Updated IEEE Radial Test Feeders Data
Updated IEEE Radial Test Feeders Data
Shunt Capacitors:
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 908
1 . .. , .-. ----- . . . . -.. I
# II(J AA 0.970 U.36X U.ulll 31U
Overhead Spacing Models: #2 AA 1.54 0.292 0.00883 156
#2 ACSR 1.69 0.316 0.00418 180
The spacing ID numbers and type for overhead lines are
#4 ACSR 2.55 0.257 0.00452 140
summarized in Table 2.
# 10 Cu 5.903 0,102 0.00331 80
# 12 Cu 9.375 0.081 0.00262 75
Table 2 # 14 Cu 14.872 0.064 0.00208 20
Overhead Line Spacings
Underground Spacing Models:
Table 4
Figure 1 shows the spacing distances between the phase Underground Line Spacings
conductors and the neutral conductor for Spacing ID
numbers used for the overhead lines. .’$j &3fI ‘m ‘,,: ~’.: ‘;:;&&ii “’..$,,,,.;
‘. “:’:/+3?
~ 6“ +++ 6“ + ~1’ ~
‘ A ‘ 4 ; ●
240 240 240
00 ● *
ID-515 ID -520
Figure 2 – Underground Line Spacings
v u
Zcm &
ID-500 ID-505 ID-51O Cable Data:
Figure 1 – Overhead Line Spacings Table 5 lists the characteristics of the various concentric
neutral cables [4] that are used in the test feeders. The
Conductor Data column numbers correspond to:
Table 3 lists the characteristics of the various conductors 1 – Conductor size in AWG or kcmil
that are used for the overhead configurations in the test 2 – Diameter over insulation (inches)
feeders[2,3 ]. The columns correspond to: 3 – Diameter over screen (inches)
4 – Outside diameter (inches)
1 – Conductor size in AWG or kcmil 5 – Copper 1/3 neutral (No. x AWG)
2 – Type of conductor 6 – Ampacity in 4 inch duct
AA = All Aluminum
ACSR = Aluminum Conductor Steel Reinforced Table 5
CU = Copper Concentric Neutral 15 kV All Aluminum (AA) Cable
3– 60 Hz resistance at 50 degrees C (ohms/mile)
1 2 3 4 5 6
4– Conductor outside diameter (inches) 2(7x) 0.78 0.85 0.98 6x14 135
5- Geometric Mean Radius (R) 110(19X) 0.85 0.93 1.06 6x14 175
6– Ampacity at 50 degrees C (amps) 2/0(19x) 0.90 0.97 1.10 7X14 200
250(37x) 1.06 1.16 1.29 13X14 260
500(37X) 1.29 1.39 1,56 16x 12 385
Table 3
10OO(61X) 1.64 1.77 1.98 20X 10 550
Conductor Data
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 909
5 – Outside diameter (inches) used in the feeder. The impedance matrix assumes a
6 – Ampacity in 4 inch duct (amps) resistivity of 100 Ohm-meters and the admittance
matrix assumes a relative permittivity of 2.3.
Table 6 2. Radial Flow Summary –a summary of the system
Tape Shielded 15 kV All Aluminum (AA) Cable input, total load, total losses and total shunt capacitors
Tape Thickness = 5 roils by phase and total three-phase.
3. Voltage Profile – voltage magnitudes and angles by
phase at each node. Voltage magnitudes are given in
per-unit.
4. Voltage Regulator Data – for each regulator in the
Configuration Codes:
system a summary of the settings and the final tap
settings.
Each test feeder will have a table of “Configuration
5. Radial Power Flow – complete node data including
Codes”. The configuration code is a unique number
line flows in amps and degrees by phase. Line power
assigned to describe the spacing model (Tables 2 and 4),
losses by phase and total three-phase are also given.
the phasing (left to right) and the phase and neutral
conductors used.
The IEEE 13 Node Test Feeder
The data for the feeders is so extensive that only the data
for the 13 node feeder will be given in this paper. Data for
all of the test feeders can be downloaded from:
‘?”
Underground
b
652 680
&
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 910
Overhead Line Configuration Data: Transformer Data:
I I I t 1 1 I
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 911
individual regulator taps is coordinated with the other
regulators. Test results for this feeder include the following
transformer connections for step-down and step-up
The IEEE 34 Node Test Feeder operations and for balanced and unbalanced loading.
This feeder is an actual feeder located in Arizona. The 1. Grounded Wye – Grounded Wye
feeder’s nominal voltage is 24.9 kV. It is characterized by: 2. Grounded Wye – Delta
3. Ungrounded Wye – Delta
1. Very long and lightly loaded 4. Delta – Grounded Wye
2. Two in-line regulators required to maintain a good 5. Delta – Delta
voltage profile 6. Open Wye – Open Delta
3. An in-line transformer reducing the voltage to 4.16 kV
for a short section of the feeder IV. Summary
4. Unbalanced loading with both “spot” and
“distributed” loads. Distributed loads are assumed to Data for five different test feeders has been developed.
be connected at the center of the line segment Data appearing in this paper are “common” to all of the
5. Shunt capacitors feeders. The total data for the 13 node test feeder is
included to illustrate the form of the data for the other test
Because of the length of the feeder and the unbalanced feeders. The data and one-line diagrams for the other test
loading it can have a convergence problem. feeders are too extensive to be included in the paper. The
data for all five test feeders are in spreadsheet format and
The IEEE 37 Node Test Feeder can be downloaded from the Web at:
The IEEE Four Node Test Feeder 1. IEEE Distribution Planning Working Group Report,
“Radial distribution test feeders”, IEEE Transactions
This feeder was not part of the original set of test systems on Power Systems,, August 1991, Volume 6, Number
published in 1992. The primary purpose of this test feeder 3, pp 975-985.
is to provide a simple system for the testing of all possible 2. J.D. Glover and M. Sarma, “Power system analysis
three-phase transformer connections. Characteristics of and design”, 2“d Edition, PWS Publishing Company,
the feeder are: Boston, MA, 1994.
3. “Overhead conductor manual”, Southwire Company,
1. Two line segments with a three-phase transformer Carrolkon, GA, 1994.
bank connected between the two segments 4. “Product data”, Section 2, Sheets 10 and 30., The
2. Data is specified for “closed” three-phase transformer Okonite Company, www.okonite.com
connections and for two transformer “open”
connections
3. Transformer data is specified for step-up and step-
down testing. The primary vokage is always 12.47
kV while the secondary voltage can be either 4.16 kV
or 24.9 kV.
4. Data is specified for balanced and unbalanced loading
at the most remote node
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 912