Basic Principles and Operation of A Transformer
Basic Principles and Operation of A Transformer
operation of a transformer
Seminar paper for course Distribution and industrial
networks
Andrea Ljubljanac
TABLE OF CONTENTS
1 INTRODUCTION...................................................................................... 1
2 STANDARDS AND PRINCIPLES ................................................................... 2
2.1 Basic transformer action ....................................................................... 2
2.2 Transformer equivalent circuit............................................................ 3
2.3 Voltage and current distribution and transformer impedance
representation ................................................................................. 4
2.4 Tap changers .................................................................................. 6
3 VOLTAGE, IMPEDANCE AND POWER RATING ............................................. 9
3.1 Voltage drop and impedance.............................................................. 9
3.2 Voltage ratio and tappings ................................................................. 9
3.3 Vector groups and neutral earthing ................................................... 10
4 THERMAL DESIGN ............................................................................... 12
4.1 Temperature rise ........................................................................... 12
4.2 Loss of life expectancy with temperature ........................................... 12
4.3 Ambient temperature ..................................................................... 13
4.4 Solar heating ................................................................................. 13
4.5 Transformer cooling classifications .................................................... 13
4.6 Selection of cooling classification ...................................................... 16
4.7 Capitalization of losses.................................................................... 16
5 CONSTRUCTIONAL ASPECTS ................................................................. 17
5.1 Cores ........................................................................................... 17
5.2 Windings ...................................................................................... 17
5.3 Tanks and enclosures ..................................................................... 18
5.4 Low fire risk types .......................................................................... 19
5.5 Underground transformers .............................................................. 19
6 ACCESSORIES .................................................................................... 20
6.1 Buchholz relay ............................................................................... 20
6.2 Sudden pressure relay and gas analyzer relay .................................... 20
6.3 Pressure relief devices .................................................................... 20
6.4 Temperature monitoring ................................................................. 21
6.5 Breathers ...................................................................................... 21
7 CONCLUSION ........................................................................................ 22
8 QUESTIONS ......................................................................................... 23
Basic principles and operation of transformer
9 HOMEWORK ........................................................................................ 24
10 LITERATURE ........................................................................................ 25
Basic principles and operation of transformer
1 INTRODUCTION
A power transformer is a passive electromagnetic device that transfers energy from one circuit
to another circuit by means of inductive coupling. Power transformers differ from other
transformer types in that they are designed to comply with regulatory requirements for mains
power interfacing, working at mains voltages and relatively high currents. The most important
specification of a power transformer is its primary to secondary transformer galvanic isolation,
which is usually specified in kV. This is a fundamental safety aspect in protecting humans from
potentially lethal earth fault conditions.
Power transformers typically have a single primary (mains side) winding and one or more
secondary windings. The secondary winding may be tapped at different points to generate
multiple voltage outputs. A power transformer operates according to Faradays Law of Induction.
Transformers are extremely efficient when operating within their design specifications.
Core type is an important consideration. Typical power transformer supplies include laminated
core. Laminations can be important as they help prevent eddy currents flowing in the core that
cause loss of efficiency. The maximum output current is specified at the point where the core is
saturated, or the windings current rating is exceeded. Power transformers are found in any
application that requires mains power.
Power transformers play an important and significant role in the power system to connecting
the subsystems and delivering the electricity to the consumers. They are one of the most
expensive elements in the power system, which is why focusing on their status of parameters is
the primary task. This seminar paper will focus on highlighting certain important aspects of
voltage selection and thermal aspects.
Voltage selection goes for determining and calculating transformer voltage ratio, the
specification of insulation levels, examples of voltage regulation, rating, tap ranges and
impedance calculations.
Thermal aspects go for specification of temperature rise and ambient conditions. Also,
constructional features of different types of a transformer in common use together with the
purpose and selection of accessories.
1
Basic principles and operation of transformer
2 STANDARDS AND PRINCIPLES
First, we will observe the phasor diagram for a single-phase transformer with a 1:1
turns ratio supplying an inductive load of power factor cosφ2.
Figure 1: Phasor diagram for a single-phase transformer with a 1:1 turns ratio supplying an inductive load of
power factor cosφ2
The whole magnetic field created by the primary is attracted into the steel core and is
encircled by the secondary winding. The actual field strength, if is considered common to
both primary and secondary transformer winding, becomes of no importance. Therefore,
only following four variables of voltage and coil winding turns remain giving the
2
Basic principles and operation of transformer
fundamental transformer expression:
U1/U2 ~ N1/N2
When a transformer is loaded, the voltage induced in the secondary winding coil drives a
current into the load. Also, the secondary current produces its own magnetic field which is
reducing (opposing) the existing field, which is why the field in the primary is reduced.
More current flows until a turns balance is reached. The final outcome is that the magnetic
field is left unchanged, comparing to the state before adding load to the secondary coil (I 1
and I2 produce equal and opposite magnetic fields). This is why we get the second
equation:
𝑁1 ∙ 𝐼1 = 𝑁2 ∙ 𝐼2
The magnetic flux levels in the core do not rise in proportion to the load current. Combining
previous two equations we get:
𝑈1 ∙ 𝐼1 = 𝑈2 ∙ 𝐼2
Transformer equivalent circuit is the essential basis for different calculations including
voltage drop or regulation under various load conditions. In Figure 2, the magnetizing circuit
is taken as a shunt-connected impedance. The magnetizing current is rich in harmonics
which must be kept in check. This is done by keeping the flux density within specified limits.
When the transformer is being energized, the transient current inrush rich in second
harmonic will result. A mentioned effect can be uncovered using transformer protection
relays in a way that they control the existence of the second harmonic component, so that
the anomalous tripping is avoided.
3
Basic principles and operation of transformer
2.3 Voltage and current distribution and transformer impedance
representation
4
Basic principles and operation of transformer
In load flow and fault studies, transformers are represented in the network
diagrams by their equivalent impedances. For two winding power transformers,
these impedances are usually represented as percentage reactance on the base of
the transformer rating. Three winding transformers can be represented in an
impedance network by three impedances, rather than a single. Both two winding
and three winding transformers have equivalent positive and negative sequence
impedances.
Transformer zero sequence impedances depend on winding vector grouping and
neutral point earthing of both transformers and/or source generators within the
system. Turns balance is normally produced within the transformer windings.
Nevertheless, under fault conditions, the zero sequence impedance results in the
extent to which the configuration allows the zero sequence current in one winding
to be balanced by equivalent ampere-turns in another winding.
Figure 4: Star/star (YNyn) transformer vector grouping with primary and secondary star points together with
source generator solidly earthed
Z0 = Z1 = Z2
Figure 5: Star/star (Yyn) transformer vector grouping with secondary star point and source generator solidly
earthed
Z0 >> Z1
In Figure 5, without primary star point earthing there is no path for zero sequence
currents on the primary side of the transformer. Therefore, zero sequence fault
currents on the secondary side are relatively small. The transformer connection
approximates to an open circuit for zero sequence components. The actual value
for Z0 depends upon the transformer magnetic circuit arising from three or five
limb constructions.
5
Basic principles and operation of transformer
2.4 Tap changers
A tap changer is a mechanism in transformers which allows for variable turn ratios
to be selected in discrete steps. Transformers with this mechanism obtain this
variable turn ratio by connecting to several access points known as taps along
either the primary or secondary winding.
Tap changers switches may be mounted separately on the side of the tank with
their own separate oil insulation, or in the main transformer tank in order to reduce
costs and result in a compact transformer design. Tap changers may be motor
driven or manually operated by a switch.
Linear arrangement is mostly used for smaller tapping ranges and results in a
simple tap changer. Reversing arrangement is commonly used for larger tapping
ranges. The coarse/fine arrangement contains some of the advantages of the
reversing arrangement but displays lower copper losses on the minimum tap
position.
The most common and economical electrical connection for double wound
6
Basic principles and operation of transformer
transformers to the main winding is at the neutral end of star connected HV
windings, though it is also possible to connect it to the delta-connected windings.
For auto-transformers, the ideal position for the tapping is at the neutral end. As
with double wound transformers, this has the advantage of a smaller, lower cost
tap changer. However, it is also possible for auto-transformers to be positioned at
the line-end taps. The line-end connection has the advantage to constant flux
density and therefore constant tertiary voltage over the tapping range.
In Figure 7 the switching sequence of the tap changer selector and diverter switch
is illustrated. The duty of the tap changer is to transfer connection from the
selected tap to a preselected neighboring tapping without interrupting the power
supply to the load. While the transfer switch is moving from contact M1 to contact
M2, the load is carried by the transition impedance (RT), which is usually a resistor.
The main contacts M1 and M2 are carrying the full load current continuously. The
diverter switch contacts T1 and T2 must be capable of sustaining arc erosion and
7
Basic principles and operation of transformer
mechanical duty resulting from making and breaking full load current. The arcing of
these contacts produces gases which saturate the neighboring oil and a barrier
must be provided to separate this oil from the main transformer oil.
In-tank tap changers have tapping winding peaks connected to the selector
contacts (maintenance free) within the main transformer oil, while diverter
switches (maintained) are enclosed in an oil-filled insulating cylinder which is piped
to its own conservator.
Bolt-on tap changers are divided into two main types:
1. Double-compartment type has a construction of separated selector contacts
from the diverter switch, in which way two main compartments are formed.
Now, they can be operated separately. Larger transformers build in the UK
prefer this type.
2. Single-compartment type is used for the lower ratings. This type of tap
changer uses selector switches which combine the function of selection and
transfer in one mechanical device.
It is notable to mention the main standard reference for power transformers, which
is IEC 60076.
8
Basic principles and operation of transformer
3 VOLTAGE, IMPEDANCE AND POWER RATING
Voltage drop happens in a transformer under secondary load conditions, due to the
leakage reactance and the winding resistance. It is most commonly expressed as a
percentage value referred to the kVA (or MVA) rating of the transformer.
Regulation of the transformer is the change in transformer terminal voltage from
no load to full load. This change matches with the volt drop appearing at the full
load. Most commonly used formula is following:
The main parameter for a transformer is the short circuit (internal) impedance. The
lowest value is limited by the minimum physical distance between windings, while
the highest is limited by the effects of the associated high leakage flux. This means
that extreme values are limited by design factor.
Three phase systems consider zero sequence impedance as well, as it determines
the magnitude of fault currents flowing between the neutral of a star-connected
winding and earth during phase-to-earth faults. This impedance depends on the
core configuration (whether it is 3 or 5 limb core) and whether or not a delta-
connected auxiliary winding is fitted.
It is always advisable to think twice before deciding on the voltage ratio for the
transformer. For example, if there is a transformer with values 132kV connecting
to the 20kV system, this does not mean that the voltage ratio is 132/20kV since we
need to take into account:
1. The 132kv voltage is not constant and may vary as much as ±10% from
the nominal value
2. Volt drop on load will lower the voltage at the 20kV terminals.
Every practical transformer will need tappings to allow selection of different voltage
ratios to suit different circumstances.
9
Basic principles and operation of transformer
majority of situations. The middle tap of a transformer is referred to as the
‘principal tap’.
On-load tappings are used for frequent changes in tapping without removing the
transformer from service. They are used in most of transmission system
applications. However, the procedure for defining voltage ratio and tapping range
often causes problems. In the standard IEC 60076-1 are defined categories of
voltage variation for transformers with tappings.
Three configurations in which three phase windings of the transformer are usually
connected are delta, a star or an interconnected star (zig-zag). The configurations
are shown in Figure 8. How the vectors are grouped and how the phase
relationship nomenclature is used are defined as follows:
Mostly the system designers are the one to decide which vector grouping
arrangement is required for each voltage level in the network, though there are
many factors influencing the decision. Important aspects from user’s point of view
are:
• Vector displacement between the systems connected to each winding of the
transformer and ability to achieve parallel operation
• Provision of a neutral earth point or points, where the neutral is referred to
earth either directly or through an impedance
• The practicality of transformer design and cost associated with insulation
requirements
• The Z winding reduces voltage unbalance in systems where the load is not
equally distributed between phases and permits neutral current loading with
inherently low zero-sequence impedance. Therefore, it is often used for
earthing transformers.
11
Basic principles and operation of transformer
4 THERMAL DESIGN
There are several ways of producing heat in a transformer. Most significant ones
are the heat produced in a transformer due to the flow of load current through the
resistance of the winding conductor, where load loss exists, and due to the heat
production in the magnetic core, where there is no load loss. Some other sources
of heat include dielectric heating of insulating materials, eddy current heating in
conductors and support steel structures. Thermal design of a transformer aims to
remove this heat economically and effectively, in a way to avoid any unwanted
deterioration of components.
The heat is produced in the windings of the conductor. Windings are insulated with
a paper type wound around them. It is saturated with oil, since the winding is
located in the oil inside of the transformer tank, so this insulation is good for
protecting (insulating) from the earthed parts and other windings.
Heat from the conductor moves through the paper type insulation, then in the bulk
of oil and it is finally conducted away from the winding, which results in dissipation
of the heat into the air. To prevent damage of the conductor, the maximum
temperature is determined, which is on average 98°C.
Generally, not all the parts of a winding are the same temperature. The warmest
part is called the “hot spot”, which location is not always known, but it can be
determined with the infrared imaging technique. Besides hot spot, also “average
winding temperature” is determined. From the researches, it is known that the “hot
spot” temperature is about 13°C above the average winding temperature.
However, when the transformer is unloaded the conductor temperature is
practically the same as the ambient temperature. From these conclusions, follows
the formula for the temperature of the hot spot:
Based on the IEC specification and conclusions written above, following can be
said:
98°C ≥ 20°C + average winding temperature rise + 13°C
Which means that the average winding temperature rise should be ≤65°C, which is
a basis of the IEC specification.
In the previous segment, it was mentioned that the insulating materials are
determined by the maximum temperature, which does not mean that immediate
insulation failure would happen, but that the insulation would have shortened
lifespan. The estimated lifespan is determined by the law due to Arrhenius:
The Arrhenius effect equalizes the periods of operation with the insulation above
12
Basic principles and operation of transformer
the “normal life” temperature with the periods of the lower temperature, where the
life is above normal. The good example is the ambient temperature of insulator
during winter and summer, which significantly changes, but after all the lifespan is
equalized.
Ambient temperature is not the same everywhere around the world. That means
that the average winding temperature rise would drop (or rise) if the ambient
temperature is higher (lower).
𝑁
1
𝑇𝑎1 = 20𝑙𝑜𝑔10 [∑ 10𝑇𝑎/20 ]
𝑁
1
The weighted value is designed to take proper account of the Arrhenius law.
Previously, one method of cooling the transformer has been mentioned, where the
heat is conducted to the oil from the windings and core, after which is transmitted
to the surrounding air at the tank surface. Practically, only the smallest pole-
mounted distribution transformers have enough tank surface to dissipate the
internal heat effectively (Figure 10.a). With larger transformers, the surface area
for heat dissipation is deliberately increased by attaching radiators to the tank. A
1000kVA hermetically sealed transformer with radiators is shown in Figure 10.b.
13
Basic principles and operation of transformer
Figure 10: Cooling arrangements: a) Tank surface only and b) Radiators on a tank
With even larger transformers, separate cooler banks are used as indicated in
Figure 11.
The only mentioned and first described method of cooling has no moving parts. It
functions in a way when the oil is warmed inside the tank it raises up (to the tops
of the radiators) and as the oil cools down it falls to the bottom of the radiator and
then back into the bottom of the tank. This is called natural circulation of cooling oil
and it repeats itself.
14
Basic principles and operation of transformer
There are several ways to increase cooling efficiency, like adding fans to the
radiators to blow cooling air across the radiator surfaces. This method is shown in
Figure 12.
Another possible increase in efficiency is achieved by pumping the oil around the
cooling circuit, and in that way boosting the natural circulation.
The classification done in the terms of IEC cooling classification codes gives the
user codes which indicate the primary cooling medium (the medium extracting the
heat from the windings and core) and the secondary cooling medium (the medium
which removes the heat from the primary cooling medium).
The following codes are used:
With coding method it is possible to choose kind of primary cooling medium and it’s
type of circulation and kind of secondary cooling medium and it’s type of circulation
(i.e. an oil-immersed transformer with natural oil circulation to radiators dissipating
heat naturally to surrounding air is coded as ONAN, while adding fans makes it
ONAF; dry type transformer uses only two-letter code, AN).
15
Basic principles and operation of transformer
4.6 Selection of cooling classification
ONAN
This type of cooling requires zero to minimum maintenance, as it has no
mechanical moving parts. Numerous developing countries prefer this type of
cooling because of the reliability, but there is an increasing cost penalty as sizes
increase.
ONAF
This type has fans fitted to the radiators, and it has the rating between 15% and
33% greater than with the fans not in operation. Therefore, the transformer has an
effective dual rating under ONAN and ONAF conditions. It can be specified as
20/25MVA ONAN/ONAF. However, it is not always desirable to use ONAN/ONAF
transformers, as in the example of transformers working in parallel. In this case,
fans would run very rarely and will produce a loud noise, which can be a problem in
environmentally sensitive areas.
OFAF
Generator transformers and power station interbus transformers often use OFAF
cooling. This cooling method is forcing the oil circulation and blowing air over the
radiators. The maintenance burden is increased owing to the oil pumps, motors
and radiator fans required. Good maintenance procedures are recommended.
ODAF/ODWF
These are special cooling categories where the oil is directed by pumps into the
closest proximity possible to the winding conductors. The external cooling medium
can be air or water. Because of the design, the operation of the oil pumps, cooling
fans, or water pumps is crucial to the rating obtainable and such transformers may
have rather poor naturally cooled (ONAN) ratings. Such directed and forced cooling
results in a compact and economical design suitable for use in well-maintained
environments.
Lower investment in materials will result in initial lower costs, but a shorter life of
transformer, when on the other side, investing a bit more initially in the
transformer can pay off in a way of a longer lifetime of the transformer.
The total cost of the transformer is called the capital cost. In most cases, the
consultant or electrical supply utility will specify separate capitalizing factors for the
load and no-load losses and typical figures for UK transmission transformers are:
no-load loss capitalization rate £4000/kW; load loss capitalization rate £650/kW.
The transformer manufacturer can then easily calculate the capitalized price
following the formula:
Capitalized cost = selling cost + 4000 x no-load losses (kW) + 650 x load loss (kW)
16
Basic principles and operation of transformer
5 CONSTRUCTIONAL ASPECTS
5.1 Cores
5.2 Windings
17
Basic principles and operation of transformer
• Three winding
Third winding is added because a third voltage level is involved or for design
reasons. A star/star transformer is often combined with third (delta-connected)
winding. This can be for numerous of reasons:
- In order to reduce the transformer impedance to zero sequence currents, so
that earth fault currents of sufficient magnitude can flow to operate the
protection
- In order to suppress the third harmonics due to the no-load current in the
earth connection when the neutral is earthed
- In order to stabilize the phase-to-phase voltages under unbalanced load
conditions
- In order to enable overpotential testing of large high voltage transformers to
be carried out by excitation at a relatively low voltage
- In order to provide an intermediate voltage level for supply to an auxiliary
load where a tertiary winding offers a more economical solution than a
separate transformer
Besides these advantages, there are still some disadvantages concerning three
winding cores, as it increases costs of a transformer by 6% to 8% which follows
also additional losses of 5%.
• Auto-transformers
This type of transformer has only one winding. Prefix auto refers to the single coil
acting alone (not to any kind of automatic mechanism). Portions of the same
winding act as both the primary and the secondary sides of the transformer (if a
tap is made part way down the winding). Since having just one winding, auto-
transformers have advantages of often being smaller lighter and cheaper than
typical two winding transformers. A disadvantage is not providing electrical
insulation between primary and secondary circuits. Auto-transformers are usually
star connected, which means that both high and low voltage systems have the
same neutral. This is only desirable in transmission systems where solid earthing of
neutrals is common at all voltage levels.
• Oil preservation
The oil inside transformer tank acts as heat transfer medium and an insulation. The
oil must be dry and free from contaminants, to keep good insulating properties.
This is done by sealing the oil inside the tank so that there is no contact with the
atmosphere. Also, there has to be left some free area to allow expansion in volume
of oil because of temperature changes. Some of the methods to be used depending
on the rating of the transformer, its location and the particular policy of the
manufacturer are:
- Sealed rigid tank – The tank is not fully filled with oil. The free space above
oil is filled with a dry gas, which has no chemical reaction with the oil. The
tank should be strong because of the large pressure changes inside of it.
- Sealed expandable tank – Not all the transformers can use this technique.
The tank is fully filled with oil, but the surfaces of the tank are flexible to
allow the expansion of oil due to temperature changes.
- Positive pressure nitrogen – It is applied to the large transformers. It is
similar to the sealed rigid tanks, just that it has venting for minimizing
pressure changes.
- Conservator (with breather) – Applied to any size of transformers. The tank
18
Basic principles and operation of transformer
is filled with oil and changes in volume are allowed by an expansion tank
(conservator) mounted above the main tank. A conservator has a vent to the
atmosphere, in which an air-drying device is located.
- Conservator (with diaphragm seal) – The expansion tank contains a flexible
synthetic rubber diaphragm which allows for oil expansion, but seals the oil
from the atmosphere.
It is crucial that the quality of tank welding, gasketing, and painting is carefully
specified and inspected prior to release from the manufacturer’s works, in order to
avoid oil leakage.
The possible situations where a transformer may be involved in a fire fall in three
categories:
- There has been an internal fault that leads to ignition and subsequent
burning of the materials within the transformer. However, arcing faults
should be cleared by overcurrent devices in short time.
- The transformer is located in the enclosed space involving materials such as
wood, which could ignite the transformer.
- The transformer is located in an enclosure in which a fire involving
hydrocarbon fuels or plastic materials occur taking the transformer in
flames.
When comparing the dry type and non-flammable liquid-immersed types to the
mineral oil-immersed units, the difference in cost is noticeable (latter are the
cheapest).
The fire protection of transformers is usually done by controlling the oil spillage
from a tank. For outdoor installations, additional protection exists, represented by
a temperature sensor located above the transformer, which initiates water spray or
foam system to extinguish the fire.
19
Basic principles and operation of transformer
6 ACCESSORIES
Beside elementary assembly of transformers, there are also additional accessories
which may or may not be obligatory for a transformer. Those are accessories for
protection, safety purposes, and monitoring.
Sudden pressure relays are usual accessories for sealed transformers, while gas
analyzer devices are only used on large important transformers.
Sudden pressure relay detects internal pressure rises due to falls, and gas devices
can be used to detect an accumulation of gases.
20
Basic principles and operation of transformer
6.4 Temperature monitoring
Oil and winding temperature is monitored in all but small (less than 200 kVA)
distribution transformers. If a transformer is correctly loaded and specified, it
should not produce excessive temperatures.
Winding temperature indicator usually has a feature to initiate automatic switch-on
and switch-off of cooling fans and oil circulation pumps. This is how ONAN/ONAF
will automatically switch from ONAN to ONAF (and vice versa), according to the
transformer loading conditions. Temperature monitoring can also help in detecting
“hot spot” winding temperature. Oil temperature monitor is usually a capillary type
thermometer with the sensor located near the hottest oil in the tank (i.e. at the top
of the tank, before hot oil enters the radiators). Both oil and winding temperature
monitors are fitted with contacts which can be set to operate at the desired
temperature. These contacts are used for alarm and trip purposes.
6.5 Breathers
Breathers are places in the vent pipes of conservators as the volume of oil
contracts on transformer cooling. They use the moisture absorbing crystals, which
are replaced when the color of them changes (this means that they are saturated
with moisture).
The alternative way is to continuously separate moisture dissolved in the
transformer oil by freezing the moisture out of the air by passing it over
refrigerating elements and then evaporating it off to the atmosphere. Breather that
uses this technique is called Drycol breather (Figure 15), which is commonly used
in the UK. This technique improves the life-span of the transformers, as
researchers state.
Some other accessories used in the transformers are also core earth link, oil level
gauge, tap changer accessories and oil sampling valve.
21
Basic principles and operation of transformer
7 CONCLUSION
In this seminar, basic components, standards, and principles of a transformer have been
described. When applying power transformer to the wanted part in the power network, it is
important to follow requirements and specifications given, together with the use of essential
monitoring, safety, and reliability accessories. Otherwise, significant damages may occur.
When choosing the transformer for one’s application, the geographical location should be taken
into consideration too, as the thermal design is dependent on the average ambient temperature,
which varies around the world. Accordingly, should the cooling systems be chosen and used.
Power transformers are a crucial part of the power systems. Considering this fact, continuous
monitoring and diagnostics of transformers increase stability, reliability, and safety as well as their
life-span. Also, non-obligatory, but desirable accessories may be used, such as Buchholz relay,
sudden pressure relay, pressure relief devices, breathers.
22
Basic principles and operation of transformer
8 QUESTIONS
o Off-circuit
o Off-load
o On-load
23
Basic principles and operation of transformer
9 HOMEWORK
a) Find the volt drop of the three-phase transformer with a leakage reactance
of 6.6%, and resistance of 2.4%. The transformer has manufacturer rating
given as follows:
U1/U2 = 12,7kV/0,23kV
S = 150 kVA
P = 120 kW
R = 2.4%
X = 6.6%
Solution:
𝑃 120
𝑝 = 𝑐𝑜𝑠𝜑 = = = 0.8
𝑆 150
Finally, we have:
Solution:
24
Basic principles and operation of transformer
10 LITERATURE
25