UCU Lighting Audit and Recommendations

This document summarizes a lighting audit conducted of the Urdaneta City University Motorpool and Gymnasium. It analyzes the existing lighting systems and illuminance levels in various areas. It then proposes new LED lighting systems to reduce energy consumption and costs. For the Motorpool, the proposed LED system would use 54 fixtures on the ground floor and 18 on the second floor, reducing total monthly electricity costs from Php 1,824 to Php 2,076. For the Gymnasium, LED pin lights are proposed for the entrance, control room and back stage, which would be more energy efficient than the existing metal halide and CFL lamps. The conclusion recommends lighting upgrades to save energy and reduce greenhouse gas emissions

Uploaded by

Jameson Pacis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
156 views6 pages

UCU Lighting Audit and Recommendations

This document summarizes a lighting audit conducted of the Urdaneta City University Motorpool and Gymnasium. It analyzes the existing lighting systems and illuminance levels in various areas. It then proposes new LED lighting systems to reduce energy consumption and costs. For the Motorpool, the proposed LED system would use 54 fixtures on the ground floor and 18 on the second floor, reducing total monthly electricity costs from Php 1,824 to Php 2,076. For the Gymnasium, LED pin lights are proposed for the entrance, control room and back stage, which would be more energy efficient than the existing metal halide and CFL lamps. The conclusion recommends lighting upgrades to save energy and reduce greenhouse gas emissions

Uploaded by

Jameson Pacis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Urdaneta City University

College of Engineering and Architecture


S.Y. 2017

“LIGHTING AUDIT”
TITLE

ILLUMINATION ENGINEERING DESIGN


SUBJECT

Auditors:
Benito, Kriskierlica
Baclig, Leonardo
Agustin,Herald
Pacis, Jameson

Prepared To:
Engr. Royland Eliger
Department Head, EE

Date: December 22, 2017


COMPUTATIONS OF LOADS AND PROPOSALS:

MOTORPOOL
A. Existing Lighting System
ILLUMINANCE OF LIGHT:
Area 1 @ Hallway = 190 lux
Area 2 @ Mechanical Laboratory = 120.67 lux
Area 3 @ Civil Engineering Laboratory = 161 lux
Area 4 @ Electrical Engineering Laboratory = 161 lux
Area 5 @ Office = 74 lux
Area 6 @ Computer Laboratory = 180 lux
Area 7 @ Room U-102 = 180 lux
Area 8 @ Room U-103 = 180 lux

Ground Floor/First Floor:


 6 - Flourescent Lamp ( 40 Watts) = 240 W
 14 - Duplex Flourescent Lamp ( 40 x 2 Watts) = 1120 W
TOTAL = 1360 W
SECOND FLOOR:
 4 - Flourescent Lamp ( 40 Watts) = 160 W
TOTAL = 160 W

Total Watts = 1360 W + 160 W = 1520 Watts

Total Kw-Hr = (1520)(5 Hrs/day) = 7.6 Kw-Hrs.

Total Monthly Kw-Hr = (7.6 Kw-Hrs.)(30 days) = 228 Kw-Hrs per month @Electricity Cost per Kilowatt-
Hour = Php. 8.00/hour

Total Electricity Cost Monthly (Lighting Loads only)

= (228) (8.00) = Php 1,824.00

B. Proposed Lighting System (through the concept of Illumination)


Maintenance Factor = 0.7 (for average conditions)
Coefficient of Utilization = 0.35 (for average fixture, medium size room)
Ceiling Height = 3.5 m
Recommended Illuminance for School:
 Auditorium, Indoor Gymnasium = 100 ~ 300
 Class room = 200 ~ 750
 Laboratory, Library, Drafting room = 500 ~ 1500

 GROUND FLOOR/FIRST FLOOR:


1. Area 1 @ Hallway = (15 x 5.3) = 30.16 m²
Recommended Illuminance = 50 lux
Type of Lamps = Duplex Flourescent Lamp
Recommended Lumens = 500 ~ 1500 Lumens = 40Watts
(5.3)(15)(50)
No. of Fixtures = (1500)(0.35)(0.7)
= 10.82 fixtures
 Use fixtures 11 of flourescent lamp w/ 1 lamp per fixture.
 Or use Fixtures 0f 5 duplex fluorescent Lamp w/ 2 lamp per fixtures and 1 fixture
for 1 flourescent lamp.

2. Area 2 @ Mechanical Engineering Laboratory = (9.8 x 7.5) = 73.5 m²


Recommended Illuminance = 50 lux
Type of Lamps = Duplex Flourescent Lamp
Recommended Lumens = 500 ~ 1500 Lumens = 40Watts
(7.5)(9.8)(50)
No. of Fixtures = (1500)(0.35)(0.7)
= 10 fixtures
 Use fixtures 10 of flourescent lamp w/ 1 lamp per fixture.
 Or use Fixtures 0f 5 duplex fluorescent Lamp w/ 2 lamp per fixtures

3. Area 3 @ Civil Engineering Laboratory = (7.5 x 5) = 37.5 m²


Recommended Illuminance = 50 lux
Type of Lamps = Duplex Flourescent Lamp
Recommended Lumens = 500 ~ 1500 Lumens = 40Watts
(7.5)(5)(50)
No. of Fixtures = (1500)(0.35)(0.7)
= 5.10 fixtures
 Use fixtures 5 of flourescent lamp w/ 1 lamp per fixture.
 Or use Fixtures 0f 2 duplex fluorescent Lamp w/ 2 lamp per fixtures and 1 fixture
for 1 flourescent lamp.

4. Area 4 @ Electrical Engineering Laboratory = (15 x 5) = 75 m²


Recommended Illuminance = 50 lux
Type of Lamps = Duplex Flourescent Lamp
Recommended Lumens = 500 ~ 1500 Lumens = 40Watts
(15)(5)(50)
No. of Fixtures = (1500)(0.35)(0.7)
= 10.21 fixtures
 Use fixtures 10 of flourescent lamp w/ 1 lamp per fixture.
 Or use Fixtures 0f 5 duplex fluorescent Lamp w/ 2 lamp per fixtures

5. Area 5 @ Office = (7.5 x 4.5) = 33.75 m²


Recommended Illuminance = 50 lux
Type of Lamps = Led PinLight
Recommended Lumens = 200 ~ 750 Lumens = 8 Watts
(4.5)(7.5)(50)
No. of Fixtures = (750)(0.35)(0.7)
= 9.18 fixtures
 Use fixtures 9 of led Pinlight w/ 1 lamp per fixture.

6. Area 6 @ Computer Laboratory = (7.5 x 4.5) = 33.75 m²


Recommended Illuminance = 50 lux
Type of Lamps = Led PinLight
Recommended Lumens = 200 ~ 750 Lumens = 8 Watts
(4.5)(7.5)(50)
No. of Fixtures = (750)(0.35)(0.7)
= 9.18 fixtures
 Use fixtures 9 of led Pinlight w/ 1 lamp per fixture.

TOTAL Lamps (Ground Floor) = 54 Fixtures or Lamps

 SECOND FLOOR:

1. Area 7 @ Room U-102 = (7.5 x 4.5) = 33.75 m²


Recommended Illuminance = 50 lux
Type of Lamps = Led PinLight
Recommended Lumens = 200 ~ 750 Lumens = 8 Watts
(4.5)(7.5)(50)
No. of Fixtures = (750)(0.35)(0.7)
= 9.18 fixtures
 Use fixtures 9 of led Pinlight w/ 1 lamp per fixture.

1. Area 8 @ Room U-103 = (7.5 x 4.5) = 33.75 m²

Recommended Illuminance = 50 lux


Type of Lamps = Led PinLight
Recommended Lumens = 200 ~ 750 Lumens = 8 Watts
(4.5)(7.5)(50)
No. of Fixtures = = 9.18 fixtures
(750)(0.35)(0.7)
 Use fixtures 9 of led Pinlight w/ 1 lamp per fixture.

TOTAL Lamps (Second Floor) = 18 Fixtures or Lamps

SUMMARY (Proposed Lighting System)

TYPES OF LAMP GROUND FLOOR SECOND FLOOR


FLOURESCENT LAMP 40 W 36 LAMP X 40 W = 1440 W 0
PINLIGHT 8 WATTS 18 PINLIGHT X 8 W = 144 W 18 PINLIGHT X 8 W = 144 W
TOTAL WATTS 1584 W 144 W

Total Watts ( 1st – 2nd floor) = 1584 + 144 = 1728 W


Total Kilowatts = 1.73 Kw Hours per week
the fixture in operation = 5 hours/day
Total Kilowatt-Hours per Day = 8.65 Kw-Hr / Day
Total Kilowatt- Hours Monthly = (8.65)(30 Days) = 259.5 Kilowatt-Hours Monthly Electricity
Cost per Kilowatt Hour = Php 8.00/hour

Electricity Cost Monthly (Lighting Loads Only) = (259.5) (Php. 8.00/hour) = Php 2,076.00
COMPUTATIONS OF LOADS AND PROPOSAL:

UCU GYMNASIUM
A. Existing Lighting System
ILLUMINANCE OF LIGHT:
Area 1 @ Entrance = 84 lux
Area 2 @ Whole Court = 278 lux
Area 3 @ Front Stage = 198 lux
Area 4 @ Control Room = 161 lux
Area 5 @ Back Stage = 74 lux

Ground Floor/First Floor:


 20 - Metal Halide Lamp ( 500 Watts) = 10000 W
 7 - PinLight ( 9 Watts) = 63 W
 3 - CFL (12 Watts) = 36 W
TOTAL = 10099 W
Recommended Illuminance for School:
 Auditorium, Indoor Gymnasium = 100 ~ 300

B. Proposed Lighting System (through the concept of Illumination)


Maintenance Factor = 0.7 (for average conditions)
Coefficient of Utilization = 0.35 (for average fixture, medium size room)

1. Area 1 @ Entrance = (9 x 2.3) = 20.7 m²

Recommended Illuminance = 50 lux


Type of Lamps = Led PinLight
Recommended Lumens = 100 ~ 300 Lumens = 8 Watts
(2.3)(9)(50)
No. of Fixtures = (300)(0.35)(0.7)
= 14 fixtures

 Use fixtures 14 of led Pinlight w/ 1 lamp per fixture.

2. Area 4 @ control room = (2 x 2) = 4 m²

Recommended Illuminance = 50 lux


Type of Lamps = Led PinLight
Recommended Lumens = 100 ~ 300 Lumens = 6 Watts
(2)(2)(50)
No. of Fixtures = (200)(0.35)(0.7)
= 4.081 fixtures

 Use fixtures 4 of led Pinlight w/ 1 lamp per fixture.

3. Area 5 @ Back Stage = (4 x 2) = 6 m²

Recommended Illuminance = 50 lux


Type of Lamps = Led PinLight
Recommended Lumens = 100 ~ 300 Lumens = 6 Watts
(2)(4)(50)
No. of Fixtures = (200)(0.35)(0.7)
= 8.16 fixtures

 Use fixtures 8 of led Pinlight w/ 1 lamp per fixture.


CONCLUSION AND RECOMMENDATION:
Lighting is a large and rapidly growing source of energy demand and greenhouse
gas emissions. At the same time the savings potential of lighting energy is high even
with the current technology, and there are new energy efficient lighting technologies
coming on the market. One of our needs in our community and environment is having a
light and more important in evening time when it comes to our safety. Without light, we
did not know what to do. We did not see what a beautiful place of our environment or
around us. In this activity with the use of lux meter conduct lighting audit to measure
the illuminance of the light in every room and we started to re-design for the lightings
and add more and exact lamp to light the room.