The document provides tables and formulas for determining the installation distance (d) and penetration distance (p) of air terminals for lightning protection based on the height (h) and radius (r) of the air terminal and the distance between down-conductors. It specifies four levels of protection, with Level I being the minimum requirement and Level IV providing the greatest level of protection. The tables provide the maximum allowable penetration distance p for different air terminal heights and radii at each protection level.

Uploaded by

Chen Mark LC
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
215 views3 pages

Air Terminal Install Distance Table - 20140306revised

The document provides tables and formulas for determining the installation distance (d) and penetration distance (p) of air terminals for lightning protection based on the height (h) and radius (r) of the air terminal and the distance between down-conductors. It specifies four levels of protection, with Level I being the minimum requirement and Level IV providing the greatest level of protection. The tables provide the maximum allowable penetration distance p for different air terminal heights and radii at each protection level.

Uploaded by

Chen Mark LC
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

According to IEC62305-3_Edition 2.

0_2010-12
AIR TERMINAL (h) Protection Method
LEVEL I LEVEL II
Rolling sphere radius r : 20 M Rolling sphere radius r : 30 M
Mesh size Wm : 5 X 5 Mesh size Wm : 10 X 10
LENGTH METRIC Down-conductors distance : 10 M Down-conductors distance : 10 M
(INCHES) (M) (TYP.) (TYP.)
Air Terminal Install Distance (d) (M)
p=h p=1/2 h p=h p=1/2 h
10 0.25 6.35 4.50 7.79 5.52
12 0.30 6.96 4.93 8.53 6.04
15 0.38 7.77 5.51 9.53 6.75
18 0.46 8.50 6.03 10.44 7.39
24 0.61 9.80 6.96 12.03 8.53
30 0.76 10.94 7.77 13.44 9.53
36 0.91 11.96 8.50 14.70 10.44
48 1.22 13.75 9.80 16.93 12.03

d = 2(2rh - h2)1/2
p = r – [r2 – (d / 2)2]1/2 The penetration distance p should be less than ht minus the height of objects to be protected
I II III IV
Penetraion Distance p 1.2187759984 1.2190379765 1.2194566617 1.2194013726
Radius of the rolling sphere r 20 30 45 60
Distance between two rods d 13.75 16.93 20.81 24.07
Height of the air-terminal h

variable value
Protection Method
LEVEL III LEVEL IV
Rolling sphere radius r : 45 M Rolling sphere radius r : 60 M
Mesh size Wm : 15 X 15 Mesh size Wm : 20 X 20
Down-conductors distance : 15 M Down-conductors distance : 20 M
(TYP.) (TYP.)
minal Install Distance (d) (M)
p=h p=1/2 h p=h p=1/2 h
9.55 6.76 11.03 7.80
10.46 7.40 12.08 8.55
11.69 8.27 13.50 9.55
12.80 9.06 14.79 10.47
14.76 10.46 17.06 12.08
16.49 11.69 19.06 13.50
18.05 12.80 20.87 14.79
20.81 14.76 24.07 17.06