Features: Ratings Auxiliary Power Supply Current Input Environmental Conditions

The document describes a power factor regulator that automatically adjusts the power factor of an electrical system through step switching. It features microprocessor control, automatic settings adjustment, alarm outputs, and monitoring of power factor and other electrical parameters. It is available in models with 6, 8, 12, or 14 steps that operate at 50 or 60 Hz and can connect to power sources from 220-240V AC to 380-415V AC.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views2 pages

Features: Ratings Auxiliary Power Supply Current Input Environmental Conditions

The document describes a power factor regulator that automatically adjusts the power factor of an electrical system through step switching. It features microprocessor control, automatic settings adjustment, alarm outputs, and monitoring of power factor and other electrical parameters. It is available in models with 6, 8, 12, or 14 steps that operate at 50 or 60 Hz and can connect to power sources from 220-240V AC to 380-415V AC.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Power Factor Regulator

www.itmikro.com

PFR140
120
80
60
Features
•• Microprocessor based intelligent auto switching
control
•• Automatic C/K and rated step adjustment
•• Automatic CT polarity correction
•• Display of power factor, current & total harmonic
distortion of current
•• Programmable sensitivity
•• Last step can be used as alarm/fan output
•• Under/over voltage alarm, under/over compensate
alarm & high harmonic distortion alarm
•• User-friendly setting
•• Complies with IEC 61000-6-2 standard

Technical Data
ENVIRONMENTAL CONDITIONS
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT Temperature : -10°C to 55°C
Current Supply voltage : 220~240 V AC / Rated current ( In ) : 5 A Humidity : 5% to 95%,
380~415 V AC Operating Limits : 0.05 A to 6.5 A non-condensing
Operating Limits : -15% + 10% Rated Frequency : 50 Hz or 60 Hz
Consumption : 10 VA max
Rated frequency : 50 Hz or 60 Hz MECHANICAL
CONTROL RANGE Mounting : Panel mounting
Power factor setting : 0.8 Ind - 0.8 Cap
PFR 140 / 120 / 80 / 60

Dimension (mm) : 144(w) x 144(h) x 90(d)


OUTPUT CONTACTS C/K setting : 0.03 - 1.20 / Automatic Enclosure protection : IP54 at the panel
Numbers of outputs : 6 / 8 / 12 / 14 Switching sensitivity : 5 - 600 s/step Approximate weight : 1.2 kg
(PFR60/PFR80 Reconnection time for
/PFR120/PFR140 ) same step : 5 - 240 s
Rated voltage : 250 V AC THD threshold : 0.20 - 3.00 ( 20% -
Contact rating : 5 A 300% ) / OFF
Expected electrical life : 100,000 operations Switching Program : Automatic / Automatic
at rated current Rotate / 4-quadrant /
Expected mechanical life : 5 x 106 operations Manual
Max current for the Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 /
common terminals : 12 A continuous 8 / 12 / 16
( Automatic if C/K set
to Auto )
Power Factor Regulator

www.itmikro.com

Typical Application Diagram

Case Dimensions Ordering Information


MODEL DESCRIPTION
PFR60 - 415 - 50 6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

PFR80 - 415 - 50 8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

PFR120 - 415 - 50 12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

PFR140 - 415 - 50 14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC

PFR60 - 220 - 50 6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

PFR80 - 220 - 50 8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

PFR120 - 220 - 50 12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

PFR140 - 220 - 50 14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC

PFR60 - 415 - 60 6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC


PFR 140 / 120 / 80 / 60

PFR80 - 415 - 60 8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

PFR120 - 415 - 60 12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

PFR140 - 415 - 60 14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC

PFR60 - 220 - 60 6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

PFR80 - 220 - 60 8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

PFR120 - 220 - 60 12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC

PFR140 - 220 - 60 14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC