LEM012SD

DIN rail single phase two wire energy meter

1.1 Safety instruction

1.2 Foreword

1.3 Performance criteria

1.4 Specifications

1.5 Basic errors

1.6 Description

1.7 Dimensions

1.8 Installation

1.9 Operating

1.10 Troubleshooting

1.11 Technical support

User manual

SEP LEMO12SD 2015


1.1 Safety instructions

Information for Your Own Safety


This manual does not contain all of the safety measures for operation of the equipment
(module, device), because special operating conditions, and local code requirements or
regulations may necessitate further measures. However, it does contain information
which must be adhered to in the interests of your own personal safety and to avoid
material damages. This information is highlighted by a warning triangle and are
represented as follows, depending on the degree of potential danger.

Warning
Means that failure to observe the instruction can result in death, serious injury or
considerable material damage.

Caution
Means hazard of electric shock and failure to take the necessary safety precautions will
result in death, serious injury or considerable material damage.

Qualified personnel
Commissioning and operation of the equipment (module, device) described in this
manual may only be performed by qualified personnel. Qualified personnel in the
sense of the safety information contained in this manual are persons who are
authorized to commission, start up, ground and label devices, systems and circuits
according to safety and Regulatory standards.

Use for the intended purpose


The equipment (device, module) may only be used for the application cases specified in
the catalog and the user manual and only in connection with devices and components
recommended and approved by SEP Europe.
Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport,
proper storage, installation and assembly, as well as proper operation and
maintenance. When operating electrical equipment, certain parts of this equipment
automatically carry dangerous voltages. Improper handling can therefore result in
serious injury or material damage.

 Use only isolated tools.


 Do not connect while circuit is live (hot).
 Do not connect the meter to a 3 phase - 400VAC – network.
 Place the meter only in dry surroundings.
 Do not mount the meter in an explosive area or exposed to dust, mildew and
insects.
 Make sure the used wires are suitable for the maximum current of this meter.
 Make sure the AC wires are connected correctly before activating the
current/voltage to the meter.
 Do not touch the meter connecting clamps directly with your bare hands, with
metal, blank wire or other material as you will have the chance of an electricity
shock and a possible chance for health damage.
 Make sure the protection cover is placed after installation.
 Installation, maintenance and repair should only be done by a qualified personnel.

SEP LEMO12SD 2015


 Never break the seals and open the front cover as this might influence the
functionality of the meter, and will be avoid any warranty.
 Do not drop, or allow physical impact to the meter as there are high precision
components inside that may break or render the meter measure accurately.

Exclusion of liability
We have checked the contents of this publication and every effort has been made to
ensure that the descriptions are as accurate as possible.
However, deviations from the description cannot be completely ruled out, so that no
liability can be accepted for any errors or omissions contained in the information
given. The data in this manual are checked regularly and the necessary corrections
are included in subsequent editions. We are grateful for any improvements that you
care to suggest.

Subject to technical modifications without notice.

Copyright
Copyright (c) 2011 SEP EUROPE All rights Reserved.
It is prohibited to pass on or copy this document or to use or disclose its contents
without our express permission. Any duplication is a violation of the law and subject
to criminal and civil penalties. All rights reserved, particularly in the event of a
patent award or utility model registration.

Registered trademarks
SEP EUROPE is registered trademark of Schotman Elektro BV.

1.2 Foreword

Thank you for purchasing the SEP LEM012SD DIN rail single phase two wire energy
meter. The SEP LEM012SD energy meter is the most advanced type electronic kWh
meter available at the market. With the SEP product range we have introduced a
large scale of energy meters on the market suitable for 110V AC to 400V AC (50 or
60Hz). Besides the normal energy meters we also developed our own pre-paid
meters with chip card, chip card re-loaders and a complete PC management control
system. For more information on other product please contact our sales department
at [email protected]

Although we produce the SEP LEM012SD meter according to IEC 62053-21 and our
quality inspection is very accurate there might always be a possibility that your
product shows a fault or failure for which we do apologize. Under normal conditions
your product should give you years of benefit and pleasure. In case there is problem
with the energy meter you should contact your dealer immediately. All energy
meters are sealed with a special seal. Once this seal is broken there is no possibility
to claim for warranty. Therefore NEVER open an energy meter or break the seal of
the energy meter. The warranty time is 6 months, after installation, and only valid
for construction faults.

SEP LEMO12SD 2015


1.3 Performance criteria:

Operating humidity ≤ 75%


Storage humidity ≤ 95%
Operating temperature -10°C - +50°C
Storage temperature -30°C - +70°C
International standard IEC 62053-21
Accuracy class 1
Protection against penetration
of dust and water IP51
Insulating encased meter of
protective class Ⅱ

1.4 Specifications:

Nominal voltage (Un) 230V AC


Operational voltage 161 - 300V AC
Insulation capabilities:
- AC voltage withstand 2KV for 1 minute
- Impulse voltage withstand 6KV – 1.2µS waveform
Basic current (Ib) 5A
Maximum rated current (Imax) 32 A
Operational current range 0.25A - 32A
Over current withstand 960A for 0.01s
Operational frequency range 50Hz ±10%
Internal power consumption ≤2W / 10VA
Test output flash rate (RED LED) 2000 impulses per kWh (0.5Wh/imp)
Pulse output rate (pins 20 & 21) 2000 pulses per kWh (0.5Wh/imp)
Power supply indicator (Green LED) Meter is connected and working OK
Consumption indicator (RED LED) Flashing at load running
Data display mode 7+1 digits for LCD display
Data save The data can be stored more than 20 years
when power cut.

1.5 Basic errors:

0.05Ib Cosφ = 1 ±1.5%


0.1Ib Cosφ = 0.5L ±1.5%
Cosφ = 0.8C ±1.5%
0.1Ib - Imax Cosφ = 1 ±1.0%
0.2Ib - Imax Cosφ = 0.5L ±1.0%
Cosφ = 0.8C ±1.0%

1.6 Description

A Register (LCD display)


B Case
C Terminal block
D Protection cover
E Security hasp

SEP LEMO12SD 2015


Material

Window of register PC inflammable retarding


Case PA inflammable retarding
Terminal block PA inflammable retarding
Protection cover PA inflammable retarding

E C
D

Single phase 32A kWh meter


Ui max = 27V / li max = 27mA
RA= 0.5 W h/imp (ti=80ms ) SO
RL = 0.5 Wh/imp
EN62053-21
ADM1D V1.0
DMMetering
kWh

3
A 21

20
SO
-

R
230 V,5(32)A,50H z
R A = 0 .5 Wh/ i m p
4 N

B
R L = 0. 5 W h/ im p
L

D
E C

1.7 Dimensions

Height 116. mm
Width 17.5 mm
Depth 59. Mm
Weight 0.12 Kg (net)
U i m a x = 2 7 V / li m a x = 2 7mA
R A = 0 .5 W h/im p (ti=8 0m s) S O
R L = 0.5 W h /im p
EN62053-21
Single phase 32A kWh meter
A DM1D V1.0
DMMetering
kWh

3
20
21

SO
-

230V,5( 32)A,50Hz
RA = 0 . 5 W h /im p
4

RL = 0 .5 Wh / im p
N

SEP LEMO12SD 2015


1.8 Installation

CAUTION
 Turn off and lock out all power supplying the energy meter and the
equipment to which it is installed before working on it.
 Always use a properly rated voltage sensing device to confirm that power is
off.

WARNING
 Installation should be performed by qualified personnel familiar with
applicable codes and regulations.
 Use isolated tools to install the meter.
 Fuse or thermal cut-off or single-pole circuit breaker can’t be fitted on the
supply line and not the neutral line.
 Case is sealed, failure to observe this instruction can result in damage for
meter.

- We recommend that the connecting wire which is used to connect meter to


outside circuit should be sized according to local codes and regulations for the
ampacity of the circuit breaker or over current device used in the circuit.
- A external switch or a circuit-breaker should be installed on the inlet wire, which
will be used as a disconnection device for the meter. And there it is
recommendation that the switch or circuit-breaker be near the meter so that it
is convenience for the operator. The switch or circuit-breaker should comply
with the specifications of the building electrical design and all local regulations.
- An external fuse or thermal cut-off which will used as a overcurrent protection
device for the meter must be installed on the supply side wire, and it is
recommended that the overcurrent protection device be near the meter so that
it is convenience for the operator. The overcurrent protection device should
comply with the specifications of the building electrical design and all local
regulations.
- This meter can be installed indoor directly, or in a meter box which is waterproof
outdoor, subject to local codes and regulations.
- To prevent tampering, secure the meter with a padlock or a similar device.
- The meter has to be installed against a wall which is fire resistant.
- The meter has to be installed in a good ventilated and dry place.
- The meter has to be installed in a protection box in dangerous or dusty
environment.
- The meter can be installed and used after being tested and sealed with a letter
press printing.
- The meter can be installed on a 35mm DIN rail.
- The meter should be installed in a available height so that it is easy to read.
- When the meter is installed in an area with frequent surges due to e.q.
thunderstorms, welding machines, inverters etc, protect the meter with Surge
Protection Devices.
- After finishing installation, the meter must be sealed to prevent tampering.

SEP LEMO12SD 2015


- Connection of the wires should be done in accordance with the underneath
connection diagram.

20
3
+ 1
L

SO
N
6 4
21 -

1 Inlet phase line


4 Inlet neutral line
3 Outgoing phase line
6 Outgoing neutral line
20 and 21 Pulse output contact

1.9 Operating

Working indication
There is a white LED which has two colors (green and red) while burning in the front
panel of LEM012SD When the meter works normally, this LED will display green. When
meter is going wrong or no power supply, the LED will turn off.

Consumption indication
There is a white LED which has two colors (green and red) while burning in the front
panel of LEMO12SD When consumption happens, the LED will flash and display red.
The more quickly LED flash, the more consumption there is. For this LED, the flash rate
is 2000 impulses per kWh (0.5Wh/imp).

Reading the meter


LEM012SD is equipped with a white backlight LCD display. During the normal working
hours, the meter will be burning this white backlight all the time. LCD display will show
the following energy data and indication message.

a) Current total energy


When the meter is in normal working, it will display only 7 +1 energy data with. The
unit is kWh. These data can’t be reset to zero by the user. Example: Total energy
is 4574899.1 kWh.
kWh

230V,5(32)A,50Hz
RA = 0.5 Wh/imp
RL = 0.5 Wh/imp

SEP LEMO12SD 2015


b) Indication for reverse use
When the meter is in the wrong connects with the incoming line and the outgoing
line, that is the incoming line is connected to the position for the outgoing line and
the outgoing line is connected to the position for incoming line, it will happen
reverse. The LCD display will show HELP 1 and the current total energy circularly to
indicate the user for the wrong connection. The period of circular display is 3
seconds.
kWh

kWh

230V,5(32)A,50Hz 230V,5(32)A,50Hz
RA = 0.5 Wh/imp RA = 0.5 Wh/imp
RL = 0.5 Wh/imp RL = 0.5 Wh/imp

1 1

c) Meter version
When the meter re-switch on the power, it will display the meter version for 3
seconds, then display the other items. As follows indication SEP version is U1.00.
kWh

230V,5(32)A,50Hz
RA = 0.5 Wh/imp
RL = 0.5 Wh/imp

Pulse output

The LEM012SD DIN rail energy meter is equipped with an pulse output which is fully
separated from the inside circuit. That generates pulses in proportion to the measured
energy for remote reading purposes and accuracy testing. The pulse output is a polarity
dependant, passive transistor output requiring an external voltage source for correct

SEP LEMO12SD 2015


operation. For this external voltage source, the voltage (Ui) should is 5-27V DC, and
the maximum input current (Iimax) is 27mA DC. To connect the impulse output,
connect 5-27V DC to connector 20 (anode), and the signal wire (S) to connector 21
(cathode). The meter pulses 2000 per kWh (0.5Wh/imp).

1.10 Troubleshooting

CAUTION
 During repairing and maintenance, do not touch the meter connecting
clamps directly with your bare hands, with metal, blank wire or other
material as you will have the chance of an electricity shock and a possible
chance for health damage.
 Turn off and lock out all power supplying the energy meter and the
equipment to which it is installed before opening the protection cover to
prevent the hazard of electric shock.

WARNING
 Maintenance or repair should be performed by qualified personnel familiar
with applicable codes and regulations.
 Use insulated tools to maintain or repair the meter.
 Make sure the protection cover is in place after maintenance or repair.
 Case is sealed, failure to observe this instruction can result in damage for
meter.

Problem Check Solution


No light for the Is AC power supply Check switch or circuit-breaker
Power supply connected to the and fuse or thermal cut-off.
indicator. meter ?

Is the 1 and 4 Reinstall terminal screws on the 1


connecting correct ? and 4. Make sure all screws are
fixed. Than there should be a
230V 50Hz AC voltage between
the terminal screws on the 1 and
4 when power supply is input.

Maybe there is a Please connect with technical


fault in the inside supporter to replace this meter.
circuit.

SEP LEMO12SD 2015


Continue
Problem Check Solution
No light for the Is the load running? Only when load is running, this
consumption LED will flash.
indicator.
Is the operating If the operating power is too low,
power too low? the spacing interval of flashing
will be prolonged so that people is
under the delusion that LED isn’t
burning.

Maybe there is a Please connect with technical


fault in the inside supporter to replace this meter.
circuit.

The register can’t Is there a power Check that the power supply
run. supply inside the indicator is burning.
meter?

Is the operating If the operating power is too low,


power too low? the spacing interval of running will
be prolonged so that people is
under the delusion that register
can’t run.

Maybe there is a Please connect with technical


fault in the inside supporter to replace this meter.
circuit.

LCD backlight can’t Is there a power Check that the power supply
lit. supply inside the indicator is burning.
meter?

Maybe there is a Please connect with technical


fault in the inside supporter to replace this meter.
circuit.

No pulse output. Is DC power supply Check the external voltage source


connected to the (Ui) is 5-27V DC.
meter?

Is the connecting Check correct connecting:


correct? connect 5-27V DC to connector 20
(anode), and the signal wire (S)
to connector 21 (cathode).

Maybe there is a Please connect with technical


fault in the inside supporter to replace this meter.
circuit.

Pulse output rate Maybe there is a Please connect with technical


wrong. fault in the inside supporter to replace this meter.
circuit.

SEP LEMO12SD 2015


1.11 Technical support

For questions about one of our products please contact:

- SEP dealer in your in your region


- Your local SEP distributor
- Email: [email protected]

www.sep-europe.nl

S.E.P. Europe
Weverstraat 4
9403 VJ Assen
Netherlands

Tel: +31(0)088- 54 60735

SEP LEMO12SD 2015

You might also like