MT-600/8000 series
MT-607i
                                               MT-8070iH / MT-6070iH
                                               Installation Instruction
1.0 Installation and Startup Guide
0
Install Environment
7
    Where              The MT-600/8000 Series is designed for industrial. The temperature range of operating
    Used               is from 32 to 113 °F (0 to 45 °C), as majority of industrial environments. It may not be
                       suitable for using in certain outdoor applications. Please consult the factory for
                       advised usage in outdoor applications.
    NEMA               The MT-600/8000 Series front bezel is NEMA 4 rated. When installed properly in a
    Rating
                       NEMA 4 panel, the NEMA 4 rating of the panel will not be compromised. This means
                       that fluids will not enter the panel during wash downs.
    Electrical         The MT-600/8000 Series has been tested to conform to European CE requirements.
    Environment
                       This means that the circuitry is designed to resist the effects of electrical noise. This
                       does not guarantee noise immunity in severe cases. Proper wire routing and
                       grounding will insure proper operation.
    Mechanical         Avoid installing units in environments where severe mechanical vibration or shocks
    Environment
                       are present.
2.0 Installation Instructions
1
2.1 Mounting Instructions
4
2.1.1 Location Considerations
8
      Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC
    output modules, contactors, starters and relays, and any other source of electrical interference are located
    away from the back of the unit.
      Particular note should be taken to the position of variable speed drives and switching power supplies.
    Their input and load cables should be screened to a central star earth point.
                                                           1
2.1.2 Making a NEMA-4 Mounting
9
 Panel       The unit can be mounted into panels with a depth of 4”(105mm). It is recommended that
 Details     the unit be mounted on the front panel of a steel enclosure, through an appropriate opening.
                          Allow a clearance of 1”(25mm) around the sides of the unit for mounting hardware. Allow
                          clearance for cable connections to the back of the unit. Unit depth may vary according to
                          cable type used. Typically, plan a depth to accommodate at least 4”(105mm) behind the
                          panel.
     NEMA-4               Put the unit through the panel cut out. Slide the clamps (packed with product) into the 4
     Mounting             holes provided around the case. Tighten the clamping screws in an even pattern until the
                          unit is secured in the panel. Screw Torque: 2.6~3.5 lbf.in. (For reaching waterproof effect
                          and to prevent the panel from being deformed.)
     VESA                 There are 4 holes on back panel for locking VESA, The screw: M4 P0.7mm, length:
     Mounting
                          shorter then 8.0mm, and screw torque: 2.6 lbf.in.
     Caution!             Do not over tighten mounting clamps!
     Note:            Specifications
                     57
                          Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and
                          panel cannot flex more than 0.010”.
 2.1.3 Environmental Considerations
10
                     z      The MT-600/8000 are to be used indoors as built in displays. Make sure that the displays
                            are installed correctly and that the operating limits are followed (See Specifications).
                     z      Do not operate the unit in areas subject to explosion hazards due to flammable gases,
                            vapors or dusts.
                     z      The unit should not be installed where fast temperature variations and/or high humidity
                            are present. This will cause condensation of water in the device.
                     z      Do not install these terminals in environments where have inflammable gases.
2.2 Power Connections
5
   Make sure that all local and national electrical standards are met when the installing the unit.
   Contact your local authorities to determine which codes apply.
 2.2.1 Power Requirements
11
                Power                        The MT-600/8000 can be powered by DC power only. The specified
                                             voltage range is 24±20% Volts DC. This insures compatibility with most
                                             controller DC systems.
                                             The power conditioning circuitry inside the unit is accomplished by a
                                             switching power supply. The peak starting current can be as high as
                                             700mA.
                Fusing                       If the display does not come on within 5 seconds of power up, remove
                Requirements                 power. An internal fuse will prevent damage if the polarity of the DC
                                             power is incorrect. Check wiring to insure proper connections and try to
                                             power up again.
                 Caution
                51
                                             An Internal fuse will prevent damage for over voltage condition however
                 High Voltage
                50
                                             it isn’t guaranteed.
                                             DC voltage sources should provide proper isolation from main AC power
                                             and similar hazards.
                                                                 2
              Caution              A Hard-wired EMERGENCY STOP should be fitted in any system using
              Emergency            an MT-600/8000 to comply with ICS Safety Recommendations.
              Stop
              Caution
              52                   Do not power the MT-600/8000 and inductive DC loads, or input
              Supply Voltage       circuitry to the controller, with the same power supply. Note: The 24 VDC
              Condition
              53                   output from some controllers may not have enough current to power the
                                   MT-600/8000.
              Caution              Wire lengths should be minimized (Maximum 1600’ (500 m) shielded,
              Wire Routing
              54                   1000’ (300 m) unshielded).
                                   Wires should be run in pairs with a neutral or common paired with a hot or
                                   signal line.
                                   If wiring is to be exposed to lightning or surges, use appropriate surge
                                   suppression devices.
                                   Keep AC, high energy, and rapidly switching DC wiring separate from
                                   signal wires.
                                   Equip ungrounded DC supplies with a resistor and capacitor in parallel to
                                   earth ground. This provides a path for static and high frequency
                                   dissipation. Typical values to use are 1MOhm and 4700pF.
                                   To prevent the HMI from becoming damaged or having sound output
              Caution              issues, after turning the device off, please wait 10 seconds before turning
                                   the device on again.
               Connection
              55             To make a connection, strip about 3/8” of insulation off the end of the
                             wire, turn the connector screw counterclockwise until the gap is wide
                             open, insert the wire all the way in, and turn the screw clockwise until it’s
                             tight.
                             Connect positive DC line to the ‘+24V’ terminal and the DC ground to the
                             ‘0V‘ terminal.
 2.2.2 Grounding Requirements
12
                         Chassis ground must be used. DC ground is not directly coupled to Earth
                         ground internally. It is preferable not to ground DC negative return to chassis
                         ground as poor site earths can introduce noise into a system, but if necessary
                         an earth connection should be made, from the power supply return point to
                         the central star earth point. Ground conductors should be as short and as large
                         in size as possible. The conductors must always be large enough to carry the
                         maximum short circuit current of the path being considered. Ground
                         conductors should be connected to a tree from a central star earth ground
                         point. This ensures that no ground conductor carries current from any other
                         branch.
 2.2.3 CE Requirements
13
         To make an MT-600/8000 comply with EMC directives, and to reduce susceptibility to electrical
      interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the
      power connector. This ground connection should be run directly to the central star earth connection
      point (as recommended in most Installation Instructions).
 2.2.4 Safety Guidelines
14
         This section presents recommended installation practices, and procedures. Since no two
      applications are identical, these recommendations should be considered as guidelines.
     Hardware                  WARNING!
     Considerations
     58
                               The system designer should be aware that devices in Controller systems could
                               fail and thereby create an unsafe condition. Furthermore, electrical
                               interference in an operator interface, such as an MT-600/8000, can lead to
                               equipment start-up, which could result in property damage and/or physical
                               injury to the equipment operator.
                               If you, or your company, use any programmable control systems that require
                               an operator or attendant, you should be aware that this potential safety hazard
                                                       3
                                       exists and take appropriate precautions. Although the specific design steps
                                       depend on your particular application, the following precautions generally
                                       apply to installation of solid-state programmable control devices. In addition,
                                       these precautions conform to the guidelines for installation of Controllers as
                                       recommended in the NEMA ICS 3-304 Control Standards.
     Programming                        To conform with ICS Safety Recommendations, checks should be placed
     Considerations                     in the controller to ensure that all writable registers that control critical
                                        parts of plant or machinery have limit checks built into the program, with
                                        an out-of-limit safe shut down procedure to ensure safety of personnel.
ICS 3-304.81 Safety Recommendations:
            Consideration should be given to the use of an emergency stop function, which is independent of the programmable
       controller.
           Where the operator is exposed to the machinery, such as in loading or unloading a machine tool, or where the machine
       cycles automatically, consideration should be given to the use of an electromechanical override or other redundant means,
       independent of the programmable controller, for starting and interrupting the cycle.
           If provision is required for changing programs while the equipment is in operation, consideration should be given to the
       use of locks or other means of assuring that only authorized personnel can make such changes.
           These recommendations are intended as safeguards against the failure of critical components and the effects of such
       failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation. *
        z The ICS 3-304.81 Safety Recommendations are reproduced by permission of the National Electrical
          Manufacturers Association from NEMA ICS 3-304
2.3 Communications Connections
6
        The ports as you look at the back of the case, are the ports for connecting to a PLC or some external
      device (Controller Connectors).
 2.3.1 Connector COM1 [RS232], COM2 [RS232]
15
     Cable                            Different cables are required for various devices.
     Requirements
                                      Restrict cable length to less than 500’ (150m) for RS485/422 devices and
     Caution                          50’ (15m) for RS232 devices to avoid communications problems.
                                      The COM light on the front of the MT-600/8000 will turn on with each
                                      Ethernet communication.
                                      Shielded cable must be used for long lengths or cables run in an electrically
                                      noisy environment.
                                      Do not run cables next to AC power lines or near sources of electrical noise.
                                      Be sure that the cable ends have been inserted all of the way into mating
                                      connectors and are secure
     Pin Designations                 Pin assignment of the 9 Pin, Male, SUB-D, COM1 [RS-232] and COM2
                                      [RS-232] Port.
                                        Pin#     Symbol         COM1 [RS232]                        COM2 [RS232]
                                        1        Not used
     COM1 [RS-232]                      2        RxD            Received Data
     COM2 [RS-232]
                                        3        TxD            Transmitted Data
                                        4        TxD                                        Transmitted Data
                                        5        GND                                Signal Ground
                                        6        RxD                                        Received Data
                                        7        RTS            Ready to send output
                                        8        CTS            Clear to send input
                                        9        Not used
                                                                   4
 2.3.2 Connector COM1[RS485] , COM3[RS485] and COM3[RS232]
16
        The 9 Pin, Female, SUB-D, COM1 [RS-485] , COM3 [RS-485] and COM3 [RS-232] Port on the back
     of the unit is the RS-232 and RS485/422 communications port for connecting to a controller.
       COM1 [RS485]2w supports MPI 187.5K.
     Connection
     Pin Designations           Pin assignment of the 9 Pin, Female, SUB-D COM1 [RS-485], COM3
                                [RS-485] and COM3 [RS-232] Port
                                Pin# Symbol Com1                Com1          Com3    Com3
                                                [RS485]2w       [RS485]4w [RS485]     [RS232]
     COM1 [RS-485]               1     Rx-      Data-           Rx-
     COM3 [RS-485]               2     Rx+      Data+           Rx+
     COM3 [RS-232]               3     Tx-                      Tx-
                                 4     Tx+                      Tx+
                                 5     GND                          Signal Ground
                                 6     Data-                                  Data-
                                 7     TxD                                            Transmit
                                 8     RxD                                            Receive
                                 9     Data+                                  Data+
2.3.3 USB Host port
17
USB 1.1 Host interface supports USB mouse, keyboard, USB Flash Drive and printer.
While using external hard drive, please use external power supply. Do not use USB port to charge external
device.
2.3.4 USB client port
18
It can use Mini USB cable (RZCMT6100) to download projects from PC by the USB 2.0 client port. Support
USB 2.0 client interface. The cable regulation must accord with HI-SPEED USB Revision 2.0 SHIELDED.
How to install USB driver of HMI i series
It is necessary to install USB driver of HMI on PC before at the first time enjoying this function. (The HMI
models: MT6050i, MT6056i, MT6070iH, MT6100i, MT8070iH and MT8100i)
1. Using USB cable mini side plug to HMI and another side plug into PC. The PC will display “Found New
     Hardware Wizard” dialog. Select “Install from a list or specific location (Advanced)”.
2. Check “Include this location in the search”, and assign the path to install Weintek HMI i Series driver
     from C:\EB8000\usbdriver.
3. If the USB driver successfully be installed, user can check it at Computer Management / Device Manager
     to check. Then user can download project to HMI i series through USB cable.
                                                      5
2.3.5 Connecter Wire
19
MT8-Ethernet/RZC045120: Direct connect (Ethernet crossover cable)
MT-600/8000                         PC or Note
Ethernet RJ45 Wire color            Book RJ45
1 TX+         White/Orange          3 RX+
2 TX-         Orange                6 RX-
3 RX+         White/Green           1 TX+
6 RX-           Green                 2 TX-
     MT8-COM1/RZC002320                                MT8-COM3/RZC004850
                          5   9
                                                                                       5   9
                          1   6
                                                                                       1   6
         5
     9
     6                                                 6   1                           5   9
         1
                                                       9   5                           1   6
                          5   9
                              6                                                        5   9
                          1
                                                                                       1   6
 2.3.6 Dip Switch
20
                                        SW1
                                       21         SW2
                                                 22             SW3
                                                               23      SW4 Mode
                                                                      24   25
                                        ON
                                       26         OFF
                                                 27             OFF
                                                               28      OFF Touch Screen Calibrate mode
                                                                      29   30
                                        OFF
                                       31         ON
                                                 32             OFF
                                                               33      OFF Hide MT8000 System Setting Bar
                                                                      34
                                        OFF
                                       35         OFF
                                                 36             ON
                                                               37      OFF Boot Loader mode
                                                                      38   39
                                        OFF
                                       40         OFF
                                                 41             OFF
                                                               42      ON Reserve
                                                                      43   44
                                        OFF
                                       45         OFF
                                                 46             OFF
                                                               47      OFF Normal
                                                                      48   49
                                             z Touch Screen Calibrate and Reset Password mode: In this
                                               mode when you power on the MT8000 series, the screen
                                               will display a “+” sign upper-left of the screen. Use a
                                               stylus or finger to push the center of the “+” until it moves.
                                               The “+” moves to upper-left, upper-right, lower -left,
                                               lower-right and center. When all five “+” are done the “+”
                                               will disappear. The Touch Screen parameter will be stored
                                               in Flash Rom.
                                             z        If losing or forgetting system passwords, users can set Dip
                                                      Switch 1 to “ON” position, the rest of Dips remain on
                                                      “OFF” position and then reboot MT8000 series. Under
                                                      this situation, MT8000 series will jump to Touch Adjust
                                                      (Touch screen calibration) mode. After calibration, the
                                                      pop-up window appears as the illustration below. Users
                                                      will be inquired if restoring the system password to the
                                                      default value.
                                             z        When “YES” is chosen, another pop-up dialog appears as
                                                      below. Users will be confirmed again if restoring the
                                                      system password to the default value and will be asked to
                                                      input “YES”. Then click OK. (The default password is
                                                      111111. However, other passwords, including download,
                                                      upload password and History backup password, have to be
                                                      reset.)
                                            Note: When the reset action is be taken, projects and saved data in
                                            the HMI will all be cleared.
                                                               6
2.4 CE Requirements
EU directives that apply to the MT-600/8000 Series:
56
  z EMC Directive (2004/108/EC) electromagnetic emissions and immunity.
  z UL508(ISBN 0-7629-0404-6)machine safety for use in Pollution Degree 2 Environment.
  z MT-600/8000 products will be CE-marked to indicate compliance with the EMC Directive.
The MT-600/8000 Series has been designed to operate satisfactorily in electromagnetic noise (immunity) and
without emitting high levels of electrical noise into the environment (emission). The units are designed to
meet European Community standards when installed per the wiring instructions in this manual.
Compatibility The MT-600/8000 has been designed to meet electromagnetic compatibility for industrial
Standards         environments.
                   z EN 55022: 2006 Class A
                   z EN 61000-3-2: 2006
                   z EN 61000-3-3: 1995+A1: 2001+A2: 2005
                   z EN 55024: 1998+A1: 2001+A2: 2003
3.0 Specifications
2
                                  MT6070iH                            MT8070iH                               MT607i
                                              Hardware Specification
     Display                                                      7" TFT LCD
     Brightness                                                    375 cd/m2
     Color                                                        65,536 colors
     Contrast Ratio                                                   500:1
     Resolution (WxH dots)                                         800 x 480
     Back light                                                       LED
     Backlight life time (avg.)                                  30,000 hr. min.
     Touch panel                                              4 wires resistive type
     Touch Accuracy                               Active Area Length(X)±2%, Width(Y)±2%
     I/O port                       COM1 (RS-232/RS-485 2W/4W), COM2(RS232), COM3(RS-232/RS-485 2W)
     Ethernet port                  N/A                                       1 Ethernet port (10/100 Base-T)
     USB                                            USB Host port x 1, USB Client port x 1
     Processor                                             32bit RISC CPU 400MHz
     Flash memory                                                    128MB
     DRAM                                                64MB DDR2 RAM on board
     SD card slot                   N/A                                              Support SD/SDHC
     Audio                          N/A                                                    YES
     RTC                                            Built-in (CR2032 3V lithium battery.)
                                               General Specification
     Input Power                                       24±20% VDC Power Isolator Inside
     Max Power Consumption                                       250 mA@24VDC
     Protection structure                                  IP65 front panel (O ring seal)
     Storage Temperature                                      -20~60°C (-4° ~ 140°F)
     Operating Temperature                                     0~45°C (32° ~ 113°F)
     Operation humidity                                    10-90% RH (non –condense)
     Enclosure                                                         Plastic
     Dimensions WxHxD                                           200 x 146 x 42.5mm
     Panel cutout dimension                                  192 x 138 mm (7.5"x5.4")
     Weight                                                  Approx. 0.85 kg (1.87 lbs)
                                                Operating System
     Operating System                       EB8000 2.0.0 or Newer                                      Windows CE.net 5.0
                                                              7
3.1 Limited Liability Warranty
         Weintek products include the isolated power supply are covered by a limited liability warranty from
    defects in material and workmanship. This warranty does not apply:
    (a) if, in the judgment of Weintek, the product fails due to damage from shipment, handling, storage, accident
         (natural and man-mad) ;
    (b) If the product fails due to misuse, including but not limit to incorrect set-up and wiring, current leakage
         from machine platform and incorrect input power;
    (c) If the product has been maintained in a manner not conforming to product's instructions or has been
         modified in any way,
    (d) If the serial number has been defaced or removed.
4.0 Dimensions of MT-607i / MT-6070iH /
3
MT-8070iH
                                                                               Bottom View
                         Front View
                                                                      Cutout dimensions:
                                                                      MT607i / MT6070iH / MT8070iH:
                                                                      192mm [7.559"] W x 138mm [5.433"] H
                         Rear View
         a     DIP SW & Reset button                 g       Com1 RS485, Com3 RS485, Com3 RS232
         b     Fuse                                  h       Com1 RS232, Com2 RS232
         c     Power connector                       i       Ethernet port (RJ-45) (MT6070iH N/A)
         d     VESA 75mm screw holes                 j       USB Host port
         e     Audio (MT6070iH N/A)                  k       USB Client port
         f     SD card slot (MT6070iH N/A)
                                                               GME8607i0_MT6070_8070iH_MT607i_Installation_101028