INSTRUCTION MANUAL FOR
83-488-100 Revision B
     MODEL
     SERIAL NUMBER
        LAMBDA EMI
405 ESSEX ROAD, NEPTUNE, NJ 07753
        TEL: (732) 922-9300
        FAX: (732) 922-9334
                                TABLE OF CONTENTS
Description                                               Page
   1 GENERAL                                                 1
     1.1 INTRODUCTION                                        1
     1.2 SPECIFICATIONS                                      2
   2 INSTALLATION                                            6
     2.1 SAFETY PRECAUTIONS                                  6
     2.2 INITIAL INSPECTION                                  6
     2.3 MOUNTING AND COOLING REQUIREMENTS                   6
     2.4 ORIENTATION                                         6
     2.5 GROUNDING AND INPUT AC POWER CONNECTION             7
     2.6 INTERNAL FUSES                                      7
     2.7 CONNECTING HIGH VOLTAGE OUTPUT                      8
     2.8 EXTERNAL FILTERING                                  8
     2.9 CLEANING                                            8
   3 OPERATION                                               9
     3.1 ‘L’, ‘S’, & ‘OEM’ MODELS                            9
     3.2 REAR PANEL                                         11
     3.3 FRONT PANEL CONTROL (‘L’ MODEL ONLY)               12
     3.4 FRONT PANEL INDICATORS (‘L’ MODEL ONLY)            13
     3.5 FRONT PANEL INDICATORS (‘L’ & ‘S’ MODELS ONLY)     13
     3.6 REMOTE CONTROL (‘L’, ‘S’, & ‘OEM’ MODELS)          14
     3.7 INITIAL CHECK-OUT PROCEDURE                        16
   4 APPLICATIONS                                           17
     4.1 DETERMINING CAPACITOR CHARGE TIME                  17
     4.2 VOLTAGE REVERSAL                                   17
     4.3 PARALLELING UNITS                                  18
     4.4 MEASURING HIGH VOLTAGES                            18
     4.5 DETERMINING AC LINE CURRENT                        19
     4.6 OPERATION AS A DC POWER SUPPLY                     19
   5 MAINTENANCE AND TROUBLESHOOTING                        20
     5.1 SAFETY PRECAUTIONS                                 20
     5.2 CALIBRATION                                        20
     5.3 MAINTENANCE                                        20
     5.4 INSPECTING THE HV OUTPUT CABLE                     20
     5.5 TROUBLESHOOTING                                    21
                                  LIST OF FIGURES
Description                                               Page
Figure 1:   XR802 Series Block Diagram                       1
Figure 2:   Output Power and Current                         2
Figure 3:   Mechanical Details                               5
Figure 4:   Input AC Power Connections                       7
Figure 5:   Model XR802L                                     9
Figure 6:   Model XR802S                                    10
Figure 7:   Model XR802 OEM                                 10
Figure 8:   Rear Panel                                      11
Figure 9:   Model XR802L Front Panel                        12
                              TABLE OF CONTENTS
Description                                       Page
Figure 10: Remote Control Example                   15
Figure 11: Current Transformer                      17
Figure 12: Peak Measurements During Pulsing         19
                                  1 GENERAL
1.1 INTRODUCTION
   The high regulation XR802 Series high voltage power supplies are designed for
   charging capacitors in laser systems and other pulsed power applications. The model
   XR802DC is a compact high efficiency high voltage DC power supply with the addition
   of an externally mounted output filter capacitor. Depending upon the application, the
   stored energy requirement of this capacitor can be quite low making the XR802DC an
   ideal power supply for applications such as compact high power RF amplifiers for
   HDTV applications.
   The XR802 Series is available in three different configurations; the XR802L, XR802S
   and XR802 OEM. These three different configurations allow the user to choose the
   method of controlling the power supply best suited to the overall system requirements.
   All three have the same mechanical dimensions, are air cooled and can be mounted in
   a standard 19" rack occupying only 8.75" of rack height. The XR802 Series provides
   up to 6,000 Watts of average power and can be paralleled for higher total system
   power.
   The XR802 Series power supply incorporates a high-frequency IGBT Series-resonant
   inverter for efficient generation of the output power. A high-performance control
   module precisely regulates the output voltage, automatically compensating for line,
   load, temperature, rep rate, and program voltage variations. Normal external fault
   conditions such as line dropout, open or short circuit load, HV arc and overtemperature
   will not damage the unit.
             AC FRONT END                                  HV OUTPUT         HV
    INPUT                                    HIGH FREQ.
    POWER    FUSES                FILTER                   SECTION           OUTPUT
             INRUSH LIMIT                    INVERTER      STEP-UP XFMR
             RECTIFIER                                     RECTIFIER
             AUX POWER                                     FILTER
                                                           HV DIVIDER
                                              CONTROL
                                               BOARD
                                              CONTROL
                            Figure 1: XR802 Series Block Diagram
                                    Page 1 of 21
                                 83-488-100 Rev. B
   The output voltage of the XR802 power supply is fully adjustable over each range.
                               100
                    % USABLE 75
                     OUTPUT
                     POWER   50
                                25
                                       25   50   75   100
                                      % OUTPUT VOLTAGE
                                     Figure 2: Output Power
1.2 SPECIFICATIONS
   OUTPUT VOLTAGE/CURRENT
   The output voltage is fully adjustable over each range. Recommended control range
   for full regulation is 10% to 100% of Full Scale. The output current from 100% to 10%
   of rated voltage is constant. This provides the full 6000 Watts of average output power
   at 100% of rated voltage.
                  Voltage Range           Max Current         Max Current
                                         Cap-Charging             DC
                      0-1 kV                14.0 A               8.0 A
                      0-2 kV                 7.0 A               4.0 A
                      0-4 kV                 3.5 A               2.0 A
                      0-5 kV                 2.8 A               1.6 A
                     0-10 kV                 1.4 A              800 mA
                     0-20 kV                700 mA              400 mA
                     0-30 kV                467 mA              260 mA
                     0-40 kV                350 mA              200 mA
                     0-50 kV                280 mA              160 mA
   CHARGE RATE:                                  DC POWER OUTPUT:
   6000 J/sec average                            8,000 watt
   REGULATION:
   ±0.1% to 250 Hz      Standard
   ±0.3% to 1 kHz       Standard        ±0.1% to 1 kHz Available
   Total pulse-to-pulse variation with no series terminating resistance/inductance.
   STABILITY
   <0.2% per hour after 1 hour warm up.
   PROGRAMMING LINEARITY
   +/-1.0% of full-scale @10% to 100% of rated output.
                                    Page 2 of 21
                                 83-488-100 Rev. B
PROGRAMMING ACCURACY
+/-1.0% of full-scale @10% to 100% of rated output.
INTERNAL STORED ENERGY
0.5 Joules Max.
EFFICIENCY:
85% minimum at full load and nominal line.
A.C. POWER INPUT CONNECTIONS
5 positions VDE/IEC Approved Terminal Block
Ø1, Ø2, Ø3, N,       for 400 VAC input voltage
Ø1, Ø2, Ø3,        for 209 VAC input voltage
INPUT VOLTAGE/CURRENT
208V Configuration: 180-264 V, 3 Phase, 50/60 Hz, 45 A max
400V Configuration: 360-440 V, 3 Phase, 50/60 Hz, 25 A max
POWER FACTOR:
Passive PFC. 85% minimum at full power and nominal line input
INRUSH CURRENT
Limited to below full power current.
PROTECTION FEATURES
  Output short circuit and HV arc-to-ground any time during operation.
  Open circuit at turn-on, will not damage power supply.
  Remote HV Safety Interlock loop
  AC input power contactor (Standard on ‘L’, ‘S’; Optional for ‘OEM’)
  Shutdown on over-temperature, overvoltage, and open interlock.
  Highly buffered I/O for noise immunity in severe electrical environments.
COOLING
Forced air with internal fan, -20°C to 40°C inlet temperature,
ENVIRONMENTAL CONDITIONS
The power supply is safe under the following conditions:
   Altitude up to 3000m (9900 ft) operating, nonoperating 12121m (40000 ft)
   Temperature 5°C to 40°C
   Storage temperature - 40°C to 85°C.
   Maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to
   50% relative humidity at 40°C.
   Fluctuations not to exceed the stated input voltage range.
   Transient overvoltages according to Installation Categories (Overvoltage
   Categories) I, II and III in accordance with IEC 1010, current revision.
   Operation only in horizontal position for w/Oil Insulated HV Output.
                                 Page 3 of 21
                              83-488-100 Rev. B
HV OUTPUT CONNECTOR AND CABLE
 Output Voltage     Connector                           Cable
 <= 6.0 kV          Amphenol ‘HN’                       RG-8/U
 > 6.0 kV           Proprietary                         Dielectric Sciences 2214 80kV
10'coaxial hv cable with grounded shield standard. Other lengths available.
METERING ACCURACY
All ±2%
FRONT PANEL
“L” Model
   3 ½ digit voltage & current meters.
   10 segment voltage and current trend bar graphs.
   Multi-turn HV output level control.
   HV ON, HV OFF, and push to view push button.
   3 position key switch removable in Off position.
“L & S” MODELS
   HV ON Indicators
   HV OFF Indicators
   INHIBIT Indicators
   END OF CHARGE Indicators
   LOAD FAULT Indicators
   OVER TEMPERATURE Indicators
SHOCK
25 Gpk, half Sine wave 11mSec, x, y, z axis (3 total)
VIBRATION
MIL-STD-810E Method 514.4 basic transportation
Common carrier 10-500Hz, 0.015 g2/Hz
Duration 1 Hour
SIZE
Standard 19" rack mount. 8.75" high, 17" deep. Refer to Figure 1 for details.
WEIGHT
80 Lbs., 36 kg      w/Oil Insulated HV Output
60 Lbs., 27 kg      w/Air Insulated HV Output (≤6kV)options:
ALL MODELS:
   Custom output voltages
   0 - 5 VDC Programming
   ±0.1% regulation to 1kHz.
   Remote output voltage sensing
   Rack mount slides
   EMI filter
                                Page 4 of 21
                             83-488-100 Rev. B
          High rep rate unshielded HV connector with silicon HV cable
          Custom length HV cable.
     XR802 OEM:
       Front panel circuit breaker
       Internal AC contactor.
                                 Figure 3: Mechanical Details
                                                  #   "   $       %
    ($
0   ("/ / 1
                                                 )(*(+(
                                                 ,-,.+/ ,
                                    %(
                                0    (//1
                                                      &# '
                                                                                  ("
                                                                               0 "(%/ / 1
                                                                          ("
                                                                      0   //1
                   ($"
                0 %( / / 1
                 "($
               0 "( / / 1
                        %(
                    0    (//1
                                  ($"
                             0#$ ($/ / 1
                                    $(
                                 0# (//1
                                              Page 5 of 21
                                           83-488-100 Rev. B
                              2 INSTALLATION
2.1 SAFETY PRECAUTIONS
    The user should be aware that if the equipment is used in a manner not specified by
    the manufacturer, the protection provided by the equipment may be impaired.
    All model XR802 power supplies contain hazardous voltage and energy. The power
    supply must only be operated by qualified personnel who have read this operator'    s
    manual and are familiar with the operation, hazards and application of the power
    supply. Proper care and judgment must always be observed. Ensure all covers are in
    place and securely fastened and the required grounding and cooling is supplied before
    connecting input AC power. Proper grounding from the input AC power is required to
    reduce the risk of electric shock. Use extreme caution when connecting input AC
    power and never apply the incorrect input power. Use extreme caution when
    connecting the high voltage output cable. Ensure all load capacitors are completely
    discharged prior to connection and never handle the output cable when the power
    supply is operating. Always replace fuses with the same type and Volt/Amp ratings.
    Never attempt to operate the power supply in any manner not described in this
    manual. Never remove DANGER or WARNING labels from the power supply, and
    replace lost or damaged labels immediately. The power supply should only be serviced
    by EMI factory qualified personnel.
2.2 INITIAL INSPECTION
    The shipping container should contain the following items: power supply, HV output
    cable, male 25-pin "D" remote control connector, test data sheet and operator'       s
    manual. Examine the items immediately for damage. Locate the serial number label on
    the side of the power supply and verify the model number, the input voltage rating and
    the output voltage rating and polarity. In the event of any damage promptly notify the
    transportation company and EMI customer service.
2.3 MOUNTING AND COOLING REQUIREMENTS
    The power supply should be mounted in a standard 19" EIA enclosure or equivalent.
    Chassis support brackets or rails must be added to the bottom of the power supply for
    proper weight distribution. In all cases adequate clearances must be provided for
    proper air flow and cable bends. Generally, at least 4" of clearance should be allowed
    at the rear of the power supply and 1" at the sides.
    When operating in an enclosed system, care must be taken to ensure the ambient inlet
    air to the power supply does not exceed the maximum operating temperature of 40°C.
    this often requires addition of a system heat exchanger.
2.4 ORIENTATION
    Power supplies with air H.V. sections (output voltage 6kVcan be operated in
    any orientation/position. Oil Insulated power supplies must be operated in a
                                   Page 6 of 21
                                83-488-100 Rev. B
   level position. More than a quarter of an inch (5.1mm) difference in height in any
   direction could cause an arcing condition in the high voltage tank.
2.5 GROUNDING AND INPUT AC POWER CONNECTION
   Proper grounding from the input AC power is required to reduce the risk of electric
   shock. The metal chassis of the power supply is grounded through the green/yellow
   earthing wire at the input AC power terminal block. Use extreme caution when
   connecting input AC power and never apply the incorrect input power. Connect the
   three lines of the input power to the L1, L2, L3 terminals and the earth ground to the
   terminal marked with the ground symbol. No neutral connection is required for the
   200V (180-264VAC) configuration If the power supply was purchased with the 400V
   (340-460VAC) configuration, connect the neutral wire to terminal marked N. The power
   supply cannot be operated from a single phase line. Refer to Section 4 "Applications",
   to calculate line currents for various operating conditions such as reduced power or
   charging very large capacitor banks.
   For input power connection use wire with min 8 AWG [0.129” (3.264 mm) diameter]
   and 600V insulation. External switch or circuit breaker (rating 40A/phase for 208VAC,
   30A/phase for 400VAC) has to be provided. Circuit breaker must be all pole mains
   disconnect. The location of the circuit breaker or switch must be as close to the supply
   as practically possible (within reach of the operator).
                            L1        L2       L3        N
                                 Figure 4: Input AC Power Connections
2.6 INTERNAL FUSES
   All internal fuses must be replaced by a fuse of proper rating and type. All the fuses
   are listed in the following table.
     Reference Designation          Location
                                                    60A, FAST, 300V for 208VAC, Class T
            F1, F2, F3
                                                    30A, FAST, 600V for 400VAC ,Class T
                                   VNR Board
              F4, F5                                2.5A, SLOW, 250V (5mm x 20mm)
              F6, F7                                3.15A, SLOW, 250V (5mm x 20mm)
               F1                  Aux Board        PTC Fuse, 2.5A, 50V
               F1                 Control Board     250mA, SLOW, 250V, 5mm x 20mm
                                     Page 7 of 21
                                  83-488-100 Rev. B
2.7 CONNECTING HIGH VOLTAGE OUTPUT
   Ensure that the power supply is off and disconnected from the input power and
   that all load capacitors are discharged and shorted to ground before making any
   connections. Never handle the HV cable during operation.
   Always use the HV connector and cable provided with the power supply or an
   equivalent substitute provided by ALE Systems. Fully insert the connector end of
   the HV cable and tighten the locking nut only "hand tight".
   When operating above 20kV and 200 Hz rep rate it is recommended that a silicone
   grease (such as Dow Corning DC-4) be used on the HV cable before insertion into the
   HV connector. This displaces the air in the connector and reduces long term corona
   effects.
   The HV cable shield is connected to the power supply chassis and should be used as
   the HV return. An additional grounding stud is provided adjacent to the HV connector
   and should also be connected to the HV return. The standard shielded HV cable can
   contact earth ground without consequence. The optional unshielded silicone HV cable
   can also contact ground, but isolating it will minimize the effects of corona in the
   system.
   Keep the minimum HV cable bend radius greater than 4" to minimize stress on the
   insulation. Keep the HV cable as distant as possible from the input power and the input
   control signals.
   Some peak current will flow out of the power supply during discharge and return
   through the HV return and system chassis. This current comes from voltage reversal in
   underdamped systems and from normal discharge of filter and cable capacitance. The
   path for this current should not parallel control signal returns since the resulting
   voltages could interfere with normal system operation. When due to voltage reversal at
   high rep rates, this current could damage the power supply. Generally a resistor in
   series with the HV output can be added to limit this current to an acceptable level.
   Refer to Section 4 "Applications" for more information.
2.8 EXTERNAL FILTERING
   An external line filter is required to insure compliance with EN55011 emission
   standards. A line filter is available from Electronic Measurements, Inc. for the
   customer’s integration into his system.
   This filter must be installed in the customer’s cabinet in such a manner as to minimize
   RF coupling from the HV DC output onto the AC mains. Due to the variations in the
   final application, it is the customer’s responsibility to insure the completed system
   complies with any applicable EMC standards.
2.9 CLEANING
   Generally, no cleaning is required. If excessive dust is collected it can be wiped off
   with a damp rag. All voltage to the supply must be disconnected and the output
   discharged before attempting to clean the unit.
                                   Page 8 of 21
                                83-488-100 Rev. B
                                 3 OPERATION
3.1 ‘L’, ‘S’, & ‘OEM’ MODEL
    MODEL XR802
    This model has full front panel instrumentation for use in laboratory, prototype or OEM
    systems. The XR802L can be operated either from the front panel or from the rear
    panel remote control connector. The front panel includes power on/off, remote/local
    and HV on/off switches, output voltage adjust, view set switch, digital voltage and
    current meters, quick reference bar graphs and status indicators. An internal AC
    contactor is included which is controlled by the front panel power switch. A BNC
    connector is provided on the rear panel for easily connecting a pulsed INHIBIT signal.
    The model XR802L can be operated as a “master” unit in parallel with several model
    XR802S “slave” units for increased output power. Refer to Section 4 “Paralleling
    Units”.
                                  Figure 5: Model XR802L
                                    Page 9 of 21
                                 83-488-100 Rev. B
MODEL XR802S
This model has only a power switch and status indicators on the front panel. It must be
operated through its remote control connector and can function as a standalone unit or
in parallel with other units. Several model XR802S units can be paralleled as "slaves"
controlled by either a "master" XR802L or a single remote control circuit. An internal
AC contactor is included which is controlled by the front panel power switch.
                              Figure 6: Model XR802S
MODEL XR802 OEM
This model has a blank front panel and is operated the same as an XR802S, from the
remote control connector only. It can function as a standalone unit or in parallel for
increased output power. The basic model XR802 OEM is supplied by externally
controlled AC power. It can also be configured with either an internal AC contactor or
front panel circuit breaker option.
                            Figure 7: Model XR802 OEM
                               Page 10 of 21
                             83-488-100 Rev. B
3.2 REAR PANEL
   Figure 8 shows the rear panel of the model XR802L. The DB-25 Female REMOTE
   connector is used to control the power supply when the CONTROL KEY SWITCH on
   the front panel is in the REMOTE position.
   The INTERLOCK terminal block (at 24 VAC) can be connected to system interlocks to
   disable the power supply when opened. Jumpering the two terminals together allows
   the power supply to operate. The external interlock switch contacts must have a
   minimum of current rating of 250 mA. No other electrical connections should be made
   to these terminals. The interlock terminals should not be connected to ground. Ground
   connection will disable power supply.
   The INHIBIT connector allows for easily connecting a pulsed INHIBIT signal when
   operating from the front panel. The INHIBIT signal in the REMOTE connector can be
   used when operating in remote control mode.
   The SLAVE connector is used to control model XR802S/XR802 OEM power supplies
   operating in parallel with an XR802L "master" unit. The model XR802S and model
   XR802 OEM do not have the INHIBIT and SLAVE connectors.
                                     Rear Panel Connectors
    Connector    Type                        Function                        Notes
    HV Output    Proprietary >6kV            Coaxial HV output               Ground referred
                 Amphenol ‘HN’ <6kV
    REMOTE       DB-25 FEMALE                Power supply control input      ‘L’, ‘S’, & ‘OEM’
                                             from user
    SLAVE        DB-25 MALE                  Power     supply   control      ‘L’ version ONLY
                                             output from master
    INHIBIT      BNC Female                  High speed HV inhibit           0-40uS Response
    SENSE        BNC Female                  Remote Sense Input              ‘RS’ Option Only
    INTERLOCK    2 Position Terminal Block   Safety Interlock                Requires isolated
                                             Opens AC contactor              switch. 500mA AC
                                                                   L1   L2   L3
                                   Figure 8: Rear Panel
                                  Page 11 of 21
                                83-488-100 Rev. B
3.3 FRONT PANEL CONTROL (‘L’ model only)
    POWER SWITCH:
    Connects AC input power to the control circuitry and closes the internal AC contactor if
    the interlock is closed.
    CONTROL SWITCH:
    Directs the power supply to take on/off and voltage program commands from either the
    front panel (LOCAL position) or the remote control connector (REMOTE position). The
    OFF position disables the power supply regardless of other commands.
    HV ON SWITCH:
    Turns on the high voltage output to the level set by the HV adjust knob. Also used with
    HV OFF to reset latched fault conditions: overvoltage, open circuit, over-temp, AC
    under-voltage, and interlock open. Resets latched faults.
    HV OFF SWITCH:
    Turns off the high voltage output. HV OFF is used to reset the latching fault conditions.
    VOLTAGE ADJUST:
    Clockwise increases the output from zero to maximum, 10 turns full scale.
    VIEW SET:
    Previews the voltage and current adjust set point before HV ON.
                            Figure 9: Model XR802L Front Panel
                                    Page 12 of 21
                                  83-488-100 Rev. B
3.4 FRONT PANEL INDICATORS (‘L’ model only)
    VOLTAGE METER
    Displays the PEAK output voltage in kV. When ‘VIEW SET’ is depressed the display
    will indicate the set point voltage.
    VOLTAGE BAR-GRAPH
    Displays the REAL-TIME output voltage as a percent of rating. When ‘VIEW SET’ is
    depressed the display will indicate the set point voltage.
    CURRENT METER
    Displays the REAL-TIME output current in Amperes. When ‘VIEW SET’ is depressed
    the display will indicate the maximum current.
    CURRENT BAR-GRAPH
    Displays the REAL-TIME output current as a percent of rating. When ‘VIEW SET’ is
    depressed the display will indicate the set point voltage.
3.5 FRONT PANEL INDICATORS (‘L’ & ‘S’ models only)
    HV ON
    Lights to indicate that the high voltage output is enabled. If a fault condition occurs the
    light will extinguish regardless of the state of the HV ENABLE.
    HV OFF
    Lights to indicate that the high voltage output is not enabled. If a fault condition occurs
    the light will blink at about a ½ Second rate.
    INHIBIT
    Lights to indicate the active state of the externally applied or internally generated inhibit
    signals. In capacitor charging applications this light will blink during each discharge
    cycle.
    END OF CHARGE
    Lights to indicate that the measured output voltage is equal to the programmed set
    point voltage.
    INTERLOCK OPEN
    Lights to indicate an open interlock loop.
    LOAD FAULT
    Lights to indicate any failure with the high voltage output. Among the failures are
    overvoltage, output overload, inverter overload, etc.. Some possible causes are:
    HV diodes shorted, O/P shorted to gnd, etc. Load fault may be activated if a very large
    cap is being charged.
    OVERTEMP
    Lights to indicate that the inverter heatsink is running too hot. The major causes for
    this would be exceeding the rated average power, a high ambient temperature, or
    locked fan.
                                     Page 13 of 21
                                   83-488-100 Rev. B
3.6 REMOTE CONTROL (‘L’, ‘S’, & ‘OEM’ models)
    All three models are easily controlled through their remote connector on the rear of the
    unit. Only the HV ENABLE (Pin 8), V PROGRAM (Pin 22) and GND (Pins 12 & 24)
    signals are required for operation. The remaining signals are provided for status
    monitoring and fault diagnosis. A schematic diagram showing the suggested interface
    circuit appears after the following description of control signals.
     DB-25   Cable
      Pin    Wire    Direction    Type           Description
      No      No
         1      1 OUTPUT          ANALOG         REAL-TIME OUTPUT VOLTAGE
         2      3 INPUT           ANALOG         CURRENT PROGRAMMING
         3      5 OUTPUT          OPEN-COL       INHIBIT INDICATOR
         4      7 OUTPUT          OPEN-COL       VOLTAGE REGULATION MODE
         5      9 OUTPUT          OPEN-COL       END OF CHARGE
         6     11 BI-DIREC        DIGITAL        OVERLOAD SYNCHRONIZATION
         7     13 INPUT           DIGITAL        INHIBIT INPUT - ACTIVE HIGH
         8     15 INPUT           DIGITAL        HV ENABLE
         9     17 OUTPUT          ANALOG         PEAK OUTPUT VOLTAGE
       10      19 OUTPUT          OPEN-COL       HV ON INDICATOR
       11      21 BI-DIREC        ANALOG         CURRENT SHARING
       12      23                 GROUND         ANALOG COMMON
       13      25 OUTPUT          ANALOG         REAL-TIME OUTPUT CURRENT
       14       2 OUTPUT          POWER          +15VDC 250mA (Fused)
       15       4 OUTPUT          OPEN-COL       CURRENT REGULATION MODE
       16       6 OUTPUT          OPEN-COL       OVER-TEMPERATURE FAULT
       17       8 OUTPUT          OPEN-COL       INTERLOCK FAULT
       18      10 OUTPUT          OPEN-COL       OVERLOAD FAULT
       19      12 OUTPUT          OPEN-COL       LOAD FAULT
       20      14 INPUT           DIGITAL        /INHIBIT INPUT - ACTIVE LOW
       21      16 BI-DIREC        DIGITAL        OSCILLATOR SYNCHRONIZATION
       22      18 INPUT           ANALOG         VOLTAGE PROGRAMMING
       23      20 OUTPUT          OPEN-COL       HV OFF INDICATOR
       24      22                 GROUND         DIGITAL & POWER RETURN
       25      24 OUTPUT          POWER          +12V 100mA (Unfused)
                                 REMOTE Connector Pin-Out
                                   Page 14 of 21
                                 83-488-100 Rev. B
Figure 10: Remote Control Example
      Page 15 of 21
    83-488-100 Rev. B
3.7 INITIAL CHECK-OUT PROCEDURE
   The power supply should have no visible damage or defects and the cover should be
   securely fastened. Properly connect the input power, control connector and HV output.
   If there is no load connected, the power supply will sense an open circuit and
   immediately shut down indicating a LOAD FAULT. If there is a short circuit or overload
   condition on the output, the power supply will operate in a 50% duty cycle protection
   mode and indicate a LOAD FAULT. An overload condition can occur if the INHIBIT
   signal is missing and the discharge rep rate is too high to allow the capacitor to fully
   charge to V PROGRAM. Double check all connections and ensure that all personnel
   are protected from the HV output. With the HV adjust at zero volts, turn the power
   supply on in the following sequence:
   XR802L FRONT PANEL CONTROL:
     Turn HV ADJUST knob fully counterclockwise.
     Turn POWER switch to ON.
     Turn CONTROL key switch to LOCAL.
     Push HV ON switch.
     Verify the HV output is at approx. zero volts.
     Increase HV output slowly and verify adjustability.
   XR802L REMOTE CONTROL:
     V PROGRAM signal (pin 22) at zero volts.
     ON/OFF signal (pin 8) at zero volts.
     Turn POWER switch to ON.
     Turn CONTROL key switch to REMOTE position.
     Assert ON/OFF signal to 15V.
     Verify HV output is at approx. zero volts.
     Increase HV output slowly and verify adjustability.
   XR802S REMOTE CONTROL:
     V PROGRAM signal (pin 22) at zero volts.
     ON/OFF signal (pin 8) at zero volts.
     Turn POWER switch to ON.
     Assert ON/OFF signal to 15V.
     Verify HV output is at approx. zero volts.
     Increase HV output slowly and verify adjustability.
   XR802 OEM REMOTE CONTROL:
     V PROGRAM signal (pin 22) at zero volts.
     ON/OFF signal (pin 8) at zero volts.
     Assert ON/OFF signal to 15V.
     Verify HV output is at approx. zero volts.
     Increase HV output slowly and verify adjustability.
                                  Page 16 of 21
                                83-488-100 Rev. B