P433 Setting Calculation
P433 Setting Calculation
Distance Protection
1
1.2 Procedure for Relay setting Calculation for MiCOM P433 Distance relay
Data required
Calculation Procedure
Loadability:
The Limiting conditions for setting the distance relay reach to avoid encroachment into loads.
As per “Reliability Standard PRC-023”, the maximum impedance for the distance relay
characteristics along 30º on the impedance plane for 0.85 per unit rated voltage and the
maximum specified current for each condition.
The maximums Load w.r.t Secondary Zmax = 0.85*VL-L/ (√3*1.5*.IL)
2
The New impedance for Parallel line drawn parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts
the Resistance axis is Z new= X (at Zmax) /SIN (Line angle)
The New Resistance from Known Reactance Rnew = Znew* COS (Line angle)
Zone Settings
Zone 1
Zone 1 = 80 % of Protection Line
X1 = Z1 * SIN (Line Angle)
Kz 1 Zero sequence compensation
Kz1 = (Z0-Z1/3*Z1)
Kz1 angle = angle of Kz1
As per manufacturer’s specification the maximum X/R ratio allowed is 10, hence considering
this limitation and the maximum loadability limit the minimum of the two is considered
Resistive reach
R2= Zone2 impedance W.R.T Secondary *COS (Line angle)
Zone 2
Zone 2 = Min of [MAX OF ((Protection line+ (0.5*Adjacent shortest line)) and
(1.2*Protection line)] and (Protected line + 05* Transformer impedance)
X2 = Z2 * SIN (Line Angle)
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec
Kz2 = (Z0-Z1/3*Z1)
Kz2 angle = angle of Kz2
3
R2= Zone2 impedance W.R.T Secondary *COS (Line angle)
R2 PH = Minimum of (8* Zone 2 Reactance and Resistance at maximum Load)
R2 G = Minimum of (8* Zone 2 Reactance and Resistance at maximum Load)
Zone 3
Zone3 = [MIN OF (1.2*Protection line + Adjacent Long line) & (Protection line + Adjacent
Long line +0.25* Adjacent Second Long Line) & (Protection line +Transformer
impedance)]
R3= Zone3 impedance W.R.T Secondary *COS (Line angle)
R3 PH-R4PH = Minimum of (8* Zone 3 Reactance and Resistance at maximum Load)
R3 G-R4G =Minimum of (8* Zone 3 Reactance and Resistance at maximum Load)
tz3 = 1 sec
Zone 4
Zone4 = 0.25 *Zone 1
R4= Zone4 impedance W.R.T Secondary *COS (Line angle)
tz4 = 1 sec
Data
4
Zero sequence Line impedance = 0.233+j1.329
CT Ratio = 1200A/1A
PT Ratio = 220kV/110V
Protected Line Length(Mahilpur) = 51.1 Km
Adjacent Shortest Line Length (Rehan) = 26.7 Km
Adjacent Longest Line Length (Bhakra Right) = 51.1 Km
Second Longest Line Length = 0 Km
Voltage ratio of the transformer = 220 kV/132 kV
Maximum load on the feeder = 795 A (for Zeebra)
CT/PT ratio = 0.6
Calculation
= √(0.07972+0.40652)
= [0.4142 * 51.1]
= 21.167 * 0.6
ZPL = 12.70 Ω
= √(0.07972+0.40652)
= [0.4142 * 26.7]
5
ZSL W.R.T Primary = 11.06 Ω
= 11.06 *0.6
ZSL = 6.635 Ω
= √(0.07972+0.40652)
= [0.4142 * 51.1]
= 21.167 * 0.6
= [0.4142 * 0]
= 0 * 0.6
6
The maximums Load w.r.t Secondary ZMAX primary = 0.85*VL-L/(√3*1.5*.IL)
ZMAX = 90.53 Ω
= 54.32 Ω
= 54.32*0.8660
R = 47.044 Ω
= 54.32*0.5
X = 27.16 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is
Znew = 27.67 Ω
The New Resistance from Known Reactance Rnew = Znew* COS (78.91)
= 27.67*cos 78.91
R new = 5.322
R = 47.044 -5.322
R = 41.722 Ω
Zone Settings
Zone 1
7
Zone 1= 80 % of Protection Line
= 0.8 * 12.70
Zone 1 = 10.16 Ω
R1PP = 41.722 Ω
R1PG= 41.722 Ω
Zone 2
Zone 2 = MIN OF [(Protected Line + 0.5*Transformer impedance at remote end) AND (MAX
OF (Protected line + (0.5*Adjacent shortest line) AND (1.2*Protected line))]
= 16.02 Ω
Zone 2 = 16.02 Ω
8
X2PP, X2PG = 15.72 Ω
R2PP = 41.722 Ω
R2PG= 41.722 Ω
Zone 3
Zone3= [MIN OF (1.2(Protected line) +Adjacent Long line) & (Protected line + Adjacent Long
line+25% Second Adjacent Long Line) & (Protected line +Transformer impedance at remote
end)]
Zone3 = 25.40
tz3 = 1 sec
R3PP = 41.722 Ω
R3PG= 41.722 Ω
Zone 4
9
Zone4 = 0.25 *Zone1 Impedance
X4 = 2.49 Ω
tz4 = 1 sec
10
11