MG17 K802 Danfoss
MG17 K802 Danfoss
Operating Guide
VLT® Soft Starter MCD 500
vlt-drives.danfoss.com
Contents Operating Guide
Contents
1 Introduction 6
2 Safety 11
2.1 Safety 11
3 Installation 13
3.1 Mechanical Installation 13
3.2 Dimensions and Weight 14
4 Electrical Installation 16
4.1 Control Wiring 16
4.1.1 Ways to Control the Soft Starter 16
4.1.2 Control Terminals 16
4.1.3 Remote Inputs 16
4.1.4 Serial Communication 17
4.1.5 Ground Terminal 17
4.1.6 Power Terminations 17
4.1.7 Finger Guard Kit 18
4.2 Power Input and Output Configurations 18
4.2.1 Internally Bypassed Models (MCD5-0021B to MCD5-0961B) 18
4.2.2 MCD5-0245C 19
4.2.3 MCD5-0360C to MCD5-1600C 19
4.3 Motor Connection 19
4.3.1 Testing the Installation 20
4.3.2 In-line Installation 20
4.3.2.1 Internally Bypassed 20
4.3.2.2 Non-bypassed 20
4.3.2.3 Externally Bypassed 20
4.3.3 Inside Delta Installation 21
4.3.3.1 Internally Bypassed 21
4.3.3.2 Non-bypassed 22
4.3.3.3 Externally Bypassed 22
4.4 Current Ratings 23
4.4.1 In-line Connection (Bypassed) 24
4.4.2 In-line Connection (Non-bypassed/Continuous) 25
4.4.3 Inside Delta Connection (Bypassed) 26
4.4.4 Inside Delta Connection (Non-bypassed/Continuous) 27
4.5 Minimum and Maximum Current Settings 28
4.6 Bypass Contactor 28
4.7 Main Contactor 28
5 Product Features 39
5.1 Motor Overload Protection 39
5.2 Adaptive Control 39
5.3 Starting Modes 40
5.3.1 Constant Current 40
5.3.2 Current Ramp 40
5.3.3 Adaptive Control 40
5.3.4 Kick-start 41
5.4 Stopping Modes 41
5.4.1 Coast to Stop 41
5.4.2 TVR Soft Stop 41
5.4.3 Adaptive Control 42
5.4.4 Pump Stopping 42
5.4.5 Brake 42
5.5 Jog Operation 43
5.6 Inside Delta Operation 44
5.7 Typical Start Currents 45
5.8 Installation with Main Contactor 46
5.9 Installation with Bypass Contactor 47
5.10 Emergency Run Operation 48
5.11 Auxiliary Trip Circuit 49
5.12 DC Brake with External Zero-speed Sensor 50
5.13 Soft Braking 51
5.14 Two-speed Motor 52
6 Operation 54
6.1 Control Methods 54
6.2 Operation and LCP 55
6.2.1 Operating Modes 55
6.3 Remote-mounted LCP 56
6.3.1 Synchronizing the LCP and the Soft Starter 56
6.4 Welcome Screen 56
7 Programming 59
7.1 Access Control 59
7.2 Quick Menu 59
7.2.1 Quick Set-up 59
7.2.2 Application Set-up Examples 60
7.2.3 Loggings 61
7.3 Main Menu 61
7.3.1 Parameters 61
7.3.2 Parameter Shortcut 61
7.3.3 Parameter List 62
8 Parameter Descriptions 63
8.1 Primary Motor Settings 63
8.1.1 Brake 64
8.2 Protection 65
8.2.1 Current Imbalance 65
8.2.2 Undercurrent 65
8.2.3 Instant Overcurrent 65
8.2.4 Frequency Trip 65
8.3 Inputs 66
8.4 Outputs 67
8.4.1 Relay A Delays 67
8.4.2 Relays B and C 67
8.4.3 Low Current Flag and High Current Flag 68
8.4.4 Motor Temperature Flag 68
8.4.5 Analog Output A 68
8.5 Start/Stop Timers 69
8.6 Auto-reset 69
9 Tools 75
9.1 Set Date and Time 75
9.2 Load/Save Settings 75
9.3 Reset Thermal Model 75
9.4 Protection Simulation 76
9.5 Output Signal Simulation 76
9.6 Digital I/O State 76
9.7 Temp Sensors State 76
9.8 Alarm Log 77
9.8.1 Trip Log 77
9.8.2 Event Log 77
9.8.3 Counters 77
10 Troubleshooting 78
10.1 Trip Messages 78
10.2 General Faults 83
11 Specifications 85
11.1 UL-compliant Installation 86
11.1.1 Models MCD5-0021B to MCD5-0105B 86
11.1.2 Models MCD5-0131B to MCD5-0215B 86
11.1.3 Models MCD5-0245B to MCD5-0396B 86
11.1.4 Models MCD5-0245C 86
11.1.5 Models MCD5-0360C to MCD5-1600C 87
11.1.6 Models MCD5-0469B to MCD5-0961B 87
11.1.7 Pressure Terminal/Connector Kits 87
11.2 Accessories 87
11.2.1 LCP Remote Mounting Kit 87
11.2.2 Communication Modules 87
11.2.3 PC Software 87
11.2.4 Finger Guard Kit 88
11.2.5 Surge Protection Kit (Lightning Protection) 88
13 Appendix 91
13.1 Symbols, Abbreviations, and Conventions 91
Index 92
1 1 1 Introduction
The VLT® Soft Starter MCD 500 is an advanced digital soft 1.1.2 Feature List
start solution for 11–850 kW (15–1150 hp) motors. The soft
starters provide a complete range of motor and system Models for all connection requirements
protection features and are designed for reliable • 21–1600 A (in-line connection).
performance in the most demanding installation situations.
• In-line or inside delta connection.
Edition Remarks
• Loggings.
MG17K8xx Instruction about using finger guard kits for IP00 • Real-time graphs.
installations added to chapter 4 Electrical Installation. • SCR conduction bar graph.
177HA382.11
MCD 5 - - - -
Current rating
0021 = 21 A, AC53b 3-30:330
0037 = 37 A, AC53b 3-30:330
0043 = 43 A, AC53b 3-30:330
0053 = 53 A, AC53b 3-30:330
0068 = 68 A, AC53b 3-30:570
0084 = 84 A, AC53b 3-30:570
0089 = 89 A, AC53b 3-30:570
0105 = 105 A, AC53b 3-30:570
0131 = 131 A, AC53b 3-30:570
0141 = 141 A, AC53b 3-30:570
0195 = 195 A, AC53b 3-30:570
0215 = 215 A, AC53b 3-30:570
0245 = 245 A, AC53b 3-30:570
0331 = 331 A, AC53b 3-30:570
0396 = 396 A, AC53b 3-30:570
0469 = 469 A, AC53b 3-30:570
0525 = 525 A, AC53b 3-30:570
0632 = 632 A, AC53b 3-30:570
0744 = 744 A, AC53b 3-30:570
0826 = 826 A, AC53b 3-30:570
0961 = 961 A, AC53b 3-30:570
0245 = 245 A, AC53a 3-30:50-6
0360 = 360 A, AC53a 3-30:50-6
0380 = 380 A, AC53a 3-30:50-6
0428 = 428 A, AC53a 3-30:50-6
0595 = 595 A, AC53a 3-30:50-6
0619 = 619 A, AC53a 3-30:50-6
0790 = 790 A, AC53a 3-30:50-6
0927 = 927 A,AC53a 3-30:50-6
1200 = 1200 A, AC53a 3-30:50-6
1410 = 1410 A, AC53a 3-30:50-6
1600 = 1600 A, AC53a 3-30:50-6
B = Bypassed
C = Non-bypassed
Mains voltage
T5 = 200 - 525 VAC
T7 = 380 - 690 VAC
Frame size
G1 = 0021 ~ 0105 A
G2 = 0131 ~ 0215 A
G3 = 0245 ~ 0396 A
G4 = 0360 ~ 0961 A
G5 = 1200 ~ 1600 A
Not used
IP rating
00 = IP00
= Not selectable 20 = IP20
Control voltage
CV1 = 24 VAC/VDC
CV2 = 110-120 VAC or 220-240 VAC
2 Safety
2 2
2.1 Safety WARNING
The following symbols are used in this guide: PROPER GROUNDING
Disconnect the soft starter from mains voltage before
carrying out repair work.
WARNING It is the responsibility of the person installing the soft
Indicates a potentially hazardous situation that could starter to provide proper grounding and branch circuit
result in death or serious injury. protection according to local electrical safety codes.
Do not connect power factor correction capacitors to the
CAUTION output of the VLT® Soft Starter MCD 500. If static power
factor correction is employed, it must be connected to
Indicates a potentially hazardous situation that could the supply side of the soft starter.
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
WARNING
NOTICE IMMEDIATE START
Indicates important information, including situations that In auto-on mode, the motor can be controlled remotely
can result in damage to equipment or property. (via remote inputs) while the soft starter is connected to
mains.
MCD5-0021B ~ MCD5-0961B:
2.1.1 Qualified Personnel
Transportation, mechanical shock, or rough handling
may cause the bypass contactor to latch into the On
Correct and reliable transport, storage, installation,
state.
operation, and maintenance are required for the trouble-
free and safe operation of the soft starter. Only qualified To prevent the motor from starting immediately on first
personnel are allowed to install or operate this equipment. commissioning or operation after transportation:
• Always ensure that the control supply is applied
Qualified personnel is defined as trained staff, who are before the power.
authorized to install, commission, and maintain equipment, • Applying control supply before power ensures
systems, and circuits in accordance with pertinent laws and that the contactor state is initialized.
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in this
manual. WARNING
WARNING UNINTENDED START
When the soft starter is connected to AC mains, DC
ELECTRICAL SHOCK HAZARD supply, or load sharing, the motor can start at any time.
VLT® Soft Starter MCD 500 contains dangerous voltages Unintended start during programming, service, or repair
when connected to mains voltage. Only a qualified work can result in death, serious injury, or property
electrician should carry out the electrical installation. damage. The motor can start with an external switch, a
Improper installation of the motor or the soft starter can fieldbus command, an input reference signal from the
cause death, serious injury, or equipment failure. Follow LCP or LOP, via remote operation using MCD PC
the guidelines in this manual and local electrical safety Software, or after a cleared fault condition.
codes.
To prevent unintended motor start:
Models MCD5-0360C ~ MCD5-1600C:
Treat the busbar and heat sink as live parts whenever
• Press [Off]/[Reset] on the LCP before
programming parameters.
the unit has mains voltage connected (including when
the soft starter is tripped or waiting for a command). • Disconnect the soft starter from mains.
• Completely wire and assemble the soft starter,
motor, and any driven equipment before
connecting the soft starter to AC mains, DC
supply, or load sharing.
WARNING
SAFETY OF PERSONNEL
2 2 The soft starter is not a safety device and does not
provide electrical isolation or disconnection from the
supply.
• If isolation is required, the soft starter must be
installed with a main contactor.
• Do not rely on the start and stop functions for
safety of personnel. Faults occurring in the
mains supply, the motor connection, or the
electronics of the soft starter can cause
unintended motor starts or stops.
• If faults occur in the electronics of the soft
starter, a stopped motor may start. A temporary
fault in the supply mains or loss of motor
connection can also cause a stopped motor to
start.
To provide safety of personnel and equipment, control
the isolation device through an external safety system.
NOTICE
Before changing any parameter settings, save the current
parameter to a file using MCD PC Software or the Save
User Set function.
NOTICE
Use the autostart feature with caution. Read all the notes
related to autostart before operation.
3 Installation
3 3
177HA427.10
3
1 4
1 MCD5-0021B to MCD5-0215B: Allow 100 mm (3.94 in) between the soft starters.
MCD5-0245B to MCD5-0961B: Allow 200 mm (7.88 in) between the soft starters.
MCD5-0245C: Allow 100 mm (3.94 in) between the soft starters.
MCD5-0360C to MCD5-1600C: Allow 200 mm (7.88 in) between the soft starters.
2 MCD5-0021B to MCD5-0215B: Allow 50 mm (1.97 in) between the soft starter and solid surfaces.
MCD5-0245B to MCD5-0961B: Allow 200 mm (7.88 in) between soft starters.
MCD5-0245C: Allow 100 mm (3.94 in) between the soft starter and solid surfaces.
MCD5-0360C to MCD5-1600C: Allow 200 mm (7.88 in) between the soft starter and solid surfaces.
3 It is possible to mount the soft starter on its side. Derate the soft starter rated current by 15%.
4 If mounted without communication modules, soft starters may be mounted side by side with no clearance.
177HA514.10
C
3 3
A
A
B
B
D
C E
Model A [mm] (in) B [mm] (in) C [mm] (in) D [mm] (in) E [mm] (in) Weight [kg] (lbs)
MCD5-0021B
MCD5-0037B
183 (7.2) 4.2 (9.3)
MCD5-0043B
MCD5-0053B
295 (11.6) 278 (10.9) 150 (5.9) 124 (4.9)
MCD5-0068B 4.5 (9.9)
MCD5-0084B
213 (8.14)
MCD5-0089B 4.9 (10.8)
MCD5-0105B
MCD5-0131B
MCD5-0141B
438 (17.2) 380 (15.0) 275 (10.8) 248 (9.8) 250 (9.8) 14.9 (32.8)
MCD5-0195B
MCD5-0215B
MCD5-0245B 26 (57.2)
MCD5-0331B 440 (17.3) 392 (15.4) 424 (16.7) 376 (14.8) 296 (11.7)
30.2 (66.6)
MCD5-0396B
MCD5-0469B
49.5 (109.1)
MCD5-0525B
MCD5-0632B
640 (25.2) 600 (23.6) 433 (17.0) 320 (12.6) 295 (11.6)
MCD5-0744B
60.0 (132.3)
MCD5-0826B
MCD5-0961B
MCD5-0245C 460 (18.1) 400 (15.0) 390 (15.4) 320 (12.6) 279 (11.0) 23.9 (52.7)
MCD5-0360C
MCD5-0380C 35 (77.2)
MCD5-0428C
MCD5-0595C 689 (27.1) 522 (20.5) 430 (16.9) 320 (12.6) 300 (11.8)
MCD5-0619C
45 (99.2)
MCD5-0790C
MCD5-0927C
Model A [mm] (in) B [mm] (in) C [mm] (in) D [mm] (in) E [mm] (in) Weight [kg] (lbs)
MCD5-1200C
MCD5-1410C 856 (33.7) 727 (28.6) 585 (23.0) 500 (19.7) 364 (14.3) 120 (264.6)
MCD5-1600C
4 Electrical Installation
177HA504.10
Re s e t Re s e t Re s e t
18 18 18
1 2-wire control
2 3-wire control
3 4-wire control
NOTICE
4.1.5 Ground Terminal
Some units use aluminum busbars. When connecting 4 4
power terminations, clean the surface contact area
Ground terminals are at the back of the soft starter.
thoroughly (using an emery or stainless steel brush), and
use an appropriate jointing compound to prevent
• MCD5-0021B to MCD5-0105B have 1 terminal on corrosion.
the input side (top).
• MCD5-0131B to MCD5-0961B and MCD5-0245C to Use only copper stranded or solid conductors, rated for
MCD5-1600C have 2 terminals; 1 on the input 75 °C (167°F) or higher.
side (top), and 1 on the output side (bottom).
Cable size: 6–50 mm2 (AWG 10-1/0) 14 mm (0.55 in) Torx T20 x 150
177HA648.10
177HA646.10
177HA647.10
Flat 7 mm x 150
177HA649.10
MCD5-0021B to MCD5-0105B
38 Nm (336.3 in-lb)
11 mm
(M10)
177HA643.10
15 mm
28 mm 5 mm
11 mm
(M10) 11 mm
(M10)
177HA644.10
15 mm
177HA645.10
12 mm
28 mm 6 mm 32 mm 13 mm
177HA686.10
1/L1, 3/L2, 5/L3
NOTICE
When installing IP00 soft starters (MCB5-131B and
above), finger guards are specified for personnel safety.
Finger guards fit over the soft starter terminals to
prevent accidental contact with live terminals. Finger
guards provide IP20 protection when correctly installed.
177HA687.10
1/L1 3/L2 5/L3
• MCD5-0360C to MCD5-0927C: 175G5664.
• MCD5-1200C to MCD5-1600C: 175G5665.
NOTICE
To be UL-compliant, the models MCD5-0131B to
MCD5-0396B require finger guards.
177HA688.10
1/L1 3/L2 5/L3
busbars at both the top and bottom. The AC supply can
be connected:
• Top-in/bottom-out.
• Bottom-in/bottom-out
Internally bypassed models MCD5-0469B to MCD5-0961B
have input and output busbars at the top and bottom of
the unit. The AC supply can be connected:
• Top-in/bottom-out.
• Top-in/top-out.
• Bottom-in/bottom-out.
• Bottom-in/top-out.
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
177HA650.11
2/T1 4/T2 6/T3
20.0
terminals on the input busbars. The bypass terminals are:
• L1B.
• L2B.
• L3B.
The busbars on non-bypassed models MCD5-0360C to
MCD5-1600C can be adjusted for top or bottom input and 4 4
output as required. See chapter 12 Busbar Adjustment
Procedure (MCD5-0360C to MCD5-1600C) for step-by-step
instructions. The soft starters are manufactured top-in/
bottom-out.
NOTICE
For models MCD5-0360C to MCD5-1600C to be UL-
compliant, mount them top-in/bottom-out, or top-out/
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3 bottom-in. See chapter 11.1 UL-compliant Installation for
more information.
Illustration 4.6 MCD5-0469B to MCD5-0961B, 469–961 A
177HA652.10
1/L1 3/L2 5/L3
4.2.2 MCD5-0245C (L1B L2B L3B)
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
(L1B L2B L3B)
2/T1 4/T2 6/T3
MCD5-0245C has dedicated bypass terminals at the bottom
of the unit. The bypass terminals are:
• T1B.
• T2B.
• T3B.
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3 2/T1 4/T2 6/T3 (L1B L2B L3B)
(L1B L2B L3B) 1/L1 3/L2 5/L3
1/L1 3/L2 5/L3
177HA429.12
small motor for testing. During this test, the control input
and relay output protection settings can be tested. This
K1 F1 1/L1 2/T1
test mode is not suitable for testing soft starting or soft
stopping performance.
3/L2 4/T2 M
3
13
NOTICE 14
When testing the soft starter with a small motor, set
K1
parameter 1-1 Motor FLC to the minimum allowable
value.
Models which are internally bypassed do not require an
external bypass contactor. K1 Main contactor (optional)
F1 Semiconductor fuses (optional)1)
1) To keep the warranty on the SCRs, use semiconductor fuses.
4.3.2 In-line Installation
Illustration 4.10 In-line Installation, Non-bypassed
4.3.2.1 Internally Bypassed
K1 F1
1/L1 2/T1 Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
3/L2 4/T2 M protection and monitoring functions even when bypassed
3
via an external contactor. Connect the bypass contactor to
5/L3 6/T3 the bypass terminals and control it by a programmable
output configured to Run (see parameters 4-1 to 4-9).
E
NOTICE
13 The bypass terminals on MCD5-0245C are:
14
K1
• T1B.
• T2B.
• T3B.
K1 Main contactor (optional)
The bypass terminals on MCD5-0360C to MCD5-1600C
F1 Semiconductor fuses (optional)1)
are:
1) To keep the warranty on the SCRs, use semiconductor fuses.
• L1B.
Illustration 4.9 In-line Installation, Internally Bypassed • L2B.
• L3B.
If necessary, the fuses can be installed on the input side.
NOTICE
K1 F1 When connecting the VLT® Soft Starter MCD 500 in
1/L1 2/T1
inside delta configuration, always install a main
T1B
3/L2 4/T2 M
contactor or shunt trip circuit breaker.
3
T2B
5/L3 6/T3
NOTICE
E
T3B
When connecting in inside delta, enter the motor full 4 4
13 load current (FLC) in parameter 1-1 Motor FLC. The MCD
14 500 automatically calculates inside delta currents based
33
K1 on this data. Parameter 15-7 Motor Connection is set to
34 Auto detect as default and can be set to force the soft
177HA617.11
K1 F1
Illustration 4.11 In-line Installation, Externally Bypassed, 1/L1 2/T
13
177HA501.11
14
K1 F1
1/L1 2/T1 K1
L1B
L3B
1) To keep the warranty on the SCRs, use semiconductor fuses.
E
13 Illustration 4.13 Inside Delta Installation, Internally Bypassed
14
K1
33
34
177HA431.12
K2
K1 Main contactor
K2 Bypass contactor (external)
F1 Semiconductor fuses (optional)1)
1) To keep the warranty on the SCRs, use semiconductor fuses.
4.3.3.2 Non-bypassed
K2
K1 F
1/L 2/T K1 F1
1/L1 2/T
L1 U1(1 U2(4
T1B U1(1) U2(4)
3/L 4/T V1(2 M V2(5 3/L2 4/T V1(2) M V2(5)
3 3
L2 W1( W2(
4 4
T2B W1(3) W2(6)
L3 T3B
E E
13
1
14
177HA500.12
1
K1
33
K1
177HA618.11
34
K2
K1 Main contactor
F1 Semiconductor fuses (optional)1)
1) To keep the warranty on the SCRs, use semiconductor fuses. K1 Main contactor
K2 Bypass contactor (external)
Illustration 4.14 Inside Delta Installation, Non-bypassed F1 Semiconductor fuses (optional)1)
1) To keep the warranty on the SCRs, use semiconductor fuses.
4.3.3.3 Externally Bypassed Illustration 4.15 Inside Delta Installation, Externally Bypassed,
MCD5-0245C
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external bypass contactor. Connect the bypass
contactor to the bypass terminals and control the K2
NOTICE K1
1/L1 2/T
F1
• T1B. L2B
5/L3 6/T
W1(3)
3
W2(6)
• T2B. L3B
•
E
T3B. 13
14
The bypass terminals on MCD5-0360C to MCD5-1600C K1
33
are:
177HA502.12
34
• L1B. K2
• L2B.
• L3B. K1 Main contactor
K2 Bypass contactor (external)
If necessary, the fuses can be installed on the input side.
F1 Semiconductor fuses (optional)1)
1) To keep the warranty on the SCRs, use semiconductor fuses.
4 4
NOTICE
Models MCD5-0021B to MCD5-0961B are internally bypassed. Models MCD5-0245C to MCD5-1600C require an external
bypass contactor.
a
a
rt s
rt
Tim
Pe
r
e(
Ho
se
u
r
co
n
ds
)
All ratings are calculated at an altitude of 1000 m (3281 ft) and ambient temperature of 40 °C (104 °F).
Contact a local supplier for ratings under operating conditions not covered by these ratings charts.
NOTICE
Models MCD5-0021B to MCD5-0961B are internally bypassed. Models MCD5-0245C to MCD5-1600C require an external
bypass contactor.
a
a
rt s
rt
Tim
Pe
r
e(
Ho
se
ur
co
nds
)
All ratings are calculated at an altitude of 1000 m (3281 ft) and ambient temperature of 40 °C (104 °F).
Contact a local supplier for ratings under operating conditions not covered by these ratings charts.
4 4 MCD5-0043B
MCD5-0053B
10
11
50
53
15
16
75
79
MCD5-0068B 15 76 23 114
MCD5-0084B 19 97 29 145
MCD5-0089B 20 100 30 150
MCD5-0105B 21 105 32 157
MCD5-0131B 29 145 44 217
MCD5-0141B 34 170 51 255
MCD5-0195B 40 200 60 300
MCD5-0215B 44 220 66 330
MCD5-0331B 70 350 70 525
MCD5-0396B 85 425 85 638
MCD5-0469B 100 500 100 750
MCD5-0525B 116 580 116 870
MCD5-0632B 140 700 140 1050
MCD5-0744B 164 820 164 1230
MCD5-0825B 184 920 184 1380
MCD5-0961B 200 1000 200 1500
MCD5-0245C 51 255 77 382
MCD5-0360C 72 360 108 540
MCD5-0380C 76 380 114 570
MCD5-0428C 86 430 129 645
MCD5-0595C 124 620 186 930
MCD5-0619C 130 650 195 975
MCD5-0790C 158 790 237 1185
MCD5-0927C 186 930 279 1395
MCD5-1200C 240 1200 360 1800
MCD5-1410C 282 1410 423 2115
MCD5-1600C 320 1600 480 2400
4.9 Power Factor Correction For applications using adaptive control to soft stop the
motor with stop times greater than 30 s, select motor
HRC fuses (such as Ferraz AJT fuses) can be used for Type
1 coordination according to the IEC 60947-4-2 standard.
NOTICE
Adaptive control regulates the speed profile of the motor
within the programmed time limit. This control may
result in a higher level of current than traditional control
methods.
Model SCR I2t (A2s) Supply voltage Supply voltage Supply voltage
(≤440 V AC) (≤575 V AC) (≤690 V AC)
MCD5-0021B 1150 170M1314 170M1314 170M1314
MCD5-0037B 8000 170M1316 170M1316 170M1316
MCD5-0043B 10500 170M1318 170M1318 170M1318
MCD5-0053B 15000 170M1318 170M1318 170M1318
4 4 MCD5-0068B
MCD5-0084B
15000
512000
170M1319
170M1321
170M1319
170M1321
170M1318
170M1319
MCD5-0089B 80000 170M1321 170M1321 170M1321
MCD5-0105B 125000 170M1321 170M1321 170M1321
MCD5-0131B 125000 170M1321 170M1321 170M1321
MCD5-0141B 320000 170M2621 170M2621 170M2621
MCD5-0195B 320000 170M2621 170M2621 170M2621
MCD5-0215B 320000 170M2621 170M2621 170M2621
MCD5-0245B 320000 170M2621 170M2621 170M2621
MCD5-0331B 202000 170M5011 170M5011 –
MCD5-0396B 320000 170M6011 – –
MCD5-0469B 320000 170M60081) – –
MCD5-0525B 781000 170M6013 170M6013 170M6013
MCD5-0632B 781000 170M5015 170M5015 –
MCD5-0744B 1200000 170M5017 170M6017 –
MCD5-0826B 2530000 170M6017 170M6017 –
MCD5-0961B 2530000 170M6018 170M60131) –
MCD5-0245C 320000 170M2621 170M2621 170M2621
MCD5-0360C 320000 170M6010 170M6010 170M6010
MCD5-0380C 320000 170M6011 170M6011 –
MCD5-0428C 320000 170M6011 170M6011 –
MCD5-0595C 1200000 170M6015 170M6015 170M6014
MCD5-0619C 1200000 170M6015 170M6015 170M6014
MCD5-0790C 2530000 170M6017 170M6017 170M6016
MCD5-0927C 4500000 170M6019 170M6019 170M6019
MCD5-1200C 4500000 170M6021 – –
MCD5-1410C 6480000 – – –
MCD5-1600C 12500000 170M60191) – –
Model SCR I2t (A2s) Supply voltage Supply voltage Supply voltage
(<440 V AC) (<575 V AC) (<690 V AC)
MCD5-0021B 1150 63FE 63FE 63FE
MCD5-0037B 8000 120FEE 120FEE 120FEE
MCD5-0043B 10500 120FEE 120FEE 120FEE
MCD5-0053B 15000 200FEE 200FEE 200FEE
MCD5-0068B 15000 200FEE 200FEE 200FEE
MCD5-0084B 512000 200FEE 200FEE 200FEE
MCD5-0089B
MCD5-0105B
80000
125000
280FM
280FM
280FM
280FM
280FM
280FM
4 4
MCD5-0131B 125000 280FM 280FM 280FM
MCD5-0141B 320000 450FMM 450FMM 450FMM
MCD5-0195B 320000 450FMM 450FMM 450FMM
MCD5-0215B 320000 450FMM 450FMM 450FMM
MCD5-0245B 320000 450FMM 450FMM 450FMM
MCD5-0331B 202000 315FM1) – –
MCD5-0396B 320000 400FMM1) – –
MCD5-0469B 320000 450FMM1) – –
MCD5-0525B 781000 500FMM1) 500FMM1) 500FMM1)
MCD5-0632B 781000 630FMM1) – –
MCD5-0744B 1200000 – – –
MCD5-0826B 2530000 – – –
MCD5-0961B 2530000 – – –
MCD5-0245C 320000 450FMM 450FMM 450FMM
MCD5-0360C 320000 – – –
MCD5-0380C 320000 400FMM1) 400FMM 400FMM1)
MCD5-0428C 320000 – – –
MCD5-0595C 1200000 630FMM1) 630FMM1) –
MCD5-0619C 1200000 630FMM1) 630FMM1) –
MCD5-0790C 2530000 – – –
MCD5-0927C 4500000 – – –
MCD5-1200C 4500000 – – –
MCD5-1410C 6480000 – – –
MCD5-1600C 12500000 – – –
Model SCR I2t (A2s) Supply voltage Supply voltage Supply voltage
(<440 V AC) (<575 V AC) (<690 V AC)
MCD5-0021B 1150 HSJ401) HSJ401)
MCD5-0037B 8000 HSJ801) HSJ801)
MCD5-0043B 10500 HSJ901) HSJ901)
MCD5-0053B 15000 HSJ1101) HSJ1101)
4 4 MCD5-0068B
MCD5-0084B
15000
51200
HSJ1251)
HSJ175
HSJ1251)
HSJ1751)
MCD5-0089B 80000 HSJ175 HSJ175
MCD5-0105B 125000 HSJ225 HSJ225
MCD5-0131B 125000 HSJ250 HSJ2501)
MCD5-0141B 320000 HSJ300 HSJ300
MCD5-0195B 320000 HSJ350 HSJ350
MCD5-0215B 320000 HSJ4001) HSJ4001)
MCD5-0245B 320000 HSJ4501) HSJ4501)
MCD5-0331B 202000 HSJ5001)
MCD5-0396B 320000
MCD5-0469B 320000 Not applicable
MCD5-0525B 781000
Not applicable
MCD5-0632B 781000 Not applicable
MCD5-0744B 1200000
MCD5-0826B 2530000
MCD5-0961B 2530000
MCD5-0245C 320000 HSJ4501) HSJ4501)
MCD5-0360C 320000
MCD5-0380C 320000
MCD5-0428C 320000
MCD5-0595C 1200000
MCD5-0619C 1200000
Not applicable Not applicable
MCD5-0790C 2530000
MCD5-0927C 4500000
MCD5-1200C 4500000
MCD5-1410C 6480000
MCD5-1600C 12500000
Model SCR I2t (A2s) Supply voltage Supply voltage Supply voltage
(<440 V AC) (<575 V AC) (<690 V AC)
MCD5-0021B 1150 A070URD30XXX0063 A070URD30XXX0063 –
MCD5-0037B 8000 A070URD30XXX0125 A070URD30XXX0125 A070URD30XXX0125
MCD5-0043B 10500 A070URD30XXX0125 A070URD30XXX0125 A070URD30XXX0125
MCD5-0053B 15000 A070URD30XXX0125 A070URD30XXX0125 A070URD30XXX0125
MCD5-0068B 15000 A070URD30XXX0160 A070URD30XXX0160 A070URD30XXX0160
MCD5-0084B 51200 A070URD30XXX0200 A070URD30XXX0200 A070URD30XXX0200
MCD5-0089B
MCD5-0105B
80000
125000
A070URD30XXX0200
A070URD30XXX0315
A070URD30XXX0200
A070URD30XXX0315
A070URD30XXX0200
A070URD30XXX0315
4 4
MCD5-0131B 125000 A070URD30XXX0315 A070URD30XXX0315 A070URD30XXX0315
MCD5-0141B 320000 A070URD30XXX0315 A070URD30XXX0315 A070URD30XXX0315
MCD5-0195B 320000 A070URD30XXX0450 A070URD30XXX0450 A070URD30XXX0450
MCD5-0215B 320000 A070URD30XXX0450 A070URD30XXX0450 A070URD30XXX0450
MCD5-0245B 32000 A070URD30XXX0450 A070URD30XXX0450 A070URD30XXX0450
MCD5-0331B 202000 A070URD31XXX0550 – –
MCD5-0396B 238000 A070URD32XXX0630 – –
MCD5-0469B 320000 A070URD32XXX0700 – –
MCD5-0525B 781000 A070URD32XXX0800 – –
MCD5-0632B 781000 A070URD33XXX0900 – –
MCD5-0744B 1200000 A070URD33XXX1100 – –
MCD5-0826B 2530000 A070URD33XXX1250 – –
MCD5-0961B 2530000 A070URD33XXX1400 – –
MCD5-0245C 320000 A070URD30XXX0450 A070URD30XXX0450 A070URD30XXX0450
MCD5-0360C 320000 A070URD33XXX0630 A070URD33XXX0630 A070URD33XXX0630
MCD5-0380C 320000 A070URD33XXX0700 A070URD33XXX0700 –
MCD5-0428C 320000 A070URD33XXX0700 A070URD33XXX0700 –
MCD5-0595C 1200000 A070URD33XXX1000 A070URD33XXX1000 A070URD33XXX1000
MCD5-0619C 1200000 A070URD33XXX1000 A070URD33XXX1000 A070URD33XXX1000
MCD5-0790C 2530000 A070URD33XXX1400 A070URD33XXX1400 A070URD33XXX1400
MCD5-0927C 4500000 A070URD33XXX1400 A070URD33XXX1400 A070URD33XXX1400
MCD5-1200C 4500000 A055URD33XXX2250 – –
MCD5-1410C 6480000 A055URD33XXX2250 – –
MCD5-1600C 12500000 - – –
4 4 MCD5-0245C
MCD5-0360C
320000
320000
6.9URD31D11A0450
6.9URD33D11A0630
6.9URD31D11A0450
6.9URD33D11A0630
6.9URD31D11A0450
6.9URD33D11A0630
MCD5-0380C 320000 6.9URD33D11A0700 6.9URD33D11A0700 6.9URD33D11A0700
MCD5-0428C 320000 6.9URD33D11A0700 6.9URD33D11A0700 6.9URD33D11A0700
MCD5-0595C 1200000 6.9URD33D11A1000 6.9URD33D11A1000 6.9URD33D11A1000
MCD5-0619C 1200000 6.9URD33D11A1000 6.9URD33D11A1000 6.9URD33D11A1000
MCD5-0790C 2530000 6.6URD33D11A1400 6.6URD33D11A1400 –
MCD5-0927C 4500000 6.6URD33D11A1400 6.6URD33D11A1400 –
MCD5-1200C 4500000 6URD233PLAF2200 6URD233PLAF2200 –
MCD5-1410C 6480000 6URD233PLAF2200 6URD233PLAF2200 –
MCD5-1600C 12500000 6URD233PLAF2800 6URD233PLAF2800 –
Two short-circuit current ratings (SCCR) are available for UL-compliant applications.
177HA425.10
1/L1 2/T1
3/L2 4/T2
5/L3 6/T3
4 4
E
A4 13
A5 14
1
A6 21
22
07 5
A 08 24
24
2
11 V DC 33
34
16 +
15
17 3
18
25
05
06 4
177HA426.12
1/L1 1) 2/T1
L1B
3/L2 1) 4/T2
L2B
5/L3 1) 6/T3
4 4 L3B
A4 13
A5 14
1
A6 21
22
07+ 5
A 08 24
24
2
11 V DC 33
34
16 +
15
17 3
18
25
05
06 4
1) MCD5-0245C current transformers are placed on the output. Bypass terminals are labeled T1B, T2B, and T3B.
5 Product Features
177HA596.10
- Iron losses. 10000
177HA289.11
100% 1
start current must be kept below a specific level.
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
700% 3 Time
Current (% motor full load current)
500%
2 Parameter 1-6 Start ramp time
3 Parameter 1-4 Current limit
400% 2 4 Full voltage current
300%
1 Illustration 5.3 Example of a 10 s Current Ramp Time
200%
177HA289.11
100%
5.3.3 Adaptive Control
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Rotor speed (% full speed) In an adaptive control soft start, the soft starter adjusts the
current to start the motor within a specified time and uses
1 Parameter 1-5 Initial current a selected acceleration profile.
2 Parameter 1-4 Current limit
3 Full voltage current NOTICE
Adaptive control cannot start the motor faster than a
Illustration 5.2 Example of Constant Current direct on-line (DOL) start. If the time set in parameter 1-6
Start ramp time is shorter than the motor DOL start time,
starting current may reach DOL levels.
5.3.2 Current Ramp
Every application has a particular starting profile based on
Current ramp soft starting raises the current from a characteristics of the load and the motor. To meet the
specified starting level (1) to a maximum limit (3), over an requirements of different applications, adaptive control
extended period (2), see Illustration 5.3. offers 3 different starting profiles. Selecting a profile that
matches the inherent profile of the application can help
Current ramp starting can be useful for applications where: smooth out acceleration across the full start time. Selecting
• The load can vary between starts (for example a a different adaptive control profile can neutralize the
conveyor, which may start loaded or unloaded). inherent profile to some extent.
50%
200%
3
177HA508.10
40%
2 100%
30%
20%
177HA507.10
3
10% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
0 Rotor speed (% full speed)
Time
NOTICE
Adaptive control regulates the load according to the
5.4 Stopping Modes
programmed profile. Start current varies according to the
selected acceleration profile and the programmed start 5.4.1 Coast to Stop
time.
The soft starter has to learn the characteristics of a new Coast to stop lets the motor slow at its natural rate, with
motor: no control from the soft starter. The time required to stop
• If replacing a motor connected to a soft starter depends on the type of load.
programmed for adaptive control starting or
stopping. 5.4.2 TVR Soft Stop
• If the soft starter has been tested on a different
motor before actual installation. Timed voltage ramp reduces the voltage to the motor
gradually over a defined time. The load may continue to
If parameter 1-1 Motor Full Load Current or parameter
run after the stop ramp is complete.
1-12 Adaptive Control Gain is changed, the soft starter
automatically relearns the motor characteristics.
Timed voltage ramp stopping can be useful for
applications where the stop time has to be extended, or to
avoid transients on generator-set supplies.
177HA509.10
• If the soft starter has been tested on a different
Time motor before actual installation.
1 Parameter 1-11 Stop Time If parameter 1-1 Motor Full Load Current or parameter
1-12 Adaptive Control Gain is changed, the soft starter
Illustration 5.6 TVR Soft Stop automatically relearns the motor characteristics.
50%
reverse flow.
40% Constant Low to medium head, high-flow
30% deceleration applications, where the fluid has high
20%
momentum.
177HA510.10
10%
0
Early deceleration Open pump systems, where fluid must drain
Time back through the pump without driving the
1 Early deceleration pump in reverse.
2 Constant deceleration
Table 5.1 Selection of Adaptive Control Deceleration Profiles
3 Late deceleration
4 Parameter 1-10 Stop Time
5.4.5 Brake
Illustration 5.7 Parameter 1-14 Adaptive Stop Profile
A brake reduces the required stop time of the motor.
CAUTION too low, the motor does not stop completely and
coasts to stop by the end of the braking period.
EQUIPMENT DAMAGE
100%
If the brake torque is set too high, the motor stops
before the end of the brake time. The motor suffers
unnecessary heating, which could result in damage.
Careful configuration is required to ensure safe operation 70%
of the soft starter and the motor. 3
A high brake torque setting can result in peak currents
Speed
up to motor DOL being drawn while the motor is
30%
stopping. Ensure that protection fuses installed in the
motor branch circuit are selected appropriately.
0%
5 5
CAUTION
177HA511.10
2
1
RISK OF OVERHEATING Time
Brake operation causes the motor to heat faster than the
rate calculated by the motor thermal model. If using 1 Parameter 1-11 Stop Time
brake functionality, install a motor thermistor or allow 2 Parameter 1-16 Brake Time
sufficient restart delay (parameter 2-11 Restart Delay). 3 Coast to stop time
When brake is selected, the soft starter uses DC injection Illustration 5.8 Brake Time
to slow the motor.
Braking
NOTICE
• Does not require the use of a DC brake contactor.
When using DC brake:
• Controls all 3 phases so that the braking currents
1. Connect the mains supply to the soft starter
and associated heating are evenly distributed
(input terminals L1, L2, L3) in positive phase
through the motor.
sequence.
Braking has 2 stages:
2. Set parameter 2-1 Phase Sequence to Positive
1. Prebrake: Provides an intermediate level of
only.
braking to slow motor speed to a point where
full brake can be operated successfully (approxi-
mately 70% speed). NOTICE
2. Full brake: Provides maximum braking torque but For loads which may vary between braking cycles, install
is ineffective at speeds greater than approxi- a zero-speed sensor to ensure that the soft starter ends
mately 70%. DC braking when the motor stops. This installation
avoids unnecessary heating of the motor.
To configure the VLT® Soft Starter MCD 500 for brake
operation:
1. Set parameter 1-11 Stop Time for the wanted For more information on using the MCD 500 with an
stopping time duration (1), see Illustration 5.8. The external speed sensor (for example for applications with
stop time is the total brake time. Set the stop variable load during the braking cycle), see chapter 5.12 DC
time sufficiently longer than the brake time Brake with External Zero-speed Sensor.
(parameter 1-16 Brake Time) to allow the 5.5 Jog Operation
prebraking stage to reduce motor speed to
approximately 70%. If the stop time is too short, Jog runs the motor at reduced speed to allow alignment
braking is not successful and the motor coasts to of the load or to assist servicing. The motor can be jogged
stop. in either forward or reverse direction.
2. Set parameter 1-16 Brake Time to approximately
25% of the programmed stop time. The brake The maximum available torque for jog forward is approxi-
time sets the time for the full brake-stage (2), see mately 50–75% of motor full load torque (FLT) depending
Illustration 5.8. on the motor. When the motor is jogged in reverse, the
torque is approximately 25–50% of FLT. Parameter 15-8 Jog
3. Adjust parameter 1-15 Brake Torque so that the
Torque controls how much of the maximum available jog
wanted stopping performance is achieved. If set
torque the soft starter applies to the motor.
NOTICE CAUTION
Setting parameter 15-8 Jog Torque above 50% may cause
REDUCED MOTOR COOLING
increased shaft vibration.
Slow speed running is not intended for continuous
operation due to reduced motor cooling. Jog operation
100%
causes the motor to heat faster than the rate calculated
90% by the motor thermal model.
80%
• If using jog, install a motor thermistor, or allow
70% sufficient restart delay (parameter 2-11 Restart
60% 3 3 Delay).
50%
5 5 40%
30%
5.6 Inside Delta Operation
1 Adaptive control, jog, and brake functions are not
20%
supported in inside delta (6-wire) operation. If these
10%
functions are programmed when the soft starter is
0%
177HA512.11 connected inside delta, the behavior is as in Table 5.2:
10%
20% Adaptive The soft starter performs a constant current start.
2
30% control
40% start
50% Adaptive If stop time is >0 s, the starter performs a TVR soft
control stop. If stop time is set to 9 s, the starter performs a
1 Jog forward stop coast to stop.
2 Jog reverse Jog The soft starter issues a warning with the error
message Unsupported Option.
3 Normal operation
Brake The starter performs a coast to stop.
Illustration 5.9 Jog Operation Table 5.2 Inside Delta Behavior at Adaptive Control, Jog,
and Brake
NOTICE
Soft start and soft stop are not available during jog
operation. Jog is only available for the primary motor.
To determine the typical start current for an application, Dryer 4.5 x FLC
use this information. Repulper 4.5 x FLC
Shredder 4.5 x FLC
NOTICE Table 5.6 Typical Start Currents for Pulp and Paper Applications
These start current requirements are appropriate and
typical in most circumstances. However, the performance Petrochemical
and start torque requirements of motors and machines
do vary. For further assistance, contact the local Danfoss Ball mill 4.5 x FLC
supplier. Centrifuge 4.0 x FLC
Food processing
K1 F
1/L1 2/T1
5 5
3/L2 4/T2
6 7
5/L3 6/T3
A4 13
A5 14
1
A6 21 K1
22
07
+ 5
A 08 24
24 2
11 VD 33
34
16 +
15
17
S1 3
18
S2 25
05
06 4
177HA522.1
Parameter settings:
• Parameter 4-1 Relay A Function
- Select Main contactor - assigns the main contactor function to relay output A (default value).
K1
F1
1/L1 2/T1
5 5
L1B
6 3/L2 4/T2 7
L2B
5/L3 6/T3
L3B
A4 13
A5 14
1
A6 21
22
07
+ 5
A 08 24
24 2 K1
11 VD 33
34
16 +
S1 15
17
S2 3
18
S3 25
05
06 4
177HA523.1
Parameter settings:
• Parameter 4-4 Relay B Function.
- Select Run - assigns the run output function to output relay B (default value).
A 2-wire circuit connected to input A (terminals 11, 16) controls emergency run. Closing input A causes the soft starter to
run the motor and ignore all trip conditions.
K1 F
1/L1 2/T1
5 5 6
3/L2 4/T2
7
5/L3 6/T3
A4 13
A5 14
1
A6 21
22
07
+ 5
A 08 24
24 2
11 VD 33
S3
34
16 +
15
17
S1 3
18
S2 25
05
06 4
177HA524.1
Parameter settings:
• Parameter 3-3 Input A Function.
- Select Emergency Run - assigns input A to emergency run function.
• Parameter 15-3 Emergency Run.
NOTICE
Although Emergency run fulfills the functionality requirements of fire mode, Danfoss does not recommend its use in
situations that require testing and/or compliance with specific standards as it is not certified.
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low-pressure alarm switch for a pumping
system). When the external circuit activates, the soft starter trips and stops the motor. 5 5
K1 F
1/L1 2/T1
3/L2 4/T2
6 7
5/L3 6/T3
A4 13
A5 14
1
A6 21
22
07
+ 5
A 08 24
24 2
VD 33
S3 11
34
16 +
15
17
S1 3
18
S2 25
05
06 4
177HA525.1
Parameter settings:
• Parameter 3-3 Input A Function.
- Select Input Trip (N/O) - assigns input A to auxiliary trip (N/O) function.
• Parameter 3-4 Input A Name.
- Select a name, for example Low Pressure - assigns a name to input A.
• Parameter 3-8 Remote Reset Logic.
- Select as required, for example Normally Closed - the input behaves like a normally closed contact.
Sensor
5 5
L1 L2 L3 N E
with the VLT® Soft Starter MCD 500 for brake shut-off. This
6
control method ensures that the MCD 500 braking always
shuts off when the motor has reached a standstill, thus L1 L2 L3 E A4 A5 A6 15 16 17 18 25
5
avoiding unnecessary motor heating. 1
2
177HA619.20
T1 T2 T3 11 16 -K10 -K11
speed and closed at any speed above 0 speed. Once the -K10
NOTICE
When using DC brake, connect the mains supply to the
soft starter (input terminals L1, L2, L3) in positive phase
sequence. Then set parameter 2-1 Phase Sequence to
Positive only.
In this application, the MCD 500 is employed with forward run and braking contactors. When the soft starter receives a start
signal (push-button S1), it closes the forward run contactor (K1) and controls the motor according to the programmed
primary motor settings.
When the soft starter receives a stop signal (push-button S2), it opens the forward run contactor (K1) and closes the braking
contactor (K2) after a delay of approximately 2–3 s (KT1). K12 is also closed to activate the secondary motor settings, which
are user-programmed for the wanted stopping performance characteristics.
When motor speed approaches 0, the external zero-speed sensor (A2) stops the soft starter and opens the braking contactor
5 5
(K2).
5
F1
1 3
3
64
6 2
2/T1 4/T2 6/T3 E 54 55 56 57 58 34
53
K12 K11 S3
K2 K1
Y2 Y2
177HA526.12
K1 K2 K10 K11 K12 K13
M1
Parameter settings:
• Parameter 3-3 Input A Function.
- Select Motor Set Select - assigns input A for motor set selection.
- Set starting performance characteristics using the primary motor set (parameter group 1 Primary Motor
Settings).
- Set braking performance characteristics using the secondary motor settings (parameter group 7 Secondary
Motor Set).
• Parameter 4-7 Relay C Function.
- Select Trip - assigns trip function to output relay C.
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the braking contactor K2 opens, modify
the settings of parameters 2-8 to 2-10.
NOTICE
Pole amplitude modulated (PAM) motors alter the speed by effectively changing the stator frequency using external
winding configuration. Soft starters are not suitable for use with this type of 2-speed motor.
When the soft starter receives a high-speed start signal, it closes the high-speed contactor (K1) and star contactor (K3). Then
it controls the motor according to the primary motor settings (parameters 1-1 to 1-16).
When the soft starter receives a low-speed start signal, it closes the low-speed contactor (K2). This action closes input A and
the soft starter controls the motor according to the secondary motor settings (parameters 7-1 to 7-16).
NOTICE
If the soft starter trips on supply frequency (16-5 Frequency) when the high-speed start signal (7) is removed, modify the
settings of parameters 2-8 to 2-10.
K3
T4
T5
T6
F1
K2
T1
5
1/L1 2/T1
4 3/L2 4/T2
T2
T3
5/L3 6/T3
K1
E
A4
A5
A6
1 K3 K1
5 5
11 K11 K2 K3
K10 21
16 24
3 K10 K3 K1
15 22
K1
K2
K2 17 2
18 K11
177HA527.1
S1 25 6 K10
K10
7 K11
1 Control voltage 6 Remote low-speed start input K2 Line contactor (low speed)
2 Remote control inputs 7 Remote high-speed start input K3 Star contactor (high speed)
3 Relay outputs K10 Remote start relay (low speed) S1 Reset contact
4 3-phase supply K11 Remote start relay (high speed) 21, 22, 24 Relay output B
5 Motor terminals K1 Line contactor (high speed)
NOTICE
Contactors K2 and K3 must be mechanically interlocked.
Parameter settings:
• Parameter 3-3 Input A Function.
- Select Motor Set Select - assigns input A for motor set selection.
- Set high-speed performance characteristics using parameters 1-1 to 2-9.
- Set low-speed performance characteristics using parameters 7-1 to 7-16.
• Parameter 4-4 Relay B Function.
- Select Trip - assigns trip function to relay output B.
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the high-speed signal (7) is removed,
modify the settings of parameters 2-9 to 2-10.
6 Operation
Control functions
• Local control is only available in hand-on mode.
• Remote control is only available in auto-on mode.
6 6 • Control via the serial communication network is always disabled in hand-on mode. Enable or disable start/stop
commands via the serial network in auto-on mode by changing the setting of parameter 3-2 Comms in Remote.
The MCD 500 can also be configured to autostart or autostop. Autostart/stop operation is only available in auto-on mode. In
hand-on mode, the soft starter ignores any autostart/stop setting. To configure autostart/stop operation, set parameters 5-1
to 5-4.
To switch between hand-on mode and auto-on mode, press the keys on the LCP.
• [Hand On]: Start the motor and enter hand-on mode.
• [Off]: Stop the motor and enter hand-on mode.
• [Auto On]: Set the soft starter to auto-on mode.
• [Reset]: Reset a trip (hand-on mode only).
The MCD 500 can also be set to allow local control only or remote control only, using parameter 3-1 Local/Remote.
If parameter 3-1 Local/Remote is set to Remote Control Only, the [Off] key is disabled. Stop the motor by remote control or via
the serial communication network.
Table 6.1 Start, Stop, and Reset in Hand-on Mode and Auto-on Mode
To stop the motor with a coast to stop, regardless of the setting in parameter 1-10 Stop Mode, press [Off] and [Reset] at the
same time. The soft starter removes power from the motor and opens the main contactor, and the motor coasts to stop.
NOTICE
Brake and jog functions operate only with in-line connected motors (see chapter 5.6 Inside Delta Operation).
177HA383.10
In hand-on mode:
• To soft start the motor, press [Hand On] on the
LCP. 1
[▲]/[▼]:
The first time an LCP is plugged into a soft starter, the soft
Third display line: Software versions for remote LCP, control software,
starter copies its parameter settings to the LCP.
model software.
Fourth display line: Product model number.
Ready S1
6.6.7 Last Start Information (S7)
MS1 000.0A 000.0kW
Primary Motor Set
The last start information screen shows details of the most
M1 000%
recent successful start:
• Start duration, (s).
6.6.2 Programmable Screen (S2)
• Maximum start current drawn (as a percentage of
motor full load current).
The user-programmable screen of the soft starter can be
configured to show the most important information for the • Calculated rise in motor temperature.
particular application. Use parameters 8-2 to 8-5 to select
Ready S7
which information to show.
MS1 000.0A 000.0kW
Last start 000 s
Ready S2
000% FLC ΔTemp 0%
MS1 000.0A 000.0kW
-.-- pf
00000 hrs 6.6.8 Date and Time (S8)
The date and time screen shows the current system date
6.6.3 Average Current (S3)
and time (24-hour format). For details on setting the date
and time, see chapter 9.1 Set Date and Time.
The average current screen shows the average current of
all 3 phases.
Ready S8
MS1 000.0A 000.0kW
Ready S3
YYYY MMM DD
MS1 000.0A 000.0kW
HH:MM:SS
0.0A
Ready S4
MS1 000.0A 000.0kW
Phase currents
000.0A 000.0A 000.0A
177HA513.10
Illustration 6.2 Bar Graph
NOTICE
The soft starter does not collect data while the graph is
paused. When graphing resumes, a small gap is shown
between the old data and the new data.
7 Programming
2. Press [▲] and [▼] to change the value. 1-6 Start Ramp Time
1-9 Excess Start Time
3. When all 4 digits match the access code, press
1-10 Stop Mode
[OK].
1-11 Stop Time
The LCP shows an acknowledgement message before 2 Protection
continuing. 2-1 Phase Sequence
2-4 Undercurrent
Enter Access Code 2-5 Undercurrent Dly
#### 2-6 Inst Overcurrent
OK 2-7 Inst Overcurrent Dly
Access Allowed 3 Inputs
SUPERVISOR 3-3 Input A Function
3-4 Input A Name
To change the access code, use parameter 15-1 Access Code. 3-5 Input A Trip
3-6 Input A Trip Dly
NOTICE 3-7 Input A Initial Dly
The security access code also protects the protection 4 Outputs
simulation and output simulation. The counters and 4-1 Relay A Function
thermal model reset can be viewed without entering an 4-2 Relay A On Delay
access code, but an access code must be entered to 4-3 Relay A Off Delay
reset. 4-4 Relay B Function
The default access code is 0000. 4-5 Relay B On Delay
4-6 Relay B Off Delay
To prevent users from altering parameter settings, lock the 4-7 Relay C Function
menus. The adjustment lock can be set to allow Read & 4-8 Relay C On Delay
Write, Read Only, or No Access in parameter 15-2 Adjustment 4-9 Relay C Off Delay
Lock. 4-10 Low Current Flag
4-11 High Current Flag
If attempting to change a parameter value or access the 4-12 Motor Temp Flag
Main Menu when the adjustment lock is active, an error 5 Start/Stop Timers
message is shown: 5-1 Auto-Start Type
5-2 Auto-Start Time
Access Denied 5-3 Auto-Stop Type
Adj Lock is On
Compressor screw
7.2.2 Application Set-up Examples
Motor full load current
The application set-ups menu makes it easy to configure Start mode Constant current
the soft starter for common applications. The soft starter Start ramp time 5s
selects the parameters relevant to the application and Current limit 400%
suggests a typical setting. Each parameter can be adjusted
7 7 to suit the exact requirements. Table 7.6 Suggested Values for Compressor Screw Applications
Compressor recip
On the display, the highlighted values are suggested
values. The values indicated by ▶ are the loaded values. Motor full load current
Start mode Constant current
Always set parameter 1-1 Motor FLC to match the motor Start ramp time 10 s
nameplate full load current. The suggested value for motor Current limit 450%
FLC is the minimum FLC of the soft starter.
Table 7.7 Suggested Values for Compressor Recip Applications
Centrifugal pump
Conveyor
Motor full load current
Start mode Adaptive control Motor full load current
Adaptive start profile Early acceleration Start mode Constant current
Start ramp time 10 s Start ramp time 5s
Stop mode Adaptive control Current limit 400%
Adaptive stop profile Late deceleration Stop mode Adaptive control
Stop time 15 s Adaptive stop profile Constant deceleration
Stop time 10 s
Table 7.2 Suggested Values for Centrifugal Pump Applications
Table 7.8 Suggested Values for Conveyor Applications
Submersible pump
Crusher rotary
Motor full load current
Start mode Adaptive control Motor full load current
Adaptive start profile Early acceleration Start mode Constant current
Start ramp time 5s Start ramp time 10 s
Stop mode Adaptive control Current limit 400%
Adaptive stop profile Late deceleration Excess start time 30 s
Stop time 5s Locked rotor time 20 s
Table 7.3 Suggested Values for Submersible Pump Applications Table 7.9 Suggested Values for Crusher Rotary Applications
Damped fan
Table 7.10 Suggested Values for Crusher Jaw Applications Navigating through parameters
• To scroll through parameter groups, press [▲] or
7.2.3 Loggings [▼].
Parameter shortcut
Please enter a
parameter number
01-01
8 Parameter Descriptions
The parameters in Primary Motors Settings configure the 1-5 Initial Current
soft starter to match the connected motor. These Range: Function:
parameters describe the operating characteristics of the
350%* [100– Sets the initial start current level for current
motor and allow the soft starter to model the motor
600% ramp starting as a percentage of motor full load
temperature.
FLC] current. Set so that the motor begins to
accelerate immediately after a start is initiated.
NOTICE If current ramp starting is not required, set the
Parameter 1-2 Locked Rotor Time determines the trip initial current equal to the current limit. See
current for motor overload protection. Its default setting chapter 5.3 Starting Modes for more details.
provides motor overload protection:
1-6 Start Ramp Time
• Class 10.
• Trip current 105% of FLA, or equivalent.
Range:
10 s* [1–
Function:
Sets the total start time for an adaptive control
8 8
180 s] start or the ramp time for current ramp
starting (from the initial current to the current
1-1 Motor FLC
limit). See chapter 5.3 Starting Modes for more
Option: Function:
details.
Model Matches the soft starter to the connected
dependent motor full load current. Set to the full load 1-7 Kick-start Level
current (FLC) rating shown on the motor Range: Function:
nameplate.
NOTICE
500%* [100–
700% FLC] CAUTION
The setting for this parameter sets the INCREASED TORQUE LEVEL
basis for calculation of all current-based Kick-start subjects the mechanical
protection settings. equipment to increased torque levels.
3 s* [0:00–4:00 Slows the response of the soft starter to 2-9 Frequency Variation
(min:s)] current imbalance, avoiding trips due to
Option: Function:
momentary fluctuations.
Selects the soft starter tolerance for frequency
variation.
8.2.2 Undercurrent ±2 Hz
±5 Hz*
If the average current of all 3 phases drops below a ±10 Hz
specified level while the motor is running, the soft starter
±15 Hz
can be configured to trip.
2-10 Frequency Delay
2-4 Undercurrent
Range: Function:
Range: Function:
1 s* [0:01–4:00 Slows the response of the soft starter to
20%* [0– Sets the trip point for undercurrent protection,
(min:s)] frequency disturbances, avoiding trips due to
100%] as a percentage of motor full load current. Set to
momentary fluctuations.
a level between the normal motor working
range and the motor magnetizing (no load) NOTICE
current (typically 25–35% of full load current). A If the mains frequency drops below
setting of 0% disables undercurrent protection. 35 Hz or rises above 75 Hz, the soft
starter trips immediately.
2-5 Undercurrent Delay
Range: Function:
5 s* [0:00–4:00 Slows the response of the soft starter to
(min:s)] undercurrent, avoiding trips due to
momentary fluctuations.
Option: Function: Input trip Input A can be used to trip the soft starter. When
(N/O) this parameter is set to Input Trip (N/O), a closed
Selects whether the soft starter verifies that the
circuit across terminals 11 and 16 trips the soft
motor has sufficient thermal capacity for a
starter (parameters 3-5 to 3-7).
successful start. The soft starter compares the
Input trip When this parameter is set to Input Trip (N/C), an
calculated motor temperature with the
(N/C) open circuit across terminals 11 and 16 trips the
temperature rise from the last motor start. The soft
8 8 starter only operates if the motor is cool enough
to start successfully.
soft starter (parameters 3-5 to 3-7).
Local/remote Input A can be used to select between local and
select remote control, instead of using the LCP keys.
Do not
When the input is open, the soft starter is in
check*
hand-on mode and can be controlled via the LCP.
Check
When the input is closed, the soft starter is in
8.3 Inputs remote mode. The [Hand On] and [Auto On] keys
are disabled, and the soft starter ignores any
3-1 Local/Remote local/remote select command from the serial
Option: Function: communications network.
To use Input A to select between local and
Selects when the [Auto On] and [Hand On]
remote control, set parameter 3-1 Local/Remote to
can be used to switch to hand-on mode or
LCL/RMT Anytime.
auto-on mode.
Emergency In emergency run, the soft starter continues to
Lcl/rmt Change between local and remote control at
run run until stopped, ignoring all trips and warnings
anytime* any time.
(see parameter 15-3 Emergency Run for details).
Local control All remote inputs are disabled.
Closing the circuit across terminals 11 and 16
only
activates emergency run.
Remote control [Hand On] and [Auto On] are disabled.
Opening the circuit ends emergency run and the
only
soft starter stops the motor.
3-2 Comms in Remote Starter The soft starter can be disabled via the control
disable inputs. An open circuit across terminals 11 and
Option: Function:
16 disables the soft starter. The soft starter does
Selects whether the soft starter accepts start
not respond to start commands. If running, the
and stop commands from the serial communi-
soft starter allows the motor to coast to stop,
cation network when in Remote mode.
ignoring the soft stop mode set in parameter
Commands that are always enabled: 1-10 Stop Mode.
• Force comms trip. When the circuit across terminals 11 and 16 is
• Local/remote control. opened, the soft starter allows the motor to
coast to stop.
• Test start.
Jog forward Activates jog operation in a forward direction
• Reset. (operates only in Remote mode).
Disable ctrl in Jog reverse Activates jog operation in reverse direction
RMT (operates only in Remote mode).
Enable ctrl in
RMT*
Vibration alarm
8.4.1 Relay A Delays
3-5 Input A Trip
Option: Function: The soft starter can be configured to wait before opening
Selects when an input trip can occur. or closing relay A.
Always active* A trip can occur at any time when the soft
starter is receiving power.
4-2 Relay A On Delay
Range: Function:
8 8
Operating only A trip can occur while the soft starter is
running, stopping, or starting. 0 s* [0:00–5:00 (min:s)] Sets the delay for closing relay A.
Run only A trip can only occur while the soft starter is
4-3 Relay A Off Delay
running.
Range: Function:
3-6 Input A Trip Delay 0 s* [0:00–5:00 (min:s)] Sets the delay for reopening relay A.
Range: Function:
0 s* [0:00–4:00 (min:s)] Sets delay between the input 8.4.2 Relays B and C
activating and soft starter tripping.
Parameters 4-4 to 4-9 configure the operation of relays B
3-7 Input A Initial Delay
and C in the same way as parameters 4-1 to 4-3 configure
Range: Function: relay A. See parameter 4-2 Relay A On Delay and parameter
0 s* [00:00– Sets a delay before an input trip can occur. 4-3 Relay A Off Delay for details.
30:00 (min:s)] The initial delay is counted from the time a
start signal is received. The state of the input
• Relay B is a changeover relay.
is ignored until the initial delay has elapsed.
• Relay C is normally open.
3-8 Remote Reset Logic
4-4 Relay B Function
Option: Function:
Option: Function:
Selects whether the remote reset input of the
Selects the function of relay B (changeover).
soft starter (terminals 25 and 18) is normally
Off Relay B is not used.
open or normally closed.
Main The relay closes when the soft starter receives a
Normally closed*
contactor start command and remains closed as long as
Normally open
the motor is receiving voltage.
8.4 Outputs Run* The relay closes when the soft starter changes
to run state.
4-1 Relay A Function Trip The relay closes when the soft starter trips.
Option: Function: Warning The relay closes when the soft starter issues a
Selects the function of relay A (normally open). warning.
Off Relay A is not used Low current The relay closes when the low current flag
Main The relay closes when the soft starter receives flag activates (parameter 4-10 Low Current Flag).
contactor* a start command and remains closed as long High current The relay closes when the high current flag
as the motor receives voltage. flag activates (parameter 4-11 High Current Flag).
CAUTION Group
Current imbalance
UNINTENDED START
Phase loss
The autostart timer overrides any other form of control. A
Power loss
The motor may start without warning.
Frequency
Undercurrent
5-1 Auto-Start Type B Instant overcurrent
Option: Function: Input A trip
Selects whether the soft starter autostarts after a Motor overload
specified delay or at a specific time of day. C Motor thermistor
Off* The soft starter does not autostart. Heat overtemperature
Timer The soft starter does autostart after a delay from the
next stop, as specified in parameter 5-2 Auto-start Time. Table 8.1 Trip Categories for Auto-reset
Clock The soft starter autostarts at the time programmed in
parameter 5-2 Auto-start Time. Other trips cannot be automatically reset.
5-2 Auto-Start Time This function is ideal for remote installations using 2-wire
Range: Function: control in auto-on mode. If the 2-wire start signal is
1 min* [00:01–24:00 Sets the time for the soft starter to present after an auto-reset, the soft starter restarts.
(hrs:min)] autostart in 24-hour clock format.
6-1 Auto-Reset Action
5-3 Auto-Stop Type Option: Function:
Option: Function: Selects which trips can be auto-reset.
Selects whether the soft starter autostops after a Do not Auto-Reset*
specified delay or at a specific time of day. Reset group A
Off* The soft starter does not autostop. Reset group A & B
Time The soft starter autostops after a delay from the next Reset group A, B & C
start, as specified in parameter 5-4 Auto-stop Time.
Clock The soft starter autostops at the time programmed in
parameter 5-4 Auto-stop Time.
8 8 Mains
frequency
The average frequency measured on 3 phases. 1 hour
NOTICE 150 ms* [100– Sets the soft starter to match the bypass
2000 ms] contactor closing/opening time. Set
Changes to the adjustment lock setting take
according to the specifications of the
effect only after the programming menu
bypass contactor used. If the time is too
has been closed.
short, the soft starter trips.
NOTICE
This adjustment affects all current-based
functions.
Trip
starter*
Warn and
log
Log only
9 Tools
NOTICE When the action has been completed, the screen briefly
The security access code also protects simulation tools shows a confirmation message and then returns to the
and counter-resets. The default access code is 0000. status screens.
The protection simulation feature enables the soft starter 3. To select a simulation, press [▲] and [▼], then
to confirm that it responds correctly and reports the press [OK].
situation on the display and across the communication 4. To turn the signal on and off, press [▲] and [▼].
network. To confirm correct operation, monitor the state of
the output.
To use the protection simulation:
5. To return to the simulation list, press [Back].
1. Open the Main Menu.
2. Scroll to Protection Sim and press [OK]. Prog Relay A
Off
3. To select the protection to simulate, press [▲] and
[▼]. On
The LCP allows simulation of output signaling to confirm Table 9.8 Motor Thermistor Status Screen
that the output relays are operating correctly.
9.8 Alarm Log The resettable counters (hours run, starts, and motor kWh)
can only be reset if the correct access code is entered.
The [Alarm Log] key opens the alarm logs, which contain:
• Trip log. To view the counters:
• Event log. 1. Press [Alarm Log].
• Counters which store information on the soft 2. Scroll to Counters and press [OK].
starter operating history. 3. To scroll through the counters, press [▲] and [▼].
Press [OK] to view details.
9.8.1 Trip Log 4. To reset a counter, press [OK], then enter the
access code. Select Reset, then press [OK] to
The trip log stores details of the 8 most recent trips, confirm.
including the date and time the trip happened. Trip 1 is
the most recent and trip 8 is the oldest stored trip. To close the counter and return to the alarm logs, press
[Back].
To open the trip log:
1. Press [Alarm Log].
2. Scroll to Trip Log and press [OK].
3. To select a trip to view, press [▲] and [▼], then
press [OK] to show details.
To close the log and return to the main display, press
[Back].
9.8.3 Counters
NOTICE
The security access code protects the counters function.
10 Troubleshooting
When a protection condition is detected, the VLT® Soft 1. Identify and clear the condition that triggered the
Starter MCD 500 writes this condition to the event log and trip.
may also trip or issue a warning. The soft starter response 2. Reset the soft starter.
depends on the protection action settings (parameter
group 16 Protection Actions). 3. Restart the soft starter.
To reset the soft starter, press [Reset] or activate the Reset
Some protection responses cannot be adjusted. Usually, remote input.
external events (for example phase loss) or a fault within
the soft starter cause these trips. These trips do not have If the soft starter has issued a warning, it resets itself when
associated parameters and cannot be set to Warn or Log. the cause of the warning has been resolved.
10 10 battery is low and the power is off, date/time settings are lost. Reprogram the date and time.
Related parameter:
• Parameter 16-12 Battery Clock.
Controller Name selected for a programmable input. Refer to Input A trip.
Current imbalance Problems with the motor, the environment, or the installation can cause current imbalance, such as:
• An imbalance in the incoming mains voltage.
• A problem with the motor windings.
An SCR that has failed open circuit. A failed SCR can only be diagnosed accurately by replacing the
SCR and checking the soft starter performance.
Related parameters:
• Parameter 2-2 Current Imbalance.
• Parameter 2-3 Current Imbalance Delay.
• Parameter 1-6 Start Ramp Time has been set higher than the setting in parameter 1-9 Excess Start
Time Setting.
• Parameter 1-6 Start Ramp Time is set too short for a high inertia load when using adaptive
control.
Related parameters:
• Parameter 1-1 Motor FLC.
• Parameter 1-4 Current Limit.
10 10
FLC too high The soft starter can support higher motor full load current values when connected to the motor
using inside delta configuration rather than in-line connection. If the soft starter is connected in-
line, but the programmed setting for parameter 1-1 Motor FLC exceeds the in-line maximum, the
soft starter trips at start (see chapter 4.5 Minimum and Maximum Current Settings).
If the soft starter is connected to the motor using inside delta configuration, check that the soft
starter detects the connection correctly. Contact the local Danfoss supplier for advice.
Related parameters:
• Parameter 1-1 Motor FLC.
• Parameter 7-1 Motor FLC-2.
Heat sink overtemp Check that cooling fans are operating. If mounted in an enclosure, check if ventilation is adequate.
Fans operate during start, run, and for 10 minutes after the soft starter exits the stop state.
NOTICE
Models MCD5-0021B ~ MCD4-0053B and MCD5-0141B do not have a cooling fan.
Models with fans operate the cooling fans from a start until 10 minutes after a stop.
Related parameter:
• Parameter 16-6 Heat sink Overtemp.
Instantaneous overcurrent There has been a sharp rise in motor current, probably caused by a locked rotor condition (shear
pin) while running. Check for a jammed load.
Related parameters:
• Parameter 2-6 Instantaneous Overcurrent.
• Parameter 2-7 Instantaneous Overcurrent Delay.
Internal fault X The soft starter has tripped on an internal fault. Contact the local Danfoss supplier with the fault
code (X).
Related parameters: None.
L1 phase loss During prestart, check that the soft starter has detected a phase loss as indicated.
L2 phase loss In run state, the soft starter has detected that the current on the affected phase has dropped
L3 phase loss below 3.3% of the programmed motor FLC for more than 1 s. This current drop indicates that
either the incoming phase or connection to the motor has been lost.
10 10 For the soft starter and the motor, check:
• The supply connections.
• The input connections.
A failed SCR can also cause phase loss, particularly an SCR that has failed open circuit. A failed SCR
can only be diagnosed accurately by replacing the SCR and checking the soft starter performance.
Related parameters: None.
L1-T1 shorted During prestart checks, the soft starter has detected a short-circuited SCR or a short circuit within
L2-T2 shorted the bypass contactor as indicated.
L3-T3 shorted Related parameters: None.
Low control volts The soft starter has detected a drop in the control voltage.
• Check the external control supply (terminals A4, A5, A6) and reset the soft starter.
If the external control supply is stable:
• Check if the 24 V supply on the main control PCB is faulty; or
• Check if the bypass driver PCB is faulty (internally bypassed models only).
• Excessive throughput.
Resolve the cause of the overload and allow the motor to cool.
Related parameters:
• Parameter 1-1 Motor FLC.
• Parameter 1-2 Locked Rotor Time.
• The motor winding has overheated. Identify the cause of the overheating and allow the motor
to cool before restarting.
NOTICE
If a valid motor thermistor is no longer used, fit a 1.2 kΩ resistor across terminals 05
and 06.
Related parameter:
• Parameter 16-9 Motor Thermistor.
Network communication (between The network master has sent a trip command to the soft starter, or there could be a network
module and network) communication problem.
Check the network for causes of communication inactivity.
Related parameter:
• Parameter 16-11 Network/Comms.
No flow Name selected for a programmable input. Refer to Input A trip.
Not ready Check if the soft starter disable function is active. If parameter 3-3 Input A Function is set to Starter
disable and there is an open circuit on terminals 11 and 16, the soft starter does not start.
Parameter out of range • A parameter value is outside the valid range.
The soft starter loads the default value for all affected parameters. To go to the first invalid
parameter and adjust the setting, press [Main Menu].
Related parameters: None.
• There is an internal communication error within the soft starter. Contact the local distributor.
Related parameter:
• Parameter 16-10 Starter/Comms.
Starter disable Name selected for a programmable input. Refer to Input A trip.
Thermistor cct (thermistor circuit) The thermistor input has been enabled and:
• The resistance at the input has dropped below 20 Ω (the cold resistance of most thermistors is
above this value) or
Unsupported option (function not The selected function is not available (for example jog is not supported in inside delta configu-
available in inside delta) ration).
Related parameters: None.
Vibration Name selected for a programmable input. Refer to Input A trip.
VZC fails px Where X is 1, 2, or 3.
Internal fault (PCB fault). Contact the local Danfoss supplier for advice.
This trip is not adjustable.
Related parameters: None.
The soft starter is not ready. Check input A (11, 16). Check if the soft starter is disabled via a programmable input.
If parameter 3-3 Input A Function is set to Starter disable, and there is an open circuit
on the corresponding input, the soft starter does not start.
The soft starter does not respond to the [Hand On] Check if the soft starter is in auto-on mode. When the soft starter is in auto-on
and [Reset] keys. mode, the hand-on LED on the soft starter is off. Press [Auto On] once to change to
local control.
The soft starter does not respond to commands • The soft starter is waiting for the restart delay to elapse. Parameter 2-11 Restart
from the control inputs. delay controls the length of the restart delay.
• The motor may be too hot to allow a start. If parameter 2-12 Motor temperature
check is set to Check, the soft starter only allows a start when it calculates that
the motor has sufficient thermal capacity to complete the start successfully. Wait
for the motor to cool before attempting another start.
• Check if the soft starter is disabled via a programmable input. If parameter 3-3
Input A Function is set to Starter disable, and there is an open circuit on terminals
11 and 16, the soft starter does not start. If there is no further need to disable
the soft starter, close the circuit on the input.
NOTICE
Parameter 3-1 Local/remote controls when the [Auto On] is enabled.
The soft starter does not respond to a start • The soft starter may be waiting for the restart delay to elapse. Parameter 2-11
command from either the local or remote controls. Restart delay controls the length of the restart delay. 10 10
• The motor may be too hot to allow a start. If parameter 2-12 Motor temperature
check is set to Check, the soft starter only allows a start when it calculates that
the motor has sufficient thermal capacity to complete the start successfully.
• Check if the soft starter is disabled via a programmable input. If parameter 3-3
Input A function is set to Starter disable, and there is an open circuit on terminals
11 and 16, the soft starter does not start. If there is no further need to disable
the soft starter, close the circuit on the input.
NOTICE
Parameter 3-1 Local/remote controls when [Auto On] is enabled.
The soft starter does not control the motor • Start performance may be unstable when using a low motor FLC setting
correctly during start. (parameter 1-1 Motor FLC). This can affect use on a small test motor with full load
current of 5–50 A.
• Install power factor correction (PFC) capacitors on the supply side of the soft
starter. To control a dedicated PFC capacitor contactor, connect the contactor to
run relay terminals.
Motor does not reach full speed. • If the start current is too low, the motor does not produce enough torque to
accelerate to full speed. The soft starter may trip on excess start time.
NOTICE
Make sure that the motor starting parameters are appropriate for the
application and that the intended motor starting profile is used. If
parameter 3-3 Input A Function is set to Motor Set Select, check that the
corresponding input is in the expected state.
• Check if the load is jammed. Check the load for severe overloading or a locked
rotor situation.
Erratic motor operation. • The SCRs in the soft starter require at least 5 A of current to latch. If testing the
soft starter on a motor with full load current less than 5 A, the SCRs may not
latch correctly.
Erratic and noisy motor operation. If the soft starter is connected to the motor using inside delta configuration, the soft
starter may not be detecting the connection correctly. Contact the local Danfoss
supplier for advice.
Soft stop ends too quickly. • The soft stop settings may not be appropriate for the motor and load. Review the
settings of:
Adaptive control, DC brake, and jog functions not • These features are only available with in-line installation. If the soft starter is
working. installed inside delta, these features do not operate.
A reset does not occur after an auto-reset when • Remove and reapply the remote 2-wire start signal for a restart.
using a remote 2-wire control.
Remote start/stop command overrides autostart/ • Only use autostart/stop in auto-on mode with 3-wire or 4-wire control.
stop settings when using remote 2-wire control.
After selecting adaptive control, the motor used an • The 1st adaptive control start is Current limit. The soft starter then learns from the
ordinary start and/or the 2nd start was different motor characteristics. Subsequent starts use adaptive control.
from the 1st start.
Non-resettable Thermistor Cct trip, when there is a • The thermistor input is enabled once a link is fitted and short-circuit protection
link between thermistor inputs 05 and 06, or when has activated.
the motor thermistor connected between 05 and Remove the link, then load the default parameter set. This disables the thermistor
06 is permanently removed. input and clears the trip.
Place a 1.2 kΩ resistor across the thermistor input.
Turn thermistor protection to Log only (parameter 16-9 Motor Thermistor).
Parameter settings cannot be stored. • Make sure to save the new value by pressing [OK] after adjusting a parameter
setting. If pressing [Back], the change is not saved.
• Check that the adjustment lock (parameter 15-2 Adjustment Lock) is set to Read/
Write. If the adjustment lock is on, settings can be viewed, but not changed.
Knowing the security access code is necessary to change the adjustment lock
setting.
• The EEPROM may be faulty on the main control PCB. A faulty EEPROM also trips
the soft starter, and the LCP shows the message Par. Out of Range. Contact the
local Danfoss supplier for advice.
The LCP shows message Awaiting data. The LCP does not receive data from the control PCB. Check the cable connection.
11 Specifications
Supply
Mains voltage (L1, L2, L3)
MCD5-xxxx-T5 200–525 V AC (±10%)
MCD5-xxxx-T7 380–690 V AC (±10%) (in-line connection)
MCD5-xxxx-T7 380–690 V AC (±10%) (inside delta connection)
Control voltage (A4, A5, A6)
CV1 (A5, A6) 24 V AC/V DC (±20%)
CV2 (A5, A6) 110–120 V AC (+10%/-15%)
CV2 (A4, A6) 220–240 V AC (+10%/-15%)
Current consumption (maximum)
CV1 2.8 A
CV2 (110–120 V AC) 1A
CV2 (220–240 V AC) 500 mA
Mains frequency 45–66 Hz
Rated insulation voltage to ground 690 V AC
Rated impulse withstand voltage 4 kV
Form designation Bypassed or continuous, semiconductor motor starter form 1
Inputs
Input rating Active 24 V DC, 8 mA approximately
Start (15, 16) Normally open
Stop (17, 18) Normally closed
Reset (25, 18) Normally closed
Programmable input (11, 16) Normally open
Motor thermistor (05, 06) Trip >3.6 kΩ, reset <1.6 kΩ
Outputs
Relay outputs 10 A @ 250 V AC resistive, 5 A @ 250 V AC AC15 pf 0.3
Programmable outputs
Relay A (13, 14) Normally open
Relay B (21, 22, 24) Changeover
Relay C (33, 34) Normally open
Analog output (07, 08) 0–20 mA or 4–20 mA (selectable)
Maximum load 600 Ω (12 V DC @ 20 mA)
Accuracy ±5%
24 V DC output (16, 08) maximum load 200 mA
Accuracy ±10%
Environmental
Protection
MCD5-0021B to MCD5-0105B IP20 & NEMA, UL Indoor Type 1
MCD5-0131B to MCD5-1600C IP00, UL Indoor Open Type
Operating temperature -10 °C (14 °F) to +60 °C (140 °F), above 40 °C (104 °F) with derating
Storage temperature -25 °C (-13 °F) to +60 °C
Operating altitude (using MCD PC software) 0–1000 m (0–3281 ft), above 1000 m (3281 ft) with derating
Humidity 5–95% relative humidity
Pollution degree Pollution degree 3
Vibration IEC 60068-2-6
Heat dissipation
During start 4.5 W per ampere
During run
MCD5-0021B to MCD5-0053B ≤39 W approximately
MCD5-0068B to MCD5-0105B ≤51 W approximately
MCD5-0131B to MCD5-0215B ≤120 W approximately
MCD5-0245B to MCD5-0469B ≤140 W approximately
MCD5-0525B to MCD5-0961B ≤357 W approximately
MCD5-0245C to MCD5-0927C 4.5 W per ampere approximately
MCD5-1200C to MCD5-1600C 4.5 W per ampere approximately
Certification
C✓ IEC 60947-4-2
UL/C-UL
MCD5-0021B to MCD5-0396B, MCD5-0245C to MCD5-1600C UL 5081)
MCD5-0469B to MCD5-0961B UL listed
MCD5-0021B to MCD5-105B UL recognized
MCD5-0131B to MCD5-1600C IP20, when fitted with optional finger guard kit
CE IEC 60947-4-2
11 11 CCC
Marine
GB 14048-6
These models are UL recognized components. Separate VLT® Soft Starter MCD 500 supports network communi-
cable landing busbars may be required within the electrical cation via easy-to-install communication modules. Each
cabinet when terminating cables sized according to the soft starter can support 1 communication module at a
National Wiring Code (NEC) regulations. time.
Number of
Recommended • USB.
Model FLC (A) lugs ordering
wires Ordering numbers for communication modules
numbers
MCD5-0131B 145 1 OPHD 95-16
• 175G9000 Modbus module.
MCD5-0141B 170 1 OPHD 120-16 • 175G9001 PROFIBUS module.
MCD5-0195B 200 1 OPHD 150-16 • 175G9002 DeviceNet module. 11 11
MCD5-0215B 220 1 OPHD 185-16
• 175G9009 MCD USB module.
MCD5-0245B 255 1 OPHD 240-20
MCD5-0331B 350 1 OPHD 400-16
• 175G9904 Modbus TCP module.
MCD5-0360C 360
MCD5-0380C 380
11.2.3 PC Software
MCD5-0428C 430 2 1 x 600T-2
MCD5-0595C 620
WinMaster PC software provides:
MCD5-0619C 650 • Monitoring.
MCD5-0790C 790 4 2 x 600T-2 • Programming.
MCD5-0927C 930 3 2 x 600T-2 • Control of up to 99 soft starters.
MCD5-1200C 1200
4 1 x 750T-4 A Modbus or USB communication module is required for
MCD5-1410C 1410
each soft starter to use WinMaster.
1 x 750T-4 and
MCD5-1600C 1600 5
1 x 600T-3
6 kV
• 175G0100 SPD Surge protection kit for G1.
11 11 • 175G0101 SPD Surge protection kit, G2-G5.
12 kV
• 175G0102 SPD Surge protection kit for G1.
• 175G0103 SPD Surge protection kit, G1-G5.
177RA001.11
1/L1 2/T1
1/L1 2/T1 M
3~
1/L1 2/T1
13
14
K1
Illustration 11.1 System with Surge Protection Kit
NOTICE
Many electronic components are sensitive to static
electricity. Voltages so low that they cannot be felt, seen,
or heard can reduce the life, affect performance, or
completely destroy sensitive electronic components.
When performing service, use proper ESD equipment to
prevent possible damage from occurring.
8. Unplug the thermistor, fan, and current 12. Identify which busbars to remove. Remove the
transformer wires from the main control PCB. bolts holding these busbars in place, then slide
out the busbars through the bottom of the soft
9. Remove the plastic tray from the soft starter (4 starter (4 bolts per busbar).
screws).
NOTICE
Remove the main plastic slowly to avoid damaging the
LCP wiring loom (wiring harness), which runs between
the main plastic and the backplane PCB.
15. Tighten the bolts holding the busbars in place to 1. Label the current transformers L1, L2, and L3
13 Appendix
Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information.
Italicized text indicates:
• Cross-reference.
• Link. 13 13
• Parameter name.
All dimensions in drawings are in [mm (in)].
D
B
Delay........................................... 51, 59, 62, 65, 67, 68, 69, 70, 73, 83
Brake
Brake.................................................... 42, 43, 44, 54, 55, 64, 70, 71 Direct on-line.................................................................... 40, 43, 73, 91
torque.............................................................................. 43, 62, 64, 71 see also DOL
DC brake........................................................................... 6, 43, 50, 84 DOL....................................................................................... 40, 43, 73, 91
DC injection......................................................................... 43, 64, 71 see also Direct on-line
Full brake............................................................................................. 43
Pre-brake............................................................................................. 43
Soft brake.............................................................................................. 6 E
Starter disable............................................ 6, 44, 66, 67, 81, 82, 83 Electromagnetic capability............................................................... 85
Busbar........................................................................... 11, 17, 87, 89, 90 Environmental....................................................................................... 86
Busbar, input................................................................................... 18, 19 Event log...................................................................................... 6, 77, 78
Busbar, output....................................................................................... 18 Excess start time..................................... 7, 59, 60, 62, 64, 70, 74, 79
Bypassed operation...................................................................... 25, 27 External zero-speed sensor........................................................ 50, 51
C F
Calculated motor temperature........................................................ 66 Fan cooling.............................................................................................. 39
Capacitors
Power factor correction capacitor................................ 11, 29, 83
Certification............................................................................................ 86
Features
Adaptive control... 6, 29, 39, 40, 41, 42, 44, 60, 63, 64, 70, 71, G
79, 84
Adaptive deceleration control....................................................... 6 Gain setting..................................................................................... 64, 71
Coast to stop.............................. 41, 42, 43, 44, 54, 55, 64, 66, 70 General fault messages...................................................................... 84
DC brake........................................................................... 6, 43, 50, 84
Emergency run................................................. 6, 48, 49, 62, 66, 73
In-line connection............... 6, 19, 21, 24, 25, 28, 54, 79, 81, 85 H
In-line installation.............................................................. 20, 21, 84 Hand-on mode........................................................................ 54, 55, 56
Inside delta......................................................................................... 81
Heat dissipation.................................................................................... 86
Inside delta connection............ 6, 19, 26, 27, 28, 44, 79, 84, 85
Inside delta installation.................................................... 21, 22, 84 Heat sink............................................................................. 11, 62, 74, 79
Internal bypass............................................................................. 6, 73 Heat sink temperature.......................................................................... 7
Jog............................................. 6, 43, 44, 54, 55, 62, 66, 73, 82, 84
Kick-start.................................................................... 6, 41, 62, 63, 70
Output signal simulation.......................................................... 6, 76 I
Output simulation........................................................................... 59
Initial current.......................................................................................... 70
Protection simulation......................................................... 6, 59, 76
Soft brake.............................................................................................. 6 Input A trip......................................................................... 78, 80, 81, 82
Soft braking configuration........................................................... 51 Input rating............................................................................................. 85
Starter disable..................................... 6, 44, 50, 66, 67, 81, 82, 83
Thermal model............................ 6, 39, 43, 44, 59, 71, 72, 75, 77 Input trip............................................................................... 7, 50, 66, 67
Timed voltage ramp....................................... 6, 41, 44, 64, 70, 91 Inputs
see also TVR Control input..................................................................................... 20
TVR........................................................................ 6, 41, 44, 64, 70, 91 Input A...... 44, 48, 49, 50, 51, 52, 53, 59, 62, 66, 67, 69, 74, 80,
see also Timed voltage ramp 81, 83, 84
Finger guard kit..................................................................................... 18 Local control input............................................................................. 6
Power input........................................................................................ 18
FLC.... 19, 21, 28, 29, 34, 39, 41, 42, 57, 60, 63, 65, 68, 70, 79, 82, Programmable input....... 37, 38, 44, 73, 76, 78, 80, 81, 82, 83,
83, 84, 91 85
see also Full load current Remote....................................................... 11, 16, 54, 55, 66, 69, 78
FLT....................................................................................................... 43, 91 Remote control input................ 6, 37, 38, 46, 47, 48, 49, 51, 53
see also Full load torque Reset.............................................................................................. 16, 67
Frequency trip....................................................................................... 65 Inside delta current....................................................................... 19, 21
Full load current...... 19, 21, 28, 29, 34, 39, 41, 42, 57, 60, 63, 65, Installation
68, 70, 79, 82, 83, 84, 91 Bypass contactor.............................................................................. 47
see also FLC Clearance............................................................................................ 13
Derating values................................................................................. 13
Full load torque.............................................................................. 43, 91
Dimension.......................................................................................... 15
see also FLT
Externally bypassed........................................................................ 21
Fuses In-line installation.............................................................. 20, 21, 84
British style (BS88)........................................................................... 31 Inside delta installation.................................................... 21, 22, 84
Bussmann fuse.................................................................................. 30 Internally bypassed.................................................................. 20, 21
European style (PSC 690).............................................................. 34 Main contactor.................................................................................. 46
Ferraz...................................................................................... 32, 35, 36 Non-bypassed............................................................................ 20, 22
Fuse................................................................................................ 20, 22 Side-by-side....................................................................................... 13
Fuse recommendation................................................................... 29 UL-compliant......................................................... 18, 19, 86, 87, 88
HRC fuse....................................................................................... 29, 85 Weight.................................................................................................. 15
HSJ......................................................................................................... 32
Instantaneous overcurrent protection......................................... 65
Motor branch circuit....................................................................... 43
Motor rated mains fuse.................................................................. 29
North American Style (PSC 690)................................................. 33 K
Power supply fuse............................................................................ 29
Keys
Protection fuse.................................................................................. 43
Control keys......................................................................... 54, 55, 56
Semiconductor fuse................ 20, 21, 22, 29, 35, 36, 46, 47, 85
LCP keys............................................................................................... 66
Short-circuit rating............................................................ 34, 35, 36
Navigation keys................................................................................ 55
Square body....................................................................................... 30
Type 1............................................................................................ 29, 85
Type 2............................................................................................ 29, 85 L
UL fuse selection.............................................................................. 34
LCP...... 6, 16, 44, 54, 55, 56, 59, 61, 66, 67, 69, 71, 72, 73, 76, 78,
84, 87, 89, 91
see also Local control panel
T
Terminals
A4............................................................................................. 16, 80, 85
A5............................................................................................. 16, 80, 85
A6............................................................................................. 16, 80, 85
Bypass.................................................................................................. 19
Bypass terminal.................................................................. 20, 22, 38
Control input..................................................................................... 16
Control terminal............................................................................... 16
Power.................................................................................................... 17
Relay terminal............................................................................. 16, 83
Terminal 05.................................................................................. 82, 85
Terminal 06.................................................................................. 82, 85
Terminal 07......................................................................................... 85
Terminal 08......................................................................................... 85
Terminal 11............................................... 48, 49, 50, 66, 81, 83, 85
Terminal 13........................................................................... 46, 73, 85
Terminal 14........................................................................... 46, 73, 85
Terminal 15......................................................................................... 85
Terminal 16............................................... 48, 49, 50, 66, 81, 83, 85
Terminal 17........................................................................... 48, 49, 85
Terminal 18.................................................................... 48, 49, 67, 85
Terminal 21.................................................................................. 47, 85
Terminal 22.................................................................................. 47, 85
Terminal 24.................................................................................. 47, 85
Terminal 25.................................................................................. 67, 85
Terminal 33......................................................................................... 85
Terminal 34......................................................................................... 85
Thermal characteristics...................................................................... 39
Thermal overload protection........................................................... 39
Trip categories....................................................................................... 69
Trip log...................................................................................................... 77
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG17K802*