PCS-902 X Instruction Manual en Customized ECKF100721 R1.00 (En XLBH5102.0063.1101)
PCS-902 X Instruction Manual en Customized ECKF100721 R1.00 (En XLBH5102.0063.1101)
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
z Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
z Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
z Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER!
It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.
WARNING!
It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.
CAUTION!
It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
z Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
z Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
z Earth
z Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
z Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
z External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
z Connection cable
Copyright
Version: PCS-902 NR ELECTRIC CO., LTD.
Manual: R1.00 69 SuYuan. Avenue, Nanjing 211102,China
P/N: EN_XLBH5102.0063.1101 Tel: 86-25-87178185, Fax: 86-25-87178208
Copyright © NR 2010. All rights reserved Website: www.nari-relays.com
Email: [email protected]
We reserve all rights to this document and to the information
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.
Table of Contents
Preface ....................................................................................................................................... i
Introduction........................................................................................................................ i
1.3 Features........................................................................................................................3
4.4.1 Voltage and current drift monitoring and auto adjustment ..........................96
5.1 Metering....................................................................................................................101
9.1 Overview...................................................................................................................173
9.2.4 PRINT..............................................................................................................180
13.2 Disposal..................................................................................................................235
Chapter 1 Introduction
1.1 Application
The PCS-902 is a numerical EHV line distance protection with the main and back-up protection
functions, which mainly is designed for transmission line of various voltage levels.
The main protection of PCS-902 comprises of pilot distance protection (POTT and PUTT) and pilot
directional earth-fault protection (DEF), which can clear the fault immediately for the whole line.
DPFC distance protection can reach to extremely fast speed for the fault near the busbar.
1.2 Function
1. Main protection
2. Backup protection
Voltage protection
3. Additional function
Auto-reclosing (79)
Synchro-checking (25)
Note!
1.3 Features
1. Protection and Control
Quickly clearing the internal fault for whole line, the time is less than 10 ms for fault where is
near the busbar, is less than 15ms for fault where is in the center of line and is less than 25ms
for fault where is in the remote end.
Plug connectors from the relay rear panel to the terminal blocks on the rack or cabinet, which
makes the on-site commissioning and replacement much easier than what you do the
commissioning using the traditional screw terminals on the rear panel.
Two independent data acquisition paths, one for fault detector element and another for
protections and logic functions, to prevent any undesired trip.
The unique DPFC distance element is integrated in the protective device, which can clear the
internal fault quickly with high sensitivity and high speed and is not affected by power swing.
Self-adaptive floating threshold which only reflects deviation of power frequency component
can defend system imbalance and system disturbance. Hence, it is both rather reliable and
very fast, and it is very sensitive but does not pickup frequently.
Main protection adopts integral transform to ensure high-speed; Back-up protection adopts
Fourier transform, which has an excellent filtering result, to ensure accuracy.
24 samples per cycle, all task including data measurement, protection calculation, logic
discrimination, event recording and protection logic calculation could be done within one
sampling period.
GPS clock synchronization – PPS (pulse per second), PPM (pulse per minute), IEC 1588
synchronization, SNTP(BC) synchronization, SNTP(PTP) synchronization, IRIG-B
synchronization and DCF77 synchronization.
High-speed 64 Kbit/s PCM channel or 2048 Kbit/s dedicated optical fiber channel for pilot
scheme (optional)
2. Communication
4 Ethernet ports at most (depend on the choosed CPU type), IEC 61850, or IEC 60870-5-103
over TCP/IP
2 Ethernet ports via optic fiber at most (ST interface or SC interface, depend on the choosed
CPU type)
Event Recorder including 1024 status change reports of binary input, 1024 self-supervision
reports and 1024 operating reports.
Disturbance recorder including 1024 fault reports, and 64 waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
4. User Interface
Friendly HMI interface with LCD and 9-button keypad on the front panel.
Software Version
Standard 1
Language
Chinese + English E
Chinese + French F
Chinese + Russian R
Chinese + Spanish S
Chinese + Portuguese P
Auxiliary Power
88~300 Vdc 1
Analog AC Inputs
Non available O
CT 1A A
CT 5A B
Digital AC Inputs
Non available 0
2 x 100Base-FX,
1
ST-Connector
2 x 100Base-FX,
ST-Connector, IRIG-B 2
input (ST)
Other 3*
Support to GOOSE
Non available O
2 x 100Base-FX,
A
ST-Connector
Other B*
Binary Inputs
Non available 0
4 fixed + 14 configurable 1
4 fixed + 32 configurable 2
4 fixed + 50 configurable 3
Binary Outputs
Non available O
33 contacts (22 contacts
A
controlled by fault detector)
44 contacts (22 contacts
B
controlled by fault detector)
Communication Ports
for Automation
2 x EIA-485 + 2 x
1
100Base-TX, RJ45
4 x 100Base-TX, RJ45 2
2 x 100Base-TX, RJ45 + 2
x 100BaseFX, 3
ST-Connector
Other 4*
Protocol
IEC 60870-5-103 A
DNP 3.0 B
IEC 61850 C*
Pilot Channel
Power line carrier 1
Note!
The items marked with “*” are not included in the basic price and have an additional cost.
2. Analog voltage
Burden
Quiescent condition <20W
Operating condition <25W
Enclosure dimensions
482.6×177×291 (unit: mm)
(W×H×D)
Mounting Way Flush mounted
Trepanning
450×179, M6 screw
dimensions (W×H)
Housing color Silver grey
Weight per device Approx. 15kg
Display language English
Housing material Aluminum
Location of terminal Rear panel of the device
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection
IP20
terminals
Pollution degree 2
2.6 Certifications
z ISO9001: 2000
z ISO14001:2004
z OHSAS18001: 1999
z ISO10012:2003
z CMMI L3
Accuracy: ≤10%
Accuracy: ≤1%Setting+40ms
Accuracy: ≤1%Setting+40ms
Accuracy: ≤1%Setting+40ms
Accuracy: ≤1%Setting+20ms
Accuracy: (inverse-time characteristic is selected) ≤5% of theoretical value + Max( 2.5 % voltage
tolerance, 0.02U2n voltage tolerance), at least
40ms
Accuracy: ≤1%Un
Accuracy: ≤1%Setting+20ms
Accuracy: (inverse-time characteristic is selected) ≤5% of theoretical value + Max( 2.5 % voltage
tolerance, 0.02U2n voltage tolerance), at least
40ms
Tolerance will be higher in case of single-phase fault with high ground resistance.
Overvoltage element
If any of the above fault detector elements operates, the GFD will operate to provide DC power
supply to the output relays to enable the output circuit.
Its criterion:
Where:
If operating condition is met, DPFC overcurrent element will operate to provide DC power supply
for output relay, and pickup signal will be kept for 7 seconds after DPFC overcurrent element drops
out.
where:
3I0: zero-sequence current derived at the neutral current circuit from three-phase currents
3I0Cal: zero-sequence current calculated depending on the summation of IA, IB and IC (i.e.
3I0Cal=IA+IB+IC)
If operating condition is met, zero-sequence overcurrent element will operate to provide DC power
supply for output relay, and pickup signal will be kept for 7 seconds after zero-sequence
overcurrent element drops out.
When CT circuit failure is detected, this element will be disabled and an alarm [Alm_CTS_CB1] or
[Alm_CTS_CB2] will be issued.
Note!
The zero-sequence current should be connected to the protective device; otherwise all
protection elements corresponding with zero-sequence current will be blocked.
If the logic setting [Opt_1P/3P_Volt] is set as “1”, i.e. the protective device adopts 1-out-of-3 mode,
so when any phase voltage is greater than the setting [V_OV], the overvoltage fault detector
element will operate to provide DC power supply for output relay, and pickup signal will be kept for
7 seconds after overvoltage fault detector element drops out.
If the logic setting [Opt_1P/3P_Volt] is set as “0”, i.e. the protective device adopts 3-out-of-3 mode,
so when three phase voltages are all greater than a threshold setting, the overvoltage fault
detector element will operate to provide DC power supply for output relay, and pickup signal will be
kept for 7 seconds after overvoltage fault detector element drops out.
Its criterion:
ΔIΦΦMAX, ΔISet, ΔITh, their meanings are as same as what mentioned in Equation 3.2-1.
When this criterion is met, the program flow still goes to the regular program, the program flow will
go to fault calculation program only if Equation 3.2-1 is also met or zero-sequence overcurrent
element also operates.
jX
ZZD
ZK
R
ZS+ZK
-ZS
ZS: Total impedance between local system and protective device location
Figure 3.4-1 shows the operation characteristic of the DPFC distance element on R-X plane when
a fault occurs in forward direction, which is the circle with the –Zs as the center and the│Zs+Zzd│ as
the radius. When measured impedance Zk is in the circle, the DPFC distance element will operate.
The DPFC distance element has a large capability of enduring fault resistance. When there is
infeed current from power source at the other end in the fault resistance, the phase of ΔIN is the
same as ΔI and the phase of voltage of fault resistance is same as ΔI, so the fault resistance
appears resistive and is in parallel with R axes. The overreaching problem that results from infeed
current can be prevented.
Figure 3.4-2 shows the operation characteristic of the DPFC distance element on R-X plane when
a fault occurs in reverse direction, which is the circle with the Z's as the center and the │Z's-Zzd│ as
the radius. The region of operation is in the quadrant 1 but the measured impedance –Zk is always
in the quadrant 3, so the DPFC distance element will not operate and have the definite
directionality.
Note!
The DPFC distance protection can be enabled or disabled by corresponding logic setting
and binary input.
There are three kinds of application modes associated with different auxiliary device and channel.
This kind of application must be cooperated with digital optical fibre interface device, such as
FOX-40F and FOX-41A.
Figure 3.5-2 Typical application using PLC channel with blocking scheme
This kind of application must be coordinated with dedicated PLC transceiver, such as LFX-912 and
LFX-913. At the same time, the pilot protection must be blocking scheme.
PCS-902 PCS-902
Protection Protection
signal signal
Figure 3.5-3 Typical application using PLC channel with permissive scheme
If PLC channel is used and the pilot protection adopts permissive scheme, this kind of application
should be selected. If the audio interface is available in the PLC equipment, additional audio
interface device is not needed. Otherwise, audio interface device should be equipped with
PCS-902, for example, CAT-50.
As shown in Figure 3.5-4, a basic PLC system consists of three distinct parts: the terminal
assemblies, the coupling equipment, and the transmission line. Terminal assemblies consist of
transmitters, receivers, and protective relays. The coupling equipment consists of the line tuner,
coupling capacitor, and line trap. The transmission line provides a suitable path for transmission of
carrier energy between terminals in the PLC band of frequencies. At the terminals, one or more
transmitters and/or receivers may be required, depending on the number of functions to be
performed.
1) Phase-to-ground coupling
2) Phase-to-phase coupling
3) Line-to-line coupling
The directional distance element is formed by distance element with overreaching scheme and
consists of undervoltage distance element, phase-to-ground distance element and
phase-to-phase distance element. The operation characteristic of these elements is as same as
that of distance protection.
PCS-902 also provides weak infeed element to identify a fault in forward direction or reverse
direction. It is invalid unless the logic setting [En_WE_POTT] is set as “1”.
In the case of weak infeed, if none of forward distance element, reverse distance element, forward
zero-sequence element and reverse zero-sequence element operate and any phase voltage or
phase-to-phase voltage is smaller than 30V, the protective device regards it as a fault in forward
direction. Thus distance element will operate for this case.
Forward zero-sequence element (F0+) and reverse zero-sequence element (F0-) are determined by
the zero-sequence power (P0). P0 derives from Equation 3.5-1.
Where:
3I0Cal: The zero-sequence current calculated depending on the summation of IA, IB and IC (i.e.
3I0Cal=IA+IB+IC)
3U0Cal: The zero-sequence voltage calculated depending on the summation of UA, UB and UC (i.e.
3U0Cal=UA+UB+UC)
ZD: The unit vector (Its amplitude is 1 and its phase angle is 78º)
The forward direction of directional zero-sequence element derives from the output of F0+ through
an AND gate with directional comparison zero-sequence overcurrent element. The reverse
direction of directional zero-sequence element derives from the output of F0- through an AND
gate with zero-sequence overcurrent element. The logic scheme is shown as Figure 3.5-6.
Another fault situation requiring timing coordination occurs when two protected lines run in parallel
or substantially in parallel through short interconnecting lines. This situation is commonly referred
as current reversal. In Figure 3.5-7, a fault occurrs on line C–D near breaker D. Relay A will be
prevented from tripping because the directional information from the relay near breaker B
indicates that the fault is in the reverse direction.
M N
A B
EM EN
C D
M N
A B
EM EN
C D
If the line A–B protection is a blocking scheme, then the relay at B sends a blocking signal to A to
prevent tripping. Conversely, if the scheme is a permissive overreaching type, then B continues
the normal guard signal to A, which indicates that A should not trip. If breaker D should open
before breaker C on the faulted line, the fault current in line A–B suddenly reverses direction as
shown in Figure 3.5-8.
In a blocking scheme, relays at both A and B have a tendency to trip incorrectly during the current
reversal, but they are prevented from doing so by the pickup and reset coordination timers. The
pickup coordination timer at B prevents the forward-looking relay at B from tripping while waiting
for the reverse-looking relay at A to send a blocking signal. Also, the reset timer at B continues
transmission of a blocking signal to A long enough to permit the forward-looking relay at A to reset.
In a permissive overreaching scheme, the initial fault near D will cause the forward-looking relay at
A to send trip permission to B. When the current reverses, relay B will suddenly see a fault in its
forward direction and time coordination is necessary to ensure that B does not trip before the
permissive signal from A can be removed. The simplest solution to this race is a pickup timer for
the forward-reaching relay, just like that described for the blocking scheme. The required timing for
this timer is the sum of
1. The difference between the reset time of relay A forward direction and the pickup time of relay
B reverse direction [A – B]
PCS-902 adopts channel-aided pilot distance protection which can be configured as POTT or
PUTT via logic settings [En_POTT_PilotP] and [En_PUTT_PilotP]. Besides, an additional
directional earth-fault element is provided for POTT to improve the sensitivity of high-resistance
fault. It is the supplement of POTT. The dedicated directional earth-fault element for POTT can be
enabled/disabled via logic setting [En_ROC_POTT].
The permissive scheme can use PLC channel or optic fiber channel as communication channel.
These signals, which are used to initiate sending permissive signal, such as normally closed
auxiliary contact of circuit breaker, external protection tripping and so on, should be connected to
the protective device directly but not to the dedicated transceiver.
&
[BI_52b_Pha_CB1]
BI_52b_Pha
[BI_52b_Pha_CB2]
&
[BI_52b_Phb_CB1]
BI_52b_Phb
[BI_52b_Phb_CB2]
&
[BI_52b_Phc_CB1]
BI_52b_Phc
[BI_52b_Phc_CB2]
&
BI_52b
If only one circuit breaker (CB1) is equipped with the device, the binary input for normally closed
auxiliary contact of CB2 will be regarded as being energized.
[BI_52b_Pha_CB1]: Binary input for normally closed auxiliary contact of phase A of CB1
[BI_52b_Phb_CB1]: Binary input for normally closed auxiliary contact of phase B of CB1
[BI_52b_Phc_CB1]: Binary input for normally closed auxiliary contact of phase C of CB1
[BI_52b_Pha_CB2]: Binary input for normally closed auxiliary contact of phase A of CB2
[BI_52b_Phb_CB2]: Binary input for normally closed auxiliary contact of phase B of CB2
[BI_52b_Phc_CB2]: Binary input for normally closed auxiliary contact of phase C of CB2
POTT
[En_POTT_PilotP]
[En_ROC_POTT]
[VEBI_ROC] &
[En_ROC_POTT]
[En_Z_POTT_Quad]
&
Zp< [Z_POTT_Quad]
ZP<[Z_POTT] ≥1
ZPP<[Z_POTT]
&
&
[En_Z_POTT]
& ≥1
PSBR_PilotP
[En_WE_POTT]
&
Distance element for weak infeed
&
0 100ms ≥1 ≥1
Other protection logic operating to trip
& Sending carrier signal 1
[BI_ExTrp_PilotP] 0 150ms
≥1
BI_52b=1
&
≥1 200ms 0
Trip confirmation &
[VEBI_PilotP]
[En_POTT_PilotP]
T1: t_Dly_CurRev
T2: t_Ext_CurRev
Please refer to Chapter 8 about the description of settings and section 7.4 about the description of
binary signals.
1. If the forward element operates and the reverse element does not operate, it will result in
sending permissive signal, at the same time, the pilot protection will operate if permissive
signal has been received from the opposite end for more than 8ms.
2. If during the time delay [t_Dly_CurRev] after the fault has been detected, the operation
condition for pilot protection is not satisfied, but the condition is only met after the delay, then
the pilot protection will operate with time delay [t_Ext_CurRev], which can prevent PCS-902
from mal-operation when current reversal happens.
3. If other protection logic operate to trip circuit breaker (such as directional zero-sequence
overcurrent protection and distance protection), permissive signal is sent immediately and the
permissive signal is kept for 100ms continually after tripping signal drops off. However, that
reverse element operate will stop sending permissive signal immediately.
4. If external protection operate to trip circuit breaker (for example, busbar protection), i.e. binary
input [BI_ExTrp_PilotP] is energized, permissive signal is sent immediately and the
permissive signal is kept for 150ms continually after trip signal drops off.
5. Three-phase trip confirmation is detected or 52b of three phases are energized (i.e.
[BI_52b_Pha] = [BI_52b_Phb] = [BI_52b_Phc] =1), moreover, three phases current are all
zero, PCS-902 will send permissive signal for 200ms if receiving the carrier signal from
opposite end of line.
6. For POTT, pilot zero-sequence element can be enabled or disabled by logic setting
[En_ROC_POTT]. For internal fault associated with high resistance, it can clear the fault
quickly. Pilot weak infeed element can be enabled or disabled by logic setting
[En_WE_POTT]. For internal fault, it can send permissive signal to opposite end of line. If
receiving permissive signal from the opposite end of line, pilot protection will operate quickly.
7. When POTT is enabled, if polit distance protection and directional earth-fault protection use
the same contact to initiate sending permissive signal, logic setting [En_Z_POTT] and
[En_ROC_POTT] can be set as “1”. If pilot distance protection and directional earth-fault
protection use independent contact to initiate sending permissive signal, logic setting
[En_Z_POTT] and [En_DEF_PilotP] are set as “1” and logic setting [En_ROC_POTT] must be
set as “0”.
8. When PCS-902 detects the status of manually closing or auto-reclosing, POTT will be
disabled.
9. For double-circuit lines on the same tower, in order to prevent incorrect selection of faulty
phase when a cross-line fault occurs, POTT based on phase-segregated command scheme
is adopted (the logic setting [Opt_Ch_PhSeg] should be set as “1”). If the operation condition
for pilot protection is satisfied and permissive signal of corresponding phase (“BI_Recv1” for
phase A, “BI_RecvB” for phase B and “BI_RecvC” for phase C) is received, pilot protection
will operate to trip faulty phase of this line.
10. When the operation condition for pilot protection is satisfied, permissive signal of faulty phase
(“Send1” for phase A, “SendB” for phase B and “SendC” for phase C) will be sent if it is a
single phase fault while permissive signals of three phase will be sent if it is a multi-phase
fault.
PUTT
[VEBI_PilotP]
[En_PUTT_PilotP]
[En_ZPG2_Quad ]
&
Zone 2 of quadrilateral distance element
[En_ZPG2]
& ≥1
Zone 2 phase-to-ground distance element & Op_Z_PilotP
& 8ms 0
[En_ZPP2]
&
Zone 2 phase-to-phase distance element
&
PSBR_PilotP
&
[En_ZPG1]
&
Zone 1 phase-to-ground distance element
[En_ZPP1]
& ≥1 ≥1
Zone 1 phase-to-phase distance element & Sending carrier signal 1
[En_ZPG1_Quad ]
&
Zone 1 of quadrilateral distance element
[BI_ExTrp_PilotP] 0 150ms
[VEBI_PilotP]
[En_PUTT_PilotP]
Please refer to Chapter 8 about the description of settings and section 7.4 about the description of
binary signals.
1. If zone 1 of distance element operates to trip circuit breaker, permissive signal is sent
immediately and the permissive signal is kept for 100ms continually after tripping signal drops
off.
2. If zone 2 of distance element operates to trip circuit breaker and permissive signal is received
from the opposite end of line for 8ms, pilot protection operates.
3. If external protection operate to trip circuit breaker (for example busbar protection), i.e. binary
input [BI_ExTrp_PilotP] is energized, permissive signal is sent immediately and the
permissive signal is kept for 150ms continually after trip signal drops off.
4. When PCS-902 detects the status of manually closing or auto-reclosing, PUTT will be
disabled.
5. For double-circuit lines on the same tower, in order to prevent incorrect selection of faulty
phase when a cross-line fault occurs, PUTT based on phase-segregated command scheme is
adopted (the logic setting [Opt_Ch_PhSeg] should be set as “1”). If zone 2 of distance
element operates and permissive signal of corresponding phase (“BI_Recv1” for phase A,
“BI_RecvB” for phase B and “BI_RecvC” for phase C) is received, pilot protection will operate
to trip faulty phase of this line.
6. When zone 1 of distance element operates, permissive signal of faulty phase (“Send1” for
phase A, “SendB” for phase B and “SendC” for phase C) will be sent if it is a single phase fault
while permissive signals of three phase will be sent if it is a multi-phase fault.
[En_DEF_PilotP]
[VEBI_ROC] &
&
Forward zero-sequence element
20ms 0
VTS
0 100ms ≥1
Sending carrier signal 2
&
(i.e. Send2)
Other protection logic operating
[BI_ExTrp_PilotP] 0 150ms
≥1
BI_52b=1
≥1
&
Trip confirmation &
200ms 0
IA,B and C<0.06In
[En_DEF_PilotP]
[VEBI_PilotP]
Please refer to Chapter 8 about the description of settings and section 7.4 about the description of
binary signals.
1. If forward zero-sequence element operates, with 20ms delay, PCS-902 sends permissive
signal to opposite end of line. At the same time, if permissive signal is received from the
opposite end of line, pilot zero-sequence element will operate after the time delay [t_DEF].
The time delay [t_DEF] can ensure DEF operate correctly when the fault with high resistance
occurs.
2. If other protection logic operate to trip circuit breaker (such as directional zero-sequence
overcurrent protection and distance protection), permissive signal is sent immediately and the
permissive signal is kept for 100ms continually after tripping signal drops off.
3. If external protection operate to trip circuit breaker (for example, busbar protection), i.e. binary
input [BI_ExTrp_PilotP] is energized, permissive signal is sent immediately and the
permissive signal is kept for 150ms continually after trip signal drops off.
4. Three-phase trip confirmation is detected or 52b of three phases are energized (i.e.
[BI_52b_Pha] = [BI_52b_Phb] = [BI_52b_Phc] =1), moreover, three phases current are all
zero, PCS-902 will send permissive signal for 200ms if the carrier signal is received from the
opposite end of line.
5. When PCS-902 detects the status of manually closing or auto-reclosing, DEF will be disabled.
[En_POTT_PilotP]
&
Recieving carrier signal 1
[En_WE_POTT]
BI_52b=1
& & Sending carrier signal 2
200ms 0
IA,B and C<0.06In &
After receiving permissive signal from opposite end of line, if local circuit breaker is in the opening
state, PCS-902 will send permissive signal to opposite end of line. When POTT is adopted, for
weak infeed end, PCS-902 will send permissive signal to opposite end of line after receiving
permissive signal from opposite end of line if any phase voltage or phase-to-phase voltage is less
than 33V, which can ensure internal fault cleared quickly by protective device of remote end when
fault detector element does not operate because of light load of line.
The conventional distance protection can manage the fault clearance of earth-faults in most of the
cases. In some applications, especially applications with long lines, the clearance can be
improved by use of an instantaneous zero-sequence overcurrent protection. Those are for
instance:
1. In the case of high infeed of fault current from the opposite end of the line, this might increase
the fault resistance seen by the distance relay to such a value that the instantaneous zone of
the distance protection will not operate.
2. In applications with series compensated lines, where the capacitor is located at the end of the
line and very strong infeed of fault current from that end, will result in a difficult problem for the
distance protection to perform a selective fault clearance. This due to the voltage reversal that
might occur.
3I0>[I_ROC_FD]
&
3I0Cal>[I_ROC_FD]
& ROC DIR+
F0+
F0-
& ROC DIR-
[En_Dir_ROC1]
≥1 [t_ROC1]
Op_ROC1
3I0Cal > [I_ROC1] &
[En_ROC1] &
[En_Dir_ROC2]
≥1 [t_ROC2]
Op_ROC2
3I0Cal > [I_ROC2] &
[En_ROC2] &
[En_Dir_ROC3]
≥1 [t_ROC3]
Op_ROC3
3I0Cal > [I_ROC3] &
&
[En_ROC3]
≥1
[t_ROC4]
[En_Dir_ROC4] & Op_ROC4
The overcurrent protection in this relay provides two-stage phase overcurrent protection with
independent definite-time characteristics. Each stage can be enabled or disabled by scheme logic
settings independently. All overcurrent element and directional element settings apply to all three
phases but are independent for each stage. Configuring the relevant settings can enable or
disable the corresponding directional element.
Reverse direction
UJ
φ=phi_RCA_OC
Forward direction
IJ
Where:
φ: The characteristic angle of phase overcurrent element, i.e. the setting [phi_RCA_OC].
Polarized positive sequence voltage is used for directional element of phase overcurrent
protection. When close-in three-phase fault happens, the positive sequence voltage maybe very
low, then memorized positive sequence polarized voltage is used instead.
β
t(I ) = Tp (Equation 3.6-1)
I
( 0 )τ − 1
Ip
Where:
β is a certain constant.
τ is the exponent.
[Opt_Characteristic_ROC] τ β
The logic scheme of inverse-time zero-sequence overcurrent protection is shown in the Figure
3.6-4.
Where:
When bus VT circuit failure happens, the distance protection will be disabled. As a substitute,
phase overcurrent protection and zero-sequence overcurrent protection will be put into work
automatically in this case if VEBI setting [VEBI_DistP] and [VEBI_ROC] are set as “1”.
Figure 3.6-5 Logic diagram of zero-sequence/phase overcurrent protection when VT circuit failure
For each independent distance element zone, full scheme design provides continuous
measurement of impedance separately in three independent phase-to-phase measuring loops as
well as in three independent phase-to-ground measuring loops.
Phase-to-phase distance element is suitable as a basic protection function against two- and
three-phase faults in all kinds of networks, regardless of the treatment of the neutral point.
Independent setting for each zone separately makes it possible to create fast and selective
protection in power systems.
Phase-to-ground distance element serves as basic earth fault protection in networks with solidly or
low impedance grounded networks. Independent setting for each zone separately makes it
possible to create fast and selective protection in power systems.
Polarized positive sequence voltage is used for distance protection so that faults with high
resistance can also be cleared easily. In case of short lines, in order to enhance performance
against high fault resistance, the impedance characteristic of the zone 1 and zone 2 could be
inclined toward quadrant 1.
If the positive sequence polarized voltage is high enough, directionality of the distance protection
using positive sequence polarized voltage is very good. However, when close-in three phase fault
happens, the positive sequence voltage may reduce to 10% or less, the distance protection will go
to low voltage program (please refer to section 3.7.1) in which memorized positive sequence
polarized voltage is used instead.
Threshold will be set forward for zones 1 and 2 of distance element before its operation, so that
directionality could be assured during busbar three phase fault. In addition, this threshold will be
changed to reverse direction after operation of the protection, so that forward close-in three phase
fault can be fully cleared. As to the zone 3 of the distance element, direction of the threshold is
always reverse, because it acts as a backup protection for busbar.
Note!
When VT circuit failure happens, the alarm [Alm_VTS] displayed, all distance protection
will be disabled.
Distance element with memorized polarization is an algorithm used when positive sequence
voltage reduces to 10% or less. There are only two possibilities for this condition: power swing or
three phase short circuit fault.
As the power swing will be identified by power swing blocking function, only three phase short
circuit should be considered and discussed herein.
Because three phase-to-ground impedance and three phase-to-phase impedance are equal in
case of three phase short circuit fault, so only phase-to-ground impedance should be measured.
Impedances of all three phase are usually equal. Nevertheless, in order to ensure fast tripping
even in the case of transition from bus fault to three phase line fault, all of three phase impedances
are calculated and operation of any phase element will lead to three phase tripping.
Distance element with memorized polarization compares phasor angle of operating voltage and
polarized voltage.
ZS: total impedance between local system and protective device location
This does not mean it will operate incorrectly during reverse direction fault but means it will
operate correctly during forward fault even if the fault occurs just on the outlet because that is
derived supposing forward direction fault.
Figure 3.7-2 shows operation characteristic of measured impedance -ZK on R-X plane. This
characteristic is a circle with line connecting ends of ZZD and Z'S as the diameter. It will operate
only when -ZK is in the circle. Therefore directionality of the protection is explicit.
The conditions mentioned above are before fading of memorized voltage, in another word, they
are transient characteristic.
jX
ZZD
ZK
Figure 3.7-3 Steady state characteristic of three phase short circuit fault
When the memorized voltage fade, Figure 3.7-3 shows operation characteristic of measured
impedance ZK on R-X plane for forward direction fault as well as that of -ZK for reverse direction
fault. Since the circle covers the origin, the equipment will be just on the margin of operation for
fault on the bus or line outlet. In order to prevent the mal-operation for bus fault, especially the
three phase bus fault with arc resistance, zone1 and 2 of distance element is equipped with a
positive threshold. Voltage value of the threshold is equal to maximum voltage drop of the arc.
Moreover, when zone 1 or 2 of distance element operates, phase of the threshold voltage will be
inverted so that the origin can be enclosed in the characteristic circle to ensure the fault can be
fully cleared. In order to ensure backup protection of zone 3, phase of threshold voltage is always
inverted and the origin is always enclosed in the characteristic circle.
This element use polarized positive sequence voltage which can improve the performance against
the fault resistance so that it can not overreach when earth fault associated with high fault
resistance occurs.
jX
A
R
-ZS
In short line case, in order to improve the relay performance against high fault resistance, phase
shift θ1 is used for polarized voltage. This phase shift could move the directional impedance
characteristic toward quadrant 1 as is shown in Figure 3.7-4. Value of θ1 can be set to 0°, 15° or
30°.
This relay could measure high fault resistance and keep a very satisfied performance under high
fault resistance condition. However, if there is a considerable power source in remote end, an
overreach caused by infeed from remote end during resistance earth fault may occur. In order to
prevent overreach, the following zero-sequence reactance relay is introduced.
Typical zero-sequence reactance characteristic is shown as the straight line A in Figure 3.7-4.
Therefore, directional impedance characteristic integrating with the zero-sequence characteristic
are adaptive with the fault resistance.
Actually, zero-sequence reactance characteristic line will incline downward for 12°. Therefore, in
an actual system, even if zero-sequence impedance angles of both ends of a line are not the same
and the phase difference exists between 3I0Cal and voltage drop on fault resistance, overreach
condition will not happen. If the directional distance element with phase shift θ1 and
zero-sequence reactance element operate simultaneously, zones 1 and 2 of distance element with
good directionality will operate.
The no-memorized positive sequence voltage is used as polarized voltage because during earth
fault, positive sequence voltage is mainly formed by healthy phase and the phase of positive
sequence voltage is kept as it was before the fault. Therefore, characteristic of zone 3 of
phase–to-earth distance element is the same as the transient characteristic of distance element
with memorized polarization and have a very good directionality.
The sensitivity of phase-to-ground distance element with Mho characteristic may be not enough
during ground fault with extreme high resistance. So additional three-zone phase-to-ground
distance element with quadrilateral characteristic is adopted in the equipment to compensate the
sensitivity of Mho characteristic. The logic relationship between quadrilateral distance element and
Mho distance element is OR. It means that any ground fault in one of the two operation zones will
be cleared. The quadrilateral phase-to-ground distance element can significantly improve the
sensitivity to clear ground fault with extreme high resistance. The three zones of quadrilateral
characteristic can be enabled or disabled by the logic setting [En_ZPG1_Quad], [En_ZPG2_Quad]
and [En_ZPG3_Quad] respectively.The operation characteristic of quadrilateral distance element
is shown in Figure 3.7-5:
Φ Φ
Where:
[Z_PG1], [Z_PG2] or [Z_PG3] are the impedance setting of corresponding zone of Mho distance
protection.
protection. It is used to improve sensitivity for ground fault with high resistance. However, if the
voltage is extreme low, the directionality of quadrilateral characteristic is not clear. But Mho
characteric of phase-to-ground distance element using polarized positive sequence voltage has
definite directionality. Therefore, In case that phase voltage is lower than 10% of rated voltage, the
quadrilateral characteric will be disabled automatically and the Mho characteric is reserved.
Zone 1,2 of phase-to-phase distance element use polarized positive sequence voltage. Phase
shift θ2 is introduced here for polarized voltage in zones 1 and 2 just like θ1 in case of
phase-to-ground distance element. It is used also for improving performance against high fault
resistance in short line case. Value of θ2 can be set as 0° or 15°or 30°.
If three-phase short circuit fault occurs, since the polarized voltage has not been memorized, its
operation characteristic is a circle passing through the origin (Please refer to Figure 3.7-3). If the
positive sequence voltage is low, the fault will be measured by impedance element with
memorized polarization. There is neither problem about dead zone nor loss of directionality for bus
fault in this case.
Z ZD is impedance setting [Z_Rev] of reverse distance element, usually, which is set to 50% of the
protected line. In order to prevent existing dead zone in the protected zone, origin is included in
1
the operation characteristic which is shifted Z ZD toward forward direction.
2
3.7.5 Blinder Scheme
The blinder characteristic shown in Figure 3.7-7 can be used to restrict the reach of a distance
relay on a long line or during heavy load conditions. The distance relay will be allowed to trip only
when both blinders are operated (i.e., the apparent impedance must be between the two
characteristics).
jX
B ZZD A
Φ
R
RZD RZD
In order to ensure distance relay not affected by load impendence, the phase-to-phase and
phase-to-ground blinders are used. As shown in Figure 3.7-7, the slope of blinder is same to
positive sequence sensitivity angle Φ, RZD is the setting [R_Blinder]. The operation region is
between line A and line B. The logic setting [En_Blinder] can decide whether the blinder is enabled
or not.
Power swing blocking for distance element will be released if any of the following PSBR elements
operate.
If any of the following condition is matched, FD PSBR will operate for 160ms.
1) Positive sequence current is lower than the setting [I_OC_PSBR] before general fault detector
element operates.
2) Positive sequence current is higher than the setting [I_OC_PSBR] before general fault
detector element operates, but the duration is less than 10ms.
I0+I2>m×I1
The “m” is an internal fixed coefficient which can ensure UF PSBR operate during power swing
with internal unsymmetrical fault, while not operate during power swing or power swing with
external fault.
If a three-phase fault occurs and FD PSBR is invalid (160ms after GFD operates), neither FD
PSBR nor UF PSBR will be able to operate to release the distance protection. Thus, SF PSBR is
provided for this case specially. This detection is based on measuring the voltage at power swing
center:
UOS=U1×COSΦ
Where:
When three-phase circuit breaker is in the unsymmetrical state, PD PSBR will operate if any of the
1) The faulty phase selected by fault phase selection element is not the phase tripped.
2) The difference of current deviation of power frequency component between two healthy
phases increases to certain value all of a sudden.
In the above diagram, x can be 1, 2 or 3. If the logic setting [En_PSBR_Zx] is set as “0”, zone x of
distance element is not blocked by PSBR and PSBR for zone x of distance element will operate
right now (i.e. output value of [PSBR_Zx] in the above diagram is “1”).
If the logic setting [En_PSBR_Zx] is set as “1”, zone x of distance element is controlled by PSBR
element. Only if zone x of distance element operates and PSBR condition for zone x is also met,
PSBR for zone x of distance element will operate (i.e. output value of [PSBR_Zx] in the above
diagram is “1”).
The logic diagram of PSBR for directional distance element of pilot protection is similar as the logic
diagram of PSBR for zone x of distance element, as shown in the following figure.
Figure 3.7-9 Logic diagram of PSBR for directional distance element of pilot protection
[PSBR_Z1]
[PSBR_Z2]
[PSBR_Z3]
existing fault. This is especially critical if the line in the remote station is grounded, since the
distance protection and directional zero-sequence overcurrent protection would not clear the fault
until their time delays had elapsed. In this situation, however, the fastest possible clearance is
desired.
The SOTF (switch onto fault) protection is a complementary function to the distance protection and
to the directional zero-sequence overcurrent protection. With the SOTF protection, a fast trip is
achieved for a fault on the whole line, when the line is being energized. It shall be responsive to all
types of faults anywhere within the protected line.
The SOTF protection shall be controlled by an reclosing logic using both voltage and current level
detectors. It shall be enabled for a period when the circuit is energized either manually or via a
auto-reclosing system.
Status of 3-pole AR
≥1
& 100ms 0
Status of manually closing
& ≥1 Op_ROC_SOTF
3I0Cal > [I_ROC_SOTF]
& 60ms 0
Status of 1-pole AR
Zero-sequence SOTF protection will operate to trip three-phase circuit breaker with a time delay of
60ms when 1-pole auto-reclosing.
Zero-sequence SOTF protection will operate to trip three-phase circuit breaker with a time delay of
100ms if 3I0Cal is greater than setting [I_ROC_SOTF] when 3-pole auto-reclosing or manually
closing.
Zone 3 of distance element for SOTF will operate to trip three-phase circuit breaker when
manually closing.
Zone 2 and 3 of distance element for SOTF without PSBR logic will operate to trip three-phase
circuit breaker if the logic setting [En_Z2SOTF_AR3P] and [En_Z3SOTF_AR3P] are set as “1”
when 3-pole auto-reclosing.
Zone 2 of distance element for SOTF with PSBR logic will operate to trip three-phase circuit
breaker when 1-pole or 3-pole auto-reclosing if the logic setting [En_Z2SOTF_AR3P] is set as “0”.
provided to avoid line overvoltage by compensation of the line capacitance and thus reduction of
the overvoltage, the overvoltage will endanger the insulation if the reactors fail (e.g. due to fault
clearance). The line must be de-energised within a very short time.
The overvoltage protection in this device detects the phase voltages UA, UB and UC or the
phase-to-phase voltages UAB, UBC and UCA. The overvoltage protection can be used for trip
purpose. Besides, the overvoltage protection can also be used to initiate transfer trip, which can
be controlled by local circuit breaker selectively.
[En_OV1]
&
[En_Vpp_OV]
&
UAB>[V_OV1] >=1
[Op_OV1]
&
UB>[V_OV1] &
>=1
[t_OV1]
&
UBC>[V_OV1]
&
UC>[V_OV1] &
>=1
[t_OV1] >=1
&
&
UCA>[V_OV1]
&
[Opt_1P/3P_OV]
[BI_52b_Pha] >=1
& [BO_OV_Init_TT]
[BI_52b_Phb]
[BI_52b_Phc]
&
[En_52b_Ctrl_TT]
[En_OV1_Init_TT]
Where:
Inverse-time characteristics (IDMT) defined in IEC60255-3 can be adopted, the formula is shown
as follows.
β
t (U ) = Tp
U (Equation 3.9-1)
( )τ − 1
Up
Where :
U p is the basic voltage (also called voltage limit), i.e. the setting [V_OVn] (n=1 or 2).
β is a certain constant.
τ is the exponent.
U is the actual value of measured voltage.
For stage 1 and stage 2 of overvoltage protection, definite-time characteristic and five kinds of
inverse-time characteristics can be choose from by setting the logic setting
[Opt_Characteristic_OVn] (n=1 or 2). The parameters of each characteristics are listed in the
following table.
[Opt_Characteristic_OVn] τ β
0: Definite-time characteristic 0 0
1: inverse-time characteristic 1 1
2: Standard inverse-time characteristic 0.02 0.14
The undervoltage protection can also use the phase voltages UA, UB and UC or the
phase-to-phase voltages UAB, UBC and UCA. Only stage 1 of undervoltage protection can be used
for alarm purpose or trip purpose. Stage 2 of undervoltage protection can be used for trip purpose
only. The undervoltage protection is used to separation instead of load shedding.
When GFD element reflecting current operates, including DPFC overcurrent element and
zero-sequence overcurrent element, the undervoltage protection will pick up.
When any of the following conditions is fulfilled, the undervoltage protection will be blocked.
1. VT circuit fails, if the voltage comes from busbar VT, the voltage will restore to the normal level
immediately after the fault being cleared away. If the voltage comes from line VT, the voltage
will decrease to zero immediately after the fault being cleared away. For the latter case, in
order to prevent undervoltage protection from not dropping off, auxiliary current criterion is
provided to resolve it. (Input 1)
3. Binary input of blocking undervoltage is energized, such as normally closed contact of line
disconnector. (Input 3)
4. Any phase of circuit breaker is open (binary input of normal close contact of breaker is
energized) and the corresponding phase current is smaller than 0.06IN. (Input 4)
[En_UV1]
Block UV
&
[En_Vpp_UV]
&
UAB<[V_UV1] >=1
&
[Alm_UV1]
&
UB<[V_UV1] &
>=1
[t_UV1]
&
UBC<[V_UV1]
&
UC<[V_UV1] &
>=1
[t_UV1] >=1
&
&
UCA<[V_UV1]
[Opt_1P/3P_UV]
&
[Op_UV1]
[En_Alm_UV1]
Where:
Inverse-time characteristics (IDMT) defined in IEC60255-3 are adopted, the formula is shown as
follows.
β
t (U ) = Tp
U (Equation 3.9-2)
1 − ( )τ
Up
Where :
U p is the basic voltage (also called voltage limit), i.e. the setting [V_UVn] (n=1 or 2).
β is a certain constant.
τ is the exponent.
U is the actual value of measured voltage.
For stage 1 and stage 2 of undervoltage protection, definite-time characteristic and five kinds of
inverse-time characteristics can be choose from by setting the logic setting
[Opt_Characteristic_UVn] (n=1 or 2). The parameters of each characteristics are listed in the
following table.
[Opt_Characteristic_UVn] τ β
0: Definite-time characteristic 0 0
1: inverse-time characteristic 1 1
2: Standard inverse-time characteristic 0.02 0.14
3: Very inverse-time characteristic 1 13.5
4: Extremely inverse-time characteristic 2 80
5: Long time inverse-time characteristic 1 120
Stub overcurrent protection only including one stage can be enabled or disabled by the logic
setting [En_OC_Stub] and normally closed auxiliary contact of line disconnector [BI_DS_Line].
Based on calculating input current, which is summation current of CT1 and CT2, the logic scheme
of stub overcurrent protection is shown as Figure 3.10-2.
Where:
Breaker failure protection issues a back-up trip command to trip adjacent circuit breakers in case
of a tripping failure of the circuit breaker, and clears the fault as requested by the object protection.
To utilize the protection information of faulty equipment and the electrical information of failure
circuit breaker to constitute the criterion of breaker failure protection, it can ensure that the
adjacent circuit breakers of failure circuit breaker are tripped with a shorter time delay, so that the
blackout range is minimum, and ensure stable operation of the entire power grid to prevent
generators, transformers and other components from seriously damaged and the power grid from
collapse.
When both the phase-segregated tripping contact from line protection and the corresponding
phase overcurrent element operate, or both the three-phase tripping contact and any phase
overcurrent element operate, breaker failure protection will send three-phase tripping command to
trip local circuit breaker with the time delay of [t_BFP1] and trip all adjacent circuit breakers with
the time delay of [t_BFP2].
Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, so zero-sequence current
criterion and negative-sequence current criterion are provided for breaker failure protection
initiated by generator and transformer protection. They can be enabled or disabled by logic
settings [En_ROC_3P_BFP] and [En_NegOC_3P_BFP] respectively.
For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, the binary
input [BI_BF_Start_WOI] is equipped, once the binary input is energized, breaker failure protection
can be chose to be initiated by normally closed contact of circuit breaker.
[BI_ExTrpA]: The binary input of phase-A tripping contact from external protection
[BI_ExTrpB]: The binary input of phase-B tripping contact from external protection
[BI_ExTrpC]: The binary input of phase-C tripping contact from external protection
[BI_ExTrp3P_L]: The binary input of three-phase tripping contact from line protection
[BI_ExTrp3P_GT]: The binary input of three-phase tripping contact from generator or transformer
protection
[BI_BF_Start_WOI]: Once the binary input is energized, breaker failure protection can be chose to
be initiated by normally closed contact of circuit breaker.
An alarm signal [Alm_BI_ExTrp] will be issued if any of the binary inputs of single-phase or
three-phase tripping contact from external protection is energized and the duration is longer than
10s.
When the protection element operates and the tripping signal issued, the breaker failure protection
will also be initiated.
The logic makes the relay ideal for single-phase tripping applications.
If ΔUOΦMAX is several times higher than the other two deviation of phase operation voltages, the
single-phase fault is ensured, otherwise, the multiplex-phase fault is ensured.
ΔUOPA Phase A
ΔUOPB Phase B
ΔUOPC Phase C
ΔUOPAB Phase AB
ΔUOPBC Phase BC
ΔUOPCA Phase CA
1) For single-phase earth fault, I0 and I2 of faulty phase are in-phase and its distance element
operates.
2) For two-phase earth fault, I0 and I2 of non-faulty phase are in-phase but its distance element
does not operate.
Pole disagreement procedure comprises of the protection of pole disagreement state and switch
onto fault protection. When the following conditions are met, pole disagreement state is ensured
delay 50ms.
1) Trip confirmation
Trip confirmation means that tripping signal is issued and any phase current is smaller than 0.06IN
4) When tripped phase current is greater than 0.06IN or 52b of tripped phase is de-energized,
SOTF protection is initiated for 200ms
1) When three-phase currents are greater than 0.06IN or three-phase 52b are de-energized,
SOTF protection is initiated for 200ms
When the primary system is in the single-phasing, three-phase trip signal will be sent with a time
delay of 200ms if the following conditions are met.
temperature.
The inverse-time thermal overload function supervises the phase currents and provides a reliable
protection against damage caused by excessive currents. When the conductor heat exceeds the
permissible value, based on a thermal model calculated from phase currents, the inverse-time
thermal overload protection can provide alarm signal to prompt operator or trip to directly isolate
the overload line.
I
KIB
For thermal overload protection without consideration of previous load current, the following
tripping characteristic is applied. For different thermal time constants τ , the operating time T is
calculated in accordance with the following equation:
I2
T = τ ⋅ ln (Equation 3.14-1)
I 2 − (k ⋅ I B ) 2
The thermal overload protection with consideration of previous load current constantly updates the
uppper thermal model calculation. The operating time T is calculated in accordance with the
following equation (complete memory in accordance with IEC 60255-8).
I 2 − I p2
T = τ ⋅ ln (Equation 3.14-2)
I 2 − (k ⋅ I B ) 2
where:
T: operating time
k: constant, overload coefficient, k2: threshold multiple of thermal capacity, corresponding with
setting [ThM_OvLd1] or [ThM_OvLd2]
The protection device is equipped with IEC60255-8 “hot” curve to make up thermal overload
protection, and it calculates real-time temperature rise curve without interruption, continuously
beginning with Ip is equal to zero from the beginning. When thermal capacity of temperature rise is
greater than setting [ThM_OvLd1] (shown as percentage), protectiondevice operates to issue
alarm signal if the logic setting [En_OvLd1_Alm] is set as “1”. When heat quantity of temperature
rise is larger than setting [ThM_OvLd2] (shown as percentage), protection device will operate to
trip if the logic setting [En_OvLd2_Trp] is set as “1” or issue alarm signal if the logic setting
[En_OvLd2_Alm] is set as “1”.
When two asynchronous systems are connected together, due to phase difference between
systems at both sides, larger impact will be led to the system during closing. In addition, the
auto-reclosing and manual closing are applied with the synchrocheck to avoid this situation and
improve the system stability. The synchrocheck includes synchronism check and dead check.
The dead check function measures the amplitude of line voltage and bus voltage at both sides of
the circuit breaker; then compare them with the live check setting [V_Live] and the dead check
setting [V_Dead]; The output is only given when the actual measured quantities match the set
conditions.
Synchrocheck in this device can be used for auto-reclosing and manual closing for both
single-breaker and dual-breaker.
When used for the synchrocheck of single-breaker, comparative relationship between reference
voltage (UL) and synchronous voltage (UB) is as follows.
Figure 3.15-1 Comparative relationship between reference voltage and synchronous voltage
When not applying voltage selection function and for single-breaker, the MCB of voltage and
voltage connecting method are shown in the following figure.
Figure 3.15-2 Wiring diagram of voltage connecting method without voltage selection for
single-breaker
In the figure, [En_LineVT] is system setting, indicating the voltage Ua, Ub, Uc used by protection is
from line VT or bus VT of the circuit breaker, it should be set according to the actual situation.
When applying voltage selection function, it involves voltage selection of bus breaker and tie
breaker for double bus and one and a half breakers arrangements. Selecting approach is as
follows.
}
}
For the disconnector positions, the normally open (NO) and normally closed (NC) contacts of the
disconnector for bus 1 and bus 2 are supplied to determine the disconnector open and closed
positions. The logic is as follows.
BI UB1D_Clsd &
UB1_SEL
BI UB1D_Open
Voltage
selection UB2_SEL
logic
BI UB2D_Clsd &
BI UB2D_Open
&
InvalidSEL
UB1 UB
UB2
After acquiring the disconnector open and closed positions of double busbars, use the following
logic to acquire the branch voltage of double busbars.
Disconnector that connect Keep the original value Obtain from Bus 1 VT
the line with bus 1 is closed (UB1_Sel=1)
Disconnector that connect Obtain from Bus 2 VT Keep the original value
the line with bus 1 is open (UB2_Sel=1)
If voltage selection is invalid (Invalid_Sel=1), keep the original selection and without switchover.
For bus breaker (take bus breaker of bus 1 as an example), the device acquires the disconnector
open and closed positions of two outgoing feeders and bus 2. The logic is as follows.
Figure 3.15-6 Logic diagram of the voltage selection function for the bus breaker in one and a half
breakers arrangement
For the tie breaker, the device acquires the disconnector open and closed positions of two
outgoing feeders and two busbars. The logic is as follows.
Figure 3.15-7 Logic diagram of the voltage selection function for the tie breaker in one and a half
breakers arrangement
When the selected voltage fails (including VT circuit failure and MCB failure), the device will issue
the corresponding voltage failure signal. If the voltage selection is invalid (Invalid_Sel=1), keep
the original selection and without switchover.
In order to easy to describe, one of the two voltages used in the synchrocheck (synchronism check
and dead check) which obtained after voltage selection function is regarded as line voltage, and
another is bus voltage.
When the frequency difference, voltage difference, and phase difference of voltages on both sides
of the circuit breaker is calculated in the protective device, they can be used as input conditions of
the synchronism check.
When the synchronism check function is enabled and the voltages of both ends meets the
requirements of the voltage difference, phase difference, and frequency difference, and there is no
synchronism check blocking signal, it is regarded that the synchronism check conditions are met.
The dead check conditions have three types, namely, live-bus and dead-line check, dead-bus and
live-line check and dead-bus and dead-line check. The above three modes can be enabled and
disabled respectively by the corresponding logic settings. The protection can calculate the
measured bus voltage and line voltage at both sides of the circuit breaker and compare them with
the setting [V_Live] and [V_Dead], when the voltage is higher than [V_Live], the bus/line is
regarded as live; when the voltage is lower than [V_Dead], the bus/line is regarded as dead.
EN [En_SynChk_AR]
SIG Start_SYN
&
[t_SynChk] 0ms
SIG UBLive SynChkOk
&
50ms 0ms
OTH ULLive &
OTH UDiffOk
OTH phiDiffOk
OTH fDiffOk
En [En_NoChk_AR] SYNOk
SIG DeadChkOk
This device comprises two synchrocheck modules, correspond to circuit breaker 1 and circuit
breaker 2 respectively.
Please refer to Chapter 8 about the description of settings and section 7.4 about the description of
binary signals.
Where:
1) UdiffOk
Voltage difference condition for AR is satisfied, voltage difference between bus voltage and line
voltage is smaller than [V_Diff_SynChk].
2) phiDiffOk
Phase difference condition for AR is satisfied, phase difference between bus voltage and line
voltage is smaller than [phi_Diff_SynChk].
3) fDiffOk
frequency difference condition for AR is satisfied, frequency difference between bus voltage and
4) Blk_SYN
The binary input of total blocking of the synchrocheck function for AR.
5) Blk_SynChk
Blocking synchronism check for AR. If the value is “1”, the output of synchronism check is “0”.
6) Blk_DeadChk
7) Start_SYN
Synchronism check starting signal, usually it was the auto-reclosure starting signal of
auto-reclosure module.
8) ULLive, UBLive
The line voltage and the bus voltage is greater than the voltage setting [V_Live].
9) UBDead, ULDead
The bus voltage and the line voltage is smaller than the voltage setting [V_Live].
10) Alm_VTS_UB
11) Alm_VTS_UL
12) DLDBOk
13) DLLBOk
14) LLDBOk
The logic diagram gives the introduction to the working principles of the synchronism check and
dead check for manual closing.
When the frequency difference, acceleration of frequency difference, voltage difference, and
phase difference of voltages on both sides of the circuit breaker is calculated in the protective
device, they can be used as input conditions of the synchronism check for manual closing.
The dead check conditions for manual closing have three types, namely, live-bus and dead-line
check, dead-bus and live-line check and dead-bus and dead-line check. The above three modes
can be enabled and disabled by the logic settings [En_LvB_DdL_M], [En_DdB_LvL_M] and
[En_DbB_DdL_M] respectively.
OTH BI_ManCls
OTH DeadChkOk_M
This device comprises two synchrocheck modules, correspond to circuit breaker 1 and circuit
breaker 2 respectively.
Please refer to Chapter 8 about the description of settings and section 7.4 about the description of
binary signals.
Where:
1) Blk_SYN_M
The binary input of total blocking of the synchrocheck function for manual closing
2) Blk_SynChk_M
Blocking synchronism check for manual closing. If the value is “1”, the output of synchronism
check is “0”.
3) UdiffOk_M
Voltage difference condition for manual closing is satisfied, the voltage difference between two
synchronous voltages is smaller than the voltage difference blocking setting [V_Diff_SynChk_M].
4) fBus_Ok, fLine_Ok
The frequency on both sides of the circuit breaker (f_Line, f_Bus) should be measured, and the
two frequencies must not deviate from the rated frequency more than ±5Hz.
5) phiDiffOk_M
Phase difference condition for manual closing is satisfied, phase difference between two
synchronous voltages is smaller than the phase difference blocking setting [Phi_Diff_SynChk_M].
6) fDiffOk_M
Frequency difference condition for manual closing is satisfied, the frequency difference between
the bus frequency and the line frequency is smaller than the frequency difference blocking setting
[f_Diff_SynChk_M].
7) fDiffDtOk_M
frequency difference between two synchronous voltages is smaller than the corresponding
blocking setting [Df/dt_SynChk_M].
8) Blk_DeadChk_M
9) ManCls_Out
Triggering signal: manually closing the circuit breaker if the value is “1”.
Note!
This device comprises two synchrocheck modules, correspond to circuit breaker 1 and
circuit breaker 2 respectively, the corresponding settings and singals will be suffixed by
CBn (n is the number of the CB and it can be 1 and 2).
7 MCB_VT_UL1 Normally closed (NC) contacts of the MCB for line 1 voltage
10 MCB_VT_UL2 Normally closed (NC) contacts of the MCB for line 2 voltage
13 MCB_VT_UB1 Normally closed (NC) contacts of the MCB for bus 1 voltage
16 MCB_VT_UB2 Normally closed (NC) contacts of the MCB for bus 2 voltage
12 ULLive The line voltage is greater than the voltage setting [V_Live]
13 ULDead The line voltage is smaller than the voltage setting [V_Live]
14 UBLive The bus voltage is greater than the voltage setting [V_Live]
15 UBDead The bus voltage is smaller than the voltage setting [V_Live]
Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and no automatic reclosing is initiated after faulty feeder is
tripped. For some joint line, such as overhead line and transformer unit wiring, overhead line and
cables, hybrid transmission lines, etc., need to ensure that only the fault of overhead line can
reclosed, or make a choice according to the actual situation.
When the protection device uses external automatic reclosure instead of the automatic reclosure,
the protection device can output some configurable output to initiate external AR, such as, contact
of initiating AR, phase-segregated tripping contact, single-phase tripping contact, three-phase
tripping contact and contact of blocking AR. According to actual requirement, these contacts can
be selectively connected to external automatic reclosure device to initiate AR.
For phase-segregated circuit breaker, AR mode can be 1-pole AR for single-phase fault and
3-pole AR for multi-phase fault, or always 3-pole AR for any kinds of fault according to actual
system requirement. If the fault still exists after reclosing or AR number is equal to preset value of
AR number, the protection device will send final tripping command. The protection device must
provide tripping function based on faulty phase selection if adopting 1-pole AR.
AR can be enabled or disabled by internal logic setting or external input. When AR is enabled, the
protection device will output contact [AR_On], otherwise, output contact [AR_Off]. After some
reclosing conditions, such as, CB position, CB pressure and so on, is satisfied, the protection
device will output contact [Ready_AR].
According to requirement, the protection device can be set as one-shot or multiple-shot AR. When
adopting multiple-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR
or 1/3-pole AR. The rest AR mode is only set as 3-pole AR and its number is determined by the
maximum 3-pole reclosing number.
For one-shot AR or first reclosing, AR mode can be selected by logic setting [En_1PAR],
[En_3PAR] and [En_1/3P_AR] or external inputs. When 3-pole or 1/3-pole AR mode is selected,
the following three types of check modes can be selected: dead check, synchronism check and no
check.
For the first reclosing, AR mode can be 1-pole AR or 3-pole AR, however, the selection is valid
only to the first reclosing, after that it can only be 3-pole AR.
When logic setting [En_SetOpt_AR] is set as “1”, AR mode is determined by logic settings:
When logic setting [En_SetOpt_AR] is set as “0”, AR mode is determined by external inputs. The
relation between AR mode and external inputs, see the table below.
The automatic reclosure must be ready to operate (AR ready) before performing reclosing. AR
ready means the automatic reclosure can perform at least one time of reclosing function: breaker
open-close-open.
When the protection device is energized or the settings modified, the following conditions must be
met before the reclaim time begins:
1. AR function is enabled
2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal
3. The duration when the circuit breaker is on closed state before fault occurrence is not smaller
than the setting [t_CBClsd_AR]
After the automatic reclosure operates, to meet the condition of AR ready once again, the
automatic reclosure must drop off (Active_AR=0) besides the above conditions which shall be met.
1. CB Closed
It means the circuit breaker is on closed position. Moreover the duration when the circuit breaker is
on closed position must be greater than the setting [t_CBClsd_AR].
2. Healthy_CB
It is an external input via opto-coupler indicating whether circuit breaker has enough energy to
close, and the input [Healthy_CB] must be energized before the automatic reclosure gets ready.
Because most circuit breakers can finish one time complete process: open-closed-open, it is
necessary that circuit breaker has enough energy before reclosing. When the time delay of AR is
exhausted, AR will be blocked if the input [Healthy_CB] is still not energized with a time delay
[t_Wait_CBHealthy]. If the function is not needed, this input cannot be configured, and its state will
be thought as “1” by default.
3. [EBI_Lockout]
It is the input signal used to block AR, which can connect with manual closing contact or tripping
contact of breaker failure protection and transformer protection. When the input is energized, the
automatic reclosure will be blocked immediately. After this input is de-energized, the blocking
condition will disappear with a time delay [t_Broaden_BlkAR].
When the internal blocking condition of AR is met (such as, zone 3 of distance protection operates,
the protection device operates for multi-phase fault, the protection device operates for three-phase
fault and so on.) The blocking flag of AR will be also controlled by the internal blocking condition of
AR. When the blocking flag of AR is valid, the automatic reclosure will be blocked immediately.
After the blocking flag of AR is invalid, the blocking for AR will disappear with a time delay
[t_Broaden_BlkAR].
4. t_Broaden_BlkAR
It is stretching time of blocking AR. AR will be blocked immediately once the blocking condition of
AR appears, but the blocking condition of AR will drop out with a time delay [t_Broaden_BlkAR]
after blocking signal disappears
5. Active_AR
It means that the reclosing logic is triggered. When any protection element operates to trip, this
element [Active_AR] will operate until AR drop off (Reset Command)
6. Any trip
Any tripping signal from external protection device or internal protection element
7. EnableAR
AR function can be enabled by internal logic settings of AR mode or external inputs besides
internal logic setting [EN_AR].
When logic setting [ExtCtrl_AROn] set as “1”, AR enable are determined by external inputs and
logic settings.
When logic setting [ExtCtrl_AROn] set as “0”, AR enable are determined only by logic settings.
For one-shot reclosing, if 1-pole AR mode is selected, the automatic reclosure will discharge when
there is three-phase tripping signal or inputs of multi-phase open position.
3.16.3.2 AR Initiation
AR mode can be selected by external inputs or internal logic settings. If the logic setting
[En_SetOpt_AR] set as “1”, AR mode is determined by the internal logic settings. If the logic
settings [En_SetOpt_AR] set as “0”, AR mode is determined by the external inputs.
AR can be initiated by tripping signal of line protection, and the tripping signal may be from internal
trip signal or external trip signal.
When selecting 1-pole AR or 1/3-pole AR, line single-phase fault will trigger 1-pole AR. When AR
is ready to reclosing (“AR Ready”=1) and the single-phase tripping command is received, this
single-phase tripping command will be kept in the protection device, and 1-pole AR will be initiated
after the single-phase tripping command drops out. The single-phase tripping command kept in
the protection device will be cleared off after all protection elements of the protection device drop
out (Reset Command). Its logic scheme is shown in Figure 3.16-2.
When selecting 3-pole AR or 1/3-pole AR, three-phase tripping will trigger 3-pole AR. When AR is
ready to reclosing (“AR Ready”=1) and the three-phase tripping command is received, this
three-phase tripping command will be kept in the protection device, and 3-pole AR will be initiated
after the three-phase tripping command drops out. The three-phase tripping command kept in the
protection device will be cleared off after all protection elements of the protection device drop out.
(Reset Command) Its logic scheme is shown in Figure 3.16-3.
2. AR initiated by CB state
&
EN [En_CBInitAR]
SIG Ready_AR
SIG 1/3PAR_Sel
3.16.3.3 AR Reclosing
After AR initiated, the protection device will output the initiating contact of AR. For 1-pole AR, in
order to prevent pole discrepancy protection from maloperation under pole discrepancy conditions,
the initiating contact of 1-pole AR can be used to block pole discrepancy protection.
When the time delay of AR expires after AR initiated, as for 1-pole AR, the result of synchronism
check will not be judged, and reclosing command will be output directly. As far as the 3-pole AR, if
the synchronism check is enabled, the reclosing command shall be determined whether is issued
or not based on the result of synchronism check. After the time delay of AR expires, if the
synchronism check is still unsuccessful within the time delay [t_Wait_SynChk_AR], the signal of
synchronism check failure (SYN_Fail) will be output and the AR will be blocked. If 3-pole AR with
no-check is enabled, the condition “SYNOk” will be established always. And here, SYNOk can be
the signal of synchronism check success from the synchronism check logic inside the protection
device or in the external protection device.
In case the system has fault, the circuit breaker will be tripped normally. After fault is cleared, the
tripping command will drop out immediately. In case the circuit breaker is in failure, etc., and the
continuous tripping time of the circuit breaker is over the time delay [t_PersistTrp], the AR will be
blocked, as shown in the following figure.
In case pilot protection adopting permissive scheme, when the communication channel is
abnormal, the main protection will disabled. In the process of channel abnormality, in case internal
fault happens to the transmission line, the backup protection at both ends of line will operate to trip
the circuit breaker of each end. Whereas the operation time of backup protection at both ends of
the line is possibly non-accordant when internal fault happens to the transmission line, whilst the
time delay of AR needs to consider the arc-extinguishing and insulation recovery ability for
transient fault, so the time delay of AR shall be considered comprehensively according to the
operation time of the protection device at both ends. When the communication channel of main
protection is abnormal (input [PLCLost] is energized), and the logic setting [En_ExtendDly_AR] is
set as “1”, then in case of internal fault, the time delay of AR shall be equal to the original time
delay of AR plus the extra time delay [t_ExtendDly_AR], so as to ensure the recovery of insulation
intensity of fault point when reclosing after transient fault. This extra time delay [t_ExtendDly] is
only valid for the first AR pulse.
>=1
& &
&
BI [PLCLost] Extend AR time
SIG Active_AR
EN [En_ExtendDly_AR]
Figure 3.16-7 Extra time delay control and blocking logic of long-time tripping
Reclosing pulse length may be set through the setting [t_PW_AR]. For the circuit breaker without
anti-pump, it is available to enable the adjustment function of reclosing pulse length by setting
logic setting [En_CutPulse_AR] as “1”. When this function is enabled, if the protection device
operates to trip during reclosing, the reclosing pulse will drop out immediately, so as to prevent
multi-shot reclosing into fault. However, the minimum reclosing pulse length is not below 50ms, so
as to ensure AR can operate. After the reclosing command is issued, AR will drop out with time
delay [t_Reclaim_AR], and can carry out next reclosing.
For transient fault, the fault will be cleared after protection device operates to trip. After the
reclosing command is issued, AR will drop out with time delay [t_Reclaim_AR], and can carry out
next reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR
initiated, the reclosing will be considered as unsuccessful, including the following cases.
1. For one-shot AR, if the tripping command is received again after the reclosing pulse is
issued, the reclosing shall be considered as unsuccessful.
2. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and
the tripping command is received again after the last reclosing pulse is issued, the
reclosing shall be considered as unsuccessful.
3. It is also available to judge whether the reclosing is successful by CB state, which can be
enabled by setting logic setting [En_UnsucChkByCB] as “1”. If CB is still in open state
with a time delay [t_Unsuc_AR] after the reclosing pulse is issued, the reclosing shall be
considered as unsuccessful. For this case, the protection device will issue signal
“Fail_AR” to indicate the reclosing is unsuccessful, and this signal will drop out after
“Reset Command”. AR will be blocked if the reclosing shall be considered as
unsuccessful.
After AR unsuccess is confirmed, AR will be blocked. AR will not enter into the ready state unless
the circuit breaker position drops out, and can only begin to enter into the ready state again after
the circuit breaker is closed.
The protection device may be set up into one-shot or multiplex-shot AR. Through the setting
[N_AR], the maximum number of reclosing attempts may be set up to 4 times. Generally, only
one-shot AR is selected. Some corresponding settings may be hidden if one-shot AR is selected.
1. 1-pole AR
[N_AR]=1 means one-shot reclosing. For one-shot 1-pole AR mode, the 1-pole AR will be initiated
only for single-phase fault and the correct faulty phase selected, otherwise, AR will be blocked. For
single-phase transient fault on the line, the line protection device will operate to trip and 1-pole AR
is initiated. After the time delay for 1-pole AR is expired, the protection device will send reclosing
pulse, and then the automatic reclosure will drop off after the time delay [t_Reclaim_AR] to ready
for the next reclosing. For permanent fault, the protection device will operate to trip again after the
reclosing is performed, and the protection device will output the signal of reclosing failure
[Fail_AR].
[N_AR]>1 means multi-shot reclosing. For multi-shot reclosing in 1-pole AR mode, the first
reclosing is 1-pole AR, and the subsequent reclosing can only be 3-pole AR. For single-phase
transient fault on the line, the line protection device will operate to trip and then 1-pole AR is
initiated. After the time delay of the first reclosing is expired, the protection device will send
reclosing pulse, and then the automatic reclosure will drop off after the time delay [t_Reclaim_AR]
to ready for the next reclosing. For permanent fault, the protection device will operate to trip again
after the reclosing is performed, and then 3-pole AR is initiated. At this time, the time delay applies
the setting [t_3Ph-Shot2_AR]. After the time delay is expired, if the reclosing condition is met, the
protection device will send reclosing pulse. It does this again and again until the reclosing is
successful or the reclosing number is equal to the maximum permitted reclosing number. If the first
fault is multi-phase fault, the protection device operates to trip three-phase and initiate 3-pole AR.
At this time, the time delay applies the setting [t_3Ph-Shot1_AR]. For the possible reclosing times
of 3-pole AR in 1-pole AR mode, see Table 3.16-1.
2. 3-pole AR
[N_AR]=1 means one-shot reclosing. For one-shot 3-pole AR mode, the line protection device will
operate to trip when the transient fault occurs on the line and 3-pole AR will be initiated. After the
time delay for 3-pole AR is expired, the protection device will send reclosing pulse, and then the
automatic reclosure will drop off after the time delay [t_Reclaim_AR] to ready for the next reclosing.
For permanent fault, the protection device will operate to trip again after the reclosing is performed,
and the protection device will output the signal of reclosing failure [Fail_AR].
[N_AR]>1 means multi-shot reclosing. For multi-shot reclosing in 3-pole AR mode, the line
protection device will operate to trip when the transient fault occurs on the line and 3-pole AR will
be initiated. After the time delay of the first reclosing is expired, the protection device will send
reclosing pulse, and then the automatic reclosure will drop off after the time delay [t_Reclaim_AR]
to ready for the next reclosing. For permanent fault, the protection device will operate to trip again
after the reclosing is performed, and then 3-pole AR is initiated after the tripping contact drops off.
After the time delay for AR is expired, the protection device will send reclosing pulse. It does this
again and again until the reclosing is successful or the reclosing number is equal to the maximum
permitted reclosing number. For the possible reclosing times of 3-pole AR in 3-pole AR mode, see
Table 3.16-1.
3. 1/3-pole AR
[N_AR]=1 means one-shot reclosing. For one-shot 1/3-pole AR mode, the line protection device
will operate to trip when the transient fault occurs on the line and 1-pole AR will be initiated for
single-phase fault and 3-pole AR will be initiated for multi-phase fault. After the respective time
delay for AR is expired, the protection device will send reclosing pulse, and then the automatic
reclosure will drop off after the time delay [t_Reclaim_AR] to ready for the next reclosing. For
permanent fault, the protection device will operate to trip again after the reclosing is performed,
and the protection device will output the signal of reclosing failure [Fail_AR].
[N_AR]>1 means multi-shot reclosing. For multi-shot reclosing in 1/3-pole AR mode, the line
protection device will operate to trip when the transient fault occurs on the line and AR will be
initiated. After the time delay of the first reclosing is expired, the protection device will send
reclosing pulse, and then the automatic reclosure will drop off after the time delay [t_Reclaim_AR]
to ready for the next reclosing. For permanent fault, the protection device will operate to trip again
after the reclosing is performed, and then 3-pole AR is initiated after the tripping contact drops off.
After the time delay for AR is expired, the protection device will send reclosing pulse. It does this
again and again until the reclosing is successful or the reclosing number is equal to the maximum
permitted reclosing number. For the possible reclosing times of 3-pole AR in 3-pole AR mode, see
Table 3.16-1.
The table below shows the possible reclosing times in various AR modes during fault.
1 1 0 0 1 1 1
2 1 1 0 2 1 2
3 1 2 0 3 1 3
4 1 3 0 4 1 4
For UHV lines, it normally applies duplicated protection configurations. If it applies reclosing
function in the line protection, it can enable the reclosing function any line protection or enable the
reclosing functions of both line protections at the same time without need to consider the match
between them.
If both sets of reclosing functions are enabled, when one of them recloses firstly by permanent
fault, the other will block the reclosing pulse according to the current condition of the faulty phase.
For one-shot AR mode, if the current is detected in the faulty phase, AR will be blocked
immediately to prevent the circuit breaker from reclosing for several times. For multi-shot AR mode,
if the current is detected in the faulty phase, the current reclosing pulse will be blocked and go into
the next reclosing pulse logic automatically. If the reclosing times are equal to the maximum
permitted reclosing number, the automatic reclosure will drop off after the time delay
[t_Reclaim_AR].
For one-shot or multi-shot AR, there is a corresponding reclosing counter at each stage. After
reclosing pulse is sent, the corresponding reclosing counter will plus 1 and the reclosing counter
may be cleared by the submenu “LOCAL CTRL”. If the circuit breaker is reclosed by other devices
during AR initiation, the automatic reclosure will go into the next reclosing pulse logic.
The following introduces several typical examples about the operating time sequence of AR, and
such examples respectively indicate the relationship of operating time sequence related to AR in
case of transient fault and permanent fault.
Fault
Trip
Open Open
52b
[t_Reclaim_AR]
Ready_AR
Active_AR
Inprog_AR
Inprog_1Ph-Shot1_AR
[t_1Ph-Shot1_AR]
Inprog_3Ph-Shot2_AR
[t_3Ph-Shot2_AR]
SYNOk
AR_Out
[t_PW_AR] [t_PW_AR]
Prep_Trp3P
Fail_AR
200ms
Time
As for the application occasions where each line is corresponding to two circuit breakers, such as
angle scheme or 3/2 breakers arrangement, it is necessary to configure different reclosing
priorities by the setting [Opt_Priority_AR] for the two circuit breakers.
When the reclosing with higher priority is reclosed into permanent fault or the circuit breaker
cannot be closed, it is necessary to block the reclosing of another circuit breaker, so as to avoid
the impact on circuit breaker due to that both circuit breakers are closed into permanent fault
simultaneously.
When the master AR is initiated, the protection device will issue the signal [WaitToSlave] to block
the slave AR.
If the master AR is successful, the signal [WaitToSlave] will drop out, and the slave AR will reclose
immediately. If the master AR fails, the master AR will send the signal “Fail_AR” and the signal
[WaitToSlave] will be kept until the “Reset Command”. If the slave AR receives the signal
“Fail_AR” or the signal [WaitToSlave] continuously for [t_WaitMaster], the slave AR will be blocked.
Note!
This protection device can also enable two sets of automatic reclosure logic at the same
time, which correspond to two circuit breakers respectively, but all the settings and singals
will be suffixed by CBn (n is the number of the CB and it can be 1 and 2).
Signal Description
EnableAR Binary input for enabling AR of corresponding circuit breaker. If
the logic setting [ExtCtrl_AROn]=1, enabling AR will be
controlled by the external input
DisableAR Binary input for disabling AR of corresponding circuit breaker. If
the logic setting [ExtCtrl_AROn]=1, disabling AR will be
controlled by the external input
BI_ExTrp1P_L The external single-pole tripping binary input from line
protection
BI_ExTrp3P_L The external three-pole tripping binary input from line
protection
BI_ExTrp3P_GT The external tripping binary input from transformer, generator
or reactor protection
The external phase-A tripping signal for corresponding circuit
BI_ExTrpA
breaker
The external phase-B tripping signal for corresponding circuit
BI_ExTrpB
breaker
The external phase-C tripping signal for corresponding circuit
BI_ExTrpC
breaker
2. Tripping logic 2
Trip phase A
Trip phase C
En_3PTrip
&
Enable AR
&
3-Pole AR
3. Blocking AR logic
Op_DEF_PilotP
&
En_DEF_Blk_AR
Op_UV1
≥1
Op_UV2 ≥1
Op_OV1
≥1
≥1
Op_OV2
Op_OC_Stub
≥1
Op_InvROC
Op_Z_Rev
Op_Perisist1P
≥1
Op_OC_VTS
& ≥1
Op_ROC_VTS
En_ZPP2_Blk_AR
&
Op_Z2 (Phase-to-phase)
≥1
En_ZPG2_Blk_AR
&
Op_Z2 (Phase-to-ground)
En_ROC1_Blk_AR
&
Op_ROC1
En_ROC2_Blk_AR
&
≥1
Op_ROC2
En_ROC3_Blk_AR
&
Op_ROC3
Op_Z3
≥1
Op_ROC4
En_PhSF_Blk_AR
&
Op_PhSelFail
EBI_Lockout ≥1 Blocking AR
VT circuit failure
2. DPFC distance protection, zone 1 of distance element and pilot protection operate to
implement selective tripping by phase selection element.
3. For zone 2 of distance protection, whether auto-reclosing blocked is adopted or not will be
decided by logic setting [En_ZPP2_Blk_AR] for phase-to-phase fault or [En_ZPG2_Blk_AR]
for phase-to-ground fault.
Zone 2 of distance element operates to to trip three-phase circuit breaker when logic setting
[En_ZPP2_Blk_AR] or [En_ZPG2_Blk_AR] is set as “1” for phase-to-phase fault or
phase-to-ground fault respectively.
4. For stage 1, stage 2 and stage 3 of directional zero-sequence overcurrent protection, whether
auto-reclosing blocked is adopted or not will be decided by logic setting [En_ROC1_Blk_AR],
[En_ROC2_Blk_AR] and [En_ROC3_Blk_AR] respectively.
5. If phase selection element fails and operation element can not drop off, three-pole tripping
command caused by phase selection failure will be sent after 200ms delay.
6. If any of the following conditions is matched, three-phase tripping signal will be sent directly.
7. Three-phase tripping will be used if two or three phases are selected by the phase selection
element.
8. Any fault occurs under following conditions, three-pole trip element will operate
The logic settings [En_3PTrip] is set as “1” (for two circuit breaker configuration, the setting
maybe with the suffix of “_CB1” and “_CB2” what correspond to circuit breaker 1 and circuit
breaker 2 respectively)
The binary input [EBI_Lockout] is energized (for two circuit breaker configuration, the setting
maybe with the suffix of “_CB1” and “_CB2” what correspond to circuit breaker 1 and circuit
breaker 2 respectively)
9. When a serious fault occurs, auto-reclosing will be blocked under following conditions:
10. Three-pole trip with auto-reclosing blocked can be selected by logic setting
[En_PhSF_Blk_AR], [En_MPF_Blk_AR] and [En_EVFault_Blk_AR] (for two circuit breaker
configuration, the setting maybe with the suffix of “_CB1” and “_CB2” what correspond to
circuit breaker 1 and circuit breaker 2 respectively).
11. If only reverse distance protection, the relay will not select faulty phase and locate where the
fault occurs.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a fault is detected during initialization when DC power supply is provided to the equipment,
the equipment will be blocked out, which means relay is out of service. Therefore you must
re-energize the relays or reset CPU module by restarting equipment to make relay back into
service.
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication and alarm contact outputs. At the same time event recording will record the failure alarm
which can be viewed in event recording report and be printed.
A common abnormality may block a certain number of protections functions while the other
functions can still work. However, if serious hardware failure or abnormality were detected, all
protection functions will be blocked and the LED “HEALTHY” will be extinguished and blocking
signal will be given by contacts output BO_FAIL. The protective device then can not work normally
and maintenance is required to eliminate the failure. All the commom alarm signal and the
corresponding repairmen suggestion have been listed below. Please refer to section 7.4.2 about
description about the alarm signal about each protective device.
Note!
If the protective device is blocked or alarm signal is sent during operation, please do find
out its reason with the help of self-diagnose record. If the reason can not be found at site,
please notice the factory NR. Please Do not simply press button “TARGET RESET” on the
protection panel or re-power on the protective device.
When any general fault detector picks up for longer than 10s, an alarm will be issued
[Alm_PersistFD] without the protective device blocked.
If 52b of three phases are energized that indicates circuit breaker is open but there is still current
detected in the line or three-phase circuit breaker is in pole disagreement, an alarm signal
[Alm_52b] will be issued after 10 seconds.
In normal operation program of the PCS-902, the phasor summation of bus three phase voltage is
checked frequently, if this phasor summation detected is higher than 0.08Unn (Unn is rated
secondary phase-to-phase voltage) and fault detection element does not operate, VTS will, after
1.25s, output an alarm [Alm_VTS].
If the phasor summation detected is lower than 0.08Unn but the bus positive voltage U1 is less
than one third of Unn (Unn is rated secondary phase-to-phase voltage), VTS will also issue an
alarm [Alm_VTS] after 1.25s when logic setting [En_LineVT] is set as “0”, otherwise, VTS will also
issue an alarm [Alm_VTS] after 1.25s when circuit breaker is closed (52b of three phases are
de-energized) or there is current existing on line.
VTS will issue an alarm [Alm_VTS] immediately when the binary input [BI_MCB_VT_Line] is
energized.
“1”
The alarm [Alm_VTS] will be reset automatically with a time delay of 10s after all three phases
voltage resume to normal condition.
If the line circuit breaker is in closed state which is indicated by 52b of three phases, but the
synchronism voltage is lower than the setting [V_Live], it is concluded that “synchronism voltage
transformer circuit failure” has occurred and an alarm [Alm_VTS_UB] or [Alm_VTS_UL] will be
issued after 10s.
If auto-reclosing is disabled, or [En_NoChk_AR] are set as “1”, synchronism voltage is not needed
to be connected and synchronism voltage transformer circuit failure supervision will be disabled.
When synchronism voltage transformer circuit failure is detected, function of synchronism check
and dead check in auto-reclosing logic will be disabled.
After synchronism voltage reverting to normal condition, the alarm will be reset automatically after
10s.
The equipment measures zero-sequence current from two sources, which is either calculated
depending on the summation of IA, IB and IC (3I0Cal=IA+IB+IC) or derived at the neutral current circuit
from three-phase currents (3I0).
If 3I0 is less than 0.75 times 3I0Cal or 3I0Cal is less than 0.75 times 3I0, after 200 ms, an alarm
[Alm_CTS] will be issued (only for one CB scheme).
If 3I0Cal exists (3I0>0.1In) but 3U0Cal derived is nearly zero (3U0Cal<3V) and at least one phase
whose current is zero, after 10s, an alarm [Alm_CTS] will be issued (for one or two CBs scheme).
When CT circuit failure is detected, CTFS will have the following influence on protection.
3U0Cal: zero-sequence voltage calculated depending on the summation of UA, UB and UC. (i.e.,
3U0Cal=UA+UB+UC)
5.1 Metering
PCS-902 performs continuous measurement of the analogue input quantities. The relay samples
24 points per cycle and calculates the RMS value in each interval and updated the LCD display in
every 0.5 second. The measurement data can be displayed on the LCD of the relay front panel or
on the local via tool software or remote PC. Navigate the menu to view the sampling value through
LCD screen.
This device can be used for one circuit breaker configuration and two circuit breakers
configurantion. If it is used for two circuit breakers configuration, some corresponding metering will
be suffixed by CBn (n is the number of the CB and it can be 1 and 2).
1. RMS Values
Please refer to section 3.15.2 about the definitions of UL1, UB1, UL2 and UB2.
Magnitude of phase current Ia, Ib, Ic (it represents the current of line, for two circuit breakers
configuration, such as one and a half breakers arrangement, it is equal to the summation of
corresponding phase currents of two circuit breakers)
Magnitude of zero-sequence current 3I0 (For one circuit breaker configuration, it is directly
measured from CT circuit, but for two circuit breakers configuration, it is calculated according to
the three-phase current of line)
Magnitude of phase currents of two circuit breakers Ia1, Ib1, Ic1, Ia2, Ib2, Ic2 (displayed only
for two circuit breakers configuration, such as one and a half breakers arrangement)
Magnitude of zero-sequence currents of two circuit breakers 3I01, 3I02 (displayed only for
two circuit breakers configuration, such as one and a half breakers arrangement)
Access path: Press key “▲” to enter main menu firstly. Select the item “VALUES“ and press key
“ENT” to enter submenu “PROT_MEASUREMENT”, and then press key “ENT”. The
corresponding metering values mentioned above are displayed on the LCD.
2. Phase Angle
Phase angle of (Ia1, Ib1, Ic1) (displayed only for two circuit breakers configuration, such as
one and a half breakers arrangement)
Phase angle of (Ia2, Ib2, Ic2) (displayed only for two circuit breakers configuration, such as
one and a half breakers arrangement)
In “PHASE_ANGLE”, the phase angles displayed about three-phase current and three-phase
voltage are based on phase A voltage.
Access path: Press key “▲” to enter main menu firstly. Select the item “VALUES” and press key
“ENT” to enter submenu “PHASE_ANGLE”, and then press key “ENT”. The corresponding phase
angles mentioned above are displayed on the LCD.
Access path: Press key “▲” to enter main menu firstly. Select the item “VALUES” and press key
“ENT” to enter submenu “TELE_MESUREMENT”, and then press key “ENT”. The corresponding
primary values mentioned above are displayed on the LCD.
5.2 Recording
5.2.1 General description
The PCS-902 series provides the following recording functions:
Event recorder
Disturbance recorder
These records are displayed on the LCD of the relay front panel or on the local or remote PC.
Navigate the menu to view the report through LCD screen.
Event recorder includes self-supervision report, status change report of binary input and operating
report. The protective device can store 1024 records of each kind for self-supervision report and
status change report of binary input, and 1024 records of operating report in non-volatile memory.
The protective device is under automatic supervision all the time. If there are any failure or
anbnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be
logged in event recorder.
When there is binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged as an event recorder.
If operator implements some operation, such as reboot protective device, modify setting, and so
on, they will be logged as an event recorder.
Use the disturbance recorder to achieve a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. An analysis
of the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.
5.2.3.2 Design
Disturbance recorder is consisted of fault report and fault waveform. Disturbance recorder is
initiated by fault detector element.
The protective device can store up to 1024 records of fault report in non-volatile memory. If a new
fault occurs when 1024 faults have been stored, the first type of fault report will be overwritten, and
then the oldest fault report will overwritten by the latest one if another new fault report is generated
again.
Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
The time resolution is 1ms using the relay internal clock synchronized via GPS if connected.
Initiating date and time is when a protective fault detection operates.
Operating time
An operating time (not including the operating time of output relays) is recorded in the report.
Faulty phase
Fault location
To get accurate result of fault location, the following settings shall be set correctly:
protective elements
For the details of designation of each protective element, please refer to section 7.4.2.
The protective device can save 64 pieces of fault waveform. If a new fault occurs when 64 fault
waveform records have been stored, the waveform of the first type of fault report will be
overwritten, and then the latest waveform record will overwrite the oldest one if another new fault
waveform is generated again. The protective device stores actual samples that are taken at a rate
of 24 samples per cycle.
GR
P
ESC
The 20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM),
others are configurable.
As to buttons of the keypad, “ENT” is “enter”, “GRP” is “group number” and “ESC” is “escape”.
This device is developed on the basis of our latest software and hardware platform, and the major
characteristics of the new platform include high reliability, great capability in anti-interference,
intellectualization and networking. See Figure 6.1-3 for hardware diagram.
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 00
z If the slots from slot No.08 to slot No.10 are not used up, the BI module can be configured
at the rest slots.
z If the slots from slot No.11 to slot No.15 are not used up, the BO module can be
configured at the rest slots.
A
*
52b
B
*
C
*
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 00
NR1102 NR1123 NR1123 NR1401 (4I,4U) NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 00
In the protection system adopting electronic current and voltage transformer (ECVT), the merging
unit will merge the sample data of ECVT, and then send it to the protection device through
multi-mode optical fibre. The DSP module 1 (NR1123) and DSP module 2 (NR1123) of protection
device receive the data from merging unit respectively through the optical-fibre interface to
complete the protection calculation and logic judgment.
The difference between the hardware platform based on ECVT and the hardware platform based
on conventional CT/VT lies in the receiving module of sample data only, and the protective device
receives the sampling data of merging unit through multi-mode optical fibre.
The +3.3V DC output provides power supply for the microchip processors, and the +5V DC output
provides power supply for all the electrical elements that need +5V DC power supply in this device.
The ±12V DC output provides power supply for A/D conversion circuits in this device, and the
+24V DC output provides power supply for the static relays of this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
A 12-pin connector is fixed on the front of the power supply module. The pin definition of the
connector is described as below.
Note!
The rated voltage of DC power supply module is self-adaptive to 220Vdc and 110Vdc, but
the power supply in other DC voltage level or power supply of AC voltage need to be
specially ordered, and check if the rated voltage of power supply module is the same as
the voltage of external control power supply before equipment being put into service.
Note!
The DC power supply module provides pin 12 and earth connector for grounding of
equipment. The pin 12 shall be connected to earth connector and the connected to the
earth copper bar of panel via dedicated grounding wire.
Note!
Efficient grounding is the most important measure for equipment to prevent EMI, so
efficient grounding must be ensured before the device is put into operation.
The MON module consists of high-performance built-in processor, FLASH, SRAM, SDRAM,
Ethernet controller and other peripherals. Its functions include management of the complete
device, human machine interface, communication and waveform recording etc.
The MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module is provided with 100BaseT
Ethernet interfaces, RS-485 communication interfaces, PPS/IRIG-B differential time
synchronization interface and RS-232 printing interface.
ETHERNET 4
COM
GPS
PRINT
Figure 6.3-3 Wiring of communication interface
The correct method of connection is shown in Figure 6.3-3. Generally, the shielded cables with two
pairs of twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to
connect the “+” and “–” terminals of difference signal; the other pair of twisted pairs are used to
connect the signal ground of the interface, i.e. connect the signal groundings of all the devices
connected with the bus to the twisted pair. The module reserves a free terminal for all the
communication ports; the free terminal has no connection with any signal of the device; it is used
to connect the external shields of the two cables when connecting multiple devices in series. The
external shield of cable shall be grounded at one of the ends.
When the module is connected to conventional CT/VT, it can perform the synchronous data
acquisition through the AC input board; when the module is connected to ECVT, it can receive the
real-time synchronous sample data from merging unit through the multi-mode optical-fibre
interface.
The module can provide 2,048 kbit/s or 64 kbit/s single-mode optical-fibre to exchange data and
signal with the opposite-side protection device.
When the module is connected to conventional CT/VT, it can perform the synchronous data
acquisition through the AC input board; when the module is connected to ECVT, it can receive the
real-time synchronous sample data from merging unit through the multi-mode optical-fibre
interface.
The following figure is the type definition for DSP module; corresponding module shall be adopted
in accordance with concrete situation.
Where:
Type D: it is used to convential CT/VT, and the device is provided with no optical-fibre channel;
Type E: it is used to convential CT/VT, and the device is provided with optical-fibre channel;
Type F: it is used to ECVT, and the device is provided with no optical-fibre channel;
Type G type module is used to ECVT; and the device is provided with optical-fibre channel;
Type K: it is used to double ECVT (multi-breaker cases), and the device is provided with
optical-fibre channel.
6.3.5 AI Module
The protection device which supports ECVT should not be equipped with this module. The slot
numbers of the module are 04 and 05. The AI module (NR1401) is applicable for the plant or
station with analog VT and CT.
There are tow types of AI module with rating 5 A or 1 A. Please declare which kind of AI module is
needed before ordering.
For one circuit breaker configuration, IA, IB, IC and 3I0 are phase current and zero-sequence
current input to AI module separately. Terminal 0401, 0403, 0405 are polarity marks. It is assumed
3I0 derived is used for calculation of zero-sequence directional element and zero-sequence
overcurrent element, but 3I0 measured is used for zero-sequence current fault detector element.
Therefore, 3I0 measured shall be connected to the equipment, otherwise all relevant
zero-sequence current protection will be disabled. Maximum linear range of the current converter
is 30In. Table 6.3-1 lists the pin number and its definition of AI module.
For two circuit breakers configuration, IA1, IB1, IC1 and IA2, IB2, IC2 are phase current input to AI
module corresponding to CB1 and CB2 respectively. Terminal 0401, 0403, 0405, 0407, 0409 and
0411 are polarity marks. It is assumed that polarity mark of CT installed on line is at line side.
Maximum linear range of the current converter is 30In. Table 6.3-1 lists the pin number and its
definition of AI module.
UA, UB, and UC are phase voltage input to AI module. UB1, UL2, UB2 are the bus or line voltage
used for synchrocheck, it could be any phase-to-ground voltage or phase-to-phase voltage. If the
auto-reclosing is disabled or enabled but without any check, the synchronism check voltage
should be disconnected.
The sending and receiving functions of GOOSE should be completed through configuring the
sending module and receiving module.
A 22-pin connector is fixed on the front of the binary input module, which can provide 18 binary
inputs. Except for terminal 0802~0805, other binary inputs are configurable. The pin definition of
the connector of binary input module located in slot 08 is described as below. [BI_n](n=1,2,…,14
can be configured as a specified binary input by PCS-PC software.
Opto+ 01
BI_Pulse_GPS 02
BI_Print 03
BI_BlkComm 04
BI_RstTarg 05
BI_1 06
BI_2 07
08
BI_3 09
BI_4 10
BI_5 11
BI_6 12
BI_7 13
BI_8 14
15
BI_9 16
BI_10 17
BI_11 18
BI_12 19
BI_13 20
BI_14 21
Opto- 22
1. Terminal 02
It is used to receive clock synchronism signal from GPS or other equipment used clock
synchronism, the binary input [BI_Pulse_GPS] will change from “0” to “1” once per second or per
minute depended on the setting [GPS_Pulse]. When setting [GPS_Pulse] is set to “1”, the
equipment receives PPM (pulse per minute), otherwise, receives PPS (pulse per second). Clock
synchronism via RS-485 bus is recommended. Only one of them can be selected.
2. Terminal 03
It is used to manually to trigger printing latest report when the equipment is configured as manual
printing mode by logic setting [En_Auto_Print]=0. The printer button is located on the panel usually.
If the equipment is configured as automatic printing mode ([En_Auto_Print]=1), report will be
printed automatically as soon as it is formed.
3. Terminal 04
It is used to block monitoring direction communication when the protective device is maintained. A
link located on the panel is used for that. When the equipment is in maintenance or commissioning
status, this link should be closed. All of the reports will not be sent via communication port then,
but local displaying and printing are still working. This link should be open during normal operation
condition.
4. Terminal 05
It is used to manually reset latching signal relay and LCD displaying. The reset is done by pressing
a button on the panel or by remote command via communication channel.
Note!
The rated voltage of binary input is optional: 24V, 46V, 110V , 220V, 125V or 250V, which
must be definitely declared in the technical scheme and the contract. It is necessary to
check whether the rated voltage of BI module meets the demand of the engineering before
putting the relay into operation.
The application of the binary input [BI_BlkComm] for digital substation communication adopting
IEC61850 protocol is given as follows.
1) The protection device should send the state of this binary input to client.
2) When this binary input is energized, the bit “Test” of quality (Q) in the message sent should
be set as “1”.
3) When this binary input is energized, the client cannot remote control the isolator link and
circuit breaker, modify settings and switch setting group.
4) According to the value of the bit “Test” of quality (Q) in the message sent, the client
discriminate whether this message is maintenance message, and then deal with it correspondingly.
If the message is the maintenance message, the content of the message will be not displayed
real-time message window, not issue audio alarm, but should refresh the picture so as to ensure
that the state of the picture is in step with the actual state. The maintenance message should be
stored, and can be inquired by independent window.
1) When this binary input is energized, the bit “Test” in the GOOSE message sent by the
protection device should be set as “1”.
2) For the receiving end of GOOSE message, it will compare the value of the bit “Test” in the
GOOSE message received by it with the state of its own binary input (i..e [BI_BlkComm]),
the message will be thought as invalid unless they are conformable.
1) When this binary input of merging unit is energized, the bit “Test” of quality (Q) of sampling
data in the SV message sent should be set as “1”.
2) For the receiving end of SV message, if the value of bit “Test” of quality (Q) of sampling data
in the SV message received by it is “1”, the relevant protection functions will be disabled, but
under maintenance state, the protection device should calculate and display the magnitude
of sampling data.
3) For duplicated protection function configurations, all merging units of control module
configured to receive sampling should be also duplicated. Both dual protection devices and
dual merging units should be fully independent each other, and one of them is in
maintenance state will not affect the normal operation of the other.
NR1521A, NR1521B and NR1521C modules are three standard binary output modules. NR1521A
can provide 11 tripping output contacts, and each output contact will be controlled by the fault
detector. NR1521B can provide 9 tripping output contacts and two signal output contacts, and
each output contact can be controlled separately by positive power supply of fault detector.
NR1521C can provide 11 tripping output contacts without being controlled by positive power
supply of fault detector. The contacts provided by NR1521A, NR1521B and NR1521C are all
normally open (NO) contacts.
Output contact can be configured as a specified tripping output contact and a signal output contact
respectively by PCS-PC software according to user requirement.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
PCS-PC software, assorted with UAPC platform device, is developed in order to meet customer’s
demand on functions of device such as device configuration and programmable design. It selects
substation as the core of data management and the device as fundamental unit, supporting one
substation joint to govern many ones of the devices. The software provides on-line and off-line
functions: on-line mode: Ethernet connected with the device to support IEC 60870-5-103 protocol
and downloading of binary files through Ethernet net; off-line mode: off-line setting configuration.
In addition, it also supports programmable logic to meet customer’s corresponding demand. For
any detail, please refer to Instruction Manual of PCS-PC Auxiliary Software.
Overall functions:
Warning: The system configuration shall only be operated by professionals who are
familiar with protection object and protection device. Or else, any incorrect configuration
may cause serious damage to the device during its operation. In general, these
configuration works have been completed before equipment leaving factory.
Warning: If the system configuration is really need, user must select “Run the whole
script” item in the right click menu before other configuration operations.
3. Use the column “ ” to choose whether hold LED or not. In case of the check box is
selected, resetting must be performed by the resetting button once it is lit. In case of the check
box is blank, the signals will reset automatically once the input signal returns.
4. If users hope the “Y_LED_5” is lit when the device is ready for AR of CB1, configure it as the
following picture.
6. The signal in the column of “Signal” can be deleted by right-click, and then left-click to execute
delete command.
7. If the original “Led Label” that starts with a “Y” means it is a yellow LED and starts with a “R”
means it is a red LED.
4. The signal in the column of “Int. Signal” can be deleted by right-click, and then left-click to
execute delete command.
2. Users can draw the elements from the column “ ” at the right to
point to a or several binary output contact. The optional signals include: Trip Elements, Alarm,
Binary Change and Other Type (Reserved).
4. The signal added in the column of “Int. Signal” can be deleted by right-click, and then left-click
to execute delete command.
Users can configure the equipment parameters, system settings and etc.
Users can select to show or hide some setting, and modify typical setting values
For the specific project, some signals relevant to synchrocheck module, auto-reclosing module
and breaker failure protection module maybe with the suffix of “_CB1” and “_CB2” what represent
the signals correspond to synchrocheck module, auto-reclosing module and breaker failure
protection module for circuit breaker 1 and circuit breaker 2 respectively.
protection is met
Phase current criterion of phase-B for breaker failure
42. BFP_OC_Ib
protection is met
Phase current criterion of phase-C for breaker failure
43. BFP_OC_Ic
protection is met
Zero-sequence current criterion for breaker failure
44. BFP_OC_I0
protection is met
Negative-sequence current criterion for breaker failure
45. BFP_OC_I2
protection is met
Synchronism check
46. UL1_Sel Voltage of line 1 is selected
47. UL2_Sel Voltage of line 2 is selected
48. UB1_Sel Voltage of bus 1 is selected
49. UB2_Sel Voltage of bus 2 is selected
50. Invalid_Sel Voltage selection is invalid
The binary output for indicating frequency difference
51. fDiffOk
condition for synchronism check for AR is met
The binary output for indicating voltage difference condition
52. UDiffOk
for synchronism check for AR is met
The binary output for indicating phase difference condition
53. phiDiffOk
for synchronism check for AR is met
54. DLDBOk Dead line and dead bus condition is met
55. DLLBOk Dead line and live bus condition is met
56. LLDBOk Live line and dead bus condition is met
57. ULLive The line voltage is greater than the voltage setting [V_Live]
58. ULDead The line voltage is smaller than the voltage setting [V_Live]
59. UBLive The bus voltage is greater than the voltage setting [V_Live]
60. UBDead The bus voltage is smaller than the voltage setting [V_Live]
The binary output for indicating dead check condition for
61. DeadChkOk
AR is met
The binary output for indicating synchronism check
62. SynChkOk
condition for AR is met
The binary output for indicating synchrocheck condition for
63. SYNOk
AR is met
64. Alm_VTS_UB Synchronous voltage circuit of bus voltage is abnormal
65. Alm_VTS_UL Synchronous voltage circuit of line voltage is abnormal
66. ManCls_Out Output of manual closing signal
The binary output for indicating synchrocheck condition for
67. SYNOk_M
manual closing is met
The binary output for indicating synchronism check
68. SynChkOk_M
condition for manual closing is met
The binary output for indicating dead check condition for
69. DeadChkOk_M
manual closing is met
agency to maintain it
AC current and voltage samplings of protection DSP
module are detected to be wrong or inconsistent with that of
116. Alm_Abnor_Smpl_MON
fault detector DSP module. Please inform manufacture or
agency to maintain it
General fault detector element operates for longer than
117. Alm_PersistFD
10s. Please check CT secondary circuit.
Zero-sequence overcurrent element operates for longer
118. Alm_PersistI0
than 10s. Please check CT secondary circuit.
119. Alm_VTS Line VT circuit failure. Please check VT secondary circuit.
CT circuit of corresponding circuit breaker fails. Please
120. Alm_CTS
check CT secondary circuit.
The auxiliary normally closed contact (52b) of
121. Alm_52b corresponding circuit breaker is abnormal. Please check
the auxiliary contact of CB
Any of the binary inputs of single-phase or three-phase
tripping contact from external protection is energized and
122. Alm_BI_ExTrP
the duration is longer than 10s. Please check all the
relevant binary inputs
Binary input of auxiliary normally closed contact
[BI_DS_Line] is energized then current can still be detected
123. Alm_BI_DS_Line
and the duration is longer than 10s. Please check the
binary input [BI_DS_Line].
Stage 2 of distance protection operates with 150ms delay
124. Op_Prot_PDF when fault occurs on healthy phase under pole discrepancy
situation
125. Op_PhSelFail Three-pole tripping for failure in fault phase selection
126. Op_1PTrpFail Three-pole tripping for failure in single-pole tripping
127. Op_Persist1P Three-pole tripping for single-phase operation
128. La Current amplitude of phase A is greater than 0.06In
129. Lb Current amplitude of phase B is greater than 0.06In
130. Lc Current amplitude of phase C is greater than 0.06In
Current amplitude of phase A flowed through CB1 is
131. La_CT1 greater than 0.06In (only equipped for two circuit breakers
configuration)
Current amplitude of phase B flowed through CB1 is
132. Lb_CT1 greater than 0.06In (only equipped for two circuit breakers
configuration)
Current amplitude of phase C flowed through CB1 is
133. Lc_CT1 greater than 0.06In (only equipped for two circuit breakers
configuration)
Current amplitude of phase A flowed through CB2 is
134. La_CT2 greater than 0.06In (only equipped for two circuit breakers
configuration)
In order to convenient for users to configure, the default configurations of LED, binary input and
binary output are provided. The definitions are as below.
Opto+ 01
BI_Print 02
BI_Pulse_GPS 03
BI_RstTarg 04
BI_BlkComm 05
BI_52b_Pha 06
BI_52b_Phb 07
Reserved 08
BI_52b_Phc 09
BI_Opt1_AR 10
BI_Opt2_AR 11
BI_Lockout 12
BI_Healthy_CB 13
Bl_ExTrp_PilotP 14
Reserved 15
BI_RMT_DTT 16
BI_Recv1 17
BI_RecvB 18
BI_RecvC 19
BI_Recv2 20
Reserved 21
COM- 22
}
}
}
}
}
}
}
}
}
}
}
}
}
}
Figure 7.5-1 Pin definition of binary output module located in slot No. 11
}
}
}
}
}
}
}
}
}
}
}
Figure 7.5-2 Pin definition of binary output module located in slot No. 12
}
}
}
}
}
}
}
}
}
}
}
Figure 7.5-3 Pin definition of binary output module located in slot No. 13
The following table is the explanation of the ouput signal mentioned above.
Chapter 8 Settings
The equipment has 10 setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, equipment parameters are common for
all protection setting groups.
Note!
All current settings in this chapter are secondary current converted from primary current by
CT ratio. Zero-sequence current or voltage setting is configured according to 3I0 or 3U0
and negative sequence current setting according to I2 or U2.
Setting Description
They are used for Ethernet communication based on the 103 protocol. When the IEC 61850
protocol is applied, the IP address of Ethernet A will be GOOSE source MAC address.
4. Comm_Addr
Communication address between the protective device with the SCADA or RTU via RS-485
5. COM1_Baud
6. COM2_Baud
7. COM1_Protocol
2: Modbus Protocol
8. COM2_Protocol
2: Modbus Protocol
9. En_BlkComm
It is set as “1” when the device is in maintainence. During such period, the fault report due to test
will not be sent upstream through communication ports, while local display and printing will not be
affected.
It is set as “0” when the device is in service. The relation between this setting and binary input
[BI_BlkComm] is “OR”, i.e. as long as one of them is set as “1”, such information as fault report
and waveform will not be sent upstream.
10. Printer_Baud
11. En_Auto_Print
If automatic print is required for fault report after protection operating, it is set as “1”. Otherwise, it
should be set to “0”.
12. En_HiSpeed_Print
It is set as “0” for common printing with high definition, while it is set as “1” for high-speed printing.
13. Opt_TimeSync
1: IRIG-B differential
3: SNTP(PTP)
4: IEEE1588
5: SNTP(BC)
6: DCF77
14. Un_BinaryInput_B08
DC voltage of power supply of the first binary input module (located on slot No.8)
0: 24V
1: 48V
2: 110V
3: 220V
15. Un_BinaryInput_B09
DC voltage of power supply of the second binary input module (located on slot No.9)
1. Active_Grp
It is current active setting group. 10 setting groups are provided for selecting, group number from 0
to 9. Equipment parameter is shared for 10 setting groups.
2. Equip_ID
It is intended to set Chinese character field codes (12 bits) or ASCII codes (last 6 bits), which can
be recognized by the device automatically. Such settings is used for printing messages.
3. I1n
4. I2n
5. U1n
6. U2n
Overview
Line parameter
1. Line_ID number of the line 0-65535
2. X1L positive sequence reactance of the line 0.00~5Unn/In (Ω)
3. R1L positive sequence resistance of the line 0.00~5Unn/In (Ω)
4. X0L zero-sequence reactance of the line 0.00~5Unn/In (Ω)
5. R0L zero-sequence resistance of the line 0.00~5Unn/In (Ω)
phase angle of line positive sequence
6. phi1_Reach 30~89 (deg)
impedance
phase angle of line zero-sequence
7. phi0_Reach 30~89 (deg)
impedance
8. K0 zero-sequence compensation coefficient 0~2
9. LineLength total length of the line 0~655.35 (km)
primary voltage of VT deriving from line
10. En_LineVT 0-1
voltage
Settings of tripping logic
current setting of DPFC current fault detector
11. I_DPFC_OC_FD 0.02~10 A×IN
element
current setting of zero-sequence current fault
12. I_ROC_FD 0.02~10 A×IN
detector element
enable auto-reclosing being blocked when
13. En_PhSF_Blk_AR 0-1
selection of faulty phase fails
enable auto-reclosing being blocked when
14. En_MPF_Blk_AR 0-1
multi-phase fault happens
enable auto-reclosing being blocked when
15. En_3PF_Blk_AR 0-1
three-phase fault happens
enable three-phase tripping mode for circuit
16. En_3Ptrip 0-1
breaker
Settings of main and distance protection functions
17. Z_DPFC impedance setting of DPFC distance element 0.00~2Unn/In (Ω)
18. En_Z_DPFC enable DPFC distance protection 0-1
impedance setting of pilot distance protection
19. Z_POTT 0.00~2Unn/In (Ω)
for forward direction element
impedance setting of pilot distance protection
20. Z_POTT_Quad for forward direction element (with 0.00~2Unn/In (Ω)
quadrilateral characteristic)
current setting of directional earth-fault
21. I_ROC_PilotP 0.02~40 A×IN
protection
22. t_Dly_CurRev time delay for fault current reversal 0~1.00s
time of pulse expanding after fault current
23. t_Ext_CurRev 0~1.00s
reversal
24. t_DEF time delay of DEF 0~1.00s
0: Definite
1: Inverse
2: Standard
Inverse
Operating characteristic selection for stage 1
125. Opt_Characteristic_OV1 3: Very Inverse
of overvoltage protection
4: Extremely
Inverse
5: Long Time
Inverse
voltage setting of stage 2 of over voltage
126. V_OV2 (Un-2Unn)
protection
127. t_OV2 time delay of stage 2 of over voltage protection 0~10.00 (s)
0: Definite
1: Inverse
2: Standard
Inverse
Operating characteristic selection for stage 2
128. Opt_Characteristic_OV2 3: Very Inverse
of overvoltage protection
4: Extremely
Inverse
5: Long Time
Inverse
Logic setting of enabling stage 1 of over
129. En_OV1 0-1
voltage protection
Logic setting of enabling stage 2 of over
130. En_OV2 0-1
voltage protection
enable 1-out-of-3 mode or 3-out-of-3 mode for
131. Opt_1P/3P_OV 0-1
over voltage protection
Logic setting of enabling phase-to-phase over
132. En_Vpp_OV 0-1
voltage protection
Stage 1 of over voltage protection operating to
initiate transfer trip
133. En_OV1_Init_TT 0-1
1: enable
0: disable
Stage 2 of over voltage protection operating to
initiate transfer trip
134. En_OV2_Init_TT 0-1
1: enable
0: disable
The binary input of 52b will be used to initiate
transfer trip
135. En_52b_Ctrl_TT 0-1
1: enable
0: disable
voltage setting of stage 1 of under-voltage load
136. V_UV1 (0-Unn)
shedding protection
time delay of stage 1 of under-voltage load
137. t_UV1 0~10.00 (s)
shedding protection
0: Definite
1: Inverse
2: Standard
Inverse
Operating characteristic selection for stage 1
138. Opt_Characteristic_UV1 3: Very Inverse
of undervoltage protection
4: Extremely
Inverse
5: Long Time
Inverse
voltage setting of stage 2 of under-voltage load
139. V_UV2 (0-Unn)
shedding protection
time delay of stage 2 of under-voltage load
140. t_UV2 0~10.00 (s)
shedding protection
0: Definite
1: Inverse
2: Standard
Inverse
Operating characteristic selection for stage 2
141. Opt_Characteristic_UV2 3: Very Inverse
of undervoltage protection
4: Extremely
Inverse
5: Long Time
Inverse
Logic setting of enabling stage 1 of under
142. En_UV1 0-1
voltage protection
Logic setting of enabling stage 2 of under
143. En_UV2 0-1
voltage protection
enable 1-out-of-3 mode or 3-out-of-3 mode for
144. Opt_1P/3P_UV 0-1
under voltage protection
Logic setting of enabling phase-to-phase under
145. En_Vpp_UV 0-1
voltage protection
Stage 1 of under voltage protection operating
to alarm
146. En_Alm_UV1 0-1
1: enable
0: disable
Settings of BFP for CB1
current setting of phase current criterion of
147. I_OC_BFP (0.02~40 )×In
BFP
current setting of zero-sequence current
148. I_ROC_BFP (0.02~40 )×In
criterion of BFP
current setting of negative-sequence current
149. I_NegOC_BFP (0.02~40 )×In
criterion of BFP
150. t_BFP1 time delay of stage 1 of BFP 0~10.00 (s)
151. t_BFP2 time delay of stage 2 of BFP 0~10.00 (s)
170. t_DeadChk time delay of voltage and dead check condition 0.01~25.00 (s)
Setting Description
1. Line_ID
Number of the line. The actual identification number of the transmission line in site, only used for
printing report.
Positive sequence and zero-sequence reactance and resistance of the line. Parameter of the
transmission line, used for calculation of fault location.
Setting step: 1°
Phase angle of positive and zero-sequence impedance of the line. Set as they should be.
4. K0
Setting principle: K0 = (Z0L–Z1L)/3Z1L, where Z0L and Z1L are zero and positive sequence
impedance of the line respectively. Actual measurement value is suggested adopted, but
calculated value with 0.05 subtracted from can also be used if there is not actual measurement
value.
5. LineLength
Total length of the line. The actual total length of the line km, used for calculation of fault location.
6. En_LineVT
If three-phase voltage used for protection measurement comes from line side (for example, 3/2
breaker), it should be set as “1”. If three-phase voltage comes from busbar side, it should be set as
“0”.
1: Three phase voltage is from line voltage, synchronism voltage is single-phase voltage from bus
voltage
0: Three phase voltage is from bus voltage, synchronism voltage is single-phase voltage from line
voltage
Note!
The setting must be set carefully. The no-voltage check and the synchronous check will
determine the locations of line voltage and busbar voltage on the basis of the setting. If the
setting is mistaken, the mistaken judgment may be made.
7. I_DPFC_OC_FD
Setting principle: This value should be greater than maximum variation of load current and
typically 0.2 In. For line with wide variation of load current like those for electric railway, heavy
rolling mill or aluminum-smelting, the setting should be increased properly so that frequent starting
of the equipment could be avoided.
8. I_ROC_FD
Setting principle: It shall be greater than maximum zero-sequence unbalance current. Setting it
based on same primary current on both ends.
9. En_PhSF_Blk_AR
If the settings is set as “1”, auto-reclosing will be blocked when selection of faulty phase fails.
10. En_MPF_Blk_AR
If the setting is set as “1”, auto-reclosing will be blocked when multi-phase fault happens.
11. En_3PF_Blk_AR
If the setting is set as “1”, auto-reclosing will be blocked when three-phase fault happens.
12. En_3Ptrip
If it is set as “1”, three-pole tripping will be implemented for any fault but auto-reclosing is not
blocked.
13. Z_DPFC
Setting principle: it shall be 80~85% impedance of whole line. For double-circuit lines, 70% of the
line impedance is recommended. However, for short line, it is recommended that DPFC distance
14. En_Z_DPFC
1: enable
0: disable
For short transmission line, if the secondary value of line impedance is less than 1/IN, DPFC
distance protection should be disabled.
15. Z_POTT
Setting principle: It shall be greater than 1.3 times impendence of whole line.
16. I_ROC_PilotP
Setting principle: It should ensure that directional earth-fault protection is sensitive enough when
an earth fault happens in the remote end of line. Usually, it should be set on the basis of that
primary fault current is not smaller than 240A.
17. t_Dly_CurRev
Time delay for dodging out of fault current reversal; It is used to avoid protective device undesired
trip when fault current reversal occurs.
18. t_Ext_CurRev
Time of pulse expanding after fault current reversal;It is used to expand the operation signal of
pilot protection after fault current reversal occurs.
19. t_DEF
20. En_POTT_PilotP
1: enable
0: disable
When POTT is used, besides setting logic setting [En_POTT_PilotP] as “1”, any of logic settings
[En_Z_POTT] and [En_ROC_POTT] must be set as “1”, otherwise, POTT is invalid.
21. En_PUTT_PilotP
1: enable
0: disable
Note!
For POTT, permissive signal is sent when distance element of POTT operates. If receiving
permissive signal from opposite end of line and local distance element of POTT operating,
tripping command is sent. For PUTT, permissive signal is sent when zone 1 distance
element operates. If receiving permissive signal from opposite end of line and local zone 2
distance element operating, trip command is sent.
Note!
If logic settings [En_POTT_PilotP] and [En_PUTT_PilotP] are both set as “0”, pilot
distance element is disabled. If logic settings [En_POTT_PilotP] and [En_PUTT_PilotP]
are both set as ‘”1”, an alarm [Alm_Setting] will be issued and protective device will be
blocked.
22. En_Z_POTT
1: enable
0: disable
23. En_ROC_POTT
1: enable
0: disable
24. En_DEF_PilotP
1: enable
0: disable
25. En_DEF_Blk_AR
The function of auto-reclosing blocked when directional earth fault protection operating; at the
same time, output three-phase tripping and lockout contacts BO_Trp3P_Lockout_1 (F09~F10)
and BO_Trp3P_Lockout_2 (F11~F12)
1: enable;
0: disable;
26. En_FD_Ctrl_TT
Whether transfer trip signal will be controlled by local fault detector element. If the setting is set as
“1”, received transfer tripping signal can not operate to trip local breaker unless local fault detector
element picks up.
27. En_WE_POTT
“1”: enable
“0”: disable
Note!
For heavy power source, logic setting [En_WE_POTT] is set as “0”, and for weak power
source or load, logic setting [En_WE_POTT] is set as “1”. It can ensure internal fault is
cleared quickly.
Note!
If logic setting [En_POTT_PilotP] is set as “0”, the logic setting [En_WE_POTT] is invalid.
28. Z_PG1
Setting principle: Setting of this zone should be 0.8~0.85 times the impedance of the line and
should be decreased properly for line with mutual inductance. The recommended value is 0.7
times the impedance of the line. The setting should avoid zone 1 of distance element maloperation
when a fault occurs in the remote bus of line.
29. R1_Quad、R2_Quad、R3_Quad
Setting principle: The proposed limitation of Z/R ratio is 1/4, in another word, it is recommended
that Z/R ratio is not smaller than 1/4.
Besides R1_Quad, R2_Quad and R3_Quad should be in the range of 0.05~200Ω/IN and ward load
impedance, these settings are recommended to satisfy the following condition:
R1_Quad≤4×Z_PG1, R2_Quad≤4×Z_PG2, R3_Quad≤4×Z_PG3. But this limitation is not
imperative. So during the calculation of the settings R1_Quad, R2_Quad and R3_Quad, the
consideration includes: the setting range of 0.05~200Ω/IN, the load impedance and the proposed
limitation of Z/R ratio.
30. Z_PP1
Setting principle: Setting of this zone should be 0.8~0.85 times the impedance of the line. The
setting should avoid zone 1 of distance element maloperation when a fault occurs in the remote
bus of line.
31. Z_PG2, Z_PG3, Z_PP2, Z_PP3, t_PG2, t_PG3, t_PP2 and t_PP3
Setting principle: Setting of the impedance and time delay of these zones should meet
requirements between various zones and operation should be ensured even for fault at end of the
line.
Note!
For impedance setting, even if some zones of distance element are disabled, these
settings must meet the following relation:
[Z_PP3]≥[Z_PP2]≥[Z_PP1];
[Z_PG3]≥[Z_PG2]≥[Z_PG1];
Impedance setting of zone 3 of distance element should be sensitive to fault at end of the
line.
The zone 1(2, 3) of phase-to-ground distance element enabled and zone 1(2, 3) of
phase-to-phase distance relay enabled, if these setting are set to “1”, in the same time, virtual
binary input [VEBI_DistP] should be set as “1”. If none of them is met, the distance protection shall
be disabled.
33. En_ZPG1_Quad、En_ZPG2_Quad、En_ZPG3_Quad
1: enable
0: disable
34. En_BI_Z1_Vld
The validity of the binary input [BI_En_Z1] for enabling/disabling zone 1 of distance protection
35. En_ZPG2_Blk_AR
1: enable;
0: disable;
36. En_ZPP2_Blk_AR
1: enable;
0: disable;
If the setting is set as “1”, zone2, 3 of distance element for auto-reclosing SOTF is enabled. If the
power swing does not occur after reclosing, the corresponding zone of distance protection which is
not controlled by power swing block will trip after a shorter time delay than [t_PG2] or [t_PP2] and
[t_PG3] or [t_PP3].
38. Z_Rev
39. t_Rev
Setting principle: it should meet requirement between zone 3 distance element and busbar
protection.
40. En_ZPG_Rev
1: enable;
0: disable;
41. En_ZPP_Rev
1: enable
0: disable
42. R_Blinder
Setting principle: It should be less than the minimum impedance measured during heavy load
conditions and it should meet the requirement of sensitivity, usually take 0.7 as sensitive
coefficient.
43. En_Blinder
1: enable
0: disable
44. phi_Shift_ZPG
Setting step: 1°
Phase shift of zone 1 and 2 phase-to-ground distance element. Recommended value: 30°for
length of the line < 10 km, 15°for length ≥10 km and 0°for length ≥40 km.
45. phi_Shift_ZPP
Setting step: 1°
Phase shift of zone 1 and 2 phase-to-phase distance element. Recommended value: 30°for length
of the line < 2 km, 15°for length ≥2 km and 0°for length ≥10 km.
46. I_OC_PSBR
Setting principle: This current setting should be greater than maximum load current of the line. The
sensitivity coefficient take 1.1.
47. En_PSBR_PilotP
The function of power swing blocking for directional distance element of pilot protection;
0: disable; directional distance element of pilot protection is not controlled by PSBR element, and
power swing blocking for zone 1,2 of distance element is released all along.
48. En_PSBR_Zx
The function of power swing blocking for zone x of distance element, x can be 1, 2 or 3;
0: disable; zone x of distance element is not controlled by PSBR element, and power swing
blocking for zone x of distance element is released all along.
49. I_ROC1, t_ROC1, I_ROC2, t_ROC2, I_ROC3, t_ROC3, I_ROC4 and t_ROC4
Note!
All zero-sequence current settings should be greater than that of zero-sequence current
fault detector element. These settings must meet the following relation:
[I_ROC1]≥[I_ROC2]≥[I_ROC3]≥[I_ROC4];
If these settings are set as “1”, stage 1, 2, 3 and 4 of directional zero-sequence overcurrent
protection will be enabled.
1: enable;
0: disable;
If the setting is set as “1”, the direction blocking to corresponding stage of directional
zero-sequence overcurrent element is enabled.
53. I_InvROC
It is set according to the fault condition via maximum fault resistance (i.e. maximum fault
resistance takes 100Ω for 220kV transmission line and 300Ω for 500kV transmission line), and it
shall be greater than the maximum unbalanced current during the normal operation condition,
usually not greater than 300A.
54. t_InvROC
It is the time constant of normal IDMT equation and the following criterion shall be met:
⎧t 0ZDinv ≥ TS + Δt
⎨
⎩t 0ZDinv ≥ t 0ZD2XL + Δt
Where:
t 0ZD2XL : The time delay of zone 2 of directional zero-sequence overcurrent protection in the
adjacent line
55. Opt_Characteristic_ROC
56. En_Dir_InvROC
Logic setting for enabling inverse-time zero-sequece overcurrent protection controlled by direction
element
1: enable;
0: disable;
57. En_FixDly_InvROC
Logic setting for enabling inverse-time zero-sequence overcurrent protection operate with an
additional time delay (100ms)
1: enable;
0: disable;
58. I_ROC_SOTF
Setting principle: This setting should ensure sufficient sensitivity to ground fault at end of the line.
59. I_OC_VTS
60. I_ROC_VTS
61. t_OC/ROC_VTS
For stage 1 and stage 2 of overvoltage protection, definite-time characteristic and five kinds of
inverse-time characteristics can be choose from by setting the logic setting
[Opt_Characteristic_OVn] (n=1 or 2). The parameters of each characteristics are listed in the
following table.
[Opt_Characteristic_OV1],
Inverse Delay Curve Tp τ
[Opt_Characteristic_OV2]
Definite time delay 0 0 DT
Inverse 1 1 InvT
Standard Inverse 0.02 0.14 IEC-NI
Very Inverse 1 13.5 IEC-VI
Extremely Inverse 2 80 IEC-EI
Long Time Inverse 1 120 IEC-LTI
63. En_OV1
1: enable
0: disable
64. En_OV2
1: enable
0: disable
65. Opt_1P/3P_OV
66. En_VPP_OV
1: enable
0: disable
67. En_OV1_Init_TT
1: enable
0: disable
68. En_OV2_Init_TT
1: enable
0: disable
69. En_52b_Ctrl_TT
Overvoltage protection operates to initiate transfer trip is controlled by normally closed auxiliary
contact of circuit breaker.
1: enable
0: disable
For stage 1 and stage 2 of undervoltage protection, definite-time characteristic and five kinds of
inverse-time characteristics can be choose from by setting the logic setting
[Opt_Characteristic_UVn] (n=1 or 2). The parameters of each characteristics are listed in the
following table.
[Opt_Characteristic_UV1],
Inverse Delay Curve Tp τ
[Opt_Characteristic_UV2]
Definite time delay 0 0 DT
Inverse 1 1 InvT
Standard Inverse 0.02 0.14 IEC-NI
Very Inverse 1 13.5 IEC-VI
Extremely Inverse 2 80 IEC-EI
Long Time Inverse 1 120 IEC-LTI
71. En_UV1
1: enable
0: disable
72. En_UV2
1: enable
0: disable
73. Opt_1P/3P_UV
74. En_VPP_UV
1: enable
0: disable
75. En_Alm_UV1
1: enable
0: disable
Voltage selecting mode of line 1, bus 1, bus 2, line 2. 0~5 corresponds to UA, UB, UC, UAB, UBC
and UCA respectively.
77. ConfigMode
78. K_USyn
79. phi_Diff_SynChk
80. phi_Fix_Diff
The fixed phase difference between two synchronous voltages: Normally it was not used. It was
only used when synchronous voltage adopts the voltage from the other side of transformer.
81. f_Diff_SynChk
82. V_Diff_SynChk
83. V_Dead
Voltage threshold of dead check condition: The setting must exceed the coupling voltage
incurred by the coupling of adjacent lines, normally it was set as 30%Un.
84. V_Live
Voltage threshold of live check condition: It should be set according to the actual situation,
normally it was set as 80%Un.
85. phi_Diff_SynChk_M
86. f_Diff_SynChk_M
87. Df/dt_SynChk
88. V_Diff_SynChk_M
89. t_close
90. t_PW_M
91. t_Wait_SynChk_M
Maximum wait time for synchronism check. If synchronism check condition can not be met during
this time, the device will directly output synchronism check fails.
92. t_1Ph-Shot1_AR
93. t_3Ph-Shot1_AR
The time delay of 3-pole AR, actually it is the time delay of 3-pole AR with dead check.
should be taken into consideration. This setting for power plant outlets or intensive network is
generally set as 10s.
94. t_Wait_CBHealthy
When AR has been ready to operate, begin to time after the input [Healthy_CB] drops off. The
input [Healthy_CB] is not still energized after the time delay [t_Wait_CBHealthy], AR will be
blocked.
95. t_Wait_SynChk_AR
The setting is the maximum allowable time used for synchronism check. In case the synchronism
check is unsuccessful after exceeding this setting, the auto-reclosing will be blocked.
96. t_Reclaim_AR
97. t_Broaden_BlkAR
Most circuit breakers can perform one time process: open-close-open action. Before reclosing, the
circuit breaker must have enough energy. The input [Healthy_CB] is used to indicate whether
circuit breakers can provide enough reclose energy. When it’s time to reclosing, and after the time
delay [t_Broaden_BlkAR], the input [Healthy_CB] is still not energized, AR will be blocked. When
this function is not needed, this input will not be configured, in which case, its default logic is that it
is always valid.
98. t_ExtendDly_AR
When the channel used for main protection is abnormal, and the logic setting
[En_ExtendDly_AR]=1, the time delay of AR will add an extra time delay [t_ExtendDly_AR] on the
basis of original time delay during fault, so as to ensure insulation recovery at fault point for
transient fault when AR operates. This setting shall consider the maximum inconsistent operating
time between the protection devices on both ends.
99. t_WaitMaster
When master AR is initiated, the protection device will output signal to block slave AR. If master
AR is succeeded to reclosing, the blocking signal will drop off and slave AR will reclosing
immediately. If master AR is failure to reclosing, the blocking signal will be kept until AR drops off.
Slave AR always receives the blocking signal for longer than the time delay [t_WaitMaster], AR will
be blocked.
100. t_PersistTrp
In case the tripping signal persist longer than this setting, the auto-reclosing will be blocked.
101. t_Unsuc_AR
The setting is the time delay from reclosing command sent to unsuccessful reclosing, which shall
be greater than the reclosing operation time of circuit breaker.
102. t_PW_AR
The setting must be greater than the reclosing time of circuit breaker.
103. En_SynChk_AR
1: enable
0: disable
Dead check mode for AR. When more than one of these three parameters are enabled, the logic
relation among these three parameters is “OR”.
105. En_NoChk_AR
AR without dead check and synchronism check is enabled or not. Reclosing command will output
directly.
106. En_SynChk_M
1: enable
0: disable
Dead check mode for manual closing. When more than one of these three parameters are
enabled, the logic relation among these three parameters is “OR”.
108. En_NoChk_M
Manual closing without dead check and synchronism check is enabled or not. Reclosing command
will output directly.
109. En_AR
It is used to enable or disable AR, which should coordinate with selection setting of AR mode and
control switch of AR to perform the function.
110. ExtCtrl_AROn
111. Opt_Priority_AR
For this case that a line is corresponding to dual circuit breakers, for instance, angle scheme or 3/2
breakers, it is necessary to configure different priority for dual circuit breakers.
112. En_SetOpt_AR
AR mode: 1-pole AR, 3-pole AR and 1/3-pole AR, which are controlled by internal logic setting. It
can also be controlled by external input.
[En_SetOpt_AR]=0, it will select AR mode by external input, refer to the table below
Each VEBI setting is one of the conditions that decide whether the relevant protection is in service,
when this relay is energized. Through SAS or RTU, the VEBI settings can be set as “1” or “0”;
and it means that the relevant protection can be in service or out of service through remote
command. It provides convenience for operation management.
These virtual binary inputs provide a convenient way for the operator to put the function in service
or out of service remotely away from an unattended substation.
Except for [VEBI_Lockout], logic relation between these virtual enable binary inputs mentioned in
the table and corresponding logic setting is AND. If it is set as “1”, auto-reclosing will be locked out.
It should be set as “0” generally.
This chapter describes human machine interface (HMI), and give operator a instruction about how
to display or print event report, setting and so on through HMI menu tree and display metering
value, including mean current, voltage and frequency etc. through LCD. In the same time, how to
change active setting group or a settable parameter value through keypad is also described in
details.
9.1 Overview
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate a LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.
GR
P
ESC
The items can be flexibly configured depending on the situations like sampling method of
protection device (conventional CT/VT and ECVT), the mode of binary output (conventional binary
output and GOOSE binary output), and whether it needs independent binary output for pole
discrepancy protection. The configurations for PCS-900 series protective device of power network
based on microcomputer are classified into standard and optional modules.
1. “ESC”:
2. “ENT”:
3. “GRP”
Page up/down
Note!
The “HEALTHY” LED can only be turned on by energizing the equipment again to restart
the relay.
Other LED indicators with no labels are configurable and user can configure them to be lit
by signals of operation element, alarm element and binary output contact according to
requirement through PCS-PC software, but as drawed in figure, there are 8 red LEDs and
10 yellow LEDs which are configurable.
It is used to access the hardware of the protection device via HyperTerminal. This port is only used
to monitor the communication state by engineering debugging personnel and debug the program
by developers.
9.1.4 Communication
The MON module is comprised by embedded processor of high performance, FLASH, SRAM,
SDRAM, Ethernet controller and other peripheral equipments. It can realize the management,
human machine interface, communication and waveform recording of the whole device. The MON
module uses the data of other modules in the receiver device of internal bus, and communicates
with LCD panel via RS-485 bus.
Take NR1102C as an example, its rear view and the definition of terminals are shown as Figure
9.1-5. This module is equipped with two 100BaseT Ethernet interface, PPS/IRIG-B differential
synchronization interface and RS-232 printer interface.
The Ethernet interface can be used to communication with PC via auxiliary software (PCS-PC) by
connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-PC). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “SETTINGS→EQUIP_SETTINS”, it should be ensured that the protection
device and PC are in the same network segment. For example, setting the IP address and subnet
mask of network A (using network A to connect with PC).
The IP address and subnet mask of protection device should be [IP_Addr_NetA]= 198.87.96.XXX,
[Subnet_Mask_A]=255.255.255.0, [En_NetA]=1. (XXX can be any value from 0 to 255 except
102).
menu commands can be recorded in the quick menu. When the five menu commands are
recorded, the latest menu command will cover the earliest one, adopting the “first in first out”
principle. It’s arranged from top to bottom and in accordance with the execution order of command
menus. Press “▲” to enter the main menu with the interface as shown in the following diagram:
For the first powered protective device, there is no recorded shortcut menu. Press “▲” to enter the
main menu with the interface as shown in the following diagram:
MainMenu
INTERFACE LANGUAGE
BOARD_INFO
COMM_TEST
ITEM_TRP_REPORT
TEST_MODE TRP_REPORT
ALM_REPORT
VERSION
BI_CHG_REPORT
CH_REPORT
CLOCK
RESET_TARGET
LOCAL_CTRL
TRIG_OSCILLOG
CLR_STATE
CLR_AR_COUNTER
DOWNLOAD
COPY_SETTINGS
SETTINGS
PROT_SETTINGS
SYS_SETTINGS
VEBI_SETTINGS
EQUIP_SETTINGS
CANCEL_PRINT
PRINT
IEC103_PROTOCOL
WAVEFORM SMPL_WAVE
PRESENT_VALUES
BI_CHG_REPORT
ALM_REPORT
TRP_REPORT
LATEST_MODIFIED
SETTINGS
ALL_SETTINGS
EQUIP_DESCRON
PROT_SETTINGS
SYS_SETTINGS
CTRL_REPORT
REPORT VEBI_SETTINGS
BI_CHG_REPORT
EQUIP_SETTING
ALM_REPORT
TRP_REPORT
AR_COUNTER
VALUES
ALM_STATE
BI_STATE
TELE_MEASUREMENT
PHASE_ANGLE
FD_MEASUREMENT
PROT_MEASUREMENT
Under the main interface, press “▲” to enter the main menu, and select submenu by pressing “▲”,
“▼” and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all the submenus under menu tree of the protection device.
9.2.2 VALUES
This menu is mainly used to display the real time sampling value of current and voltage and the
input state of the protection device, which fully reflects the running environment of the protection
device. As long as the displayed values of the two items consist with the actual running situation,
basically, the protection device can work normally. This menu is set to greatly facilitate the
debugging and maintenance of people on site.
9.2.3 REPORT
This menu is used for displaying the fault report, abnormal record, binary signal and running
reports , so that the operator can load to view and use as the reference of analyzing accidents and
maintaining the device. All the reports are stored in non-volatile memory, it can still record the
reports even if it losses its power. Each type of report can be saved for 1024 times.
9.2.4 PRINT
This menu is used for printing device description, setting, fault report, abnormal record report,
binary signal, waveform and information related with 103 Protocol.
9.2.5 SETTINGS
This menu is used for checking the setting of device equipment parameter, vitual binary input
setting, protection setting, logic setting and system parameter, as well as modifying any of the
above setting items. Morever, it can also execute the setting copy between different setting
groups.
9.2.6 LOCAL_CTRL
This menu is used for resetting the tripping relay with latch, protection device signal lamp, LCD
display, as the same as the resetting function of binary input. Record the currently acquired
waveform data of the protection device under normal condition for printing and uploading SAS.
Besides, it can send out the request of program download.
9.2.7 CLOCK
It’s used to display and modify the current date and time of the protection device.
9.2.8 VERSION
It’s used to check the information like the program version of each intelligent module in the
protection device and the program generating time.
9.2.9 TEST_MODE
This menu is mainly used for developers to debug the program and for engineers to maintain
device. It can be used to check module information and item fault message, and fulfill the
communication test function. It’s also used to generate all kinds of report or event to transmit to the
SAS without any external input, so as to debug the communication on site.
messages.
3 ITEM_TRP_REPORT Check the fault report one by one.
4 TRP_REPORT Check the fault reports.
5 ALM_REPORT Check the self-supervision reports
6 BI_CHG_REPORT Check the binary signals.
7 CH_REPORT Check the reports of channel status.
9.2.10 INTERFACE
This menu is mainly used for set LCD display language. This menu includes the following
command menus.
Under normal condition, the LCD will display the following interface. The LCD adopts white color
as its backlight that is activated if once there is any keyboard operation, and is extinguished
automatically after 60 seconds of no operation.
The displayed content of the interface contains: the current date and time of the protection device
(with a format of yy-mm-dd hh:mm:ss:), the currently valid setting group number, the three-phase
current sampling value, the zero-sequence current sampling value, the three-phase voltage
sampling value, the zero-sequence voltage sampling value, the synchronism voltage sampling
value, line frequency and the address relevant to IP address of Ethernet A. If all the sampling
values of the voltage and the current can’t be fully displayed within one screen, they will be
scrolling-displayed automatically from the top to the bottom.
If the device has detected any abnormal state, it’ll display the self-check alarm information.
For the situation that the fault report and the self-check report coexist, the upper half part is fault
report, and the lower half part is self-check report. As to the upper half part, it displays separately
the record number of fault report, fault name, generating time of fault report (with a format of
yy-mm-dd hh:mm:ss:), protection element and tripping element. If there is protection element,
there are relative time on the basis of fault detector element and fault phase. At the same time, if
the total lines of protection element and tripping element are more than 3, a scroll bar will appear
at the right. The height of the black part of the scroll bar basically indicates the total lines of
protection element and tripping element, and its position suggests the position of the currently
displayed line in the total lines. The scroll bar of protection element and tripping element will roll up
at the speed of one line per time. When it rolls to the last three lines, it’ll roll from the earliest
protection element and tripping element again. The displayed content of the lower half part is
similar to that of the upper half part.
If the device has no self-check report, the display interface will only show the fault report.
Please refer to section 7.4.2 about all the possibly displayed fault report.
Please refer to section 7.4.2 about all the possibly displayed self-supervision report.
It will be displayed on the LCD before the fault report and self-check report are confirmed. Only
pressing the restore button on the protection screen or pressing both “ENT” and “ESC” at the
same time can switch among the fault report, the self-check report and the normal running state of
protection device to display it. The binary input change report will be displayed for 5s and then it
will return to the previous display interface automatically.
2. Press the “▲” or “▼” to move the cursor to the “VALUES” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most);
6. Press the “ENT” or “ESC” to exit this menu (returning to the “VALUES” menu);
2. Press the “▲” or “▼” to move the cursor to the “REPORT” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
7. Press the “ENT” or “ESC” to exit this menu (returning to the “REPORT” menu);
For the fault report, view the single item fault report by the command menu
“ITEM_TRP_REPORT”, and the item fault report produces with change of any item of fault report.
The item fault report can save for 1024 times at most.
2. Press the “▲” or “▼” to move the cursor to the “TEST_MODE” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “ITEM_TRP_REPORT”,
and then press the “ENT” to enter the menu;
5. Press the “ESC” to exit this menu (returning to the “TEST_MODE” menu).
2. Press the “▲” or “▼” to move the cursor to the “TEST_MODE” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “BOARD_INFO”, and
then press the “ENT” to enter the menu;
5. Press the “ENT” or “ESC” to exit this menu (returning to the “TEST_MODE” menu).
2. Press the “▲” or “▼” to move the cursor to the “PRINT” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
Press the “+” or “-” to select pervious or next record. After pressing the “ENT”, the LCD will
display “Start Printer Now”, and then automatically exit this menu (returning to the menu “PRINT”).
If the printer doesn’t complete its current print task and re-start it for printing, and the LCD will
display “Printer Busy Now…”. Press the “ESC” to exit this menu (returning to the menu “PRINT”).
Press the “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and ending
numbers of printing message. After pressing the “ENT”, the LCD will display “Start Printer Now…”,
and then automatically exit this menu (returning to the menu “PRINT”). Press the “ESC” to exit this
menu (returning to the menu “PRINT”).
5. If selecting the “WAVEFORM” or “SETTINGS”, press the “ENT” or “►” to enter the next
level of menu;
6. After entering the submenu “SETTINGS”, press “▲” or “▼” to move the cursor, and then
press the “ENT” to print the corresponding default value. If selecting the
“PROT_SETTINGS” or “ALL_SETTINGS”:
Press the “+” or “-” to select the setting zone to be printed. After pressing the “ENT”, the LCD will
display “Start Printer Now…”, and then automatically exit this menu (returning to the menu
“SETTINGS”). Press the “ESC” to exit this menu (returning to the menu “SETTINGS”).
7. After entering the submenu “WAVEFORM”, press the “ENT” to enter the “SMPL_WAVE”.
Without waveform data, the LCD will display “No Wave Form Data!” (Before executing
the command menu “SMPL_WAVE”, it’s necessary to execute the command menu
“TRIG_OSCILLOG” in the menu “LOCAL_CTRL”, otherwise the LCD will display “No
Wave Form Data!”). With waveform data existing:
Press the “+” or “-” to select pervious or next record. After pressing the “ENT”, the LCD will
display “Start Printer Now…”, and then automatically exit this menu (returning to the menu
“WAVEFORM”). If the printer doesn’t complete its current print task and re-start it for printing, and
the LCD will display “Printer Busy Now…”. Press the “ESC” to exit this menu (returning to the
menu “WAVEFORM”).
2. Press the “▲” or “▼” to move the cursor to the “SETTINGS” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “SETTINGS”).
Note!
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of all displayed information of the command menu and the
relative location of information where the current cursor points at.
2. Press the “▲” or “▼” to move the cursor to the “SETTINGS” menu, and then press
the “ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “SETTINGS” );
8. If selecting the command menu “EQUIP_SETTINGS”, move the cursor to the setting
item to be modified, and then press the “ENT”;
Press the “+” or “-” to modify the value (if the modified value is of multi-bit, press the “◄” or “►”
to move the cursor to the digit bit, and then press the “+” or “-” to modify the value), press the
“ESC” to cancel the modification and return to the displayed interface of the command menu
“EQUIP_SETTINGS”. Press the “ENT” to automatically exit this menu (returning to the displayed
interface of the command menu “EQUIP_SETTINGS”).
Move the cursor to continue modifying other setting items. After all setting values are modified,
press the “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”. Directly press the “ESC” or
press the “◄” or “►” to move the cursor. Select the “Cancle”, and then press the “ENT” to
automatically exit this menu (returning to the displayed interface of the command menu
“EQUIP_SETTINGS”).
Press the “◄” or “►” to move the cursor. Select “No” and press the “ENT”, all modified setting item
will restore to its original value, exit this menu (returning to the menu “SETTINGS”).
Press the “◄” or “►” to move the cursor to select “Yes”, and then press the “ENT”, the LCD will
display password input interface.
Input a 4-bit password (“+”, “◄”, “▲” or “-”). If the password is incorrect, continue inputting it,
and then press the “ESC” to exit the password input interface and return to the displayed interface
of the command menu “EQUIP_SETTINGS”. If the password is correct, LCD will display “Save
Setting Now…”, and then exit this menu (returning to the displayed interface of the command
menu “EQUIP_SETTINGS”), with all modified setting items as modified values.
Note!
For different setting items, their displayed interfaces are different but their modification
methods are the same. The following is ditto.
9. If selecting the command menu “VEBI_SETTINGS”, move the cursor to the setting to
be modified, and then press the “ENT”;
10. If selecting the command menu “EQUIP_SETTINGS”, move the cursor to the default
item to be modified, press the “ENT”
Note!
After modifying the parameter settings of the device, the “HEALTHY” indicator lamp of the
protection device will go out, and the protection device will automatically restart and
re-check the protection setting. If the check doesn’t pass, the protection device will be
blocked.
11. If selecting the command menu “PROT_SETTING”, the LCD will display the following
interface:
4. PROT_SETTINGS
Group NO select
Current Group NO 01
Group NO To be Edited 02
Press the “+” or “-” to modify the value, and then press the “ENT” to enter it. Move the cursor to
the setting item to be modified, press the “ENT” to enter.
Note!
After modifying the equipement parameter of the device, the “HEALTHY” indicator lamp of
the protection device will go out, and the protection device will automatically restart and
re-check the protection setting. If the check doesn’t pass, the protection device will be
blocked.
2. Press the “▲” or “▼” to move the cursor to the “SETTINGS” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “COPY_SETTINGS”,
and then press the “ENT” to enter the menu.
Press the “+” or “-” to modify the value. Press the “ESC”, and return to the menu “SETTINGS”.
Press the “ENT”, the LCD will display the interface for password input, if the password is incorrect,
continue inputting it, press the “ESC” to exit the password input interface and return to the menu
“SETTINGS”. If the password is correct, the LCD will display “copy setting OK!”, and exit this menu
(returning to the menu “SETTINGS”).
Press the “+” or “-” to modify the value, and then press the “ESC” to exit this menu (returning to
the main menu). After pressing the “ENT”, the LCD will display the password input interface. If the
password is incorrect, continue inputting it, and then press the “ESC” to exit the password input
interface and return to its original state. If the password is correct, the “HEALTHY” indicator lamp
of the protection device will go out, and the protection device will re-check the protection setting. If
the check doesn’t pass, the protection device will be blocked. If the check is successful, the LCD
will return to its original state.
2. Press the “+”, “-”, “+”, “-” and “ENT”; Press the “ESC” to exit this menu (returning to
the original state). Press the “ENT” to carry out the deletion.
Note!
The operation of deleting device message will delete all messages saved by the protection
device, including fault report, self-check report, binary signal and run report. Furthermore,
the message is irrecoverable after deletion, so the application of the function shall be
cautious.
2. Press the “▲” or “▼” to move the cursor to the “CLOCK” menu, and then press the
“ENT” to enter clock display
3. Press the “▲” or “▼” to move the cursor to the date or time to be modified;
4. Press the “+” or “-” to modify value, and then press the “ENT” to save the modification
and return to the main menu;
5. Press the “ESC” to cancel the modification and return to the main menu.
2. Press the “▲” or “▼” to move the cursor to the “VERSION” menu, and then press the
“ENT” to display the software version;
2. Press the “▲” or “▼” to move the cursor to the “TEST_MODE” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “COMM_TEST”, and
then press the “ENT” to enter the menu, at this moment, the LCD will display “Enter
Communication Test Now…”;
4. Press the “▲” or “▼” to move the cursor to select the corresponding command menu “All
Test”, “Trip Test”, “Alarm Test” and “BI Test”.
Note!
If no input operation is carried out within 60s, exit the communication tes and return to the
“TEST_MODE” menu, at this moment, the LCD will display “Communication Test Exit
Now…”.
5. If selecting the “All Test”, press the “ENT”, and the device will successively carry out the
“Trip Test”, “Alarm Test” and “BI Test”..
6. If selecting the “Trip Test”, “Alarm Test” or “BI Test”, press the “ENT”.
7. Press the “+” or “-” to page up/down, and then press the “▲” or “▼” to move the scroll bar.
(taking the “Trip Test” as an example):
Move the cursor to select the corresponding protection elements. Press the “ENT” to execute the
communication test one by one, the SAS will receive the corresponding fault report, and view the
fault report produced by communication test in the command menu “ITEM_TRP_REPORT”.
Note!
If no input operation is carried out within 60s, exit the communication transmission and
return to the “TEST_MODE” menu, at this moment, the LCD will display “Communication
Test Overtime Exit”.
If selecting the “Alarm Test” or “BI Test”, not only the SAS can receive the corresponding
self-check report or binary signals, but also the self-check report or binary signals
produced by communication test can be respectively viewed by the two command menus
of “ALM_REPORT” and “BI_CHG_REPORT” in the menu “REPORT”.
8. Press the “ESC” to exit this menu (returning to the menu “TEST_MODE”, at this moment,
the LCD will display “Communication Test Exit Now…”.
Note!
The LCD interface provided in this chapter is a mere reference and available for explaining
specific definition of LCD. The displayed interface of the actual protection device may be
different from it, so you shall be subject to the actual protection device.
Chapter 10 Communications
This section outlines the remote communications interfaces of NR Relays. The protective device
supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet),
selected via the model number by setting. The protocol provided by the protective device is
indicated in the submenu “EQUIP_SETTINGS”.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
Note!
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NR cannot assume responsibility for
any damage that may occur to a device connected to the network as a result of incorrect
application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
To use the rear port with IEC60870-5-103 communication, the relevant settings to the protective
device must be configured.
The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the
protective device as the slave device. It is properly developed by NR.
Initialization (reset)
Time synchronization
General interrogation
General commands
Disturbance records
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
All general classification service group numbers can be gained by printing, implementing submenu
“IEC103_PROTOCOL” in the menu “PRINT”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
All channel numbers (ACC) of disturbance data can be gained by printing, implementing submenu
The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave
device. It is properly developed by NR too. All the service of this relay is based on generic
functions of the IEC60870-5-103. The following table lists all the group number of this relay. And
this relay will send all the relevant information about group caption to the SAS or RTU after
establishing a successful communication link.
10.5.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual IEC 61850-7-2 abstract services and objects are mapped to MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED and communication
system realized according to IEC 61850-5 and IEC 61850-7. Each configured device has an IEC
Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single
line information is stored in a System Specification Description (SSD) file. The entire substation
configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the
combination of the individual ICD files and the SSD file, moreover, add communication system
parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of
GOOSE and SV to SCD file.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains information
about the IED logical device.
The GGIO logical node is available in the PCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the PCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
MMXU.MX.Hz: frequency
The following list describes the protection elements for PCS-902 series relays. The specified relay
will contain a subset of protection elements from this list.
PTUC: undercurrent
PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS
PTUV: undervoltage
RBRF:Breaker failure
RSYN: Synchronism-check
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For
PCS-902 series relays protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined to
a new “operate” of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-900 series relay.
10.5.4.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE VEBI
settings in device.
The PCS-900 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-900 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M16 Time M M Y
M17 File transfer O O Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
S56 TimeActivated-Operate O N
File transfer
S57 GetFile M/O Y
S58 SetFile O N
S59 DeleteFile O N
S60 GetFileAttributeValues M/O Y
Time
SNTP M Y
The PCS-902 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.
The GOOSE service supports the exchange of public data comprised of data sets, it is used to
protect the data transmission which requires high real-time like tripping, breaker position and
interlocked information. The information exchange of GOOSE service is based on the
publish/subscribe mechanism, and any IED device in the same GOOSE network can be
conducted as subscription terminal to receive data and as publication terminal to provide
data to other IED device as well, so that the increasing or modification of communication data
between IED devices can be realized in a much easier way.
In order to ensure the real-time property and reliability of GOOSE service, GOOSE message
adopts ASN.1 code which relates to basic encoding rule (BER) and transmit data directly in
Ethernet link layer without passing through TCP/IP protocol and also adopts special
receiving/sending mechanism.
Sending of the GOOSE message adopts heartbeat message and position-altering message fast
resending combination mechanism. If the data in GOOSE data sets is not changed, the heartbeat
message whose interval is T0 will be sent, the status number (stnum) in message will not be
changed and the sequence number (sqnum) will be increased progressively. If the data in GOOSE
data set is changed, after sending a frame of position-altering message, the position-altering
message will be fast resent in the interval of T0, T1, T2, and T3. The status number (stnum) in the
message whose data is position-altered will be increased, and the sequence number (sqnum) will
be started from zero.
The GOOSE receiving can detect link interrupt according to the TATL (Time Allow to Live) in the
GOOSE message. The GOOSE data receiving mechanism can be divided into single frame
receiving and dual-frames receiving. The intelligent operation box uses dual-frames receiving
mechanism and update data after receiving two frames of messages with the same GOOSE data.
Other protection and monitoring devices use single frame receiving mechanism and update data
immediately after receiving position-altering message (stnum changed). If the status number
(stnum) in the received message is not changed, dual-frames message confirmation will be used
to update data.
2. GOOSE Alarm
GOOSE will alarm the abnormal conditions produced during receiving/sending process, the
GOOSE alarms mainly include: GOOSE network A/B network link breaking alarm, GOOSE
configuration inconformity alarm and GOOSE network A/B network-storm alarm.
The GOOSE network A/B link breaking alarm is: this alarm will be produced when correct GOOSE
message is not received in 2 times of the TATL (Time Allow to Live).
The GOOSE configuration inconformity alarm is: the attribute of GOOSE control block of GOOSE
publisher and subscriber like configuration version number must be identical. Otherwise this
GOOSE configuration inconformity alarm will be produced.
The GOOSE network A/B network-storm alarm is: when network-storm is produced in GOOSE
network, if data flow of network port is beyond normal range and abnormal message is produced,
this GOOSE network A/B network-storm alarm will be produced.
3. GOOSE Service
When service status of the device is set to 1, the GOOSE message sent by the device has a Test
Flag and receiving terminal can obtain service status of sending terminal by the test flag of
message. When the service status of sending terminal conforms to that of receiving terminal, the
device will carry out normal processing to the received GOOSE data. When the service status of
sending terminal doesn’t conform to that of receiving terminal, the device will process the received
GOOSE data accordingly to ensure that the serviced device will not influence the normal running
of device, improving the flexibility and reliability of GOOSE service.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
11.1 Introduction
This chapter focuses on the instructions on how to install and commission the protective device,
including procedures for mechanical and electrical installation, energizing and checking of external
circuitry, setting and configuration as well as verifying settings and performing a directionality test..
It can be used as a reference if a periodic test is performed.
1) The “Safety information” presents warning and note signs, which users should draw
attention to.
2) The “Overview” gives an overview of the major task when installing and commissioning the
protection equipment.
3) The “Unpacking and checking the protective device” contains instructions on how to
receive the protection equipment.
4) The “Installing the protective device” contains instructions on how to install the protection
equipment.
5) The “Checking the external circuitry” contains instructions on how to check that the
protection equipment is properly connected to the protection system.
6) The “Energizing the protective device” contains instructions on how to start-up the
protection equipment.
7) The “Setting the protective device” contains instructions on how to download settings and
configuration to the protection equipment.
9) The “Verifying settings by secondary injection” contains instructions on how to verify that
each included function operates correctly according to the set value.
10) The “Final Check” contains instructions on how verify that the protection equipment is
properly configured.
The chapter is addressing the installation, commissioning and maintenance personnel responsible
for taking the protection into normal service and out of service. The installation personnel must
have a basic knowledge of handling electronic equipment. The commissioning and maintenance
personnel must be expert in using protection equipment, test equipment, protection functions and
the configured functional logics in the protection.
Warning signs
Warning!
Strictly follow the company and country safety regulations. Working in a high voltage
environment requires serious approach to avoid human injuries and damage to
equipment.
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
Always avoid touching the circuitry when the cover is removed. The product contains
electronic circuitries which can be damaged if exposed to static electricity (ESD). The
electronic circuitries also contain high voltage which is lethal to humans.
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
Never unmount the front or back cover from a powered equipment or from a protection
equipment connected to powered circuitry. Potentially lethal voltages and currents are
present.
Caution signs
Caution!
Always transport modules using certified conductive bags. Always handle modules using
a conductive wrist strap connected to protective ground and on a suitable antistatic
surface. Electrostatic discharge (ESD) may cause damage to the module.
Do not connect live wires to the protection equipment. Internal circuitry may be damaged.
Always use a conductive wrist strap connected to protective ground when replacing
modules. Electrostatic discharge (ESD) may damage the module and protection
equipment circuitry.
Take care to avoid electrical shock if accessing wiring and connection protection
equipment when installing and commissioning.
Note signs
Note!
Changing the active setting group will inevitably change the protection equipment’s
operation. Be careful and check regulations before making the change.
The protection assembly is designed for a maximum continuous current of four times
rated value.
Activating the other setting group without proper configuration may seriously affect the
protection equipment’s operation.
11.3 Overview
The settings for each function must be calculated before the commissioning task can start. A
configuration, made in the configuration and programming tool, must also be available if the
protection equipment does not have a factory configuration downloaded.
The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle.
The connection to the protection system has to be checked in order to verify that the installation
was successful.
The installation and commissioning task starts with configuring the digital communication modules,
if included. The protection equipment can then be configured and set, which means that settings
and a configuration has to be applied if the protection equipment does not have a factory
configuration downloaded. Then the operation of each included function according to applied
settings has to be verified by secondary injection. A complete check of the configuration can then
be made. A conformity test of the secondary system has also to be done. When the primary
system has been energized a directionality check should be made.
Carefully examine the protection panel, protection equipment and other accessory parts
to check if any physical damage has occurred during installation.
Panel wiring:
Check the conducting wire used in the panel to assure that the cross section meet the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Label:
Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable:
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator links and push buttons work normally
and smoothly.
3) Check that all items are included in accordance with the delivery documents.
The user is requested to check that all software functions are included according to the delivery
documents after the terminal has been energized.
These product checks cover all aspects of the protection, which should be checked to ensure that
the protection has no physically damages prior to commissioning, all functions are correctly and all
input quantity measurements are within the stated tolerances.
Sufficient space must be reserved in front of and at rear of the protection panel to allow access for
maintenance and future modifications. Flush mounted protection equipment should be mounted
so that equipment modules can be added and replaced without excessive demounting.
11.5.2 Dimensions
The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. PCS-902 series is IEC
4U high and 19” wide. Figure 11.5-1 shows its dimensions and Figure 11.5-2 shows the panel
cut-out.
101.6
177.0
465.0
101.6
179.0
4-Ф6.8
450.0
All these influences can effect the operation of electronic apparatus. On the other hand, electronic
apparatus can transmit interference that can disrupt the operation of other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Note!
All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
Note!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (refer to Figure 11.5-3).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
Note!
For metallic connections please observe the voltage difference of both materials according
to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
There are some ground terminals on some connectors of the relays, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear
panel (refer to Figure 11.5-4) is the only ground terminal of this device.
The grounding strips must be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Data of braided copper strip: threaded M4, 4.0mm2. Proper terminations must be fitted to both
ends (press/pinch fit and tinned) with a hole so as to bolt them firmly to the connecting items.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
When using screened cabling always use 360° full screen cable bushing to ensure screen
coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing
current and voltage measuring signals in the same cable. Also use separate cables for control and
measuring circuits.
Heavy-duty terminal block, M4 threaded terminal ends. VT circuit must be connected with the
protective device through an MCB.
Auxiliary power cords cross can be directly screwed fixed on the rear panel of DC board..
Welding terminals. Those devices are supplied with sufficient M4 screws for connections to the
rear mounted terminal blocks using ring terminals, with a recommended maximum of two ring
terminals per relay terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except for the EIA RS-485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
Connect the unit to the grounding bar of cubicle with green/yellow conductor; connected to the
protective Earthing terminal at the back of the DC board. Attend that the earth wire must be as
short as possible. All cautions have to be taken to ensure the best electrical conductivity,
particularly the contact quality and stainless conductor. The impedance between the relay Earthing
terminal and the Earth must be less than 20mΩ under 12Volt, 50Hz. What matters is that the
device has to be only grounded at one point. Loop grounding from unit to unit is not allowed.
Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark
grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey
(transmit) back-side connectors.
Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature
radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with
loose fit.
Note!
Always hold the connector, never the cable, when connecting or disconnecting optical
fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre damping
thus making communication impossible.
When using galvanic connection between protective relay and communication equipment or
point-to-point galvanic connection between two protective relays it is essential that the cable
installation is carefully done. This is true regardless of type of module used, only the possible
length of the cable differs. The factors that must be taken into account is the susceptibility for noise
disturbance, due to that the levels of the communication signal are very low. For the best result, a
cable with twisted pairs with screen should be used.
For RS485 serial communication interface, a termination 120-ohm resistor has to be connected at
each extremity of the bus. Please refer to Chapter 10.
Check that the wiring is in strict accordance with the supplied wiring diagram.
Polarity check
Grounding check
The polarity check verifies the integrity of the circuits and the phase relationship. The check should
be performed as close as possible to the relay. The primary injection test verifies the CT ration and
the wiring all the way through from the primary system to the relay. Injection must be performed to
each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases
and the neutral line are measured.
Check that the value of the auxiliary supply voltage remains in the permissible range under all
operating conditions. Check that the polarity is correct according to the instruction manual on the
rear plate of DC board.
Preferably, disconnect the binary input connector form the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the relay’s specifications.
Note!
The binary inputs may be energized from an external dc auxiliary supply (e.g. the station
battery) in some installations. Check that this is not the case before connecting the field
voltage otherwise damage to the protection may result. The status of each binary input can
be viewed using either tool software installed in a portable PC or by checking the front
man-machine interface LCD. When each binary input is energized the display will change
to indicate the new state of the inputs.
Preferably, disconnect the binary output connector form the binary output cards. Check all
connected signals so that both load and polarity are in accordance with the relay’s specifications.
User must energize the power supply to the relay to start it up. This could be done in a numerous
of ways, from energizing a whole cubicle to energizing a single relay. The user should reconfigure
the relay settings. The relay time must be set. The self-supervision function should also be
checked to verify that the relay unit operates properly. User could also check the software version,
the relay’s serial number, the installed modules, and their ordering number to ensure that the relay
is according to delivery and ordering specifications.
Connect the relay to DC power supply correctly and turn the relay on. Check displayed program
version and time in command menu to ensure they are corresponding to what ordered.
If time and date is not being maintained by substation automation system, it should be set
manually.
Set the date and time to the correct local time and date using menu item “CLOCK”. Please refer to
the section “Adjust the Clock” for detailed procedures.
If the auxiliary supply fails, fit a battery on CPU board, time and date will be maintained. Therefore
when the auxiliary supply is restored, the time and date will be corrected and there is not need to
set it again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
The relay has latched signal relays which remember the state of the trip. Therefore these
indicators may also illuminate when the auxiliary supply is applied. If any of these LEDs are
lightened, then they should be reset before proceeding with further testing. If the LED is
successfully reset, the LED goes out.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Download from a PC or laptop with tool software or remotely by SCADA. Front port
communication has to be established before the settings can be downloaded.
To change settings through the local HMI need a password which is “+”, “◄”, “▲” and “-” keyboard
on the front panel.
Unless previously agreed to the contrary, the customer will be responsible for determining the
application-specific settings to be applied to the protection, testing of any scheme logic applied by
external wiring and/or configuration of the protection’s internal programmable scheme logic.
The test is not intended for the verification of operation of the complete system from the relay to
the remote location, but for the protection’s rear communications port and any protocol converter
necessary.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
Note!
Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
At the same time, the calculated settings, substation configuration diagram, the protective device
diagram and the instruction manual are necessary for tests.
The relay has to be set before the testing can start. Only the functions that are used should be
tested.
All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters. The user could
also energize the binary input [BI_BlkComm] to disable communication function to ensure that no
events are reported to remote station during the test.
The setting checks ensure that all of the application-specific protection settings (i.e. both the
protection’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
Unplug all the terminals sockets of this protective device, and apply insulation resistance test to
each circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading can then be checked
either in the protection’s submenu “PROT_MEASUREMENT” column or a portable computer
connected to the front communication port with tool software.
The measurement accuracy of the protection is ± 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
This test verifies that the accuracy of voltage measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading either in the protection’s
submenu “PROT_MEASUREMENT” or a portable computer connected to the front
communication port with tool software.
The measurement accuracy of the protection is ±5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
3) Self-check and the transition of binary input in the process of devices start
1) Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to facilitate testing.
If it is necessary to disconnect any of the external wiring from the protection in order to perform a
foregoing tests, it should be ensured that all connections are replaced in accordance with the
relevant external connection or scheme diagram. Confirm current and voltage transformer wiring.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.
Chapter 12 Maintenance
NR numerical relay does not require any special maintenance. All measurements and signal
processing circuit are fully solid state. All input modules are also fully solid state. The output relays
are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows a corrective rather
than preventive maintenance strategy. Therefore, maintenance checks in short intervals are not
required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw relay board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the primary
system is live when withdrawing an AC module. Never try to insert or withdraw the relay board
when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “ALM_REPORT” screen on the LCD.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, CPU, SIG, BI, BO,
etc.) and hardware type-form to the removed module. Furthermore, the CPU module replaced
should have the same software version. In addition, the AI and PWR module replaced should have
the same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “VERSION”.
Caution!
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could from damages. After replacing the CPU module, check the settings.
1) Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
Warning!
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
Unplug the ribbon cable on the front panel by pushing the catch outside.
After replacing the CPU module, input the application-specific setting values again.
Warning!
Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.
Warning!
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the CPU module, check the settings.
Danger!
After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.
12.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies and current transformer connections are
isolated to prevent any chance of an electric shock. Use a smooth cloth to clean the front panel.
Do not use abrasive material or detergent chemicals.
12.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-6 the storage temperature should be from -25oC to 70oC, but the temperature of from -10oC
to 40oC is recommended for long-term storage.
13.1 Decommissioning
1. Switching off
To switch off the PCS-902, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
Danger!
Before disconnecting the power supply cables that connected with the DC module of the
PCS-902, make sure that the external miniature circuit breaker of the power supply is
switched off.
Danger!
Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
3. Dismantling
The PCS-902 rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
Danger!
When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note!
Strictly observe all local and national regulations when disposing of the device.