EXPERIMENT TITLE:
WATER COOLING TOWER SYSTEM
LECTURER: PN. NOR IZYAN BINTI ZULKAFLI/DR NIDZAMMUDIN BIN MD. YUSOF
LECTURER REMARKS EVALUATION
Objectives
Introduction & Theory
Procedure and Apparatus
Data and Result
Analysis and Discussion
Conclusions
References
TOTAL
1.0 OBJECTIVE
To investigate the relationship between cooling load and cooling range.
2.0 DATA AND RESULTS
Table 1: Data for 0.5kW Cooling Load
No. T1 T2 T3 T4 T5 T6 T7 Heater Flowrate Orifice Pressure
(°C) (°C) (°C) (°C) (°C) (°C) (°C) Power (LPM) Differential Drop
(W) (Pa) (Pa)
1 23.9 23.5 23.2 22.2 26.8 23.6 23.6 538 3 0.0 0.0
2 24.0 23.5 22.9 22.2 26.0 22.8 23.5 540 3 0.0 0.0
3 24.1 23.6 22.7 22.2 25.4 22.7 23.5 539 3 0.0 0.0
4 23.9 23.5 22.5 22.2 25.2 22.5 23.4 537 3 0.0 0.0
5 22.1 23.6 22.5 22.2 24.9 22.1 23.4 536 3 0.0 0.0
Table 2: Data for 1.0kW Cooling Load
No. T1 T2 T3 T4 T5 T6 T7 Heater Flowrate Orifice Pressure
(°C) (°C) (°C) (°C) (°C) (°C) (°C) Power (LPM) Differential Drop
(W) (Pa) (Pa)
1 22.8 22.5 25.8 22.2 26.3 22.6 23.4 1023 3 0.0 0.0
2 22.6 22.5 25.4 22.2 27.2 23.1 23.3 1029 3 0.0 0.0
3 22.7 22.6 25.8 22.1 27.8 23.5 23.4 1028 3 0.0 0.0
4 22.6 22.4 25.2 22.2 28.4 23.7 23.5 1024 3 0.0 0.0
5 22.4 22.2 25.5 22.1 28.6 23.9 23.4 1025 3 0.0 0.0
Table 3: Data for 1.5kW Cooling Load
No. T1 T2 T3 T4 T5 T6 T7 Heater Flowrate Orifice Pressure
(°C) (°C) (°C) (°C) (°C) (°C) (°C) Power (LPM) Differential Drop
(W) (Pa) (Pa)
1 23.9 23.7 24.3 22.3 30.7 24.8 23.4 1538 3 0.0 0.0
2 23.6 23.8 25.0 22.1 32.1 25.6 23.4 1532 3 0.0 0.0
3 23.8 23.8 25.5 22.1 32.6 25.9 23.4 1550 3 0.0 0.0
4 23.6 23.7 25.5 22.1 32.9 26.0 23.6 1556 3 0.0 0.0
5 23.5 23.7 25.5 22.3 33.2 26.4 23.4 1541 3 0.0 0.0
Figure 1 shows water inlet and outlet temperature for 0.5kW
3.0 ANALYSIS AND DISCUSSION
Figure
2 shows
water
inlet and outlet temperature for 1.0kW
Figure 3 shows
water inlet
and outlet
temperature for 1.5kW
Figure 4 shows graph of relationship for three different power
CONCLUSION
For the conclusion, the experiment can be concluded that if the power of the heater is increasing
the temperature increase and the cooling range of the tower will also increase. The aim of the
experiment is to achieve the successful investigation of the relationship between cooling load
and cooling range. We have discovered many different things while conducting this experiment.
Other than that, importance things that we just noticed on the experiment is always make sure the
system is running at the steady state before start collecting the date during the experiment
running.