1. The study models the transformation of Germany's electricity load curve between 2008-2050 under reference and decarbonization scenarios. 2. It uses a partial decomposition approach to distinguish the load curves of relevant applications and scales them according to projected changes. 3. Results of the FORECAST model show electricity demand increases 178% by 2050 in the reference scenario but decreases 1% in the decarbonization scenario, where technologies like electric mobility and heat pumps contribute significantly more to load.

Uploaded by

tania__star
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views17 pages

German Curve

1. The study models the transformation of Germany's electricity load curve between 2008-2050 under reference and decarbonization scenarios. 2. It uses a partial decomposition approach to distinguish the load curves of relevant applications and scales them according to projected changes. 3. Results of the FORECAST model show electricity demand increases 178% by 2050 in the reference scenario but decreases 1% in the decarbonization scenario, where technologies like electric mobility and heat pumps contribute significantly more to load.

Uploaded by

tania__star
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

The German load curve in 2050:

structural changes through energy


e ff i c i e n c y m e a s u r e s a n d t h e i r i m p a c t s o n
the electricity supply side

Tobias Boßmann, Rainer Elsland, Fridolin Lickert, Martin Wietschel


Fraunhofer Institute for Systems and Innovation Research ISI, Karlsruhe, Germany
eceee summer study 2013, 07th of June 2013
2

Motivation
Historical load curves

•  What will the electricity load curve look like in the future, assuming uncontrolled
Asssessment
electricity consumption of the
behaviour (i.e.mean load profile of
no demand-side the 3rd
management)?
Wednesday of every month in summer time between
•  How can we model the future transformation of the load curve?
1996 and 2012
•  What are the impacts of transformations in the load curve on the dispatch of power
plants?
3

Agenda

1.  Motivation
2.  Methodology
3.  Case study
4.  Conclusion
5.  Critical appraisal and outlook
4

Methodology
Model environment
•  Socio-economic drivers •  Existing power plants
•  Energy carrier prices •  Renewable capacities
•  Technology data •  bottom-up simulation model •  Energy carrier prices
•  available for EU27+3
•  Emission factors •  Weather time series
•  projection until the year 2050
•  Energy balances

FORECAS PowerACE
T Europe

•  agent-based electricity
•  Annual final energy system model •  Power plant and grid
demand •  hourly calculation investment and dispatch
•  Energy saving potentials •  available for EU27+2 + •  Emissions
•  Emissions MENA region •  Electricity prices
•  Curtailment
5

Methodology
eLOAD: energy LOad Curve ADjustment
tool
•  Socio-economic drivers •  Historical load curves •  Conventional power
•  Energy carrier prices •  Appliance specific load plant capacities
•  Technology data profiles •  Renewable capacities
•  Emission factors •  Temperature time series •  Energy carrier prices
•  Energy balances •  Weather time series

FORECAS Electricity System


eLOAD PowerACE
T demand load curve

•  Annual final energy •  Appliance specific load •  Power plant dispatch


demand curves •  Emissions
•  Energy saving potentials •  Electricity prices
•  Emissions •  Curtailment
6

M e1 t h o d o l o g y
Distinction between relevant and less relevant applications according to ratio of electricity
P a r tdemand
i a l dincrease/decrease
e c o m p ocompared
s i t i otontheaoverall
p pelectricity
r o a cdemand
h ( Pin the
DA base) year
Relevant applications Less relevant
2 applications
Decomposition of the system load curve into load curves for relevant applications
INPUT: Annual electricity demand projection distinguished by country, sector, and
application,
Base year

remaining
technology (results load
from FORECAST model)

3 4
Scaling of application specific Database: Scaling of remaining load
load curves according to -  Load profiles acc. to cumulated evolution
evolution between base and -  Historic load curves of less relevant applications
projection year -  Temperature time between base and projection
series year
5
Projection year

Reaggregation of the system load curve

OUTPUT: Electricity load curve for a specific projection year and country
(serves as input for PowerACE model)
7

Methodology
Load profiles
Load profiles originate from
•  Internal data base
•  Generation from load measurements in
the framework of field tests
•  Neural Networks
•  Conditional Demand Analysis
•  Publicly available profiles
•  Building simulation models
•  Norms/standards
•  Time organisation model
•  Conclusion by analogy

Source: own calculations based on REMODECE


project
8

Case study
Scenario setting
Setting: Germany, 2008-2050
Scenarios:
•  Reference scenario
•  Decarbonisation scenario
Main drivers (based on Energy Roadmap 2050 of European Commission)
•  GDP: +1.1% p.a.
•  Population: -12% between 2008 and 2050

Scaling Partial decomposition


Approach (SCA) approach (PDA)
Reference
X X
Scenario (RS)
Decarbonisation
X
scenario (DS)
9

Case study
Scenario setting
Demand side (=> FORECAST model)
•  Reference scenario
•  Business-as-usual
•  Energy carrier prices further increase until 2050
•  Decarbonisation scenario
•  Intensified diffusion of energy saving options
•  Increased use of recycling products
•  Increased refurbishment rate
•  Comprehensive introduction of new technologies
•  Energy carrier prices: further increase until 2030, then decline

Hourly load (=> eLOAD)


•  No demand-side management
10

Case study
Results of FORECAST model
Germany

+178%
-20% ∆a,abs [TWh] |∆a,abs| /∑| ∆|a,abs| /dtotal,
-9%
Reference

∆a,abs| 2050

+1% E-Mobility +31 15% 5%


∑ = +2%
compared to 2008
Heat pumps +14 8% 3%
-5%
Storage -8 4% 1%
heater
Decarbonisation

+402% ∆a,abs [TWh] |∆a,abs| /∑| ∆|a,abs| /dtotal,


-20% ∆a,abs| 2050
-23%
E-Mobility +69 22% 12%
∑ = -1% -8%
compared to 2008 Heat pumps +41 14% 8%

-14% Storage -12 4% 2%


heater
11

Case study
Results from eLOAD

RS-SCA RS-PDA DS-PDA


Maximum load 90 GW 97 GW 103 GW
Minimum load 39 GW 35 GW 34 GW
Capacity factor 72% 66% 62%
Ramp rate factor 0.58% 0.70% 0.78%
12

Case study
Results from eLOAD
Variation of daily load distribution
RS-SCA vs. RS-PDA RS-PDA vs. DS-PDA
(impacts from new approach) (impacts from scenario
settings)
13

Case study
Scenario setting
Supply side (=> PowerACE model)
•  No distinction between the two scenarios => ceteris paribus
•  Total installed capacity: 255 GW
•  Whereof 90 GW conventional
•  Whereof 165 GW RES
•  Total RES generation: 400 TWh
14

Case study
Results from PowerACE-Europe
15

Case study
Results from PowerACE-Europe

RS-SCA
Total electricity demand 564 TWh
Lignite CCS 74 TWh / 5480 h
Hard coal CCS 80 TWh / 4520 h
Gas CCS 19 TWh / 2600 h
Gas without CCS 9 TWh / 510 h
Oil 12 TWh / 510 h
Import -18 TWh
RES 403 TWh / 2440 h
Total input into pump storage 16 TWh
Hrs. with neg. residual load 1670
Share of curtailed RES 3%
16

Conclusion

•  Efficiency measures can limit further growth of electricity demand


•  Savings are erased electrification of transport and heat generation sector

•  Applying the PDA, the future load curve will experience a thorough deformation
•  a rise in peak demand as well as peak load hours and an increase in volatility
(compared to today’s shape and the estimation via the scaling approach)
•  if no additional strategies are undertaken (e.g. demand response, grid
extension, storage capacities) use of peak power plants and curtailment of RES
will increase
•  electric vehicles and heat pumps are particularly suitable for load shifting

Outlook
•  Integration of demand-side management
•  Consideration of impacts of efficiency measures on load profile
17

Thank you for your attention!