Advanced Boiler Technologies for
Commercial and Industrial
Applications - Ultramizer® AHRS
2012 Emerging Technologies Summit
October 16, 2012, Pasadena, CA
Neil P. Leslie, P.E., Gas Technology Institute
847 768 0926,
[email protected]Ultramizer® AHRS Technology
> Core Transport Membrane Condenser
(TMC) technology developed by GTI
with support from a number of
government and gas utility
stakeholders
> Uses a robust nanoporous membrane
to selectively recover sensible and
latent heat and pure water from
natural gas combustion byproducts
─ avoids corrosive condensate
> Successfully developed for Retrofit &
New Commercial/Industrial boilers
─ Licensed to Canon Boiler Works
(CBW)
Ultramizer® AHRS tubes in a
bundle assembly
2
Why Heat Recovery from Boilers?
>There is a large population of
outdated and inefficient
commercial and industrial
boilers
─ Many old boilers need replacement
─ New technology options available for
improved efficiency
─ Utility emerging technology programs
can be a key catalyst for new high-
efficiency equipment
3
US Commercial and Industrial
Boiler Population
Over 75% of larger commercial and Commercial
industrial boilers greater than 30 years old Number
Total Boiler
Average Capacity per
Building Type Capacity
of Boilers Facility (MMBtu/hr)
(MMBtu/Hr)
Education 35,895 128,790 3.6
Office 28,030 297,090 10.6
Health 15,190 317,110 20.9
Other 11,900 88,970 7.5
Lodging 10,545 140,830 13.4
Public Assembly 7,280 55,205 7.6
Retail 5,585 47,230 8.5
Warehouse 5,365 72,385 13.5
Total 119,790 1,147,610 9.6
Industrial
Other
Food Paper Chemicals Refining Metals Total
Industrial
< 10 MMBtu/hr 6,570 820 6,720 260 1,850 7,275 23,495
10‐50 MMBtu/hr 3,070 1,080 3,370 260 920 3,680 12,380
50‐100 MMBtu/hr 570 530 950 260 330 930 3,570
100‐250 MBtu/hr 330 540 590 200 110 440 2,210
>250 MMBtu/hr 70 490 350 220 120 110 1,360
Total Units 10,610 3,460 11,980 1,200 3,330 12,435 43,015
Source: EEA/ORNL (2005) 4
Steam Systems and Energy
Efficiency Opportunities
5
Natural Gas Boiler Flue Gas
Heat Recovery
> Natural gas combustion produces 18% water
volume in flue gas 10% of fuel energy input
> Steps to higher energy efficiency
sensible & latent heat recovery
─ Sensible = reduce exhaust temperature by
preheating water (or other use) up to 88%
efficiency
─ Latent = condensing exhaust water vapor to liquid
releases energy that can be recovered over
88% efficiency
─ Caution: Exhaust condensate is usually corrosive
(pH 3-5)
6
Cannon Ultramizer® System
• Combines Cannon’s high temperature
(HTE) and low temperature (LTE)
Feedwater Economizers with Ultramizer®
AHRS Technology to provide the ultimate
in heat and water recovery
• Recovers Sensible and Latent Heat and
clean water from flue gas stream
• Boiler efficiencies of 95% are possible
• Reduction in emissions is equal to the
reduction in fuel consumption
• http://www.cannonboilerworks.com/ultrami
zer.html
7
7
Flexible Installation Options
8
Boiler Efficiency
Improvement Options
The Ultramizer® provides
high boiler efficiency
while:
• Reducing make‐up
water demand
• Avoiding a corrosive
condensate
management issue that
would otherwise cost
the commercial or
industrial customer
Based on Baxter test conditions.
Efficiency can go as high as 95% depending on operating conditions.
9
Ultramizer® Energy & Consumer Savings
300 hp Boiler @80% average firing rate
Energy Energy Cost Water
Water Cost
Savings Savings Savings
Savings*
MMBtu/yr ($/yr) (Gallons/yr)
6000
8,200 $65,590 251,900 $2,519
hours/year
8000
10,930 $87,450 335,900 $3,359
hours/year
* Assuming $10/1000 gallons for water purchase and clean-up
10
Ultramizer® AHRS Demonstrated at Baxter
Healthcare & Richardson Brand Candy
> Demonstrations provided key engineering information for
further advancement of the Ultramizer® AHRS
> Pump speed control, cavitations, and humidity instrument
failures have led to design modifications that ultimately
improved the Ultramizer® AHRS product offering
> Knowledge gained facilitated the transfer of this technology into
non-boiler installations, thus dramatically increasing the impact
of the newly commercialized Ultramizer® AHRS
11
Ultra-High Efficiency Boiler
AHRS at Richardson Brand in New York
> Operating since 2011
> Over 15% savings in steam production
costs
> Up to 20% less make-up water
consumed
> Lower NOx and CO2 emissions
12
Ultra-High Efficiency Boiler
AHRS at Baxter Healthcare
> Operating since 2010
> Providing energy, carbon and
water savings
> Measured efficiency 92.5%
> Over 250,000 gallons of annual
estimated water savings
13
Independent Evaluation: Baxter
Healthcare, May 2012
> Ultramizer® AHRS retrofit to
Boiler No. 1 of two 250HP
boilers
─ Includes HPE, LPE & 2nd
Generation TMC
> Boiler produces saturated
steam at 110 psig
> Installed Data Acquisition
System
> Validation tests conducted
using portable analyzer and
manual data collection over 2
days
─ DAS found unreliable
14
Validation Testing Approach
> Boiler No.1 in manual control
> Boiler No. 2 in auto control to accommodate load swings
> Boiler No. 1 tested from 10% to 95% firing rate on control panel
in 10-15% increments on May 1, 2012
> Tests repeated on May 2, 2012
> Flue gas data - portable Testo 350 analyzer
> Combustion air temperature - Fluke handheld thermometer
> Feed water flow rate – Strap-on ultrasonic meter
> Pre-installed instruments and meters – manually recorded
15
Boiler Efficiency Calculations
> Indirect Heat Loss Method (ASME PTC 4.1 procedure)
─ Used flue gas combustion data to calculate stack losses
(dry gas, moisture, and unburned CO and hydrocarbon)
─ Fuel to steam efficiency = 100% - percent stack loss -
radiation loss (assumed 0.5% of input) – blow down loss
(assumed 3% of feed water flow rate)
> Direct Input/output Method
─ Calculated from natural gas input and steam output flow
rates and heat contents
─ Found unreliable because of erratic steam flow
measurements
16
Boiler Efficiency Results
> Combustion efficiency similar 95.0%
Boiler 1 Efficiency at FW Econo Outlet
across firing rates indicating good 93.0%
Combustion Efficiency
air-fuel ratio control
91.0%
Fuel to Steam Efficiency
89.0%
> Fuel to steam efficiency lower at
87.0%
Efficiency (%)
85.0%
low firing rates due to increased 83.0%
percent radiation losses 81.0%
79.0%
77.0%
75.0%
Excess Oxygen 0% 10% 20% 30% 40% 50% 60% 70%
Firing Rate Set on Hawk Control Panel
80% 90% 100%
7.00
6.00
5.00 Boiler 1 Boiler 2
4.00 Average Gas Consumption
(MMBtu/hr) 5.658 3,214
g
3.00
Testo O2
2.00 Average Steam Production (pph)
In‐Situ O2 4,788 2,615
1.00
Combustion Efficiency (at Feed
0.00
0% 20% 40% 60% 80% 100%
Water Economizer outlet for 85.7% 83.2%
Boiler 1)
Firing Rate
Fuel-to-Steam Efficiency 84.3% 81.1%
17
Heat Recovered by AHRS
> LPE and TMC recovered an average of 307,172 Btu/hr, or 5.6%
of input
> 55% of heat was recovered by LPE and 45% by TMC
Average of
Test 2B Test 4 Test 7 Test 9B Tests 1 ‐9
Firing Rate Set on Hawk Control Panel 25% 50% 75% 95% 54%
Flue Gas Temp Entering Condensing Economizer oF 245.6 251.4 259.4 267.3 251.6
Flue Gas Temp Exiting Condensing Economizer oF 122.5 122.1 121.8 125 123.1
Remaining Sensible Heat in Flue Gas BTU/h 136,820 170,436 226,480 289,458 187,252
Latent Heat in Flue Gas BTU/h 94,123 119,214 155,201 139,874 119,920
Total Available Heat BTU/h 230,944 289,650 381,682 429,332 307,172
Heat recovered by TMC and LPE ‐ Available Heat Btu/hr 230,944 289,650 381,682 429,332 307,172
18
Boiler Efficiency with AHRS
> Ultramizer® AHRS increased combustion efficiency from 85.7% to
91.3%
> Average NOx corrected to 3% O2 was 9.7 ppm.
Average
Test 2B Test 4 Test 7 Test 9B Test 1-9
Firing Rate Shown on Hawk Panel 25% 50% 75% 95%
Average Firing Rate [%] 40% 49% 62% 78% 53%
Natural Gas Cinsumption MMBtu/hr 4.190 5.115 6.486 8.201 5.544
k Losses (Heat in Flue Gases out of FW Economizer) MMBtu/hr 0.596 0.729 0.934 1.190 0.791
Heat Recovered by LPE and TMC MMBtu/hr 0.231 0.290 0.382 0.429 0.307
Heat in Flue Gases Outlet of TMC MMBtu/hr 0.365 0.440 0.552 0.760 0.484
Combustion Efficiency at FW Economizer Outlet 85.8% 85.7% 85.6% 85.5% 85.7%
Combustion Efficiency at TMC Outlet 91.3% 91.4% 91.5% 90.7% 91.3%
19
Additional Information
> Ultramizer® versus Other Technologies
(http://www.cannonboilerworks.com/Ultramizer®_pages/other_tech.html)
> Frequently Asked Questions and Answers:
(http://www.cannonboilerworks.com/Ultramizer®_pages/faq.html)
> Ultramizer® Calculator designed to show potential financial
savings based on simplified operating conditions that may be
similar to many customer's operations, this is a tool intended to
help justify the detailed study time and expense required for
proper evaluation of each customers savings potential.
http://www.cannonboilerworks.com/ultramizer_pages/index.html
20
General Boiler Application Criteria
> Boiler sizes ranging from 100 to 1,200 boiler HP
output range
> Greater than 15 - to 300-psig saturated operating
steam pressure
> Natural gas fired (Can consider a bypass arrangement
for backup fuel systems)
> Makeup water requirements of more than 25% of total
boiler feed water
> Annual capacity factor of minimum 50%