Design Creteria Varation Order

This document outlines design criteria variations for a detergent factory project in Erbil, Iraq. It specifies dead, live, snow, and wind loads based on standards like IBC and UFC 3-301-01. Dead loads include loads from sandwich panels, photovoltaic panels, and other sources. Live loads are specified as 0.25 kn/m2. Snow loads are set at 0.4 kn/m2 maximum based on location. Wind speed is set at 160 km/h resulting in 0.55 kn/m2 windward pressure. It also changes the bay spacing from 7m to 6m for storage hangers to reduce weight. Sandwich panel specifications are provided.

Uploaded by

Hayman Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
185 views1 page

Design Creteria Varation Order

This document outlines design criteria variations for a detergent factory project in Erbil, Iraq. It specifies dead, live, snow, and wind loads based on standards like IBC and UFC 3-301-01. Dead loads include loads from sandwich panels, photovoltaic panels, and other sources. Live loads are specified as 0.25 kn/m2. Snow loads are set at 0.4 kn/m2 maximum based on location. Wind speed is set at 160 km/h resulting in 0.55 kn/m2 windward pressure. It also changes the bay spacing from 7m to 6m for storage hangers to reduce weight. Sandwich panel specifications are provided.

Uploaded by

Hayman Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Design criteria variation order

Client: Sahel Erbil co.


Project: Detergent factory
Location: IRAQ-Erbil

According to the tender concept design loads we went to explain the loads that we prefer to use as
the following:
1. loads
 Dead loads:
 Sandwich panel loads = 0.09 kn/m2
 photovoltaic panels load = 0.2 kn/m2
 Other dead loads = 0.0.11 kn/m2
 Live loads:
according to IBC standard it the live loads (All roof surfaces subject to maintenance workers)
so, the live load will be 0.25 kn/m2.
 Snow loads:
Here in Iraq there is no standards or codes to determine carefully the snow loads, but according to
the location of the project which has Hight about 375 m from the sea level the maximum recognized snow
thickness is about 20 cm and by taking the density of the non-iced snow with the value 1.5 kn/m3 so the total
load will be 0.3 kn/m2 so we can but it 0.4 kn/m2 for maximum case.
Here in erbil we designed many projects fo different clients such as: U.S army, GKPI, DNO….
They all ordered the snow load to be not more than 0.4 kn/m2
 Wind speed:
According to UFC 3-301-01 we can take the design wind speed with 160 km/h.
That lead to the windward faces pressure about 0.55 kn/m2
2. Bays spacing
In addition to the loads we want to change the bays spacing from 7 m to 6 m for the storage hanger
only to make the project weight lower.
3. Sandwich panel specifications:
The specification which we can obtain it here in Iraq is as the following:
 Factory: Arihan – Zakho – Iraq.
 Density: 38 kg/m3
 Internal steel plate thick 0.4 mm.
 External steel plate 0.5 mm.
 All steel plats galvanized and preprinted and polyester coated.