SC RC Energo Install SRL
Str. Transilvaniei nr. 132
Raport termografic TGF-185
CP2 - Incarcare - Tablou cuptor
Prepared for:
SC Romcarbon SA
Str. Transilvaniei nr. 132
NECESITA INTERVENTIE IMEDIATA!
Inspected By:
Inspection Date: 5/9/2017 1:55:18 PM Location
Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344
CP2 - Incarcare - Tablou cuptor (3).IS2
Necesita interventie imediata!
Image Info
Image Range 30.2°C to 218.7°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:55:18 PM
Calibration Range -20.0°C to 350.0°C
Main Image Markers
Name Temperature Emissivity
Hot 218.7°C 0.80
Cold 30.2°C 0.80
2
Inspected By:
Inspection Date: 5/9/2017 1:55:37 PM Location
Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344
CP2 - Incarcare - Tablou cuptor (4).IS2
Necesita interventie legatura papuc sus si siguranta
dreapta.
Image Info
Image Range 29.2°C to 84.7°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:55:37 PM
Calibration Range -20.0°C to 350.0°C
Main Image Markers
Name Temperature Emissivity
Centerpoint 40.1°C 0.80
Hot 84.7°C 0.80
P0 81.4°C 0.80
P1 82.4°C 0.80
3
Inspected By:
Inspection Date: 5/9/2017 1:56:25 PM Location
Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344
CP2 - Incarcare - Tablou cuptor (8).IS2
Necesita interventie!
Image Info
Image Range 25.8°C to 79.9°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:56:25 PM
Calibration Range -20.0°C to 80.0°C
Main Image Markers
Name Temperature Emissivity
Centerpoint 35.0°C 0.80
Hot 79.9°C 0.80
Cold 25.8°C 0.80
P0 66.8°C 0.80
4
Inspected By:
Inspection Date: 5/9/2017 1:56:58 PM Location
Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344
CP2 - Incarcare - Tablou cuptor (9).IS2
Necesita interventie Papuc stanga.
Image Info
Image Range 21.9°C to 113.4°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:56:58 PM
Calibration Range -20.0°C to 350.0°C
Main Image Markers
Name Temperature Emissivity
Hot 113.4°C 0.80
Cold 21.9°C 0.80
P0 104.6°C 0.80
P1 84.8°C 0.80
P2 62.7°C 0.80
5
Inspected By:
Inspection Date: 5/9/2017 1:57:26 PM Location
Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344
CP2 - Incarcare - Tablou cuptor (10).IS2
Image Info
Image Range 27.9°C to 79.8°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:57:26 PM
Calibration Range -20.0°C to 80.0°C
Main Image Markers
Name Temperature Emissivity
P0 60.1°C 0.80
P1 63.0°C 0.80
P2 60.8°C 0.80
6
Inspected By:
Inspection Date: 5/9/2017 1:57:34 PM Location
Equipment Equipment Name:
Ambient Air Temp: Wind Speed
Load (%) Max Rated Load:
Exception Temperature: Potential Problem
Recommended Action Repair Priority:
Emissivity: 0.80 Reflected Temperature: 20.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS45-16040344
CP2 - Incarcare - Tablou cuptor (11).IS2
Necesita verificare papuci
Image Info
Image Range 28.9°C to 73.4°C
Camera Model TiS45
IR Sensor Size 160 x 120
DSP Version 3.10.6
OCA Version 3.10.6
Image Time 5/9/2017 1:57:34 PM
Calibration Range -20.0°C to 80.0°C
Main Image Markers
Name Temperature Emissivity
P0 72.0°C 0.80
P1 69.4°C 0.80
P2 55.5°C 0.80
P3 69.3°C 0.80
P4 70.1°C 0.80
P5 62.5°C 0.80