An ISO 9001-2000 Company

Cheetah Xi™ Enclosure


Installation Instructions

DESCRIPTION
The Cheetah Xi™ enclosure (See Exhibit 1) is made
of 18 gauge steel with a baked on enamel finish (red
or black). It is designed so that it can be surface or
flush mounted. Numerous conduit knockouts are
provided on all four sides of the enclosure to
facilitate easy wiring access into the enclosure. The
knockouts allow connection of either ½” or ¾”
conduit. The removable exterior door is hinged on
the left side of the back-box and is equipped with a
key-lock to prevent unauthorized access to system
components.
Threaded press-studs are supplied in enclosure
back-box for easy installation of the following system
components (sold separately):
A. Cheetah Xi™ Controller (qty. 1)
B. AC Power Transformer (qty. 1)
C. Bosch FPT-DACT-LC, P/N 10-2528
D. Class A Peripheral Bus Card, P/N 10-2792* Exhibit 1: Enclosure
E. Multi-Interface Module (MIM), P/N 10-2583*
F. Ethernet Module, P/N 10-2627*
G. Two 18 AH batteries (maximum)
SUPPLIED MOUNTING HARDWARE
The following mounting hardware is supplied with
* MIM, Ethernet module and Class A Peripheral Bus
the enclosure for future installation of the electronic
card share a common mounting location. Only one
components. Store hardware inside the enclosure
component can be installed at a time.
after enclosure installation.
See Exhibit 2 for component layout within the
02-12025 Cabinet Keys (qty. 2)
enclosure.
02-12033 Standoff Kit
02-2715 M/F Standoff, .625” (qty. 5)
ENCLOSURE ORDERING
02-12014 Hardware Kit
Part Numbers: 10-2541-c (c: R = Red, B = Black) 4153-142 Lock Washer, #6 (qty. 2)
Weight: 16 lbs. (7.3 kg) empty 02-1361 6-32 Hex Nut (qty. 2)
(door and back box) 02-4992 Ground Wire (qty. 1)
02-4035 Nut and star washer kit
(contains 20 nuts and washers)

® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
While every precaution has been taken during the preparation of this document to ensure the accuracy of its content, Fike assumes no responsibility for errors or omissions.
Fike reserves the right to make changes to the product or this document without notice.
www.fike.com P/N 06-426 Rev. 1 page 1 of 4
ENCLOSURE INSTALLATION
1. The enclosure’s outer door can be removed to
make installation of the back box easier. To

HEARTBEAT
SYS TRBL
LINE 1

LINE 2
remove the outer door, unscrew the hinge
P6
P7

screws located at the top and bottom of the


C P8
enclosure.
2. Determine the quantity and size of conduit to be
P9

attached to the enclosure and remove


P10

appropriate knockouts. Knockouts provide for


P11

attachment of ½” or ¾” conduit. Do not use


conduit knockouts located in the bottom of the
A enclosure if installing batteries.
D
B E
F LNote: Fire Alarm System wiring is classified
as either power-limited or nonpower-limited
per NEC Article 760. All power-limited
wiring must be separated from all nonpower-
limited wiring by a minimum distance of ¼”
G G
(6 mm). Refer to documentation provided
with each electrical component for
designation of power-limited versus
nonpower-limited circuits.
Exhibit 2: Enclosure Layout 3. Mount the enclosure at the selected location.
See Exhibit 3 for enclosure dimensions.
MOUNTING LOCATION Surface Mounting
The following guidelines shall be adhered to when Utilize the four tear-drop openings in the back of
selecting the enclosure mounting location: the back box to secure it to the mounting surface
with suitable anchors.
1. Mount the enclosure on a surface that is
vibration free, clean and dry. Flush Mounting
2. Mount the enclosure in an area that is free from Cut and frame an opening in the wall to fit the
sources of electromagnetic interference and back-box dimensions. Secure the box in place
radio frequency interference; as these are types utilizing the through holes provided on the sides
of problems that could adversely affect the of the back box.
successful operation and useful life of the
electronic equipment housed in the enclosure. iCAUTION
3. Mount the enclosure in an environment with a The enclosure is NOT fire rated. Do not mount
nominal room temperature of 15°-27°C / 60° - on or in a fire rated wall unless wall is properly
80°F, with a relative humidity of 85 percent. framed to maintain specific fire rating.
4. Allow sufficient clearance around the enclosure
4. Reinstall the outer door using existing mounting
to allow the door to swing freely.
hardware.
5. Mount the enclosure at a height that allows easy
5. Connect the outer door grounding wire, as
access to system electronic components for
shown in Exhibit 4, using the hardware provided.
maintenance and service.
Adjust routing of grounding wire as necessary to
allow full movement of outer door. Check for
continuity between door and back box.
6. If the enclosure was ordered with the optional
dead-front panel, refer to the documentation
supplied with the panel for installation
instructions.

® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
P/N 06-426 Rev.1 page 2 of 4 www.fike.com
Exhibit 3: Enclosure Dimensions

® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
www.fike.com P/N 06-426 Rev. 1 page 3 of 4
OUTER DOOR
HINGE SIDE

OUTER DOOR
BACK BOX
LOCK WASHER GROUNDING
HINGE SIDE
P/N 4153-142 STUD
(2 PLACES)

#6-32 LOCK NUT


(2 PLACES) BACK BOX
GROUNDING
STUD

A A

GROUND WIRE (B)


P/N 02-4992

Exhibit 4: Outer Door Ground Wire Installation

® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
P/N 06-426 Rev.1 page 4 of 4 www.fike.com