Main feature
Ensuring the air supply rate to a cleanroom
complies with the EU GGMP and ISO 14644-3
recovery rate requirements
W Whyte 1, N Lenegan 2 and T Eaton 3
1
 School of Engineering, University of Glasgow, Glasgow G12 8QQ; 2 Energy and Carbon Reduction Solutions,
Ashton-Under-Lyne, Lancashire, OL5 0RF; 3 AstraZeneca, Macclesfield, Cheshire, SK10 2NA
Abstract                                    According to the EU GGMP, a Grade B              measurement, C0 is the initial
The European Union Guidelines to            cleanroom should have a maximum                  concentration, and C is the
Good Manufacturing Practice (EU             concentration of particles *0.5µm                concentration after time t.
GGMP) includes a recommendation             during operation of 352,000/m3 and in                The recovery rate and recovery time
for a ‘clean-up’ of airborne particles      the at rest condition of 3520/m3, and            both measure the particle decay and one
in the cleanroom after completion of        therefore the required maximum drop              test result can be easily converted to the
operations, where the concentration         in the concentration of particles during         other. No required recovery rate or
should decay by up to 100, or 10 fold,      ‘clean-up’ is 100 fold. In a Grade C             recovery time is specified in ISO 14644-3,
in 15 to 20 minutes. When designing a       room, the maximum ‘operational’                  but the EU GGMP requirement of a 100
ventilation system for non-unidirectional   condition is 3,520,000/m3 and the ‘at            fold particle concentration reduction
airflow EU GGMP Grade B and C               rest’ condition is 352,000/m3, which is a        in less than 20 minutes is often applied
cleanrooms, it is necessary to determine    10 fold reduction. Particles *0.5µm are          to cleanrooms not regulated by the
if the proposed air supply rate will be     normally measured during the clean-up            EU GGMP.
sufficient to provide the air change rate   tests, and not particles *5µm, as the                When a non-unidirectional airflow
for the clean-up specified in the EU        larger particles give a greater decay rate       cleanroom is being designed, the air
GGMP, and such a method is provided         than actually occurs, because of particle        supply rate has to be determined.
in this article. The air change rates for   deposition onto cleanroom surfaces               However, it is usually unclear whether
other decay times and reductions in         caused by gravity (ISO 14644-3:2005              this air supply rate is sufficient to ensure
particle concentrations in cleanrooms       suggests that test particles should be           the ‘clean up’ requirements given in the
can also be calculated by this method.      less than 1 µm). The decay time given            EU GGMP. If the calculated air supply is
                                            in the EU GGMP for both Grade B and              insufficient the recovery time will be
Introduction                                C rooms is between 15 to 20 minutes              longer than desired and the recovery
Annex 1 of the EU GGMP covers               and, as a decay time of 15 minutes is            rate slower. It is not until the cleanroom
various aspects of sterile products         a more stringent requirement than 20             is built and manufacturing starts, that
manufacture, including contamination        minutes, it is the time often applied.           testing can be carried out, and it would
control. It suggests that manufacturing         ISO 14644-3:2005 gives two recovery          be useful if a method was available to
cleanrooms will quickly recover from        tests to determine a cleanroom’s                 predict what air supply rate is necessary
the generation of high concentrations of    ability to recover quickly from a high           to ensure a specified reduction in
airborne particle contamination and         concentration of particles, namely,              particle concentration in a given time.
should ‘clean up’ in 15 to 20 minutes       the recovery time and recovery rate.             Carrying out a recovery test provides a
(guidance value) after completion of        Test particles are introduced into the           qualification test that gives confidence
operations, to the particle limit stated    cleanroom and the recovery time is               that the airflow in the non-UDAF
for the ‘at rest’ state. This applies to    obtained by measuring the time for the           cleanroom is well designed and will
cleanrooms designated Grade B and           airborne particle concentration to decay         provide effective particle removal.
Grade C, which have non-unidirectional      by a factor of 100:1. If the recovery time           The concentrations of airborne
airflow, but not to Grade A cleanrooms      is set at 15 -20 minutes, this test is similar   contamination in non-unidirectional
which have unidirectional airflow,          to that specified by the EU GGMP for a           airflow rooms can be calculated by a set
or to Grade D which has no specified        Grade B cleanroom.                               of equations known as the ‘ventilation
‘operational’ particle concentration.           The recovery rate is obtained from           equations’, and their application to
Achieving this ‘clean up’ time is           measurements of the decay of                     cleanrooms has been discussed by
considered to demonstrate that the          concentration of test particles in the           Whyte, Whyte and Eaton (2012).
cleanroom has a ventilation effectiveness   cleanroom and calculated by Equation 1:          These equations can determine the
that cannot be guaranteed by a simple                                                        concentrations of particles or microbe-
                                            Equation 1
air supply rate specification which                                                          carrying particles (MCPs) in cleanroom
provides the required airborne                                                               air as the particle concentration (a)
contamination in the steady-state                                                            builds up when activity starts, (b)
                                            Where, n = recovery rate, t is the time
condition.                                                                                   remains relatively steady during
                                            elapsed between the first and second
                                                                                             manufacturing, or (c) decays when
22 Clean Air and Containment Review | Issue 26 | April 2016                                        www.cleanairandcontainment.com
                                                                                                                               Main feature
activity stops. The decay equation can                       Or, when logarithms to the base 10         time of between 15 and 20 minutes is
be used to determine the air change rate                  are used,                                     given in the EU GGMP as a ‘guidance’
required to satisfy the EU GGMP ‘clean                                                                  time but 15 minutes is used as it is the
                                                          Equation 5
up’ requirements, or another specified                                                                  most stringent requirement. Equation 5
recovery time or recovery rate of                                                                       is used, as follows, to calculate the
particles measured by the ISO 14644-3                                                                   required air changes per hour.
recovery test methods.
                                                          It is interesting to note that the right
                                                          hand side of Equations 1 and 5 are
Decay and recovery rate equations
                                                          identical, and therefore the recovery
When people leave a cleanroom and
                                                          rate (n) is equal to the air change rate
machinery is turned off, the concentration                                                                  If the same calculations are carried
                                                          (N) at the test location.
of particles in the cleanroom air will                                                                  out for an EU GGMP Grade C room,
                                                               Equations 4 and 5 can be used to
decay. Similarly, when the introduction                                                                 where the maximum ‘operational’
                                                          calculate the room air change rates (N)
of test particles is stopped during the                                                                 concentration is 3,520,000/m3, the ‘at
                                                          required by a cleanroom to comply with
ISO 14644-3 recovery tests, there will be                                                               rest’ condition is 352000/m3, and a
                                                          the EU GGMP, or other recovery times
a decay of particles over time. These                                                                   clean-up time assumed to be 15 minutes,
                                                          or rates. How this is done is illustrated
decays occur in an exponential way that                                                                 the required air change rate per hour is 9.2.
                                                          by the following example, which calculates
is predicted by the Equation 2, and in                                                                      The air change rates per hour obtained
                                                          the air change rate for EU GGMP Grade
the manner shown in Figure 1.                                                                           for Grade B and C cleanrooms of 18.4
                                                          B and C cleanrooms, and can be used
                                                                                                        and 9.2, respectively, are applicable
Equation 2                                                for all Grade B and Grade C cleanrooms
                                                                                                        to all cleanrooms of the same grade,
                                                          as long as air mixing is effective.
                                                                                                        although only if perfect air mixing
Where, C = airborne concentration                                                                       is achieved throughout the cleanroom.
                                                          Calculating air change rates to
of particles after a given decay time,                                                                  The next section of this article discusses
                                                          comply with the EU GGMP clean-
CO = initial airborne concentration                                                                     how the result should be modified for
                                                          up requirements
of particles, N = room air change rate,                                                                 situations where good air mixing is
                                                          An EU GGMP Grade B cleanroom is
t = decay time                                                                                          not achieved and there may be less air
                                                          being designed with an air supply rate
    It is important to note that in Equation                                                            supply at the test location.
                                                          of 3.33 m3/s, and the question to be
2 it is the ‘air change rate’ that affects
                                                          answered is whether this air supply
the decay rate and not the ‘air supply rate’.                                                           Consideration of ventilation
                                                          is sufficient to achieve the clean-up
This is different from the steady-state                                                                 effectiveness of cleanrooms
                                                          requirements given in EU GGMP for a
condition, where the particle concentration                                                             If efficient air diffusers are used to
                                                          Grade B cleanroom. The cleanroom has
in the operational condition during                                                                     supply filtered air to a cleanroom, and
                                                          a floor area of 10m x10m and is 3m high
manufacture is determined by the air                                                                    the room air is extracted at low-level
                                                          i.e. the air volume is 300m3, and the air
supply rate. The air change rate and                                                                    exhausts around the cleanroom, then,
                                                          change rate is therefore 40 air changes
the air supply rate are related as shown                                                                as shown by Whyte et al (2014) and
                                                          per hour. According to the EU GGMP,
below.                                                                                                  Lenegan (2014) there will be good air
                                                          the cleanroom should have a maximum
                                                                                                        mixing between supply and cleanroom
Equation 3                                                concentration during operation of
                                                                                                        air. However, if air mixing is not perfect,
                                                          particles *0.5µm of 352,000/m3, and this
                                                                                                        then locations in the cleanroom will
                                                          concentration is taken as the ‘worst
                                                                                                        receive less clean air than average and,
    If Equation 2 is rearranged, the                      case’ initial concentration after activity
                                                                                                        at that location, the decay of airborne
following equation is obtained                            stops. The particle concentration given
                                                                                                        particles will be slower than required.
                                                          in the EU GGMP for particles *0.5µm in
Equation 4                                                                                                   The ventilation effectiveness at a
                                                          the ‘at rest’ condition is 3520/m3, which
                                                                                                        location in a cleanroom can be determined
                                                          is the concentration that must be achieved
                                                                                                        by measuring the air change rate at the
                                                          at the end of the clean-up test. A recovery
                                                                                                        test location and comparing it to the
                                                                                                        overall cleanroom average (Whyte et al,
                      ϰϬϬϬϬϬ
                                                                                                        2014). The ratio of the air change rate
                      ϯϱϬϬϬϬ                                                                            at the test location to the overall
                      ϯϬϬϬϬϬ                                                                            cleanroom average is called the Air
                                                                                                        Change Effectiveness (ACE) index.
ŽŶĐĞŶƚƌĂƚŝŽŶ;ͬŵϯͿ
                      ϮϱϬϬϬϬ
                      ϮϬϬϬϬϬ                                                                            It is calculated as follows.
                      ϭϱϬϬϬϬ
                      ϭϬϬϬϬϬ
                                                                                                           If the air mixing is perfect, the ACE
                       ϱϬϬϬϬ
                                                                                                        index will be 1 but if the test location
                           Ϭ
                               Ϭ   ϭϬϬ   ϮϬϬ               ϯϬϬ          ϰϬϬ         ϱϬϬ
                                                                                                        receives more clean air, the ACE index
                                               dŝŵĞ;ƐͿ                                                 will be higher than 1. Locations that
Figure 1 – Decay of small particles in a non-unidirectional cleanroom                                   receive less clean air will have an ACE
supplied with 40 air changes per hour                                                                   index lower than 1. When the ACE
www.cleanairandcontainment.com                                                     Clean Air and Containment Review | Issue 26 | April 2016 23
Main feature
index is less than the room average i.e.       correct ‘clean-up’ performance. The           requirements, or may specify a required
 1, the air change rate will have to be        correct air supply rate will be that          particle decay in terms of recovery time
increased to achieve the required              which is needed to provide for the most       or recovery rate. Where the specification
clean-up, recovery time or recovery rate       demanding of the four parameters.             differs from that of the EU GGMP,
at the location under consideration.           It has been previously difficult to           Equations 4 or 5 can be used to calculate
    It has been shown in a previous            calculate the air supply rate needed for      the required air change rate, and an
section of this article that the recovery      the clean-up requirements of Annex 1 of       example of how this is carried out is
rate (n) is the same as the air change         the EU GGMP, or another recovery rate         given in this article.
rate (N) at the test location, and this fact   or time. This article describes a method
can be used to obtain the ACE index.           to calculate the clean-up requirement.        References
The decay of test particles introduced             If the cleanroom has to comply with       1. Lenegan N (2014). Diffuser
into the cleanroom can be used to              the EU GGMP and be capable of                    performance in cleanrooms. Clean
obtain the recovery rate, which is the         reducing the airborne concentration in           Air and Containment Review, Issue
same as the air change rate at the test        a Grade B cleanroom by a 100 fold in 15          18, pp8-14.
location. The recovery rate (air change        minutes, then, if there is perfect mixing
                                                                                             2. Whyte W, Whyte WM and Eaton T
rate) at the location can then be              of supply and room air, an air change
                                                                                                (2012). The application of the
compared to the overall air change rate        rate per hour of 18.4 is sufficient. If the
                                                                                                ventilation equations to cleanrooms:
of the cleanroom and the ACE index             cleanroom is a Grade C, an air change
                                                                                                Part 1; The equations. Clean Air
obtained. Investigations carried out by        rate per hour of 9.2 is required. These
                                                                                                and Containment Review, Issue 12,
Whyte et al (2014) showed that in              two air change rate assume that the
                                                                                                pp4-8.
non-unidirectional airflow cleanrooms,         supply and room air are perfectly mixed
with effective air diffusers fitted, the       and that no location within the               3. Whyte W Ward S Whyte WM and
ACE index is unlikely to be less than 0.7.     cleanroom receives less clean air than           Eaton T (2014). Decay of airborne
An ACE index of 0.7 can therefore be           other location. Good air mixing can              contamination and ventilation
used to compensate for lower air change        be achieved by means of efficient air            effectiveness of cleanrooms.
rates that might occur at some locations       diffusers and low level extracts around          International Journal of Ventilation,
in this type of cleanroom.                     the cleanroom. Poor air mixing will              13(3), pp211-219.
    The air change rate required to            require more air to be supplied to
                                                                                             4. ISO 14644-3: 2005. Cleanrooms and
produce the correct ‘clean up’ in an EU        the cleanroom but when efficient air
                                                                                                associated controlled environments.
GGMP Grade B cleanroom with perfect            diffusers filters and low level extracts
                                                                                                Part 3: International Organization
air mixing was previously calculated           are used, an ACE index of 0.7 will
                                                                                                for Standardization, Geneva,
to be 18.4/h. Applying an ACE index            compensate for non-uniform air mixing.
                                                                                                Switzerland.
correction factor of 0.7, the minimum          This will result in a required increased
air change rate per hour to ensure the         air change rate for an EU GGMP Grade          5. EU GGMP (2008). The rules
correct clean-up should be increased           B cleanroom of 27 per hour and for a             governing medicinal products in the
from 18.4 to 26.3. For a Grade C               Grade C cleanroom 13 per hour.                   European Union –Volume 4 -EU
cleanroom, where a 10 fold reduction               The calculations in the previous             guidelines to good manufacturing
within 15 minutes is required, the air         paragraph assume the airborne                    practice – medicinal products for
change rate per hour should be                 concentration during operational                 human and veterinary use – Annex 1
increased from 9.2 to 13.                      conditions is the maximum acceptable             –Manufacture of sterile medicinal
    The air supply rate should now be          by the EU GGMP, and the shortest                 products. European Commission,
checked in the example to make sure            decay time of 15 minutes. However,               Brussels.
that it is sufficient. In the example, an      it would be unusual to find that the
air supply rate of 3.33m3/s, which is          airborne concentration in the operational
                                                                                               Full biographical notes for
equivalent to an air change rate of 40         condition was as high as the maximum
                                                                                               W (Bill) Whyte are on page 10.
air changes per hour, was thought to           allowed by the EU GGMP and, therefore,
be appropriate. This is greater than the       the required drop in particle concentration
                                                                                               Tim Eaton, B.Sc. (chemistry), is
required air changes for the clean-up,         would be less than 100-fold. This would
                                                                                               Sterile Manufacturing Specialist at
and the proposed air supply rate is            require a lower air change e.g. a 10 fold
                                                                                               AstraZeneca. His full biographical
therefore sufficient.                          drop instead of a 100 fold would half the
                                                                                               notes may be found in CACR20
                                               air change rate. Similarly, if a ‘clean up’
                                                                                               (October 2014) on page 9.
Discussion and Conclusions                     time of 20 minutes instead of 15 minutes
It is necessary when designing non-            is acceptable, then the air change rate
                                                                                               Nigel Lenegan, B.Eng., C.Eng.,
unidirectional airflow cleanrooms to           can also be reduced. The air change rate
                                                                                               MCIBSE, is founder and managing
ensure that the air supply rate will be        for these less stringent requirements can
                                                                                               director of Energy & Carbon
sufficient to (a) achieve the correct          be calculated by the method described
                                                                                               Reduction Solutions. His full
particle concentration in the cleanroom        in this article.
                                                                                               biographical notes may be found
in the steady-state condition, (b) control         Cleanrooms that are not regulated
                                                                                               in CACR18 on page 13.
the heat gains in the cleanroom (c)            by the EU GGMP may have similar
compensate for room air leakage and            clean-up requirements to those that are
process air exhaust, and (d) provide the       regulated, or may have different clean-up
24   Clean Air and Containment Review | Issue 26 | April 2016                                      www.cleanairandcontainment.com