven Slave ID selection 1 to 7 (User configurable)
Ø Default baudrate 19200 and slave ID 1
Ø 12 LED indicators
Ø Five way DIP switch for Slave ID & Baud rate selection

Figure 1.1 (Product Image)

3.TERMINAL CONNECTIONS

04 01 02 14 11 12 24 21 22 34 31 32 44 41 42 54 51 52 64 61 62 74 71 72
1NO 1C 1NC 2NO 2C 2NC 3NO 3C 3NC 4NO 4C 4NC 5NO 5C 5NC 6NO 6C 6NC 7NO 7C 7NC 8NO 8C 8NC

4. SPECIFICATIONS 5. DIP SWITCH SELECTION

Contacts 1 C/O DIP SWITCH


Slave ID
1 2 3 4 5
No. of Channels 8
NA X X OFF OFF OFF
Relay Specifications 1 X X OFF OFF ON
Nominal Coil Voltage 24V DC 2 X X OFF ON OFF
3 X X OFF ON ON
Must Operate Voltage 18V DC
4 X X ON OFF OFF
Max Coil Voltage 33V DC
5 X X ON OFF ON
Coil Current Per Channel 46 mA 6 X X ON ON OFF
7 X X ON ON ON
Operate (Set) Time 15 ms max
Baud Rate
Release (Reset) Time 5 ms max
9600 OFF OFF X X X
Endurance Mechanical : 10000000 ops 19200 OFF ON X X X

Electrical : 100000 ops 38400 ON OFF X X X


57600 ON ON X X X
Dielectric Strength
6. LED Display
Coil to contact 5000VAC for 1 minute
LED Name LED COLOR INDICATION
Open contacts 1000VAC for 1 minute
Power LED (PWR) Green Always ON when device is powered
Relay Contact Rating 10A @ 277VAC / 30VDC
Receive LED (Rx) Green Blinks when receives command from master
o
Operating Ambient -40 to 70 C
Transmit LED (Tx) Red Blinks when transmits response to master
Humidity 98% RH, 40oC
Will turn OFF if no command received within
Terminations 10 secs
Status LED (Stat) Red
Coil Termination Screw type, for 2.5 mm sq.wire Flashes for 500ms ON, 500ms OFF when SID = 0
(hardware setting), module is disabled
Contact Termination Screw type, for 2.5 mm sq.wire

Mounting 35 mm DIN rail 7. Communication

Ordering information ERLYMD-2-1-S8-1CO-24V Communication Port RS485 Slave


Communication Protocol Modbus protocol
Dimensions 133(W) x 87(H) x 78(D) (in mm)
Baud Rate 9600, 19200, 38400, 57600 (User Configurable), Default 19K2
Weight 328.8 grams
Fixed Settings Parity (None), Stop bits = 1, Data Length = 8

Coil addresses Starting from 0 to 7

Doc. name : OP INST ERLYMD-2-1-S8-1CO-24V OP566-V01(Page 1 of 2)


DANGER SAFETY SUMMARY
DANGER
Ø Do not install in areas with excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat. regular impact shocks or excessive vibration. Indicates that death or severe personal injury will result if proper precautions are not
taken.
WARNING
8. DIN RAIL MOUNTING
Indicates that death or severe personal injury may result if proper precautions are not
taken.

NOTCH CAUTION
With a safety alert symbol, indicates that minor personal injury can result if proper
precautions are not taken.

35 mm NOTE :
DIN RAIL
Indicates that an unintended result or situation can occur if the relevant information is
not taken into account.

SAFETY PRECAUTIONS
NOTCH Ø This manual is meant for person involved in wiring, installation and operation of the
Figure 1.2 (Side view) equipment.
Ø Safety related conditions, symbols & instructions that appear in this operating manual
Ø Install the device as shown in the figure 1.2, such that module properly fits on the din rail or on the equipment must be strictly followed to ensure operator's and instrument's
within the notches, also allowing sufficient space around it for heat dissipation. safety.
Ø Commissioning is absolutely prohibited until it has been completely ensured that the
9. WIRING DETAILS machine, in which the components described here are to be installed, is in full
compliance with the provisions of the EC Machinery Directive.
DC Supply BAUD OPTIONAL
}

RATE SID
CONNECTION
+24V GND DANGER
}

(RS485)

Ø Failure to comply with appropriate safety guidelines can result in severe personal
+ - + - 6 PIN
injury or property damage. Always exercise proper caution when working with
JACK

PWR
1 2 3 4 5
ON
LED_TX LED_RX LED_STAT electrical equipment.
24V RS485
Ø Improper grounding may result in communication error, electric shock or fire.
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8
6 PIN
JACK WARNING
Master RS485 Ø Read complete instructions prior to installation and operation of the controller/card
Ø Proper transport, storage, installation, assembly, commissioning, operation and
PLC
maintenance are required to ensure that product operate safely and without any
problem.
04 01 02 14 11 12 24 21 22 34 31 32 44 41 42 54 51 52 64 61 62 74 71 72 CAUTION

Figure 1.3 (Wiring Diagram) Ø In addition to the danger and warning information provided in the manual, the
applicable national, local and system specific regulations and requirements must be
INTERNAL PINOUT DESCRIPTION FOR 6 PIN JACK (PORT 1) taken into account.
Ø If product and components from other manufacturers are used, these must be
Pin Description recommended or approved by SELEC Controls Pvt Ltd.

1 RS485 Slave +ve


EMC GUIDELINES
2 NA Ø The permissible ambient conditions must be complied
Ø Power supply lines length to be maintained within 10m.
3 NA

4 NA MAINTENANCE
5 NA Ø Clean the equipment regularly using a soft cloth.
Ø Do not use Isopropyl Alcohol or any other organic solvents for cleaning.
6 RS485 Slave -ve Ø Conductors must not come in contact with the internal circuitry of the controller or else
it may lead to a safety hazard that may cause electrical shock to operator.
CAUTION

Ø In situations of high transmission speed, long distance or high noise, the high quality
twisted pair cable should be used. However in situations of low transmission speed
and low noise, PVC twisted pair cable will be compatible.

WARNING DISCLAIMER LIABILITY


Ø The power supply connection cable must have a cross section of 1 sq. mm or greater We have reviewed the contents of this publication to ensure consistency with the
and insulation capacity of at least 1.5 kV. hardware and software described. Since variance cannot be precluded entirely, we
cannot guarantee full consistency However the information in this publication is
reviewed and any necessary corrections are included in subsequent editions.
WIRING INSTRUCTIONS
SERVICE DETAILS
Ø In PLC control system, many devices are controlled at the same time and actions of
This device contains no user serviceable parts and requires special equipment and
any device could influence each other, i.e. breakdown of any device may cause the
specialized engineers for repair.
breakdown of the entire auto-control system and danger. Therefore, we suggest you
Please contact service center for repair on the following numbers :
wire a noise protection circuit at the power supply input terminal.
Tel. No. : + 91-7498077172 ; Email : [email protected]
Ø Use the shortest possible wire length.
Ø Use wire trays for routing where possible.
Ø To minimize voltage drops when wires must run a long distance, consider using NO WARRANTY ON UNIT DAMAGED DUE TO WRONG POWER SUPPLY.
multiple wires for the return line. (Specifications are subject to change, since development is a continuous process.)
Ø Avoid running lower voltage wiring near higher voltage wiring.
Ø Avoid running input wiring close to output wiring where possible. Selec Controls Pvt. Ltd., India
Ø Avoid running DC wiring in close proximity to AC wiring where possible. Factory Address :
Ø Avoid creating sharp bends in the wires. EL-27/1, Electronic Zone, TTC Industrial Area, MIDC, Mahape, Navi Mumbai - 400 710, INDIA.
Ø The output terminals should not be loaded more than the values/range specified by Tel. No. : +91-22-4148 419/430 | Fax No. : +91-22-28471733
the manufacturer. Toll free : 1800 227 353 (BSNL/MTNL Subscribers only)
Ø Always use a continuous length of wire. Do not splice wires to attain a needed length. Website : www.selec.com | Email : [email protected]

Doc. name : OP INST ERLYMD-2-1-S8-1CO-24V OP566-V01(Page 2 of 2)