NORTHBRIDGE
2.9MVA 3-15kV Transformer Unit
Transformer Enclosure MV Switchgear Cubicle
The transformers are packaged inside an ISO type container of the
following dimensions:
HV Switchgear
Length: 2991mm The transformer package includes MV switchgear on a
Width: 2438mm frame type ABB SafePlus CV, 15kV, 630A.
Height: 2591mm
Weight ± 9400kG Construction
Manufacturer: ABB
The container is metal clad and is of robust construction and provides Type: SafePlus Type C,V
IP55 protection for the switchgear and control system. The Rated Voltage: 15kV
transformer unit is suitable for permanent or temporary outdoor Nominal Voltage: refer to transformer
installation. The container incorporates forklift pockets, DNV Nominal Frequency: 50Hz / 60Hz
overhead lifting points and twist lock corners. Short Time Current: 21 kA
Maximum Ambient Temperature: + 40°C
Capacity Rated Current: 630A
Protection: IP2x
The unit is rated: 2900KVA, 3phase 50hz/60hz
Enclosures Control Interlock Panel
Folded steel and ISO container type enclosure are both available in
two forms: one designed for fixed installation at permanent outdoor When the control panel is energised, the main transformer cooling
locations, the other transportable for moving from site to site. Both fans will operate and a supply made available to the Battery
types give IP55 and have overhead lifting facilities. Charger.
The control panel has the following function:-
Start main transformer Cooling Fans
General Arrangement Supply Battery Charger
Control MV breaker Trip Relay Circuit
The Transformer Unit is designed to be used for step up or step down Control LV breaker Shunt Trip Circuit
applications. Control Main Transformer and door interlock protection
circuits
Each unit consists of the following components:-
These relays and indicator lamps are connected to 24V DC from
MV Cable Termination Chamber the battery to maintain indication of fault if the main power is
MV switchgear Cubical disconnected
Transformer
LV Circuit Breaker Control Room
LV Cable Termination Chamber Lighting, and power sockets are located in the Control Room and
Control Interlock Panel are powered from the auxiliary supply
Control Room
28V Battery/Charger Unit The control room also contains:-
Earth Bar MV Switchgear Cubicle
24V Battery Charger Unit
Control Interlock Panel
Access to MV Cable Connections
Rubber Mat
1
Page
NORTHBRIDGE NORTHBRIDGE
Middle East Industrial Services Pte Ltd
United Arab Emirates United Kingdom Singapore
[Link] [Link] [Link]
DUSTRIAL SERVICES DUSTRIAL SERVICES
NORTHBRIDGE
2.9MVA 3-15kV Transformer Unit
Transformers
The transformers are housed at each end of the enclosure and
accessed by double doors. The base of the enclosure transformer
section is continuously welded to form a ‘Bund’ in the event of
cooling oil leakage.
Additional cooling is provided by fans mounted in the side of the
enclosure.
Protection device for the transformer and access doors are wired to
the control panel.
Three phase oil-immersed distribution transformer specification:-
Type: CTMU 24 HA 2900
Power / Cooling: 2,500kVA (overload capacity 116%) see Note 1
Number of Phases: 3
Rated Frequency: 50Hz / 60Hz
Primary Voltage: 11000 (5500)+-2x10%/433 (50Hz)
6351(3175)+-2x10%/433 (50Hz)
+20% with 60Hz
Secondary Voltage: 433
Connection: YN(YN)yn0, D(D)yn11
Altitude: < 1,000m
Maximum Ambient + 40°C
Temperature:
Impedance voltage 6%
at rated current:
Note 1: Overload capacity 110% at 2540/433V, 50Hz.
2
Page
NORTHBRIDGE NORTHBRIDGE
Middle East Industrial Services Pte Ltd
United Arab Emirates United Kingdom Singapore
[Link] [Link] [Link]