Valve Symbols Pipe and Fitting Symbols: Double Line Single Line

This document provides mechanical piping legend and notes including: 1. Pipe and fitting symbols for double line, single line, valves, and miscellaneous piping components. 2. General piping notes regarding existing utilities, minimum pipe cover, grades, and fitting sizes. 3. Notes specifying end connections for single line fittings and providing thrust restraint and control rods.

Uploaded by

Priadi Kausar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views1 page

Valve Symbols Pipe and Fitting Symbols: Double Line Single Line

This document provides mechanical piping legend and notes including: 1. Pipe and fitting symbols for double line, single line, valves, and miscellaneous piping components. 2. General piping notes regarding existing utilities, minimum pipe cover, grades, and fitting sizes. 3. Notes specifying end connections for single line fittings and providing thrust restraint and control rods.

Uploaded by

Priadi Kausar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

1 2 3 4 5 6

c CH2M HILL 2004. ALL RIGHTS RESERVED.


PIPE AND FITTING SYMBOLS
DOUBLE LINE SINGLE LINE NOTES: VALVE SYMBOLS This document is
MECHANICAL LEGEND AND NOTES released for
1. ONLY FLANGED END CONNECTIONS ARE SHOWN HERE FOR DOUBLE LINE FITTINGS. REVIEW, under
GENERAL PIPING NOTES FITTINGS WITH OTHER END PATTERNS ARE SHOWN SIMILARLY ON THE CONSTRUCTION the authority of
EXISTING PIPE GATE
DRAWINGS. ALSO SEE PIPING SPECIFICATIONS.
Stephen A. Bianchetta
1. UNDERGROUND UTILITIES SHOWN ARE TAKEN FROM EXISTING RECORDS AND ARE SHOWN 2. SYMBOLS SHOWN HERE FOR SINGLE LINE FITTINGS ARE GENERIC ONLY. REFER TO PIPING P.E. 89204
FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. THE CONTRACTOR SHALL CONTACT ALL SPECIFICATIONS FOR SPECIFIC END CONNECTIONS FOR SINGLE LINE PIPE AND FITTINGS. on, August 28, 2006
NEW PIPE
UTILITY OWNERS AND CONFIRM LOCATIONS OF UTILITIES AT LEAST 48 HOURS BEFORE BUTTERFLY
3. PROVIDE THRUST RESTRAINT FOR ALL FLEXIBLE COUPLINGS, FCA’S, ETC. AS SPECIFIED.
BEGINNING CONSTRUCTION. THE CONTRACTOR SHALL ACCURATELY LOCATE AND
UNCOVER ALL EXISTING UTILITIES BEFORE BEGINNING CONSTRUCTION. ANY DAMAGE 4. PROVIDE CONTROL RODS FOR ALL BELLOWS EXPANSION JOINTS AND COUPLINGS AS SPECIFIED.
EXISTING PIPE TO BE ABANDONED GLOBE

APVD
RESULTING FROM THE CONTRACTOR’S OPERATIONS SHALL BE REPAIRED AT THE
A
CONTRACTOR’S EXPENSE. WHERE CROSSING OF EXISTING UTILITIES OCCUR, PROVIDE BALL
12" MINIMUM CLEARANCE EXCEPT WATER MAINS SHALL BE 18". CROSS UNDER ALL WATER EXISTING PIPE TO BE REMOVED
MAINS WHERE NOT POSSIBLE TO PROVIDE 16" CLEARANCE. MISCELLANEOUS PIPING SYMBOLS

BY
2. MINIMUM COVER OVER PIPING SHALL BE 3’-0", BELOW FINISHED GRADE.

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
UNLESS OTHERWISE SHOWN OR NOTED. WELDED JOINT SEATING PORT

CH2M HILL AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CH2MHILL.
STRAINER
3. PROVIDE MINIMUM PIPE COVER, AS SPECIFIED. GENERALLY LAY PIPE TO UNIFORM GRADES

APVD
ECCENTRIC PLUG
BETWEEN THE ELEVATIONS SHOWN, UNLESS OTHERWISE APPROVED. IN SOME CASES,
GROOVED END JOINT
EXISTING CONDITIONS PROHIBIT UNIFORM GRADES BETWEEN THE ELEVATIONS SHOWN, SIGHT GLASS
PLUG OR COCK
AND FIELD ADJUSTMENTS TO UNIFORM GRADES ARE REQUIRED AS APPROVED.

S BIANCHETTA
4. SIZE OF FITTINGS SHOWN ON PLANS SHALL CORRESPOND TO ADJACENT STRAIGHT RUN FLANGED JOINT GAUGE WITH COCK
OF PIPE, UNLESS OTHERWISE INDICATED. TYPE OF JOINT AND FITTING MATERIAL SHALL BE
THE SAME AS SHOWN FOR ADJACENT STRAIGHT RUN OF PIPE.
BACKFLOW PREVENTER
5. LOCATION AND NUMBER OF PIPE HANGERS AND PIPE SUPPORTS SHOWN IS ONLY MECHANICAL JOINT
APPROXIMATE. CONTRACTOR SHALL DESIGN SUPPORTS AS SPECIFIED.

REVISION
6. ALL JOINTS SHALL BE WATERTIGHT. WALL PIPES SHALL BE USED WHEREVER REDUCER

CHK
PIPING PASSES FROM A STRUCTURE TO BACKFILL. BELL & SPIGOT JOINT (LEADED) SWING CHECK

7. ALL FLEXIBLE CONNECTORS AND FLANGED COUPLING ADAPTERS SHALL BE PROVIDED WITH FLEXIBLE HOSE BALL CHECK

K TROSPER
THRUST TIES AND ANCHORS, UNLESS OTHERWISE NOTED. THRUST PROTECTION
HUB & SPIGOT JOINT
SHALL BE ADEQUATE FOR TEST PRESSURES SPECIFIED.
HOSE VALVE (HV- X) OR (V-X)
(RUBBER GASKET)
8. SYMBOLS, LEGENDS, AND PIPE USE IDENTIFICATIONS SHOWN SHALL BE FOLLOWED X = NO. IN SPECS
THROUGHOUT THE PLANS, WHEREVER APPLICABLE. NOT ALL OF THE VARIOUS PIPING
BALL JOINT
COMPONENTS ARE NECESSARILY USED IN THE PROJECT. S SAMPLE
9. ALL BURIED PIPING SPECIFIED TO BE PRESSURE TESTED, EXCEPT FLANGED, WELDED, OR ADAPTER SIDE GATE SYMBOLS
SCREWED PIPING, SHALL BE PROVIDED WITH THRUST RESTRAINT. THRUST RESTRAINT FOR GROOVED END ADAPTER FLANGE

DR
NEW PIPING SHALL BE AS SPECIFIED IN SECTION 15200.
B 10. NUMBER AND LOCATION OF UNIONS SHOWN ON PLANS IS ONLY APPROXIMATE. PROVIDE
ELEVATION VIEW PLAN VIEW PRESSURE RELIEF

K TROSPER
ALL UNIONS NECESSARY IN THE OPINION OF THE ENGINEER TO FACILITATE CONVENIENT FLANGED COUPLING ADAPTER
REMOVAL OF VALVES AND MECHANICAL EQUIPMENT.
AIR AND/OR VACUUM RELEASE
11. WHERE A GROOVED END COUPLING IS SHOWN, IT SHALL BE THE RIGID JOINT TYPE, UNLESS

DATE
SLUICE
OTHERWISE SPECIFIED. WHERE A FLANGED COUPLING ADAPTER IS SHOWN, A STANDARD FLEXIBLE COUPLING
REGULATED SIDE
FLANGE SHALL BE JOINED TO THE COUPLING ADAPTER.

DSGN
PRESSURE CONTROL

NO.
METAL BELLOWS EXP JOINT BUTTERFLY
REGULATED SIDE

ELASTOMER BELLOWS EXP JOINT PRESSURE REGULATOR

WASTEWATER COLLECTION SYSTEM

AND LIFT STATION IMPROVEMENTS


ELBOW UP ACTUATOR SYMBOLS
YARD PIPING LEGEND
VALVE DESIGNATIONS

CITY OF PHARR

PHARR, TEXAS
E OR M ELECTRIC MOTOR S SOLENOID
ELBOW DOWN
DOUBLE LINE SINGLE LINE
MANUAL VALVES AND CHECK VALVES
EXISTING PIPE TEE UP

NEW PIPE TEE DOWN

REUSE OF DOCUMENTS:
8" - V 500
SIZE OF VALVE
C EXISTING PIPE TO BE ABANDONED LATERAL UP
PIPING DESIGNATION VALVE DESIGNATION
EXAMPLE:
4" W1 VALVE TYPE, SEE
EXISTING PIPE TO BE REMOVED LATERAL DOWN
SPECIFICATION
SECTION 15202

NEW EXISTING CONCENTRIC REDUCER 4" W1


CONTROL VALVES
NON-FREEZE HOSE VALVE (V-X)
X = NO. IN SPECIFICATIONS
FLOWSTREAM IDENTIFICATION FCV

MECHANICAL LEGEND
ECCENTRIC REDUCER (SEE INSTRUMENTATION AND CONTROL LEGEND)
NON-FREEZE HOSE VALVE X
PIPE DIAMETER
WITH HOSE RACK (V-X)
X = NO. IN SPECIFICATIONS REDUCING BUSHING
FLOW DIRECTION

VALVE SYMBOL

GENERAL
GATE VALVE UNION
* BUBBLE WITH FUNCTION AND THE
BUTTERFLY VALVE CAP TAG NUMBER DESIGNATION
(SEE I&C LEGEND FOR TAGGING INSTRUMENT IDENTIFICATION)
SEATING
FLOW
PORT
ECCENTRIC PLUG VALVE
ANCHOR

INDICATOR POST VALVE

ELBOW, 90 DEGREE
FIRE HYDRANT

D CATHODIC PROTECTION TEST


CROSS
STATION

CATHODIC PROTECTION ANODE


TEE

NOTES: VERIFY SCALE

BAR IS ONE INCH ON


1. EXISTING PIPING AND EQUIPMENT IS SHOWN EITHER
ELBOW, 45 DEGREE ORIGINAL DRAWING.
LIGHT-LINED, AND/OR SCREENEDAND /OR NOTED AS 0 1"
EXISTING. NEW PIPING AND EQUIPMENT IS SHOWN
HEAVY-LINED. DATE AUGUST 2006

PROJ 323362
LATERAL
DWG G-6

SHEET 6

FILENAME: 00ng007d_323362.dgn PLOT DATE: 8/29/2006 PLOT TIME: 9:10:48 AM