SCP250 VAR/Power Factor Controller
Class 200 Equipment
                                                                                                              SCP250
                                                                                                          VAR/Power Factor
                                                                                                             Controller
The SCP 250 senses generator output voltage and current, provides an output
signal that is electronically injected into the voltage regulator. When VARs are
controlled, the voltage regulator (or static exciter) changes its output until the
programmed reactive load current is attained. When power factor is controlled,
the regulator changes the excitation until the selected power factor is obtained.
The unit is designed so that the voltage regulator is in total control of generator
excitation until the generator breaker is closed. At breaker closure the SCP 250
assumes excitation control.
The SCP 250 also contains a voltage limiting feature so that in the event utility
power is lost and the peaking generator main breaker remains closed, the
voltage regulator will not go to full or no excitation. Voltage limiting is adjustable
                                                                                                                        APPLICATIONS
between ±10% and ±30% Because the unit is designed for behind-the-panel                                                    Page 2
mounting, provisions are included for remotely locating the VAR/PF switch and
VAR/PF adjust potentiometer.
                            FEATURES                                                                                    SPECIFICATIONS
                                                                                                                            Page 2
• Specifically designed to operate with the standard Basler SR, KR, selected AVCs,
   and SSR regulator series and with Basler SSE static exciter-regulators.
• Front Panel Selection of either VAR or power factor control.
• With P.F. control, reactive load changes automatically when KW load is changed.
• Models suitable for use in generator or synchronous motor applications.                                              INTERCONNECTION
• Solid-state design.                                                                                                      DIAGRAMS
• Does not require use of motor operated control.                                                                            Page 3
• Responds rapidly to system changes.
• Provides system control over wide range of loading conditions.
• Easily calibrated on-site                                                                                            OUTLINE DRAWING
• Accommodates standard voltage sensing inputs.                                                                             Page 4
• Provisions for remote operation.
• Mechanically rugged and compact.
• UL recognized and CSA certified.
                     ADDITIONAL INFORMATION
INSTRUCTION MANUAL
        Request publication 911000099Y
                                                                                                                                   UKR-7
                                                                                                                                    9-03
                                  P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A. 62249 PHONE 618-654-2341 FAX 618-654-2351
SCP250 VAR/Power Factor Controller
                      APPLICATION                                              SPECIFICATIONS
       GENERATOR PEAKING                                           • INPUT POWER:
       On peaking generator applications, the paralleling            Voltage Sensing and Power
       circuit of a voltage regulator presents large changes in      Voltage:
       reactive current when the bus voltage changes by a            120-139.208-240.416-480. 520-600 VAC, ±10%, 60Hz
       relatively small amount. However, the regulator’s ability     100-120, 190-208,380-415,440-500 VAC, 10%, 50Hz
       to compensate for large changes in bus voltage can be         Phase                                         : Single
       exceeded. Two examples serve to illustrate typical            Burden: 25 VA
       problem areas:                                                Current Sensing
         (1) A generator equipped with a voltage regulator           Current:
            adjusted for 4% droop can have a variation in VAR        3-5 Amperes, withstands up to 30 amps for 15 sec.
            (volt amperes reactive) load from 0 to 100% with a       without failure.
            4% decrease in bus voltage. Further decreases in         Phase                                         : Single
            bus voltage would overload the generator.                Burden: 3VA
         (2) An increase in bus voltage can cause leading          • OUTPUT: Normal ±1VDC to ±3VDC
            power factor conditions with the associated danger                  High     ±1VDC to ±9VDC
            of the machine pulling out of synchronization.         • OUTPUT VOLTAGE LIMITING: Adjusts range of
                                                                     output voltage over range shown above.
       To minimize the possibility of either (1) or (2) above      • ACCURACY OF CONTROL:
       occurring, the voltage regulator is often adjusted for        Power Factor: Reactive component of current is
       operation in a “safe” region rather than a region that                proportional to real component within ±5% of
       utilizes the full KVA capability of the generator.                    maximum rated current.
                                                                     VAR: Reactive component of current maintained at
       The SCP 250 VAR/Power Factor Controller regulates                     programmed level within 25% of      maximum
       VAR flow or power factor when operating in parallel with    rated
       another power system. The excitation is adjusted              current.
       automatically to compensate for bus voltage changes.        • TEMPERATURE: Operates within temperature range
       A typical peaking application is illustrated in Figure 1.        of -40°C (-40°F) to +70°C (+158°F).
                                                                   • VIBRATION: Withstands 1.3 Gs from 5 to 26Hz, .036
       The SCP 250 is not for use on single or multiple paral-          D.A. from 26 to 51Hz, and 5 Gs from 52 to 260Hz
       leled generators except when paralleled to an infinite        without damage or degradation of performance.
       grid source. When not paralleled to a utility bus, use      • SHOCK: Withstands 15 Gs in each of three mutually
       Basler regulators with reactive compensation provisions       perpendicular axes.
       for droop and cross current.                                • MOUNTING: Behind-the-panel.
                                                                   • FINISH: Dark brown, lusterless, textured, baked
       SYNCHRONOUS MOTORS                                            enamel.
       On synchronous motor applications the SCP 250 can           • WEIGHT: 5.75 pounds net, 8 pounds shipping.
       be programmed to the desired power factor so that the       • APPLICABLE TO:
       motor power factor is maintained during normal loading        AVC63-12, AVC125-10
       conditions. Also, during transient loading conditions,        SRA, SSR, SR-F, SR-H, and SR-E.
       the power factor controller makes corrective motor field      KR, -FF, and -FFM.
       excitation adjustments and thereby minimizes the              SSE.
       possibility of pole slip. A typical motor application is    Refer to the SCP 250 Instruction Manual 911000099Y
       shown in Figure 2.                                          for specific interconnection data.
       HOW TO ORDER:                                               SAMPLE SPECIFICATION:
       Refer to the following chart to determine your require-     The VAR/Power Factor controller shall be a static
       ments.                                                      device. It shall provide a choice of VAR or Power Factor
                                                                   control. It shall control VAR or Power Factor within ±5%
       When the SCP 250       in a 60 Hertz    in a 50 Hertz       of maximum rated current. Provisions shall be available
       is to be used in       power system,    power system,       for field connection at the basic sensing voltages: 120-
                              order            order
                                                                   139,208-240,416-480, 520-600 VAC +5%, -10%. It shall
       A generator
       application            SCP250 G-60      SCP250 G-50
                                                                   operate over a temperature range of -40°C to +70°C. It
       A motor                                                     shall contain a voltage limiting feature adjustable
       application            SCP250 M-60      SCP250 M-50         between ±10% and ±30% of rated voltage. The VAR/
                                                                   P.F. controller shall be a Basler Model SCP 250.
                                                       SCP250 VAR/Power Factor Controller
      INTERCONNECTION DIAGRAMS
Figure 1 - Typical Interconnection Diagram - Generator Application
  Figure 2 - Typical Interconnection Diagram - Motor Application
                                                                                 7
SCP250 VAR/Power Factor Controller
                                                                OUTLINE DRAWING
                                                                     Figure 3- Outline Drawing
       Note: These drawings are NOT intended for installation purposes.
       Refer to Instruction Manual received with equipment for proper installation drawings.
       All drawings and data subject to change without notice.
       All dimensions in inches (millimeters)
                             ISO           em
                                       Syst
                        Basler
                  lity
                                   ®
               Qua R e g
                         i st e r e d
                Highland, IL: ISO 9001
             Wasselonne, France: ISO 9001
                 Taylor, TX: ISO 9001
      P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE   Route 143, Box 269, Highland, Illinois U.S.A. 62249   1300 North Zhongshan Road, Wujiang Economic Development Zone
        Tel +33 3.88.87.1010 Fax +33 3.88.87.0808        Tel +1 618.654.2341 Fax +1 618.654.2351                         Suzhou, Jiangsu Province, PRC 215200
                 e-mail: [email protected]                      e-mail: [email protected]                        Tel +86(0)512 6346 1730 Fax +86(0)512 6346 1760
                                                                          www.basler.com                                      e-mail: [email protected]