BACKER ROD 16 GA. x 1½” W.

BACKER ROD PLANS


& SEALANT STRAP ANCHOR W/ & SEALANT
2” VERTICAL LEGS N.T.S.
PROVIDE GAP
EQUIVALENT TO PROVIDE GAP EQUIVALENT TO
ANTICIPATED LIGHT GAGE METAL ANTICIPATED FRAME DRIFT
FRAME DRIFT BACKER AS REQ’D

NOTES:
1. FOR FIRE-RATED
CONSTRUCTION, USE
FIRE-RATED SEALANT
2. FIREPROOFING FOR
STEEL NOT SHOWN
3. APPLIES TO TYPE I
AND TYPE II HYBRID
4. TYPE III HYBRID WOULD
REQUIRE FULL BEARING AT
STEEL INTERFACES WITH
COLUMNS & BEAMS

3D VIEWS

COLUMN CONNECTION DETAILS OPTION 1


DETAIL 02.120.1101 REV. 10/15/08
© 2011 INTERNATIONAL MASONRY INSTITUTE
FIG. 6
IMI TECH BRIEF 02.13.02

BACKER ROD & SEALANT,


BOTH SIDES OF CMU WALL
3/16” Ф WIRE ANCHOR

LIGHT GAGE METAL


BACKER AS REQ’D

NOTES
1. FOR FIRE-RATED CONSTRUC-
TION, USE FIRE-RATED SEALANT
2. FIREPROOFING FOR STEEL NOT
PROVIDE GAP SHOWN
EQUIVALENT TO 3. APPLIES TO TYPE I AND II HYBRID
FRAME DRIFT
ANTICIPATED 4. TYPE III HYBRID WOULD REQUIRE
FULL BEARING AT STEEL INTER-
FACES WITH COLUMNS & BEAMS

COLUMN CONNECTION DETAIL


DETAIL 02.120.1103 REV. 07/24/09
© 2011 INTERNATIONAL MASONRY INSTITUTE
FIG. 6
IMI TECH BRIEF 02.13.02

BACKER ROD & SEALANT,


BOTH SIDES OF CMU WALL
3/16” Ф WIRE ANCHOR

LIGHT GAGE METAL


BACKER AS REQ’D

NOTES
1. FOR FIRE-RATED CONSTRUC-
TION, USE FIRE-RATED SEALANT
2. FIREPROOFING FOR STEEL NOT
PROVIDE GAP SHOWN
EQUIVALENT TO 3. APPLIES TO TYPE I AND II HYBRID
FRAME DRIFT
ANTICIPATED 4. TYPE III HYBRID WOULD REQUIRE
FULL BEARING AT STEEL INTER-
FACES WITH COLUMNS & BEAMS

COLUMN CONNECTION DETAIL


DETAIL 02.120.1103 REV. 07/24/09
© 2011 INTERNATIONAL MASONRY INSTITUTE
OPTION 1A OPTION 1B

SIZE GAP FOR DRIFT & DEFLECTION


OF BEAM FOR TYPE I HYBRID; OR
FILL GAP W/ DRYPACK FOR TYPE II
OR TYPE III HYBRID
OPTION 1A: A-SHAPED BLOCK AT
TOP COURSE; OR OPTION 1B: CUT
OUT FACE SHELL AND REPLACE
AFTER GROUTING; HEIGHT VARIES

1/4” THK x 6” WIDE PLATES FOR


SHEAR TRANSFER; WELD TO
BEAM AFTER CMU PLACEMENT
THROUGH-BOLT OR LAG BOLT AS
REQ’D FOR SHEAR TRANSFER

BOND BEAM AT SECOND


COURSE FROM TOP

GROUT & REINFORCING


AS REQ’D

UNDERSIDE OF BEAM OPTION 1


DETAIL 02.120.1201 REV. 03/02/09
© 2011 INTERNATIONAL MASONRY INSTITUTE
OPTION 2

SIZE GAP FOR DRIFT & DEFLECTION


OF BEAM FOR TYPE I HYBRID; OR
FILL GAP W/ DRYPACK FOR TYPE II
OR TYPE III HYBRID
OPTION 2: SOLID BLOCK AT
TOP COURSE (HEIGHT VARIES)

1/4” THK x 6” WIDE PLATES FOR


SHEAR TRANSFER; WELD TO
BEAM AFTER CMU PLACEMENT
THROUGH-BOLT OR LAG BOLT AS
REQ’D FOR SHEAR TRANSFER

BOND BEAM AT SECOND


COURSE FROM TOP

GROUT & REINFORCING


AS REQ’D

UNDERSIDE OF BEAM OPTION 2


DETAIL 02.120.1202 REV. 03/02/09
© 2011 INTERNATIONAL MASONRY INSTITUTE
TEMPORARY FORMWORK
FOR GROUT

STUDS WELDED TO
UNDERSIDE OF BEAM
1/4” THK x 6” WIDE PLATES
FOR SHEAR TRANSFER;
WELD TO BEAM AFTER CMU
PLACEMENT
OPTION 3: GROUT SOLID
FOR TYPE II OR TYPE III
HYBRID ONLY
THROUGH-BOLT OR
LAG BOLT AS REQ’D
FOR SHEAR TRANSFER

BOND BEAM AT TOP


COURSE

GROUT & REINFORCING


AS REQ’D

UNDERSIDE OF BEAM OPTION 3, TYPE II OR TYPE III HYBRID ONLY


DETAIL 02.120.1203 REV. 03/02/09
© 2011 INTERNATIONAL MASONRY INSTITUTE