Cooling Tower
Fungsi dari cooling tower adaah untuk mendinginkan kembali air
proses. Prinsip operasi pada cooling tower adalah terjadinya proses
perpindahan massa dan perpindahan panas secara simultan.
Tipe Cooling Tower
1. Atmospheric spray tower
2. Chimney-assisted natural draft towers
3. Hyperbolic fan assisted towers
4. Counterflow-induced draft towers
5. Crossflow-induced draft towers
6. Forced draft towers
7. Wet-dry towers
Atmospheric,
dependent on wind
velocity.
Hyperbolic stack natural draft
Hyperbolic assisted with forced draft fans
Counterflow-induced draft
Crossflow-induced draft.
Forced draft.
Induced draft with surface precooler for very hot water; also called wet/dry tower
CONTOH SOAL
Diambil dari illustration 7.11, Treybal, 1980
A plant requires 15 kg/s (1984 lb/min) of cooling water to flow through
its distillation-equipment condensers, thereby removing 270 W (55270
Btu/min) from the condensers. The water will leave the condensers at
45 oC. It is planned to cool the water for reuse by contact with air in an
induced-draft cooling tower. The design conditions are as follows:
entering air at 30 oC dry-bulb, 24 oC wet-bulb temperature, water to be
cooled to within 5 C of the inlet-air wet-bulb temperature, i.e., to 29 oC;
an air/water-vapor ratio of 1,5 times the minimum. Makeup water will
come from a well at 10 oC, hardness 500 ppm dissolved solids. The
circulating water is not to contain more than 2000 ppm hardness. For
the packing to be used, Kya is expected to be 0,9 kg/m3.s.ΔY (202
lb/ft2.h. ΔY), for a liquid rate at least 2,7 kg/m2.s and a gas rate 2,0
kg/m2.s (1991 and 1474 lb/ft2.h, respectively. Compute the
dimensions of the packed section and the makeup water requirement.