A50-30-00 220-230V 50Hz / 230-
240V 60Hz
A50-30-00 220-230V 50Hz / 230-240V 60Hz Contactor
—
General Information
Extended Product Type A50-30-00 220-230V 50Hz / 230-240V 60Hz
Product ID 1SBL351001R8000
EAN 3471522081803
Catalog Description A50-30-00 220-230V 50Hz / 230-240V 60Hz Contactor
A50 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up
to 690 V AC / 1000 V AC or 220 V DC. The contactors can also be used for many other applications such as
isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design.
Long Description
- Main poles and auxiliary contact blocks: 3 main poles, front and side-mounted add-on auxiliary contact
blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of
accessories is available.
—
Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900
—
Popular Downloads
Data Sheet, Technical Information 1SBC100122C0202_Ch02
Instructions and Manuals FPTC407700P0003
—
Dimensions
Product Net Width 70 mm
Product Net Depth / Length 108 mm
Product Net Height 110 mm
Product Net Weight 1.160 kg
—
Technical
Number of Main Contacts NO 3
Number of Main Contacts NC 0
Number of Auxiliary Contacts NO 0
Number of Auxiliary Contacts NC 0
Standards Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 /
60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1; EN 60 947-1 and
amendment 2 to IEC 947-4-1
Rated Operational Voltage Main Circuit 1000 V
A50-30-00 220-230V 50Hz / 230-240V 60Hz 2
Conventional Free-air Thermal Current (I th ) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 100 A
Rated Operational Current AC-1 (I e ) (690 V) 40 °C 100 A
(690 V) 55 °C 85 A
(690 V) 70 °C 70 A
Rated Operational Current AC-3 (I e ) (1000 V) 55 °C 23 A
(220 / 230 / 240 V) 55 °C 53 A
(380 / 400 V) 55 °C 50 A
(415 V) 55 °C 50 A
(440 V) 55 °C 45 A
(500 V) 55 °C 45 A
(690 V) 55 °C 35 A
Rated Operational Power AC-3 (P e ) (220 / 230 / 240 V) 15 kW
(380 / 400 V) 22 kW
(415 V) 25 kW
(440 V) 25 kW
(500 V) 30 kW
(690 V) 30 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1 10 x Ie AC-3
Short-Circuit Protective Devices gG Type Fuses 100 A
Maximum Breaking Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Maximum Electrical Switching Frequency AC-1 600 cycles per hour
AC-2 / AC-4 150 cycles per hour
AC-3 600 cycles per hour
Rated Insulation Voltage (U i ) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (U imp ) 8 kV
Maximum Mechanical Switching Frequency 3600 cycles per hour
Rated Control Circuit Voltage (U c ) 50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Coil Consumption Average Holding Value 50 / 60 Hz 18 V·A
Average Holding Value 50 / 60 Hz 5.5 W
Average Pull-in Value 50 Hz 190 V·A
Average Pull-in Value 60 Hz 180 V·A
Operate Time Between Coil Energization and NO Contact Closing 8 ... 27 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Connecting Capacity Main Circuit Flexible with Cable End 6 ... 16 mm²
Rigid Cable 6 ... 25 mm²
Connecting Capacity Auxiliary Circuit Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Connecting terminals (delivered in open position) Main M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
poles
Terminal Type Screw Terminals
—
Environmental
Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
Close to Contactor for Storage -60 ... +80 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C
Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C
Climatic Withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible 3000 m
Resistance to Shock acc. to IEC 60068-2-27 Shock Direction: A 20 g
Closed, Shock Direction: B1 10 g
Open, Shock Direction: B1 5 g
Shock Direction: B2 15 g
Shock Direction: C1 20 g
Shock Direction: C2 20 g
A50-30-00 220-230V 50Hz / 230-240V 60Hz 3
RoHS Status Following EU Directive 2002/95/EC August 18, 2005 and amendment
—
Certificates and Declarations (Document Number)
BV Certificate BV_2634H07559D0
CB Certificate CB_FR_602227A
CCC Certificate CCC_2006010304213057
CCC_2008010309289461
CSA Certificate CSA_1033838_LR056745
Declaration of Conformity - CE 1SBD250801U1000
DNV Certificate DNV-GL_TAE00000TX
DNV GL Certificate DNV-GL_TAE00000TX
EAC Certificate EAC_RU C-FR ME77 B01010
Environmental Information 1SBD250008E1003
GOST Certificate GOST_POCCFRME77B07175
Instructions and Manuals FPTC407700P0003
LR Certificate LRS_9830011E4
RINA Certificate RINA_ELE128713XG001
RMRS Certificate RMRS_0507015250
RoHS Information 1SBD350054R1000
UL Certificate UL_20120830-E312527-10-1
UL Listing Card UL_E312527
—
Container Information
Package Level 1 Units 1 piece
Package Level 1 Width 140 mm
Package Level 1 Depth / Length 146 mm
Package Level 1 Height 96 mm
Package Level 1 Gross Weight 1.16 kg
Package Level 1 EAN 3471522081803
Package Level 2 Units 20 piece
Package Level 2 Gross Weight 23.2 kg
Package Level 3 Units 160 piece
—
Classifications
Object Classification Code Q
E-nummer 3227804
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
UNSPSC 39121529
—
Categories
Low Voltage Products and Systems → Control Products → Contactors → Block Contactors