0% found this document useful (0 votes)
243 views7 pages

Verificare Termografica Tablou Cuptor

The document contains 11 infrared images and reports of a furnace panel taken by a Fluke TiS45 infrared camera. Each image identifies potential problems such as needed repairs to connections, safety switches or verification of pads. The highest exceptional temperature recorded was 218.7°C and immediate intervention was recommended for some issues identified.

Uploaded by

Stefan Duca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
243 views7 pages

Verificare Termografica Tablou Cuptor

The document contains 11 infrared images and reports of a furnace panel taken by a Fluke TiS45 infrared camera. Each image identifies potential problems such as needed repairs to connections, safety switches or verification of pads. The highest exceptional temperature recorded was 218.7°C and immediate intervention was recommended for some issues identified.

Uploaded by

Stefan Duca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

SC RC Energo Install SRL

Str. Transilvaniei nr. 132

Raport termografic TGF-185


CP2 - Incarcare - Tablou cuptor
Prepared for:

SC Romcarbon SA
Str. Transilvaniei nr. 132

NECESITA INTERVENTIE IMEDIATA!


Inspected By:

Inspection Date: 5/9/2017 1:55:18 PM Location


Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344

CP2 - Incarcare - Tablou cuptor (3).IS2


Necesita interventie imediata!

Image Info
Image Range 30.2°C to 218.7°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:55:18 PM
Calibration Range -20.0°C to 350.0°C

Main Image Markers


Name Temperature Emissivity
Hot 218.7°C 0.80
Cold 30.2°C 0.80

2
Inspected By:

Inspection Date: 5/9/2017 1:55:37 PM Location


Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344

CP2 - Incarcare - Tablou cuptor (4).IS2


Necesita interventie legatura papuc sus si siguranta
dreapta.

Image Info
Image Range 29.2°C to 84.7°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:55:37 PM
Calibration Range -20.0°C to 350.0°C

Main Image Markers


Name Temperature Emissivity
Centerpoint 40.1°C 0.80
Hot 84.7°C 0.80
P0 81.4°C 0.80
P1 82.4°C 0.80

3
Inspected By:

Inspection Date: 5/9/2017 1:56:25 PM Location


Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344

CP2 - Incarcare - Tablou cuptor (8).IS2


Necesita interventie!

Image Info
Image Range 25.8°C to 79.9°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:56:25 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature Emissivity
Centerpoint 35.0°C 0.80
Hot 79.9°C 0.80
Cold 25.8°C 0.80
P0 66.8°C 0.80

4
Inspected By:

Inspection Date: 5/9/2017 1:56:58 PM Location


Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344

CP2 - Incarcare - Tablou cuptor (9).IS2


Necesita interventie Papuc stanga.

Image Info
Image Range 21.9°C to 113.4°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:56:58 PM
Calibration Range -20.0°C to 350.0°C

Main Image Markers


Name Temperature Emissivity
Hot 113.4°C 0.80
Cold 21.9°C 0.80
P0 104.6°C 0.80
P1 84.8°C 0.80
P2 62.7°C 0.80

5
Inspected By:

Inspection Date: 5/9/2017 1:57:26 PM Location


Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344

CP2 - Incarcare - Tablou cuptor (10).IS2

Image Info
Image Range 27.9°C to 79.8°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:57:26 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature Emissivity
P0 60.1°C 0.80
P1 63.0°C 0.80
P2 60.8°C 0.80

6
Inspected By:

Inspection Date: 5/9/2017 1:57:34 PM Location


Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344

CP2 - Incarcare - Tablou cuptor (11).IS2


Necesita verificare papuci

Image Info
Image Range 28.9°C to 73.4°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:57:34 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature Emissivity
P0 72.0°C 0.80
P1 69.4°C 0.80
P2 55.5°C 0.80
P3 69.3°C 0.80
P4 70.1°C 0.80
P5 62.5°C 0.80

You might also like