ETR 9090 Instruction Manual PDF
ETR 9090 Instruction Manual PDF
14A
SOFTWARE VERSION
3.3 AND HIGHER
Model ETR-9090
Microprocessor Based
SMARTER LOGIC® Auto Tune PID Controller
MARTER®
S
LLO
OGGIIC
C
INSTRUCTION MANUAL
INSTRUCTION MANUAL SM
ARTER ®
Section 1: INTRODUCTION
This manual contains information for the installation and C/F and security codes are held in a non-volatile
operation of the Ogden Model ETR-9090 auto-tuning memory and retained for ten years if the unit is left
micro-processor based controller with Smarter Logic®. unpowered. Batteries are not necessary.
Ease of use is an essential feature on this versatile The auto-tuning function determines the correct
controller. Four touch keys are used to select sensor proportional band, rate and reset values to provide
type, control mode, control parameters, alarm mode, accurate control with minimal overshoot and tempera-
degrees C/F, auto-manual mode, and to lock the ture oscillation. This is accomplished without the need
parameters from the prevention of unauthorized for expensive and time consuming procedures for
tampering. Two large 4-digit displays show process set-up of control parameters. In case of a power failure
and set point values at a glance. Precise 14 slope or temporary shutdown, the instrument retains the
sensor linearization, self-diagnostic capability, cold correct parameters. This instrument also has manual
junction compensation and 3-mode PID calculations are override capabilities that allow the operator to bypass
automatically executed by the single chip microproces- the auto-tuning parameters. Required fine tuning
sor. The wide selection of parameters, values, sensor adjustments can then be made.
types, set points, control modes, alarm modes, degrees
WARNING!
Failure of devices, such as the thermocouple-RTD sensor, heater output relay or temperature control can result in
severe damage to a product while in process, melting of the heater or a damaging fire. An over-temperature
protection device must be installed in your process that will remove all power from the heating circuit if the above
failure occurs. We recommend that this device be classified as a safety control and carry FM, U.L. and CSA Listing
or Certification. Failure to install high-limit temperature control protection where a potential hazard exists, could
result in damage to equipment and property, and severe injury to personnel.
LINE THREE–ALARM:
Example:
Standard Model: ETR-9090-1 2 1
Thermocouple Type J, K, T, E, B, R, S, N, heating relay, with alarm
Section 3: SPECIFICATIONS
Line Voltage: 90-264 VAC, 50-60 Hz, 20-32VAC/DC and 10-16VDC available.
Input: Type: J, K, R, T, B, E, S, N
thermocouple, PT100 ohm
RTD (DIN) 43760/BS1904
or JIS) and –10 to 60mV
(given span).
Power consumption: Less than 5VA.
Accuracy: ±.1%, ± least significant digit.
NON-VOLATILE MEMORY
• Retains process parameters when power is off
MODEL ETR-9090
Section 4: INSTALLATION
Wiring Precautions:
WARNING!
• Before wiring, verify the label for correct model num-
RISK OF ELECTRIC SHOCK - Dangerous and poten- ber and options. Switch off the power when checking.
tially fatal voltages are present when working on this • Care must be taken to ensure that maximum voltage
equipment. Before installation or beginning any ratings specified in Section 3 on previous page are
troubleshooting procedures, the electric power to this not exceeded.
equipment must be disconnected and locked out as • It is recommended that power to these instruments
described by OSHA Standards. Units suspected of be protected by fuses and circuit breakers rated at
being faulty must be removed and returned to Ogden for the minimum value possible.
inspection and/or repair. They contain no user service-
• All units should be installed inside a suitably ground-
able components.
ed metal enclosure to prevent live parts being acces-
WARNING! sible to human hands and metal tools.
• All wiring must conform to appropriate standards of
To help minimize the possibility of fire or shock hazards, good practice, national and local codes and regula-
do not expose this instrument to rain or excessive tions. Wiring must be suitable for the maximum volt-
moisture. This control is not to be used in hazardous age, current, and temperature ratings expected in the
locations as defined in Articles 500 and 505 of the system.
National Electric Code. • Both solderless terminals or “stripped” leads as
specified in Figure 4.2 below can be used for power
CAUTION! ! leads. Only “stripped” leads should be used for ther-
mocouple connections to prevent compensation and
Do not use this instrument in areas subject to resistance errors.
hazardous conditions such as excessive shock,
vibration, dirt, moisture, corrosive gases or oil. The • Take care not to over-tighten the terminal screws.
ambient temperature of the areas should not exceed • Unused control terminals should not be used as
the maximum rating specified in Section 3, on previous jumper points as they may be internally connected,
page. causing damage to the unit.
• Verify that the ratings of the output devices and the
Unpacking: inputs as specified in Table 4.2 on Page 8 are not
exceeded.
Upon receipt of the shipment remove the instrument
from the carton and inspect the unit for shipping dam- • Electric power in industrial environments contains a
age. If any damage due to transit is noticed, report and certain amount of noise in the form of transient volt-
file a claim with the carrier. Write down the model num- ages and spikes. This electrical noise can enter and
ber, serial number, and date code for future reference adversely affect the operation of microprocessor-
when corresponding with our service center. The serial based controls. For this reason we strongly recom-
number (S/N) and date code (D/C) are located inside mend the use of shielded thermocouple extension
the control. wire which connects from the sensor to the controller.
This wire is a twisted-pair construction with foil wrap
Mounting: and drain wire. The drain wire is to be attached to
Make panel cutout to dimensions shown below. Insert earth ground at the control end only. We carry both
the controller into the panel cutout. The maximum type J and type K in our stock.
panel thickness is 1⁄8" (3mm). NOTE: The use of motor starters in place of magnetic
contactors should be avoided. They have very large
inductive loads that can damage the controller’s relay.
9/16"
1-25/32"
(45mm)
5/16"
1-25/32"
(45mm)
SPADE TONGUE
Panel Cutout CONNECTOR FOR
Panel NO. 6 STUD 20 AWG
3/8"
3-3/8"
(86mm)
3-3/4"
(95mm)
Optional
F1 S1 DC
Alarm
Common 1 6 Supply
+
Alarm Power
N/O 2 7 –
C Current.
3 8 Control + Voltage
RTD NO – Pulsed
Sensor – – 4 9 O/P Voltage
+ +V NC
T/C mA V
5 10
Figure 4.3 Rear Terminal Connections
+ grey + red
B Platinum/Rhodium - red - grey
* grey * grey
* Color of overall sheath Chromel® and Alumel® are registered trademarks of Hoskins Mfg. Co.
Fuse
5A
1 6 Incoming
Power
CAUTION
SHOCK 2 Internal 7
HAZARD Relay
3 8
Red –
Thermocouple
4 9
Heater
+ 5 10 3 Amps
Maximum
360W/120V
720W/240V
Maximum
A 3
Heater
Load
B 4
B 5 Figure 4.4
Example of wiring connections for
RTD Sensor Connections ETR-9090-122 with Relay Output.
Control
Fuse
1A
1 6 Control
Power
2 7
3 + 8 Heater
Fuse
Red –
Thermocouple
4 – 9 Heater
Power
+ 5 10
Heaters
1 2
Solid State
Relay
+
4 3
This diagram can also be used
for controls with 4-20mA output.
Figure 4.5
Example of wiring connections for
ETR-9090-132 with Pulsed Voltage Output
for Solid State Relay
Coil
o o Three
Phase
o o o Heater
Three Phase o o Power
Delta Heater
Load 3-Pole Heater
Magnetic Fuses
Contactor
NEMA
o o or
DP
Figure 4.6
ETR-9090-121 with Relay Output.
Heaters connected in 3-Phase to Contactor.
With Alarm option.
Return Key Resets the controller to its normal status. Also stops
auto-tuning, output percentage monitoring and manual
mode operation.
for 6 seconds
Output Percentage Allows the set point display to indicate the control
Press and Monitoring output value in percent.
Press and Manual Mode Execution Allows the controller to enter the manual mode.
This can be used if the sensor fails.
for 6 seconds
PROCESS VALUE
SET VALUE
Level 2
Long
(6 seconds)
2. LED test.
All LED segments must be lit for 4 seconds.
Long
(6 seconds)
SP SP SP
Perfect
Integral Too Low
Proportional Band Too High Derivative Too High
TIME
TIME TIME
The proportional band (Pb) is a temperature band oscillations then gradually decrease the propor-
expressed in degrees. When the controller is within this tional band until steady cycling is observed.
band, the time proprtioning functions are active. Record this important proportional band percent-
age (Pc).
Integral action (automatic reset) corrects for offset (load
error) for load variations. Reset wind-up inhibition prevents PV
integral action from occurring outside of the proportional
PV (Process value)
band. Software antisaturation minimizes process oscilla- Tc
tions when the load changes.
SET POINT
OFFSET PROPORTIONAL BAND
LOWER PB
PD P
TIME
Table 5.5 Tuning Guide
ADJUSTMENT SEQUENCE: SYMPTOM: SOLUTION:
1.) Proportional Band Slow Response Decrease Proportional Band (Pb)
High Overshoot or Oscillations Increase Proportional Band (Pb)
2.) Integral Time (Reset) Slow Response Increase Reset (i.e. Decrease Integral Time)
Instability or Oscillations Decrease Reset (i.e. Increase Integral Time)
3.) Derivative Time (Rate) Slow Response or Oscillations Decrease Rate (i.e. Decrease Derivative Time)
High Overshoot Increase Rate (i.e. Increase Derivative Time)
The ramp rate ( ) is expressed in degrees/minute In order to enter the manual mode operation press both
the “Scroll” key and the “Return” key for longer than 6
seconds and release. Now the control will display the out-
EXAMPLE 1: The process temperature cannot change
put percentage with a range of –100% to 100%. A posi-
more than 5 degrees per minute.
tive value for heating output percentage and a negative
value for cooling output percentage. Press the UP or
Adjust =5 DOWN key to adjust the output percentage. Zero output
percentage disables the heating output.
EXAMPLE 2: The process temperature cannot change
more than 60 degrees per hour.
Table 5.6 Parameter Lockout
Set Point
Process Temperature
Temperature
=0 =1 =2 =3
PROCESS HIGH ALARM PROCESS LOW ALARM DEVIATION HIGH ALARM DEVIATION LOW ALARM
ASP1 ASP1
moves
SV SV SV SV
with SV
ASP1 ASP1
moves
with SV
=4 =5 =6 =7
INHIBITED INHIBITED INHIBITED INHIBITED
PROCESS HIGH ALARM PROCESS LOW ALARM DEVIATION HIGH ALARM DEVIATION LOW ALARM
=8
OUTBAND ALARM INBAND ALARM
=9 = 10
INHIBIT OUTBAND ALARM
= 11 = 12 = 13
INHIBIT INBAND ALARM DWELL TIME OUT RELAY OFF DWELL TIME OUT RELAY ON
SOAK CONTROL SOAK CONTROL
ASP1
SV Once set point Once set point
is reached. is reached.
ASP1 SV timer is activated SV timer is activated
= MINUTES = MINUTES
Alarm is not active the first incident See Ramp Example on Page 17 See Ramp Example on Page 17
Table 5.7 (Continued)
Descriptions of Alarms
Process High Alarm: Alarm is actuated whenever the process value rises above the alarm set point. Changing
the control set point does not affect the process alarm trip point.
Process Low Alarm: Alarm is actuated whenever the process value falls below the alarm set point. Changing
the control set point does not affect the process alarm trip point.
Deviation High Alarm: Alarm is actuated whenever the process value goes above the control set point by a
predetermined (alarm Value) amount. Changing the control set point changes the alarm set point value
maintaining the same deviation from the control set point.
Deviation Low Alarm: alarm is actuated whenever the process value falls below the control set point by a
predetermined (alarm Value) amount. Changing the control set point changes the alarm set point value
maintaining the same deviation from the control set pint. This alarm value is a negative number.
Inhibited alarms do not energize the alarm relay the first the alarm area, the Inhibited Alarm offers ON as a nor-
time the process temperature enters the alarm area. mal alarm. For some systems, it is useful to bypass the
From the second time the process temperature enters first alarm section while the system is heating up.
HEAT TRANSFER
HEAT SOURCE MEDIUM
Figure 5.5 Display Shift
Changing these values can make the control useless because it can be put out of calibration. Do not
WARNING! attempt to re-calibrate this temperature controller unless you have an adequate calibration instrument
available. This must be used to simulate the sensor input.
The controller must operate under power for at least 45 3.) Press the scroll button again and the high calibration
minutes before starting the calibration procedure. This parameter ( ) will be displayed. Adjust the input sim-
allows the internal components to reach the proper ulator to the high calibration (span) value as indicated in
operating temperature. Connect the calibrating instru- the chart. Adjust the controller to the same value. Press
ment to the ETR control and power leads. the button for exactly 6 seconds to calibrate the
STEP: high (or SPAN) calibration point.
1.) Press and release the scroll key ( ) cycling 4.) The calibration is now complete. Press the scroll but-
through the parameters to make certain they are cor- ton again and process value and setpoint value will
rect. Note the display flow chart on pages 10 & 11. Long appear.
scrolls (pressing the button for 6 seconds) must be used Check intermediate values to test mid-range calibration
where indicated. Check parameters such as ,input accuracy. The procedure can be repeated again if the
type, degrees C or degrees F and resolution. The span accuracy of the controller is not acceptable. Also you
of the control ( ) and ( ) must be extended out can easily add an arbitrary offset value if desired during
to their maximum values. Example: when using a type the calibration procedure by changing the simulator
“J” thermocouple the low range value must be –58 value.
degrees F (–50 deg. C) and the high range value Calibration can be recorded in the accompanying chart.
must be 1832 degrees F (1000 deg. C). These values
are listed in the chart on page two for other sensor
types. The span of the control can be narrowed to your CALIBRATION VALUES
preferred range after the calibration procedure is com- T/C Type ‘J’ RTD DIN
pleted. SENSOR SENSOR
2.) Press the scroll button again for a long scroll and the 32°F 32°F
low calibration parameter ( ) will be displayed. 1112°F 752°F
Adjust the input simulator to the value indicated in the
chart to the right. This value must also match the value NOTE: The above values must be used for correct cali-
in the controls display. Correct if necessary. Press the bration.
button for exactly 6 seconds to calibrate the low (or
zero) calibration point.
CALIBRATION RECORD
Control Date Calibrated Date Next
No.: Calibrated: By: Calibration Due:
Section 7: TROUBLESHOOTING
Experience has proven that many control problems are not caused by a defective instrument. See chart below and
Table 7.1 on the next page for some of the other common causes of failures:
If the points listed above have been checked and the controller does not function, it is suggested that the instrument
be returned for inspection.
Do not attempt to make repairs. Also, it is advisable to use adequate packing materials to prevent damage in
shipment.
NOTE:
Control can be removed from housing by pushing in
latch located on bottom of bezel and pulling control
from housing. Power must first be disconnected.
Table 7.1 Troubleshooting