100%(1)100% found this document useful (1 vote) 451 views397 pagesU.A.Bakshi, M.V.Bakshi-Protection and Switchgear-Technical Publications (2006) PDF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
A. Bakshi
V. Bakshi
ve
va
ma :
Technical Publications Pune™Table of Contents
1.2 Functions of Protective Relaying...
17 Egsetial Qualtes of Protecive Relaying
121 Relabiiy.
4.9 Terminologies used in Protective Relaying...
4.44 Current Transformers (C.T.).1.12.2 Bat Type Current Transformer... wh ab ae eseeees tata eseee 424
1.13 Why Secondary of C.T. Should nat be p Open ?. 2. — 1-24
1.14 Potential Transformers (P.T.). ee oon nea 1-25
dT Consinucion Le
4.45 Comparison of C.T. and P.T....
1.16.2 Phase Angie Error . 8
1.16.3 Reduction of Ratio and Phase Angie Errors. . 1.34
1.17 Advantages and Disadvantages of Instrument Transformers.............1-33
Review Questions a - 4-33
21.1 Basic Trip Circuit Operation
2.1.2 Auviliary Switch .
22 Tapping ‘Schemes in Circuit Breaker ..
fays with Make Type Contact
2.2.2 Relay with Break Type Contact
2.3 Electromagnetic Attraction Relay
EST ANTaee Nimatre Type Say
2.3.2 Solenoid and Plunger Type Relay
2.3.3 Operating Principle of Electromagnetic ‘tection Relays.
2.3.4 Advantages of Electromagnetic Relays. . . ‘
2.3.5 Disadvantages of Electromagnetic Relays
236 Lonitrect cine fue.
2.4.2 Shaded Pole Type Induction Relay
2.4.3 Watthour Meter Type induction Relay.
2.44 Induction Cup Type Relay... a
2.5 Nondirectionat Induction Type Overcurrent Relay o
2.5.2 Operation
2.6 Directional Power Relay
2.7 Directional induction Type Overurent Relay ..
TT Operation. oe
1 ir ni
2.8 Thermal Relays. = - st tetearserseeroee 2-262.9 Universal Relay Torque Equation
423 1g Characteristics on R-X Diagram
et Dis ates o pene
ee seeeressiies
4.3.4 Disadvantages...
Abo Rais or Admitance Relay
2 onion
iasenaa Equation
i 414.3 Operating Charscies
RE SE5.14 Protection Against Unbalanced Loading
‘Examples with Solutions ..... ;
MT) NE8.2 Phase Comparison Method of Carrier Current Protection
8.3 Advantages of Carrier Current Protection,
8.4 Static Relays...
8.5 Basic Elements of Stee Raley.
8.51 Input Element. i posites onto
852 Measuring Bement...
8.5.3 Output Element...
x is.
8.6.2 Limitations of Static Relays .
8.7 Semiconductor Devices used in Static Relays.
8.8 Static Time Current Relay..
B.B.1 Static Tima-Curment Characheristies 0G
9.3 D.C. Circuit Breaking .
9.4 AC. Circuit Breaking.
9.6 Current Interruption in A.C. Circuit Breakers
DMMLG NS 3 2s ee ES ee9.7 Transient Recovery Voltage... 9-12
9.8 Effect of Different Parameters an Transient Recovery Voltage (TRV). = 13
98.1 Effect of Natural Frequency on TRV.
tudEisiibas teat
29 Recsveny Voltage a os . woes B16
‘3,1 Effect of Reactanca Drop on Recovery Volisge re
9.9.2 Effect of Amature Reaction on Recovery Voltage 8-16
9.10 Single Frequency Transient
9.11 Double Frequency Transient
9.12 Derivation of Rate of Rise of TRV. 3.
9.12.1 Expression for Maximum Value of Restriking Voltage E... and Corresnonding Time t... 9-24
9.12.2 Expression for RRRV and Maximum RRRV “
9.12.3 Frequency of Oscillation of Restrking Voltage {Transion)
‘9.12.4 Rastriking Voltage Under Various Conditions
9.12.5 First Pole to Clear Factor
9.13 Interruption of Capacitive Currents ..
§.14 Current Chopping (interruption of Low Magnetizing Current)
9.15 Resistance Switching...
9.16 Arc Extinction...
9.16.1 High Resistance Interruption.
8.16.2 Low Resistance or Current Zero interruption
9.16.3 Artificial Curent Zero interruption.
917-1 Themmal lomzatng 8
9.17.2 lonization by Collision . .... cee 837
9.17.3 Thermal Eiesion from Surface of Contacts........ . cic OF
9.17.4 Secondary Emission at Contact Surface. 7
9.17.5 Field Emission. . “7
9.17.6 Photoemission. a7
9.18 Deionization
9.18
18.1 Recombination. . SIT a7
9.18.2 Difusion, : . 337
918-3 Condaction of Met
9.19 Are Formation .
9.20 High fogsiarce Arc Interrupti
e02Ssiten ak cee oe oe 938
9.20.3 Cooling OF Are... se sesso sees ee esse eens eeees ee eee eee e es ees
ASS S| RRB EC ESR ARS SAR 79.21 Low Resistance or Zero Point Extinction ....
9.284 Ag Interruy Theorioe a
: 20.2 Cassels Tory. _ - oat
Examples with Solutions
105.2 Working... .e esses vos woe 10-5
1052.1 Cross Bast Type _ 108
10.5.2.2 Axial Blast Type. s 106
108. Comorsse Ax Syst fo Ae Gis Creat Bahar .
10. Tr Sulphur Hexafluoride (SF Cet reser. . . 10-13
07.1 Properties of SFs Gas... see coe OTE
‘VO.7-1.1 Physical Properties... = a wu 10-14
107.12 Chemical Properties... . sue wee 1014
ic Progerk
10.7.2 Construction of Non-Pulfar Type SFs Breaker. * 10-18
jor2s or
10.7.3 Single Pressure Puller Type SFy Crouit Breaker 10-18
10.7.4 Double Pressure Type SF Circuit Breaker, . pases 10-19
10.7.5 Advantages of SF: Circuit Breaker... - =... . 10-20
10.7.6 Disadvaniages....... 0.0... poeta eee ee errr teeter ee 1D
10.7.7 Applications . 10-2110.8 Vacuum Circuit Breakers - - eossessense IZ
10.8.1 Electrical Breakdown in High Vacus. 10-21
82 Consiucton te
10.83 Working ce 10-23
10.8.4 Advantages... a = woo cies OE
1085 Disadvantages Lo ary")
i0A8 Ramen Seth Cur co poe 105
10.87 Applica . 10-25
10.2.1 Plain Break Ol Circuit Breaker 10-26
10.8.1. Stage Break Oi Circuit Breaker - - - 10.28
10912Doutie Bewak Oi Cicait Beaker ae
Afi fing Py fe Oil Cir x
10.9.4.4 Advantages of Pain Break Oi Circus Seoaker 10:50
10.9.15 Dissdvantages of Plain Brook Od Cre Breaker _ 10.0
109.18 Applications... ae 10:30
10.9.2 Salf Ganseaied Pressure Ql Grout ier
10.9.2. Pisin Explosion Pot. . . 10-31
1 1959
108.23 Sell ion Pot . 10-32
10.8.2 Ga Blast Exptsion Pot . 1033
10.9.3 Forced Blast Of Ciouit Breakers 0 IOS
10101 Consiucion Es
10.10:2 Operation... 10.38
10.104
10.105 Dis
10.10:6 Applications...
10.11 HVDC Circuit Breaker ws
10.12 Selection of Circuit Breaker ........
10. 13 Circuit Breaker Ratings . a sseaweeucessssususeaeeasen whensanessas
10.13.1 Rated Voltage .... . . 1041
10.13.2 Rated insuiation Level........ : trvetpaneadad ceeteevere MMT10.13.6 Rated Short Cireuit Breaking Current 2... 10-42
10.13,7 Rated Short Circuit Making Cunent....... . teen 1043
10.13.8 Rated Peak Withstand Curent . pee TOS
10.13.9 Rated TRY for Terminal Faults ............ 10-43
10.13.10 Rated Operating Sequence __ - a 1044
1811 Rand uta Cd Oe . 10.44
10.13.12 Rated Pressure of Compressed Gas... cose sous 10-44
10.14 Type Tests...
10.15 Routine Tests
10.16 Development Tests .
10.17 Reliability Tests.
10.18 Commissioning Tests -
10.19 Short Circuit Test Layout ..... Ao . eesesnenes 10-48
10.19.1 Short Circuit Testing Plants. : : - 10-48
10.19.2 Layout of a Short Circuit Testing Station... . ease . 10-49
10.19.3 Short Circuit Generator and Drive Motor 0S
10.194 Short Circuit Transformers . 0... 6. ee cece eee eee eae eeee renner 10-51
10.19.5 Reactors wees - ererrreetes 1051
10.19.6 Master Circuit Breaker... see eee weenee 1051
10.19.7 Making Device bese soccer MOET
10.1946 Capacitor . 1051
10.19.9 Resistors . ‘ 10-51
10.19.10 Test Cubicles... co cee eee : 10.51
10.19.11 Sequence Switch, .. ee eeereereeees 10.52
10.20 Indirect Testing
TOT Unit Testing
10.202 §)
10.21 Types of Synthetic Test Circuits ..
10.21.1 Parallel Current injection Method
10.21.2 Sesies Current injection Method - oe
10.21.3 Brown Boveri's Synthetic Testing Creu... 2.0... seeeee resis 10ST
DAA POG Wet a ace ee _ fe oss 1-4
11.2 Ungraunded or Isolated Neutral System
11.3 Earthed Neutral System.11.4 Solid Grounding ..
11.5 Resistance Earthin:
11.6 Reactance Earthing
11.7 Resonant Grounding
11.8 Voltage Transformer Earthing
41.9 Earthing Transformer ....
11.10 Resistance of Grounding Systems.
14.12 Grounding Grids.
abt Design Princicie 04 Sidbatinion:Gutondiny Sosian
12.5 Protection Against Lightning .. 12-9
12.6 Protection of Generating Stations and Substations Against Direct Strokes.
-esnnunansannnsnnansasssnnstssissssnsnesnennssnnestntinsssnensinnntentsnnnsennnnned 2010),
12.7 Protection of pan smiss on Lines Against Direct Strokes 12-14
1212
12.7.4 Advantages of Ground Wire -
12.7.8 Disadvantages of Ground Wire.
12.7.8 Use of Ground Wire. ,
12.8 Protection of Trenemistion Line by Auxlary Devices
Ni
(Indirect Strokes).12.10 Requirements of Surge Diverter ..
12.11 Operation of a Typical Surge Diverter {Lightning Arrester
12.12 Classification of Surge Arresters.....
12.13 Terms and Specifications used in Surge Arresters.
12.14 Hor Gap Arrester
12.14,1 Advantages:
RA. 2 Dinter oc IR
12.15 Ros Gap arrester or Spark Gap Arrester en 212-24
12.15.7 Limtations. : 126
12.16 Multigap Arrester
12.47 Expulsion Type Arrest.
12.17.1 Advantages -
1247.2 Disadvantanes..
12.18 Valve T) Lightning Arrester.
216.1 Sevies ip Assembly. .
12.18.2.Non Linear Resistors... .
12.18.3 Working
VQN64 AGVOOAQOS oo see eee eee e secs cece ee eevee ese seeesueeseneees
2.18.5 Disadvantages: - 12-33
12.16.6 Applications .. .
12.19 Metal Oxide Lightning Arresters.
12.20 Location of Lightning Arresters
12.21 Rating of Lightning Arrester
12.22 Tests on Lightning Arrester
12.23 Surge Absorber...
12.24 Summary of Protective Devices
TOP CeProtective Relaying
41.4 Introduction
Protective relaying is one of the several features of the power system design
Every part of the power system is protected. The factors affecting the choice of
protection are type and rating of equipment, location of the equipment, types of faults,
abnormal conditions and cost,
The protective relaying is used to give an alarm or to cause prompt removal of
any element of power system from service when that element behaves abnormally.
The abnormal behaviour of an clement might cause damage or interference within
effective operation of rest of the system. The protective relaying minimises the damage
to the equipment and interruptions to the service when electrical failure occurs. Along.
with some other equipments the relays help to minimise damage and improve ‘the
service.
The relays are compact and self contained devices which can sense the abnormal
conditions. Whenever an abnormal condition exists, the relay contacts get closed. This
inturn closes the trip circuit of a circuit breaker. The circuit breakers are capable of
disconnecting a faulty element, when they are called upon to do so by the relays
Thus entire process includes the operations like occurrence of fault, operation of relay
opening of a circuit breaker and removal of faulty element. This entire process is
automatic and fast, which is possible due to effective protective relaying scheme.
The protective relaying scheme includes protective current transformers, voltage
transformers, protective relays, time delay relays, auxiliary relays, secondary circuits,
trip circuits etc. Each component plays its own role, which is very important in the
overall operation of the scheme. The protective relaying is the team work of all these
components, The protective relaying also provides the indication of location and type
of the fault
(4)Protection and Switchgoa 1-2 Protective Relaying
1.2 Functions of Protective Relaying
The various functions of protective relaying are :
1. The prompt removal of the component which is behaving abnormally by
closing the trip circuit of circuit breaker or to sound an alarm
ing part so as to avoid the d
To disconnect the abnormally 0
interference within effective operation of the rest of system,
age or
3. To prevent the subsequent faults by disconnecting the abnormally. operating
part
4. To disconnect the faulty part as quickly as possible so as to minimise the
damage to the faulty part itself. For example, if there is a winding fault in a
machine and if it persists for a long time then there is a possibility of the
damage of the entire winding. As against this, if it is disconnected quickly then
only few coils may get damaged instead of the entire winding
To restrict the spreading of the effect of fault causing least interference to the
rest of the healthy system. Thus by disconnecting the faulty part, the fault
effects get localised
6. To improve the system performance, system reliability, system stability and
service continuity
The faults can not be completely avoided but can be minimised. Thus the
protective relaying plays an important role in sensing the faults, minimizing
the effects of faults and minimizing the damage due to the faults
41.3 Protective Zones
in a protective relaying scheme, the circuit breakers are placed at the appropriate
ts such that any element of the entire power system can be disconnected for
repairing work, usual operation and maintenance requirements and also under
abnormal conditions like short circuits. Thus a protective covering is provided around
cach element of the system.
A protective zone is the separate zone which is established around each system
at. The significance of such a protective zone is that any fault occurring within a
given zone will cause the tripping of relays which causes opening of all the circuit
breakers located within that zone, The various components which are provided with
the protective zones are generators, transformers, transmission Lines, bus bars, cables,
capacitors ete. No part of the system is left unprotected. The Fig. 1.1 shows the
various prot
we zones, used in a systemProtection and Switchgear 4-3 Protective Relaying
| 4 Generator transtormer
i protective one
(= 8 bar protective zane
Fig. 1.1 Protective zon
The boundaries of protective zones are decided by the locations of the current
transformers.
In practice, various protective zones are overlapped. The overlapping of protective
zones is done to ensure complete safety of each and every element of the system. The
zane which is unprotected is called dead spot. The zones are overlapped and hence
there is no chance of existence of a dead spot in a system. For the failures: within the
region where two adjacent protective zones are overlapped, more circuit breakers get
tripped than minimum necessary to disconnect the faulty element. If there are no
overlaps, then dead spot may exist, means the circuit breakers lying within the zone
may not trip eventhough the fault occurs. This may cause damage to the healthy
system. The extent of overlapping of protective zones is relatively small. The
probability of the failures in the overlapped regions is very low, consequently the
tripping of too many circuit breakers will be also infrequent The Fig, 1.2 shows the
overlapping of protective zones in the primary relayingProtection and Switchgear 1-4 Protective Relaying
‘Generator protection
“
Low vaitage .
switchgear Generator
protectin
Susbar
Pane:
vanstommer ———+! pt
protection \ “-——— Transtormer
igh voltage
setch gear, +!
protection Bear
Transmission
tine ‘Tranannénsion bre
protection
High voltage :
‘swtchgesr—= | poa= 1 Busbar
rotecton
Fig. 1.2 Overlapping zones in primary relaying
It can be seen from the Fig. 1.2 that the circuit breakers are located in the
connections to each power system element. This provision makes it possible to
disconnect only the faulty element from the system. Ocassionally for economy in the
number of circuit breakers, a breaker between the two adjacent sections may be
omitted but in that case both the power system sections are required to be
disconnected for the failure in either of the two.
Each protective zone has certain protective scheme and each scheme has number
of protective systems. .
1.4 Primary and Backup Protection
The protection provided by the protective relaying equipment can be categorised
into two types as
1. Primary protection
2. Backup protection
The primary protection is the first line of defence and is responsible to protect all
the power system elements from all the types of faults, The backup protection comes
inte play only when the primary protection fails.Protection and Switchgear 1-5 Protective Relaying
The backup protection is provided as the main protection can fail due to many
reasons like,
1. Failure in circuit breaker
2. Failure in protective relay
3. Failure in tripping circuit
Failure in dic. tripping voltage
Loss of voltage or current supply to the relay
Thus if the backup protection is absent and the main protection fails then there is
a possibility of severe damage to the system.
When the primary protection is made inoperative for the maintenance purpose, the
backup protection acts like a main protection. The arrangement of backup protective
scheme should be such that the failure in main protection should not cause the failure
in back up protection as well. This is satisfied if back up relaying and primary
relaying do not have anything common. Hence generally backup protection is located
at
rent stations from the primary protection. From the cost and econemy point of
view, the backup protection is employed only for the protection against short circuit
and not for any other abnormal conditions.
1.4.1 Concept of Backup Relaying
Consider the backup relaying employed for the transmission line section EF as
shown in the Fig, 1.3.
ttt 5 gg) oo
} Ee} 42}
Transmission
fine
Fig. 1.3 Backup relaying
The relays C, D, G and H are primary relays while A, B, I and J are the backup
relays.
rmally backup relays are tripped if primary relay fails. So if the primary relay E
fails to trip, then backup relays A and B get tripped. The backup relays and associated
backup relaying equipments are physically apart from the faulty equipment.Protection and Switchgear 1-6 Protective Relaying
The backup relays A and B provide backup protection for fault at station K. Also
the backup relays at A and F provide the backup protection for the faults in line DB.
The backup relaying often provides primary protection when the primary relays
are out of service for repairs.
It is obvious that when the backup relay operates, the larger part of the system is
disconnected
The important requirement of backup relaying is that it must operate with
sufficient time delay so that the primary relaying is given a chance to operate. When
fault occurs, both the type of relays starts relaying operation but primary is expected
to trip first and backup will then reset without having had time to complete its
relaying operation
il adjacent
mine the
When the given set of relays provides the backup protection for se
system elements then the slowest primary relaying of any af these will dete
necessary time delay of the given backup relays.
1.4.2 Methods of Backup Protection
The various methods used for the backup protection are classified as,
1. Relay Backup Protection : In this scheme, a single breaker is used by both
primary as well as backup protection but the two protective systems are
dif
nt
Breaker Backup Protection : In this method, separate breakers are provided for
primary and backup protection. Both the types of breakers are at the same
station.
3. Remote Backup Protection : In this method, separate breakers are provided for
primary and backup protection. The two types of breakers are at the different
stations and are completely isolated and independent of each other
4. Centrally Co-ordinated Backup Protection : In this method, primary protection
is at various stations. There is a central control room and backup protection for
all the stations is at central control room, Central control continuously inspects
the load flow and frequency in the system. If any element of any part of the
tem fails, load flow gets affected which is sensed by the control room. The
control source consists of a digital computers which decides the proper
switching action, The method is also called centrally controlled backup
protection
1.5 Nature and Causes of Faults
Any fault in electrical apparatus is nothing but the defect in its electrical circuit
which makes current path directed from its intended path: Normally due to breaking
of conductors or failure of insulation, these faults occur, The other reasons forProtection and Switchgear 1-7 Protective Relaying
occurance of fault include mechanical failure, accidents, excessive internal and external
stresses, The impedance of the path in the fault is low and the fault currents are
comparatively large. The reduction of the insulation is not considered as a fault until
its shows some effect such as excessive current flow or reduction of impedance
between conductors or between conductors and earth.
When a fault occurs on a system, the voltages of the three phases become
unbalanced. As the fault currents are large, the apparatus may get damaged. The flow
‘of power is diverted towards the fault which affects the supply to the neighbouring
zone.
A power system consists of generators, transformers, switchgear, transmission and
distribution citcuits. There is always a possibility in such a large network that some
fault will eccur in some part of the system. The maximum possibility of fault
occurance is on transmission lines due to their greater lengths and exposure to
atmospheric conditions
‘The faults can not be totally eliminated from the system but their occurance can be
minimised by improving system design, quality of the equipment and maintenance.
The faults can be classified according to causes of their incidence. The breakdown
may occur at normal voltage due to deterioration of insulation. The breakdown may
also occur due to damage on account of unpredictable causes which include perching
of birds, accidental short circuiting by snakes, kite strings, three branches etc The
breakdown may occur
by lighting
The AC faults can also be classified as single line to ground fault, double line to
ground fault, three phase fauilt, that may occur in the system due to unbalance in
current and voltage, over voltages, reversal of power, power swings, under frequency,
temperature rise and instability
t abnormal voltages due to switching surges or surges caused
It may be necessary to know the frequency of the fault occurance on various parts
of the system which help in designing suitable protection circuit. Following table gives
us an idea as to how the faults are distributed in the various parts of the system.
Equipment % of total faults
|_1) | Overtiead tines 50
|_2) | Switchgear 0} CS
3) | Transtormer 12
4) | Cables 44
5) | hiscafansous 8
6) | Control equisment 3
7) | Cts ang PTs 2
Table 1.1Protection and Switchgear 1-8 Protective Relaying
It can be seen from the above table that maximum number of faults are occuring
on overhead Lines. In case of three phase system, the breakdown of insulation between
one of the phases and earth is known as line to ground fault. In line to line fault,
there is insulation breakdown between either of the two phases. While the insulation
breakdown between bwo phases and earth forms double line to ground fault. The
tion between three phases is nothing but three phase fault
wing table gives occurance of these faults
breakdown of insu
Foll
‘Type of Fault Representation % occurance
1) Line to Gragund (L-G —_—_—_—_— cS
2} Line ok
mm = s
3) Line to Line te Ground —r— 5
ig)
4) Uneeune toting | Dortess
ao
It can be seen from the above table that most of the faults are line to ground faults
ry in nature. The
word transitory refers to the fault which remains for short duration of time. The fault
current varies with time. For example if a twig falls across a line and ocross arm and
burns itself out or just falls down then the fault is transient as it vanishes after few
cycles. During first one to three cycles, the fault current is very high but later on
decreases very rapidly. This zone in which the current is very high but decreases very
rapidly is called ‘sub transient” state. After these first few cycles, the rate of current
decrease is slower. Thi is called ‘transient’ state. This state remains for several
cycles. After the transient state is over, steady state is reached. During the steady state,
the rms value of short circuit current remains constant. The circuit breaker operates
during transient state.
in case of overhead lines. A large number of these faults are transit
zon
This fault current produced by line to ground fault has considerable magnitude. So
the protective system must be properly designed $0 as to have reliable operation of
relays under line to ground fault.
The Line to Line to Line (L-L-L} fault is nothing but symmetrical three phase fault
which normally occurs due to carelessness of operating personnel. Usually the phase
lines are tied together with the help of a bare conductor so 4s to protect the lineman
working on the lines agains inadvertent charging of the line. Sometimes after the
work, if lineman forgets to remove the tie up between phase lines and if the circuif
breaker is closed then three phase symmetrical fault occurs.Protection and Switchgear 1-9 Protective Relaying
The most serious effect of uncleared fauit is nothing but fire which «lestrovs the
equipment, spreads up in the system and causes total failure. The most common type
of fault which may prove to be dangerous is short circuit, Due to tis tault, there is
great reduction in line voltage over a major part of the power system. There is
damage which may result to the elements of the system by electric arc which
accompanies short circuit. The other apparatus in the system are damaged due to
overheating and due to setting up of abnormal mechanical forces. The stability of the
power system is disturbed which may sometimes result in complete shut down of the
power system. Due to reduction. in voltage, currents drawn by motors are abnormally
high. This may result into loss of industrial production. So such faults are avoided
from occuring by designing suitable and :eliable but economical protective scheme.
1.6 Fault Current Calculation using Symmetrical Components
In case of three phase balanced sys
magnitude and are displaced from each other by 120°. The currents and voltages are
thus said to be symmetrical. The analysis of such system is easy which is done on per
phase basis. But when the load is unbalanced, the analysis using normal techniques
becomes difficult, Under such case, method of symmetrical components can be
adopted as suggested by Fortescue. According to his theorem, the unbalanced phasors
can be resolved into three balanced systems of phasors. The balanced sets of
component can be given as (a) positive sequence component (b) negative sequence
component (c} zero sequence component.
E A system of vectors is having
-_— positive phase sequence when it has
all vectors having same magnitude
and are displaced by 120% They
have same time interval to achieve
fixed axis of reference as that of
generated voltage. The positive
Ean sequence is designated by use of
Fig. 1.4 Positive phase sequence with subscript P. Tt is shown in. the
anticlockwise rotation of vectors (1-2-3) Fig. 14 The vectors come to X axis
in order of 1, 2 and 3.
em, currents and voltages are equal in
A system of vector is having negative phase sequence when it has all vectors
having same magnitude and are displaced by 120" But arrive at the reference axis at a
regular interval same as that of positive sequence but in reverse order i.e, in order of
1, 3, 2. It is shown in the Fig. 1.4 suffix n is used to designate negative sequence.Protection and Switchgear 1-10 Protective Relaying
Ex
Fig. 1.5 Negative phase sequence with clockwise rotation of vectors. (1-3-2)
A system of vectors is having zero phase
—_——+ Ew sequence if all the three vectos are not
displaced in time from each other and there
will be no phase sequence. In such cases the
Ex current or voltage in the 3 phase circuit wil
vary simultaneaulsy in all the 3 phases. Such
Fig. 1.5(a) Zero phase sequence? Phase sequence is shown in the Fig. 1S(a)
suffix 0 is used to designate zero sequrnce:
———_- &
Consider a system having three vectors and it can be resolved into positive,
tive and zero phase sequence components as shown int the Fig. 1.6 It is possible
to get 3 vectors by using following equations.
E, = Etp + Bin + Evo
= Ex + Em + Ew
os
"
Exp + Bim + Ex
ie Ean
i) Positive sequence of phase Il) Negative sequence of phase iti) Zero sequence of phase
Fig. 1.6
Consider in general a power system network as shown in the Fig. 1.7 suppose that
fault occurs at point P in this system. Due to this currents I,. I. f, flow out of the
system while V,, V,, Vj are the line voltages with respect to groundProtection and Switchgear 114 Protective Relaying
B . If it is assumed that the system is
operating at no load before occuring a fault,
¥ then the positive sequence voltages of all
wht b synchronous machines will be equal and has
value same a3 prefault voltage at P. Let this
voltage be E,
The voltage E
positive sequence network. There is no
coupling between sequence network, the
sequence voltages at P can be given in terms
of sequence currents and Thevenin sequence impedance as
is present only in the
Fig. 1.7
Vp] JE] [Z, 9 0 fly
Vm) = }O/-10 Odl,
Vig o} Lo 0 Zy/lty
Based on the types of fault, the sequence voltages and currents are constrained
resulting to a particular connection of sequence networks. The sequence currents and
voltages and fault currents and fault voltages can then be easily obtained
1.7 Essential Qualities of Protective Relaying
A protective relaying scheme should have certain important qualities. Such an
essential qualities of protective relaying are,
1. Reliability
2 Selectivity and Discrimination
3. Speed and Time
4. Sensitivity
5. Stability
6. Adequateness
7. Simplicity and Economy
1.7.1 Rellabllity
A protective relaying should be reliable is its basic quality. It indicates the ability
of the relay system to operate under the predetermined conditions. There are various
components which go into the operation before a relay operates. Therefore every
component and circuit which is involved in the operation of a relay plays an
important role. The reliability of a protection system depends on the reliability of‘otection and Switchgear 1-12 Protactive Relaying
various component
transiormers (P.T.s), cables, trip circuits ete. The proper maintenance also plays an
important role in improving the reliable operation of the system. The reliability can
not be expressed in the mathematical expressions but can be judged from the
statistical data. The statistical survey and records give good idea about the reliability
of the protective system. The inherent reliability is based on the design which is based
on the long experience. This can be achieved by the factors like,
like circuit breakers, relays, current transformers (C.'T.s), potential
i) Simplicity ii) Robustness
High contact pressure iv} Dust free enclosure
iv} Good contact material vi) Good workmanship and
vi) Careful maintenance
4.7.2 Selectivity and Diserimination
The selectivity is the ability of the protective system to identify the faulty part
correctly and to disconnect that part without affecting the rest of the healthy part of
system. The discrimination means to distinguish between. The discrimination quality
of the protective system is the ability to distinguish between normal condition and
abnormal condition and also between abnormal condition within protective zone and
elsewhere, The protective system should operate only at the time of abnormal
"1 and not at the time of normal condition, Hence it must clearly discriminate
between normal and abnormal condition. Thus the protective system should select the
foulty part and disconnect only the faulty part without disturbing the healthy part of
the system,
condit
‘The protective system should not operate for the faults beyond its protective zone.
For example, consider the portion of a typical pawer system shown in the Fig, LS
O39
Fig. 1.8
It is clear from the Fig. 1.8 that if fault Fz occurs on transmission line then the
careuit breakers 2 and 3 should operate and disconnect the line from the remaining
1. The prote
e system should be selective in selecting faulty transmission tineProtection and Switchgear 1-13 Protective Relaying
only for the fault F; and it should isolate it without tripping the adjacent transmission
line breakers or the transformer.
If the protective system is not selective then it operates for the faults beyond its
protective zones and unnecessary the large part of the system gets isolated. This
causes a lot of inconvenience to the supplier and users.
1.7.3 Speed and Time
A protective system must disconnect the faulty system as fast as possible. If the
faulty system is not disconnected for a long time then,
1. The devices carrying fault currents may get damaged
2. The failure feads to the reduction in system voltage. Such low voltage may
affect the motors and generators running on the consumer side.
3. If fault persists for long time, then subsequently other faults may get
generated.
The high speed protective system avoids the possibility of such undesirable effects.
The total time required between the instant of fault and the instant of final arc
interruption in the circuit breaker is called fault clearing time. It is the sum of relay
time and circuit breaker time. The relay time is the time between the instant of fault
occurrence and the
stant of closure of relay contacts, The circuit breaker time is the
time taken by the circuit breaker to operate to open the contacts and to extinguish the
arc completely, The fault clearing time should be as small as possible to have high
speed operation of the protective system.
Though the small fault cle:
provided. This is because,
1. To hav
g time is preferred, in practice certain time lag is
e clear discriminat
between primary and backup protectic
2. To prevent unnecessary operation of relays under the conditions such as
transients, starting inrush of current etc
Thus fast protective system is an important quality which minimises the damage
and it improves the overall stability of the power system
1.7.4 Sensitivity
The protective system should be sufficiently sensitive 50 that it can operate reliably
when required. The sensitivity of the system is the ability of the relay system to
operate with low value of actuating quantity.
It indicates the smallest value of the actuating quantity at which the protection
starts operating in relation with the minimum value of the fault current in the
protected zone.Protection and Switchgear 1.14 Protective Retaying
y coil
The relay sensitivity is the function of the volt-amperes input to the rel
necessary to cause its operation. Smaller the value of volt-ampere input, more sensitive
is the relay. Thus 1VA input relay is more sensitive than the 5VA input relay.
Mathematically the sensitivity is expressed by a factor called sensitivity factor Ke,
It is the ratio of minimum short circuit current in the protected zone to the minimum
operating current required for the protection to start.
\
Ket
where Ks
1, = minimum short circuit current in the zone
sensitivity factor
1, = minimum operating current for the protection
1.7.5 Stability
The stability is the quality of the protective system due to which the system
remains inoperative and stable under certain specified conditions such as transients,
disturbance, through faults ete. For providing the stability, certain modifications are
required in the system design. In most of the cases time delays, filter creuits,
mechanical and electrical bias are provided to achieve stable operation during the
disturbances.
1.7.6 Adequateness
There are variety of faults and disturbances those may practically exists in a power
system. It is impossible to provide protection against each and every abnormal
condition which may exist in practice, due to economical reasons. But the protective
system must provide adequate protection for any clement of the system. The
aciequateness of the system can be assessed by considering following factors,
1. Ratings of various equipments
2 Cost of the equipments
3. Locations of the equipments
4. Probability of abnormal condition due to internal and external causes
5. Discontinuity of supply due to the failure of the equipment
41.7.7 Simplicity and Economy
In addition to all the important qualities, it is necessary that the cost of the system
should be well within limits, In practice sometimes it is not necessary to use ideal
protection scheme which is economically unjustified. In such cases compromise is
done. As a rule, the protection cost should not be more than 5% of the total cost. But
if the equipments to be protected are very important, the economic constraints can be
relaxed.Protection and Switchgear 1-15
The protective system should be as simple ax possible so that it can be easily
maintained. The complex system are difficult from the maintenance point of vi
simplicity and reliability are closely related to each other. The simpler systems are
always more reliable,
1.8 Classification of Protective Relays
All the relays consist of one or more elements which get energised and actuated
by the electrical quantities of the circuit, Most of the relays used now a da
electro-mechanical type which work on the principles of electromagnetic attraction and
electromagnetic induction.
are
1.8.1 Electromagnetic Attraction Type Relays
The electromagnetic attraction type relays operate on the principle of attraction
an armature by the magnetic force produced by undesirable current or movement
plunger in a solenoid. These relays can be actuated by ac. or dic. quantities. The
various types of these relays are,
1. Solenoid Type
and the oper:
In this relay, the plunger or iron core moves into a solenoid
jon of the relay depends on the movement of the plunger
Attracted Armature Type ; This relay operates on the current setting, W!
current in the circuit exceeds beyond the limit, the armature gets attracted by
the magnetic foree produced by the undesirable current. The current rating of
the circuit in which relay is connected plays an important role in the operation
of the relay
3. Balanced Beam Type : In this relay, the armature is fastened to a balanced
beam, For normal current, the beam remains horizontal but when current
exceeds, the armature gets attracted and beam gets tilted causing the required
operation
1.8.2 Induction Type Relays
These relays work on the principle of an electromagnetic induction. The use of
these relays is limited to a.c. quantities. The various types of these relays are,
1. Induction Dise Type : In this relay, a metal dise is allowed to rotate between
the two clectromagnets. The electromagnets are energised by alternating
currents. The two types of constructions used for this type are shaded pole
type and watthour meter type.
2. Induction Cup Type : In this relay, electromagnets act as a stator and
energised by relay coils. The rotor is metallic cylindrical cup typeProtection and Switchgear 1-16 Protective Relaying
1.8.3 Directional Type Relays
These relays work on the direction of current or power flow in the circuit. The
various types of these relays are,
1. Reverse Current Type : The relay is actuated when the direction of the current
is reversed or the phase of the current becomes more than the predetermined
value
2 Reverse Power Type : The relay is actuated when the phase displacement
between applied voltage and current attains a specified value
1.8.4 Relays Based on Timing
In relays the time between instant of relay operation and instant at which tripping
of contacts takes place, can be controlled. This time is called operation time, Based on
this, the time relays are classified as,
of relay
L. Instantaneous Type : In this type no time is lost between operatic
and tripping of contacts. No intentional time delay is provided
Definite Time Lag Type : In this type intentionally a definite
provided between operation of relay and tripping of contact
ime tag is
Inverse Time Lag type : In this type, the operating time is approximately
inversely proportional to the magnitude of the actuating, quantity
1.8.5 Distance Type Relays
These relays work on the principle of measurement of voltage to current ratio. In
this type, there are two coils. One coil is energised by current while other by voltage.
The torque produced is proportional to the ratio of the two quantities. When the ratio
reduces below a set value, the relay operates. The various types of these relay’ are,
|. Impedance Type : In this type, the ratio of voltage to current is nothing but an
impedance which is proportional to the distance of the relay form the fault
point.
2. Reactance Type : The operating time is proportional to the reactance which is
proportional to the distance of the relay from the fault point
3. Admittance Type : This is also called mho type. In this type, the operating
time is proportional to the admittance.
1.8.6 Differential Type Relays
A differential relay operates when the vector difference of two or more electrical
quantities in the circuit in which relay is connected, exceeds a set value, These are
class
as,Protection and Switchgear 1-17 Protective Relaying
1. Current Ditferential Type : In this type, the relay compares the current
entering a section of the system and the current leaving the section. Under
fault condition, these currents are different.
Voltage Differential Type : In this type, two transformers are used. The
secondaries of the transformers are connected in series with the relay in such @
way that the induced e.m.f.s are in opposition under normal conditions. Under
fault condition, primaries carry different currents due to which induced e.m.ts
no longer remain in opposition and the relay operates,
y
1.8.7 Other Types of Relays
Various other types of relays which are used in practice are,
1. Under voltage, current, power relay : This relay operates when the voltage,
current or power in a circuit falls below a set val
a
we
Over voltage, current, power relay : This relay actuates when the voltage,
current or power in a circuit rises above a set value.
3. Thermal Relay : This relay actuaies due to the heat produced by the current in
the relay coil.
4. Rectifier Relay : In this relay, the quantities to be sensed are rectified and then
given to the moving coil unit of the relay.
Permanent Magnet Moving Coil Relay : In this relay, the coil carrying current
is free to rotate in the magnetic field of a permanent magnet. This is used for
dec. only.
6. Static Relay : This relay uses some electronic method for sensing the actuating
quantity, It uses a stationary circuit.
7. Gas Operated Relay : The gas pressure is adjusted according to the variations
in the actuating quantity. This gas pressure is used to actuate the relay
Buchholz relay is an example of such type of relay
1.9 Terminologies used in Protective Relaying
The various terminologies used in the protective relaying are,
1. Protective Relay: It is an electrical relay, which closes its contacts when an
actuating quantity reaches a certain preset value. Due to closing of contacts,
relay initiates a trip circuit of circuit breaker or an alarm circuit.
2. Relay Time : It is the time between the instant of fault occurrence and the
instant of closure of relay contacts.
3. Breaker Time ; It is the time between the instant at circuit breaker operates
and opens the contacts, to the instant of extinguishing the arc completely.Protection and Switchgear 1
18 Relayin
z
10.
the instant of fault and
Fault Clearing Time : The total time required betwee
the instant of final arc interruption in the circuit breaker is fault clearing time.
It is sum of the relay time and circuit breaker time.
Pickup: A relay is said to be picked up when it moves from the ‘OFF
position to ‘ON’ position. Thus when relay operates it is said that relay has
picked up
Pickup Value: It is the minimum value of an octuating quantity at which
relay starts operating, In most of the relays actuating quantity is current in the
relay coil and pickup value of current is indicated along with the relay
Dropout or Reset : A relay is said to dropout or reset when it comes back to
original position ie. when relay contacts open from its closed position. The
value of an ing quantity current or voltage below which the relay cesets
is called reset value of that relay
Time Delay : The time taken by relay to operate after it has sensed the fault
is called time delay of relay. Some relays are instantaneous while in some
ntionally a time delay is provided.
relays in
Sealing Relays or Holding Relays : The relay contacts are designed for light
Weight and hence they are therefore very delicate. When the protective relay
closes its contacts, it is relieved from other duties such as time lag, tripping
ties are performed by auxiliary relays which are also called
ete. These
sealing relays or holding relays
‘Current Setting : The pick up value of current can be adjusted to the required
level in the relays which is called current setting of that relay. It is achieved by
use of tappings on the relay coil, which are brought out to a plug bridge as
shown in the Fig. 19. The tap values are expressed in terms of percen
fond rating of current transformer (C.T.) with which relay is associated
% current 100 125 150 200 Plug bridge
setting values
Tavelay cai!
Fig. 1.9 Tapping for current settingProtection and Switchgear 1-19 Protective Relaying
Thus the value of pickup current can be obtained as,
Pickup current = ‘ current setting x rated secondary current of C.T.
So if CT. is 500/10 A ie. rated secondary current is 10A and the current setting is
150 then pickup current is 15 x 10 = 15 A ie. 150% of 10. So when relay coil current
is greater than or equal to pickup values, relay operates.
11. Plug Setting Multiplier (P.S.M.); The ratio of actual fault current in the relay
coil to the pickup current is called plug setting multiplier (P-5.M.)
Mathematically it can be expressed as,
_ fault current in relay coil
PSM Pickup value
rated secondary current of CT.
12. Time/P.S.M. Curve : For a relay, a curve showing relation between time and
plug-setting multiplier is provided which is called time/P-S.M. curve. A typical
curve for a relay is shown in the Fig. 1.10.
It can be observed that
for low values of
‘overcurrents the operating
time varies inversely with
the current, But as the
current increases = and
approaches upto 20 times
its rated value then the
time becomes: almost
constant. This type of
characteristics is necessary
Time jn sec
9 246 6 0124 to ensure discrimination
—— PSM. on very high — fault
Fig, 1.10 Time / P.S.M.'curve currents flowing through
healthy part of the system
Using this curve and time-setting multiplier, the actual time of operation of a relay
can be obtained, For example, the time in seconds corresponding to PS.M. of 10 is 4
seconds as shown in the Fig. 1.10. Multiplying this by a time-setting multiplier, actual
time of operation can be obtained.
13, Time-setting Multiplier: Similar to current setting, a relay is provided with
a feature with which its time of operation can be controlled. This feature isProtection and Switchgear 1-20 Protective Relaying
known as time-setting
multiplier. Its dial is
calibrated from @ to 1 in
steps of 0.05 as shown in
the Fig. 1.11
The value: of
time-setting multiplier along
with the time obtained from
time/P.SM. curve decides
the actual time of operation
Fig. 1.11 Time-setting multiplier of the relay. For example if
time-setting multiplier is
selected as 0.2 while time corresponding to P-S.M, of 10 is 4 seconds then,
. 1
Actual time of operation = time in seconds « time-setting multiplier
= 4 02 =08 seconds
14. Trip Circuit: The opening operation of circuit breaker is controlled by a
circuit which consists of trip coil, relay contacts, auxiliary switch, battery
supply etc. which is called trip circuit
tarth Fault: The fault involving earth is called earth fault. The examples of
earth fault are single line to ground fault, double line to ground fault etc
15.
16. Phase Fault : The fault which does not involve earth is called phase fault. The
example is line to line fault.
17, Protective Scheme : The combination of various protective systems covering a
particular protective zone for a particular equipment is called protective
scheme, For example a generator may be provided with protective systems like
overcurrent, differential, earth fault etc. The combination of all these systems is
called generator protective scheme.
18. Protective System : The combination of circuit breakers, trip cin
other protective relaying equipments is called protective system.
19. Unit Protection : A protective system in which the protection zone is clearly
defined by the C:T. boundaries is called unit protection. Such systems work for
internal faults only.
and
its, C.
20. Reach ; The limiting distance in which protective system responds to the
faults is called reach of the protective system. The operation beyond the set
distance is calied over-reach while failure of distance relay within set distance
is called under-reach.Protection and Switchgear 1-24 Protective Relaying
1.10 Instrument Transformers
In heavy currents and high voltage a.c. circuits, the measurement can not be done
by using the method of extension of ranges of low range meters by providing, suitable
shunts. In such conditions, specially constructed accurate ratio transformers called
instrument transformers. These can be used, irrespective of the vol
ratings of the a.c. circuits. These transformers nat only extend the range of the low
range instruments but also isolate them from high current and high voltage ac
circuits. This makes their handling very safe. These are generally classified as (i)
current transformers and (ii) potential transformers.
age and current
1.11 Current Transformers (C.T.)
The large alternating currents which can not be sensed or passed through normal
ammeters and current coils of wattmeters, energymeters can easily be measured by
use of current transformers along with normal low range instruments
A transformer is a device which consists of two windings called primary and
ide to another with suitable change in the
level of current or voltage. A current transformer basically has a primary coil of one
secondary. It transfers energy from one
or more tums of heavy cross-sectional
7 area, In some, the bar carrying high
current may act as a primary, This is
connected in se
carrying high current.
with the line
The secondary of the transformer
is made up of a large number of turns
of fine wire having small
cross-sectional area. This is usually
Fig. 1.12 Current transformer rated for 5A, This is connected, to the
coil of normal range ammeter,
Symbolic representation of a current transformer is as shown in the Fig. 1.12.
4.14.4 Working Principle
These transformers are basically step up transformers ie. stepping up a voltage
from primary to secondary. Thus the current reduces from primary to secondary. So
from current point of view, these are step down transformers, stepping down. the
current value considerably from primary to secondary.
Let Ny
Number of turns of primary
N
Number of turns of secondary
1, = Primary current1-22 Protective Relaying
Secondary current
As N; is very high compared to Nj, the ratio I, to 1, is also very high for current
transformers, Such # current ratio is indicated for representing the range of current
transformer, For example, consider a 500 : 5 range then it indicates that CT. Steps
down the current from primary to secondary by a ratio 500 to 5
i, _ 500
I, 2
Knowing this current ratio and the meter reading on the secondary, the actual
high line current flowing through the primary can be obtained.
mu> Example 1.1: 4 250 : 5, current transformer is use? along with an ammeter. If
ammeter reading is 2.7 A, estimate the line current.
Solution :
1 = 135A
So line current is 135 A.
1.42 Construction of Current Transformers
There are two types of constructions used for the current transformers which are,
1. Wound type
2. Bar type
1.12.1 Wound Type Current Transformer
In wound type construction, the primary is wound for more than ene full tum, on
the core. The construction is shown in the Fig. 1.13Protoctive Ralaying
Fig. 1.13 Wound type current transformer
In a low voltage wound type current transformer, the secondary winding is
wound on a bakelite former, The heavy primary winding is directly wound on the top
of the secondary winding with a suitable insulation in between the two. Otherwise the
primary is wound completely separately and then taped with suitable insulating
material and assembled with the secondary on the core,
The current transformers can be ring type or window type. Some commonly used
shapes for the stampings of window type current transformers are shown in the
Fig. 1.14.
TO 0
(a) Rectangular (b) Ring (¢) Stadium
Fig. 1.14 Stampings for current transformers
The core material for wound type is nickel-iron alloy or an oriented electrical steel.
Before installing the secondary winding on core it is insulated with the help of end
collars and circumferential wraps of pressboards. Such pressboards provide additional
insulation and protection to the winding from damage due to the sharp cornersProtection and Switchgear 1628 Protective Relaying
4.12.2 Bar Type Current Transformer
In this type of current transformer, the primary winding is nothing but a bar of
suitable size. The constriction is shown in the Fig. 1.15.
Seconds Bartype
a primary
Core
Seconcary
4.15 Bar type current transformer
The insulation om the bar type primary is bakelized paper tube or a resin directly
moulded on the bar. Such bar type primary is the integral part of the current
transformer. The core and the secondary windings are same in bar type transformer.
The stampings used for the laminations in current transformers must have high
cross-sectional area than the ordinary transformers. Due to this, the reluctance of the
interleaved corners remains as low as possible. Hence the corresponding, magnetizing
current is also small. The windings are placed very close to each other so as to reduce
the leakage reactance. To avoid the corona effect, in bar type transformer, the extemal
diameter of the tube is kept large.
The windings are so designed that without damage, they can withstand short
circuit forces which may be caused due to short circuit in the circuit in which the
current transformer is inserted.
For small line voltages, the tape and varnish are used for insulation. For line
voltages above 7 kV the oil immersed or compound filled current transformers are
used.
1.13 Why Secondary of C.T. Should not be Open 7
It is very important that the secandary of CT. should not be kept open. Either it
should be shorted or must be connected in series with a low resistance coil such as
current coils of wattmeter, coil of ammeter etc. If it is left open, then current through
secondary becomes zero hence the ampere tums produced by secondary whichProtection and Switchgear 1-28 Protective Relaying
generally oppose primary ampere tums becomes zero, As there is no counter mm,
unopposed primary m.mf. (ampere tums) produce high flux in the core. This
produces excessive core losses, heating the core beyond limits. Similarly heavy e.mfs
will be induced on the primary and secondary side. This may damage the insulation
of the winding. This is danger from the operator point of view as well. It is usual to
ground the C.T. on the secondary side to avoid a danger of shock to the operator.
Hence never open the secondary winding circuit of a current transformer while its
primary winding is energised.
Thus most of the current transformers have a short circuit link or a switch at
secondary terminals. When the primary is to be energised, the short circuit link must
be closed so that there is no danger of open circuit secondary
1.14 Potential Transformers (P.T.)
The basic principle of these transformers is same as current transformers. The high
alternating voltage are reduced in a fixed proportion for the measurement purpose
with the help of potential transformers. The construction of these transformers is
similar to the normal transformer, These are extremely accurate ratio step down
transformers. The
lings are low power rating windings. Primacy winding con
of large number of turns while
secondary has less number of tums and
usually rated for 110 V, irrespective of
the primary voltage rating. The primary
is connected across the high voltage line
while secondary is connected to the low
range voltmeter coil. One end of the
secondary is always grounded for safety
Primary of PT.
purpose. The connections are shown in
Fig, 1.16 Potential transformer the Fig, 1.16.
As a normal transformer, its ratio can be specified as,
Ny
So if voltage ratio of P-T. is known and the voltmeter reading is known then the
high voltage to be measured, can be determined,
mp Example 1.2: A 11000 : 110, potential transformer is used along with a vattmeter
reading 87.5V. Estimate the value of line voltageProtection and Switchg Protective Relaying
Solution
11000
T10-
= &75V
11000
110
and
= 8750 ¥
This is the value of high voltage to be measured.
1.14.1 Construction
The potential transformer use larger core and conductor sizes compared to
conventional power transformer. In potential transformer, economy of material is not
time of design. The
an important consid actu
consideration
acy is an important
The shell type or core type construction is preferred for potential transformer. The
shell type is used for low voltage while core type for high voltage transformers. At
the time of assembly special core is required to reduce the effect of air gap at the
joints
The coaxial primary and secondary windings are used, to reduce the leakage
reactance. The secondary winding which is a low voltage winding is always next ta
the core, The primary winding is a single coil in low voltage transformers. For high
voltages, insulation i the main problem. Hence in high voltage potential transformers,
primary is divided into number of small sections of short coils to reduce the need of
insulation between coil layers.
The cotton tape and varnished cambric are used as the insu
Hard fiber separators are used in between the cc
transformers are used for the voltage levels above 7 kV.
tions for windings.
js. The oil immersed potential
For oil filled potential transformers, oil filled bushings are used. Two bushings are
required when no side of the line is at earth potential.
The overall construction of single phase, two winding potential transformer is
shown, in the Fig. 1.17.Protection and Switchgear
Protective Relaying
Secondary
low voltage
winding
Primary
High vottage
bushings,
neuiaton
high woitage
‘winging
1.15 Comparison of C.T. and P.T.
The comparison of C.T. and PT. is given in the following table,
Fig. 1.17 Single phase potential transtormer
Sr. Current Transformer Potentiat Transformer
No.
1. | it can be treated as series transtormer under| it can be weated at parallel transtormer
viflval short circu conditions, under open cirewt secondary.
2 Secondary must be always shorted ‘Secondary is nearly under open circuit
conditions
a A small vonage exists across its terminals as) Full line vollage appears cross Ite terminals
connected in series
4 |The winding caries ful ine current ‘Tho winding bs impcessad with ful line
voltage.
6. The primary current and excitation vanes. ‘The line voltage is simost constant hence
over a wie range. exciting current and flux density varies over
a limited range.
8. | The primary convent is independent of the | The primary current depends on the
secondary oxcut conditons,
secondary circus conditions
Needs only one bushing as the Iwo ence of
primary winding are Brought out through the
same insulator Hence there Is saving in
cost,
Twa bus
cot the i
ings are required when neither sie
if at ground potenti
Table 12Protection and Switchgear 1-28 Protective Relaying
1.16 Errors in the Instrument Transformer
For an instrument transformers, it is necessary that the transformation ratio must
be exactly equal to turns ratio and phase of the secondary terms (voltage and current)
must be displaced by exactly 180° from that of the primary tenns (voltage and
current). Two types of errors affect these characteristics of an instrument transformer
which are,
1. Ratio error
2. Phase angle error
1.16.1 Ratio Error
In practice it is said that current transformation ratio 1, / 1, is equal to the tums
ratio N, / Nz. But actually it is not 90. The current ratio is not equal to turns ratio
because of magnetizing and core loss components of the exciting current. It also gets
affected due to the secondary current and its power factor. The load current is not a
constant fraction of the primary current. Similarly in case ef potential transformers, the
voltage ratio V, /V, is also not exactly equal to N,/N, due to the factors
mentioned above. Thus the transformation ratio is not constant but depends on the
load current, power factor of load and exciting current of the transformer. Due to this
fact, large error is introduced in the measurements done by the instrument
transformers, Such an error ix called ratio error.
The ratio error is defined as,
nominal ratio — actual ratio
% Ratio error = : 100
‘actual ratio
= Styx 100
where K, = feed ier corre . for ©. T.
rated secondary current
ted pri volta
_ _fated primary voltage for PT
rated secondary voltage
and Re actual primary current bee CT.
corresponding secondary current
actual primary voltage for Pt
corresponding secondary voltage uo
The approximate formula to calculate R is given by,Protection and Switchgear 1-20 Protective Relaying
Re
where n = turns ratio
I, = less component of exciting current
1, = secondary current
Now
here 1, = primary currer
while precisely the formula to calculate R is,
1,, sin8 +1, cosé
R= ne
n 7
where 1,, = magnetising component of exciting current
5 = angle between secondary winding induced voltage
and. secondary winding current
3 is positive for lagging p.f. and negative for leading pf
1.16.2 Phase Angle Error
In the power measurements, it is must that the phase of secondary current is to be
displaced by exactly 180° from that of primary current for C-T. While the phase of
secondary voltage is to be displaced by exactly 180" from that of primary voltage, for
PT. But actually it is mot so. The error introduced due to this fact és called phase
angle error. It denoted by angle @ by which the phase difference between primary and
secondary is different from 180°.
‘The precise expression to calculate the angle @ is,
ind
o-= degreeProtection and Switchgear 1-30 Protective Relaying
1
alz
1
+ | degree
Lh
Similar to ratio error, this error also depends on the components of exciting
current (1), load current ie, secondary current and power factor. This error does not
affect the measurements of only current or veltage but do affect at the time of power
and energy measurements.
The phase angle error for P.T. is defined as,
i
[X, cos6-R,, sind]+icX, -1,R; rad
g- ak ee
nv;
i LX =p;
Oe Ve, Pe 008 B — Ray sin 8] Vy
where & = secondary pf. angle
R,, = equivalent resistance of transformer referred to
R
secondary = R; +R; =R) +
at
Xa. = equivalent reactance of transformer referred to
secondary = X; + Xj =X) + x
nt?
X, = reactance of primary winding
R, = resistance of primary winding
¥, = primary voltage
V, = secondary voltage
l= Leese and In =k sin b
where %, = no load power factor angle
Xye = equivalent reactance of transformer referred to primary
= Xp +X =X) +n? x,
R,, = equivalent resistance of transformer referred to primary
= R,+R)=R, +n R;
and n= we Me for potential transformer
2Protection and Switchgear 1-31 Protective Relaying
1.16.3 Reduction of Ratio and Phase Angle Errors
The ratio and phase angle errors can be minimized by using following methods
1. As the errors depend on components of exciting current, reduce the
magnetizing and loss components of exciting current. This requires to provide
smaller magnetic path, good core material and low flux density in core
Reduction of resistance and leakage reactance. The values decide the secondary
cireult power factor which affects the errors. This can be achieved by providing
thick conductors and smaller length of mean turn
Providing turns compensation at no load the actual ratio exceeds the turns
ratio thus the solution to this is to reduce primary tums or increasing
secondary turns and to make actual ratio equal to nominal ratio for one
particular value af load.
wim Example 1.3: The no load current components of a ctirtent transformer are,
magnetizing component = 102A
38A
turrent transformati
it howd.
Solution : Iq = IQA, Ic = 38A
1000 _
core foss component
T
ratio is 1000 / 5 A. Calculate the approximate ratio error at
nominal ratio 200
At full load, l; =
200- 207.6
% Ratio error = 100
ae Example 14: A current transformer hes @ single turn primary and 400 secondary
ignetizing current is 90A while core loss current is 404. Secondary circuit
phase angle is 28°. Calculate the actual primary current and ratio error when secondary
carries SA current,
turns, The m
Solution : 1, = 90A, 1, = 40A, 5 = 28%,1, = 5A
n= 2 ~ 409Protection and Switchge:
Now actual ratio «RR
1-32
te Sind +1, 6088
Nx sin 28 + 40x cos 28
400 +
5
415.514
Actual primary current » actual ratio * 1,
% Ratio error
415514 = 5 = 20775703
K,- Ro _ 400- 415514
Rs ass 1
-3.733%
Protective Relaying
um Example 1.5: A current transformer has turns ratio 1399 mud is rated as 200054.
The
sore foss component is 3A and magnetizing component is 8A, wnder full load
conditions. Find the-phase angle and ratio errors under full load condition if secondary
circuit power factor is 0.8 leading
Solution : k
8
Nominal ratio
Actual ratio
Rated I
4
sin
% Ratio error
and 8
3A, 1,,= 8A, cos 8 = 08 leading
3 a 399
cos"! 0.8 = ~ 36.86"
sin (-36.869 = - 0.6
4 BxE0.6)430.8
399. z
398 . 52
K,-R 400-398.52
ig 100 = «100
0.3713%
180[1.,, 0088 -I¢ sind ]
® ni; J
ve as leadingProtection and Switchgear 1-33 Protective Relaying
180 [8x 0.8-3x(-0.6)
x 3095
= 0.2355"
1.17 Advantages and Disadvantages of Instrument Transformers
The advantages of instrument transformers can be listed as,
1. The normal range voltmeter and ammeter can be used along with these
transformers to measure high voltage and currents.
2. The rating of low range meter can be fixed irrespective of the value of high
voltage or current to be measured
‘These transformers isolate the measurement from high voltage and current
circuits, This ensures safety of the operator and nwkes the handling of the
equipments very easy and safe.
4. These can be used for operating many types of protecting devices such as
relays or pilot lights.
5. Several instruments can be fed economically by single transformer.
Disadvantage ;
The only disadvantage of these instrument transformers is that they can be used
only for a.c. circuits and not for d.c, circuits.
Applications of C.1.s and P.T.s :
The C.1's and P.T.s are used for,
1. Circulating current differential protection
2. Over current phase fault protection.
3. Distance protection
4. Intermediate CTs for feeding protective devices, measuring systems, relays etc
Review Questions
What i& protective relaying ? What i a reloy *
Paplain the oarious functions of protective relaying
What is a protective zone ? With a simple diagram, show the tarious zones im ci typical power
systent
Why the protective ames are arranged in overlap fashion ? With the help of sample diagram, shocr
how the zones are ocerlappedt
Explain tohat és miemt by primary protection and backup protection.
Slate the taraous nsethoste used fo provide hachiep protectionsProtective Relaying
Discuss the basic action of backup protection
Diserss the quality of “relabllity’ of a protectioe relaying. Which Sectors affect the eclibilty ?
1. Discuss in brief the various essential qualities of protective relaying.
Daoine ond explsie relay time, brenker time anc fault clearing time.
Wty Hite delay is intentionally provided in practical relays ?
Discuss the classification of protective relays.
Explain the following terms related to protective relaying
it Pickup {i) Dropout or reset it) Time etry
Joy Holding relay 0) Trip cineuit vi) Protectize scheme
vith Protective systens vii) Current setting ix} Plug-setting exltiplier
1h Tiite-settnne menitiplier
What is time S.M. curee ? How it cam be used to obtain the actual operation time of « reloy *
g99Electromagnetic Relays
2.1 Introduction
An important clement of any protective relaying scheme is a relay. It is a device
which detects the fault and is responsible to energize the trip circuit of a circuit
breaker. This isolates the faulty part from rest of the system. In an electromagnetic
relay, the driving torque is created based on an electrical or electronic principle, While
the restfining torque is generally provided with the help of springs. The two torg
are mechanically compared and the relay operates when driving or operating torque is
more than the restraining torque. Thus,
Ts = Driving torque or operating torque
Restraining torque
T, = Resultant torque = TT,
s
The relay operates when the resultant torque Ty is positive. Let us study the basic
action of a trip circuit with a relay
2.1.1 Basic Trip Circuit Operation
Consider a simplified circuit of a typical relay as shown in the Fig. 2.1. Usually the
relay circuit is a three phase circuit and the contact circuit of relays is very much
complicated, The Fig. 2.1 shows a single phase simplified circuit to explain the basic
action of a relay. Let part A is the circuit to be protected. The current transformer C.T
is connected with its primary in series with the line to be protected. The secondary of
CT. is connected in series with the relay coil. The relay contacts are the part of a trip
circuit of a circuit breaker. The trip circuit consists of a trip coil and a batt
addition to relay contacts. The trip circuit can operate on ac. or dc.
If the fault occurs as shown in the Fig. 21, then current through the line
connected to A increases to a very high value. The current transformer senses this
current. Accordingly its secondary current increases which is nothing but the current
through a relay coil, Thus the relay contacts get closed mechanically under the
influence of such a high fault current. Thus the trip circuit of a circuit breaker gets
closed and current starts flowing from battery, through trip coil, in a trip circuit, Thus
the trip coil of a circuit breaker gets energised. This activates the circuit breaker
opening mechanism, making the circuit breaker open. This isolates the faulty part
from rest of the healthy system
(@-9)Protection and Switchgear 2-2 Electromagnetic Relays
Tep eat ~ Trp circu
the Faw
s
Circuito be
ratected
Fig. 2.4 Typical relay circuit
2.1.2 Auxiliary Switch
Another important device in the trip circuit is an auxiliary switch. It ts a
multipoint switch generally 4 point, @ point, 12 point or 24 point. This switch is
mechanically coupled with operating mechanism of the circuit breaker. Thus when
circuit breaker opens, the switch also gets opened. The switch is in the trip circuit and
hence when it opens, it breaks the current through the trip circuit. Once the current in
the trip circuit is interrupted the relay contacts come to normal position. The
advantage of an auxiliary switch is that the breaking of trip circuit takes place only
across the switch and hence possible arcing due to current interruption across the
relay contacts gets avoided. Such arcing is harmful for relay contacts as relay contacts
te and light. To interrupt a current through the inductive circuit like trip
cireuit a robust mechanical switch is necessary. This purpose is served by an auxiliary
switch, protecting delicate relay contacts. In addition to this, indication circuits
showing whether circuit breaker is open or close and some other control circuits also
get connected or disconnected by an auxiliary switch.
The auxiliary switch is generally placed in the control cabinet of the circuit
breaker.
2.2 Tripping Schemes in Circult Breaker
Two schemes are very popularly used for tripping in circuit breakers which are,
1. Relay with make type contact 2. Relay with break type contact
The relay with make type contact requires auxiliary dic. supply for its operation
while the relay with break type contact uses the energy from the main supply source
for its operation. Let us see the details of these two types of schemes.Protection and Switchgear 2-3 Electromagnatic Relays
2.2.1 Relays with Make Type Contact
The schematic diagram representing the arrangement of various elements in a
relay with make type contact is shewn in the Fig. 22
Ro oY 8B
Battary
- supply
Equipment to be
protected
Fig. 2.2 Relay with make type contact
As mentioned earlier, a separate supply is necessary for the relay operation. The
relays are connected in star while the relay contacts are connected in parallel. The
entire relay contact unit is connected in series with the auxiliary switch, trip coil and
the battery, Relay contacts are open in normal position.
Operation : When the fault occurs, the current through relay coils increases to a
very high value. Due to this, the normally open relay contacts C,, C; and C; get
closed. This activates the trip coil of a circuit breaker. The auxiliary switch is initially
closed along with the circuit breaker, So when contacts C,, C; and Cy are cloved, the
current flows through trip coil of circuit breaker. This activates the trip coil which
‘opens the circuit breaker. As auxiliary switch is mechanically coupled with the circuit
breaker, it also gets opened. This interrupts the current through trip coil. Thus supply
to faulty part gets interrupted and trip coil also gets de-energized. This brings the
relay contacts back to normal position. Due to auxiliary switch, arcing across relay
contacts gets avoided. As relay contacts are normally open and they ‘make’ the circu
to open the circuit breaker hence called make type contact relayProtection and Switchgear 2-4 Electromagnetic Relays
2.2.2 Relay with Break Type Contact
The schematic arrangement of various elements in a relay with break type contact
is shown in the Fig. 22.
Equipment to
be protecies
Fig. 2.3 Relay with break typo contact (using C.T.s}
This type of relay does not require external battery supply for the tripping. T
current transformers (CTs) or potential transformers (V".T-s) are used to derive the
energy required for the relay from the main supply source. The relay using CTs to
derive operating energy from the supply is shown in the Fig. 23.
In this scheme, the r
The th
oc n supply using
CTs. The trip coils of circuit breakers are de-energized under normal condition. When
the fault occurs, heavy current flows through relay coils due to which relay contacts
Cy, C; and C) break. Thus current flows through trip coils of circuit breaker due to
which circuit breaker gets open.
coil and tip coil of each phase
phases are then conne
connected in seri
jed in star. Under normal working, the relay con
and Cy are closed. The energy for relay coils is derived fr
The Fig. 2.4 shows the break type contact relay using I'"T. to derive energy to keep
relay coils energized,Protection and Switchgear 2-5 Electromagnetic Relays
R YB
Creve
breaker
Fig. 2.4 Rolay with break type contact (Using P.T.)
In this type, in addition to normal trip coils of circuit breaker, an additional
undervoltage trip coil is used. All the relay contacts are in series the
undervoltage trip coil. Through potential transformer, for normal voltage, the
undervoltage trip coil is kept energized, When the voltage becomes less than the
normal value, the magnetic effect produced by undervoltage trip coil reduces which is
responsible for the opening of the circuit breaker. When fault occurs, the normal trip
coils of circuit breaker come into the picture and are responsible for the opening of
the circuit breaker,
In both the types, relay contacts ‘break’ to cause the circuit breaker operation hence
the relay is called break type contact relay.Protection and Switchgear 2-6
2.3 Electromagnetic Attraction Relays
In these relays, there is a coil which enerzises am electromagnet _ When the
operating current becomes large, the magnetic field produced by an electromagnet is
so high that it attracts the armature or plunger, making contact with the trip circuit
are simplest type of relays, The various types of electromagnetic
attraction type relays are,
contacts. Thes
}. Attracted armature relay
2. Salenoid and plunger type relay
2.3.1 Attracted Armature Type Relay
¢ are two types of structures available for attracted armature type relay which
i) Hinged armature type
ii) Polarised moving iron type
The twa types of attracted armature type relays are shown in the Fig. 2.5ta) and (bp
To trip circuit
Moving
iron
To tip oircunt
Etestromagnet
é
Input input
Vort Vor!
(a) Hinged armature type relay {fo} Polarised moving won type relay
Fig. 25
in attracted armature type, there exists a laminated electromagnet which carries a
coil. The coil is energized by the operating quantity which is proportional to the
circuit voltage or current. The armature or a moving iron is subjected to the magnetic
force produced by the operating quantity. The force produced is proportional to the
square of current hence these relays can be used for a.c. as well as dc, The spring isProtection and Switchgear 2-7 Electromagnotic Rolays
used ta produce restraining force. When the current through coil inereases beyond. the
limit under fault conditions, armature gets attracted. Due to this it makes contact with
contacts of a trip circuit, which results in an opening of a circuit breaker
The minimum current at which the armature gets attracted to close the trip circuit
is called pickup current.
Generally the number of tappings are provided on the relay coil with which its
turns can be selected as per the requirement. This is used to
operating quantity at which relay should operate
djust the set value of an
An important advantage of such relays is their high operating speed. In modem
relays an operating time as small as 05 msec is possible. The current-time
characteristics of such relays is hyperbolic, as shown in the Fig. 26.
Operating
{ime ia
50
49
30
20
0 070030 Curent
in toting
Fig. 2.6 Current-time characteristics
2.3.2 Solenoid and Plunger Type Relay
The Fig, 2.7 shows the schematic arrangement of solenoid and plunger type relay
which works on the principle of electromagnetic attraction
It consists of a solenoid which is nothing but an electromagnet, It also consists a
movable iron plunger. Under normal working conditions, the spring holds the plunger
in the position such that it cannot make contact with trip circuit contacts.
Under fault conditions when current through relay coil increases, the solenoid
draws the plunger upwards. Due to this, it makes contact with the trip circu
contacts, which results in an apening of a circuit breaker.Protection and Switchgear 2-8 Electromagnetic Relays
Electromagnet ——e|
To tip circuit
Movatie
von plunger
[Spring
Fig. 2.7 Solenoid and plunger type relay
2.3.3 Operating Principle of Electromagnetic Attraction Relays
The electromagnetic force produced due to operating quantity which is exerted on
armature, moving iron or plunger is proportional to the square of the flux in the air
gap. Thus neglecting the saturation effect, the force is proportional to the square of the
operating current. Hence such relays are useful for ae. and dic. both
For dic. operation : In d.c. operation, the electromagnetic force is constant. When
this force exceeds the restraining force, the relay operates.
Now F, = KP
where F, = Electromagnetic force
K, = constant
1 = Operating current in a coil
And F, = Ky
where F, = Restraining force due to spring including friction
K, = Constant
On the verge of relay operating, electromagnetic force is just equal to the
restrai
ing forceProtection and Switchgear 2-9 Electromagnetic Relays
KP = Ky
>_k
eo
1 1k, = constant
This is the cure
at which relay operates in case of d.c, operation
For ac. operation : In a.c. electromagnetic relays, the electromagnetic force is
proportional to square of the current but it is not constant. It is given by,
where I, = Maximum value of the operating c
K = constant
It shows that the electromagnetic force consists of two components
i) Constant, independent of time.
ii) Pulsating at double the frequency of applied voltage.
The total force thus pulsates at double the frequency:
If the restraining force F, which is produced by the spring is constant then the
armature of relay will be picked up at time t; and it drops off at time t, as shown in
the Fig. 2.8.
Fig. 2.8 Electromagnetic force and current curves
Thus relay armature pulsates at double frequency. This causes the relay to hum
and produces a noise. It may cause damage to the relay contactsProtection and Switchgear 2-10 Electromagnetic Relays
To overcome this difficulty, the air gap flux producing an electromagnetic force is
divided into two fluxes acting simultaneously but differing in time phase. This causes
resulting electromagnetic force to be always positive. If this is always greater than
restraining force F, then armature will not vibrate. The phase lag between the twa
components of flux can be easily produced using shading in a relay, The flux through
the shaded pole lags behind the flux through the unshaded part
2.3.4 Advantages of Electromagnetic Relays
The various advantages of electromagnetic relays are,
1. Can be used for both ac, and dc
2. They have fast operation and fast reset
3. These are a taneous. Though instantaneous, the operating tine
varies with current. With extra arrangements like dashpot, copper ring etc
slow operating and resetting times can be obtained
4. High operating speed with operating time in few milliseconds also can be
achieved
5. The pickup can be as high as 90-95% for d.c. operation and 601 to 90% for the
ion.
dc. oper:
6 Modern relays are compact, simple, reliable and robust
2.3.5 Disadvantages of Electromagnetic Relays
The few disadvantages of these relays are,
1. The directionat feature is absent.
2. Due to fast operation the working can be affected by the transients. As
transients contain d.c. as well as pulsating component,
less than set value, the relay can operate during transients.
jer steady state value
2.3.6 Applications of Electromagnetic Relays
The various applications of these relays are,
1. The protection of various ae. and dic. equipments
2 The over/under current and over/under voltage protection of various a.c. and
de. equipments
3. In the definite time lag over current and earth fault protection along
definite time lag over current relay.
4. For the differential protection.
Used as auxiliary relays in the contact systems of protective relaying schemes.Protection and Switchgear 2-11 Electromagnetic Relays
2.4 Induction Type Relays
The induction type relays are also called magnitude relays. These relays work on
the principle of the induction motor or an energy meter. In these relays a metallic
is allowed to rotate between the two electromagnets. The coils of the electromagnets
are energized with the help of alternating currents. The torque is produced in these
ion of ong alternating flux with eddy currents induced in the
by another alternating flux. The two fluxes have same frequency but
displaced in time and space. As the interaction of alternating fluxes is the base of
operation of these relays, these are not used fer the dic, quantities. These are widely
used for protective relaying involving only a.c. quantities.
relays due fo the interac
Based on the construction, the various types of the induction type relays are,
1. Shaded pole type
2 Watt hour meter type
3. Induction cup type
Before studying these types in detail, let us derive the torque equation for the
induction type relays, which is same for all the three types of relays.
2.4.1 Torque Equation for Induction Type Relays
As mentioned earlier, the a ing currents supplied to two electromagnets
produce the two alternating fluxes $, and >. These two fluxes have same frequency
but they have a phase difference of « in between them such that 2 leads oy. Thus the
two fluxes can be mathematically expressed as,
ferna
$1 = 1m sin ot (
+
$2, Sin (at + 0 a
These alternating fluxes
cause the induced em.fs in the
rotor. Due to the induced
e.més, the eddy currents i; and
ig are circulated in the disc. The
two eddy currents react with
each other to produce a force
hich acts on the rotor
The Fig. 29 shows how the
forces are produced in a section
of rotor due to the alternating
fluxes. The instant considered
to show the various quantities is when both the fluxes are directed downwards and
Fig. 2.9 Torque productionProtection and Switchgear 2-12 Electromagnotic Relays
are increasing in magnitude, The induced eddy currents lag behind the respective
fhuxes by 90°,
Assumption : The parts of rotor in which rotor currents flow have negligible
stance and hence the rotor currents are in phase with the respective indw
voltages
The induced voltages are proportional to the rate of change of fluxes and hence
the eddy currents also are proportional to the rate of change of fluxes. Hence we ean
write
de,
8)
SO at
do,
i, « Ma 4)
a ae
Substituting ¢) d @2 from (1) and (2) we get,
1G im SOY oy. cos ut 6)
dt
ig x Altan sinGor eel yg. cos (ut «a) (6)
dt
The forces are produced due to the interaction of @, with iy and §) with {,
B® tig a
and Fy bi ®)
The directions of F, and F, can be obtained by Flemings left hand rule. It can be
sven from the Fig. 2.9 that the two forces are acting in the opposite directions and
hence the net force acting on the disc is proportional to the difference between the
two forces
Fo« Fp-F
Foe Qrip~ Orin °)
Substituting the proportional expressions of §,, $9, i. iy from (1). (2), (5) and (6) in
the equation (9) we get.
F [bay $1 (68 +) 4 COS OL ~ $y,,8iN wt }5,,cO8K0K + c)}
= G1m Gam [sin (ot + a) cos (cat) - sin (ad) cos (ot + ce) ]
© Pim 2m [sin (eat + a at) ]
F * Gn boq sing a0)Protection and Switchgear 2-13 Electromagnetic Relays
The equation (10) gives the net force acting on the disc which is proportional to
sin
Substituting the rm.s. values of the fluxes instead of maximum values we get.
=o) sing (a)
It is important to note that the net force or torque acting on the disc is same a
every instant, The action of relay under such force is free from vibrations.
It can be observed from the equation (10) that if a is zero then the net force is
zero and dise cannot rotate. Hence there must exist a phase difference between
two fluxes. The torque is maximum when the phase difference a. is %F.
The direction of the net force which decides the direction of rotation of disc
depends on which flux is leading the other. In practice various constructions are used
to produce phase displacement between the two fluxes.
2.4.2 Shaded Pole Type Induction Relay
The construction of shaded pole induction relay is shown in the Fig. 2.10.
Frog
= Disc
Fig. 2.10 Shaded pole type induction relay
It consists of an aluminium disc which is free to rotate in an air gap of an
electromagnet. The part of pole face of each pole is shaded with the help of copper
band or ring. This is called shading ring. The total flux @ produced due to the
alternating current split into two fluxes displaced in time and space due to the
shading ring,
Due to the alternating flux, e.m.f. gets induced in the shading ring. This emf
drives the currents causing the flux to exist in shaded portion. This flux lags behind
the flux in the unshaded portion by angel a.Protection and Switchgear 2-14 Electromagnotic Relays
Let ¢, = Flux in shaded portion
= Flux in unshaded portion
EMF. induced in the disc due to ,
EMF. induced in the disc due to 4,
1, = Induced current due to E,
Induced current due to Ey
E, lags behind ¢, by 90° while E, lags behind 9, by 90° The current I, lags E, by
sinall angle § while I, lags E, by small angle B. This angle is generally neglected and
1, and |, are assumed to be in phase with E, and E, respectively, in practice. The
phasor diagram is shown in the Fig. 2.11
Fig. 2.11 Phasor diagram
As proved in the previous section, neglecting jb we get,
T « @ 6, sina
where T = Torque
Assuming fluxes ¢, and 6, to be proportional to the current [ in the relay coil we
can write,
T « Psing
T .._k = constant
As sin a is constant for the given design. Thus the torque is proportional to the
square of the current through the coil.Protection and Switchgear 2-15 Electromagnetic Relays
2.4.3 Watthour Meter Type Induction Relay
The construction of this type of relay is similar to the watthour meter which is
very popularly used everywhere. Thus relay has double winding structure. The
arrangement is. shown in the Fig, 2.12
E shaped
magnet
Seconary — oo
col
Fig. 2.42 Watthour meter type induction relay
It consists of two magnets, one E shaped magnet and other U shaped magnet. The
disc is free to rotate in between these two magnets. The upper E shaped magnet
carries both primary winding which is relay coil and the secondary winding. The
primary carries the relay current I, which produces the flux @). The emt. gets induced
in the secondary due to this flux. This drives current I; through secondary, Due to this
current I, flux $3 gets produced in the lower magnet. This flux lags behind the main
flux 4; by an angle a, Due to the interaction of these two fluxes, the torque is exerted
on the disc and disc rotates.
Assuming that the entire flux $, enters the disc from upper magnet and entire flux
¢2 enters the disc from lower magnet, we can write,
To « @@ sina
In this relay, the tapping can be provided on the primary. With the help of this
suitable number of primary turns can be selected and hence current setting can be
adjusted.
Most of the induction relays are of this type. An important feature of this relay is
that its operation can be controlled by opening or closing of the secondary winding. It
is opened, no current can flow through secondary hence flux ¢, cannot be produced
and hence no torque can be produced, Thus relay can be made inoperative opening
the secondary winding.Protection and Switchgear 2-16 Electromagnetic Relays
2.4.4 Induction Cup Type Relay
construction of this type of relay is very similar to an induction motor. The
ement is shown in the Fig. 2.13.
Cup type
rotor
Elociromagnet
Fig. 243
The stator consists of twa, four or more poles. These are energized by the relay
coils. The Fig, 2.13 shows 4 pole structure and the two pairs of coils. The coils 1 and 1
are connected while the coils 2 and 2 are connected to form two pairs of coils. The
rotor is hollow cyclindrical cup type in structure. Compared to induction motor the
diffe ce is that im this relay the rotor core is stationary and only rotor conductor
portion is free te rotate about its axis
The currents and respective fluxes produced by the two pairs of coils are displaced
from each other by angle a. Thus the resultant flux in the air gap is rotating. So
rotating, magnetic field is produced by two pairs of coils. Due to this, eddy currents
the cup type rotor. These currents produce the flux. The interaction of
produce the torque and the rotor rotates in the same direction as that
ng magnetic field. A control spring and the back stop carried on an arm
attached to the spindle of the cup, are responsible to prevent continuous rotation.
These relays are very fast in operation. The operating time of the order of 10
milliseconds is possible with this type. This is because the rotor is light having very
The induction cup structure can be used for two quantity or
low moment of inertia.Protection and Switchgear 2647 Electromagnetic Relays
Coe
a“ single quantity relays. A single quantity relay
rome ‘Means both the coils are fed by the same actuating
(rducton quantity with a fixed phase angle shift in between
top) them. To reduce the rotor inertia and to make the
operation more fast, double induction loop
structure is used, Such a structure is shown in the
Fig. 2.14 Double induction loop 52 14
structure
In all, the induction relays are widely used for
protective relays involving ac. quantities. High, low and adjustable speeds are
possible in these relays. Various shapes of time against operating quantity curves can
be obtained.
2.5 Nondirectional Induction Type Overcurrent Relay
This rela
is also called earth lea
kage induction type relay
The overcurrent relay operates when the current in the circuit exceeds a certain
preset value. The induction type nondirectional overcurrent relay has a construction
similar to a watthour meter, ight modification. The Fig. 2.15 shows the
constructional details of nondirectional induction type over current relay.
Primary
wending
‘Currant
vermin
from ¢.
Fig. 2.15 Nondirectional induction over current relayProtection and Switchgear 2-18 Electromagnetic Relays
It consists of two electromagnets. The upper is E shaped while the lower is U
shaped. The aluminium disc is free to rotate between the two magnets. The spindle of
the disc carries moving contacts and when the disc rotates the moving contacts come
in contact with fixed contacts which are the terminals of a trip circuit.
The upper magnet has two windings, primary and secondary. The primary is
connected to the secondary of C. T. an the line to be protected. This winding is
tapped at intervals. The tappings are connected to plug setting bridge.
With the help of this bridge, number of tums of primary winding can be adjusted.
Thus the desired current setting for the relay can be obtained. There are usually seven
sections of tappings to have the overcurrent range from 50% to 200% in steps of 25%
These values are percentages of the current rating of the relay. Thus a relay current
rating may be 10A i.e, it can be connected to C:T, with secondary current rating of
1A but with 50% setting the relay will start operating at SA. So adjustment of the
current setting is made by inserting a pin between spring loaded jaw of the bridge
socket, at the proper tap value required. When the pin is withdrawn for the purpose
of changing the setting while relay is in service then relay automatically adopts a
higher current setting thus secondary of CT. is not open circuited. So relay remains
operative for the fault occurring during the process of changing the setting.
The secondary winding on the central limb of upper magnet is connected in series
with winding on the lower magnet. This winding is energized by the induction from
primary, By this arrangement of secondary winding, the leakage fluxes of upper and
lower magnets are sufficiently displaced in space and time to produce a rotational
torque on the aluminium disc. The control torque is provided by the spiral spring
When current exceeds its preset value, disc rotates and moving contacts on spindle
make connection with trip circuit terminals. Angle through which the disc rotates is
between 0° to 360°, The travel of the moving contacts can be adjusted by adjusting
angle of rotation of disc. This gives the relay any desired time setting which is
indicated by a pointer on a time setting dial, The dial is calibrated from 0 to 1. This
does not give direct operating time but it gives multiplier which can be used along
with the time-plug setting multiplier curve to obtain actual operating time of the relay.
The time-plug setting multiplier curve is provided by the manufacturer
2.5.1 Time-Current Characteristics
Time required to rotate the disc depends on a torque. The torque varies as current
in the primary circuit. More the torque, lesser is the time required hence relay has
inverse time characteristics. The Fig. 2.16 (see on next page ) shows the time-current
characteristics for the overcurrent relay. Such characteristics are called Inverse Definite
Minimum Type (LD.M.T.) characteristics. This is because, the characteristics shows
inverse relation between time and current for small values of currents, But as current2-19 Electromagnetic Rel
10 1.0. MT characteristics
a 2 4 6 8 wm 2 8 6
Opersting current (P: 8. M)
Fig. 2.16 Time-current characteristics
increases, some definite time is required by the relay. So the characteristics becomes
straight line for higher values of currents. Such LD.M.T. characteristics can be obtained
by saturating the iron in the upper magnet so that there cannot be inerease in the flux
once: current achieves certain high value.
The P.S.M, can be obtained ax,
PSM, = _ Peal current in relay coil _
" Rated secondary C.T. current x Current setung
Fault current in relay coil = Line fault current x C.T. rati
2.5.2 Operation
The torque is produced due to induction principle, as explained in the section
24.1. This torque is opposed by restraining force produced by spiral springs. Under
normal conditions the restraining force is more than driving force hence dise remains
stationary. Under fault conditions when current becomes high. the disc rotates through
the preset angle and makes contact with the fixed contacts of trip circuit. The trip
circuit opens the circuit breaker, isolating the faulty part from rest of the healthy
systemProtection and Switehgear 2-20 Electromagnetic Relays
time muttiplier setting of 0.6. The primary of relay is connected to secondary
g ridio 40/5. Calculate the time of operation if the circuit carries a fault current
eos 0 6 20 PSM.
Fig. 217
Solution = Let us calculate PSM. first
Fault current in relay coil = actual fault current * C.T. ratio
* 5
= 3000 x 355
= 625A
Rated secondary of CT. = 5A
Current setting = 150% =
PSM. = “z= 8.333
From Fig. 2.17, approximate time for P-S.M. of 8.33 is 18 sec
Actual operation ti
= 18 x time setting multiplier
= 18*06
= 1.08 seconds
usp Example 2.2: The Fig. 2.18 shows the part of a typical power system. If for the
discrimination, the time grading margin between the relays is 0.6 sec, calculate the time
of operation of relay 1 and time setting multiplier for relay 2. Refer to characteristics
green in the Fig. 2.17. The time setting multiplier of relay T ts 0.3Protection and Switchgear 2-21 Electromagnetic Relays
He
5005 S008 Fou current
100
150% 126%
Fig. 2.18
Solution : For relay 1: Current setting = 125 % = 1.28
Fault current = 4000 A
CT. ratio = 500/5
5
Fault current in relay coil © 4000 x ==
= WA
- 40
SM. = =
PSM. = sr735 764
From the Fig. 2.17, the corresponding time for 64 P.S.M. is approximately 3 sec
Actual time of operation © 3x time setting multiplier = 3 = 0.3
= 0.9 sec
For relay 2: Current setting = 150% = 15
Actual time of operation = time of operation of relay 1 + time margin
0.9 + 0.6 = 15 sec
Fault current = 4000 « ae
. Fault current _
TI secondary rating = current setting
40
= = 533
Se1lS 53
=40A
PSM.
From the Fig. 2.17, the corresponding time for 5.33 PSM. is approximately 3.8 sec
Actual time of operation
Time setting multiplier = si jor PSM. obtained
1
3
uw
= 0395 = 04
a
This is the required time setting multiplier for the relay 2Protection and Switchgear 2-22 Electromagnetic Relays
2.6 Directional Power Relay
The directional relay means the relay operates for the specific direction of the
actuating quantity in the circuit. The directional power relay operates when power in
the circuit flows in the specific direction. The construction and principle of operation
relay is similar to the induction type watthour meter relay. The difference is
hour meter type relay the torque is produced due to interaction of the
produced by only the current derivéd from secondary of CT, while in
directional power relay the torque is produced due to interaction of the fluxes
produced from both voltage and current of the circuit. The relay has two windings,
one acts as voltage coil while other as current coi
magnet carries a voltage coil or potential coil which is energized from P.T. while the
which is energized from CT. in the line to be
protected. The construction is shown in the Fig. 2.19.
flux
|, similar to. a wattmeter. The upper
lower magnet carries a current co
Fig. 2.19 Directional power relay
The number of tappings are provided to the current coil with which desired
nt setting can be achieved. The restraining torque is provided by: the spiral
spring. The spindle of dise carries the moving contacts which make contact with
tripping circuit terminals when the disc rotates. The voltage coil provided on the
upper magnet produces the flux 4). This lags the voltage V by 90° The current I is
sensed by the cureent coil on lower magnet which produces the flux $3. This is in
phase with current I. The current I lags voltage V by an angle ¢. The angle between 4;
and 9; is a as shown in the phasor diagram in the Fig. 2.20Protection and Switchgear 2-23 Electromagnetic Relays
Fig. 2.20
‘The interaction of fluxes}, and $; produces the torque. Hence we can write,
T & 6 @ sin
But © Vo and al
while a= 9-9
T x VIsin (90-4)
T a Vicos$ x power in circuit
Under normat working conditions, the driving torque acts in the same direction as
that of restraining torque. This moves the moving contacts away from the fixed
tripping circuit contacts, Thus relay remains. inoperative as long as power flow is in
one particular direction.
But when there is a current reversal and hence the power reversal then the driving
torque acts in opposite direction to the restraining torque in such a manner that the
moving contacts close the tripping circuit contacts. This opens the circuit breaker to
isolate the faulty part
This relay is used for providing the reverse power protection to synchronous
machines. The relay can be single phase or three phase.
2.7 Directional Induction Type Overcurrent Relay
The directional power relay is not suitable to use as a protective relay under short
circuit conditions, This is because under short circuit conditions the voltage falls
drastically and such @ reduced voltage may net be sufficient to produce the driving
torque required for the relay operation. Hence in practice, directional induction type
overcurrent relay is used. This relay operates almost independent of system voltage
and power factor.
The directional induction type overcurrent relay uses two relay elements mounted
on a common case. These elements are,Protection and Switchgear 2-24
Electromagnetic Relays
1. Directional element which is directional power relay
2. Nondirectional element which is nondirectional overcurrent relay
The schematic arrangement of such a directional relay is shown in the Fig, 2.21.
vonage.
coil
‘Voltage from PT.
v
Fig. 2.21 Directional overcurrent relay
Directional
element
Nondirectional
elementProtection and Switchgear 2-25 Electromagnetic Relays
Directional element : The directional element is nothing b
relay which operates when power in the circuit flows in a ps
voltage coil of this clement is energized by a system voltage through a potential
transformer. The current coil on the lower magnet is energized by the system current
through a current transformer. The trip contacts of this relay (1 — 1) are connected in
ndary winding of nondirectional element
a directional power
icular direction. The
series with the se
Nondirectional element ; The current coil of the directional element is connected
in series with the primary winding of nondirectionat element. The plug setting bridge
is provided in this element to adjust current setting as per the requirement. The trip
contacts (1 - I') are in series with winding on lower magnet of nondirectional
element. So unless and until trip contacts (1 - 1’) are closed by the movement of the
disc of directional element, the nondirectional element cannot operate. Thus the
movement of the nondirectional element is controlled by the directional element.
2.7.1 Operation
Under normal conditions, power flows in the proper direction and hence
directional element of the relay is inoperative. Thus the secondary winding on lower
magnet of nondirectional element is apen and hence nondirectional element is also
inoperative.
When the fault takes place, the current or power in the circuit has a tendency to
flow in reverse direction, The current flows through current coil of directional element
which produces the flux. The current in the voltage coil produces another flux. The
two fluxes interact to produce the torque due to which the disc rotates. As disc
rotates, the trip contacts (1 - 1‘) get closed. Note that the design of directional element
is such that it is very sensitive and though voltage falls under short circuit, the current
coil is responsible to produce sufficient torque to have disc rotation. It is so sensitive
that it can operate even at 2% of power flow in reverse direction.
The current also flows through the primary winding on the upper magnet of
nondirectional element. Thus energizes the winding to produce the flux, This flux
induces the emf, in the secondary winding of the nondirectional element according to
induction principle. As the contacts (I - 1’) are closed, the secondary winding has a
closed path. Hence the induced emf. drives the current through it, producing the
another flux. The two fluxes interact to produce the driving torque which rotates the
disc. Thus the contacts of trip circuit get closed and it opens the circuit breaker to
isolate the faulty section.
So tional clement must operate first to have the operation of the
nondirectional element.
The following conditions must be satisfied to have the operation of the entire
relayProtection and Switchgear Electromagnatic Relays
1, The direction of current in the circuit must reverse to operate directional
element.
2 The current value in the reverse direction must be greater than the current
setting,
> The high value of current must persist for a ime period which is greater than
the time setting of the relay
2.7.2 Directional Characteristics
Let us study the phasor diagram to understand the directional characteristics of
the rel
Let v
1
© = Angle between V and I
Relay voltage through P.T.
Relay coil current through CT
Note : The system current is generally lagging the voltage but with suitable
jon the relay current is made to lead the voltage by angle 6.
Due to this, the correct operation of relay at all the types of faults under all
system condition is ensured.
So current I leads voltage V by angle @
¢y = Flux produced by voltage V
This flux dy lags voltage V by an angle 6.
4 = Flux produced by current I
‘The flux ¢, is in phase with the current 1.
The phasor diagram is shown in the Fig. 2.22. The voltage V is taken as reference.
Operating
‘ smuion 7 | for maxienom torave
Non
operating
fegion
ty Zero rave ine
Fig. 2.22 Phasor diagram and directional characteristicProtection and Switchgear 2-27 Electromagnetic Relays
The torque is proportional to the fluxes ¢y, ¢; and sine of the angle between the
two fluxes.
T = $y 6sin @y “op
= oy + sin (@ +4)
Now oy « Vand
= KVI sin @ +
where K constant
Maximum torque occurs when sin (@ + @) is I ie
O46 = OF
The cor
ion for the maximum torque is shown dotted in the Fig. 2.22
The torque is zero when sin (@ + 6) = 0 ie.
8+9 = 0 of 130°
This will be satisfied when the relay current I phasor lies along the $y phasor or
in antiphase with @y. The corresponding line is called zero torque line and is shown
in the Fig. 2.22. This line is at right angles to the maximum torque condition line
Thus the directional clement operates, provided that the current phasor lies within
+90° of the maximum torque line. If it is displaced more than 9 then the element
will restrain. Both operating as well as monoperating regions are shown in the
Fig. 222.
Maximum torque angle : The angle by which the current supplied to the relay
leads the voltage supplied to the relay so as te obtain the maximum torque is called
maximum torque angle (M.T.A.). It is denoted as t in the Fig, 2.22.
From the Fig, 2.22, we can write,
6 = 9
Substituting in the torque equation,
T = KVIsin @ + 90-1)
T = KV1 cos @-1)
This is the torque equation interms of maximum torque angle +. The typical values
of the maximum torque angle are 0°, 30%, 45° etc.Protection and Switchgear 2-28 Electromagnetic Relays
2.8 Thermal Relays
Thermal relays werk on the
principle of heating effect of an electric
current in the relay coil. Instead of the
nent of temperature, these
relays sense the temperature rise
produced by the current
In a simplest thermal relay, a
bimetallic strip is used. The strip is
mounted above a resistance coil
arrying current t produce necessary
heating effect. The spring is used to
make the connection between contac - 7 or
and the strip. The insulated lever arm Heating col
used to carry the contact which is curent
pivoted. To have variable settings, the Fig. 2.23
nsion in the spring can be adjusted.
The Fig, 223 shows the schematic diagram of thermal relay.
Under normal condition:
the heating due to current 1 is not enough to heat the
strips and contacts remain closed as strip remains straight
When there is overloading, then the current | increases beyond safe value
producing very high FR losses and corresponding large heat. Thus the strip gets
heated up and bends. Due to the bending of the strip, the spring opens the contacts
and current is interrupted
In some cases, the bimetallic strips themselves carry the current without using a
heater coil. These relays are commonly used i ge ac and dic
hrough current
protection of low va
motors. In case of large motors, the bimetallic strip is connected
transformer.
2.9 Universal Relay Torque Equation
Most of the protection relays consist of some arrangement of electromagnets with
armature or induction disc, which carry contacts, The relays also carry the closing or
opening of contacts control devices like trip coils of circuit breaker. The electromagnets
have current, voltage or both the types of windings. Currents through windings
produce magnetic fluxes and torque is developed by the interaction between the fluxes
of same windings or between the fluxes of both the windings. In general the torque
produced by current winding is proportional to square of the current the tonque
produced by voltage winding is proportional to square of the voltage, and the torqueProtection and Switchgear 2-29 Electromagnetic Relays
produced by both the windings is proportional to product of voltage and the current
Mathematically we can write,
Torque produced by current coil, = K, P
Torque produced by voltage coil = K,V*
Torque produced by both the coils = K,V1 cos (01)
where Kj, Kz and Ky = constant @ = angle between V and I
1 = maximum torque angle
Torque produced by control spring = Ky
The control springs are used as restraining elements
If all the elements are present in a relay then total torque produced by all the
causes can be expressed by a general equation as,
T = K\P + K,V? + K,VI cos (8-1) + Ky
This equation is called universal relay torque equation the term Ky can be a
restraining torque due to springs or gravity.
By assigning positive and negative signs to certain constants and lets other
constants to be zero and sometimes by adding similar other terms, the operating
characteristics equation of all the types of protective relays can be obtained from
universal equation,
For example, for overcurrent relay K; = Ky = 0 and the spring torque is negative
20 we get,
T=KP-K,
For the directional relay K, = K; = 0 and the spring torque is negative
So we get,
T = K, Vi cos (0-1) — K,
Review Questions
1. Explain the operation of basic trip circuit
Feplain the following schemes used in circuit breakers,
Relay with mae type contact
ip Relay with brew: type contact
3. Describe any one type of electromagnetic attracted armature relay
4. Describe with neat sketch the operation of solenoid and plunger type relayProtection and Switchgear 2-30 Electromagnetic Relays
Derive the torque oquating for electromngnetsc attraction relays sehen used for
0
apees
A) Ac, operation:
State the advarvages, disadvantages ond applications of electromagnetic rotays
Derive the torque oquation for the induction type relays
8. Describe the operatios: of fallowineg relays witht meat sketches,
1 Shaded pole type induction relay
li) Watthour meter type induction relay
Ji) Inductive:
up type relay
2 Explain with the Relp of a neat diggramt, the construction and werking of a nondieectional
Fnduction type avercurveut relay. Draw anal explain its time-current characteristics
What ie .D.M.T characteristics of a relay?
Explain the working principle of directional power relay,
Of setting LD.MGT. relay ? What iacitial data i required ? How 18 the
wit than simple LDMLT relay ?
What is the proce
directional relay differ
13. Explain with
relay,
ety of neat sketch, the construction and working of directional induction type
14, State the conditions to be satisfies by directional refey before its aeration
15. raw the directional characteristice and explain what és maximum torque angle
16. What is wniversat relay
An-LDM.T. overcurrent relay has 2 current seiting of 150% and has a time multiplier setting af
05 . The relay és connected in the circuit with the help of C.T. having ratio 500 : 5 A. Calewiste
the time of operation af the relay if circuit carries a fault current of $000 A. The relay
characteristics are givem in the Fig. 2.24
raiue equation ? What is Hs use ?
= Tine mutiptier = 1
os wo & 2
—+ PSM
Fig. 2.24 Relay characteristicsPratection and Switchgear 2-31 Electromagnetic Relays
18. For a particular transmission line, relays are used as shoum in the Fig. 2.25.
20011 200"
[ cs. }—# Ls]
|
Fig. 225
For discrimination, the time grading margin 1s 0.5 sec.
Determine the time of operation of the thro relays assuming that both the relays have characteristics
fs shoton in the Fig. 2.25. The relay T hes time setting winltiplier of 2. Find the time setting
‘muitiplier of relny 2 (Ans, + 0.56 sec, 1.06 nec, 0.3364)
Woite a mote on therm relays.
g00(@ - 32)Differential Protection
3.1 Introduction
In the overcurrent relays, a current is sensed but such relays are not very sensitive
as these relays cannot distinguish between heavy loads and minor fault conditions, tn
such cases, differential relays can be used
A differential relay is defined as the relay that operates when the phasor
difference of two or more similar electrical quantities exceeds a predetermined value
Thus a current differential relay operates on the result of comparison between the
phase angle and magnitudes of the currents entering and leaving the system to be
protected, Under normal conditions, the two currents are equal in phase and
magnitude hence relay is inoperative. But under fault conditions, this condition no
longer exists. The relay is connected in such a manner that the difference between
current entering and current leaving flows through the operating coil. If this difference
current exceeds a preset value then the relay operates and opens the circuit breaker.
Almost any type of relay when connected in a certain way can be made to operate
as a differential relay
3.2 Types of Differential Relays
The various types of differential relays are,
1. Current differential relay
2. Biased beam relay or percentage differential relay
3. Voltage balance differential relay
3.2.1 Current Differential Relay
Most of the differential relays are of current differential type. Consider an over
ted in the circuit so as to operate as the current differential relay
current relay conn
This is shown in the Fig. 3.1
Two current transformers are used having same ratio are connected on the either
side of the section to be protected. The secondaries of current transformers are
connected in series, so they carry induced currents in the same direction, Let current 1
(3-4)3-2 Differential Protection
Generator winding to extemal
_ fering. Exe
‘Differential retay
Fig. 3.1 Current differential relay
is owing through the primary of current transformers towards the external fault. As
the current transformers are identical, the secondaries of current transformers will
carry equal currents. Due to the connection of relay, no current will flow through the
‘operating coil for the relay. Hence relay will remain inoperative. So relay cannot
‘operate if there is an external fault.
Consider now that an internal fault occurs at point A, as shown in the Fig. 3.2
The current flows
through the fault from both
sides. The two secondary
currents through C.s are
not equal. The current
flowing through the relay
coil is now 1, + 1 This
high current causes the
relay to operate.
ft should be noted that
the fault current need nat always flow to the fault from both sides. A flow on one
side only or even some current flowing out of one side while a large current entering
the other side can cause differential relay to operate. Thus the amount of current
flowing through a relay coil depends upon the way the fault is being fed
Fig. 3.2 Action of differential rotay
This relay suffers from the following disadvantages,
1. The current transformers are connected through cables called pilot cables. The
impedance of such pilot cables generally causes slight difference between the
currents at the ends of the section to be protected. A sensitive relay can
operate to a very small difference in the two currents, though there is no fault
existing,
2. The relay is likely to operate inaccurately with heavy through current flows
This is because the assumed identical current transformers may not haveProtection and Switchgear 3-3 Ditfore
ial Protection
identical secondary currents due to the constructional errors and pilot cable
impedances.
3. Under severe through fault conditions, the current transformers may saturate
and cause unequal secondary currents. The difference between the currents
may approach the pick value to cause the inaccurate operation for the relay
4. Under heavy current flows, pilot cable capacitances may cause inaccurate
operation of the relay
All these disadvantages are overcome in biased beam relay.
3.2.2 Biased Beam Relay or Percentage Differential Relay
As the name suggests, this relay is designed to operate to the differential current
in terms of its fractional relation with the actual current flowing through the protected
cireuit.
The Fig. 2.3 shows the arrangement of a biased beam relay
Ateenator wining
ct to be protected cr
TAT
Restraining cod ———e
Ta tip circuit
Operating cos
Fig. 3.3 Biased beam relay
The simple circuit connection of this type of relay is shown in the Fig. 3.4.
Alternator winding
cr ta be protected CT
Rstrainieg coll
Fig. 3.4 Simple circuit of biased beam relayProtection and Switchgear 3-4 Differential Protection
ting coil © of the relay carries a differential current (1, ~ 1) while the
The ope
restraining coil R carries the current proportional to (*
as the operating coll is
connected at the midpoint of the restraining coil. This can be explained as,
Let N = Total number of turns of restraining coil
So current f, lows through ~ tums while current I; flows through
1, N
(+l)
=N
Effective ampere tums =
fl, +1.)
Thus it ean be assumed that the current {4512 \ flows through the entine N’ turns
Of the restraining coil.
Under nermal and through load conditions, the bias force produced due to the
restraining coil is greater than the operating force produced by operating coil hence
relay is inoperative. When internal fault
occurs, the operating force becomes more
than the bias force. Due to this, beam
u wl moves and the trip contacts are closed to
open then circuit breaker.
The operating characteristics of this
type of relay is shown in the Fig. 35
It can be soen that except at tow
a currents, the characteristics is a straight
8) OR kb); ——e line.
Thus the ratio of the differential
Fig, 3.5 Operating characteristics operating current to the average
restraining, current is a fixed percentage
Hence the relay name is percentage
differential relay.
The relays with constant slope
characteristics are called constant slope
percentage differential relays
In some relays, the slope of the
characteristics increases as the short
sire current —inereases. Such
characteristics is shown in the Fig 3.6.
Short rout current —=
Fig. 3.6 Increase in slope characteristicProtection and Switchgear 3-5 Differential Protection
Such relays are called increasing slope percentage differential relays.
The important fact about increasing slope type relays is that their cost is more but
require less accuracy in the performance of their current transformers. Constant slope
type relays require good accuracy in the performance of the current transformers.
3.2.3 Voltage Balance Differential Relay
This ix also called opposed
type, th
over current relay is connected
in series with the secondaries of
the current transformers. This is
voltage method. In thi
shown in the Fig. 37.
Under normal conditions, the
current at the two ends of the
nto be protected is same. «
Hence there is no. voltage drop
across the relay to cause the current to flow
Fig. 3.7 Voltage balance differential relay
Under fault conditions, the currents in the two secondaries of current transformers
are different, This causes a large voltage drop across the relay. Thus the voltage
alance of the circuit gets disturbed, Hence large current flows through the relay due
to which the relay operates to open the circuit breaker.
3.3. Busbar Protection
The busbar plays an important role in the supply system. The busbar faults are
rare but if occurs there can be interruption of supply, considerable damage and loss.
Hence busbar protection is must and it must be fast, stable and reliable, The busbar
protection needs to protect not only the busbar but the apparatus associated with it
such as circuit breakers, isolating switches, instrument transformers etc
3.3.1 Busbar Faults
The various busbar faults can be classified as,
1. Failure of insulation due to material deterioration.
Failure of circuit breaker
Earth fault due to failure of support insulator
Plashover due to sustained excessive over voltages.
Errors in the operation and,maintenance of switchgear.
Earthquake and mechanical damage
Accidents due to fo!
Flashover due to: heav
n bodies falling across the busbars
y polluted insulator
zeProtection and Switchgear 3-6 Differential Protection
3.4 Frame Leakage Protection of Busbar
All busbar protection schemes are mostly designed for earth faults. Each conductor
is surrounded by the earthed metal barrier. All the metal frameworks are bonded
together and insulated from earth. The switchgear framework is also insulated from
lead cable sheaths.
‘The arrangement of frame leakage protection to a single busbar substation with a
switchgear unit is shown in the Fig. 38.
incoming
transformer ¢9)
Fig. 3.8 Frame leakage protection of busbar
Metal supporting frame work known as fault bus is earthed through a CT. When
the fault is there, a contact between conductor and earth results. This drives current
through this CT. This energizes the frame leakage relay.
The CT energizing the check relay is mounted in neutral earth of the transformer.
‘The contacts of check relay and frame leakage relay are in series.
Thus before tripping circuit gets energized both the relays must operate. Once
both the relays operate due to earth fault, all the breakers will trip connecting the
equipment to the busbar. Due to check relay, accidental operation of ‘single relay to
trip the circuit gets avoidedProtection and Switchgear 3-7 Differential Protection
3.5 Circulating Current Protection of Busbar
This is nothing but the differential scheme of the protection of busbar. The
circulating current principle states that under normal working conditions or external
fault conditions, sum of the currents entering the bus equals sum of the currents
leaving the bus, Under any abnormal conditions in the protected zone j.c. short circuit
or phase to phase faults, the current condition gets disturbed and sensing this the
relay can be operated
The Fig. 3.9 shows the principle of circulating current protection of busbar.
Fig. 3.9 Circulating current protection of busbar
Ih
Under normal condition, "1 = 0.
1, are the currents in the circuits connected to the busbar.
ie +1, +1, +i +h +i, =0 (vector sum)
No current flows through the relay and hence remains inoperative
Under fault conditions,
i+, st +.+h=i
where i, = Fault current = unbalanced current:
The unbalanced current flows through the relay and the relay operates
Under normal conditions, currents in the secondaries of CT balance each other and
no current flows through the relay, Thus relay is inoperative. Under any fault
conditions, the fault current flows through relay coil to activate it
To obtain exact balance of currents, all current transformers must have same ratio.
But in practice there exists a difference in the magnetic conditions of iron cored
current transformers and false operation of the relay is possible, at the time of external3-8 Differential Protection
Protection and Switchge:
s. For large fault currents there is a possibility of saturation of the cores-of current
formers, To overcome such difficulties, a special type of C.T. having no iron core
ss used, It is called linear coupler,
The linear coupler has a property. that its
secondary voltage is proportional to the primary
current and the secondary windings of all the
linear couplers are connected in series to the
relay. This is shown in the Fig. 3.10,
Buspar
The sum of the voltage outputs of linear
couplers is equal to the vector sum of the
voltages in the circuits connected to the busbars.
Relay Hence under normal conditions overall voltage
Fig. 3.10 in the secondary circuit is zero and relay is
inoperative. Under fault conditions, there is
resultant voltage in the secondary and the relay operates.
A high impedance relay can differentiste property the internal and external faults
compared to normal low impedance relay. Hence in circulating current protection,
n impedance relays are used, A high resistance is connected in series with relay
ng coil to get high impedance relay, This resistance is called sta
3.6 High Impedance Differential Protection of Busbar
Another method to provide differential protection to busbar is based on sensing a
voltage drop across a high impedance, under fault conditions. The scheme is shown in
the Fig. 3.11.
yu
. Measuring
Trenetommer On unt
Lines impedance
Fig. 3.11 High impedance busbar protectionProtection and Switchgear 3-8 Differential Protection
The basic principle remains same as differential scheme. Under normal conditions
vector sum of the currents in the lines is zero. Hence Ij ic. current flowing through
high impedance Z,, is zero. And the relay is inoperative.
During fault conditions, unbalanced current exists. Such an out of balance current
ven to
1, flows through Zy causing a high voltage drop V, across it. It is
transformer. A measuring unit is connected to the secondary of sformer w
cordingly. Main advantage is that ax voltage
drop is sensed, saturation of core of one of the current transformers has no effect on
measures this drop and trips the relay
the protection schem:
3.7 Difficulties in Busbar Protection
The various difficulties in the busbar pro
ic
tion are,
ferent
2 Large number of circuits to be protected.
3. Saturation of cores of current transformers due to d.c. component in short
circuit current is possible which produces ratio error
4. Due to various bus sections, the scheme becomes complicated
With large load changes, relay settings need to be changed
Review Questions
1. What are diffevential relays ? How they are classified ?
2. Explain the working of folowing differential relays,
vetay
1) Percentage difirentiat relay
421) Voltage Balance Aifferentiat relay
in the
3 Exp need of Isher protection and difficulties in hes bor pret
4. Explain frame teak ction of busbar
S Explain current circulating protection of busta
differential protection of basta.
| i) Current differe
6. Expl sight omy
goo(3 - 10)Distance Protection
4.1 Distance Relays
In the relays discussed uptil now, the operation of the relays is dependent on the
magnitude of the current or voltage of the circuit to be protected. In distance relays,
the operation is dependent on the ratio of the voltage and current, which is expressed
interms of an impedance. Hence basically distance relays are called impedance relays
‘The impedance is nothing but an electrical measure of di
line. The relay operates when the ratio V/I ie. impedance is less than a predetermined
value. As the ratio V/I affects the performance of these relays, the relays are also
called ratio relays. Dependent on the ratio of V and I there are three types of
relays which are,
ance along a transmission
1. Impedance relay which is based on measurement of impedance Z.
2 Reactance relay which is based on measurement of reactance X
3. Admittance or Mho relay which is based on measurement of component of
admittance Y.
1m short, a distance relay is one whose performance is based on the measurement
of impedance, reactance or admittance of line between the location of relay and the
point where fault occurs
4.2 Impedance Relay
The impedance relay works corresponding to the ratio of voltage V and current I
of the circuit to be protected. There are two elements in this relay, the one produces
torque proportional to current while the other produces a torque proportional to
voltage. The torque produced by the current element is balanced against torque
produced by the voltage element. Thus the current element produces operating torque,
pickup torque which can be said to be positive torque. The voltage element produces
restraining torque, reset torque which can be said to be negative torque. So this relay
is voltage restrained overcurrent relay.
@-1Protection and Switehg 2 Distance Protection
The Fig, 4.1 shows the basic operating principle of an impedance relay.
Fig. 4.1 Basic operation of impedance reli
The current element is energized by current through C.T. while valtage element is
tage through P.T. The section AB of the line is protected zane.
ized by v
Under normal conditions, the ratio of voltage V and current I is denoted as Z,
which is impedance of line. The relay is inoperative under this condition
When the fault occurs at point F in the protected zone then the voltage drops
while current increases. Thus the ratio V/I ie. the impedance reduces drastically. This
is the impedance of line between the point at which relay is connected and the point F
ai which fault occurs. So when the impedance reduces than its predetermined value
Z;, if trips and makes the circuit breaker open.
4.2.1 Torque Equation
The positive torque produced by the current element is proportional to F while
the negative torque produced by the voltage element is proportional to V7
Let control spring effect produces a constant torque of - Ky
Hence the torque equation becomes,
T= kK P-KV-K, ay
wre K,, Ky are the constants, while V and I are rms. values.
At the balance point, when the relay is on the verge of operating, the net torque is
zero hence we can write,
0 = Kj P-K, V2~Ky
2 Wo = K, P- Ky = Q
Dividing both sides by Ky P,Protection and Switchgear 4.3 Distance Protection
&
Z= f o
VK:
Generally the spring effect is neglected as its effect is dominant at low currents
which generally do not occur in practice. So with Ky = 0,
Zz
= + constant “
4.2.2 Operating Characteristics
‘As seen from the equation (4), it can be stated that the impedance relay is on the
verge of operating at a given constant vaiue of the ratio V/I, which can be expressed
as an impedance.
For a particular fault position, the ratio V/I i.e. impedance is constant. It changes
if the fault position changes. If fault is nearer to relay, this ratio will be low and as
fault position moves away from the relay the ratio becomes higher and higher. So it
can be installed to operate for the section to be protected and once installed and
adjusted for a parti
at section
lar section, it is inoperative beyond ¢
The operating, characteristics of the relay is shown in the Fig, 4.2
peratng
paraing charactors
‘woo
| (ore que)
y—
Fig. 4.2 Operating characteristics
As the effect of spring is dominating for the lower values of currents, the
characteristics shows a noticiable bend at lower currents.Protection and Switchgear 4-4 Distance Protection
But for all practical purposes, the dotted line, which represents a constant value of
Z may be considered as an operating characteristics.
The impedance Z which is predetermined set value is given by.
1
slope of characteristics
y will pickup for any combination of V and I represented by any point
above the line in the positive torque region. In other words for any value of Z less
than the constant value represented by the line, the relay will operate.
By adjustments, the slope of the characteristics can be changed so that the relay
will respond to all the values of impedance less than any desired upper limit
4.2.3 Operating Characteristics on R-X Diagram
‘The operating characteristics of an impedance relay can be more easily represented
by a diagram called R-X diagram. The diagram is shown in a plane having X-axis as R
(resistance) while the Y-axis as X (reactance). This plane is called R-X plane. The
impedance Z can be expressed as,
Z= Rojx
12) = VRE?
B= Rex? a)
Mathematically Ȣ + y? =f represents an equation of circle where x and y are
vertical and horizontal co-ordinates while r is the radius. Similarly the equation (1)
represents circle where R and X are vertical and horizontal co-ordinates and
magnitude of impedance|Z| is the radius of the circle. The centre of this circle is at
point where R and X axes intersect each other ie. origin.
From equation (1) we can write,
sang = %
6 = tant 2
R
The numerical values of ratio V and 1 determine the length of the radius vector 2
while the phase angle ¢ between V and | determines the exact position of the vector
z
lf Lis in phase with V then the Z vector lies along R-axis. If I lags vector V then X
is negative while if | leads vector V then X is positive.Protection and Switchgear 4-5 Distance Protection
‘The operation of the relay is independent of phase angle $ and hence the
‘operating characteristic is a circle with radius equal to magnitude of Z which is
predetermined set value.
‘At any value of Z less than the radius of the circle, the relay operates, Hence the
entire portion inside the circle is positive torque region i.e. operating region of the
relay while the portion exterior to the circle is megative torque region ic.
nonoperative region, as shown in the Fig. 43.
Fig. 4.3 Characteristic on R-X
if Z, = Impedance between relay and fault point
Z = Set value for impedance = Radius of circle
Then for, Z < Z .. relay operates
Z > Z__... relay is inoperative
Such a relay is nondirectional and can operate for faults on either side of a point
where relay is installed.
4.2.4 Disadvantages of Plain Impedance Relay
The plain impedance relay suffers from following disadvantages,
1. It is nondirectional and can operate for faults on both sides of a point where
relay is connected. Hence it fails to discriminate between internal and external,
faults,Protection and Switchgear 4-6 Distance Protection
2 When fault occurs, an are exists. The arc resistance of line fault affects the
performance of this relay.
3. As a large area is covered by the circle on each side on R-X plane, the power
swings also can affect the performance of this relay.
‘The nondirectional performance can be made directional by adding o directional
element in the plain impedance relay,
4.2.5 Directional Impedance Relay
‘The directional impedance relay can be obtained by adding a directional element
in the basic impedance relay. The element can sense the direction of power or current
flow and relay can operate only if the direction of power flow is in one particular
direction with respect to the point where relay is installed.
The characteristics of a
directional element is a tilted
straight line passing through
origin, which can be shown in
R-X diagram as represented in
the Fig.44. The dotted line
indicates the line of maximum
torque. While the dotted portion
shown above the line indicates
the opering region of the
directional element.
Now such a pure directional
element is added to the
impedance relay, we get the
resultant characteristics which is
a combination of a straight line
and a circle of radius |Z|. Thus
the resultant characteristics
obtained by superimposing the straight line characteristics of directional element on
the circle of the impedance relay is shown in the Fig. 4.5. The relay trips for the points
which are within the circle and above the directional characteristics. The operating
region is just a semicirele. The shaded portion shown in the Fig. 45 is a positive
torque region i.e. the operating region of the felay.
Modified Characteristics : By supplying additional voltage to the voltage coils of
an impedance relay, the torque equation of the relay can be modified. The additional
voltage supplied is proportional to the line current and is called current bias. The
modified torque equation is,
Fig. 4.4 Directional characteristicsDistance Protection
Protection and Switchgear
Fig. 4.5 Directional impedance relay characteristics
T= KP-K,(V+K IP
where (V+ Ky 1) = voltage supplied to voltage coil
Due to this additional current bias, the circle representing i
characteristics on R-X diagram shifts. The radius of circle remains same as V/I but its
centre gets shifted from origin. This is shown in the Fig. 4.6. By controlling current
bias, shift of the circle can be adjusted as per the requirement. (See Fig. 4.6 on next
page)
4.2.6 Use of Impedance Relay for Transmission Line Protection
Let us see how an impedance relay can be used for the transmission line
. The scheme is called distance protection for the transmission line. The
voltage coil of the relay is fed from P.T. while its current coil is fed from C.T. as
shown in the Fig. 4.7.i
Fig. 4.6 Modified directional impedance relay characteristics
ay
Fig. 4.7 Use of impedance relayDistance Protection
Let Ip = Line current when fault occurs at point X
Ve = Supply voltage when fault occurs at point X
jig = Current supplied to current coil when fault occurs
Vp = Voltage supplied to voltage coil when fault occurs
'V = Normal supply woltage
1 = Normal line current
io ¥ = impedance of healthy section
2s Es impedance when fault occurs
°
‘The relay is connected at point A. The fault occurs at point X. The voltage coil of
relay receives voltage V; and current coil receives current js, when fault occurs. The
‘setting of the relay is selected, such that it protects the transmission line upto point B.
‘Thus for any fault between A-B similar to that shown at point X, the impedance under
fault condition will be less than the predetermined value of impedance Z, and the
relay will operate.
«xProtection and Switchgear 10
Hf the impedance relay used is nondirectional, it can protect the line from faults for
all fault positions within the section AC too. So nondirectional relay provides
protection on either side of the point where relay is located. But if the portion of line
AB only is to be protected, then the directional impedance relay can be used. As
directional unit permits tripping only in one direction, the section AB will be protected
but relay will not operate for any fault positions between section AC,
Whether the relay is directional or nondirectional, if its setting is such that for
impedance less than Z; defined upto point B, the relay should operate then for any
fault positions to the right of point B like point Y the relay will not operate
The characteristics of the directional distance scheme discussed above can be
shown on R-X diagram. It is shown in the Fig, 4.8 (See Fig. on previous page}. The
various sections of the line are represented by straight lines on the R-X diagram
For fault at X, Z, < Z, hence point X is in the operating region and relay will trip.
So for any fault position along line AB, relay will trip as the entire section AB is in
the protected zone. For fault at Y, it can be seen that the impedance Z, > Z,, hence
point lies outside the cirele hence in the negative torque region and relay remains
inoperative.
4.3 Reactance Relay
In this relay the operating torque is obtained by current while the restraining
torque due to a current-voltage directional relay. The overcurrent element develops the
positive torque and directional unit produces negative torque
‘Thus the reactance relay is an overcurrent relay with the directional restraint
The directional element is so designed that the maximum torque angle is 90"
4.3.1 Construction
+— Polarizing coll
Operating
coal
1 : v
Fig. 4.9 Schematic arrangement of reactance rolay
Restraining
collProtection and Switchgear 41 Distance Protection
The structure used for the reactance relay can be of induction cup type. It is a four
pole structure. It has operating coil, polarizing coil and a restraining coil. The
schematic arrangement of coils for the reactance relay is shown in the Fig. 4.9.
The current I flows from pole 1, through iron core stacking to lower pole 3. The
winding on pole 4 is fed from voltage V. The operating torque is produced by
interaction of fluxes due to the windings carrying current coils ie. intera
produced by poles 1, 2 and 3. While the restraining torque is developed due to
interaction of fluxes due to the poles 1, 3 and 4. Hence the ope
proportional to the square of the current (T°) while the resh
proportional to the product of V and | (VIj. The desired maximum torque angle is
obtained with the help of RC circuit, shown in the Fig. 49.
nt of fluxes.
ting torque is
ing torque is
4.3.2 Torque Equation
The driving torque is proportional to the square of the current while the
restraining, torque is proportional to the product of V and |
Hence the net torque neglecting the effect of spring is given by,
T = K, P-K, Vi cos @-t)
At the balance point net torque is zero,
0
K, I? - K, V 1 eos @-1)
K, P = K, Vi cos @=1)
* K, = Ky ¥ cos (0-2)
K, = K; Z cos @-+)
Adding, torque angle is adjusted as.90°
K; Z cos (8-909
: K, Z sin 8
, K
Zeina =
Consider an impedance triangle shown :
in the Fig. 4.10.
x
Zsin@ = X = reactance
ZcosO = R= resistance
x = BS constant R
Fig. 4.10Protection and Switchgear Distance Protection
Thus the relay operates on the reactance only. The constant X means a straight
parallel to X-axis on R-X diagram. For the operation of the relay, the reactance seen by
the relay should be smaller than the reactance for which the relay is designed.
4.3.3 Operating Characteristics
The operating characteristics
‘of such relay is a straight line
parallel to the x-axis ie R-axis
on RX diagram. All the
pedance vectors have their
tips lying on the straight line
representing constant reactance.
‘The resistance component of the
impedance has no effect on the
vperation of the relay. It
vesponds only to the reactance -
component of the impedance.
The characteristics is shown in
the Fig. 4.11
Fig. 4.11 Operating characteristics of reactance
relay
The relay will operate for all the impedances whose heads lie below the operating
whether below or above the R-
characteris
4.3.4 Disadvantages
This relay as can be seen from the characteristics is a nondirectional relay. This
will not be able discriminate when used on transmission line, whether the fault has
taken place in the section where relay is located or it has taken place in the adjoining
section. It is not possible to use a directional relay of the type used with basic
impedance relay because in that case the relay will operate even under normal load
conditions if the system is operating at or near unity pf. conditions, The reactance
relay with directional feature is called mho relay or admittance relay.
4.4 Mho Relay or Admittance Relay
In the impedance relay a separate unit is required to make it directional while the
same unit can not be used to make a reactance relay with directional feature. The mho-
relay is made inherently directional by adding a voltage winding called polarizing
winding. This relay works on the measurement of admittance Y 2 6. This relay is also
called angle impedance relay.Protection and Switchgear Distance Protection
4.4.1 Construction
This relay also uses an induction cup type structure. It also has an operating coil,
polarizing coil and restraining cqil. The schematic arrangement of all the coils is
shown in the Fig, 4.12
Polarising
co) I
Operating ‘Series tuning
coll
eT
2 4
Restraining coll
q raining ot
v
Fig. 4.12 Schematic arrangement of admittance relay
In this relay the operating torque is obtained by V and I element while the
restraining torque is obtained by a voltage element. Thus an admittance relay is a
voltage restrained directional relay.
The operating torque is produced by the interaction of the fluxes due to the
windings carried by the poles 1, 2 and 3, While the restraining torque is produced by
the interaction of the fluxes due to the windings carried by the poles 1, 3 and 4
Thus the restraining torque is proportional to the square of the voltage (V"} while
the operating torque is proportional to the product of voltage and current (VI). The
torque angle is adjusted using series tuning circuit.
4.4.2 Torque Equation
The operating torque is proportional to VI while restraining torque is proportional
to V2. Hence net torque is given by,
T = K, V [cos (8-1) - Ky V? - Ky
where K, = control spring effectProtection and Switchgear 4-14 Distance Protection
Generally control spring effect is neglected (Ky = 0).
And at balance net torque is also zero.
0 = K, Vics @-)-K V?
K, Vicas @-1) = K)V?
v2
Ky 005 @=3) = Ka ey
¥
T
.% —
Z = gheos @-2)
This is the equation of a circle having diameter K,/K, passing through origin. And
this constant K,/K, is the ohmic setting of this relay.
K
K; cos @-
4.4.3 Operating Characteristics
As seen from the torque equation, the characteristics of this relay is a circle
passing through origin with diameter as K,/K,
Let & = Z_ = ohmic setting of relay = diameter
The circle is shown in the Fig. 4.13.
Fig. 4.13 Operating characteristics of mho relayProtection and Switchgear -15 Distance Protection
The relay operates when the impedance seen by the relay falls within this circle.
Consider two lines AB and AC with mho relay located at the point A. The relay will
operate for the faults occurring in the section AB only and not for the faults occurring
in the section AC. This shows that this relay is inherently directional without any
additional directional unit required,
The angle t can be adjusted to be 45%, 60°, 75° and so on, This angle is maximum
torque angle. The setting of 45° is used for high voltage (33 or 11 kV) distribution
lines, the setting of 60° is used for 66 or 132 k¥ lines while the setting of 75° is used
for 275 and 400 kV lines.
sum Example 4.4: On a R-X diagram show a line having an impedance of 3 + j 40. On
the same diagram show the operating characteristics of,
1. Impedance relay
2 Reactance relay
3. Mho relay
Assume thal these relays are adjusted to just operate for a zero impedance short circuit
at the end of the line section.
If an arcing short circuit fault having ar arc impedance of 1 + 0 Q occurs anywhere on
the Hine, find for each type of distance relay, the maximum portion of the line that can
be protected.
Solution ; The line OA is the impedance vector with impedance 3 + j 42
OB = 3
BA = 4
The circle with © as a centre and OA as radius represents the characteristics of an
impedance relay.
‘The line parallel to the resistance axis at a distance of 4, passing through point A,
corresponding to reactance of the impedance given, represents the characteristics of a
reactance relay.
Draw the circle with OA as the diameter, passing through O and A represents
characteristics of mho relay.
The characteristics are shown in the Fig. 4.14. (See on next page)
The impedance of arcing fault is 1 + j 0, is represented by OD.
_ The line parallel to the OA is drawn from point D, cutting the mho circle at point
F and cutting the impedance circle at pont E.
Draw fine FN parallel to R-axis to cut OA at N and draw EM parallel to R-axis to
cut OA at M
Then the ratio ON/OA represents the line protected by mho relayProtection and Switchgear 4-16 Distance Protection
* Cheractenstics of
reactance relay
Seale; 1:1 unit
Characteristics of
mho relay
Fig. 4.14
ON .
S100 = % of line protected by mho relay
= dno
= 8%
While the ratio OM/OA represents the line protected by impedance relay.
a +100 = % of line protected by impedance relay
4.35
= 43.100
= 5%
Now reactance relay is unaffected by the presence of the arc resistance and hence
even with the arc present the % of line protected by the reactance relay is 100%.Protection and Switchgear 4
4.5 Classification of Distance Relays
We have seen that the distance relay basically measures ohmic values and operates
when the impedance is below the preset value. The distance relays are classified as,
1. Definite distance relays : These can be of impedance type, reactance type or
mho type. This operates instantaneously for the faults upto certain
predetermined distance from the relay.
7 Distance Protection
2. Distance time relays : These can be also of impedance type, reactance type or
mho type. In these relays the time of operation is proportional to the distance
of the fault from the point where relay is installed. The fault nearer to the
relay operates it faster than for the faults further away from the relay.
Let us discuss the construction and operation of these two types of distance relays.
4.5.1 Definite Distance Type Impedance Relay
The construction of this relay can be balanced beam type or induction disc type.
The balanced beam type construction of definite distance impedance relay is shown in
the Fig. 4.15.
. Restraining Operating
Pry, ool col | om c-r
Fig. 4.15 Definite distance type impedance relay
It consists of a balanced beam pivoted at the central point C. The beam carries the
armatures of the two electromagnets. The two electromagnets are energized by a
current from C.T. and voltage from P.T., which are located in the circuit to be
protected. The voltage coil acts as restraining coil while the current coil acts as
operating coil. The beam also carries the moving contacts which can bridge the two
fixed contacts of a trip circuit when the relay operates.
Operation : The torque produced by voltage coil is proportional to square of the
voltage (K, V?) while the torque produced by current coil is proportional to the square
of the current (K; P). Under normal operating conditions, the torque produced byProtectio
stance Protection
id Switchgear
voltage coil is more than the torque produced by the current coil. ‘Thus restraining
torque is more than the operating torque and hence the relay is inoperative. On the
occurrence of any fault, the voltage of system decreases and current increases. Thus
the ratio V/I which is impedance also decreases. It falls below its preset value. The
torque produced by current coil becomes greater than the torque produced by the
voltage coil. Hence beam experiences a pull on the current coil side. As the beam tilts,
the moving contacts of beam bridges the fixed contacts of the trip circuit. This
operates the trip circuit and opens the circuit breaker.
Torque Equation : The torque by voltage coil is proportional to V? while that by
current coil is P-
The relay will operate when torque produced by voltage coil is less than that
produced by current coil. $o we can write,
Kv? < K,/? relay operates
where K,, K; = constants
vt
P
v
T
2
So for impedance value less than JK, /K; , the relay operates.
The constants K, and Ky are dependent on the ampere tums of the two
electromagnets. By providing
tappings on the coils, K, and K can
be changed and hence any preset
value for the impedance can be
adjusted as per the requirement.
Characteristics. = The Fig. 4.16
shows the characteristics of the
definite distance type impedance
relay. The Y-axis represents time for
operation while the X-axis represents
distance which is measured interms a
of impedance between fault position Distance ——=
and the point where relay is Fig. 4.16 Characteristics of definite distance
installed, impedance relayProtection and Switchgear 4-19 Distance Protection
For the entire length AB of the line, the time of operation remains constant,
irrespective of distance. But if fault cccurs in the section of line which {s not protected,
the operating time becomes suddenly infinite as shown in the Fig. 4.16. Towards end
of the protected zone, the curve rises gradually.
Its advantages are,
1, Superior to the time graded over current relay
2. Number of feeders in series which can be protected is unlimited as the relay
time is constant.
‘The one limitation of these relays is the absence of back up protection.
4.5.2 Distance Time Impedance Relay
This relay adjusts automatically, its time or operation corresponding to the
distance of the fault from the relay.
Operating time « Z x distance
‘The Fig. 4.17 shows the schematic arrangement of distance time impedance relay.
Fig. 4.17 Distance time impedance relayProtection and Switchgear 4-20 Distance Protection
It consists of an induction type over current relay unit which is a current driven
element. The spindle which is carrying the dise of the element is connected to a
second spindle with the help of spiral spring coupling. This second spindle carries
moving contacts which is nothing but a bridging piece which can bridge the trip
contacts when felay operates. The trip contacts are normally open and spindle is held
in this position by an armature held against the pole face of an electromagnet. This
electromagnet is energized by the voltage of the circuit to be protected.
Operation : Under normal conditions, the force exerted by voltage restraining
magnet is more than that produced by an overcurrent induction element. Thus the trip
contacts remain open and the relay is inoperative.
When the fault occurs, the induction disc starts rotating. The speed. of the disc is
proportional to the operating current, neglecting the spring effect. Hence the time
which the disc requires to turn through the given angle varies inversely with current.
‘As the disc rotates, spiral spring is wound. This exerts a force on armature so as to
pull it away from the voltage restrained magnet. The disc continues to rotate till the
tension of the spring is sufficient to overcome the restraining force produced by
voltage restraining magnet on the armature. Immediately the moving contacts bridge
the fixed contacts of tripping circuit. This opens the circuit breaker to isolate the faulty
section.
The angle through which the dise must rotate to close the trip contacts depends on
the pull required by armature which is restrained by voltage restraining magnet. This
pull is thus proportional to the voltage of system. Greater this pull, greater will be
travel of the disc. So travel for the disc is proportional to the voltage V. But the time
which disc takes to rotate through certain required angle varies inversely with current
(1/1), Thus effectively,
Time of operation of relay « Vx Z o distance
In actual practice the pull on
armature is proportional to the V*
while the torque on disc is
proportional to the [? Hence the
time distance characteristics of this
relay is nonlinear im nature, as
shown in the Fig. 4.18. The exact
curve is shown dotted while the
assumed line is shown thick. The
mininwm operating time for the
relay is generally 0.2 seconds.
(impedance)
Fig, 4.18 Time-distance characteristics of
distance time impedance relayProtection and Switchgear 4-21 Distance Protection
4.5.3 Applications and Advantages of Distance Relays
The various advantages of the distance relays are.
1. Gives faster operation
2. Simpler to co-ordinate
3. Less effect of fault levels and fault current magnitudes:
4. Permits high line loading,
5. With the need at readjust ments, permanent settings can be dane.
Thus the distance relays are used for providing the primary ie, main protection
and backup protection for a.c. transmission and distribution lines against the following
faults,
1. Three phase faults
2. Phase to phase faults
3. Phase to earth faults
4.6 Frequency Relay
The frequency of the induced emf. is related to the speed of the synchronous
generators by the relation,
where f = frequency
N, = synchronous speed of generator
P = mumber of poles
If the load is reduced, the speed of the synchronous generator increases and
frequency increases. While if load inceeases, the speed decreases and the frequency
decreases. Hence frequency relays are required if frequency changes from its normal
value and are used in the generator protection and for load frequency control.
The frequency relays can be electromagnetic or static relays. These can be under
frequency or over frequency relays.
Constructionally it consists of two pairs of cails and a cup type rotor as shown in
the Fig. 4.19.Protection and Switchgear 4-2 Distance Protection
cup
rotor
Fig. 4.19
It uses a Ferraris measuring system. The frequency relays are connected to the
secondary of voltage transformer. The two pairs of coils are connected in parallel to
the supply voltage through the impedances.
Now impedances are functions of frequency. At normal frequency the impedances
are tuned balancing each other. Thus no torque is experienced by the cup type rotor at
normal rated frequency
If frequency increases then there is unbalance in the impedances and torque say
clockwise in nature is exerted on the rotor. This operates the relay if frequency
increases beyond the setting. This is over frequency relay.
If frequency decreases then again there is unbalance in the impedances. But now
torque exerted on the rotor is anticlockwise. This operates the relay if frequency
decreases beyond the setting. This is under frequency relay
By varying the position of sliding resistor the frequency setting can be adjusted.
The pickup sensitivity can be controlled by adjusting the restraining spring.
Review Questions
Explain fully bow on impeslance relay is used for distance protection obtain its operating
characteristic. Dace its operating characteristics om RX diagram
State the désadearitages of buske fimpedance rely
Explain the operation of directional impedence relay. Draw its characteristics on R-X diggram.
How these characteristics cam be modified, similar to that of mko relay ?
Draw and explain the ful scheme of protecting s transmission line using ax impedance relay.Protection and Switchgear 4-23 Distance Protection
following distance relays
Explain the construction, working, torque equation asd characteristice a
By Reactance relay
ii) Mho relay
Explain the construction sand working
1) Definite distance type impedence relay
i) Distance time impedance relay
State the adrantages ar applications of distance relays
A line section has an impedance of 28 + j 5.0 Skew this on R-X dliegrane, as impedance vector. If
the relay is adjusted to operate for w 2270 impestance short circuit at the end of the Hine section,
show on the same R-X diagrant the characteristics of,
1 Impedance relry
2, Reactance relay
3, Mio rely
Assume that centre of mma relay character en an impedance vector. If the arching fault
eccurs with an impedance of 1.5 + j0 © anyeohere along the line, find for each type of distance
relay the maximarns portion of the Hine hat can be protected. (Ams. : 82%, 100% and 85%)
Q00(4-24)Generator Protection |
5.1 Introduction
The generators used in the power system are the alternators which produce very
high ac. voltages. The protection of generators is very much complex due to the
following reasons,
nd
1. The generators are very large machines producing very high voltages
connected to busbars.
Various other equipments are always associated with the generators. Such
equipments are prime movers, excitation systems, vollage regulators, cooling
systems etc. Thus protection of generators must consider the presence of these
other equipments also,
3. The generators are v
costly, expensive and very important factor in a power
system, The protection scheme must be such that it should not shut off the
generators as far as possible, The shut off generators result in a power
shortage.
All these factors make the design of protection scheme for the generator, very
much complex
Before studying the various protection schemes for the generators, let us discuss
various faults which can occur associated with the generators,
5.2 Generator Faults
The various fatilis which can occur associated with a generator can be classified as,
1. Stator faults : The faults associated with the stator of the generator.
2 Rotor faults : The faults associated with the rotor of the generator.
3. Abnormal running conditions : This includes number of abnormal conditions
which may occur in practice, from which the generator must be protected
Let us discuss these faults in detail
6-1)Protection and Switchgear 5-2 Gonorator Protection
5.2.1 Stator Faults:
The stator faults means faults associated with the three phase armature windings
of the generator. These faults are mainly due to the insulation failure of the armature
windings. The main types of stator faults are,
1
«¢ to carth faults
hase to phase faults
3. Inter-turn faults involving turns of same phase winding.
The most important and common fault is phase to earth fault. The other two are
not very common while inter-turn fault is very difficult to detect
5.2.4.4 Phase to Earth Faults
These faults mainly occur in the armature slots. The faults are dangerous and can
cause severe damage te the expensive machine. The fault currents less than 20 A cause
egligible burning of core if machine is tripped quickly, But if the fault currents are
high, severe burning of stator core can take place. This may lead to the requirement of
replacing the laminations which is very costly and time consuming. So to avoid the
damage due to phase to earth faults, a separate, sensitive earth fault protection is
necessary for the generators alongwith the earthing resistance.
5.2.1.2 Phase to Phase Favits
The phase to phase faults means short circuit between two phase windings. Such
faults are uncommon because the insulation used between the coils of different phases
in a slot is large. But once phase to earth fault occurs, due to the over heating phase
to phase fault also may occur. This fault is likely to occur at the end connections of
the armature windings which are overheating parts outside the slots. Such a fault
causes severe arcing with very high temperatures, This may lead to melting of copper
and fire if the insulation is not fire resistant,
5.2.1.3 Stator Inter-Turn Faults
The coils used in the altemators are generally multitum coils. So short circuit
between the tims of one coil may eccur which is called an inter-turn fault. This fault
occurs due to current surges with high value of (L di/dt) voltage across the tums. But
if the coils used are single turn then this fault can not occur. Hence for the large
machines of the erder of 50 MVA and more, it is a normal practice to use single turn
coils. But in some countries, multiturn coils are very commonly used where protection
against inter-turn faults is must.Protection and Switchgear 5-3 Generator Protection
5.2.2 Rotor Faults
The rotor of an alternator is generally a field winding as most of the alternators
are of rotating field type. The field winding is made up of number of turns. So the
conductor to earth faults and short circuit between the tums of the field winding, are
the commonly occurring faults with respect toa rotor. These
faults
e caused
the severe mechanical and thermal stresses, acting on the field winding insulation.
The field winding is generally not grounded and hence single line ta ground fault
does not give any fautt current. A second fault to earth will short circuit the part of
the field winding and may there by produce an unsymmetrical field system. Such an
unsymmetrical system gives rise to the unbalanced forces on the rotor and results in
excess pressure on the bearings and the shaft distortion, if such a fault is not cleared
very early. So it is very much necessary to know the existence of the first occurrence
cof the earth fault s0 that corrective measures can be taken before second fault occurs,
The unbalanced loading on the generator is responsible to produce the negative
sequence currents, These currents produce a rotating magnetic field which rotates in
opposite direction to that of rotor magnetic field. Due to this field, there is induced
em. in the rotor winding. This causes overheating of the rotor.
Rotor earth fault protection and rotor temperature indicators
are provided to large rating generators.
re the essential and
§.2.3 Abnormal Running Conditions
In practice there are number of situations in which generator is subjected to some
abnormal running conditions. The protection must be provided against the abnormal
conditions, These abnormal conditions include
1. Overloading
2. Overspeeding
Unbalanced loading
3
4. Overvoltage
5. Failure of prime mover
6
Loss of excitation (Field failure)
Cooling syste failure
5.2.3.1 Overloading
Due to the continuous overloading, the overheating of the stator results. This may
increase the winding temperature. If this temperature rise exceeds certain limit, the
insulation of the winding may get damaged. The degree of overloading decides the
effects anct temperature rise. The overcurrent protection is generally set to very highProtection and Switchgear 5
‘Generator Protection
Je hence continuous overloads of less value than the setting cannot be sensed by
reurrent protection.
§.2.3.2 Overspeeding
In case of hydraulic generators a sudden loss of load results in overspeeding of
the generator. This is because the water flow to the turbine cannot be stopped of
reduced instantly. Generally a turbogovernor is provided to prevent the ovespeeding,
But if there is any fault in the turbine governor then the dangerous overspeeding may
take place, Hence it is necessary to supervise the working of turbine governor and
take some corrective measures if there is some fault in the governor.
5.2.3.3 Unbalanced Loading
The unbalanced loading of the generator results in the circulation of negative
sequence currents. These currents produce the rotating magnetic field. This rotating
magnetic field rotates at the synchronous speed with respect to rotor. The direction of
rotation of this magnetic field is opposite to that of rotor. Hence effectively the relative
speed between the two is double the synchronous speed.
Thus the em. gets induced, having double the normal frequency, in the rotor
winding. The circulating currents due to the induced ¢.m.f. are responsible to overheat
the rotor winding as well as rotor stampings. Continuous unbalanced load more than
10% of the rated load causes tremendous heating which is dominant incase of
cylindrical rotor of truboaltemators
The reasons for the unbalanced load conditions are,
1. Occurrence of unsymmetrical faults near the generating station.
2. The failure of
phases,
cuit breaker near the generating station in clearing all the three
Negative sequence protection is important to prevent dangerous situations due to
negative sequence currents which are because of unbalanced load conditions.
5.2.3.4 Overvoltage
The overvoltages are basically due to the overspeeding of generators, Another
son for the overvoltages is the faulty operation of voltage regulators. Not only’ the
ternal overvoltages are dangerous but atmospheric surge voltages can also reach to
the generators, Such atmospheric surge voltages are generated by direct lighting
strokes to the aerial lines of high voltage system. Inductively and capacitively, these
surges can get transferred to the generator. To protect the generators from surge
voltages, the surge arresters and surge capacitors are often used.
At the time of restriking across the contacts of circuit breakers, the transient over
voltages get generated. Such surges are called switching surges and can be limited byProtection and Switchgear 5-5 Generator Protection
the uses of modern circuit breakers. R-C surge suppressors also help in reducing
switching surges. Another situation, when the transient overvoltages are generated, is
when the ares are grounded. During arcing grounds, the transient voltages having
amplitudes five times more than the normal line to neutral peak amplitude are
generated. Such transient voltages are dangerous and can be reduced by using
resistance earthing.
5.2.3.5 Failure of Prime Mover
The failure of prime mover results in motoring operation of synchronous
generator. The generator draws active power from the network and conti
at synchronous speed as a synchronous motor. This may lead to dangerous mechanical
e ng
of the steam turbine blades may result. To prevent this the reverse power protection
wes to run
nditions if allowed to persist for more than twenty seconds. The serious overhea
achieved by directional power relays is used.
5.2.3.6 Loss of Excitation
The loss of excitation or reduced excitation is possible due to the field failure ie
opening of field winding or due to short ci
exciter system,
ft in field or due to some fault in
Such loss of excitation results in loss of synchronism within a second and this
causes the increase in speed of the generator. Since power input to the machi
remains same, the generator starts working as an induction generator, drawing the
reactive power from the bus. The machine starts drawing an exciting current from the
system, which is equal to the full load rated value. This leads to the overheating of
the stator winding and the rotor body due to induced currents. The loss of excitation
may also lead to the pole slipping condition which results in the voltage reduction for
the output above half the rated load,
Loss of excitatien should not persist for long and corrective measures like
disconnection of altemator should be taken immediately. For this a tripping scheme
can be used which can trip the generator circuit breaker immediately when there is a
field failure.
5.2.3.7 Cooling System Failure
The {allure of cooling system also causes severe overheating to rise the
temperature above safe limit. This may lead to insulation failure, causing some other
faults to occur. The thermocouples or resistance thermometers are used in large
machines to sense the temperature. The corrective measures are taken whenever the
temperature exceeds the limit
Apart from the above dominant abnormal conditions, some conditions may exist
wiich are rare in practice, Such conditions are, wrong synchronization, localProtection and Switchgear 5-6 Generator Protection
overheating, leakage in hydrogen circuit, moisture in the generator winding, oxygen in
water circuit, vibrations, bearing currents, excessive bearing temperature etc.
5.3 Basic Differential Protection Scheme for Generators
A basic differential protection scheme used for the generators is shown in the
Fig. 5.1. It is known that the differential relay operates when the phasor difference of
two or more similar electrical quantities exceeds a predetermined value
Generator
ct. ‘wineang cr
External
faut
~~ pitferentis!
Fig. 5.1
Suppose the current | flows through the primary of CTs to the external fault. If
the twa CTs have same ratio, then no current will flow through the relay and it
remains inoperative.
relay
But now if an internal fault occurs at point X as shown in the Fig. 5.2, the current
flows through the fault from both the sides. The primary currents are [, and I; while
the secondary currents are i, and iy, So the current flowing through the relay will be
i; + ip Even some current flowing out of one side while a large current entering the
other side will cause the differential current. Such a current is responsible to operate
the relay
Different
relayProtection and Switchgear $-7 Generator Protection
‘Thus the relay current is proportional to the phasor difference between the
currents entering and leaving the protected circuit and if the differential current
exceeds the pickup value, the relay operates
This basic differential scheme has following disadvantages
1, This circuit operates inaccurately with heavy external faults.
2 The CTs may saturate and cause unequal secondary currents and the
difference of secondary currents may approach the pickup value to operate the
relay unnecessarily.
These disadvantages are overcome in the percentage differential relay.
§.4 Basic Percentage Differential Protection Scheme for Generators
This protection scheme is also called biased differential protection scheme. The
Fig. 5.3 shows the connections of the percentage differential relay, in such a protection
scheme.
Generator
winding
——— Operating
5 ' call
Restraining cot
Fig. 5.3 Percentage differential protection scheme
The fault occurs at point X and the primary currents in the circuit are 1, and I;
The CT, secondary currents are i, and i;. The current flowing through the operating
coil of the relay is i, ~ i While the current flowing through the restraining coil of the
relay is;
\
the restraining coil.
+2). This is because the operating coil is connected to the midpoint of
Thus if the number of tums of the restraining coil is N then i, flows through
N,N
im
vol
and i; flows through remaining N, The total ampere tums are eN
2Protection and Switchgear 5-8 ‘Generator Protection
4 | This is as good as the flow of current 2} through the entire restraining
coil
The operating characteristics
of such a biased differential
relay is shown in the Fig. 5.4
The characteristics shows that t
except at low currents, ratio of
differential operating current to
average restraining current is a
Operating currant
Operating region
ine
Nonoperating region
= ve torque
fixed percentage. Hence the
relay is called the percentage
differential relay
This basic percentage Resting
differential protection scheme current
forms the basis of _ the
practically very commonly used
percentage differential protection scheme for alternator stator windings. This popular
as Biased differential protection or Mers-Price protection
scheme is know
Let us discuss the details of Merz-Price protectis
n scheme for the three phase
ernator stator windings
5.5 Merz-Price Protection of Alternator Stator Windings
This is most commonly used protection scheme for the alternator stator windings.
The scheme is also called biased differential protection and percentage differential
protection
In this method, the currents at the two ends of the protected section are sensed
using current transformers. The wires connecting relay coils to the current transformer
secondaries are called pilot wires
Under normal conditions, when there is no fault in the windings, the currents in
the pilot wires fed from C.T. secondaries are equal. The differential current i) - iy
through the operating coils of the relay is zero, Hence the relay is inoperative and
system is said to be balanced.
When fault occurs inside the protected section of the stator windings, the
differential current i, - {, flows through the operating coils of the relay. Due to this
current, the relay operates, This trips the generator circuit breaker to isolate the faulty
section. The field is also disconnected and is discharged through a suitable impedance.
The Fij
star connected 4
5.5 shows a schematic arrangement of Merz-Price protection scheme for a
'
nator.Protection and Switchgear Generator Protection
‘iar sonnectes
sSlamalr stale cH.
‘weg a rota
Arena - eartng
on i
coreg
ol ¥
8
aot
wn 0.6.» Oporaing ont
RC. Restraining cot
CB Creat breaker
Peteeniags ——
(terete ralay
Fig. 5.5 Merz-Price protection for star connected alternator
The differential relay gives protection against short circuit fault in the stator
winding of a generator. The C.T.s are connected in star and are provided on both, the
eutgoing side and machine winding connections to earth side. The restraining coils are
energized from the secondary connection of C.T.s in each phase, through pilot wires
The operating, coils are energized by the tappings from restraining coils and the CT
neutral earthing connec
¢ delta connected alternator stator winding,
as shown in the Fig. 5.6.
Delta carmela abarsatae ex.
state vending a cata
= eaching
mewn |
OS —— Operating cot
RE —e Rosimining oot
CB = Creu oroaker
Percentage
‘amarentalrsiay
Fig. 5.6 Merz-Price protection for delta connected alternatorProtection and Switchgear
Generator Protection
The C.T.s on the delta connected machine winding side are conne
while the C.T.s at outgoing ends are connected in star. The restraining coils are placed
in each phase, energized by the secondary connections of C.T.s while the operating
coils are energized from the restraining coil tappings and the C.T. neutral earthing.
If there is a fault due to a short circuit in the protected zone of the windings, it
produces a difference between the currents in the primary windings of C.T.s on both
sides of the generator winding of the same phase, This results in a difference between
ndary currents af the two current transformers. Thus, under fault conditions,
a differential current flows through the operating coils which is responsible to trip the
relay and open the circuit breaker. The differential relay operation depends on the
relation between the current in the operating coil and that in the restraining coil.
the se
addition to the tripping of circuit breaker, the percentage differential relay trip
hand reset multicontact auxiliary relay. This auxiliary relay simultaneously initiates the
following operations,
L. Tripping of the main circuit breaker of generator
2 Tripping of the field circuit breaker
3. Tripping of the neutral circuit breaker if it is present
4. Shut down of the prime mover
Turn on of CO, gas if provided for safety of generator under faulty conditions,
6. Operation of alarm and for annunciator to indicate the occurrence of the fault
and the operation of the relay the field must be opened immediately otherwise
it starts feeding the fault.
When differential relaying is used for the protection, C.T's at both the ends of
generator must be of equal ratio and equal accuracy otherwise if the error is excessive,
wrong operation of the relay may result. The causes of unequal currents on both the
sides of C-T’s without any fault are ratio errors, unequal lengths of the leads, unequal
secondary burdens ete
This scheme provides very fast protection to the stator winding against phase to
phase faults and phase to ground faults. If the neutral is not grounded or grounded
through resistance then additional sensitive earth fault relay should be provided.
The advantages of this scheme are,
1. Very high speed operation with operating time of about 15 msec.
2. It allows low fault setting which ensures maximum protection of machine
windings.
3. It ensures complete stability under the most severe through and external faults.Protection and Switchgear 5-14 Generator Protection
4. It does not require current transformers with air gaps or special balancing
features.
5.6 Restricted Earth Fault Protection of Generator
Generally Merz-Price protection based on circulating current principle provides the
tion against intemal earth faults. But for large genes
tors, as tl
se are cos
nal protection scheme called restricted earth fault protection is provided
When the neutral is solidly grounded then the generator gets completely protected
against earth faults. But when neutral is grounded through earth resistance, then the
stator windings get partly protected against earth faults. The percentage of winding
protected depends on the value of eart
ing resistance and the relay setting,
In this scheme, the value of earth resistance, relay setting, current rating of earth
resistance must be carefully selected, ‘The earth faults are rare near the neutral point as
the voltage of neutral point with respect to earth is very less. But when earth fault
occurs near the neutral point then the insufficient voltage across the fault drives very
low fault current than the pick up current of relay coil. Hence the relay coil remains
inoperative. Thus 15 to 20% winding from the neutral side remains unprotected in this
scheme. Hence it is called restricted earth fault protec
protect 85% of the winding
jon. It is usual practice to
The restricted earth fault protection scheme is shown in the Fig,
Neutral
point
Restricted earth fault relay
Fig. 5.7 Restricted earth fault protection
Consider that earth fault occurs on phase B due to breakdown of its insulation to
earth, as shown in the Fig. 5.7. The fault current |, will flow through the core, frameProtection and Switchgear 5-12 Generator Protection
of machine to earth and complete the path through the earthing resistance, The C:T
secondary current |, flows through the operating coil and the restricted earth fault
relay coil of the differential protection. The setting of restricted earth fault relay and
setting of overcurrent relay are independent of each other. Under this secondary
current I, the relay operates to trip the circuit breaker. The voltage V\. is sufficient to
drive the enough fault current I, when the fault point x is away from the neutral
point
If the fault point x is nearer to the neutral point then the voltage Vp, is small and
not sufficient to drive enough fault current 1. And for this 1, relay cannot operate.
Thus part of the winding from the neutral point remains unprotected. To overcome
this, if relay setting is chosen very low to make it sensitive to low fault currents, then
wrong operation of rel
y may result, The relay can operate under the conditions of
he.
y through faults, inaccurate CTs, saturation of C.T.s ete. Hence practically 15% of
from
neutral point is kept unprotected, protecting the remaining 85% of
the winding against phase fo earth faults
5.6.1 Effect of Earth Resistance on % of Winding Unprotected
Let us see the effect of earth resistance on the % of the winding which remains
unprotected
Consider the earth
resistance R used to limit earth
fault current as shown in the
Fig. 58
The value of the resistance
K limits the earth fault current
If the resistance R is very
small i.e, the neutral is almost
solidly grounded, then the fault
current is very high. But high
Earth fault currents are not desirable
resistance hence small R is not preferred
Fig. 8.8 for the large machines
For low resistance R, the value of R is selected such that full load current passes
through the neutral, for a full line to neutral voltage V.
In medium resistance R, the earth fault current is limited to about 200A for full
line to neutral voltage V, for a 60 MW machine.
In high resistance R, the earth fault current is limited to about 10 A. This &
for distribution transformers and generator-transformer units.
usedProtection and Switchgear $-13 Gonerator Protection
Now higher the value of earth resistance R, less is the earth fault current and less
percentage of winding gets protected. Large percentage of winding remains
unprotected.
Let V = Full line to neutral voltage
1 = Full lond current of largest capacity generator
R = Earth resistance
Then the value of the resistance R is.
Vv
Req
And the percentage of windi protected
given by,
| % of winding unprotected = ®!s 100
ue
where 1, = Minimum operating current in the primary of CT
If relay setting used is 15% then 1, is 15
machine and so on.
€
protect
of the full load current of the largest
ge of windings of small capacity ma
nes running parallel get
iter percenta
4
‘amp Example 5.1: A generator is protected by restricted earth finult protection. ‘The
are 13.2 kV, 10 MVA. The percentnge of winding protecied against
phase to ground fiult is 85%, The relay setting is such thot it trips for 20% ont of
balance. Calculate the resistance to be added in the neutral to ground connect
Solution : ‘The given values,
Vo = 12kV Ra
ng = 10 MVA
From rating, calculate the full load current,
Rating in VA 10108
hs = a
V3 Vy V3*13.2«108
= 437.386 A
Relay setting is 20% out of balan
¢ i. 20% of the rated current activates the relay
+ 20 ay
L 4387 .386x 87.477 A
Minimum operating currentrotection and Switchgea
5-14 Generator Protection
V = Line to neutral voltage
°% of winding u
R= 13.0680
mp Example 5.2: A star connected 3 phase, 12 MVA, T1 KV alternator has a phase
reactance of 10%. It is protected by Mera-Price circulating current scheme which is set
to operate for fault current not less than 200 A. Calculate the value of earthing
resistance to be provided im order to ensure that only 15% of the alternator winding
remains unprotected
Solution : The given values are,
V, nkV Rating = 12 MVA
Rating = V3 I,
12«10® = V3«11%109 x1,
12x10
=
¥3x 11x 10%
= 629.8366 A = I = rated current
_ Hx
= 29 V
Gi 6350.85:
‘% Reactance = —>x100
where
reactance per phase
and 1 = rated current
629.8366 X
6350, 8529
6
®
100
xX = 100830
Reactance of unprotected windingProtaction and Switchgear 5-45 Generator Protection
(@e of unprotected winding) « (X)
15
79572-0083
= 015122
v = voltage induced in unprotected winding
15 5
= =x V = 0.15% 6350,8529
709% V = 0-15%6350.852:
= 992.6279 V
i = Fault current
= 200A
Z = Impedance offered to the fault
v _ 982.6270
i 200
4.76310 (l}
Z = f+] (reactance of unprotected winding)
Z = rej O15I2R
12Z| = Je? (0.15127 » Q)
Equating (1) and 2),
47631 = fr? + (0.1512)?
22.6875 = r* + 0.02286
P= 266d
r= 476079
This is the earthing resistance required.
5.7 Unrestricted Earth Fault Protection
The unrestricted earth fault protection uses a residually connected earth fault relay.
It consists of three C-T.s, one in each phase. The secondary windings of these CT's are
connected in parallel, The earth fault relay is connected across the secondaries which
carries a residual current. The scheme is shown in the Fig. 5.9-
When there is no fault, under normal conditions, vector sum of the three line
currents is zero, Hence the vector sum of the three secondary currents is also zero.Protection and Switchgear
Earthing
resistance:
To tip creult
Fig. 5.9 Unrestricted earth fauit protection
. and I, are €.T, secondary currents then under normal conditions we
i,tiget, = 0
The sum of the three currents is residual current Ig, which is zero under normal
conditions.
The earth fault relay is connected in such a way that the residual current flows
through the relay operating coil. Under normal condition, residual current is zero se
relay does not carry any current and is inoperative. However in presence of earth fault
condition, the balance gets disturbed and the residual current Ips is no more zero. If
this current is more than the pickup value of the earth fault relay, the relay operates
and opens the circuit breaker through tripping of the trip circuit
In the scheme shown in the Fig. 5.9, the earth fault at any location near or away
from the location of C-T's can cause the residual current. Hence the protected zone is
not definite. Such a scheme is hence called unrestricted earth fault protection.
5.8 Balanced Earth Fault Protection
In practice for small rating alternators, the neutral ends of the three phases are
connected to a single point. Hence it is not possible to introduce C.T. in each phase on
neutral side as required in Merz-Price protection. In such cases, the balanced earth
fault protection can be used.Protection and Switchgear 5-17 Generator Protection
The balanced earth fault protection is shown in the Fig. 5.10.
Generator
Jnvoes, er
casi Popp
Fig. 5.10 Balanced earth fault protection
At the outgoing side, the three C-T-s are connected in parallel as are connected in
unrestricted earth fault protection. A single CT. is connected on the neutral side in the
pilot wire connecting neutral of alternator fo earth. The neutral earthing is achieved
through the earthing resistance. A relay is connected across the C-T. secondaries
Under norma! conditions, the alternator line currents add to zero. Hence the vector
sum of the currents through the secondaries of C.T. ig also zero. Thus no current flows
igh the relay and as ne
tral carries zero current hence no current is supplied to
lay is inoperative
If the fault appears at F, at a position outside the protected zone then the sum of
the alternator line currents is exactly equal to the current in the neutral. Thus zero
current flows through the relay is inoperative
But if the fault occurs at F, which is the protected zone t
alternator line currents is different than the current through neutral side current
transformer, Hence a residual current flows through the relay. If this is greater than
the pickup value of the relay, the relay operates. This trips the tripping circuit,
opening the circuit breaker
vector sum of
By this scheme, the protection against earth faults is restricted to the region
between the neutral and the position where line current transformers installed.Protection and Switchgear 5-18 Generator Protection
5.9 100% Earth Fault Protection
AS seen uptill now, no protection scheme is in a position to give complete
protection to the stator of generator against earth faults. The maximum protection
achieved is upto 85 to 90% from the schemes discussed uptitl now
But in modern days it is possible to provide 100% earth fault protection to the
jor of the generator. It uses a coupling transformer and the coded signal current:
scheme is shown in the Fig, 5.11
of 125 Hz
Fig. 5.11 100% earth fault protection
A coupling transformer is connected between the earth and the earthing resistance
R ie, in neutral to ground circuit, The primary of the coupling transformer is excited
by coded signal current source. This coded signal current has a frequency of 12.5 Hz.
This current is continuously injected into the generator stator winding through the
secondary of the coupling transformer.
During the normal condition the signal current injected into the stator flows
through stray capacitance of the generator and directly connected system. But when
earth fault occurs,
.e stray capacitance is bypassed. This increases the monitoring
current. This increase is measured by a measuring device. Depending upon this
measurement an immediate corrective action is taken.
This scheme gives the protection of 15 to 20% of stator winding from the neutral
side, the portion which is unprotected by Merz-Price protection. The remaining
portion is protected by Mere-Price protection. Overall 100% of stator winding gets
protected against earth faultsProtection and Switchgear 5-19 Generator Protection
$.10 Stator Protection Against Interturn Faults
The Merz-Price protection system gives protection against phase to phase faults
and earth faults. It does not give protection against intertumn faults. The interturn fault
is a short circuit between the turns of the same phase winding. Thus the current
produced due te such fault is a local circuit current and it does not affect the currents
entering and leaving the winding at the two ends, where CTs are located. Hence
Merz-Price protection cannot give protection against interturn faults.
In single turn generator, there is no question of interturn faults but in multiturn
generators, the interturn fault protection is necessary. So such interturn protection is
provided for multiturn generators such as hydroelectric generators. These generators
have double winding armatures, This means, each phase winding is divided into two
halves, due to the very heavy currents which they have to carry. This splitting of
single phase winding into two is advantageous in providing interturn fault protection
to such hydroelectric generators,
The Fig. 5.12 shows the interturn fault protection scheme used for the generator
with double winding armatures.
GL.
Two parallel paths.
Siem phase P-———> Phase
winding
Fig. 5.12 Interturn fault protectionProtection and Switchgear §-20 Generator Protection
The scheme uses cross differential principle, Each phase of the generator is doubly
wound and split into two parts $, and $; as shown in the Fig. 5.12. The current
transformers are connected in the two parallel paths of the each phase winding. The
secondaries of the current transformers are cross connected. The current transformers
work on circulating current principle. The relay is connected across the cross
connected secondaries of the current transformers.
Under normal operating, conditions, when the two paths are sound then currents
in the two parallel paths S, and S, are equal. Hence currents in the secondaries of the
current transformers are also equal. The secondary current flows round the loop and
is same at all the points. Hence no current flows through the relay and the relay is
inoperative
If the short cireuit is developed between the adjacent turns of the part S, of the
winding say then currents theough S; and S; no longer remain same, Thus unequal
currents will be induced in the secondaries of the current transformers. The difference
of these currents flows through the relay R. Relay then closes its contacts to trip the
circuit breaker which isolates the generator from the system.
Such an interturn fault protection system is extremely sensitive but it can be
vound armatures.
applied to the generators having doubly
5.11 Rotor Earth Fault Protection
The rotor circuit of the alternator is not earthed and dc. voltage is imposed on it:
And hence single ground fault in rotor does not cause circulating current to flow
through the rotor circuit. Hence single ground fault in rotor does not cause any
damage to it. But single ground fault causes an increase in the stress to ground at
*r points in the field winding when voltages are induced in the rotor due to
jents. Thus the probability of second ground fault increases.
If the second ground fault occurs then part of the rotor winding is bypassed and
the currents in the remaining portion increase abruptly. This causes the unbalance of
rotor circuit and hence the mechanical and thermal stresses on the rotor. Due to this,
rotor may get damaged. Sometimes damage of bearings and bending of rotor shaft
takes place due to the vibrations, Hence the rotor must be protected against earth
fault
Method 1; In this method a high resistance is connected across the rotor circuit. It
is provided with centre tap and the centre tap point is connected to the ground
through a sensitive earth fault relay as shown in the Fig. 5.13.Protection and Switchgear Genorator Protection
High resistance:
+ Sensitive
‘earn
Loot Bt tear
Brete 2 slay
Fiat warding oe
5,13 Rotor earth fault protection
Except the centre point, the earth fanlt relay detects the earth faults for most of the
rotor circuit. Thus most of the rotor winding part is protected against the earth faulis
Method 2 : The modem method of providing earth fa
injection or a.c, injection. The scheme is shown in the Fig. 5.14
it protection includes dic
A small dc. power
supply is connected to
the field circuit. A fault
detecting sensitive
relay and the resistance
Excher
Generator
ees ernie
are also connected in
series with the circuit
This high resistance
limits the current
through the circuit.
Resistance for current lening
Sensitive
A fault at any relay
point on the field
circuit will pass a
current of — sufficient
usilary
magnitude through the | 5
relay to cause its
operation. The dc.
supply is preferred and
simple to use and it
has no problem of the =
leakage currents. In
case of ac. injection, Fig. 5.14 Rotor earth fault protection
the high resistance is
replaced by a capacitor.Protection and Switchgear 5-22
The earth fault relays are instantaneous in operation and are connected to an
alarm circuit for indication and to take the proper action. This is because, a single
ground fault does not require an immediate action of isolating the generator.
5.12 Protection Against Loss of Excitation
The lose of excitation of the generator may result in the loss of synchronism and
slightly increase in the generator speed. The machine starts behaving as an induction
generator, It drawn reactive power from the system which is undesirable, The loss of
excitation may lead to the pole slipping condition. Hence protection against loss of
excitation must be provided.
The protection is provided using directional distance type relay with the generator
terminals
When there is loss of excitation, the equivalent generator impedance varies and
traces a curve as shown in the Fig. 5.15. This Fig. 5.15 shows the loss of excitation
aracteristics alongwith the relay operating characteristics, on R-X diagram.
wR
Locus of equivalent
(gonerasor impecance
dug fe ascii
Fig. 5.15 Loss of excitation characteristics
The equivalent generator impedance locus traces a path from first quadrant of R-X
diagram to the fourth quadrant, The distance relay is used which covers the portion of
the fourth quadrant where impedance locus path exists. Thus when the impedance
takes value in the region covered by the relay characteristics, the relay operates. The
relay operates when generator first starts to slip poles. Then relay trips the field circuit
breaker. And it disconnects the generator from the system, too. When the excitation is
regained and becomes normal, the generator can then be retumed to service instantlyProtection and Switchgear 5-23 Generator Protection
5.13 Negative Sequence Relays
The negative relays are also
provide protection against negative sequence component of unbalanced currents
existing due to unbalanced loads or phase-phase faults, The unbalanced currents are
w as these currents can cause
lied phase unbalance relays because these relays
us from generators and motors point of v
overheating, Negative sequence relays are g
generators and motors against unbalanced currents
lly used to give protection t
A negative sequence relay has a filter circuit which is operative only for negative
sequence components. Low order of over current also can cause dangerous situations
hence a negative sequence relay has tow current settings. The earth relay provides
protection for phase to earth fault but not for phase to phase fault. A negative
sequence relay provides protection against phase to phase faults which are responsible
to produce negative sequence components.
The Fig, 5.16 shows the schematic arrangement of negative phase sequence relay
cr,
Fig. 5.16 Negative phase sequence relayProtection and Switchgear 5-24
Basically it consists of a resistance bridge network. The magnitudes of the
impedances of all the branches of the network are equal. The impedances Z, and Z,
are purely resistive while the impedances Z, and Z, are the combinations of resistance
and reactance. The currents in the branches Z> and Z, lag by 60° from the currents in
the branches Z, and Z,. The vertical branch B-D consists of inverse time characteristics
relay, The relay has negligible impedance.
The current Iy gets divided
™ 72 into two equal parts f, and I;. And
I, lags 1; by 60% The phasor
diagram is shown in the Fig. 5.17.
Rt = ie
Let 1, = L
The perpendicular is drawn
from point A on the diagonal
meeting it at point B, as shown in
° aA? the Fig. 5.17. This bisects the
Fig. 5.17 diagonal.
« |e
OB = >
Now in triangle OAB,
oB
cos = OR
8 (5)
2
ree =k (uy
Now I, leads Ip by 30° while [, lags I by 30°
Similarly the current Ip gets divided into two equal parts 1, and 1,. The current
lags t, by 60°. Fromm equation (1) we can write,
1
K =h=h (2)
‘The current 1, leads Ig by 30° while current I, lags Ip by 30°
The current entering the telay at the junction point B in the Fig. 5.16 is the vector
sum of Ij, Iy and lyProtection and Switchgear 5-25 Generator Protection
Tray = hh +1;
le ly
+ -& (leads Ix by 30% + 2 (lags Ip by
y a! 30) va igs In by 309)
The vector sum is shown in the Fig. 518 when the load is balanced and no
tive sequence currents exist.
neg.
te
Tk can be seen from the
i+i
haley =
Thus the current entering the relay at point B is zero. Similarly the newultant
current at junction D is also zero, Thus the relay is inoperative for a balanced system
Now consider that there is unbalanced load on generator or motor due to which
negative sequence currents exist. The phase sequence of C.T. secondary currents is as
shown in the Fig. 5.19 (a). The vector diagram of I, Is and Ty is shown in the
Fig, 5.19 (b) under this condition.
The components 1, and I are equal and opposite to each other at the junetion
point B. Hence 1, and ly cancel each other. Now the relay coil carries the current ly
and when this current is more than a predetermined value, the relay trips closing the
contacts of trip circuit which opens the circuit breaker,Protectio
(a) GT. secondary currents
Fig, 5.19 Negative sequence currents
Zero Sequence Currents ; The zero sequence components of secondary currents
are shown in the Fig. 5.20 (a). We know that,
~ |
(a) (b) te)
Fig. 5.20 Zero sequence currents
ta ty by
ie = Tal,
iy = fyoty
These sums are shown in the Fig. 5.20 (b) and (c). It can be seen from the
Fig. 5.20 (d) that,
i+, = fy in phase with by
The total current through relay is f) +i, +[y, Thus under zero sequence currents
the total current of twice the zero sequence current flows through the relay. Hence the
relay operates to open the circuit breakerProtection and Switchgear 8-27 Generator Protection
To make the relay sensitive to only
et negative sequence currents by making it
inoperative under the influence of zero
sequence currents is possible by
GT. connecting the current transformers int
delta as shown in the Fig. 5.21. Under
delta connection of current transtor
in the
eT no zero sequence current can flow
network.
Fig. 5.21 Delta connection of C.T.s
5.13.1 Induction Type Negative Sequence Rel
y
her commonly used negative sequence relay is induction type. Its construction
is similar to that of induction type over current relay. The schematic diagram of this
type of relay is shown in the Fig. 5.22
ny ®
Fig. 5.22 Induction type negative sequence relay
The central limb of upper magnet carries the primary which has a centre tap. Due
to this, the primary winding has three terminal 1, 2, and 3. The section 1-2 is
energized from the secondary of an auxiliary transformer to R-phase. The section 2-3
is directly energized from the Y-phase current
The auxiliary transformer is a special device having an air gap in its magnetic
circuit. With the help of this, the phase angle between its primary and secondary can‘Generator Protection
Protection and Switchgea
be easily adjusted. In practice it is adjusted such that output current lags by 120°
rather than usual 180° from the input.
So, I, = Input current of auxiliary transformer
Ig) = Output current of auxiliary transformer
and Igy lags Ip by 120°
Hence the relay primary carries the current which is phase difference of ly; and Iy
Positive Sequence Currents : The C.T. secondary currents are shown in the
5.23 (a). The Fig. 323 (b) shows the position of vector fy; lagging Ix by 120° The
5.23 (c} shows the vector sum of Igy and — ly.
The phase difference of Ip, and ly is the vector sum of Ip, and — fy. It can seen
mm the Pig. 5.23 (c) that the resultant is zero. Thus the relay primary current is zero
nd relay is inoperative for positive sequence currents.
(0) C.7, secondary currents (b) Current Ing
(0) Relay current
Fig. 5.23 Positive sequence currents.Protection and Switchgear 5-29 Generator Protection
Negative sequence currents : The C.T. secondary currents are shown in the
Fig.5.24(a). The Fig. 524 (b) shows the position of Ig, lagging I, by 126° The
Fig. 5.24 (c} shows the vector difference of Ip, and ly which is the relay current,
Under negative sequence currents, the vector difference of Igy and Ty results into a
current I as shown in the Fig. 5.24 (c). This current I flows through the primary coil
of the relay
Tag Te
(a) €.7. secondary currents {0} Current ing
fc) Relay current
Fig. 5.24 Negative sequence currents
Under the influence of current L the relay operates, The dise rotates to close the
trip contacts and it opens the circuit breaker.
This relay is inoperative for zero phase sequence currents. But the relay can be
made operative for the flow of zero sequence currents also by providing an additional
winding on the central limb of the upper magnet of the relay. This winding is
connected in the residual circuit of the three line C.T.s. This relay is called induction
type negative and zero sequence relayProtection and Switchgear 5-20 Generator Protection
The schematic arrangement of induction type negative and zero sequence relay is
shown in the Fig. 5.25.
Awaay
| ie mar
Fig. 5.25 Induction type negative and zero sequence relay
5.14 Protection Against Unbalanced Loading
When the load on the generator becomes unbalanced, negative phase sequence
currents flow, The negative sequence components produce a rotating magnetic field
which rotates at synchronous speed in a direction opposite to the direction of rotor
field. Hence effectively the relative speed between the two is double the synchronous
speed. Thus double frequency currents are induced. in the rotor. These currents cause
severe heating of the rotor and can cause damage to the rotor. The unbalanced stator
currents also cause severe vibrations and heating of stator. Hence it is necessary to
provide the negative sequence protection to the generators against the unbalanced
load conditions.
The negative phase sequence filter alongwith the overcurrent relay provides the
necessary protection against the unbalanced loads.
The relative asymmetry of a three phase generator is given by the ratio of negative
sequence current to the rated current. Mathematically it can be expressed as,
% S ‘100
where %S
percentage asymmetry
1, = Negative sequence current
I = Rated currentProtection and Switchgear 5-34 Generator Protection
The negative sequence protection scheme is shown in the Fig. 5.26,
Genewstor
or
iter
Relay
Fig. 5.26 Negative sequence protection
A negative phase sequence filter is connected to the secondaries of the current
transformers. A negative phase sequence filter consists of resistors and inductors.
‘These are so arranged that under normal operating conditions, the relay is inoperative.
The filter circuit is stable for the symmetrical overloads up to about three times the
rated full load.
When unbalanced load occurs, the negative phase sequence filter cireuit produces
an output proportional to the negative phase sequence components. This is directed
through the relay coil. Hence the relay operates to open the circuit breaker to isolate
the generator,
Examples with Solutions
wm Example 5.3: The neutral point of a 11 kV alternator és earthed through a resistance
of 12 01, the relay is set to operate when there is out of balance current of 0.8 A. The
CT's have @ ratio of 2005. What percentage of the winding is protected against carth
faults. What must be the minimum oalue of earthing resistance required to give 90% of
protection to each phase ?Protection and Switchgear 5-32 Generator Protection
Solution : The given values are,
Vi = 1kKV R=2Q CT ratio = 2000/5
i, = relay current = 08 A
L, = minimum operating line current (CT. primary)
kx 2000 ~ 0.8 2000
“ 5 5
= 300A
% Winding anprotected =
= 60.46.%
‘we Winding protected = 100 - 60.46 = 39.53 %
Thus with R = 122 only 39.53 % winding is protected.
It is necessary to give 90% protection.
% Winding unprotected = 100 - 90 = 10%
R«l,
10% = v «100
Rx 320
10 = G50. asx "1°
R = 198469
This is the minimum value of resistance to give 90% protection to the largest
machine
> Example 5.4: A 50 MVA, 3 phase, 33 KV synchronous generator is protected try the
rice protection using 1000/5 ratio CTs. It is provided with restricted oarth fault
protection with the earthing resistance of 7.5 Q . Calewlate the percentage of winding
unprotected in cach phase against earth faults if the mininium operating current of the
relay is 0.5 A
Solution : The given values are,
V, = 33KV CT. ratio = 1000/5 R=750Protection and Switchgear 5-33 Generator Protection
i, = 05 A = relay current
minimum operating current (primary)
Vy _ 33x10"
ves
3 V3
= 1905255 V
% Winding unprotected = x10
sm Example 5.5: A 13.2 £V, 3 phase, 100 MW at 0.8 pf lag, alternator has reactance
02 pur, If it is equipped with a circulating current differential protection set to operate
at Feast at 500 A fault current, determine the magnitude of the neutral grounding
resistance that leaves the 10% of the winding unprotected.
Solution ; The given values are,
Vi = 1B2KV cos@=08 P= 1l0QOMW X=0.2 pu.
Now P= V3, |, cos
loox10® = J3x 13.26 108% 1, = O8
I, = 546733 A = 1 = full load a
The p.u. reactance is given by,
1x
pu.X = 4) where X = reactance per phase
‘3467.33 ‘i
02 = where V =
f13.2%10° ) v3
3
X = 0.2787 0 per phase
% af unprotected winding = 10%
0
e of unprotected winding, = «0.2787
Reactan 7Protection and Switch:
Generator Protection
= 0.02787
Voltage induced in 10% of unprotected. winding
1. _ 132x108
joa" Y = 709" — yg = 782023 V
Let this voltage bev = 762.1023 V
where
Now
where
Ze=4
Z = Impedance offered to the fault
rt = Resistance in neutral
x = Reactance of 10% of winding
v = Voltage induced in 10% winding
= 762.1023 V
i = Foult current = 500 A
reser _ 762.1023
300
75 (0.02787)? = 15242
+? + (0.027877 = 2.3232
eos 23224
r= 1540
This is the required resistance in neutral earthing.
‘a
Example 5.6: An alternatar stator winding protected by a percentage differential relay
is shown in the Fig. 5.27. The relay has 15% slope of characteristics (I, ~ 1.) against (I,
+ 1y/2). The high resistance ground fault has occurred near the grounded neutral end of
the generator winding while the generator is carrying load. The currents flowing at each
enrd of the generator winding are also shown, Assuming C.T, ratio to be 50/5 A, will
the relay operate tv trip the circuit breaker ?Protection and Switchgear 5-35 Generator Protection
+ +PA
300+ JOA 340 +0.
Torque, 18% Slope
{ “ve
torque
(ay
Fig. 5.27
Solution : From the given current at two ends, let us calculate C.T. secondary
currents at two ends,
5
iy = G00 + j Ope 3A
5
and ip = GI +) Oxo = 34a
The directions of currents are shown in the Fig. 5.28.
Fig. 5.28
The current flowing through the relay coil is i, i.
ipwig = 3-34=-04A
While 15h 343-4 324
From the characteristics of 15 % slope, corresponding to + > the out of balance
curtent required is,
iy - iy Siopex( "4 }
0.15x3.2
0.48 A
4Protection and Switchgear 5-36 Generator Protection
15% Slope
Fig. 529,
above
This is shown in the
‘Thus i, - iz must be
more than 048 A ie.
line to
operate the relay but
actual point is located
ite ee below line in
2 negative torque region.
Fig. 5.28 Hence the relay will
not operate.
lm Example 5.7: A 66 KV, star connected alternator has a transient reactance of 2 2
per phase and negligible winding resistance. It is protected by circulating current
Merz-Price protection, The atternator neutral is earthed through the resistance of 7.5 Q.
The relays are set to operate when there is out of balance current of 1 A in secondary of
500/5 A current transformers. How much % of winding is protected against earth fault?
Solution : The given values,
VU = 66k¥ X=20/phase r=750 CT. = 500/5
Let the x % of winding is unprotected,
Reactance of unprotected winding = ino” 22002x%a
vy 6x10
at = 2 = 3810511 V
3 3
V = Voltage across unprotected winding
x
= 79g % 3810-514 = 38.1051 x Vv
r= 75Q
Z = Impedance offered to the fault
= r+j 02x)
= 75+) (002% a
Iz) = ¥@5?+0.029*
i = fault current
= out of balance secondary current x C.T. ratio
full voltageProtection and Switchgear 5-37
1200
3
= 100A
v
7
IZ)
aca? . 3810511
10.57 +(0.02y7 = =
(757 + (0.02 x)? = 0.1452 x
56.25 + 4x10x* = 0.1452 x*
O.1448 7 = 56.25
x? = 388.4668
x = 19.7%
This is % of winding unprotected.
% of winding protected = 100 - 19.7
= 80.29 %
itm Example 5.8: A synchronous generator rated at 20 kV protected by circulating
current system having neutral grounded through a resistance of 15 Q. The differential
protection relay is set to operate when there is an out of balance current of 3 A, The
CT's have ratio of 1000/5 A, Determine,
i) The % of winding remains unprotected
iD Value of earth resistance to achieve 75% protection of winding
Solution : The given values are,
Vi = 20kV, 3A, R=158, CT ratio = 1000/5
) 1, = minimum line operating current (C-T, primary)
=, 1000 _ 31000
= igxe
= GOA
Ve
= 11597 ¥
% X = % of winding unprotected
= Blo grog = 15*620, ng
V 11547tection and Switchge
7794 %
ii) We want 75% protection,
%X = 100-75 = 25%
Remaining conditions are same except R.
RI
25 100
Vv
R600
25 100
11547
2511547
600% 100
4811
This is the required earth resistance.
jmp Example 5.9: The Fig. 5.30 shows the percentage differential retay used for the
protection of an alternator winding. The relay has minimum pickup current of 0.25 A
and has a % slope of 10%. A high resistance ground fault occurs near the grounded
neutral end of the generator winding with the current distribution as shown in the
Fig. 5.30. Assume a C.T. ratio of 400 : 5, determine if relay will operate.
so+i0 A moe 00 +0 A
A
Foun
Fig. 5.30
Solution: For the given current at the two ends, the CT. secondary currents can be
obtained using C.T. ratio as,
. . 5
i) = (380 + j 0) xa 4754
. 5
(340 0) x = 4.25 A
(380 +40) * Fm
ip- ip = 475-425=05A
iti, _ 4.754425
2 z
= 45A
So ij - iy current flows through operating coil while 4.5 A flows through the
restraining coilProtection and Switchgear 5-39 Generator Protection
With the minimum pickup current of 825 A, and slope 10%, the operating
characteristics is as shown in the Fig, 5.31,
= Actual paint
Minimum
pickup current
45a
(538)
Fig. 5.31
‘The equation of the characteristics is,
y
mxte
At origin, x = 0 but y = 0.25
y= ¢= 025
Hence characteristic equation is,
(a ~
where m = slope = 0.1
(iy = iy)
For aa 4.5 we get,
Ayr ip = ed 5)+0.25
= O74
Thus to operate the relay, i, ~ iy must be greater than 0.7 A when “142
is 4.5 A.
But actually i, - iy = 0.5 A as shown. It is located below the line in negative torque
region hence relay will not operate.
im Example 8.10: An alternator rated 10 KV protected by balanced circulating current
system has its neutral grounded titrough a resistance of 10 ohms. The protective retay is
set to operate when there is an out of balance current of 1.8 amperes in the pilot wires
which are connected to the secondary of current transformers with ratio 1000/5,Protection and Switchgear 5-40 ‘Generator Protection
Determine
i) The percentage winding which remains unprotected
ii) The minimum value of the earthing resistance required to protect 80% of the winding.
(V1. August-2002)
Solution : Vj, = 10 KV, R = 10.0, CT. ratio = 1000/5, i, = 184
1, = minimum operating line current (C.T. primary)
= a 1310 = 360 4
V = line to neutral voltag ube ee 573.5026 V
i) % Winding unprotected = M109 = 2O* 260-100
= 62,3538 %
ii) Tt is necessary to give 80 % protection.
% Winding unprotected = 100 = 80 = 20 %
Rx 360
20 = s7a55006 “1°
R = 3.20759 Minimum earthing resistance requited
tm Example 5.11: An alternator stator winding protected by a percentage differential
relay is shown in Fig. 5.32a). The relay has 0.15 amp minimum pick up and « 12%
slope of characteristics tiy ~ i) V, ( = }
fiear the grounded neutral end of the generator winding while generator is carrying
load. The currents flowing at each end of the generator winding are shown in Fig. 5.32.
Assuming that the CT's have 400/3 amps ratio mud no inaccuracies will the relay trip
the generator CB under this fault condition.
A high resistance ground fault has occured
Fig. 5:32(a)Protection and Switchges 5-41 Generator Protection
Positive torque
S— Slope 12%
Tip
2
Fig. 5:32(b)
(AU-April-2004)
Solution: From the given current at two ends, let us calculate C.T, secondary
curents at two ends,
375 8
= (300+ j0)x
iy = (300+) 25 = 45.4
The relay coil current = 75 A
itis |
aS? = 4125 A
From the characteristics of 12 % slope, corresponding to | 12 "2 }. the out of
2
balance current required is,
ip- i = slope «{ 4!2.) = 01244125 = 0.495 A
\ }
Thus ij - i must be more thatn 0.495 A for relay to operate. And actually it is
0.75 A. Hence the relay will operate :
tly)
Fig, 5.33Protection and Switchgear 5-42 Generator Protection
Actual point is located in positive torque region. Slope of line through actual point is
As this slope is more than 12% of the characteristics given, relay will operate.
mp Example 5.12: A 3 phase, 10 MVA, 6,6 kV alternator supplies a load of 8 MVA at
0.8 pf. and is being protected through Merz-price circulating current system and its
relays are sa set that they da not operate until the out of balance current ocurs at 20%
of full load current. Calculate the value of earth resistance to be provided in order to
ensure that only 10% of alternator winding remains unprotected. Assume alternator
reactance of 10% Neglect resistance of the alternator. (AU-Dec,-2004)
Solution : V, = 6.6 kV, Rating = 10 MVA, V = V,/3 = 38105117 V.
Rating = ¥3 Vil,
__10x10%
V3 x 66x10
x
yx loo X = Reactance per phase
1, = = 874.7731 A so Full load current
% Reactance
874.7751X
38105117
X = 0.4356 0
10 = 100
Reactance of unprotected winding = jap 056 = 0.04356 2
y
Voltage induced in unprotected winding
10
100
i = Fault current = 20% of I, = 174.954 A
V = 38105117 V
© = impedance offered to fault = 2.178 0
Bur Z = A+} 0.083560
[Z| = JR? = (0.04356)?
(2.178)? = R? + (0.04356)?
R = 21779 Earth resistance requiredProtection and Switchgear 5-43 Generator Protection
im Example 5.13: Current transformers of current ratio of 1000/3 A are used for
protection of @ star connected 3 phase, 10 MVA, 6.6 kV alternator. if the relay is set to
operates for a minimum current of 0.5 A, Calculate the percentage of each phase stator
winding which is unprotected agains earth fault when the machine operates at normal
ttoltage. Assume that star point of alternator is earthed titrough a resistance af 7.5 Q.
(AU-April-2005)
1000/5, i, = 0.54
Solution: V, = 6.6% 10° V, R=75Q. C1. ratio =
i, x GT, ratio = 0.5 «ie = 100A
Vy. 6.610%
v ~ = 38105117 V
we
7.5% 100
«100 = ai0ariy «10°
‘im Example 5.14; A 500 RVA, 6.6 KV star connected alternator has a synchronous
reactance of 1.0: per phase and negligible resistance. The differential relay operates if
the out of balanice current through it exceeds 30% of the normal full load current of the
alternator, The star point of the alternator is earthed through a resistance of 5.0 . What
percent of the stator winding is left unprotected ? Show that the effect of the alternator
reactance ean be neglected. {AU-Dec.-2005)
Solution : The full load current,
i, = Ya = 500x102
V3V, ¥3%6.6x10°
30% I, = 0.3 x 43,738 = 13.1214 A
= 43738 A
‘Out of balance curent
Let winding unprotected =
X ay:
00 Ori)
Impedance of x winding
Value of earthing resistance = 5.
Total impedance at fault of the fault circuit.
= (5+) 001 x}
Voltage induced in x % of winding
= 66x10? x _ 66x
“B00
Veltage induced
Impedance
Out of balance current =.Protection and Switchgear 5-44 Generator Protection
sox
3
R124 = SF pat vf
This is to be solved by trial and error method. Hence effect of alternator reactance
can be neglected.
66x
waits =
x 1.7217 % . «Winding unprotetced.
‘The equation (1) can be solved as,
66x,
53
13.1214
Considering magnitude.
5)? + (O.01x)?
{25+(001)? = 2904 x
25+ (0.01x)?
x
8.4334 x?
L7217%
This shows that the reactance can be neglected without any error.
Review Questions
1. Which ane th
rious types of faults which can occur in a generator ? Explain in brie
2. Why the protection of generators is complex ? Explain,
3. Which are the various abnormal raneting conditions, which may exist in a generator ? What are
their effects and how these effects cari be sainttiized ?
4. Explain the basic differential protection scheme, What are its disadvantages ?
5. Explain the basic perventage differential protection scheme, Draw its operating charac
showing positive anid megatite tongiee regions.
6. Brace and explain the Merz-Price protection of alternator stator windings. State its actoantages.
What if the role of auxiliary relay, in Merz-Price protection 7
8, Explaive the restricted ert fault protection of generators.
9. Derive the expression for the percentage of winding unprotected int the restricted! exrth fault
protection.
10. Explain the operation of unrestricted earth fault protection scheme.
11. Draw and explain balanced carth fanelt protection scheme,
12. Fs it possible that 100 % winding of generstar is protected against earth fates ? How ?
13. Suggest the scheme Jor interturn fault protection for Stator of alternator,Protection and Switchgear 5-45 Generator Protection
1,
15,
16,
1”,
19
20.
Explain the negative phase sequence protection for the generators.
Wihat are the methods to provide rotor earth fault protection ?
How the protection against loss of excitation is provided in generators 7 Why it is important ?
erator is provided with restricted earth-faudt protection. The ratings are TI RV, SOMO KVA,
The percentage of winding protected against phase to ground font és 80%. The relay setting: such
that it trips for 25% ont of balance. Calculate the xesistance to be added in newtral to ground
comnectian. (Ans. 1.94.0
‘The neutral point of a 10,000 V alternator és carthed through a resistance of 10 ohms, the relay is
set to operate when there is an out of batence current of 1A. The CTs have a ratio of 1000/5.
What percentage of the winding ts protected against fault to earth and what must be enininnune
nulue of earthing resistice Fo give 90% protection to cach phase winding ?
(Ans. : 62.5%, 2.88 2)
A 3 phase, 2 pole, 17 KV, 10,000 kVA alternator as neutral exrthed through a resistance of 7
ohms. The machine has current balance protection which openttes upon out af bilance current
exceed 20% of full toad. Determine ‘%e of winding protected against carth fault. (Ams. :88.4%)
‘The Fig. 5.34(a) shows percentage differential relay applied to the protection of an alternator
winding, The relay has 10% slope of characteristics J, ~ Ip bs (Ty + B)/2.
A high resistance ground fault occurred near the grounded neutral end of the generator winding
while generator is carrying load. As a consequence. the currents in amperes flowing at each ed of
the winding are shown in Fig. 534(b). Assunting CT. ratio of 400/5 amperes, will the relay
‘operate to trip the Breater. (Ans, + Relay will not operate?
Circuit
breaker s20+)0
Os 0 "
‘Operating coll
Fig. 5.34(a)
Oth
——> Characteristic
Fig. 5.34(b)Protection and Switchgear
Generator Protection
21
‘ATL RY, 3 plaase alternator has full loud rated current of 200 A. Reactance of armature winding is
1Spercent, The differential protection system is set to operate om carth fault currents of more than
200 A, Find the neutral earthing resistance, which gives earth fault protection to 90" of stator
winding (Ans, : 3.145 0)
A star-connectal 3+phase 10 MVA, 6.6 kV alternator hes @ per phase reactance of 10%. It is
protected by Merz-Price circulatingseurrent principle which is set to operate for fault currents not
less than 175 A. Caleulate Use wale of earthing resistance to be provided in orer to ensire that
only 10P% of the alternator winding remains unprotected, (Ans, : 2171.9)
Astor connected. 3 phase, 10 MVA, 6.6 kV alternator is protected by Merz-Price circulating
current principle using 1000/5 amperes current transformers. The star point of the altermator is
earthed through a resistance of 7.501. If the minimum operating current for the relay is 0.5 A,
calculate the percentage of each phase of the stator winding which is unprotected against earth
faults when the machine is operating at narmal voltage. (Ans. : 19.69%)
A 6600 volt S-phase turbo-alternator has a maximum continuous rating of 2,000 KW at 08 pf.
and its, reactance is 12.5%, dt és equipped with Mers-Price circulating current protection which is
set (a operate at fault currents not less tha 200 amperes. Find wiat value of the nettral earthing
resistance lenwes 10% of the windings unprotected ? (Ans. : 1.89.9
1. ASO MVA, Jphiase, 33 RV alternator is being protected by the use of circulating current batence
selene using 2000/5 ampere current transformer, The neutral of the generator is carthed through a
NGR of 75 ohms. If the pick up current for the relay is just abooe 0.5 ampere, setermine what
percentage of the winding of each phase unprotected ogainst eartit when the machine operates at
nominal roltage. (Ans, : 7.88%)
gooInduction Motor Protection
6.1 Introduction
Based on the control action i.e. starting, stopping or reversal, various controlling
elements known in electrical terms as switchgear are employed for the proteetion of
duction motor. Generally two basic protections viz short circuit protection and
‘overload protection are provided for each motor. The switchgear used for protection
includes contactors with H.RC fuse and thermal overload relays along with cireuit
breakers.
If the rating of the motor is upto 150 kW then contactors and fuses can be used
while for motors having rating beyond 150 kW, circuit breakers are used, The
contactor is a kind of switch through which supply can be given to the motor when
its coil is energized. If the current to be interrupted is six times the rated current of
the motor then contactors can be used.
6.2 Abnormal Conditions and Failure in Case of Induction Motor
‘The three phase induction motors are used in numerous industrial applications.
Hence before studying the protection circuit we have to consider the abnormal
conditions and failure that may occur in case of induction motor.
If the motor is heavily loaded beyond its capacity then it will be overload
condition of motor in which case motor draws heavy current from the supply and
there will be simultaneous rise in temperature of winding and deterioration of the
insulation resulting in damage of winding. Hence the motor must be protected against
this mechanical overloading with overload protection circuits. Normally thermal
overload relays, over current relays or miniature circuit breaker with built in trip coils
may be used.
It might be possible that the rotor is locked or starting lasts for longer duration or
rotor does not move becatise of excessive load (stalling) at start. In all these cases
motor draws heavy current from the supply and results in damage to the winding
due to overheating as stated above. In this case thermal relays or instantaneous
overcurrent relays are used.
(6-1)Protection and Switchgear 6-2 Induction Motor Protection
If the supply conditions are abnormal such as loss of supply voltage, unbalanced
supply voltage, phase sequence reversal of supply voltage, over voltage, under voltage
or under frequency then also the performance of the motor is affected. With
unbalanced supply voltage there will be excessive heating while with undervoltage the
motor draws more current for the same load, For undervoltage protection,
undervoltage relays are used
With correct phase sequence, the motor runs in one direction. With change in
phase sequence of supply it runs in other direction which is dangerous in some of the
applications such as cranes, hoists or elevators. In such cases phase reversal relay may
provided which will disconnect the supply to the motor through the circuit
breaker.
get damaged which may
‘hare rare in nature. For
Due to excessive temperature rise, the insulation may
lead to stator earth fault or stator phase to phase fault w
low rating motors, HRC fuses provide sufficient protection against these faults while
for large motors, differential protection may be used.
Due to blowing of fuse in any phase or open circuit in one of the three phases
results in single phasing. In such case motor continues to run and if it is loaded to its
rated value then it will draw excessive current which will damage the rotor and
eventually the motor will be damaged due to excessive overheating. Normally thermal
overload relays are used against single phasing. Sometimes special single phase
preventer may be provided.
ven in
Summary of abnormal condition. and protection circuit to be employed is i
the table.
a
Abnormal condition Choice of pratection circuit to be employed
1] Mechanical overtoad ‘Overoad release, thermal overload relay, over
‘current relays, miniature circuit breaker (MCB) with
builtin trip: coi
2 | Stating oF prolonged starting of motor Thermal relays, instantaneous overcurrent relay.
3 | Under voltage Under voltage release, under voltage relay.
4 | _Unbatanced voliage Negative phase sequence rotays.
5 | Reverse phase sequence Phase reversal relay.
6 | Phase to phase fault or phase to earth HRC fuse, Instantanoous overcurrent relays. For
fault large motors, differentia! protecton may be
employed for economy.
7_| Single phasing ‘Thermal overload relays, single phase prevent
Table 6.1Protection and Si
ge:
6-3 Induction Motor Protection
‘The moter protection circuit that is designed should be simple inv operation and
economically feasible. Its cost should be less than 5% of the motor cost. It should also
be kept in mind that during starting and permissible overload conditions, the
protection circuit should not operate. The choice of motor protecting circuit is based
on various factors such as rated voltage, rated kW, size of motor, type of induction
motor, type of starter, type of switchgear used, cost of moter, type of load, starting
current possibility of occurrence of abnormal conditions etc.
6.3 Protection Circuit for Induction Motor
The protection cireuit along with its single line diagram is shown in the Fig, 6.1,
Fuse
Thecmal overload relay
XN ‘Switch supply
ON pushbutton Fuse
(normaly open)
‘OFF
(Nermaily — Bution
closed)
“bbs?
ve Be ACE
Contactar
energizing
coil contral coil
induction
Motor
() {b) Single fine diagram
Fig. 6.4Protection and Switchgear 6-4 Induction Motor Protection
The three phase supply is given to the motor through various elements such as
fuse, switch, contactor and thermal overload relay. The control circuit of contactor
consists of energizing coil, start and stop buttons. The start (ON) push button is
normally open green switch while the stop (OFF) push button is normally closed red
switch
When the start button is pressed then the contactor coil is energized as it gets
supply voltage. The coil attracts the plunger when excited and the main contacts are
closed along with the auxiliary contact. Even if the ON push button is released, the
contactor coil remains energized as it gets supply through auxiliary contacts. Thus
moter starts running
The OFF push button which is normally closed when pressed cuts the supply of
the contactor coil and hence the main as well as auxiliary contacts are open so motor
eventually stops. If supply voltage fails, control coil is de-energized which opens the
contactor and motor stops
During overload condition, the thermal overload relay operates. Thermal overload
relay consists of bimetallic strips. Because of bending of one or more bimetallic strip
resulls in operation of common lever which operates the trip contacts to de-energize
the coil and disconnects the supply to the motor.
The bimetallic strips are either heated directly by flow of current or with the help
‘of special heater coil through which motor current flows. For large motors, these
relays are connected in secondary of current transformers. The bimetallic strips can be
‘of self setting type or hand resetting type in which mechanical reset is required as the
trip mechanism locks itself in eperated condition. It should be observed that the rating,
of thermal relay should be such that it should not operate during normal starting
conditions, A setting range is provided for adjustment for various load conditions.
Protection against short circuit is provided with the help of HRC fuses.
6.4 Single Phasing Preventer
If one of the supply line is disconnected due to open circuit or improper contact in
switeh then still the motor continues to run. The power is then supplied to the
remaining windings. The current in the other phases increases to about 3 times its
normal value, This is called single phasing which results in unbalanced stator currents.
The component which is present in this unbalanced current called negative sequence
component causes magnetic flux rotating in opposite direction to the main flux. This
results in double frequency currents to induce in the rotor to cause its heating. Thus
major damage to motor may take place due to single phasing if proper precaution is
not taken. As the phase overcurrent relays react slowly, they cannot give the
instantaneous protection against single phasing.Protection and Switchgear 6-5 Induction Motor Protection
For small motors separate protection against single phasing is normally not
provided as thermal relays sense the increased current in remaining phases due to
single phasing and provides the sufficient protection
A separate single phasing protection circuit is required in case of large induction
motors as even a small unbalance can cause damage to motor winding and rotor. The
single phasing preventer is shown in the Fig, 6.2.
Control
circuit
Auxiliary
‘Three phase
UM,
Fig. 6.2
As shown in the figure, it consists of C.Ts connected in each phase. The output of
control circuit is fed to the level detector which sense the magnitude of unbalance,
Depending on this output from the control circuit the tripping command to the starter
or the circuit breaker is given when negative sequence current exceeds its preset limit.Protection and Switchgear 6-6 Induction Motor Protection
6.5 Ground Fault Protection
‘The ground fault protection is achieved using earth leakage circuit breaker (ELCB)
When the fault current or leakage current flows through earth return path then it
forms the earth fault. These faults are relatively frequent and hence protection is
required against these which is provided with the help of Earth leakage circuit
breaker.
Consider an example of a person whose finger sticks into the socket. Even though
the metal enclosure is securely earthened, the person will receive a severe shock.
‘Under such case there must be certain device that will cut the supply. This can be
done with the help of ELCB which will typically trip in around 25 ms if current
exceeds its preset value
‘The schematic of ELCB is shown in Fig. 6.3.
Pn oo ‘Fault to
snaie Gircuit i i wt aoe
phase 8u ‘ teakage or
arf Breaker : S
{Ho 2 ve terminal
Fig. 6.3
As shown in the Fig. 6.3 ELCB consists of a small current transformer surrounding
live and neutral wire. The secondary winding of current transformer is connected to
relay circuit which can trip the circuit breaker which is connected in the circuit.
Under normal conditions, the current in line and neutral conductor is same so the
net current (I, —I1y) flowing through the core is zero. Eventually there will not be any
production of flux in the core and no induced emf. So the breaker does not trip.
If there is a fault due to leakage from live wire to earth or a person by mistake
touching to the live terminal then the net current through the core will no longer
remain as zero but equal to I, -Iy or I, which will set up flux and emf in CT. As
per the preset value the unbalance in current is detected by C.T. and relay coil is
energized which will give tripping singal for the circuit breaker. As C.T. operates with
low value of current, the core must be very permeable at low flux densities.Pratection and Switchgear 6-7 Induction Motor Protection
In case of three phase circuits, single ring shaped core of magnetic material,
encircles the conductor of all three phases as shown in the Fig. 64. A secondary is
connected to relay circuit. Under normal condition, the component of fluxes due to
fields of three conductors ate balanced and secondary carries negligible current.
Core
of CT.
Secondary
of. GT.
Fig. 6.4
During faulty condition, the balance is disturbed and current is induced in the
secondary to trip the circuit breaker through relay.
This method to provide earth fault protection is called core balance type
protection or zero sequence current transformer (ZSCT) protection. In case of earth
faults, to avoid burning of coils and stampings the motor must be disconnected as
quickly as possible from the supply.
The Fig. 6.5 shows ZSCT protection scheme. It is preferred for the systems with
neutral earthed via resistance. (See on next page)
6.6 Phase Fault Protection
Protection is also called short circuit protection. At the time of such a fault,
the current increases by 8 to 10 times the full load current of the motor, Attracted
armature type relay wi
the full load current. This is because starting current can be 4-5 times full load current
connected in each phase with a current setting of 4-5 timesProtection and Switchgear Induction Motor Protection
Three
¥ phase
& supply
Induction
motor
Fig. 6.5 Earth fault protection by ZSCT
Hence to operate the relay only under fault condition such a setting is necessary. Such
a protection is shown in the Fig. 6.6.
cts
|. 6.6 Phase and earth fault protectionProtection and Switchgear 6-9 Induction Motor Protection
The phase faults can cause burn out of coils and stampings and hence motor
should be disconnected as quickly as possible when fault occurs, Fast over current
relays also are used to provide phase fault protection
As mentioned above to avoid relay functioning during starting, the short circuit
protection current setting must be just above the maximum starting current of the
motor.
6.7 Phase Reversal Protection
The direction of induction moter depends on the direction of rotating magnetic
field produced by the stator windings. For a particular phase sequence RYB the
motor rotates in a particular direction due to corresponding direction of rotating
magnetic field. But if any two lines are interchanged after repairs the phase sequence
reverses such as YRB, Then the direction of rotating magnetic field also reverses and
induction motor starts rotating in opposite direction. Such a change of direction is
s, lifts or in threading mills
dangerous if the induction motor is used for cranes, h
ete.
Thus to disconnect induction motor from supply if there is phase reversal, phase
reversal protection is provided.
This protection is provided using motor driven dise working on electromagnetic
principle. The secondaries of two current transformers connected in two lines drive the
motor to operate the disc. The arrangement is such that for a normal direction of
motor, disc rotates in a particular direction which keeps the auxiliary contacts closed.
But if thete is phase reversal then the torque produced reverses to rotate the disc in
opposite direction. Due to this auxiliary contacts get opened. This intumn either
operates the circuit breaker or de-energises starter coil to disconnect the motor from
the supply. Thus phase reversal protection for the induction motor is achieved. Naw a
days solid state phase reversal relay sensing the phase reversal is used
Review Questions
Explaie abnorivial conditions and possible failure of induction sotors
Wikich type of protection as selected for various abnormal conditions ?
Explain the overland protection using thermal relays used for induction motor.
‘How earth fault protection is provided to the induction motors ?
Explain single phasing én induction motors. How motor is protected from single phasing
‘How pha
faults protection is provided to the induction motors ?
Wat is phase reversal ? What is its effeet ? How it i prevented in induction motors ?
goa(6 - 10)Transformer Protection
7.1 Introduction
‘The transformers are static devices without having any rotating part and are
totally enclosed. Hence the chances of faults occurring on transformers are much rare
as compared to the faults occurring on generators. Similarly possibilities of running on
abnormal conditions are also less in transformers compared to the generators,
But though the fault possibility is rare, if fault occurs, the transformer must be
quickly disconnected from the system. The rare faults if not cleared quickly can get
developed into the major faults which may be very serious for the transformer. Hence
the protection must be provided to the transformers against possible faults,
‘The use of series fuses is very common in case of small distribution transformers
instead of circuit breakers. Hence it is not necessary to install any automatic protective
relaying equipments with the distribution transformers. But the power transformers
having large ratings always need some type of automatic protective relaying
equipments, to give protection against the possible faults.
7.2 Possible Transformer Faults
‘The generators are subjected to the number of faults and abnormal conditions but
the transformers are not. The various possible transformer faults are,
1. Overheating, 2. Winding faults
3. Open circuits 4. Through faults
5. Over fluxing
Let us discuss these faults.
7.2.1 Overheating
The overheating of the transformer is basically of sustained overloads and short
circuits. The permissible overload and the corresponding duration is dependent on the
type of transformer and class of insulation used for the transformer. Higher loads are
permissible for very short duration of time. The overloading which continues for
longer time is dangerous as it causes overheating of the transformer. Similarly the
failure of the cooling system, though rare, is another possible cause of overheating.
(7-4)Protection and Switchgear 7-2 Transformer Protection
Generally the thermal overload relays and temperature relays, sounding the alarm are
used to provide protection against overheating. Similarly temperature indicators are
also provided, On the transformers, when temperature exceeds the permissible limits,
the alarm sounds and the fans are started, The thermocouples or resistance
temperature indicators are also provided near the winding. These are connected in a
bridge circuit. When temperature exceeds the limiting safe value, the bridge balance
gets disturbed and alarm is sounded. If the corrective action is not taken within
certain period of time then the circuit breaker trips.
7.2.2 Winding Faults
The winding: faults are called intemal faults. These faults are,
i) Phase to phase faults
ii) Earth faults
) Intertum faults
The overheating or mechanical shocks cause to deteriorate the winding insulation.
If the winding insulation is weak, there is a possibility of short circuit between the
phases or between the phase and ground. Also the possibility of short circuit between
the adjacent turns of the same phase winding is also possible.
When such an internal fault occurs, the transformer must be quickly disconnected
from the system. If such a fault persists for longer time, there is possibility of oil fire.
The differential protection is very commonly used to provide protection against such
faults. But this protection is not economical for the transformers below 5 MVA for
which an over current protection used. For the high capacity transformers in
addition to main differential protection, the overcurrent protection is also provided as
a backup protection. For earth fault protection, the restricted earth fault protection
system, neutral current relays or leakage to frame protection system is used.
7.2.3 Open Circuits
‘The open circuit in one of the three phases is dangerous as it causes the
undesirable heating of the transformer. A separate relay protection is not provided for
the open circuits as open circuits are much harmless compared to other faults. In case
of such faults, the transformer can be manually disconnected from the system.
7.2.4 Through Faults
Through faults are the external faults which occur outside the protected zone.
Through faults are not detected by the differential protection. If the through faults
persists for long period of time, the transformer may get subjected to the thermal and
mechanical stresses which can damage the transformer. The overcurrent relays with
undervoltage blocking. zero sequence protection and negative sequence protection areProtection and Switchgear 723 Transformer Protection
used to give protection against through faults. The setting of the overcurrent
protection not only protects the transformer but also covers the station busbar and
portion of a transmission line, Such a protection acts as a backup protection for the
differential protection
7.2.5 Overfluxing
The flux density in the transformer core is proportional to the ratio of the voltage
to frequency i.e. V/E. The power transformers are designed to work with certain value
‘of flux density in the core, In the generator transformer unit, if full excitation is
applied before generator reaches its synchronous speed then due to high V/f the
averfluxing of core may result. Higher core flux means more core loss and overheating
‘of the core. The saturation of magnetic circuit is also the probable cause for the
coverfluxing operation. The V/f relay called volts/hertz relay is provided to give the
protection against overfluxing operation, This relay does not allow exciting current to
flow till the generator reaches to a synchronous speed and runs to produce voltage of
proper frequency. The overfluxing relays with enough time lag also can be provided.
Apart from these faults, some other faults like tap-changer faults, high voltage
surges due to lightning and switching, incipient faults ie. slow developing faults may
also occur in the transformers. The Buchholz relay is used for oil immersed
transformers to give the protection against incipient faults.
7.3 Percentage Differential Protection for Transformers:
The percentage differential protection or Merz-Price protection based on the
circulating current principle can also be used for the transformers. This system gj
protection against phase to phase faults and phase to ground faults to the power
transformers.
The principle of such a protection scheme is the comparison of the currents
entering and leaving the ends of a transformer. The vector difference of currents I = ly
passes through the operating coil while the average current (I, + I;)/2 passes through
the restraining coil, In normal conditions, the two currents at the two ends of the
transformer are equal and balance is maintained. So no current flows through the
operating coil of the relay and relay is inoperative. But when there is phase to phase
fault or phase to ground fault, this balance gets disturbed. The difference current
flows through the operating coil due to which relay operates, tripping the circuit
breaker,
Compared to the differential protection used in generators, there are certain
important points which must be taken care of while using such protection for the
power transformers. These points are,Protection and Switchgear Ted Transformer Protection
1. Ina power transformer, the voltage rating of the two windings is different. The
high voltage winding is low current winding while low voltage winding is
high current winding. Thus there always exists difference in current on the
primary and secondary sides of the power transformer. Hence if C-'s of same
ratio are used on two sides, then relay may get operated through there is no
fault existing:
To compensate for this difficulty, the current ratios of C.T.s on each side are
different. These ratios depend on the line currents of the power transformer
and the connection of C:T.s, Due to the different tums ratio, the currents fed
inte the pilot wires from each end are same under normal conditions so that
the relay remains inoperative. For example if K is the turns ratio of a power
transformer then the ratio of C.T.s on low voltage side is made K times greater
than that of C.T.s on high voltage side.
In case of power transformers, there is an inherent phase difference between
the voltages induced in high voltage winding and low voltage winding. Due to
this, there exists a phase difference between the line currents on primary and
secondary sides of a power transformer. This introduces the phase difference
between the C.T. secondary currents, on the two sides of a power transformer.
Though the turns ratio of C.T's are selected to compensate for tums ratio of
transformer, a differential current may result due to the phase difference
between the currents on two sides. Such a differential current may operate the
relay though there is no fault, Hence it is necessary to correct the phase
difference.
To compensate for this, the CT. connections should be such that the resultant
currents fed into the pilot wires from either sides are displaced in phase by an
angle equal to the phase shift between the primary and secondary currents. To
achieve this, secondaries of C.Ts on star connected side of a power
transformer are connected in delta while the secondaries of C.T's on delta
connected side of a power transformer are connected in star.
The Table 7.1 gives the way of connecting C.T. secondaries for the various types of
power transformer connections.
Power Transformer Connections
Table 7.1Protection and Switchgear 7-5 Transformer Protection
With such an arrangement, the phase displacement between the currents gets
compensated with the oppositely connected C.T. secondaries, Hence currents fed to
the pilot wires from both the sides are in phase under normal running conditions and
the relay is ensured to be inoperative.
3. The neutrals of C.T. star and power transformer stars are grounded.
4, Many transformers have tap changing arrangement due to which there is a
ty of flow of differential current. For this, the turns ratio of C.T's on
les of the power transformer are provided with tap for of C.T.s on both
sides of the power transformer are provided with tap for their adjustment.
For the sake of understanding, the connection of C.T. secondaries in delta for star
side of power transformer and the connection of C.T. secondaries in star for delta side
of power transformer is shown in the Fig. 7:1 (a) and (b).
ua Delta side of 5. 7. secomtariee
or sce wanstormer
a pews
a power
Franstormer
CT Pilot wires
Secondaries
icone
(a we
Fig. 7.4
7.3.1 Merz-Price Protection for Star-Delta Transformer
Let us study the Merz-Price protection for the star-delta power transformer. The
primary of the power transformer is star connected while the secondary is delta
connected, Hence to compensate for the phase difference, the C.T, secondaries on
primary side must be connected in delta while the C.T. secondaries on delta side must
be connected in star. The star point of the power transformer primary as well as the
star connected C.T. secondaries must be grounded.
‘The circuit diagram of the scheme is shown in the Fig. 7.2
‘The restraining coils are connected across the C.T. secondary windings while the
operating coils are connected between the tapping points on the restraining coils and
the star point of C-T. secondaries.Transformer Protection
Protection and Switchgear
Aep6s jeyussoy.g, ae
J9UUO}SURA JOMOd EYDP-46}S 205 UOHDB}ONd 92Nd-ZA0W Z'L “BLY
seyeog yn <2.
100 BuNmedg "90
boo Buwiensoy Oe
san
wa
a9
uo it
-
sauepucoes“ 1
peFeUUOD JIS
Jo 4,
epueces a soepucoes 4'9
ponoouon 8100 Ad papowe>
sauuso}suen oMod eyop- sg pavawer seis,
90,Protect
n and Switchgear 7-7 Transformer Protection
With the proper selection of tums ratio of CTs the coils are under balanced
condition during normal operating conditions. The C.T. secondaries carry equal
currents which are in phase under normal conditions. So no current flows through the
relay and the relay is inoperative.
With an internal fault in power transformer windings, the balance in the C.T.s get
disturbed. The operating coils of differential relay carey currents proportional to the
difference of current between the two sides of a power transformer. This causes the
relay operation which trips the main circuit breakers on both the sides of the power
transformer.
The basic requirements of the differential relay are,
1. The differential relay must not operate on load or external faults.
2. It must operate on severe internal faults.
The relay satisfying these requirements is used in Merz-Price protection.
It is important to note that this scheme gives protection against short circuit faults
between the tums ie. interturn faults also. This is because when there is an interturn
fault, the turns ratio of power transformer gets affected. Due to this the currents on
both sides of the power transformer become unbalanced, This causes an enough
differential current which flows through the relay and the relay operates.
7.3.2 Merz-Price Protection for Star-Star Transformer
The Fig. 7.3 (Gee Fig, on next page) shows the Merz-Price protection system for the
star-star power transformer, Both primary and secondary of the power transformer are
connected in star and hence C.T. secondaries on both the sides are connected in delta
to compensate for the phase displacement.
The star points of both the windings of the power transformer are grounded, The
restraining coils are connected in the CT, secondaries. The operating coils are
connected between the tapings on the restraining coil and the ground. The operation
of the scheme remains same for any type of power transformer as discussed for
star-delta power transformer7-8 Transformer Protection
Protection and Switchgear
J9UUOJSUEN JOMOd 1035-1895 40) UORDe}OId OOUd-ZIOW E41 “Bly
punaig
al
soyeo.n yang "2°
109 Buen "10
oo Buntensoy Ou
Ix — a
apes jequasoy.g.
| —
Lo
copie 9 i
wend gs sweoubne 13
lent mos ad
sounojste9 sOM0d 1855-2015 pejpeuoo sess
feaProtection and Switchgear 7-9 Transformer Protection
im Example 7.1: 4 three phase power transformer having a tine voltage ratio of 400 V
to 33 KV is connected im star-deita, Tie C.T.s on 400 V sidle have current ratio as
1000/5. What must be the C.T. ratio on 33 kV side
Assume current on 400 V side of transformer to be 1000 A.
Star delta
A transformer
cr.
secondaries | C
I»
C.T. secondaries
Fig. 7.4
Solution : The arrangement is shown in the Fig. 74
Qn the primary side, which is 400 V side of transformer the current is 1000 A.
Hence C.Ls primary will carry current of 1900 A,
The CT, ratio is 1000/5 on the primary side hence the current in C.T.
Secondaries which is phase current of delta connected C.T.s is,
5
100% 7555
Ip 5A
This is shown in the Fig. 74
= 31, =5¥3 AProtection and Switchgear 7-40 Transformer Protection
This is because the C.T. secondaries are connected in delta
‘The same current flows through the star connected C.T. secondaries. Hence each
secondary of C.T. on the secondary side of transformer carries a current of 5¥3 A.
For the power transformer the apparent power on both sides must be same.
Primary apparent power
Valu = Y¥3Ve te
¥3x400%1000 = 3x 33000xI,)
4001000 _
© 330007
Secondary apparent power
u
I
2.12 A
Thus each primary of C.T.s connected in star carries a current of 12.12 A while
each secondary of C.T's connected in star carries a current of 5V3 A.
Hence the C.T. ratio on 33 KV side is,
Primary current _ 12.12
CT. ratio = g—— = 14
rate ~ Secondary current 5/3
‘This is the required C.T. ratio on 33 kV side.
7.4 Problems Encountered in Differential Protection
‘The problems encountered in the simple differential protection are,
1, Unmatched characteristics of C.T.s : Though the saturation is avoided, there
exists difference in the C-T. characteristics due to ratio error at high values of
short circuit currents. This causes an appreciable difference in the secondary
currents Which can operate the relay, So the relay operates for through external
faults.
This difficulty is overcome by using percentage differential relay, In this relay,
the difference in current due to ratio error exists and flows through relay coil.
But at the same time the average current (I, + 1)/2) flows through the
restraining coil which produces enough restraining torque. Hence relay
becomes inoperative for the through faults.
2. Ratio change due to tap change : To alter the voltage and current ratios
between high voltage and low voltage sides of a power transformer, a tap:
changing equipment is used. This is an important feature of a power
transformer. This equipment effectively alters the turns ratio. This causes
unbalance on both sides. To compensate for this effect, the tappings can be
provided on C.T:s also which are to be varied similar to the main power
transformer. But this method is net practicableProtection and Switchgear 744 Transformer Protection
The percentage differential relays ensure the stability with respect to the
amount of unbalanee occurring at the extremities of the tap change range.
3, Difference in lengths of pilot wires ; Due to the difference in lengths of the
pilot wires on both sides, the unbalance condition may result, The difficulty is
overcome by connecting the adjustable resistors in pilot wires on both sides,
These are called balancing resistors. With the help of these resistors
equipotential points on the pilot wires can be adjusted. In percentage
differential relays the taps are provided on the operating. coil and restraining,
coil to achieve balance.
4. Magnetizing current inrush : When the transformer is energized, the condition
initially is of zero induced emf. and it is similar to the switching of an
inductive circuit. Due to this the transient inrush of magnetising current flows
in to the transformer. This current is called magnetizing current inrush. This
current may be as great as 10 times the full load current of the transformer.
This decays very slowly and is bound to operate differential protection of the
transformer falsely.
The factors whieh affect the magnitude and direction of the magnetizing current
inrush are,
a, Size of the transformer
b. Size of the power system
¢, Type of magnetic material used for the core.
d, The amount of residual flux existing before energizing the transformer,
e. The method by which transformer is energized.
If the transformer is energized when the voltage wave is passing through zero, the
magnetizing current inrush is maximum. At this instant, the current and flux should
be maximum in highly inductive cireuit. And in a half wave flux reversal must take
place to attain maximum value in the other half cycles. If the residual flux exists, the
required flux may be in same or opposite direction. Due to this magnetizing current
inrush is less or more. If it is more, it is responsible to saturate the core which further
increases its component
This current decays rapidly for first few cycles and then decays slowly. The time
constant L/R of the circuit is variable as inductance of circuit varies due to the change
in permeability of the core. The losses in the circuit damp the inrush currents,
Depending on the size of the transformer, the time constant of inrush current varies
from 0,2 sec to 1 sec.
The waveforms of magnetizing inrush current in three phases is shown in the
Fig. 75.Protection and Switchgear 7-12 ‘Transformer Protection
Phase R
Phase Y
Phase 8
Fig. 7.5 Typical magnotizing Inrush current waveforms
‘There are number of ways ensuring immunity from the operation by magnetizing
surges. Firstly the relay may be given a setting higher than maximum inrush current.
Secondly the time setting may be made long enough for the magnetizing current to
fall to a value below the primary operating current before the relay operates. But these
simple remedies are inconsistent with high speed and low primary operating current.
In the latest method, the harmonic content of the magnetizing current flowing in
the operating circuit is filtered out and passed through a restraining coil. This is called
harmonic current restraint.
7.4.1 Harmonic Restraint and Harmonic Blocking
The high initial inrush of magnetizing currents consist of a high component of
even and odd harmonics.
Table 7.2 gives the typical values of harmonic contents in a magnetizing current.
Order of harmonic content in magnetizing Amplitude as a % of fundamental
current
a 63.0
EM 268
e 5AProtection and Switchgear 7-13 Transformer Protection
= a4
e a7
-
Table 7.2
carries the fundamental component of the inrush current only.
passed through the restraining
The operating «
The harmonic contents and fundamental together is
coil.
Thus more the harmonic contents in the inrush current, more is the restraining
torque and the relay does not operate. So use of percentage differential protection
rather than simple differential protection is preferred, The circuit used to compensate
the effect of magnetizing current using harmonic restraint method is shown in the
Fig. 7.6.
Restraining
coils
Fig. 7.6 Magnetizing current compensation
‘The filter F, is designed to pass the fundamental 50 Hz component which excites
the operating coil Ry. The magnetizing current has large third harmonic component.
There is an additional restraining coil R,. The filter F; is designed to pass the third
harmonic component which energizes the additional restraining coil R,. The current
passing through normal restraining coil and current passing through additional
restraining coil R, produce sufficient restraining torque. This compensates for the
differential current resulting due to the flow of magnetizing current
The separate blocking relay in series with the differential relay is used. The
operation of this relay is based on harmonic component of inrush current. This relay
consists of 100 Hz blocking filter in operating coil while 50 Hz filter in restraining coil.
At the time of inrush current, second harmonic component is maximum and thus
blocking relay is blocked with its contacts remain open.Protection and Switchgear 7-14 Transformer Protection
In short circuit case, the harmonic component is negligible and 50 Hz component
is dominant. Hence the blocking relay operates to close its contact. This principle is
called harmonic blocking.
7.5 Frame Leakage Protection
This protection is nothing but the method of providing earth fault protection to the
transformer. This protection can be provided to the metal clad switchgear.
The arrangement is shown in the Fig, 7.7.
units of metal clad switchgear
1 Earth fault current
Earthing.+ Earth fouk
bus
ct: a Ea
Concrete
foundation
= Eathing
Fig. 7.7 Frame leakage protection
The metal clad switchgear is lightly insulated from the earth.
‘The frame of the switchgear ie. enclosure is grounded. This is done through a
primary of current transformer in between,
The concrete foundation of switchgear and the other equipments are lightly
insulated from the ground. The resistance of these equipments with earth is about
12 ohms.
‘When there is an earth fault, then fault current leaks from the frame and passes
through the earth connection provided. Thus the primary of C.T. senses the current
due to which current passes through the sensitive earth fault relay, This operates the
relay.
Such a protection is provided only for small transformers. For the large
transformers, the differential protection is enough to sense and operate for the earth
faults.Protection and Switchgear 7-15 ‘Transformer Protection
7.6 Buchholz Relay
‘The Buchholz relay is a gas operated relay used for the protection of oil immersed
transformers against all the types of internal faults. It is named after its inventor,
Buchholz. The slow developing faults called incipient faults in the transformer tank
below oil level operate Buchholz relay which gives an alarm. If the faults are severe
disconnects the transformer from the supply.
It uses the principle that due to the faults, oil in the tank decomposes, generating
the gases. The 70% component of such gases is hydrogen which is light and hence
rises upwards towards conservator through the pipe. Buchholz relay is connected in.
the pipe, as shown in the Fig, 7.8. Due to the gas collected in the upper portion of the
Buchholz relay, the relay operates and gives an alarm
Fig. 7.8 Basic arrangement of Buchholz relay
‘The constructional features of Buchholz relay are shown in the Fig. 7.9.
(See Fig. 7:9 on next page.)
Under normal conditions, the Buchh: relay is full of oil. It consists of a cast
housing containing a hinged hollow float. A mercury switch is attached to a float. The
float being rotated in the upper part of the housing. Another hinged flap vaive is
located in the lower part which is directly in the path of the oil between tank and the
conservator. Another mercury switch is attached to a flap valve. The float closes the
alarm circuit while the lower flap valve closes the trip circuit in case of internal fault.Protection and Switchgear 716 Transformer Protection
2 Test cock to collect gas sample
te
alarm Gas accumulates
Float titing with reduced oi level
Mercury on
sswiten
Hinge To trip circuit
Hinge —
Mareury swatch
(==> To conservator
top of
transformer
‘main tank
Flap
valve
Fig. 7.9 Construction of Buchholz relay
7.6.1 Operation
There are many types of internal faults such as insulation fault, core heating, bad
switch contacts, faulty joints ete. which can occur, When the fault occurs the
decomposition of oil in the main tank starts due to which the gases are generated. As
mentioned earlier, major component of such gases is hydrogen, The hydrogen tries to
rise up towards conservator but in its path it gets accumulated in the upper part of
the Buchholz relay. Through passage of the gas is prevented by the flap valve.
When gas gets accumulated in the upper part of housing, The oil level inside the
housing falls. Due to which the hollow float tilts and close the contacts of the mercury
switch attached to it. This completes the alarm circuit to sound an alarm. Due to this
operator knows that there is some incipient fault in the transformer. The transformer
‘onnected and the gas sample is tested. The testing results give the indication,
what type of fault is started developing in the transformer. Hence transformer can be
disconnected before fault grows into a serious one. The alarm circuit does not
immediately disconnects the transformer but gives only indication to the operator. This
is because some times bubbles in the oil circulating system may operate the alarm
circuit through actually there is no fault,Protection and Switchgear 7-17 Transformer Protection
However if a serious fault such as internal short circuit between phases, earth fault
inside the tank ete. occurs then the considerable amount of gas gets generated. Thus
due to fast reduce level of oil, the pressure in the tank increases. Due to this the oil
rushes towards the conservator, While doing so it passes though the relay where flap
valve is present. The flap valve gets deflected due to the rushing oil. Due to this the
mercury switch contacts get closed. This energizes the trip circuit which opens the
cireuit breaker. Thus transformer is totally disconnected from the supply.
The connecting pipe between the tank and the conservator should be as straight as
possible and should slope upwards conservator at a small angle from the horizontal
This angle should be between 10 to 11°
For the economic considerations, Buchholz relays are not provided for the
transformers having rating below 500 kVA.
7.6.2 Advantages
The various advantages of the Buchholz relay are,
1. Normally a protective relay does not indicate the appearance of the fault. It
operates when fault occurs, But Buchholz relay gives an indication of the fault
at very early stage, by anticipating the fault and operating the alarm circuit
Thus the transformer can be taken out of service before any type of serious
damage occurs.
2, It is the simplest protection in case of transformers.
7.6.3 Limitations.
The various limitations of the Buchholz relay are,
1. Can be used only for oil immersed transformers having conservator tanks.
2. Only faults below oil level are detected,
3, Setting of the mercury switches can not be kept too sensitive otherwise the
relay can operate due to bubbles, vibration, earthquakes mechanical shocks ete.
4. The relay is slow to operate having minimum operating time of 0.1 seconds
and average time of 0.2 seconds.
7.6.4 Applications
The following types of transformer faults can be protected by the Buchholz relay
and are indicated by alarm :
Local overheating
Entrance of air bubbles in oil
3. Core bol
insulation failureProtection and Switchgear 7
Transformer Protection
|. Short circuited laminations
. Loss of oil and reduction in oil level due to leakage
4
5
6. Bad and loose electrical contacts
?. Short circuit between phases
8. Winding short circuit
9. Bushing puncture
10. Winding earth faults
Examples with Solutions
‘imp Example 7.2: A 12 kV/132 kV power transformer is connected in delta-star. The
CTs on the law voltage side have turns ratio of 600/5. Find the suitable turns ratio
{for the C.T.s on high valtage side
Solution : The connections are shown in the Fig. 7.10.
°
Fig. 7.10
Let the current on the primary i.e. low voltage side of power transformer be 600 A.
This current will flow through each line on primary of transformer.Protection and Switchgear TH49 Transformer Protection
Hence current in each secondary of star connected C.T. on primary is the phase
current Ip as shown in the Fig. 7.10,
5
Ip = 6x2 =5A
ip = 600%
The same in line current |, which is line current for the C.T-s connected in delta
‘on secondary of transformer.
‘Hence current in each secondary of C.T. which is phase current of C.T. i
the line value.
= % A for. T. secondary connected in delta
‘Now apparent power on both sides is same,
V3 Vink = V3 Viaha
V3x11000%600 = 3 «1320001, >
11000% 600
ha = “33000
= SOA
This is the current flowing through each primary of delta connected C.T.
. C.T, ratio on high voltage side =
6/43)
= 17.32:1
sm Example 7.3: A 3 phase, 200 kVA, 11 KVAOO V transformer is connected in
delta-siar. The C.P's on low voltage side have turns ratio of 500/5. Determine the CT.
ratio on high voltage side. Also oblain the circulating current when the fauelt of 750 A
of following types occur on the tow voltage side :
i) Earth fault within the protective zone
ii) Earth fault outside the protective zone
iti) Phase fo phase fault within the protective zone
iv) Phase to phase finalt outside the pratective zone
Assume balanced voltage.
Solution : The connections are shown in the Fig. 7.11,
On primary which is delta connected, C.T.s are connected in star while
On secondary which is star connected, C:T.s are connected in delta.
Let current on low voltage side be 500 A.
Now Iz = 500AProtection and Switchgear 7 +20 Transformer Protection
Star.
cr HV. Side Oetta- LV. Side
secondaries er
2 -= se secondaries
R ane R
Yo Y
aot} Op
eh
bie
. Fig. 7.44
CT. ratio 500/5
Current through primary of C.T. on low voltage side
= 12 = 500A
Current through each secondary of delta connected C-T.s
5
= 500x2. = 5 A
0
Line current through pilot wires
Bly
= N5A
Same is the current through each secondary of star connected C.T. on high voltage
side.
= 5V3.A on hy. side C.T. secondaries
Apparent power on both sides of transformers is same.
Vali = Y3Veo le
3x11000«1,, = V3*400%500Protection and Switchgear 7-24 ‘Transformer Protection
400500
T1000
= 11GB A
hue
This is current through each primary of C.T.s connected in star.
Current ratio of C.T.s on high voltage side
18.18
WS
= 2099-1
(i) Consider the earth fault within the protective zone as shown in the Fig. 7.12.
(See Fig. 7.12 on next page.)
Now hz = 750A
Equating apparent power,
V3 Vila = V3 Vio he
f3x11000x1,, = v3 «400x750
2727 A
la
This is the line current on hwv. side under fault condition.
The C:T. ratio is 2.099 : 1. Hence corresponding current through C.T. secondary on
1
hy. side is, = WI xs = 1299 A
So 12.99 A current will flow through the relay and relay will operate
Consider the earth fault outside the protective zone as shown in the Fig. 7.13.
The line current on secondary is 750 A,
5
750% 5
75 A
75x35 = 12.99 A as delta connected
Secondary CT. current
"
"
Current in pilot wires‘Transformer Protection
Protection and Switchgear
zee Bia
syooseoy C3) G)
©
vera
vorProtection and Switchgear 7-23 Transformer Protection
Fig. 7.43
‘The currents are shown in the Fig. 7.13.
So on both sides the current is balanced hence no current will flow through the
relay and relay will not operate.
iii) Phase to phase fault in the protected zone on low voltage side. This is shown
in the Fig. 7.14.Protection and Switchgear 7-24 Transformer Protection
Fig. 7.14
Due to such fault current will flow in two phases of low voltage winding but in
all three phases in high voltage winding as shown in the Fig, 7.14, This current on
high voltage side will flow through the relay and relay will operateProtection and Switchgear. 7-28 Transformer Protection
i
y be
+t
Fig. 7.15
iv) Consider phase to phase fault outside the protected zone as shown in the
Fig. 7.15. The various currents and corresponding distribution is also shown in
the Fig. 7.15.
As the currents on both sides are balanced, no current flows through the relay
hence relay will not operate.
imi Example 7.4: A 3 phase transformer rated for 33 KV/6.6 KV is connected starjdelta
and the protecting current transformers on the low voltage side hive a ratio of 400/5.
Determine the ratio of the current transformers on H.V. side. Draw the connection
diagram showing how the relay operates under fault conditions,Protection and Switchgear 7-26 Transformer Protection
Solution : C:T.s on delta connected side are star connected. Hence the secondary
phase currents are equal to curtents in pilot wires.
Cs on star connected side are delta connected hence current in secondary is
‘equal to current in pilot wires divided by V3.
Assume 400 A is flowing in the lines on low voltage side i.e. 6.6 KV side.
Now primary apparent power = secondary apparent power
VIVu la = V3 Va he
Vi «33% 10° x ky) = V3 x 66 x 10° x 400
hy = BOA
This is primary current of C.T. on high voltage side.
On the delta side of transformers the C.T. secondaries are star connected. Their
secondary current is 5 A. Hence current fed in pilot wires from low voltage side is 5
A. Same current is fed from C.T, connections on high voltage side which are delta
connected
Hence secondary current of C.Ts on high voltage side is 5/3 A.
Thus C.T, ratio on HT. side is 80; 5/J3 ie. 27.7121
The connection diagram is shown in the Fig. 7.16.
cr.
Secondaries
in dete
= Secandari
OT
Restraining colls
Fig. 7.16Protection and Switchgear 7-27 Transformer Protection
mm Example 7.5: A S-phase transformer having line voltage ratio of 440 VAL kV is
connected in star/Delia. The protection transformer on the LY side have a current ratio
of 500/S. What must be the ratio of the protection transformer connected on HV side ?
(AU-April-2005)
Solution : The arrangement is shown in the Fig. 7.17
‘Star detta
A {ransformer
on.
secondaries i" i
indeita
nTA
ls
C.T secondaries
Fig. 7.47
On primary side which is 440 V side, let the current be 500 A.
Thus C-T.s will carry the current of 500 A.
The C.T. ratio is 500/5 A hence secondary phase current of C.T-s on primary side
is,
5
Ip = g5q*500= 5A
WB 1,= SBA »» Delta connected C.T.sProtection and Switchgear 7-28 Tran
mer Protection
The same current flows through the star connected C.T. secondaries. Hence each
secondary of C.T. on the secondary side of transformer carries a current of 53 A.
The apparent power on both sides must be same
V3Vuhy = ¥3Va le
V3» 440% 500 = ¥3%11« 109 «1iy
20.A
Ta
Thus each primary of CT's connected in star on H.V. side carries a current of 20
A while each secondary carries current of 5V3 A.
Hence the C.T. ratio on 11 kV side is,
Primary current _ 20
Secondary current 5/3
2.309: 1 .» Required C.T, ratio on HLV, side
um Example 7.6: A 3 phase 500 KVA, 11 kV/04 kV transformer is connected in
Deita/star. The protection transformer on the LV side have turns ratio of 500/5. What
will be the C.T. ratio on the HV side of the transformer ? (AU-Dee.-2005)
Solution : ‘The connections are shown in the Fig. 7.18,
‘Siar
at H.V, Side Delta Lv, Side
secondaries CT
== ser secondaries
R
Oy
8 an |__o,
te =
Fig. 7.48Protection and Switchgear 7-30 Transformer Protection
State the problems encountered im a simple differential protection of transformers.
Write a notes om
i) Magnetic current in rust
li) Harmonie restraint and harmonic Blocking
ti) Frame leakage pratection
Drow ond explain the constriction and working of Buchiots relay. Against which faults Buchholz
‘relay gives the protection ? State its advantages and disaduumatages,
Describe with the kelp of a neat diagram the connections of differential protection of a transformer.
A Splinse 33/6.6 kV starftctia connected transformer is protected by differential system. The C.T.'s
on ET side hawe ratio of 300/5. Show that the C.T.s om HT side will have at matio 60 : 5/3.
Al 3. phase transformer of 220/91,000 tine volts is connected in starficlta. The protective
transformers on 220 V side have a current ratio of 600/S. What should be C.T. ratio om 11,000 V
side? (Ans. : 1.385: 1)
A S-phase, 220/11000 V transformer is connected in star-delta and the protective transformers on
i 5 i
the 220 V sides humor a current ratio of 600Fx, What must be the ratio of the CTs om the
9 of $001 Fe. of
114000 V side anid how shall they be connected ? (Ans. : 12:5)
A tree phase 66 RV/IL RV power transformer is connected in starfitelta, The transformer is
protected by Merz-Price circulating current system. Protecting current transformers on the low
voltage side have a ratio of 250/5, Find the ratio.of the current transformers on higit voltage side.
(Ans. : 141: 1)
. A three phase power transformer has a voltage ratio of 33/6.6 KV and is star delta connected. The
protective C.T.3 on the 6.6 KV side have a current ratio of 100, What must be the ratio of
protective CT's on the 33 kV side ? fans, : 35:1)
gooCarrier Aided Protection
and Static Relays
8.1 Block Schematic of Carrier Aided Protection
Carrier aided protection is used for the protection of transmission lines. The carrier
currents with high frequency range are transmitted and received with the help of
transmission lines for protection, The schematic representation of carrier current
protection is shown in the Fig. 8.1.
Bus bar
k CB.
Relay]
nit
Canter current Carver current
transmit, equipment
Receiver, Power
amplifier. Line tuning
uni, Master oscillator
Fig. 8.41 Schematic: of carrier current protection
The identical carrier equipments which include transmitter, receiver, line tuning
unit, master oscillator, power amplifier etc. are provided at each end of the
transmission line, The description of various blocks in the schematic representation is
given below.
1. Coupling capacitor
The various carrier equipments described above are connected to the transmission
line with the help of coupling capacitor. The capacitive reactance is given by aa
Hence for carrier frequency it offers less reactance while high reactance for normal
(6-1)Carrier Aided Protection
Protection and Switchgear B-2 and Static Relays
power frequency. It can be seen that the carrier current signals are allowed to pass
through this capacitor and enter in carrier equipment while power frequency currents
are blocked. The inductance connected in. series with the coupling capacitor reduces
the impedance to further low value. Thus a condition of resonance is achieved at
carrier frequency.
2. Line Trap Unit
This unit is between the busbar and the connection of coupling capacitor to the
line. It consists of parallel combination of inductance (L) and. capacitance (C) acting as
tuned circuit. This circuit offers low impedance to power frequency currents while
offers very high impedance to carrier frequency currents which prevents the high
frequeney carrier to enter in the neighbouring line and carrier currents flow only in.
the protected line.
3. Protection and Earthing of Coupling Equipment
Due to lightning, switching transients or faults, overvoltage surges are produced
on the transmission lines. These overvoltages may produce stress on coupling
equipment and line trap unit. For protection purpose, the nonlinear resistors are
connected across line trap unit in series with a protective gap. These resistors with
protective gap is connected across inductor in the coupling unit. The length of the gap
is adjusted in such a way that, spark over takes place at a set value of avervoltage.
The earth rod is used is for earthing of coupling unit so as to get low resistance earth
path. The relay room consists of carrier equipment panel which is connected to station
earthing system
4. Electronic Equipments
Following electronic equipments are generally used at each end of the line,
a) Transmitter unit
b) Receiver unit
©) Relay unit
a) Transmitter Unit :
The general representation of power line carrier equipments is shown in the
Fig, B.2.
Normally the frequencies with range from 50 to 500 kHz are employed in various
frequency bands with each has specific bandwidth. The oscillator is used for the
generation of carrier frequency and it is tuned for a particular frequency which is
chosen for particular application. Sometimes a crystal oscillator may also be used
which gives particular bandwidth after selecting particular type of crystal. Voltage
stabilizers are employed for maintaining the oscillator output voltage constant. The
losses in the transmission path between transmitter and receiver at remote end of lineCarrier Aided Protection
Protection and Switchgear 8-3 and Static Relays
pa |. Transmission
IT, - line
OO Coupling
Line capacitor
trap unit
Bus
bar
4 Line tuning unit
I
It Power amplifier
cH Master oscilator
Fig. 8.2 Representation of carrier current protection unit
are overcome with the help of amplifier which increases the level of the signal to be
transmitted,
The attenuation in signal is due to losses in coupling equipment which are
constant for given frequency range. Depending on length of line, frequency whether
conditions and the size and type of line, the line losses vary
If weather is fairly reasonable then the attenuation is of the order of 0.1 dB/kHz at
80 kHz which increases 0.2 dB/km at 380 kHz. If we consider 250 km line then the
output of power amplifier is about 20 W. For a particular bandwidth the amplifier
should give maximum power. Depending on the type of protection required, various
methods are adopted for the control of transmitter. The interconnection between
oscillator and amplifier is done through control circuit. The block diagram
representation of transmitting unit is shown in the Fig. 83 (a).
Form
relay
unit
Fig, 8.3 (a) Transmitting unitCarrier Aided Protection
Protection and Switchgear Bea id Static Relays
b) Receiving Unit :
The block schematic of receiving unit is shown in the Fig. 8.3 (b).
From
i, oat wee | —-[_ Sar
“Amplifier
Fig. 8.3 (b) Receiving unit
The signal is reduced to a safe value with the help of attenuator. The undesired
signals which are signals from subsequent sections or spurious signals are prevented
by using band pass filter. The matching element matches the impedance of the
transmission line and receiving section. The undesired signals are generated either by
short circuits or radio interferences, The malfunctioning of this unit is avoided due to
the noise signals by using the set value above 2 milliwatts which is above noise level.
If the carrier signals have power level of 20 W and receiver unit is set at higher level
of 5 milliwatts then the operation is unaffected by spurious signals. For avoiding the
overloading, the signals should be attenuated before applying it to the amplifier
detector.
© Frequency Spacing : The subsequent line sections use various frequencies. The
carrier signals are prevented from entering into next section by wave traps. The filters
from receiving unit filters other frequencies. The frequency bands of various sections
are properly co-ordinated.
d) High Frequency Signal Modulation
For modulation of power frequency signals, the modulator is used. The signal after
modulation is passed to the amplifier and then transmitted through coupling unit.
From the half cycle line currents, the required blocks of carrier signals are generated
with the help of oscillator. The level of line current at which oscillator generates these
carrier blocks should be theoretically coristant but practically there is critical minimum
current. The modulation of line current into high frequency carriers is shown in the
Fig, 84.Carrier Aided Protection
Protection and Switchgear 6-5 and Static Relays
High frequency
carrier blocks
Fig. 8.4 Modulation of line current
8.2 Phase Comparison Method of Carrier Current Protection
‘There are various methods of carrier current protection. Some of them are as given
below :
1. Directional comparison method
2. Phase comparison method
‘The block diagram of the phase comparison method is shown in the Fig. 85.
Fig. 8.5 Block diagram of phase comparison method
In this method, the phase relation between the current entering in the protected
zone and current leaving the protected zone is compared without comparison of
magnitudes of currents, It does not provide back up protection which is to be
additionally provided but it acts as main protection.Carrier Aided Protection
Protection and Switchgear 8-6
In this method the signals are sent from each end of the line while they are
received at the other end. The signals are obtained from C.T. secondaries and are
related to the current flow in the main line.
In the absence of any fault on the line, the signal is sent for alternate half cycles
from each end resulting in continuous signal on the line. For external fault the same
condition holds good. If there is an internal fault, the current in one of the lines
reverses in phase and remains below fault detector setting resulting in sending the
carrier only for half the time. The relay is arranged to sense the absence of signal in
the line, When the phase angle between the two signals reaches to a certain set value,
the tripping occurs.
For internal fault condition, the transmitted signals and received signals are almost
in phase with each other. The comparator compares these signals. For alternate half
cycles, the signal is absent so the comparator gives output which operates to trip
relay. Various signals in primary circuit, secondary circuit transmitter, receiver
comparator during external fault are shown in the Fig. 8.6.
End 1 End 2
Primary current
‘Secondary signal
‘Transmitted signal
:
Signal fed to recaiver
:
tn err
Fig. 8.6 (a) External faultCarrier Aided Protection
Protection and Switchgear 8-9 and Static Relays
8.5 Basic Elements of a Static Relay
The Fig. 8.7 shows the block diagram of a static relay indicating its basic elements.
Su
a, eee] emer
Relaying amplifier
Rela
Teor Gone Tamaoraa
Fig. 8.7 Block diagram of a static relay
8.5.1 Input Element
The relaying quantity can be the output of C.T. or P.T. or it may be the output of
a transducer or it may be combination of various signals. Thus an electronic circuit
such as rectifier is required as an input element to get the input signal in a convenient
form before applying it to a measuring element. Some mixing circuits such as op-amp
adder may also be required as an input element.
8.5.2 Measuring Element
This is the heart of the static relay. It compares the output of an input element
with a set value and decides the signal to be applied to the output element which
ultimately drives the tripping circuit, Thus measuring element is a deciding signal
generator:
Measuring element can be classified as,
1. Single input device
2. Two input device
3. Multi-input device
The single input devices, depending on the protection and control schemes are
further classified as,
a. Noncritical Repeat Function (All or Nothing Relay) :
As the name suggests, these
devices are completely unenergized
Instantaneous cue, of energized much higher than the
noneritical (contracts} marginal condition required, to.
produce very fast response. It can be
represented as shown in the Fig. 88.
Fig. 8.8 Noncritical repeat function The input Ris aither nero tooCarrier Aided Protection
Protection and Switchgear 8-10 and Static Relays
higher than the marginal operating level. Such devices are instantaneous with
response time less than 20 ms, The switching power gain associated with them is
generally 10°. Such devices have multiple output contacts
The main funetions of such devices in the protection are,
1, To produce final tripping signal to the circuit breaker.
2. To produce signals to perform supplementary functions such as alarming,
intertripping, ete
3. To act as intermediate switching stages in a complex protection scheme.
b. Critical Measuring Function :
This device is a sort of on-off controller. It activates when the input signal reaches
to some critical level decided by the protection scheme. Such a device is shown in the
Fig. 89.
Input Instantaneous
noncritical
Fig. 8.9 Instantaneous critical function
Thus when input R is greater than some critical value P, it operates, While for
reset, input R must be less than kP (k $1).
It has only one output and switching gain need not be high. The output of such
device then can be connected to instantaneous noneritical to obtain multiple outputs.
The various requirements of critical function devices are,
1. High accuracy,
2. Long term consistency:
3. Fast and reliable operation.
4. High controllable reset ratio.
¢. Definite or Fixed Time Function :
This is nothing but a delay function
1 element. It produces a define time delay
between its input and the output, The delay
a Sori «May ‘be provided between the application of
R input and activation of output or between
removal of input and resetting of output. It is
_Fig. 8.10 Definite time function shown in the Fig. 8.10.Carrier Aided Protection
Protection and Switchgear a-11 and Static Relays
The input is noncritical type ie. either zero or too high than the marginal
requirement, Practically charging time of a eapacitor is controlled to obtain fixed time
delay
d, Input Dependent Time Function :
This function depends on the input characteristics and decides the time
accordingly
The common form of input dependent time function characteristics is,
t = £(R") where R = input
and n
negative
The function and its characteristics are shown in the Fig. 8.11.
t
tnput Input
dependent
‘ime function
Fig. 8.11 Input dependent time function
As n is negative, as the input increases the operating time decreases. So operating
time is inversely proportional to some power of the input. The examples of such
relays are inverse definite minimum time lag overcurrent and earth fault relays
The two input devices are ver
while multiple input devices are extension of two input devices to extend the range of
characteristics.
common such as comparators, level detectors ete
8.5.3 Output Element
‘The signals obtained from the measuring element are required to be amplified
before applying to the tripping circuit. Thus output element is an amplifier. Sometimes
this element not only amplifies the signals but multiplies them or combines them with
other signals to delay them.
8.5.4 Feed Element
The measuring element uses electronic circuits consisting transistors, diodes ete.
The output element uses transistor as an amplifier, All these components, circuits
alongwith the tripping circuit require d.c. supply for the proper functioning. The feed
element provides the d.c. voltage required by the various elements.Carrier Aided Protection
Protection and Switchgear 8-12 and Static Relays
8.6 Comparison of Static and Electromagnetic Relays.
The conventional electromagnetic relays use the moving parts such as an armature,
ise etc. Thus they are bulky in size. These relays are robust and highly reliable. These
are subjected to differential forces under fault conditions and hence required to have
delicate setting of small contact gaps, special bearing arrangements, clutch assemblies
etc. Thus there are lot of manufacturing difficulties and problems related to
mechanical stability associated with electromagnetic relays. The current and potential
transformers are subjected to high burdens in case of electromagnetic relays.
The static relays are commonly using the transistor circuits and called transistor relays.
‘Thisis because transistor can be used as an amplifying device as well as a switching deviee.
Hence any functional characteristics as per the requirement can be obtained by the static
relays. The transistor circuits can perform functions like summation, integration, comparison.
etc.
8.6.1. Advantages of Static Relays
The various advantages of static relays are,
1, The moving parts are absent. The moving parts are present only in the actual
tripping circuit and not in the contro! circuit.
2. The burden on current transformers gets considerably reduced thus smaller
CTs can be used
3, The power consumption is very low as most of the circuits are electronic,
4, The response is very quick.
5
. As moving parts are absent, the minimum maintenance is required, No bearing
friction or contact troubles exist.
6. The resetting time can be reduced and overshoots can be reduced due to
absence of mechanical inertia and thermal storage.
7. The sensitivity is high as signal amplification can be achieved very easily.
The use of printed circuits eliminates the
possible.
9. As electronic circuits can be used to perform number of functions, the wide
range of operating characteristics can be obtained, which almost approach to
ideal requirements.
ing errors and mass production is
10, The low energy levels required in the measuring circuits make the relays
smaller and compact in size
11, The testing and servicing is simplified.Carrier Aided Protection
Protection and Switchgear 8-13 and Static Relays
8.6.2 Limitations of Static Relays.
Inspite of various advantages, the static relays suffer from the following
limitations,
1. The characteristics of electronic components stich as transistors, diodes etc. are
temperature dependent. Hence relay characteristics vary with temperature and
ageing.
2. The reliability is unpredictable as it depends on a large number of small
components and their electrical connections.
3. These relays have low short time overload capacity compared to
electromagnetic relays.
4. Additional dic. supply is required for various transistor circuits
5. Susceptable to the voltage fluctuations and transients.
6. Less robust compared to electromagnetic relays.
Now a days effect of temperature on the semiconductor devices can be
compensated by careful design of the circuits.
8.7 Semiconductor Devices used in Static Relays
The various electronic components, devices and circuits which are commonly used
in static relays are,
1, Semiconductor diodes : This includes the conventional p-n junction diode,
zener diode, avalanche diode and the circuits using these diodes such as
rectifiers, regulators, references ete.
2. Transistors : This includes bipolar junction transistors (BJT) and field effect
transistors (FET). The transistors are used as amplifiers or as switches in the
static relays. The direct coupled amplifiers using transistors are also used in
the static relays.
3. Unijunction transistor : The device UJT having negative resistance
characteristics is often used to obtain relaxation oscillator, the output of which
is used to trigger SCR.
4. Thyristor family : This includes various two and three terminal and four layer
electronic devices such as silicon controlled rectifier (SCR), triac, diac, silicon
controlled switch (SCS). Such devices are used in static relays to obtain high
speed switching characteristics.
5. Logic circuits : Most of the relays are bistable devices i.e. they are operated in
two stable states either ON or OFF, The logic circuit also has two states highGarrier Aided Protection
4 and Static Relays
Protection and Switchgear B-
ie, ON and low ie. OFF. Hence logic circu
static relays.
play an important role in the
6. Filler cirewits : The RC and LC filters are also used in static relays after
rectifiers to obtain smoothing of dic, voltage generated. To obtain fast
smoothing instead of conventional capacitor filter, the phase splitting before
the rectification is used in static relays.
7. Multivibrators : The various multivibrators using transistors aze used to
produce square waveforms in static relays, The diode clippers also can be used
to obtain square waveforms.
8 Time delay circuits : The variety of time delay circuits such as delay lines, RC
circuits, timer circuits, resonant circuits using transistors, thyristors and ICs are
used in static relays. Depending upon the requirement of time delay, the
particular circuit is chosen. The delay lines are used for shorter delays while
RC charging and discharging circuits are used for longer delays. The time
delays of the order of micro secs to hours can be achieved using such time
delay circuits.
9. Level detectors : In static relays, it ig necessary to detect the operating levels of
various signals and used it to produce the necessary actuating signals. The
level detector circuits using the diodes, rectifier and RC elements are
commonly used in static relays.
10, Analog cireuits : The op-amp available in IC form is very common in building
analog circuits such as adder, subtractor, differentiator, integrator, inverting
amplifier, noninverting amplifier etc. Op-amp also can be used to obiain the
circuits like zero crossing detector, Schmitt trigger etc. All such circuits are
used in various types of static relays.
8.8 Static Time Current Relay
This is nothing but instantaneous overcurrent relay. The Fig, 8.12 shows the block
diagram of static time current relay.
Ampiier |
‘ter
Tepping
Fig. 6.12 Block diagram of time current static relayCarrier Aided Protection
Protection and Switchgear +15 and Static Relays
The secondaries of line CT's are connected to the summation circuit. The output
of summation C.T. is given to the input C.T. The input C.T, is called auxiliary CT.
which has taps on the primary for selecting the required pickup and current range.
Then the output of auxiliary C.T. is rectified and smoothened. It is then applied to
overload level detector and RC timing circuit, When the voltage across the timing
capacitor reaches to a critical value then it triggers the level detector. The output of
the level detector is amplified as per the requirement and given to the tripping circuit.
This operates the output device. The charging of capacitor in a timing circuit is
achieved by a voltage derived from CT current. This voltage is obtained across a
nonlinear resistor by passing rectified current through it, The proper selection of
nonlinear resistor and RC timing circuit allows to obtain desired shape of time current
characteristics of the static relay.
‘The current at which the level detector trips is called threshold current denoted as
[ieehott- Thus for an overcurrent relay,
when Ty, while the relay characteristics angle is 0. Let I, be the current setting
magnitude. Then the relay operates. when,
I, S [cos (6-0)Carrier Aided Protection
Protection and Switchgear 8-20 and Static Relays
The output of the phase comparator is applied to a level detector through timer if
time delay is required. ‘The output of the level detector is amplified and given to the
trip circuit.
‘The phase comparator is generally of two types,
1, Hall effect generator which is popularly used in Russian countries,
2 Rectifier bridge type comparator which is popularly used in European countries.
‘The static directional overcurrent relays are very sensitive and directional unit can
be made reliable dewn to 1% of the system voltage.
8.10 Static Differential Relay
A differential relay is the relay which operates when the phasor difference of two
or more similar electrical quantities exceed a predetermined value.
In static differential relay, two similar quantities either voltages or currents are
compared. The comparator measures the vector difference between the two similar
input signals. The rectifier bridge type comparator is generally used in the static
differential relay. The block diagram is shown in the Fig. 8.17
Compara
Fig. 8.17 Static differential retay
Input
|
Input,
8
In normal conditions, the two quantities balance each other and the comparator
output is zero and the relay is inoperative.
For any internal fault conditions, the comparator senses the phase difference
between the two quantities and produces the output. This is amplified and given to
the trip circuit which operates the relay.
This scheme is used for protection of the generators and transformers against any
type of internal fault
The various advantages of static differential relay over electromagnetic differential
relay are, highly sensitive, compact, very fast in operation, low power consumption,
less burden on input CTs and inrush current proof characteristics.Carrier Aided Protection
Protection and Switchgear 8-24 and Static Relays
The basic static differential relay scheme is shown in the Fig, 8.18,
Bridge rectiter
comparator
ot ot ——_
Equipment
to be protected
Operating
Restraining
Fig. 8.18 Static differential relay scheme
Let n, and n, be the number of turns of operating and restraining coils
respectively. Then the relay operates when,
K,n,t, > K,n, 1, +K’
where k, and k, are design constants while K’ is the 5
ing control torque.
8.11 Static Distance Relay
In the distance relay, the operation is dependent on the ratio of the voltage and
current, which is expressed interms of an impedance. The relay operates when the
ratio V/1 ie. impedance is less than a predetermined value. The distance relays
include impedance, reactance and admittance relays as discussed earlier. In static
relays the comparison of voltage and current is achieved by clectronic comparator
circuits.Carrier Aided Protection
Protection and Switchgear 8-22 and Static Relays
The basic block diagram of static distance relay is shown in the Fig. 8.19.
Me ‘Measuring | St
h euit
Comparator [Hf || at, t
“ Measuring
k creut |S,
Fig. 8.19 Basic static distance relay scheme
The line voltage V,, and line current I, are given as the inputs to the two
measuring circuits. The circuits produce the outputs S$, and S, depending upon their
characteristics. Thus,
§ = K Vi +h hy
S, = Ky Vy +Ky I,
where K;,K3,K3 and Ky are to be selected according to the requirement of the
characteristics
Now depending upon whether the comparator is amplitude or phase comparator
and the constants K, to K,, the various characteristics of the distance relay can be
obtained
‘The various types of derived voltages S,andS, for amplitude and phase
comparators to obtain particular characteristics are given in the Table. 8.1.
No, Amplitude comparator
‘Operating
1 I aw WZy ¥ Directional
LZ,
2 tht byl 1 2q-¥% 12a M impedance
|
ote hi 1 y-¥sine i Ze Reactance
1, Zn~¥, vy, Mo
Tab!Carrier Aided Protection
Protection and Switchgear 8-23 and Static Relays
The characteristics of various schemes as obtained from above Table 8.1 are shown.
in the Fig. 8.20.
cating
x x x _
2p Opecating
i f
Gog R Cpemhe a Re
Operating |
(8) Directional (b} impedance (c) Reactance (a) Mine
Fig. 8.20
The static distance relays are used popularly for protection of medium and long
transmission lines, parallel feeders and interconnected and T connected lines.
8.12 Microprocessor Based Relay
Let us see the relay logic which is very important in understanding the
microprocessor based relay. The relay can be ON or OFF ie. it has two stable states
Similarly output of a logic function is ON ie. high or OFF ie. low. The three basic
logic functions are,
1.AND 2OR 3. NOT
AND function :
The block schematic of AND function and the truth table is shown in the
Fig, 8.21. In the truth table 1 indicates high while 0 indicates low. AND is nothing but
a multiplication.
AND |}-—* C=A-B
{a) Block schematic ‘(b) Truth tabie-
Fig, 8:21 AND function
The diode AND gate is shown in the Fig, 8.22 (a) while the AND operation using
relays is shown in the Fig. 8.22 (b).Carrier Aided Protection
Protection and Switchgear 8-24 and Static Relays
4
R —“ —_" ASB=AANDB
A A He
8 CHAS oe
(a) Diode AND (0) AND with relays
Fig. 8.22
‘OR function :
‘The block schematic of OR function and the truth table is shown in the Fig, 8.23.
‘The OR function is nothing but an addition.
[aye] csaors |
oO
,
:
:
(a) Block schematic (0) Truth table
Fig. 8.23 OR function
The diode OR gate is shown in the Fig. 824 (a) while the OR operation using
relays is shown in the Fig. 8.24 (b).
A CHAt8
Ate
{a} Diode OR, {b) OR with relays:
Fig. 8.24Carrier Aided Protection
Protection and Switchgear 8-25 and Static Relays
NOT function :
‘The NOT function is inverting function of the input, So if input A is 0 then output
is 1 and viceversa. The output is denoted as A. It is shown in the Fig: 8.25.
A [ca
-—
Ae NOT ck of 4
1] a
(a) Block schematic (b) Truth table
Fig. 8.25 NOT function
By using NOT function with basic AND and OR two more logical functions can be
obtained which are NAND and NOR
The truth tables for NAND and NOR are given in the Table. 8.2.
Table 8.2
All these functions can be achieved using transistors also. It is called transistor
transistor logic (TTL).
The Fig. 8.26 shows the block diagram of microprocessor based relay.
The output of line CT is given to the input receiver block where signal is
processed. The signal processing includes surge protector, rectifier, smoothening filters,
auxiliary CT ete. depending upon the requirement. This signal is an analog signal. The
A/D converter converts this to a digital signal which is accepted by the
microprocessor. The microprocessor is a decision making block. The digital ‘signal
received is compared with the reference to generate the proper tripping signal, This is
a digital signal which is converted to analog again to operate the tripping coil. This is
achieved by the D/A converter. The data logger captures the data and feeds it to the
microprocessor when there is a request from the microprocessor. The information can
be displayed with a proper display device by taking signal from the microprocessorCarrier Aided Protection
Protection and Switchgear 8-26 and Static Relays
Circuit
breaker
cr a
Tripping signal
DIA convertor
Signal AD
processing converter Microprocessor
Display
Data, | ata
sottgy logge request
Fig. 8.26 Microprocessor based overcurrent relay
‘The main advantage of such relay is that it is programmable. The programme can
take care of on line calculations and take the decision accordingly. Another important
advantage of microprocessor based relay is that one microprocessor unit can perform
the relaying operation of several systems.
‘Thus various advantages of microprocessor based relay are,
1. Very efficient and reliable.
2. Highly accurate.
3. Ve
y fast in operation.
4, Programmable in nature
5. One unit can perform relaying of several systems.
6 Economical for large systems
7. Useful for centralley co-ordinated back up protection.
Only are must be taken that the microprocessor unit must be properly shielded as
it gets affected by external interferences and environment. Proper care of earthing
must also be taken.
Review Questions.
1. Draw and explain block schematic of carrier aided protection
2. Which electoomic equipments are used at ench end of the line ?
3h. Explain the transmitting unit used in carrier aided protection
4. Explain the block diagram of phase comparision method.Carrier Aided Protection
Protection and Switchgear 8-27 and Static Relays
State the advantages of cartier current protection.
Explaiee the basic elements of static relays.
Compare static and electromagnetic relays
State the advantages of static relays,
Which are the wirious semiconductor devices used in static relays 2
Draw and explain the block diagrant of static time-curnent relay
rac and explain the circuit diagram of static instantaneous over current relay.
Draw and explain circuit diagram of static inverse time aver current relay.
Draer and explain the circuit diagram of static directional overcurrent relay.
Draco and explain the circuit diagram of static differentical rely.
White « note on static distance relays.
White a note on microprocessor base relay.
Qog(8 - 28)Theory of Arc Quenching
9.1 Introduction
The different circuits of a power system viz transmission lines, distributors,
generating stations etc. are required to be operated under both normal and abnormal
conditions. Whenever any fault occurs somewhere in the system, it must be
immediately detected and disconnected from the system. This is necessary since it
ensures less damage to the faulted apparatus and the fault is not spread into the
stem. Also quick recovery of fault results in less interruption of service to the
consumers
Previously the function of switching on and off of the power system elements was
accomplished with the help of switch and fuse which is placed in series with the
circuit. But it suffers some difficulties such as replacement of fuse takes a long time.
So supply to the consumers will be restored after long time. The another limitation is
that it will not be able to interrupt successfully the heavy fault currents. Due to these
disadvantages the use of switch and fuse unit is restricted to the low: voltage and
small capacity circuits where frequent operations are not performed.
With the development in power system the transmission lines and various
equipments operate at very high voltages
arrangement explained earlier will fail to serve the desired function in high cap:
rrying large currents. The switch and fuse
city
circuits. The use of circuit breakers can facilitate the opening and closing of heavy
electric circuits smoothly and efficiently. A circuit breaker can make or break a circuit
either manually or automatically under no load, full load or short circuit conditions.
Thus it forms important element in any protective scheme,
Any circuit breaker essentially consists of fixed contact and moving contact. Under
abnormal condition
mechanism makes the moving contact to move away from the fixed contact, Whenever
contacts are separated from each other the circuit is not breaked immediately as heavy
arc is drawn between the contacts which will continue for some time. The resistance
of this are is high Which causes large power loss in the process. Also the components
of cireuit breaker are under heavy mechanical and electromagnetic stresses.
or whenever the circuit breaker is operated then the internal
(9-1)Protecti
in and Switchgear Theory of Arc Quenching
9.2 Formation of an Arc
Now let's see the formation of an arc. Under faulty conditions heavy current flows
through the contacts of the circuit breaker before they are opened. As soon as the
contacts start separating, the area of contact decreases which will increase the current
density and consequently rise in the temperature. The medium between the contacts of
circuit breaker may be air or oil. The heat which is produced in the medium is
sufficient enough to ionoise air or oil which will act as conductor. Thus an are is
struck between the contacts. The p.d. between the contacts is sufficient to maintain the
arc. So long as the arc is remaining between the contacts the circuit is said to be
uninterrupted.
The current flowing between the contacts depends on the are resistance. With
increase in arc resistance the current flowing will be smaller. The arc resistance
depends on following factors,
a) Degree of ionisation ; If there are less number of ionised particles between
the contacts then the arc resistance increases.
b) Length of are: The arc resistance is a function of length of are which is
nothing but separation between the contacts. More the length, more is the arc
resistance,
©} Cross-section of arc: If the area of cross-section of the arc is less then arc
resistance is large.
9.2.1 Initiation of Arc
There must be some electrons for initiation of an arc when fault occurs circuit
breaker contacts start separating from each other and the electrons are emitted which
ave produced by following methods.
i) By high voltage gradient at the cathode, resulting in field emission
ii) By increase of temperature, resulting in thermionic emission.
9.2.1.1 By High Voltage Gradient
As the moving contacts start separating from each other, the area of contact and
pressure between the separating contacts decreases. A high fault current causes
potential drop ( of the order of 10° V/cm) between the contacts which will remove the
electrons from cathode surface. This process is called field emission.
9.2.4.2 By Increase of Temperature
With the separation of contacts there is decrease in contact area which will
increase the current density and consequently the temperature of the surface as seenProtection and Switchgear 8-3 Theory of Arc Quenching
before, which will cause emission of electrons which is called thermal electron
emission
In most of the circuit breakers the contacts are made up of copper which is having
less thermionic emission.
9.2.2 Maintenance of an Arc
In the previous section we have seen the initiation of the arc by field emission and
thermionic emission. The electrons while travelling towards anode collide with another
electrons to dislodge them and thus the arc is maintained. The ionizing is facilated by,
i) High temperature of the medium around the contacts due to high current
densities. Thus the kinetic energy gained by moving electrons is increased.
ii) The increase in kinetic energy of moving electrons due to the voltage gradient
which dislodge more electrons from neutral molecules.
iii) The separation of contacts of circuit breaker increases the length of path which
will increase number of neutral molecules. This will decrease the density of gas
which will increase free path movement of the electrons.
9.2.3 Arc Extinction
It is essential that are should be extinguished as early as possible. There are two
methods of extinguishing the arc in circuit breakers which are namely,
a) High resistance method
b) Low resistance or current zero method
9.2.3.1 High Resistance Method
In high resistance method the arc resistance is increased with time, This will
reduce the current to such a value which will be insufficient to maintain the are, Thus
the current is interrupted and the arc is extinguished. This method is employed in
only dic, circuit breakers. The resistance of the arc may be increased by lengthening
the arc, cooling the arc, reducing the cross-section of the arc and splitting the arc.
These methods will be discussed in detail later in this chapter
9.2.3.2 Low Resistance Method
The low resistance or current zeto method is employed for are extinction in a.c.
circuits. In this method are resistance is kept low until current zero where extinction
cof are takes place naturally and is prevented from restriking. This method is employed.
in many of the modern ac, circuit breakers.Protection and Switchgear 9-4 Theory of Arc Quench
9.3 D.C. Circuit Breaking
The breaking in case of dic. circuits can be explained as follows. For this, we will
consider a circuit which will consist of generator with voltage E, resistance R,
inductor L and the circuit breaker as shown in the Fig. 9.1 (a).
R
Circuit
breaker
Fig. 9.4 (a)
‘The voltage-current relationship can be represented as shown in the Fig. 9.1 (b).
From the 9.1 (b), it could be seen that curve AB represents the voltage E — iR,
ing but current at any instant. The curve XY represents the voltage-current
characteristics of the arc for decreasing currents,
t cnn
t vottage:
Fig. 9.1 (b) Voltage-current relationship
When the circuit breaker starts opening it earries the load current | = 5. In the
graph shown the current is shown to be reduced to iy, iy and is respectively. Section
PF represents voltage drop is whereas qs represents arc voltage which is greater than
available voltage. The are becomes unstable and the difference in voltage is suppliedProtection and Switchgear 9-5 Theory of Arc Quenching
di
by inductance L across which the voltage is e, = L 7. For decreasing values of
currents this voltage is negative and according to Lenz's law it tries to maintain the
are.
The voltage across inductance L. is seen to be positive in the region of currents iy
and ip since the arc characteristics lies below the curve AB. The arc current in this
region tries to increase so interruption of current is not possible in this region
Afterwards the arc is lengthened with increase in contact separation which will raise
the are voltage above the curve AB.
The operation in case of d.c. circuit breakers is said to be ideal if the characteristics
of the arc voltage are above the curve AB even in the region of currents iy and iz. This
is shown in the Fig. 9.2
‘Arching
time
Fig, 9.2 Are voltage characteristics
It can be seen that arc voltage is greater than E ~ i and the balance between the
voltages is supplied by the voltage across the inductance e, which is proportional to
rate of change of current i
Thus the function of the circuit breaker is to raise the arc characteristics without
affecting its stability. This is done by reducing the arcing time which is the time from
contact separation to final extinction of arc. But it will increase extinction voltage.
Hence compromise between arcing time and arc extinction voltage is made.
9.4 AC. Circuit Breaking
There is a difference between breaking in case of d.c. and acc. circuits. In ac.
circuits the current passes through zero twice in one complete cycle. When the
currents are reduced to zero the beakers are operated to cut-off the current. This willProtection and Switchgear 9-6 Theory of Arc Quenching
avoid the striking of the are. But this conditions is difficult to achieve and very much
expensive.
The restriking of arc when current is interrupted is dependent on the voltage
between the contact gap at that instant which will intumn depend on power factor.
Higher the power factor, lesser is the voltage appearing across the gap than its peak
value.
Now before studying the actual current interruption in a.c, circuits we will see
some theory which will help us in understanding this concept.
9.5 Short Circuit in R- L Series Circuit
Consider a series R-L circuit as shown in the Fig. 9.3 in which switch S is
suddenly closed at time
eo E,, sin (wt + 9)
Fig, 9.3. R-L series circuit
Applying KVL to above circuit,
dita
LGptRice
dita
LSP + Ri = Ey sin (ot+0) -
This equation can be solved to get the expression for current i. This is a
non-homogeneous differential equation whose solution consists of two parts viz
complementary solution and particular solution ie. i= ic + ip.
Complementary Solution : To get the complementary solution we will consider
the auxiliary equation which is obtained by equating right hand side of above
equation to zero,
LosRiso 6 @
Separating the variables,
d R
-patProtection and Switchgear 9-7 Theory of Arc Quenching
Integrating and solving,
logi = = & t+K where K is constant of integration
Considering K = log. A
log i = log, e CRY + log, A
log.i = log. Ae CRUE
‘Taking antilog on both sides,
i= AeeReut
This is complementary solution. This component of current is seen to be
exponentially decaying component and called D.C. component. The constant of
integration A depends on initial conditions which may be zero, positive or negative.
es AerRUt -- 3)
Particular Solution : For particular solution we will take a trial solution as,
i = C cos (ot +0) + D sin (at +0) on (4)
Taking g and <
fabs tion,
gir of above equation
-Cosin (ot +8) + Dacos (ot +8)
= Ca? cos (at +8) = D af sin (ot +8)
c
Substituting these values of C and D in the trial solution we get,
tk cos (ot +0) + Ey,
ol ®
sin (ot +4) ... 6)
m2Ir 9-8 ‘Theory of Arc Quenching
Protection and Switchg:
cos @ =
sin $ cos (ot+8) + cos $ sin (ot +8)
[sin (ot +6) cos} - cos (tat +8) sin g]
sin (at +8-$)
sin (ot +0=8) 6)
The particular solution given by above equation is sinusoidal and is called A.C.
component.
Complete Solution : The total current i is given by,
i= ict
i= Ae (R/Uty. Em in (ot 40-4) on
yR sol?
To find the value of A let us put the initial conditions, Att =0, i= 0. WR is
assumed to be very smalt compared to o L: fR? +a"? = aL
and @ = tan! = = 90°
Case (i): If switch is closed at e = 0
Also i=
FR? +07?
This is the maximum value of A. Thus the d.c. component is maximum when
switch is closed at zero voltage.
‘Case (ii): If switch is closed at € = E,nay
t=O O=9° = a/2
EmaxProtection and Switchgear 9-9 Theory of Arc Quenching
O= sin (90° 909
A=0
If switch is closed when e = E,,, then A = 0 ise. dic. component is zero,
‘Thus when the circuit consisting of R and L supplied with alternating voltage, is
closed at t = 0, the resulting current consists of two components viz ac. and dc.
components which are superimposed on each other. The d.c. component magnitude is
decided by the voltage at the instant of switching. When switch is closed at voltage
zero, the d.c. component is maximum whereas the dc. component is zero when switch
is closed at voltage maximum,
D.€..Component
Fig. 9.4 Maximum D.C. component
Fig. 9.5 No D.C, component
‘The analysis of three phase short circuit of an altemator is done by similar way as
we have done the analysis of short circuit of series R-L circuit. The current flowing
through the phases of alternator during short circuit has similar wavefarm to that ofProtection and Switchgear 9-10 Theory of Arc Quenching
R-L circuit as shown previously if we neglect armature reaction and variation in the
field current
During the short circuit, the current flowing through alternator rises rapidly to a
high value during first quarter cycle. The flux which is crossing the air gap is large
during first couple of cycles.
The subtransient reactance denoted by Xj is defined as that reactance during first
two or three cycles. This is very less and correspondingly short circuit current is large.
After first few cycles which are coming under subtransient state the r.m.s. value of
short circuit current goes on reducing but the decrease in current is not fast as in
subtransient state. This state is called transient state and the corresponding reactance is
called transient reactance denoted by X'y. The circuit breaker contacts separate in this
state.
Finally the transients vanish and current will reach to steady sinusoidal state
called steady state. The reactance in this state is called steady state reactance denoted
by Xa.
The currents in the different phases are having different d.c. components. So their
waveforms will be different. In the Fig. 9.6 the oscillogram of the current in the phase
having zero d.c. component is shown.
che Sitep}>—— transient =} Steady
HAA
9.6 Oscillogram of current in the phase having zero d.c. componentProtection and Switchgear 9-11 Theory of Are Quenching
9.6 Current Interruption in A.C. Circuit Breakers
Now we will see how the current interruption takes place in a.c. circuit breakers.
Generally the ac. circuit beakers employ zero point interruption technique
Let us consider an alternator on no load to which a circuit breaker is connected
which is shown in the Fig. 9.7. The circuit breaker is in open position with its other
side short circuited.
ereuit
9.7 Sudden 3 phase short circuit of an alternator
When the voltage of phase B wart neutral is zero, the circuit breaker is closed.
Under this condition the B phase current will have maximum d.c. component and its
current waveform will be unsymmetrical about normal zero axis. This is shown in the
Fig. 9.8.
Fig, 9.8 Current and voltage during fault clearingProtection and Switchgear 9-12 Theory of Are Quenching
‘The current is zero before t = 0 as the alternator is on no load. The short circuit is
applied at t = 0 and current increases to very high value ( nearly 10 to 25 times full
load current) during first quarter cycle. The peak of first current loop is shown by OA
which is maximum instantaneous value of current during short circuit. This
instantaneous peak value of first current loop is called making current which is
expressed as kA peak.
Now the circuit breaker contacts will separate after few cycles which are taken by
relay and other operating mechanism. At time say t = T, the contacts of circuit breaker
separate. The r.m.s, value of short circuit current at that instant of contact separation is
called breaking current.
As seen earlier an arc is struck between the contact when they start separating.
The are current varies sinusoidally for few cycles. At t = T; the arc is interrupted as
the dielectric strength of arc space builds sufficiently. This will avoid the continuation
of are. Thus the are will be extinguished.
The voltage waveform is shown in the Fig, 9.8, Before the instant t = 0, the
contacts are closed so the voltage between them is zero. At the instant t = T,, the
contacts begin to separate and voltage across them starts increasing, This voltage is
nothing but the drop across the are. The current and the voltage across arc are in
phase as the are is resistive. Due to increased are resistance the voltage across contacts
increases in the next cycles. Finally at t= Tp the are is extinguished. A high frequency
transient voltage appears across the contacts which is superimposed on power
frequency voltage. This high frequency voltage tries to restrike the arc. Hence it is
called Restriking Voltage or Transient Recovery Voltage. This is the voltage which
appears across circuit breaker contact which is responsible for restriking of arc. The
power frequency system voltage between the circuit breaker contacts after arc
extinction is called Recovery Voltage. The prospective current shown in the waveform,
may be defined as the current that would flow inthe circuit if circuit breakers were
replaced by solid conductor.
9.7 Transient Recovery Voltage
The transient recovery voltage has effect on the behaviour of circuit breaker. This
voltage appears between the contacts immediately after final arc interruption. This
causes high dielectric stress between the contacts. If this dielectric strength of the
medium between the contacts does not build up faster than the rate of rise of the
transient recovery voltage then the breakdown takes place which will cause restriking:
of arc. Thus it is very important that the dielectric strength of the contact space must
build very rapidly that rate of rise of transient recovery voltage so that the
interruption of current by the circuit breaker takes place successfully. The rate of rise
of this transient voltage depends on the circuit parameters and the type of theProtection and Switchgear 9-43 Theory of Arc Guenching
switching duty involved. The rate of building up of the dielectric strength depends on
the effective design of the interrupter and the circuit breaker.
If it is desired to break the capacitive currents while opening the capacitor banks,
there may appear a high voltage actoss the contacts which can cause reigintion of the
arc after initial are extinction. Thus if contact space breaks down within a period of
‘one fourth of a cycle from initial are extinction the phenomenon is called Reigintion. If
moving, contacts of circuit breakers move a very small distance from the fixed contacts
then reigintion may occur without overvoltage. But the arc gets extinguished in the
next current zero by which time moving contacts should be moved by sufficient
distance from fixed contacts. Thus the reignition is in a way not harmful as it will not
lead to any overvoltage beyond permissible limits.
If the breakdown occurs after one fourth of a cycle, the phenomenon is called
Restrike. In restriking, high voltage appear across the circuit breaker contacts during
capacitive current breaking. In successive restrikes, voltage will go on increasing which
may lead to damage of circuit breaker. Thus the circuit breakers used for capacitors
should be free from Restrike i.e. they should have adequate rating,
9.8 Effect of Different Parameters on Transient Recovery Voltage (TRV)
As seen from the previous section, after the final current, zero high frequency
transient voltage appears across the circuit breaker poles which is superimposed on
power frequency system voltage and tries to restrike the arc. This voltage may last for
@ few tens or hundreds of microseconds. If the shape of this TRV is seen on the
oscilloscope then it can be seen that it may be oscillatory, non-oscillatory or a
combination of two depending upon the characteristics of the circuit and the circuit
breaker. The waveform is as shown in the Fig. 9.9
Power frequency
Recovery voltage
“== Transient
‘voltage
Fig. 9.9 Shape of transient recovery voltage
This voltage has a power frequency component and an oscillatory transient
component, The oscillatory component is due to inductance and capacitance in the
circuit. The power frequency component is due to the system voltage. This is shown
in the Fig. 9.10,Protection and Switchgear 9-14 Theory of Arc Quenching
Restriking
a" voltage
Recovery
voltage
\ fi
\. aro
7
Fig, 9.10 Voltages after final current zero
The transient oscillatory component lasts for few microseconds after which power
frequency voltage remains. The transient component has frequency given by,
where {,, = Frequency of transient recovery voltage
= Equivalent inductance
C = Equivalent capacitance
9.8.1 Effect of Natural Frequency on TRV
With increase in the natural frequency the rate of rise of TRV at current zero
increases. This is shown in the Fig. 9.11. The rate of rise of transient recovery voltage
is represented by slopes of tangents to the three waveforms drawn at different
frequencies.
Rate of rise of TRV causes voltage stress on the contact gap which will continue
the arc, If the frequency is increased then relatively small time is available for building
of dielectric strength of contact gap. Hence increase in frequency causes greater
stresses, The rate of rise of TRV is related with the breaking capacity of a circuit
breaker. Thus it also means rate of rise of TRV is dependent on natural frequency of
‘TRV. As frequency increases the breaking capacity reduces.Protection and Switchgear 9-45 Theory of Arc Quenching
AB,C = Tangents indicate
slope of TRV at t= 0
Fig. 9.11 Effect of frequency of TRV
9.8.2 Effect of Power Factor on TRV
At the instant of final current zero the voltage appearing across the C.B, contacts is
affected by the p.f. of the current. At current zero the are is extinguished, After this
power frequency voltage appears across the circuit breaker, The instantaneous value of
the voltage at current zero depends on phase angle between the current and voltage.
For unity p.f, load as shown in the Fig, 9.12 both voltage and current are in phase
and are zero at the same instant,
Recovery voltage
Fig. 9.12 Unity power factorFig. 9.13 Zero power factor
If we consider zero power factor currents, the peak voltage E,,,, is impressed on
the circuit breaker contacts at the current zero instant. This instantaneous voltage gives
more transient and provides high rate of rise of TRV. Hence if the p.f. is low then
interrupting of such current is difficult.
9.9 Recovery Voltage
As scen previously it is the voltage having normal power frequency which appears
after the transient voltage.
9.9.1 Effect of Reactance Drop on Recovery Voltage
Before fault is taking place let us consider that the voltage appearing across circuit
breaker is V;. As thé fault current increases, the voltage drop in reactance also
increases. After fault clearing the voltage appearing say V, is slightly less than Vj.
‘The system takes some time to regain the original value.
9.9.2 Effect of Armature Reaction on Recovery Voltage
The short circuit currents are at lagging power factor. These lagging p.f. currents
have a demagnetizing armature reaction in altemators. Thus the induced emé. of
alternators decreases. To regain the original value this em.f. takes some time. Thus the
power frequency component of recovery voltage is less than the normal value of
system voltage.Protection and Switchgear 9-47 Theory of Are Quenching
9.10 Single Frequency Transient
Consider the — circuit
it bresker shown in the Fig. 9.14.
This circuit produces the
single frequency restriking
Faut voltage transi
e=E,, sinot
The natural frequency
of oscillation is given by,
1
Fig. 9.14 fe = 2a JL
where L. = Inductance in henry
C = Capacitance in farads
Depending upon the values of L and C, the frequency ranges from 10 Hz to
10 kHz, The citcuit configuration in actual power system is complicated and it has
distributed capacitance and inductances. In such circuits the TRV has several
components of frequencies which is shown in the Fig. 9.15.
The transient shown in the Fig. 9.15 is obtained by operating the terminal fault
where reactance between the fault and circuit breaker is negligible
Peak of the restriking voltage
Restniking
cument voltage
Fig. 9.15
9.11 Double Frequency Transient
In last section we have considered inductance |. and capacitance C an only one
side of circuit breaker. But it may be on both sides of circuit breaker, This is shown in
the Fig. 9.16.Protection and Switchgear 9-18 Theory of Arc Quenching
Foutt
Fig. 9.16
The points 1 and 2 are
equipotential points before clearing
the fault, But after the arc extinction
there will be two circuits which
may oscillate at their own natural
frequenciés and thus a composite
double frequency transient appears
Fig. 9.17 across circuit breaker, This is shown
in the Fig. 9.17.
The circuit configuration, the type of fault and the type of neutral earthing are the
important factors which will decide the frequency, rate of rise and peak value of the
TRV.
The TRV wave is defined by specifying the peak value and time required to reach
the same or it can be specified by defining the segment of lines which enclose the
TRV waveform.
9.12 Derivation of Rate of Rise of TRV
‘As seen previously the transient voltage that appears across the circuit breaker
contacts at the instant of arc extinction is called Restriking Voltage. The rate of rise of
restriking voltage RRRV is nothing but rate which is expressed in volts per
micro-second, This will represent the rate at which Transient Recovery Veltage is
increasing, The rate of rise of TRV is dependent on system parameters.
With e as the restriking voltage in volts then
RRRV = . volts / psec
‘The maximum instantaneous value attained by the restriking voltage is called the
peak restriking voltage.
With the given specifications of TRV the circuit breaker must be able to interrupt
the short circuit breaking current. The peak value of TRV, time te reach the peakProtection and Switchgear 9-20 Theory of Are Quenching
where,
¢ = voltage across breaker terminals nothing but restriking voltage
Differentiating (1),
di _ ea de
aoa
(2
The solution of 'e’ will thus depend on the current and if interruption takes place
at current zero ie. when t = 0 then,
Ew
i= Gpsinot
and after opening of circuit breaker,
St Ee wcosat
dt @L*
E
= Em t rt=0
Te 608 a
Substituting this in (2),
Ew Jf @e
SPosat = 7+CTe
This is standard equation and solution of this equation is,
e= &-[)-«e( se]| wa (AD
This is an expression for restriking voltage in which,
E,, = Peak value of recovery
voltage phase to neutral in
volts.
time in sec.
4
inductance in henries
oF
'
capacitance in farads
restriking voltage
Fig. 9.19Protection and Switchgear 9-24 Theory of Arc Quenching
9.12.1 Expression for Maximum Value of Restriking Voltage E,,
and Corresponding Time t,,
Now
if eis to be maximum
= -1 where t=t,
y¥lc
Time at which maximum restriking voltage occurs is,
ty = nbc
And peak value of restriking voltage,
On = 2Eq
where E,, is equal to active recovery voltage (ie. instantancous value of recovery
voltage at current zero)
9.12.2 Expression for RRRV and Maximum RRRV
Now RRRV
maximum RRRV
and
1
when sin = = 1
yeProtection and Switchgear 9-22 Theory of Arc Quenching
for maximum RRRV
Maximum RRV
Maximum RRV = 2 & Ew fa
9.12.4 Restriking Voltage Under Various Conditions
The restriking voltage 'e' under various conditions will be,
t
“Eom yi]
where V,, active recovery voltage i.e. the instantaneous value of recovery voltage
at current zero and V,, can be written as
Var = Ky Ky Ks Em
Here E,, is the peak value of system voltage where,
K, is factor which takes into accounts effect of circuit p.f. and K, = sin
So if @= 9% Kel
K, is factor which accounts effect of armature reaction on recovery
valtage.
K;, is phase factor or first pole to clear factor.
9.12.5 First Pole to Clear Factor
The first pole to clear facter is given by,
RMS voltage between healthy phase
and faulty phase
Phase to neutral voltage with fault
removed
Factor pole to clear factor =
In three phase systems if fault does not involve the earth, the voltage across the
circuit breaker pole first to clear is 1.5 times the phase voltage. The arc extinction inProtection and Switchgear 9-23 Theory of Arc Quenching
the three poles of three phase circuit breakers is not simultaneous as currents are 120°
out of phase. In practical systems the recovery voltage of the pole first to extinguish
the are is of the order of 1.2 to 15 times of the phase voltage.
If fault involves earth and the neutral is grounded through reactor, the recovery
voltage is influenced by the equivalent system reactances
Thus in 3 phase circuits K, = 1 if neutral is earthed and fault is also earthed.
While K;=15 if neutral is earthed and fault is insulated or neutral is insulated and
fault is earthed,
Example 9.1; In short circuit test on @ 3 pole, 132 kV circuit breaker, the followi
observations are made p.f. of fault 0.4, recovery voltage 0.9 times full line value, the
breaking current symmetrical, frequency of oscillations of restriking voltage 16 kHz.
Assume neutral is grounded and fruit is not grounded. Determine average RRRV.
Ve h-«( te}
where Vor = Ky K2 Ky En
Solution ; e
Kj(takes into account pf. effect) = sin ¢
K; (takes into account armature reaction effect) = 0:9
K, (Phase factor or 1* pole to dear factor)
=1 for both neutral and fault grounded.
= 15 for any one of the two not grounded.
In the problem,
K, = sin @ = sin [eos! 04] = 0.9165
K, = 09 Kk,
line to ground
= Bye = 10777
"Ys
5
2n «16x 1
1x10Protection and Switchgear 9-24 Theory of Arc Quenching
Time to reach maximum restriking voltage
Maximum t, = xyLG = —*
1x1
Maximum restriking voltage,
= 2Vy
= 2K, Kz Ky Em = 2 * 0.9165 x 0.9 « 1.5 x 107.77 x 10°
= 2.66682 x 10° V
‘Average RRRV,
Maximum restriking voltage 266682 10°
‘Time to reach maximum restriking voltage x /1x10°
= 8.48 « 10° V/sec = 8.48 « 10° kV/sec = 8.48 kV/usec
ump Example 9.2: In a short circwit test om a 130 KV, 3 phase system, the breaker gave
the following results : pf. of fault 0.45, recovery voltage 0.95 times full line voltage,
breaker current symmetrical, and restriking transient had a natural frequency 16 kHz.
Determine average RRRV. Assume fault is grounded,
Solution :
2130
Eq = 2190 9644 kV
Va
Ver = Ki Kp Ky Em where Ky = sing = 0.8930
= 0.8930 «0.95 «1 « 106.144 K, = 095
= 90.047262 kV Ky =i
Maximum e = 2 Vy, = 180,09452 kV
Maximum time = x/L€
Maximum t
Maximum e _ _ 180,09452
Average RRRV = SOOT = pawlondoF
= 5.76302 kV /useeProtection and Switchgear 9-25 Theory of Are Quenching
wm Example 9.3 : Calculate the RRRV of 132 kV circuit brenker with neutral earthed.
S.C. data as follows: Broken current is symmetrical, restriking voltage has frequency
20 kHz, pf. 0.15, Assume fault is also earthed,
Solution : K, = sin 6 = sin (cos * 0.15) = 0.9886
K, =1
Ky =1 both grounded
Ey = LPAI oz g7755 EW
Va
Var = Ki Ky Ks Em
= 10654889 kV
Maximume = 2 V,,
= 213.09778 kV
ty = ayLe
1 1
id . TC = ty = a sec
a " 2af Le x 2h,
Maximutn ty = ———/—— see
2x 20x10
Cmax, 213,09778
RRRV = ne D7 @0x10" xD)
= 852 kV/ sec
iam Example 9.4: A 50 Hz generator has emf to neutral 7.5 kV (rims). The reactance
of gencrator and the connected system is 40 and distributed capacitance to neutral is
0.01 pF with resistarice negligible . Find,
i) mactineuin voltage across te circuit breaker contacts
ii) frequency of oscillations
iii) RRRV average upto first peak of oscillations.
Solution X=2efL=42
L = 4/2nx50= 00127 H.
E, = f2 x 7.5 = 10.606 kVProtection and Switchgear 9-26 Theory of Arc Quenching
1) Maximum voltage = 2% Ey,
= 2» 10.606 = 21.212 kV
1 1
2 f= a
2nfLC ax f0.0127 «0.01% 10%
= 14.1227 kHz
3) Maximum time to reach maximum voltage is,
ty = mf LO =o =
a Ws oF aaa
Average RRRV = Maximum voliage
21.212
(1 / 2x 14,1227 109]
= 0509 KV/ p sec
wm Example 9.5: In a system having 220 KV, the line to ground capacitance 0.013 wF,
inductance 3.5 H. Determine voltage appearing across pole of circuit breaker if a
magnetising current of 6.5.A instantaneous, is interrupted. Determine also the value of
resistance to be used across the conttacts ta eliminate the restriking vattage,
ic
i { t
‘Solution : e=E, [ ~ cos ]
1
2
oO
é
2
Energy stored in 'L’ = energy given to capacitor
instantaneous value
e=iyl7€ where
= 65 {3
(0.015«10%)
= 99.3.kV
To eliminate restriking voltage and critical damping, condition,
R = 05//C
7.635 ke
05 5
( xProtection and Switchgear 9-27 Theory of Arc Quenching
mm Example 9.6: A 50 Hz, 3 ph alternator, jtas rated voltage 13.5 kV, connected to
circuit breaker, inductive reactance 4 QYph, C = 2 pF
Determine maximum RRRV, peak restriking voltage, frequency of oscillations
Solution : Ey = Y2*185 is opo7 ky
X = 2nfL 2 L = 0.012733 H and C= 2 uF
i
fy = = 0.997 kHz
2nyLe
Maximum restriking voltage = 2 E,,
= 22.0454 kV
*, Maximum RRRV
Maximum RRRV
2 fy Em -
= x x 0997 x 10? x 22.0454 kV/sec
= 0.06907 kV/ psec
9.13 Interruption of Capacitive Currents
In power systems capacitor banks are used in the network which supplies reactive
power at leading, power factor.
There are Various conditions such
Pr
ra as opening a long transmission
{ Circuit line oi ng load ‘GF disconnecting a
cu & breaker capacitor bank ‘ete., in’ which ‘it is
reqiiifed 'to interrupt the capacitive
‘currents ‘Which’ is a‘ difficult’ task
for the Gietiit’ “bréakets” To
Fig. 9.20 Interruption of capacitive currents U"derstand this difficulty let us
consider a simple circuit shown in
the Fig, 9.20.Protection and Switchgear 9-28 Theory of Arc Quenching
The value of load capacitance C, is greater than C. The voltage across a capacitor
cannot change instantaneously. The currents supplied to the capacitor are generally
small and interruption of such currents take place at first current zero, Also at the
beginning, the rate of rise of recovery voltage is low and increases slowly. Whenever
such circuit is opened a charge is trapped in the capacitance C,, The voltage e, across
the load capacitance will hold the same value when circuit was opened. This voltage
is nothing but peak of supply voltage as power factor angle is nearly 90° leading.
After opening the circuit the voltage V¢ across the capacitance C oscillates and
approaches a new steady value. But due to small value of capacitance C, the value
attained is close to the supply voltage. The recovery voltage e, is nothing but
difference between ee and e,, Its initial value is zero as the circuit breaker will be
closed and increases slowly in the beginning. When Vc reverses after half cycle, the
recovery voltage is about twice the normal peak value. Therefore it is possible that at
this instant arc may restrike as the electrical strength between the circuit breaker
contacts is not sufficient. The circuit will be reclosed and e,, oscillates at a high
frequency
The supply voltage at this instant will be at its negative peak; therefore a high
frequency oscillation takes place.
At the instant of restrucking the arc, the recovery voltage V, is zero. The voltage
across the load capacitance reaches — 3 times the peak value of normal supply voltage.
The recovery voltage then starts increasing. If again restriking of arc takes place, a
high frequency of oscillation of e; takes place. Such several repetitions of the restriking
cycle will increase the voltage across load capacitance to a dangerously high value. In
practice this voltage is limited to 4 times the normal peak of the voltage. This
represented in the Fig, 9.21.
Thus in the successive restrikes, the energy 7 is to be dissipated which is
quity large and the circuit breaker may get damaged in the process of restriking.
Hence’ the ‘citcuit ‘breakers those are to be used for capacitors must be free from.
restriking and should have adequate rating for capacitive current s ing so that
severe vollage transients cain bé avoided.
If cireuit breakers .are, closed, while switching capacitor banks in parallel, the
pre-arcing: that, is arc.is_ struck, before contacts touch together, takes place. This may
damage. the,contacts,.as the. energy in’ the are is converted into heat. Thus while
switching...wigh, capacitor, banks suitable reactor L must used in series to limit high
fogquency, iqrush current.Protection and Switchgear 9-30 Theory of Arc Quenching
Consider the circuit shown in the Fig. 9.22.(a).
e= E,sinot Load
Fig. 9.22 (a) Circuit diagram showing interruption of inductive currents.
Current finaly
suppressed before
natural zero.
Natural
‘current zero
First chop ——| Time =
chop
Fiestrestake
Are
current
‘SS Recovery
‘tansient
Prospective vahies:
‘of voltage with chopping
Fig. 9.22 (b)Protection and Switchgear 9-31 Theory of Arc Quenching
While interrupting low inductive currents the rapid deionization of contact space
and blast effect may cause the current to reduce abruptly to zero well before the
natural current zero. This current chopping causes very serious voltage oscillations.
Let the arc current be i when it is chopped down to zero value. The stored energy
in the inductor which 5 Li will be discharged in to the capacitance so that the
capacitor is charged to a prospective voltage V such that,
1
ag
V=ifl7E volts
This prospective voltage is extremely high as compared to the normal system
voltage. The frequency of natural oscillations is given by,
lie
tie
2
To understand this point let us consider a small example of 220 KV circuit breaker
interrupting a magnetizing current of 10 A t.m.s. of transformer. Let the current be
chopped at the instantaneous value of 7A. Let the value of inductance and capacitance
be 35 H and 0.0020 pF
Assuming that all the inductive energy is transferred to capacitance and using the
above formula,
5
= 7) |——__
. [| 0,0020% 10-* |
e = 926 kV
This voltage will appear across the circuit breaker contacts. Such a transient
voltage having high RRRV appears across the contacts. There will be restriking of arc
at some point. If the are restrikes further, chop may occur. Thus before final
interruption of current there will be many chops and the circuit breaker will fail to
clear the fault. Alternately if the restrike does not occur, the severe voltage stress will
appear across circuit breaker contacts,
The rise of voltage before restriking is an important factor. The lower is the rate of
rise, more is the time required for deionization and high voltage will be reached.
After first chopping the deionising force which is still in action acts and second
chop of current takes place. But the arc current is now smaller than the previous one
and arc current collapses and restriking voltage is again build. Thus a sequence of
chops will occur and are will continuously decrease until a final chop brings arcProtection and Switchgear 9-32 Theory of Arc Quenching
current to zero, There ‘Will not be any further restriking as the gap is almost deionise.
This is represented in the Fig. 9.22 (b).
9.15 Resistance S
Tt can be seen from previous sections that the interruption of low inductive -
currents, interruption of capacitive currents give rise to severe voltage oscillations.
These excessive voltage surges during circuit interruption can be prevented by the use
of shunt resistance R across the circuit breaker contacts. This process is known as
Resistance Switching,
hing
When the resistance is connected across the arc, a part of the arc current flows
through the resistance. This will lead to decrease in arc current and increase in rate of
deionization of the arc path and resistance of arc. This will increase current through
shunt resistance . This process continues until the current through the are is diverted
through the resistance either
External completely or in major part. If
the small value of the current
c remains in the arc then the path
5 fF ° becomes so unstable that it is
Fixed Movad ‘er easily extinguished
contact contact y io .
The resistance may be
itched in and
are current can be transferred
The time required for this action
is very small. As shown in the
Fig. 9.23 the arc first appears
across points A and B which is
“Damped restrking voltage then transferred across A and C.
Fig, 9.23 Typical resistor connection
automatically s
sci
=<
PA seating votage
The shunt resistance also
ensures the effective damping of
the high frequency re-striking
Fig. 9.24 voltage transients. This is shown
in the Fig. 9.24
We will now derive a relation which will show how damping is achieved.
Consider the eirevit and Laplace transform equivalent as shown in the Fig. 9.25.Protection and Switchgear 9.33 Theory of Are Quenching
R
Fault
(a) Circuit (0) Equivalent circuit
Fig. 9.25
Applying KVL to loop (1)
v 1 i
oa (st+xe)h@-sbho @
Applying KVL to loop (II),
1 1
O=--ch w)+(R+J5) In (8) - Gi)
From equation (ii),
1) = (*sCR) Ls)
Substituting this value in equation (i)
1, (s)
Vv -
v (s-+Z6) (1 # sCR) I (s)
V _ fereereeser-4]y
oa [st SRLC+E4R a (s)
Vv z
Zt ERLCS LS +R)
vi
(= ee
*Re* Le)
Using partial-fractions,Protection and Switchgear 9-34
1s) =
2R
Pt «= se
ys) e VE ee
RF Gane
Taking inverse Laplace transform,
i (t) =
‘The natural frequency of oscillation is given by,
° (cos + sin Jy t
Theory of Arc Quenching
I
It can be seen that with the value of the resistance R equal to or less than
1
2
within the permissible limits of circuit breaker.
“ie
Considering different values of R, the
oscillations observed are shown in the Fig. 9.26.
In air blast circuit breakers it is observed that
the rate at which dielectric strength of gap
incteases is lower than in oil breakers, Since air
has a much lower dielectric strength than the
gases at same temperature and pressure in oil
circuit breaker. The dielectric strength of a gas
increases with pressure. Thus the air blast circuit
breaker is more sensetive to restriking voltage
transient, In low or medium voltage air blast
circuit breaker the rate or rise of restriking
voltage is higher. Thus shunt resistors are used
For critical damping
R
L/C, the oscillatory nature of the transient will not be there and RRRV will beProtection and Switchgear 9-35 Theory of Arc Quenching
for low and medium voltage air blast circuit breakers. Also in case of oil circuit
breakers the resistance switching is not employed as it is not sensitive to RRRV.
inmip Example 9.7; In 132 kV transmission system, the phase to ground capacitance is
0.01 pF, The inductance being 6 H, Calculate the voltage appearing across the pote of a
circuit breaker if a magnetizing current of 10 A is interrupted. Find the value of
resistance to be used across contact space to climinate the striking voltage transient.
Solution ; L=6H
C = 001 pF = 0.01 x 10°F
i= WA
Voltage appearing across poles of circuit breaker, is given by,
= 1 /—_o&__
0.01% 10%
= 10 (24494.89)
Vi= 245 kV
The value of resistance to be used across contact space is given by,
iff
R= HE
ai
2y 0.01«x10%
3 (2494.89)
R= 12242
9.16 Are Extinction
The electric discharge which is taking place between the electrodes is nothing but
the electric arc, We have seen that when contacts of circuit breakers are separated, an
are is established between the contacts which will last for some period. The circuit
breaker should be capable of extinguishing this are without damaging. The behaviour
of circuit breaker is greatly influenced by the arc.Protection and Switchgear 9-36 Theory of Arc Quenching
Interruption of arc in case of dic. circuits is much more difficult than that in case
of a.c. circuits. In a.c. currents the natural current zero point is available where the arc
vanishes and prevented from restriking,
The arc extinction in case of circuit breakers is not taking place frequently but still
it produces lot of stress on the breaker. The different methods adopted for the arc
extinction can be grouped into following three categories,
9.16.1 High Resistance Interruption
In this technique the resistance of current path is increased rapidly so. that voltage
drop is increased. The are gets extinguished when the system voltage is insufficient to
maintain the arc due to high voltage drop. This is normally used in dic. circuit
breakers and air break type ac. circuit breakers having low capacity. The system
inductance stores the energy which is dissipated in the arc.
9.16.2 Low Resistance or Current Zero Interruption
This method is used only in case of a.c. circuit breakers, At the natural current
zero point of a.c. wave, the arc is interrupted and is prevented from restriking though
there is high restrking voltage by increasing the dielectric strength of the contact gap.
This method is used in high power ac. circuit breakers
9.16.3 Artificial Current Zero Interruption
In HVDC ystems this method is employed for breaking d.c. currents where
current is made zero artificially.
9.17 lonization of Gases
The non-ionized gas is generally a good dielectric medium. But the ionized gas is
a conductor as it contains free electrons. In circuit breakers the contact space is ionized
by following ways,
9.17.4 Thermal lonization
At normal temperatures, molecules of gas are moving at various velocities in
various directions and possess K.E. as 5 mv?, With increase in temperature the
molecules break up in simpler form and then to atoms. At high temperature more and
more collision takes place which will produce free electrons thus produces the
ionization by heat and called thermal ionization.Protection and Switchgear 9-37 Theory of Arc Quenching
9.17.2 lonization by Collision
Any particle may be atom, molecule or electron at higher velocity may strike
another particle so that the energy of moving particle is imparted to other one. This
energy is sufficient to remove electrons from atoms. This is called ionization by
collision,
9.17.3 Thermal Emission from Surface of Contacts
Whenever contacts of a breaker are closed, they are pressed against each other at
high pressure. With the contact separation, the pressure between them reduces so true
area of contact is decreased to a few spots on the surface. Due to this, high current
density areas are produced which will cause high local temperature. Due to this,
thermal emission takes place at contact surface.
9.17.4 Secondary Emission at Contact Surface
Under the influence of strong electric field between the contacts the electrons move
from one contact to other producing emission from contact surface.
9.17.5 Field Emission
The voltage gradiant at the contact surface is high which is sufficient to remove
electrons from surface of electrodes since as contacts separate initially voltage gradiant
is very high which causes breakdown of gas. This is called field emission
9.17.6 Photoemission
The electron emission from contact surface due to incident of light energy is called
photoemission.
9.18 Deionization
In circuit breakers the deionization is an important process as it supports arc
extinction. This can be discussed in short as follows,
9.18.1 Recombination
If a gas contains positive ions and electrons then there is tendency between them
to combine and form a neutral atom. This is called recombination. This will assist arc
extinction as combination of positive ions and negative charges takes:place inside.
9.18.2 Diffusion
The electrons from highly ionized space diffuse to the surrounding weakly ionized
space which is an important process in building up dielectric strength.Protection and Switchgear 9-38 Theory of Arc Quenching
9.18.3 Conduction of Heat
This will make the temperature to reduce and will help recombination. Particles at
high temperature travel to the space at lower temperature. Thus kinetic energy is
removed from the space which is ionized between the contacts.
9.19 Arc Formation
As seen earlier the separation of contacts of circuit breaker results in high local
temperature on the contact surface. The contact surface get ionized due to thermal
emission and the electrons are emitted. The space between the contacts is ionized and
mes conducting. Thus the arc is initiated between the contacts.
be
The Fig. 9.27 shows general form of are voltage and arc current. It can be seen that
voltage is nearly constant when current is nearly at its maximum.
‘Arc volage
Are current
Fig. 9.27
The arc path is purely resistive and the are voltage is in phase with an are current.
When the contacts are separated the arc voltage increases due to increase in arc
length. The are voltage is increased till it becomes more than system voltage across the
contacts where arc gets extinguished.
9.20 High Resistance Arc Interruption Methods
The various methods of high resistance and interruption are,
1. Lengthening the are
2. Splitting of are
3. Cooling of are
9.20.1 Lengthening the Arc
In this method the arc length is increased by using arc runners which are horn,
like blades of conducting material. The arc runners are connected to arcing contacts
and it is in the shape of letter "V'. The arc is initiated at the bottom and blows
upwards due to electromagnetic force. Due to this arc length increases and
consequently arc is extinguished.Protection and Switchgear 9-39 Theory of Arc Quenching
Final position of are
Electromagnetic
fore in upward
direction
‘Asc initiation
Fig. 9.28 Arc lengthening
9.20.2 Splitting of Are
In this method elongation of are is done and the arc is split using arc splitters
which are specially made plates of resin bonded fibre glass. These plates are placed in
perpendicular path to arc so that it will be pulled towards it by electromagnetic force.
When the arc is pulled upwards it gets elongated then split and cooled due to which
it gets extinguished. This is shown in the Fig. 9.29.
H y ‘Spittor
Lengthening of art
‘Acc moving upwards
due to electromagnetic force
Arc
runners
Initiation of are
Fig. 9.28 Arc splitting
9.20.3 Cooling of Arc
As already seen, the recombination of
nized particles can be done by cooling the
arc which removes heat from the arc. This is done by bringing the arc in contact with
cooled air. Due to cooling the arc diameter reduces which will increase its resistance.
‘This will help in arc extinction.Protection and Switchgear 9-40 Theory of Are Quenching
9.21 Low Resistance or Zero Point Extinction
This method is used in a.c. are interruption. The current becomes zero two times
in a cycle. So at each current zero point the arc vanishes for small instant and again it
appears
But in ac. circuit breakers the are is interrupted at a current zero point. The space
between the contacts is deionized quickly if there is fresh unionized medium such as
oil or fresh ait or SF, gas between the contacts at current zero point. This will make
dielectric strength of the contact space to increase such that are will be interrupted
and discontinued after current zero. This action produces high voltage across the
contacts which is sufficient to reestablish the are. Thus the diclectric strength must be
build more than the restriking voltage for faithful interruption of arc, Then the arc is
extinguished at next current zero.
While designing the circuit breakers the care is taken so as to remove the hot
gases from the contact space immediately after the are. So that it can be filled by fresh
dielectric medium having high dielectric strength.
In summary we can say that the are extinction process is divided in thee parts,
a) Arcing phase
b) Current zero phase
c) Post arc phase
In arcing phase, the temperature of the contact space is increased due to the arc
‘The heat produced must be removed quickly by providing radial and axial flow to
gases. The arc can not be broken abruptly but its diameter can be reduced by the
passage of gas over the arc, When a.c. current wave is near its zero, the diameter of
the arc is very less and consequently arc is extinguished, This is nothing but current
zero phase. Now in order to avoid the reestablishment of arc, the contact space must
be filled with dielectric medium having high dielectric strength. This is post are phase
in which hot gases are removed and fresh dielectric medium is introduced,
9.22 Arc Interruption Theories.
There are two main theories explaining current zero interruption of arc
1) Recovery Rate Theory or Slepian's Theory
2) Energy balance theory or Cassie's Theory
9.22.1 Slepian's Theory
Slepian described the process as a race between the dielectric strength and
restriking voltage. After every current zero, there is a column of residual ionised gas
This may cause arc to strike again by developing necessary restriking voltage and this9
a1 Theory of Arc Quenching
voltage stress is sufficient to detach electrons out of their atomic orbits which releases
great heat.
So in this theory rate at which positive ions and electrons recombine to form
neutral molecules is compared with rate of rise of restriking voltage. Due to
recombination dielectric strength of gap gets recovered. So rate of recovery of
dielectric strength is compared with rate of rise of restriking voltage.
If the restriking voltage rises more rapidly than the dielectric strength, gap space
breaks down and are strikes again and persists,
In the Fig. 9.30,
a) Rate of dielectric strength is
more than restriking voltage Vota
© Restriking voltage
b) Rate of dielectric strength is less
than rate of rise of restriking
voltage,
The assumption made while
developing this theory is that the
restriking voltage and rise of dielectric Fig. 9.30
strength are comparable quantities
which is not quite correct. The second drawback is that the theory does not consider
the energy relations in the arc extinction. The arcing phase is not covered by this
theory so it is incomplete.
9.22.2 Cassie's Theory
Alternative explanation of above process is afforded by Cassie's theory or also
called Energy balance theory.
Cassie suggested that the reestablishment of are or interruption of an arc both are
energy balance process. If the energy input to an are continues to increase, the are
restrikes and if mot, are gets interrupted.
‘The theory makes the following assumptions :
a) Are consists of a cylindrical column having uniform temperature at its cross
section. The energy distributed in the column is uniform
b) The temperature remains constant.
¢) The cross section of the are adjusts itself to accomodate the arc current.
d) Power dissipation is proportional to cross sectional area of arc columnProtection and Switchgear 9-42 Theory of Arc Quenching
‘The energy equation as expressed by Cassie is given by,
dQ .
SQ = EEN
a
where Q = Energy content / length of are in em
E = volts /cm
Total current
N = Total power loss / cm
Breakdown occurs if power fed to the arc is more than power loss. The theory is
true for high currents.
Immediately after current zero, contact space contains ionised gas and therefore
has a finite post zero resistance.
Now there is rising restriking voltage. This rising réstriking voltage causes a
current to flow between the contacts. Due to this current flow, power gets dissipated
as heat in the contact space of circuit breaker.
Initially when restriking voltage is zero, automatically current and hence power is
zero. It is again zero when the space has become fully deionise and resistance between
the contacts is infinitely high. In between these two extreme limits, power dissipated
rises to a maximum. If the heat so generated exceeds the rate at which heat can be
removed from contact space, ionisation will persist and breakdown will occur, giving
an are for another half cycle.
|
Fig. 9.31 Waveform of a.c. areProtection and Switehgear 9-43 Theory of Arc Quenching
Examples with Solutions
ma Example 9.8: A 50 cycles, 3 phase alternator with grounded neutral has inductance
‘of 1.6 mH per phase and is connected fo busbar through a circuit breaker. The
capacitance to earth between the alternator and circuit breaker is 0.003 wF per phase.
The cirewit breaker opens when rms value of current is 7500 A., Determine the
following:
i) Maximum rate of rise of restriking voltage.
ii) Time for maximum rate of rise of restriking voltage.
iif) Frequency of oscillations
Neglect first pole to clear factor.
‘Solution :
i= 7500 A, L=16 mH, C = 0.003 pF
X= Infl = 2% 50% 16 x 10-3 = 0.502659
Peak value of active recovery voltage (Phase to neutral)
Eq = (ix Xi) x V2 = (7500 x 0.50265) x V2
= 53314083 V
f, = frequency of oscillations =
1
2nJLe
1
2na/1.6x 107 « 0.003 x 10°
= 72643.96 Hz
Maximum RRRV = Inf, Ep = 2x x 72643.96 x 53314083
= 2433443822 V/sec
= 2433.4438 V/psec
‘Time for maximum RRRV
_ WiC
2
= 3.4414 psec
iam Example 9.9 : [na short circuit test on @ 132 kV, 3-phase system the breaker gave the
following results pf. of the fault 0.4, recovery voltage 0.95 of fall line value, breaking
current is symmetrical and the restriking transient had a natural frequency of 16 KHz
Determine RRRV assuming that the fault is grounded. [AU-May-2006)Protection and Switchgear 9-44 Theory of Are Quenching
Solution :
v2x132
. 43
= KK, Ky Ey where Ky = sing
= 107.77 kV
= cos 0.4 = 66.42°
= sin (66.429 =
= 0.95
19165
el
(0.9165) (0.95) (1) (107.77) = 93.83 kV
Maximum e = 2 V,, = 2(93.83) = 187.66 kV
Maximum time = avEC,
Maxi ts ===
aximum 2h ~ Ixtexd “ee
Maximume _ 187.66
Average RRRV =e qisscip ” Hm0sT » 6 KViisec.
tii) Example 9.10: What is the prospective voltage ¢ across the stray capacitance of
0.0023 UF, when the instantaneous current chopped by circuit brenker is 7 A, The value
of the inductance in the circuit is 35.2 H ? IAU, Dee.-2004)
Solution : Prospective voltage appearing across C.B. is given by,
e= ijk
c
L = 352H
C = 0.0023 wF = 0.0023 x 10-* F
i=7A
(Gear
x
= 7(123710.74)
e = 865.97 kV
mam Example 9.11: A circuit breaker is rated at 1200 A, 1500 MVA, 33 kV, 3 sec,
3-phase. What are its rated breaking current and making current ? (AU, Dec.-2004]Protection and Switchgear 9-45 Theory of Arc Quenching
Solution :
MVA
V3xkV
= _ 1500x108
Vax 33% 108
= 26.24 kA
Rated symmetrical breaking current (rms) =
Rated making current = 2.55 x 26.24
= 66.92 kA
Short time rating = 26.24 kA for 3 sec.
um Example 9.12: A 3phase alternator has the line voltage of 11 kV. The generator is
connected to a circuit breaker. The inductive reactance upto the circuit breaker is
5.2./ phase, The distributed capacitance upto circuit breaker between phase and neutral
is 0,001 F. Determine peak restriking voltage across the CB, frequency of restriking
voliage transients, average rate of restriking voltage upto peak restriking voltage,
maximum RRRV. {AU, Dec.-2004]
Solution =
xl
En = 8.98 kV
B
X = 2afL
x 5
Ls so rage 7 001591 H
C = 0.001 pF
1. 1
2aVLC — 2n,(0.01591) (0.001 x 10-*)
Maximum restriking voltage = 2 E ,, = 2(8.98) = 17.96 kV
= 3990111 Hz.
e- Ea[1-coo gi]
= Ey geesinet,
a> *= ec
This is the expression of RRRV
Ea 898
VEC (0.01591) (0.001 <10*)
Maximum RRRV =Protection and Switchgear 9-46 Theory of Arc Quenching
= 2.251 kVijsec
Maximume _2x898_ 17.96
Maximumt ~ (/2f,) ~ (/2*39901.11)
Average RRRV
1.43 kViusec
him Example 9.13: In a system of 132 kV, the circuit phase to ground capacitance is 0.02
microfarad, the induétance is SH. Calewlate the voltage appearing across the pole of a
circuit brenker if a magnetic circuit of 8 A is interrupted instantaneously. Calculate the
value of the pre-insertion resistor to be used across the comtact space. (AU, May-2005]
Solution: L=S5H, C= 0.02 uP = 0.02 108 F
i=BA
Voltage appearing across poles of circuit breaker is given by,
Jes [5 - soni
V = ye =a 5 = evason 108
Vo = 126.491 kV
The value of resistance to be used across contact space is given by,
1{t
R= We
1/5 __
2¥0.02% 10%
450% 108)
R = 7.9056 kt)
mp Example 9.14: in a short circuit test on a circuit breaker the following readings were
observed on a single frequency transient time to reach the peak recovery voltage 40 sce
and the peak restriking voltage 100 kV. Determine the average RRRV and the frequency
of oscillations. {AU, May-2005]
Solution ; Average RRRV is given as,
Peak restriking voltage (E,,)
Average RRRV = Peakrestriking voltage (Eq)
verage Time to reach the peak (Fy,)
109
100%10 3509
Average RRRV = 2500 Vissec
Natural frequency {, is given by,Protection and Switchgear 9-47 Theory of Arc Quenching
1 1
2m 2(40«10-*)
© ays” 12500 He
12.5 kHz.
Review Questions
Define a circuit breaker ? Describe its operation in brief
Discuss the arc phenomenon ina circuit breaker.
What are different arc interruption methods ? Explain any ene in detail
Explain the following terms related to circuit breaker,
i) Arc voltage ii) Restriking voltage iii) Recovery voltage
Explain the fault clearing process by giving ascillographs of short circuit current,
Discuss the effect of various parameters on TRY.
Obtain an expression for rate of rise of restriking voltage.
Explain resistance switching as applied to cireutt breakers.
Explain in detail the theories which explain the arc extinction phenomenon.
Write @ note on interruption af capacitive currents,
White « nate on current chopping phenomenon.
. Explain in detail dc. current breaking.
. A 3 phase alternator has line voltage of 11 AV. The generator is connected to a circuit breaker. The
inductive reactance upto circuit breaker is 5.0 per phase. The distributed capacitance upto circuit
breaver between phase and neutral is 0.01 wF. Determine
2) Peak restriking voltage across circuit breaker
by Frequency of restriking voltage transient
©) Average rate of restriking voltage upto peak restriking voltage
) Maximum RRRV (Ans, : 18 kV; 12637 os ; 0.456 kV/isec: 714 Viusec)
. Ina short circuit test on a 3 pole circuit breaker of feult wre 0.4, the recovery coltage was 0.95
times full tine voltage. The breaking current was symmetrical. The frequency of oscillations of
restriking voltage tas 15000 cis, Estimate the average rate of rise of restriking voltage, The neural!
is grounded and fault involves earth. Neglect first pote to clear factor. (Ans. : 4.8 kVhisec)
5. In a system of 132 AY the circuit phase to ground capacitance is 0.01 mF, the series inductance is
6 H. Calculate the voltage appearing across the pole of a circuit breakers if a current of 10 A
{instantancous) is interrupted, Calculate value of the resistance to be used across contact space 10
climinate the restriking voltage transient tans. : 245 KV ; 12.25 kQ)
gooCircuit Breakers
10.1 Introduction
‘As already seen in the last chapter, whenever any fault occurs in the power
system then that part of the system must be isolated from the remaining healthy part
of the system. This function is accomplished by circuit breakers, Thus a circuit breaker
will make or break a circuit either manually or automatically under different
conditions such as no load, full load or short circuit. Thus it proves to be an effective
device for switching and protection of different parts of a power system.
In earlier days fuse was included in the protective system. But due to some
limitations they are not used in practice now a days. The main difference between a
fuse and circuit breaker is that under fault condition the fuse melts and it is to be
replaced whereas the circuit breaker can close or break the circuit without
replacement.
10.2 Requirements of Circuit Breaker
The power associated with the circuit breakers is large and it forms the link
between. the consumers and suppliers. The necessary requirements of circuit breakers
are as follows,
1. The normal working current and the short circuit current must be safely
interrupted by the circuit breaker.
2. The faulty section of the system must be isolated by circuit breaker as quickly
as possible keeping minimum delay.
3. It should not operate with flow of overcurrent during healthy conditions.
4. The faulty circuit only must be isolated without affecting the healthy one.
10.3 Basic Action of a Circuit Breaker
‘The Fig. 10.1 shows the elementary diagram of a circuit breaker. It consists of two
contacts a fixed contact and a moving contact. A handle is attached at the end of the
moving, contact. It can be operated manually or automatically. The automatic operation
needs a separate mechanism which consists of a trip coil. The trip coil is energized by
(10 - 1)Protection and Switchgear 10-2 Circuit Breakers:
secondary of the current transformer. The terminals of circuit breaker are brought to
power supply
Supply d
siding |G. Tip
contact col
So ‘Automatic
mechanism for
opening and closing
the circuit
contacts
Contacts open
Fixedt aa
contact Contacts closed
Fig. 10.1 Basic action of circuit breaker
Under normal working conditions the emf, produced in the secondary winding of
the transformer is insufficient to energize the trip coil completely for its operation.
‘Thus the contacts remain in closed position carrying the normal working current. The
contacts can be opened manually also by the handle.
Under abnormal or faulty conditions high current in the primary winding of the
current transformer induces sufficiently high emf. in the secondary winding so that
the trip coil is energized. This will start opening motion of the contacts. This action
‘will not be instantaneous as there is always a time lag between the energization of the
trip cireult and the actual opening of the contacts. The contacts are moved towards
right away from fixed contact.
‘As we have seen already the separation of contacts will not lead to breaking or
interruption of circuit as an are is struck between the contacts. The production of arc
delays the current interruption and in addition to this it produces large amount of
heat which may damage the system or the breaker. Thus it becomes necessary to
extinguish the arc as early as possible in minimum time, so that heat produced will
lie within the allowable limit. This will also ensure that the mechanical stresses
produced on the parts of circuit breaker are less.
‘The time interval which is passed in between the energization of the trip coil to
the instant of contact separation is called the opening time, It is dependent on fault
current level.
‘The time interval from the contact separation to the extinction of are is called
arcing time. It depends not only on fault current but also on availability of voltage for
maintenance of arc and mechanism used for extinction of arc.Protection and Switchgear 10-3 Circuit Breakers
10.4 Classification of Circuit Breakers
The circuit breakers are classified by various ways. The different criteria for
classification. of circuit breakers are as follows,
i) Interrupting medium fi) According to service
iii) Way of operation iv) Action
v) Method of control vi) Way of mounting
vii) Tank construction. Contacts
According to the interrupting medium the circuit breakers are classified as air
circuit breaker, air blast circuit breaker, oil it breaker and. magnetic blast circuit
breaker,
According to service there are two types of circuit breakers viz indoor circuit
breaker and outdoor circuit breaker.
Depending on the operation, the types of circuit breakers are gravity opened,
gravity closed and horizontal break circuit breaker.
On the basis of action, the circuit breakers are classified as automatic and
non-automatic circuit breaker.
According to method of control, the circuit breaker may be controlled directly or it
may be operated remotely. The remote control may be manual, pneumatic or electrical.
The way of mounting classifies the circuit breakers into panel mounted, rear of
panel or remote from panel type.
Depending on the tank construction, the circuit breakers are classified as separate
tank for each pole type or one tank for all poles type.
(On the basis of contacts, the different types of circuit breakers are Butt, Wedge,
Laminated flat contact, Explosion chamber ete.
Out of the various ways of classification of circuit breakers the general way of
classification is on the basis of medium used for arc extinction which is normally oil,
air, Sulphur Hexa Flouride (SF,) or vacuum,
Each type of circuit breaker is associated with its own adynatages and
disadvantages. We will now consider some types of circuit breakers in detail.
10.5 Air Blast Circuit Breakers
These type of circuit breakers were employed in earlier days for voltages ranging
from 11 to 1100 kV. At high voltages this type of circuit breakers are most suitable. In
this type of circuit breakers the compressed air is used for the arc extinction. Hence it
is called compressed air circuit breaker.Protection and Switchgear 10-4 Circuit Breakers
10.5.1 Construction of an Air Blast Circuit Breaker
The Fig. 10.2 shows the constructional details of air blast circuit breaker.
ELEVATION END-VIEW
One pole of an extra high voltage air blast circult-breaker
10,
TEE
Baga
1"
a
2
Details of double arc extinction chamber
1, Tank airreservior (receiver) |& Moving contact (in 3)
2. Hollow insulator assembly 9, Connection for current
3. Double arc extinction chamber 10. Compression springs
4. Preumatic operating mechanism 11, Openings for air outler
5 Operating rod 12, Arcing horns Optional
6 Pneumatic value 43, Resistance switching unit
7. Foved contact (in 3) 14, Enclosure
45. Port
Fig. 10.2 Construction of air blast circuit breakerProtection and Switchgear 10-5 Circuit Breakers
At the bottom there is a tank which is called air reservoir with the valves. On this
reservoir there are three hollow insulator columns. On the top of each insulator
column there is double arc extinguishing chamber, The current carrying parts are
connected to the arc extinction chambers in series. The assembly of entire are
extinction chamber is mounted on insulators as there exists large voltage between the
conductors and air reservoir.
The double arc extinction chamber is shown separately in the Fig. 10:2 (b). It can
bbe seen that for each circuit breaker pole there are six breaks as there are three double
arc extinction poles in series. Each arc extinction chamber consists of two fixed and
two moving contacts. These contacts can move axially so as to open or close. The
position depends on air pressure and spring pressure. The opening rod is operated by
the opening mechanism when it gets control signal (may be electrical or pneumatic).
This will lead to flow of high pressure air by opening the valve. The high pressure air
enters the double arc extinction chamber rapidly. Due to the flow of air the pressure
on moving contacts increases than spring pressure and contacts open. The contacts
wavel through a small distance against the spring pressure. Due to the motion of
moving contacts the port for outgoing air is clesed and the whole arc extinction
chamber is filled with high pressure air. But during the arcing period the air passes
through the openings shown and takes away ionized air of arc. In case of making
‘operation the valve is tured which connects hollow column of insulator and the
reservoir, The air is passed to the atmosphere due to which pressure of air in the
chamber is dropped to atmospheric pressure and closing of moving contacts is
achieved against spring pressure.
10.5.2 Working
An auxiliary compressed air system is required by this type of circuit breaker. This
will supply air to the air reservior of the breaker. During the opening operation, the
air is allowed to enter in the extinction chamber which pushes away moving contacts.
The contacts are separated and the blast of air will take ionized gases with it and
helps in extinguishing the arc. This will require only one or two cycles. There are two
major types.- cross blast and axial blast.Protection and Switchgear 10-6 Circuit Breakers
In cross blast type, the blast of air cuts across the arc. It is less frequently used in
the practice. In axial blast type, the blast of air is along the arc. This type of design is
common in use.
10..2.4 Cross Blast Type
The Fig. 10.3 shows the schematic arrangement of a cross blast type.
Ate spits
Fig. 10.3 Cross blast type circuit breaker
The flow of air is across the arc. The moving contact is near to the arc splitter
assembly. The air blast forces the are on to the arc splitter plates. These plates will
lengthen the arc, Depending upon the breaking capacity of the breaker, the size and
number of plates are decided. The fixed contact is mounted at the base between the
two insulating blocks. It consists of a number of silver surfaced spring loaded copper
fingers. The arcing portion is surfaced with a silver tungsten alloy. The moving
contact consists of flat copper silver faced blade, Resistance switching is not required
as sufficient resistance is automatically introduced in the arc to control the restriking
transient. The cross blast breakers are commonly used in indoor circuit breakers of
medium high voltage class.
10.5.2.2 Axial Blast Type
In this type the flow of blast of air is along the line of are. This is shown in the
Fig. 104.10-7 Circuit Breakers
Fixed
Opening
(a) (b)
Fig. 10.4 Axial blast type circuit breaker
There are two subtypes which are shown jn the Fig. 104 (a) and (b) viz single
blast type and double blast type. The double blast arrangement is also called radial
blast type due to the fact that the blast flows radially into the space between the
contacts,
In this type air flows from high pressure reservior to the atmosphere through a
nozzle, whose design makes air to expand in the low pressure zone. It will attain high
velocity. The high speed air flowing axially along the arc will cause removal of heat
from the periphery of the arc. The diameter of arc reduces to a low value at current
zero. At this instant of the arc interruption the contact space is filled with the fresh
air. This will make possible to remove the hot gases and fast building up of the
dielectric strength of the medium.
‘As already seen during the contact closing, the air from the extinction chamber is
allowed to pass to the atmosphere. This will reduce the pressure on the moving
contacts and will assist the closing operation. The total operation is represented in the
Fig, 105.Circuit Breakers
Protection and Switchgear 10
Awiliary
contacts
Resistor
uit
Terminal
‘Compressed air fram
Fig. 10.5 Modification in air blast circuit breaker
In air blast circuit breaker, the pressure generated in the extinction chamber is
independent of arc current the circuit breaker is said to be of external energy source
‘The air pressure in this type of breaker is constant which is sufficient enough to break
the rated breaking current. In this type of circuit breakers the breaking capacity is
found by pressure of extinguishing medium.
For low values of currents, the arcing time does not change appreaciably since
pressure is independent of arc current. For breaking low current, high pressure air
will be required. Due to this the current gets chopped before reaching natural zero.
This will give rise to high restriking voltage and the contact space is not likely to
break down. Therefore these high voltages must be allowed to discharge to avoid
breakdown of insulation of circuit breaker. Thus resistance switching is commonly
employed in these breakers.
The Fig. 10.5 shows the modified arrangement for a double arc extinguishing
chamber. When the contacts are opened the air flows in the arc extinguishing
chamber. The separating of main contacts lead to closing of auxiliary contacts which
will connect resistance across the arc for a short time. The auxiliary contacts are
mounted in inclined V shaped insulators.Protection and Switchgear 19-9 Circuit Breakers
After the arc extinction the pressure on either side of auxiliary contacts is adjusted
in such away that auxiliary contacts open and resistor circuit is interrupted. Ceramic
resistances of non-linear characteristics are used for resistance switching,
10.5.3 Compressed Air System for Air Blast Circuit Breaker
The schematic arrangement shown in the Fig. 10.6 represents compressed air
system.
on oo, as momvar
Fig. 10.6 Diagram of compressed air system
The air reservoir in the air blast circuit breaker contains air of pressure of the
order of 20-30 kg force/cm?, This air pressure is maintained by these reservoirs for
4 to 12 repeated operations.
When the pressure in the air reservoir of the circuit breaker reduces below a
cettain value say 20 kgffem*, the pneumatic valve opens automatically and air is
allowed to enter in the air reservoir from compressed air system at high pressure, The
pressure in the air reservoir is then maintained at a desired valueProtection and Switchgear 10-40 Circuit Breakers.
The size of compressor depends upon the number of circuit breakers, the number
of makes and breaks expected and amount of air to be used in each make and break.
The compressor feeds the air at high pressure into the main receiver through oil filters
and water filters.
10.5.4 Advantages
The various advantages of air blast circuit breakers are,
i) No fire hazards are possible with this type of circuit breaker.
ii) The high speed operation is achieved
iii) The time for which arc persists is short. Thus the arc gets extinguished early.
iv) As arc duration is short and consistent, the amount of heat released is less and
the contact points are burnt to a less extent. So life of circuit breaker is
increased.
v) The extinguishing medium in this type of circuit breaker is compressed air
which is supplied fresh at each operation. The arc energy at each operation is
less than that compared with oil circuit breaker. So air blast circuit breaker is
most suitable where frequent operation is required
vi) This type of circuit breaker is almost maintenance free.
vii) It provides facility of high speed reclosure.
viii) The stability of the system can be well maintained.
10.5.5 Disadvantages:
The various disadvantages of air blast circuit breakers are,
i) f air blast circuit breaker is to be used for frequent operation it is necessary to
have a compressor with sufficient capacity of high pressure air.
ii) The maintenance of compressor and other related equipments is required
iii) There is possibility of air leakages at the pipe fittings.
iv) It is very sensitive to restriking voltage. Thus current chopping may occur
which may be avoided by employing resistance switching.
10.5.6 Applications
‘The air blast circuit breakers are preferred for arc furnace duty and traction system
because they are suitable for repeated duty. These type of circuit breakers are finding
their best application in systems operating in range of 132 kV to 400 kV with breaking
capacities upto 7000 MVAProtection and Switchgear 10-11 Circuit Breakers
10.6 Air Break Circuit Breaker
In air circuit breakers the atmospheric pressure air is used as an are extinguishing
medium. The principle of high resistance interruption is employed for such type of
breakers, The length of the are is increased using are runners which will increase its
resistance in such a way that the voltage drop across the arc becomes more than the
supply voltage and the are will be extinguished,
‘This type of circuit breaker is employed in both a.c, and dc. type of circuits upto
12 KV. These are normally indoor type and installed on vertical panels, The
lengthening of are is done with the help of mangetic fields. Some typical ratings of
this type of circuit breaker are 460V - 3.3 kV with current range 400 - 3500 A or 6.6
kV with current range 400-2400 A ete.
10.6.1 Construction
The Fig. 10.7 shows the constructional details of air break circuit breaker.
(0) Contact closed (W) Contacts open
Principle of alt-break circuil-breaker
1. Main contacts 5. Arc splitier plates
2. Arcing contacts 6, Current carrying terminals
3 Are rising in the direction of the arrow 7. Arc runners
4. Are getting split
Fig. 10.7 Construction of air break circuit breakerProtection and Switchgear 40-42 Circuit Breakers.
It consists of two sets of contacts.
1) Main contacts
2) Arcing contacts
During the normal operation the main contacts are closed. They are having low
resistance with silver plating. The arcing contacts are very hard, heat resistant. They
are made up of copper alloy. Arc runners are provided at the one end of arcing
contact. On the upper side are splitter plates are provided.
10.6.2 Working
As seen from the Fig. 108 the
contacts remain in closed position during Contact
normal condition. Whenever fault occurs, “L-3
the tripping signal makes the circuit cumemt —
breaker contacts to open. The arc is
drawn in between the contacts
Whenever the arc is struck between
(a) Contact closed
the contacts, the surrounding air gets C4" NS ised gon
ionised. The arc is then cooled to reduce ®
the diameter of arc core. While (b) Gontacts separated
separating, the main contacts are Fig, 40.8 Working of air break circuit
separated first. The current is then breaker
shifted to arcing contains, Later on the
arcing contacts also start separating and arc between them is forced upwards by the
electromagnetic forces and thermal action. The arc travels through the arc runners.
Further it moves upwards and split by are splitter plates. Due to all this finally the are
gets extinguished as the resistance of the arc is increased.
Due to lengthening and cooling, are resistance increases which will reduce the
fault current and will not allow to reach at high value. The current zero points in the
ac. wave will help the arc extinction. With increase in arc resistance the drop across it
will go on increasing.
Whenever are leaves the contacts it is passed through are runners with the help of
blow out coils which provide a magnetic field due to which it will experience a force
as given by electromagnetic theory (F = BIl). This force will assist in moving the arc
upwards. The magnetic field produced is insufficient to extinguish the arc. For systems
having low inductances arc gets extinguished before reaching extremity of runners
because lengthening of are will increase the voltage drop which is insufficient to
maintain the are.Protection and Switchgear 10-13
suit Breakers
For high inductance circuits if it is not extinguished while travelling through are
runners then it is passed through are splitters where it is cooled. This will make the
effective deionization by removing the heat from arc,
10.6.3 Applications
This type of circuit breakers are commonly employed for industrial switchgear,
auniliary swithgear in generating stations
10.7 Sulphur Hexafluoride (SF,) Circuit Breaker
Pure sulphur hexafluoride gas is inert and thermally stable. It is having good
18 properties. It is also an electronegative gas and has
dielectric and arc exting
strong tendency to absorb free electrons. SF, gas remains in gaseous state upto a
temperature of 9° C. Its density is about five times that of air and the free heat
convection is 1.6 times as much as that of air. Also being inert it is non-inflamable,
non-poisonous and odourless.
The contacts of the breaker are opened in a high pressure flow of SF, gas and an
arc is struck between them The conducting electrons from the arc are captured by the
ammobile negative ions. The loss. of this conducting electrons
gas to form relativel
developes enough strength of insulation which will extinguish the arc. Thus SF, circuit
breakers are found to be very effective for high power and high voltage service and
widely used in electrical equipments. Only the care to be taken is that some
by-products are produced due to breakdown of gas which are hazard to the health of
the personnel and it should be properly disposed.
Several types of SF, circuit breakers are designed by various manufacturers in the
world during the recent years which are rated for voltages from 3.6 to 760 kV
The property of this gas is that the gas liquifies at certain low temperatures. The
liquification temperature can be increased with pressure This gas is commercially
manufactured in many countries and now used extensively in electrical industry
‘The gas is prepared by burning coarsely crushed roll sulphur in fluorine gas in a
steel box. The box must be provided with staggered horizontal shelves each containing
about + kg of sulphur. The steel box is gas tight. After the chemical reaction taking
place in the box, the SE, gas obtained contains impurities in the form of fluorides such
45 S,F\y SF, etc. Thus it must be purified before it is supplied. The manufacturing of
‘this gas at large scale reduces its cast.
The dielectric strength of SF, gas at any pressure is more than that of air. When
the gas comes in contact with the electric arc for long period, the decomposition
effects are small and dielectric strength is not considerably reduced and the metallic
fluorides that are formed are good insulators and are not harmful to the breaker.Protection and Switchgear 10-14
40.7.1 Properties of SF, Gas
The properties of SK, gas are divided as,
1, Physical properties
2. Chemical properties
3. Dielectric properties
10.7.1.1 Physical Properties
i) The gas is colourless, odourless, non-toxic and nonharmful to health,
ii) The gas is non-inflammable.
iii) It is heavy gas having high density.
iv) Liquification starts at low temperatures which depends on pressure.
v) The heat transferability is high as compared to air at same pressure
vi) The heat content property is much more which will assist cooling of arc after
current zero.
vii) ‘The gas is electronegative.
10.7.1.2 Chemical Properties
i) The gas is chemically inert and stable upto 500° C. The life of metallic part,
contacts is longer in SF, gas. The components do not get deteriorated. Hence
the maintenance requirements are reduced.
ii) During are extinetion, SF, is decomposed to SFy, SF; The products of
decomposition are toxic and hence proper care must be taken for their
disposal.
iii) The metallic fluorides are good dielectric materials. Hence are safe for electrical
equipment
10.7.1.3 Dielectric Properties
i) The dielectric strenght of SF, gas at atmospheric pressure is 29 times that of
air and 30% less than that of dielectric oil.
ii) At higher pressure, the dielectric strength of a gas increases. This is very much
advantageous as smaller clearances and small size of components are required
for same kV. The variation is shown in the Fig. 10.9
iii) The breakdown voltage in SF, gas is a function of pressure The gas follows the
Paschen's law which is given as "In uniformly distributed electric field the
breakdown voltage in a gas isdirecily proportional to the product of gas
pressure and electrode gap". The parameters affecting breakdown voltage areProtection and Switchgear 10-16 Circuit Breakers
vii) The breakdown is initiated at sharp edges of conducting parts having
maximum stress concentration. Good dielectric stress distribution is important
viii) The breakdown value depends on the wave shape characterised by peak value,
wave front, polarity in case of impulse wave etc. The breakdown voltages
reduces with increase in steepness and increase in duration of wave.
ix) Even with dilution of SF, with air, its dielectric strength is not much affected.
As already seen the gas is electronegative so arc time constant is lower which
is nothing but the time required to regain dielectric strength by medium after
final current zero. This time is of the order of few microseconds in this type of
circuit breaker,
10.7.2 Construction of Non-Puffer Type SF, Breaker
The Fig. 10.11 shows the constructional details of SF, circuit breaker. It consists of
arc interruption chamber wherein fixed and moving contacts are enclosed. The
chamber is filled with SF, gas, The chamber is connected to a reservoir containing SF,
as.
Insulated rods
for operating
moving member
Fixed
Thember
oon, &
SN
Fig. 10.11 Construction of SF, breal
When the contacts of circuits breakers are opened, the valve mechanism allows
high pressure SF, gas from the reservior to flow towards the arc interruption
chamber The fixed contact is a hollow, cylindrical current carrying contact fitted with
arc horn. The moving contact is also hollow cylinder containing holes in the sides to
permit SF, gas to pass through these holes after flowing across the arc. The tips of
fixed and moving contacts are coated with copper tungsten arc resistant material. TheProtection and Switchgear 10-18 Circuit Breakers
The single flow pattern has limited quenching ability and is used for breaking
currents. The four stages of puffer action explains arc quenching process in single flow
puffer type circuit breaker.
When breaker is fully closed, the pressure in puffer cylinder P; is equal to that of
outside the cylinder. But during opening operation, puffer cylinder and moving
contact tube start moving, Gas gets compressed withing puffer cylinder (P, > P,).
When contacts move further, are is drawn. The compressed gas flows from higher
pressure P, to lower pressure P2 through the nozzle.
After further advancement the flow pattern was improved. The gas from puffer
cylinder was allowed to flow in forward direction through nozzle and also in reverse
direction through hollow contact tube
‘Double flow removes the heat from the are efficiently and causes lengthening of
are, It gives the breaking capacity one and half times more than that of single flow
type. So now a days double flow pattern is used in SF, circuit breakers.
10.7.3 Single Pressure Puffer Type SF, Circuit Breaker
It employs puffer principle explained earlier. The Fig. 10.13 shows principle of
operation of single pressure puffer type SF, circuit beraker. The operating mechanism
(1) is installed at base of the insulator and is linked with movable contact in the
interrupter by means of insulating operating red (4) and a link mechanism (5):The
circuit breaker is filled with SF, gas at a pressure of about 5 kgf/cm*. The breaking
time obtained with puffer type breaker is nearly 3 cycles.
(a) Breaker fully closed (b) Contacts separated
1. Moveabia Cylinder ( Puffer Cylinder) 5, Fixed Piston
2. Moving Contact 6. Gas trapped in before compression
2. Fixed Contact 7, Compressed gas between 1 and 5
4. Insulating Nozzie 8. The arc being extinguished by puffer action
Fig. 10.13 Single pressure puffer type SF, breakerProtection and Switchgear 10-19 Circuit Breakers
In this case, gas is compressed by the moving cylinder system and is released
through a nozzle while extinetion of an arc.
The Fig. 10.13 (a) illustrates fully closed position of interrupter. Moving cylinder 1
is coupled with moving contact 2 against the fixed piston 5. As a result there is a
relative motion between 1 and 5 and the gas is compressed in the cavity 6, This
trapped gas is released through a nozzle hole, during arc extinction process. During
the travel of moving contact 2 and movable cylinder 1 gas puffs over the arc and
reduces arc diameter by axial convertion and radial dissipation. At current zero arc
diameter becomes too small and are gets extinguished.
The puffing action continues for sometime even after the are extinction until the
contact space is filled with cool and fresh gas.
10.7.4 Double Pressure Type SF, Circuit Breaker
In this type, gas from high pressure system is released into low pressure system
through a nozzle during are extinction process.
In this circuit breaker, gas is made to flow from zone P, to P; through a
convergent divergent nozzle. The nozzle is located such that flow of gas covers the
arc. Gas flow attains almost supersonic speed in divergent portion of nozzle, thereby
gas takes away the heat from periphery of arc causing reduction in diameter of the
arc. Finally arc diameter becomes almost zero at current zero and arc gets
extinguished. Arc space is filled with fresh SF, gas which increases dielectric strength
‘of contact space.Protection and Switchgear 10 - 20 Circuit Breakers
10.7.5 Advantages of SF, Circuit Breaker
10.
The disadvantages of this type of
The advantages of SF, circuit breaker are,
1. The s
rating.
mal circuit breaker of same
e of SF, breaker is smaller than conver
2. SF, gas is noninflammable and chemically stable, decomposition products are
not explosive hence no danger of fire
3. Same gas is recirculated in the circuit hence requirement of gas is small
4, Ample overload margin ; For the same size of conductors, current carrying
ability of SF, circuit breaker is about 15 times than that of air blast cireuit
breaker because of more heat transferability.
» The breaker is silent in operation and does not make sound like air blast
circuit breaker due to its closed gas circuit.
6. Sealed construction avoids contamination by moisture, dust ete:There are no
carbon deposites,
7. Minimum maintenance required for this breaker. It requires light foundation
and minimum auxiliary equipment.
8. Ability to interrupt low and high fault currents, magnetising currents,
capacitive currents without excessive overvoltages with small arcing time.
9. Problems connected with current chopping are minimum.
10. No contact replacement required. Contact corrosion is very small hence
contacts do not suffer oxidation.
7.6 Disadvantages
breaker are,
1. Sealing, problem arises due to the type of construction
2. Imperfect joint lead to leakage of gas
3. ‘The presence of moisture in the system is very dangerous.
4. Double pressure SF, circuit breaker are relatively costly due to type of
construction and complex gas system.
5. Internal parts should be cleaned thoroughly during periodic maintenance
under clean and dry environment.
6. Special facilities are needed for transporting the gas, which is very costly.
7. SF, breakers are costly as there is high cost of SF, gas.
8. Since the gas is to be reconditioned after every operation, additional equipment
is requited for the same.
9, Arced SF, gas is poisonous and should not be inhaled.Protection and Switchgear 10-21 Circuit Breakers
10.7.7 Applications
A typical SE, circuit breaker consists of interrupter units. Each unit is capable of
interrupting currents upto 60 kA and voltages in the range 50-80 kV. A number of
units are connected in series according to system voltage. SF, breakers are developed
for voltage ranges from 15 to 500 kV and power of 10 MVA to 20 MVA ratings and
with interrupting time of 3 cycles and less,
10.8 Vacuum Circuit Breakers
In vacuum type of cireuit breakers, vacuum is used as the are quenching medium.
It is superior medium than any other arc quenching medium as vacuum offers highest
insulting strength.
li we consider that the contacts of circuit breakers are opened in vacuum, the
interruption occurs at first current zero. The dielectric strength of the contact space
builds up very rapidly at a rate which is very much higher than that with other
circuit breakers
When the contacts of the breaker are opened in vacuum, an arc is produced
between the contacts due to ionisation of metal vapours of contacts, which can be
explained by field emission theory. An intensely hot spot is created at the instant of
contact separation because of high current density.But the arc is quickly extinguished
as metallic vapours, electrons and ions produced during the are are condensed on the
surface of the breaker.This will lead to fast recovery of dielectric strength. This is an
important feature of vacuum as an are quenching medium which will assist arc
extinction and restriking of are is prevented. The vacuum circuit breaker consists of
‘one or more vacuum interrupter units per pole.
The vacuum switching devices have several merits such as high rate of rise of
dielectric strength, silent operation, suitability for repeated operations, simple
‘operating mechanism, free from explosion and long life:
The unique quality of vacuum interrupters is that the contacts are required to be
travelled by small distance and less weight of moving contacts. Many repeated
‘operations can be performed with this type of breaker
10.8.1 Electrical Breakdown in High Vacuum
The pressure below about 10-5 mm of mercury are considered to be high vacuum.
The charged particles from one electrode moving towards other at such a pressure wi
not cause collision with the molecules of residual gas. Hence ionization by collision of
particles is less in vacuum as compared to in the gas.
If a small gap (say 0.5 mm) is kept between the electrodes in the vacuum and
voltage is gradually increased, at a certain voltage the gap breaks down and currentProtection and Switchgear 10-22 Circuit Breakers
increases rapidly, The phenomenon is called vacuum breakdown. With pressure
remaining constant the breakdown chracteristics are influenced by surface, condition
and material of electodes.
Due to high arc energy, electrons emission takes place from surface of the
electrodes. High heat is produced and core will be at very high temperature. Few
spots having high current densities are produced. Thus thermal emission takes place
from surface of electrodes which is a cause for arc formation in case of these breakers
10.8.2 Construction
‘The Fig, 10.15 shows the schematic representation showing the constructional
details of vacuum circuit breaker.
Fixe
Fig. 10.15 Construction of vacuum circuit breaker
It consists of vacuum chamber in which fixed contact, moving contact and are
shield are mounted, The movable member is connected to the control mechanism by
stainless steel bellows. The bellows permit the sealed construction of the interrupter
They are covered by protective shield . The contacts are made of large stem with large
disc shaped faces.The disc is provided with symmetrical grooves such that segments
of two contacts are not along same line. This geometry facilitates the rapid movement
of arc instead of ramaining stable at one point and arc remains in diffused state. The
enclosure is made up of impermeable insulating material like glass. The material
should not be porous and should have capability to retain high vacuum The
supporting end flanges are made up of non-magnetic metal.Protection and Switchgear 10-23, Circuit Breakers
‘The are shields or vapour shields are supported on insulating housing such that
they cover the contact region. The metal vapour released from the contact surface
during arcing is condensed on these shields and is prevented from condensing on the
insulating enclosure.
The possibility of leak is eliminated due to permanent sealing of vacuum chamber.
The outer insulator is made up of glass or ceramics
10.8.3 Working
‘When the contacts are separated due to some abnormal conditions, an arc is struck
between the contacts. The arc is produced due to ionisation of metal ions and depends
very much on material of contacts.
‘The arc interruption process in vacuum interrupters is different from other types
‘of circuit breakers. The separation of contacts causes release of vapour which is filled
in the contact space. It contains positive iens liberated from contact material. The
vapour density depends on the current in the are. When current decreases, the rate of
vapour release decteases and after current zero, the medium regains its dielectric
strength if vapour density is reduced.
When current to be interrupted is very small (of the order of few hundred amps)
in vacuum, the are has several parallel paths. The total current is divided into many
parallel arcs which repel each other and spreads over contact surface. This is called
diffused are which can be interrupted easily.
At high values of currents, the arc gets concentrated on a smalll region. It causes
rapid vapourisation of the contact surface. The interruption of arc is possible if arc
remains in diffused state. If it is quickly removed from the contact surface, the arc will
be restriked.
‘Arc extinction in vacuum breakers is greatly influenced by material and shape of
contacts and technique of condensing metal vapour.The path of the arc is kept moving
$0 that temperature at any one point will not be high
After final are interruption there is rapid building up of dielectric strength which
is pecularity of vacuum breaker. They are suitable for capacitor switching as it will
give restrike free performance. The small currents are interrupted before natural
current zero which may cause chopping whose level depends on material of contact.
‘The chopping levels are affected by,
a) The vapour pressure of cathode material with increase in vapour pressure, the
chopping level is lowered,
b) The thermal conductivity, if thermal conductivity is low and the chopping level
is also low. Current chopping level for some materials is given in the
Table 10.1Protection and Switchgear 10 +25 Circuit Breakers
grown from molten metal which releases small quantity of gas. But the process is very
slow, costly and commercially not feasible. The another possible solution to this
problem is to use zone-refined copper which is gas free.
The metals like aluminium, copper, silver, tin ete were tested for electrode erasion.
At high currents the cathode spots formed shows a high vapour pressure that is
supplied by vapourisation, The loss from cathode, causes gain in weight for anode
due to the condensation of cathode vapour on the anode when it is cold.
Another important thing that must be considered is that the electrodes should not
weld with each other and dielectric strength of the gap must be recovered very
rapidly,
Thus the requirements to be satisfied by a vacuum circuit breakers are
complicated. Hence no single metal is suitable for the electrodes. Thus the compromise
is made and it shows that use of dicopper magnesium (Cu,Mg), dicesium copper
(CuCe,), copper bismuth (CuBi) gives the satisfactory performance.
10.8.6 Recovery Strength Characteristics
The satisfactory working of vacuum circuit breaker is possible if the electrical
strength after arcing is properly recovered. In this type of the breaker, the conducting
medium of the arc is supplied by contact erosion and recovery of electric strength
mostly depends on condensation of electrode vapour.
A reduction in number of vapour ions lead to improvement in recovery strength
When pressure is reduced to such a value that the breakdown voltage is
independent of pressure then under this case, the factors affecting breakdown voltage
are the type of contacts, contact surface etc. Highly polished electrodes has good
breakdown strength.
10.8.7 Applications
In countries like India, the installation of such breakers proves to be effective as it
requires little maintenance. They are employed for outdoor installations ranging from
22 kV to 66 kV. With limited rating ranging from 60 to 100 MVA they are suitable in
many applications,
Recently installed capacities of such breakers are 11 kV, 25 kV and 33 kV.
Thus for voltages upto 36 kV, vacuum circuit breakers with single interrupter is
becoming extremely popular for metal enclosed switchgear, arc furnace installations,
auxiliary switchgear in generating stations and other industrial applications.
10.9 Oil Circuit Breakers
These are one of the oldest type of circuit breakers which employs oil as arc
quenching medium. The contacts of the circuit breakers are separated in the oil. TheProtection and Switchgear 10-26
bubbles of gas are formed which prevent restriking of the arc after the current reaches
zero point of the cycle. There are two types of oil circuit breakers,
1) Circuit breakers using large quantity of oil or the bulk oil circuit breakers.
2) Circuit breakers using minimum quantity of oil called minimum oil circuit
breakers
After the current zero, the oil moves in the arc space which is an important part of
the action of an ail circuit breaker which may be effected by,
L) the pressure developed due to natural head of oil above contacts.
2) the pressure generated by the action of arc current itself.
3) the pressure developed by external parameters.
Thus the oil circuit breakers are further grouped into following categories,
1) Plain break oil circuit breakers.
2) Self generated pressure oil circuit breakers (also called self blast oil circuit
breakers.)
3) Externally generated pressure oil circuit breakers (also called force blast oil
circuit breakers.)
10.9.1 Plain Break Oi) Circuit Breaker
It consists of a strong, weather tight earthed tank containing oil upto certain level
and air above the oil level. Both the fixed and moving contacts are immersed in oil.
When the contacts are separated, an arc is struck between the contacts with -
production of large amount of heat. This will increase the temperature to near about
5000°K which will vapourize the oil into gases such as hydrogen with small
percentage of methane, ethylene and acetylene. With the withdrawl of moving contact,
arc length increases and gas formation rate decreases as temperature lowers.
When distance between fixed contact and moving contact reaches at critical value,
the arc gets extinguished at some current zero.
There are two types of plain-break oil circuit breakers,
a) Single break oil circuit breaker
b) Double break oil circuit breaker.
10.9:1.1 Single Break Oil Circuit Breaker
The single break oil circuit breaker principle is represented in the Fig. 10.16. The in
and out of the current is through the terminal bushings. There is only one arc which
is struck between the fixed and moving contact. The current breaks at one bushing
and the moving contact is supported by the other bushing through sliding contact.Protection and Switchg: 10-27
Current{
Terminal
bushings
Top piate
Driving
Oil level
Fig. 10.16 Single break oil circuit breaker
10.9.1.2 Double Break Oil Circuit Breal
The principle of this type of circuit breaker is shown in the Fig. 10.17. There are
two fixed contacts associated with terminal bushing which makes contacts with the
‘Air cushion
Terminal
Fig. 10.17 Double break circuit breakerProtection and Switchgear 10-28 Circuit Breakers
moving contacts during normal operating condition, The lever containing the moving
contacts can be operated with the help of crank.
When the contacts are separated, two ares are drawn. Thus there are two breaks in
series, This can achieve rapid are lengthening which eliminates the need for a specially
fast moving contact speed. But this introduces unequal voltage distribution across the
breaks with uneven sharing of total interrupting duty. One break may take 70 to 80
percent of the interrupting duty.
When such a breaker interrupts an earth fault, the recovery voltage is not equally
divided between the two breaks. This statement can be very well understood by
considering the eguivalent electrical circuit shown in the Fig. 10.18, where C,
represents. capacitance between fixed and moving contacts whereas C; represents
capacitance between moving contact and earth
fa) (b) Equivalent circuit
Fig. 10.18
Let I be the fault current
From the Fig. 10.18 (b),
v= volts
aq
oG@sc) “Ns
Let C = 10 pF and C; = 40 pF being typical values in practice.
My _ oC +z) _ G+
Vy oG Cc
Vi. 10440 _ 50
¥. 0 10Protection and Switchgear 10-29 Circuit Breakers.
v= 5Vp
It can be seen from the above expression that about 83% of the system voltage
appears across gap and only 17% appears across moving contact and earth. In order to
equalize the voltage across the gaps, high resistances or capacitors are connected
across them.
Fig. 10.19 Capacitive voltage grading
Let a capacitor of 50 pF be connected as shown in the Fig. 10.19.
Vi tC, +Cy _ 10440450
Now, Vi G+, 050
100
60)
= 1.66
V, = 1.66 V,
Thus V; becomes equal to 1.66 times that of V;. If value of Cy is chosen to be high
then the difference between V, and V2 can be further reduced. If instead of capacitors,
high values of resistors are used it will also cause damping. The resistance values are
generally of the order of 10,000 to 100,000 ohms. The resistor selected may be
non-linear one.
10.9.1.3 Factors Affecting Performance of Plane Break Oil Circuit Breaker
The factors which influence the performance of plain break oil circuit breakers are
as follows,
i) The critical length of the break
ii) The speed of the contact movement. In order to extinguish the arc earlier, the
speed should be high therefore double break circuit breakers are preferred.
iii) The head of oil above the contacts.
iv) The clearance between the live contacts and the earthed pressurized tank,Protection and Switchgear 10-30 Circuit Breakers
The factors which influence on increased breaking capacity are considerable head
of oil and large clearances. Thus for large breaking capacity, the circuit breaker will be
large.
10.9.1.4 Advantages of Plain Break Oil Circult Breaker
The various advantages of plain oil circuit breaker are,
i) The arc energy is easily absorbed by the oil due to its decomposition.
ii) The gases formed due to oil decomposition has good cooling properties
iil) The cooling surfaces formed by surrounding oil is clase to the are.
iv) After current zero a flow of cool oil flows in the contact space which is having
dielectric strength.
v} The oil used aets as an insulator.
10.9.1.5 Disadvantages of Plain Break Oil Circuit Breaker
The various disadvantages of plain break oil circuit breaker are,
i} There is no special control over the arc other than the increase in length by
separating the moving contacts. Hence large arc length is required for faithful
interruption.
ii) These breakers have long and inconsistent arcing times.
iii) These breakers do not permit high speed interruption
10.8.1.6 Applications
Such types of circuit breakers are suitable upto 150 MVA capacity and hence
installed in low capacity applications having voltages not more than 11 kV
10.9.2 Self Generated Pressure Oil Circuit Breaker
This type of circuit breakers are also called self blast oil circuit breakers where are
control is provided by internal means. The pressure developed by the arc is used in
speeding up the movement of oil in the contact space at the instant after the current
zero. This is achieved by surrounding the contact by a pressure chamber. This will
make it possible to increase the breaking capacity of such circuit breaker while the
arcing time is reduced,
The action of arc will itself set up pressure which is dependent on magnitude of
currents. Thus proper design of pressure chamber must be done in order to ensure
that pressure developed is sufficient to extinguish the arc at low currents, while it
should not be excessive which may break the chamber at heavy currents. Thus a wide
variety of designs are possible. Some of them are discussed belaw.Protection and Switchgear 10-31 Circuit Breakers.
10.9.2.1 Plain Explosion Pot
This is shown in the Fig. 10.20. It consists of a
Fixed rigid cylinder made up of a insulating material.
contact, The cylinder contains the fixed and moving
contacts. The moving contact is a cylindrical rod
which can pass through a small opening called
Por throat. The motion of moving contact is vertical.
Whenever fault occurs in the system the
contacts will start separating with the formation
Mouing of arc in between them. The heat contained in the
contact arc causes the decomposition of the oil into a gas
at very high pressure in the pot. This high
pressure forces the oil and gas around the arc to
Fig. 10.20 Piain explosion pot
extinguish it
It can be seen that if the final arc interrupt‘on does not take place while the
maving contact is inside the pressure chamber then it occurs immediately after the
moving contact leaves the pot as emergence of moving contact from the pot allows a
high velocity axial blast of gas to release through the throat producing rapid are
extinction. As the arc extinction takes place axially of the arc, it is also called axial
explosion type.
‘The major drawback with this type is that it cannot be used for very high or very
low fault currents. At low fault current values, the pressure developed is small thus
arcing time is increased. On the other hand at high fault currents due to very high
pressure developed there is possibility of bursting the explosion pot or chamber.
Therefore it is suitable for moderate short circuit currents only.
§.2.2 Cross Jet Explosion Pot
It is the modification of plain explosion pot which is shown in the Fig. 10.21. The
Fig, 10.21 shows the four stages of operation. It consists of cylinder made up of
insulating material. There are channels on one side which act as arc splitters. The use
of arc splitters is to increase the arc length which will assist arc extinction by
lengthening the arc.
In stage 1 shown in Fig, 10.21, the moving contact has separated from the fixed
contact and an are is formed while in stage 4 final arc extinction is shown where the
moving contact is out of the throat:
When an fault occurs, the moving contacts begin to separate. An arc is struck
initially at the top of pot. The gas formed exerts pressure on the oil when the moving
contact moves away from the arc splitter ducts, fresh oil is forced across the path ofProtection and Switchgear
10-32
Circuit Breakers
Explosion
chamber
ta) tb)
co) te)
Fig. 10.21 Cross jet explosion pot
arc. The arc is then passed through the arc splitters due to which its length increases
which causes the are extinction.
This type of circuit breaker gives satisfactory performance at heavy fault currents.
However for small fault current, pressure developed by gas which is function of fault
current is less and the performance is not satisfactory.
10.9.2.3 Self Compensated Explosion Pot
Fixed contact
[fila
| LAZY
Lateral
orifices:
Cross jet
‘explosion pot
RSS
L,
Moving contact
Fig. 10.22 Self compensated explosion pot
This type is essentially a
combination of plain explosion and cross
jet explosion type. Hence it can interrupt
low as well as heavy short circuit
currents effectively. Tt is represented in
the Fig. 10.22
It consists of two chambers, the
upper chamber is the cross jet explosion
pot with arc splitter ducts, while the
lower chamber is the plain explosion
pot.
When fault current is heavy, the rate
of generation of gas is very high and it
will act similar to cross jet explosion pet.
When the moving contact moves away
from the arc splitter duct, the arc
extinction takes place,Protection and Switchgear 10-33 Circuit Breakers
When fault current is low the rate of gas generation is low and the tip of moving
contact takes some time to reach lower chamber. By this time the gas builds up
sufficient pressure as there is no much leakage. When the moving contact comes out
of throat the arc is extinguished by plain pot action,
With increase in fault current level, the operation will tend more and more similar
to cross jet explosion pot. Thus interruption of fault current is possible in the wide
range.
10.9.2.4 Oil Blast Explosion Pot
Fixed cantact It is shown schematically in
i the Fig, 10.23. It consists of an
Gos producing js
chamber intermediate contact along with
moving contact. Initially the
intermediate contact and lower
moving contact move
downwards together, An arc is
(prermediate struck between 1 and 2. The arc
causes oil in upper chamber to
Hollow moving be subjected to high pressure.
When the intermediate contact
Fig. 10.23 Oil blast explosion pot has reached its maximum travel,
the lower contacts start moving
away from it and arc is struck between 2 and 3. Since the lower contact is hollow rod
it is shut down by pressure which was developed by first arc. But this type has a
disadvantage of long arcing time.
10.9.3 Forced Blast Oil Circuit Breakers
In the self blast oil circuit breakers, the pressure was developed due to the arc to
force the oil across the arc path. The major disedvantage with this type is long arcing
Himes and inconsistancy at lower currents as pressure developed is insufficient to force
the oil in arc path. This difficulty is overcome in force blast oil circuit breakers which
will not relay on the arc to generate the pressure but it is supplied from some external
source:
This can be achieved by piston cylinder arrangement. The movement of piston is
coupled. mechanically to moving contacts or spring released by tripping mechanism.
‘This arrangement enables high speed interruption.
When a fault occurs, the contacts get separated and an arc is struck. The piston
forces a jet of oil towards the contact gap which will extinguish the arc, The typical
scheme is shown in the Fig. 10.24.Protection and Switchgear 10-34 Circuit Breakers
i
A
4
escavesarswcseperaesespreseeN
TE fs
i Fixed
Moving contact
sss
Fig. 10.24 Externally generated pressure breaker
The performance of the
breaker is constant even at low
currents as pressure developed
is independent of fault current
to be interrupted. This can be
seen from following graph
represented in the Fig. 10.25.
Another advantage is that
quantity of oil required is
Self pressure
Arc duration in see
Breaking current
reduced considerably. If Fig. 10.25 Operating time-breaking current
current chopping is there characteristics
while interrupting small
inductive currents then damping by resistance switching is required.
10.10 Low Oi! or Minimum Oil Circuit Breaker
With the increase in system voltage the quantity of oil in bulk oil circuit breakers
also increases. It gives additional expenses, increases the risk of fire and causes
maintenance problem. This will make necessary the design of a type of circuit
breakers which requires a low volume of oil. It is observed that oil serves two
purposes. Firstly it acts as arc quenching medium and secondly it insulates live parts
from earth. It is found that only a small percentage (about 10%) of oil is used for arc
extinction process and major part is used for insulation purposes.
A low or minimum oil circuit breaker uses a small container having oil which is
just enough for arc extinction. The container of oil is supported on porcelain
insulators, so that required insulation can be obtained for live parts from earth. Thus
low oil circuit breaker has added advantage that it requires less space than the bulk
il type. This is an important consideration in large installations.
With respect to quenching of arc, the oil behaves identically in bulk as well as low
oil circuit breaker. By using suitable are control devices the arc extinction can be
further facilitated in low oil circuit breaker.Protection and Switchgeal
Circuit Breakers
10.10.1 Construction
The Fig. 10.26 shows the constructional details of a single phase minimum oil
circuit breaker.
Fixed contact
‘Arc xtintion
‘davies
Moving
contact
Operating
red
Fig. 10.26 Const
ion of minimum oil circuit breaker‘Switehgear and Protection 10-36 Circuit Breakers:
It consists of two separate compartments which are separated from each other.
Both these compartments are filled with the oil The upper chamber is called the
circuit breaking chamber while the lower chamber is called the supporting chamber.
The two chambers are separated by a partition and oil from both the chambers are
prevented from mixing with each other. This type of arrangement has two advantages.
just
sufficient for arc extinction. Secondly small amount of oil is to be replaced as the oil in
the supporting chamber does not get contaminated by the arc.
Firstly the circuit breaking chamber requires a small volume of oil which is
1) Supporting Chamber ; This is a bottom chamber which is made up of
procelain and mounted on metal chamber. It is filled with oil which is
physically separated from the oil in circuit breaking chamber. The oil inside
the supporting chamber and the annular space formed between the porcelain
insulation and backelised paper is employed for insulation.
2) Circuit Breaking Chamber : It is a porcelain enclosure which is mounted on
the top of the supporting compartment. It is also filled with oil and consists of
following parts
i) Upper and lower fixed contacts
ii), Moving contact
ifi) Turbulator
The moving contact is hollow. It consists of a cylinder which moves down over a
fixed pistion, The turbulator forms an are control device and it has both axial and
radial vents, The axial venting ensures the interruption of low currents whereas radial
venting ensures interruption of heavy currents.
3) Top Chamber : It is a metal chamber mounted on the top of circuit breaking
chamber. It provides expansion space for the oil present in circuit breaking
chamber. It also contains a separator which avoids loss of oil by centrifugal
action caused by circuit breaker operation during fault conditions.
10.10.2 Operation
Under normal operating conditions, the moving contact and fixed contacts are in
engaged position. During abnormal conditions the moving contact is pulled down by
the tripping springs. With the separation of contacts, an arc is struck between them.
The energy in the arc causes vapourisation of oil This will produce gases at high
pressure. This action prevents the oil to pass through central hole in the moving
contact and results in forcing series of oil through the passages of the turbulator. The
process of turbulation is one in which sections of the arc successively quenched, by
the effect of separate streams of oil moving across each sectionProtection and Switchgear 10 - 37 Circuit Breakers.
10.10.3 Maintenance of Oil Circuit Breakers
The maintenance of oil circuit breakers consists of checking of contacts and
dielectric strength of the oil. After fault has been interrupted by circuit breaker, fault
current flows for short time or load currents for several times, its contacts may be
burnt due to arcing, Also there may be some loss of dielectric strength of oil due to
carbonisation. This will reduce rupturing capacity of the breaker, Thus periodic
checking of circuit breakers is essential after regular interval of 3 or 6 months.
Following points should be kept in mind while checking,
i) Check the current carrying parts. It they are burnt replace them.
ii} Check the dielectric strength of oil. If its colour is changed then it should be
changed or reconditioned. The oil in good condition withstands 30 kV for one
minute with 4mm gap between electrodes.
iii) Check the insulation for any damage. Clean the surface with removal of carbon
deposites with strong and dry fibric.
iv) ‘The oil level should be checked.
v} The closing and tripping mechanism should be checked.
10.10.4 Advantages
‘The advantages of minimum oil circuit breaker are,
i) The quantity of oil required is small.
fi) The space requirement is reduced.
ili) The risk of fire is reduced.
10.10.5 Disadvantages
‘The disadvantages of minimum oil circuit breaker are,
i) Due to smaller quantity of oil, the degree of carbonisation is increased
ii) The gases are difficult to remove from the contact space in time.
iii) The dielectric strength of the oil deterorates rapidly as degree of carbonisation
is high,
10.10.6 Applications
Minimum oil circuit breakers are now available for all voltages and for the highest
breaking capacity hence preferred in most of the protection schemes.Protection and Switchge
10.11 HVDC Circuit Breaker
In ac. circuit breakers, are extinction is achieved at the natural current zero of the
ac, waveform used. But in d.c. circuit breakers, natural zero of voltage and current is
not available as both are continuously available. Thus for extinction of an arc, artificial
current zero is required to be introduced. Such an artificial current zero is possible by
connecting LC circuit in parallel with the circuit breaker. The LC circuit is responsible
to produce oscillatory arc currents having many artificial current zeros. At one of the
artificial current zero arc gets extinguished.
10-38 Circuit Breakers
The Fig. 10.27 shows the
Circuit breaker principle of HVDC circuit
vatege* To breaker. The HVDC circuit
De ‘ood breaker is nothing but a vacuum
circuit breaker. The LC circuit
along with a switch is connected
| in parallel with this circuit
6 Lo Seren breaker.
—_—__—_—_— ‘i i
Paratal CG aroun The capacitor C used is
to introduce arificial precharged capacitor with the
surrent zara polarities as shown in the
Fig. 10.27. When the circuit
breaker starts. opening, the
switch in the LC circuit gets
closed. Due to the charged capacitor, the discharging current starts flowing in opposite
direction to that of load current carried by the circuit breaker. Due to this, arcing
current starts oscillating, producing many natural zeros. Thus artificial commutation
results and arc extinction is achieved.
Fig. 10.27 HVDC circuit breaker
The large transient recovery voltage is the main constraint in HVDC circuit
breaker and circuit breaker must able to withstand it. For successful operation of such
a circuit breaker, the switch in LC circuit must be a high speed switch with a very fast
response. Such systems are complex and very costly as they require costly protection
and control systems.
10.12 Selection of Circuit Breaker
The following parameters are required to be known for selecting proper rat
circuit breaker at a given location on a power system :
i) The maximum fault current which is to be interrupted by the breaker.
ii) The maximum current to be carried momentarilyProtection and Switchgear 10-39 Circuit Breakers
As it is discussed previously the fault current consists of both ac. and dic
components and its correct calculation is very complex. A simplified method is
recommended by IEEE committee is given below :
1, To determine firstly the required interrupting capacity of circuit breaker the
highest value of initial rms alternating current for any type and location of
fault. It can be considered as three phase fault as it carries maximum fault
current except in some cases. This current can be obtained by using
sub-transient reactance for generators and transient reactance for synchronous
motors while induction motors are to be neglected, Following multiplying
factors can be applied to take into account the d.c. components of currents and
decrements of both a.c, and de. components.
8 cycle or slow breaker 1.0
5 cycle breaker 1
3 cycle breaker 12
2 cycle breaker 14
Before applying multiplying factor, all the given factors are increased by 0.1 for
the breakers on the generator bus where 3 phase short circuit kVA exceed
500,000.
2. To determine the required rated momentary current with time 1 sec or less of
a breaker, The calculation of highest value of initial rms a.c, current can be
done as given in the step (1) except using sub-transient reactances of all the
machines including induction motors. Multiply the value of current obtained
by 16.
Momentary rated rms current of a circuit breaker = 15 x
Xi
mm Example 10.4: A generator connected through 5 cycle CB to a transformer is rated
S000 KVA with the reactances of Xy"= 10 %, Xy = 16 % and Xy = 100%. Ibs
operating at no load and rated voltage when 3 phase short circuit occurs between
breaker and transformer. Find
i) sustained short circuit in breaker
ii) the initial symmetrical rms current in breaker
maximum possible d.c. component of short circuit in breaker
iv) the momentary current rating of the breaker
v) current to be interrupted by breaker vi) the interrupting kVA
Solution : Let the base be 8000 kVA.
8000
Sustained short circuit kVA = 100 = 8000 KVA. as Xy = 100 %10+40 Circuit Breakers
Sustained short circuit current =
Let Vy = 138 kV
Sustained short circuit current = _8000 = 334.70 A
Vix 138
Sub-transient short circuit KVA = 008 100 = 80000
Sub-transient or initial symmetrical current = —600*100__ sau795 4
© lWxvdx 13.8
Maximum possible d.c. component = J2%3347.05 = 4732.73 A
Momentary current rating = 1.6 x 3347.05 = 5355.28 A.
Current to be interrupted = 1.1 x 3347.05 = 3681.75 A
Interrupting kVA = J3x 368175x138 = 8799.836 kVA
10.13 Circuit Breaker Ratings
A circuit breaker is a mechanical switching device capable of making, carrying and
breaking current under normal circuit conditions and also making, carrying for
specified time and breaking current under specified abnormal conditions.
The circuit breaker is also required to perform some additional functions as the
application demands such as,
i) to provide selectivity with breakers
il) to provide facility for remote closing and tripping
iii) to provide facility for interlocking
iv) to provide facility for indication
Some of the important characteristics or ratings that must be possessed by every
high voltage a.c. circuit breaker arc as follows,
1. Rated voltage
Rated insulation level
Rated normal current
Rated frequency
Rated duration of short circuit
Rated short circuit breaking current
Rated short circuit making current
Rated peak withstand current
exe PeenProtection and Switchgear 10-44
9. Rated TRV for terminal fault
10. Rated operating sequence
11. Rated supply voltage for opening and closing devices and auxiliary circuits
12. Rated pressure of compressed gas for interruption
10.13.1 Rated Voltage
It is a voltage of a circuit breaker which refers to higher system voltage for which
it is designed, It is expressed in kV and the value is rms, value. In case of three
phase circuits it is nothing but phase to phase voltage. A circuit breaker must be
assigned two voltage ratings one corresponding to maximum nominal system voltage
and other maximum design voltage which indicated the maximum operating voltage
which should not be exceeded.
10.13.2 Rated Insulation Level
The different circuit breakers connected in power system are subjected to power
frequency over voltages due to various effects such as regulation, Ferranti effect ete.
The circuit breaker must withstand this overveltage. This can be tested by carrying out
different tests. During some single phase to ground faults voltage of healthy line to
earth increases. So higher values of insulation are suggested. The insulation is
provided for each pole external and internal between live parts and earth. It is also
provided between poles and between terminals of same pole internal and external.
10.13,.3 Rated Current
It is defined as rm.s. value of the current that can be carried by the circuit breaker
continuously with temperature rise within the specified limits. Some of the preferred
values of rated currents are 400, 630, 800, 1250, 1600, 2000 A rms. etc. The rated
current of a circuit breaker can be checked by carrying out temperature rise tests. The
current carrying parts along with the contacts are designed based on temperature rise.
For given cross section of a conductor and certain value of current, the temperature
rise is dependent on conductivity of material. Hence while designing high conductivity
material must be used. If material is having low conductivity then cross-section of the
conductor is increased,
410.13.4 Rated Frequency
The performance of circuit breaker is greatly influenced by frequency. The
different characteristics like breaking capacity are based on rated frequency. With
increase in frequency, eddy currents in the metallic parts will increase which will
cause more heating and rise the temperature of current carrying parts, Hence if a
circuit breaker designed for one particular frequency is used at some anotherProtection and Switchgear
frequency then temperature will not remain in specified limits. So the rating is to be
changed accordingly.
The breaking time is also affected by the frequency as it is associated with time for
half cycles during are extinction. The breaking time decreases with increase in
frequency.
The frequency has a pronounced effect on TRV and rate of rise if TRV. So a circuit
breaker designed for one particular frequency can not used for other frequency unless
the results are faithful for that frequency.
10.13.5 Rated Duration of Short Circuit
‘The short time current of a circuit breaker is t.m.s. current that it can carry in a
closed position during specified time under given conditions. It is expressed in kA for
a period of one second, The rated duration of short circuit is commonly 1 second. The
circuit breaker must carry the current equal to its breaking capacity for this duration.
This can be tested by carrying out short time current test and checked that the poles
are not getting damaged or welded. The insulation should not be damaged. The poles
must be able to withstand the mechanical force developed. The design for normal
current rating is sufficient to carry short circuit current for 1 sec.
10.13.6 Rated Short Circuit Breaking Current
it is rms. value of highest short circuit current which the circuit breaker is
capable of breaking under specified conditions of TRV and power frequency voltage
and expressed in KA r.m.s. at contact separation.
The voltage appearing across circuit breaker after arc interruption is nothing but
Transient Recovery voltage. The limit on breaking current is governed by specified
conditions of TRV and power frequency recovery voltage. This limit is determined by
carrying short circuit test. The current waveform is shown in the Fig, 10.28.
Fig. 10.28Protection and Switchgear 10-43 Circuit Breakers
The breaking current is expressed by two values
i) The rms. value of a.c. component at the instant of contact separation given by
Tae
“
v2
ii) The percentage dic. component at the instant of contact separation given by
Tyee 100
Tae
The standard values of r.m.s. currents are 8, 10, 123, 16, 20, 25, 31, 5, 40 kA ete.
In earlier days-the breaking capacity is expressed in MVA so that fault levels can
also be determined. But now it is expressed in kA for specified conditions of TRY.
10.13,7 Rated Short Circuit Making Current
This is defined as the peak value of first current loop of short circuit. current
which the circuit breaker is capable of making at its rated voltage. There are certain
cases under which the circuit breaker may close when fault is existing. Under such
cases current reaches to maximum value at peak of first current loop, The circuit
breaker should be able to close without difficulty and withstand the mechanical forces
developed during a closure. This is checked by carrying out making current test
Rated making current = 1.8 x {2 Rated short circuit breaking
25 x Rated short cireuit breaking current
{2 in above expression converts rans. value to peak value while factor 1.8 is
considered for doubling effect of short circuit current
10.13.8 Rated Peak Withstand Current
It is defined as the instantaneous value of short circuit current which circuit
breaker can withstand safely in closed position. It is expressed in terms of kA
instantaneous.’ The Value suggested for this current is equal to rated shott circuit
making current. To test this peak withstand current short circuit with maximum
asymmetry is applied to circuit breaker in one phase. The peak withstand. current test
is combined with short time current test. The stresses produced due to high current
must be sustained by the circuit breaker
10.13.9 Rated TRV for Terminal Faults
‘The TRV waveform can be specified by various methods such as specifying the
peak value and time to reach it of specifying parameters which will decide the line
segment which will represent TRV wave, The methods are respectively called twoProtection and Switchgear 10-44 Circuit Breakers
parameter and four parameter method. The
two parameter method is represented in the
Fig, 10.29.
The circuit breakers must be provided
with Rated TRV, The breaking current test is
carried out on circuit breaker with specified
TRV
The standards provide different
parameters such as voltage, and time to plot
‘the line segments. The TRV wave can be Fig. 10.29
drawn within the segment. The circuit
breaker must be tested for S.C, breaking current test with TRV waveform above
standard waveform,
10.13.10 Rated Operating Sequence
It represents the sequence of opening and closing operations which circuit breaker
can perform under specified conditions. As per specifications the circuit breaker
should be able to perform the operating sequence as pet one of the ways
yQ-t-CO-T-CcO ii) CO-r-cO
where © = Operation of opening
t = 3 minutes for circuit breaker not to be used for rapid
auto-reclosure:
Q
o
n
Closing followed by opening
Te
3 minutes
15 sec for circuit breaker not to be used for rapid
auto-reclosure
10.13.11 Rated Supply Voltage for Closing and Opening Devices
The performance of auxiliary supply circuits and operating mechanisms is
important in addition to ratings of or main circuit and poles, The supply voltage is
provided by auxiliary circuits to the trip coil and closing coil which are having certain
minimum voltage below which it will not operate. For correct operation the frequency
must be properly chosen. The rated supply voltage and supply frequency of closing
and opening devices and auxiliary circuits is important.
10.13.12 Rated Pressure of Compressed Gas
The air blast circuit breaker and some of the SF, breakers use pneumatic while
some other SF, breakers use hydraulic operating mechanisms where minimum andProtection and Switchge:
10-45 Circuit Breakers
maximum values of pressures are specified certain tests like no load test are carried
out with conditions of the pressures. The pressure switches are also fitted in the
auxiliary systems of the operating mechanism.
certain cases like rated
ing overhead lines rated
52kV and above, Rated line charging current for circuit breakers controlling, overhead
lines rated 72.5 kV and above.
Some additional rated characteristics are to be specified
characteristics for short-line faults for circuit breakers controll
There are certain special switching duties like capacitor switching, reactor
switching, DC switching, inductive current switching. The stress produced is usual
and severe. Different circuit breakers behaves differently, The interruption of low
inductive currents is achieved by SF, while capacitor current switching is done
excellently by VCB, Depending upon the type of application the following
characteristics are specified,
i) Rated out of phase breaking current
ii) Rated cable charging breaking current
iii) Rated single capacitor bank breaking current
iv) Permissible switching overvoltages
v) Rated capacitor bank in rush overvoltages
vi) Rated small inductive breaking current
vil) Rated time quantities
viii) Repeated operating, duty.
In actual design of circuit breakers following parameters are considered
1. Current rating
2. Breaking capacity
3. Making capacity
4. Type of protective mechanism
5. Short time rating
6. Type of mechanism
7. Accessories
8. Indications
9. Locks and interlocks
10. Operational life
11, Ease of maintenance
12. Volume / weight
13. Control voltage10-46 Circuit Breakers
Depending upon the above parameters the different circuit breakers are designed
for their efficient operation.
10.14 Type Tests
As mentioned earlier these tests are carried out on first few circuit breakers to
prove the rated characteristics of the breakers. The necessary information which
includes assigned ratings, drawings, reference standards, rated operating pressure and
voltage, support structure ete must be supplied to the testing authorities before
conducting these tests. These details are included in the type tests report. After
ig the breaker by carrying out these tests, there should not be any change in
design.
Type tests are classified as follows,
a) Mechanical tests
b) Tests of temperature rise, millivolt drop test
o) High voltage test
d) Basic short circuit test
i) Making test
ii) Breaking test
iii) Operating sequence tests at 10%, 30%, 60%, 100% of rated breaking current
with specified TRV conditions
©) Critical current tests
f) Single phase short circuit fest
g) Short time current test
In addition to above tests some more tests are recommended on circuit breakers to
be used in specific applications, which are,
a) Short line fault tests
b) Out of phase switching tests
©} Cable charging current switching test
4) Capacitive current switching tests
¢) Small inductive current breaking tests
f) Reactor current switching testsProtection and Switchg
10.15 Routine Tests.
Before dispatch of circuit breakers, these tests are performed. Routine test is
defined as a test of every circuit breaker made to the same specifications. They include
the following tests.
a) Mechanical operation tests
b) Millivelt drop test, Measurement of resistance
c} Power frequency voltage tests
d) Voltage tests on auxiliary circuits, control circuits
The quality of the circuit breaker can be very well checked by these tests, Also any
defects in the materials and construction is detected.
10.16 Development Tests
These tests, are very much essential to observe the effect of different parameters
‘on the circuit breakers performance. Variety of tests are performed on individual
as well as on complete assemblies.
If a circuit breaker is tested frequently with change in its contact speed, then we
can see the effect of contact speed on breaking capacity. The different parameters and
their effects are theoretically predicted. Full scale prototypes are manufactured after
testing and measurement. The data available in the company is used by the designers
for example for the design of contacts, the configuration can be derived from available
designs of contact assemblies.
Each subassembly has certain functional requirement e.g. the contacts should give
low resistance in closed position. Therefore to verify the capability of contact
configurations, development tests are conducted, depending on _ functional
requirements. The modifications are done on the basis of these test results.
10.17 Reliability Tests
The newly manufactured circuit breakers are tested by type tests and routine tests.
But the conditions during these tests are not the conditions that exist at the field. At
site the circuit breaker is subjected to various stresses due to,
a) Variation in ambient temperatures
b) Extremely low and high temperatures
) Rain moisture
d) Vibrations on account of earthquakes
) Dust and chemical fumes
) Overloads and over voltagesProtection and Switchge 10-48 Circuit Breakers
Also the maintenance of the breaker may not be done by skilled persons. Thus the
performance of the breaker is tested under these adverse conditions by reliab: tests.
The circuit breaker is subjected to extremely high temperature created in test
chambers. The various parts are critically examined after testing,
10.18 Commissioning Tests
These test are performed after the proper installation of the breaker at the site. The
‘operational readiness and proper assembly is verified. High accuracy is not generally
expected in such tests. The test facilities available at site is also important factor.
These include following tests,
a) Mechanical operation tests
b) Measurement of travel, simultaneous touching of contacts
) Measurement of insulation resistance and DC resistance
d) Checking the operation by energising of relays
e) Checking the operation by energising the manual operating signal
10.19 Short Circuit Test Layout
The short circuit testing is an experimental method for proving the ratings of the
breaker and checking its performance for further developments. Many of these tests
come under type tests. By carrying out experimentation and problems related to
cireuit breaking, the modern EHV (Extra High Voltage) breakers are developed.
Due to short circuits, severe stresses are produced on circuit breakers, The circuit
breaker must be capable of withstanding the stresses. The short circuit current
duration is about 1 see or 3 sec. The short time current test verify the capability of
breaker.
Due to short circuit, thermal stresses are produced on contacts and current
carrying parts. The stress is also produced on insulation. The poles and terminals
experience electro-dynamic forces.
The making capacity checks the ability of breaker to close on short circuit. The
breaker should be capable of closing effectively without contact welding. The breaking
capacity verify the ability to clear short circuits. The operating mechanism and the
interrupter should able to perform these functions efficiently.
The stresses developed during short circuit depend on magnitude of fault current
and design of breaker. After current zero, the contact space is subjected to TRV.
Therefore for reliable operation and performance of circuit breaker on short circuit,
short circuit testing plants are specially biProtection and Switchgear 10-49 Circuit Breakers
10.19.1 Short Circuit Testing Plants
‘There are three types of testing stations which are as follows,
4) Field type testing station where power required for testing is taken directly
from large power system and the breaker under tests is connected.
b) Laboratory type testing station where the short circuit generators provide the
power for testing. The breaker may be tested directly or indirectly.
©) Composite testing station which is a combination of field type testing station
and laboratory type testing: station.
10.19.2 Layout of a Short Circuit Testing Station
It is represented in the Fig. 10.30. The short circuit generators provide the power
required. There may be two or more generators though in the figure shown it is only
one. Three phase induction motor drives the generator and impulse excitation is
provided.
Se Netenl poor
ewsese
sss
pad
# OM
ws
w= Maser crcut breaker
“— ResorProtection and Switchgeai 10-50 Circuit Breakers
For adjusting magnitude of short circuit current, variable series resistors and
reactors are provided. The master circuit breaker has. higher capacity than the breaker
under test. If breaker under test fails to operate, then master breaker operates to
protéct the’ circuit. Making switch is a closing device specially designed which can
close at desired moment and carries the making currents.
The test voltages are obtained by transformers, These single phase units are
connected in various ways to get different test voltages. This also includes some
equipments necessary-for measurement, record and control, and auxiliary equipments
with a sequence switch to obtain sequential operation.
10.19.3 Short Circuit Generator and Drive Motor
The circuit breakers under test are supplied power with this generator. The
generator must withstand high reactive power surges for short duration. Their design
is therefore somewhat different from conventional alternators
The generator is driven by a three phase induction motor mounted on same shaft.
The impulse excitation is provided by separate d.c. converter. The short circuit current
at lagging power factor have a demagnetizing effect which reduces emf. So the
voltage before the short circuit will be less. Thus the generator field current is boosted
by impulse excitation. The field current is increased to about 10 times its normal value
at the time of short circuit. The arrangement of circuit is shown in the Fig. 10.31.
Bus
s R
Making clrcult breaker Making switch
MY
Uy My Wy
} Pan tot genertr wing
Ma YeZy
Uz Waa,
Fig. 10.31 Circuit arrangement in short circuit test layout
Pant 2 of generator winding10 +52
Protection and Switchy
10.19.11 Sequence Switch
During short circuit testing, many operations are performed in a sequence and
total time is very less to perform manual operation. A sequence switch performs the
sequential operations as it is a drum switch with several contacts which is rotated by
‘a motor. Due to rotation of drum, control circuits are opened or closed as per specific
sequence. The sequences for breaking capacity test in one test are as follows which
takes nearly 0.2 seconds,
i) Drive moter of short circuit generator made off
ii) Impulse excitation switched on
ili) Master circuit breaker closed
iv) Oscillogram circuit connected
v) Make switch closed
vi) Circuit breaker under test opened
vii) Master circuit breaker opened
viii) Excitor switched off and its field supressed
10.19.12 Different Measurements
Since the test events takes very short time, all measurements must be recorded by
oscillographs. Light beam oscillograph which are easily operated are used for slow
varying quantities like current, voltage, contact travel or trip signal etc. TRV
phenomenon requires only 1 msec, For recording such fast quantities, CRO is used
The following quantities are recorded during the test,
i) Short circuit current in each phase
ii) Voltage across each pole before, after and during short circuit
iii) Fluid pressure
iv) Contact travel speed
v) Generator voltage
vi) TRV
vii) Current in trip cireuit
10.20 indirect Testing
It is possible that the short circuit power that can be obtained from the testing
station. may be insufficient to test a breaker of high capacity. Even a single pole of a
EHV breaker can not be tested by direct means.Protection and Switchgear 10-53 Circuit Breakers
The EHV circuit breaker consists of many arc interrupter units which are
separately tested called unit testing. If one unit is tested, the capacity of complete pole
and breaker is determined. This method of Unit Testing is adopted internationally.
Synthetic testing is another popular method which permits testing of breaker,
10.20.1 Unit Testing
The madern EHV circuit breakers contains two or more similar interrupters per
pole, These interrupters operate simultaneously and share the voltage across the pole
equally. The breaking capacity is also equally shared. The results obtained on one unit
can be extended further for total capacity of breaker. This is known as unit testing or
element testing. It is internationally accepted method
During the application of unit test, the voltage must be reduced by a factor b so
the corresponding impedances are also reduced by b to get test voltage across the unit
by following expression.
as where m = number of units per pole and ane unit is tested
B[3 Bi-
a= where n units are tested
Let us consider the examples of a 3 pole, 220 KV breaker with 3 units per pole
Voltage across one pole = 5 = 127 KV
1 1
asa; ms3 asg
Voltage required for testing one unit = a x voltage per pole = 127 x 5 = 42.33 kV
L and C of the test circuit is also reduced to get same natural frequency as that of
direct testing.
In direct test,
Natural frequency, f, = 1
Inv lC
, ‘ 1 I
In unit testin; f, = ——eee =
. wee VTE
a
The natural frequency of TRV remains unchanged. Time scale also remains
unchanged.Protection and Switchgear 10 +55 Circuit Breakers
Mase sate ds
user vrai eg,
‘a t
aged
cont
vs O82] om
res
Beaker
Fig. 10.33 (a) Parallel current injection method
1 & ty
t
'
*
1
‘Arc voltages
‘Transient recovery
Fig. 10.33 (b) Parallel current injection method waveforms
In this method the voltage circuit (2) is effectively connected in parallel with
current circuit (1) and test breaker before main current Ig in test breaker current is
properly simulated.Protection and Switchgear 10-57 Circuit Breakers
are in opposition. The stresses produced in the synthetic test and these in actual
network must be same but it is not the actual case because of several factors like high
current, high voltage, instant of applying voltage ete.
10.21.3 Brown Boveri's Synthetic Testing Circuit
This circuit is shown in the Fig. 10.35. The short circuit current is supplied from
low voltage circuit. The restriking and recavery voltage is supplied by different high
voltage circuit.
HIGH CURRENT CIRCUIT =————. | ——_e HIGH VOLTAGE CIRCUIT
a tt
; |
Fig. 10.35 Brown-Boveri's synthetic testing circuit
The high current circuit on left side consists of short circuit generator G, short
circuit transformer with resistor Rg and capacitor Cg which controls natural frequency
of current. The short circuit power is supplied at voltages Vs which corresponds to
about 30 kV which is smaller than recovery voltage required for testing. The recovery
voltage is supplied by high voltage circuit on right side.
The test breaker and auxiliary breaker S, are opened. together. Before the current
interruption takes place in breaker B, the spark gap is triggered by control 5, and
voltage V is applied to breaker B, During final current zero only current i; flows
through breaker B. Previously is = ic + iy which is interrupted by $; and breaker B.
But now breaker B has to interrupt only iy. Hence restriking voltage across breaker B
is given by HV circuit
Review Questions
State the requirements of a circuit breaker and explain the basic action of circuit breaker.
State the classifiention of cirewit brewer based on different factors,
Expltinn the construction and working of air break circuit breaker.
Write a note om air blast cicuit breaker,
Explain plain break oil circuit breaker
Explain with the help of neat sketch the construction and working of mirinmnum oil circuit breaker.Protection and Switchgear 10-58 Circuit Breakers
17
18,
19,
What are its advantages and disndvantages, compared to bulk oil circuit breaker ?
Explain in brief cross jet and plain jet explosion pot
red in circuit bremkers ?
Why SF, gas is pre
Write a 1
€ om dielectric properties of SF. gus
Explain the construction and working of SF. circuit Brenker.
What are aidewittages and disadvantages of SF breaker ?
Explain the construction, working, advantages and the disndvantages of eacum circu
Explain the arc interruptioe taking place im vacuum,
What are the possible applications of vactiumn cinewit breakers ?
Explain the process of are extinction in vacuum.
White a note ont
4B) Unit testing i) Synthetic testing
Describe short circuit test layout for a circuit breaker,
What are the different ratings of circuit breakers ? Explain any one in detail ?
Wrie a note on HVDC circuit broker.
gQo0Power System Earthing
11.1 Introduction
‘The earthing or grounding is nothing but the connection of neutral point of the
supply system to the general mass of earth in such a way that immediate discharge of
electricity can take place without danger.
When grounding is provided then it ensures the safety of personnel against
electrical shocks and avoids accidents, The equipment is also protected against
lightning and voltage surges. The voltage stress on lines is reduced along with that on
the equipments with respect to earth under abnormal conditions. With earthing, the
earth fault currents are controlled for protective relays.
There are two ways in which the three phase systems can be operated. These are
viz. with isolated neutral and with earthed neutral.
But presently isolated neutral system is not used as with such system during fault,
large transient voltages with magnitude several times that of normal value is
produced which may cause breakdown of insulation. This results in damage of the
concerned equipment and interruption of the supply system. Inspite of this the
advantage of this system is under earth fault on one of the phases, the remaining two:
healthy phases will continue supplying load for a shorter period,
11.2 Ungrounded or |solated Neutral System
‘As the name indicates, the system neutral is not connected to the earth in this
system. Thus the neutral is isolated from the earth. A simple isolated neutral system is
shown in the Fig. 11.142)
‘There is always capacitive coupling between conductors and earth which causes
capacitive currents to flow in the system. The line conductors have capacitance
between one another and to earth. The capacitance between conductors is represented
in delta while capacitance between conductor and earth is in star for 3 phases. As the
grounding characteristics of the system are little affected by line capacitances, they can
be neglected.
(4-4)Protection and Switehgear 11-2 _____ Power System Earthing
Ven
Ven
Fac We
Yon
(a) Ungrounded system Phasor diagram
Fig. 11.1
‘The capacitance to earth of each phase is uniformly distributed along its entire
length and for all the calculations this capacitance is grouped to form a single
capacitor connected between each phase and earth. These currents lead their respective
voltages by 90° as shown in the phasor diagram. Fig. 11.1 (b)
Vy Fulline te tne Va For a perfectly transposed line
Paco (symmetrically spaced) the capacitive
Norma! fine currents Tye, Tye and Tye are equal in
oeanh vahage| magnitude and displaced from each
Noutrat other by an angle of 120°. In balanced
load condition with symmetrical
spacing between conductors, the
potential of neutral will be equal to
Ve that of earth as shown in the Fig. 11.2.
Fig. 11.2 Potential of each phase to earth The charging currents Ixc, yc and
before fault Igc are balanced and their resultant is
zero and no current flows to the earth.
R 8 ‘Now let us consider the earth fault on
Y phase say at point P. The
corresponding phase will be at earth
Line to Keeutrat potential while the remaining healthy
fear voltage ire line value fro
equal to line Phases acquire line value from phase
Earth voltage value as shown in the Fig. 11.3
The capacitive current will not
flow in this phase. The potential of
shifted
Fig. 14.3 from earth potential position to
position shown in the Fig. 11.3.
Line votiage
neutral is not zero but itProtection and Switchgear 14-3 Power System Earthing
The circuit diagram and the corresponding phasor diagram during the fault is as
shown in the Fig. 11.4.
Generator
(a) Circuit diagram Xb) Phasor diagram
Fig. 11.4
Under fault condition, the capacitive currents are unbalanced and the fault current
flows through the faulty line, into the fault and retums to the system via earth and
through the earth capacitances Cy and Cy. The current in Y line has. two components
‘one Igc and other Ipc and the respective voltages driving these currents are Vgy and
Vys and the phase difference between currents and voltages is 90° due te capacitive
nature of the impedance of the circuit. The vector sum of Inc and Inc gives fault
current Ip.
Voltage to earth of R phase = ¥3- Vp
Voltage to earth of B phase = V3. Vp,
I V3 V phase
We have, Tec = x o
He ~
rly we have,
Tye ow Vow 2 3 Vie
me Sac Xe
Both Vpiuse and Xe are equal
and the fault current is given by
vector sum of Ie and Ige as shown
in the Fig. 11.5.
Fig. 11.5Protection and Switchge: 41-4 Power System Earthing
From the diagram,
cos 39° = O12)
Tre
boy 30°
“z= Inc cos
oy 8
= he
From the above equation, it can be seen that the current flowing through faulty
phase is three times the normal line to neutral capacitive current flowing in each
phase of the healthy system
The following observations can be seen from the above analysis
1. With an ungrounded neutral system, if there is phase to earth fault then the
voltages of the healthy phases with respect to earth rise from normal phase to
neutral value towards full line value which may result in insulation breakdown.
2. The capacitive current in the remaining healthy phases increases to /3 times its
normal value
3. The capacitive current in the faulty phase is 3 times its normal value
4A capacitive current flows into the earth, If its magnitude is in excess of 4 to $
amperes then it is sufficient to maintain an arc in the ionized path of the fault.
This current can remain even after clearance of fault. This phenomenon of
persistant arc is called arcing ground. The system capacity will be charged and
discharged in cyclic order due to which high frequency transients may occur
which will cause high voltages of the order of 5 to 6 times the normal value
may be present which results in insulation breakdown. This may cause another
line to line fault because of insulation breakdown either on same circuit or on
another circuit. Thus a minor fault also results in insulation breakdown and
interruption of supply
Due to unbalance in capacitive currents during fault, discriminative type of fault
indicator can not be installed. But the neutral shift indicator may be inserted in the
system which only indicates the occurrence of earth fault but does not give its
location,Protection and Switchgear 11-5 Power System Earthing
The advantages of isolated neutral includes the operation of the system with single
line to ground fault. Also the radio interference is minimized due to absence of zero
sequence currents.
In summary, the ungrounded system does not provide protection against earth
fault to adequate level with chances of insulation breakdown because of which a
phase to phase fault may occur. Due to all these reasons this system is not commonly
used in practice now a days. The earthed neutral system has many advantages due to
which it is preferred in modem power system installations.
11.3 Earthed Neutral System
In this system, the neutral is earthed either directly or through resistance or
reactance depending on the requirement. Thus the system neutral can be grounded
effectively or non-effectively. In effectively grounded system, the neutral is grounded
directly and hence it is called solid grounding. Following methods are adopted for
non-effectively grounded systems.
i) Resistance earthing
ii) Reactance earthing
iii) Arc supression coil or resonant earthing
iv) Voltage transformer earthing
v) Earthing transformer
The advantages of neutral earthing are as follows,
i) The arcing grounds are prevented from occuring by employing suitable
switchgears.
ii) As the neutral point is not shifted in this system, thus the voltages of healthy
phases remains nearly constant.
iii) ‘The static charges which are induced are grounded immediately and are thus
prevented from causing any disturbance,
iv) The faulty part of the system can be isolated from the remaining system with
the help of earth fault relays,
¥) The magnitude of transient voltage is small in this system.
vi) The discriminative type fault indicator can be installed on such systems.
vii) This system is more reliable, provides safety to personnel and equipment with
reduced operational and maintenance cost than ungrounded system.Protection and Switchge 1 Power System ing
11.4 Solid Grounding
In this method of earthing, neutral is directly connected to earth by a metallic
connection or a wire of negligible resistance and reactance. The charging currents flow
through the system under normal condition similar to ungrounded system,
Because of the connection of system neutral point to earth, it always remains at
earth potential at all operating conditions and under faulty conditions voltage of
healthy phase will not exceed,
The solid grounding is represented in the Fig, 11.6.
"PIT ——e tp 42
fs
TIT —o
(a) o
Fig. 14.6 Solid earthing
Whenever there is earth fault
on any one phase (phase B in this
case), the phase to earth voltage of
faulty phase is zero while voltage
to earth of the remaining two
healthy phases will be normal
phase voltages as neutral in this
case is not shifted. The phasor
diagram corresponding to this
condition is shown in the Fig, 11,7.
Let the capacitive currents
flowing in the healthy phases be Ip
and ly. the resultant capacitive
current is vector sum of Ip and [y.
The alternator in addition to
capacitive current also provides the fault current Ip. This current flows from fault
point through faulty phase and then return to the alternator through earth and neutral
Fig. 11.7 Phasor diagramProtection and Switchgo: 11-7 Power System Earthing
connection, The resistance of earth fault is negligible. The magnitude of fault current
after the analysis is given by,
3V ph
Z+Zz4Zo
Ip =
This current is mainly dependent on zero sequence impedance of the source of
power and that of phase conductor upto fault point. As the resistive component of
zero sequence impedance is normally negligible, the fault current which is large can
be assumed as lagging the faulty phase voltage by 90°. From the phasor diagram, il
can be seen that Ip and Ic are exactly opposite due to which capacitive current is
neutralised by high fault current which eliminates the possibility of arcing grounds
and overvoltages. The discriminative types of switchgears may be used in this method,
Following are disadvantages of this method,
i) Due to high value of fault currents, the system may become unstable and there
will be greater interference to neighbouring circuits. Thus this method is
employed where system impedance is sufficiently large to limit fault current
ii) With high values of fault currents, circuit breakers are difficult to handle and
heavy contacts are to be provided in the circuit breakers.
The above disadvantages can be overcame by employing high rupturing capacity
and high speed circuit breakers along with fast operating relays.
This method is used in high voltage systems with voltages below 33 kV with total
capacity not exceeding 5000 kVA for the economic reasons.
11.5 Resistance Earthing
In the cases where it is necessary to limit the fault current then the current
limiting element must be inserted in the neutral and earth, One of the ways of
achieving this is the use of resistance earthing where one or more resistances. are
connected between neutral and earth. The resistor may be either of wire or water
column resistances for voltages of 6.6 kV and above. Metallic resistors do not change
with time and requires little maintenance, But owing to its inductive nature they have
disadvantage with overhead lines exposed to lightning as impulses or the travelling
waves are subjected to. positive reflection and cause stress on ins
breakdown. Liquid resistors ate free from these disadvantages and have simple and
robust construction.
As shown in the Fig. 11.8(@) let the earth fault occurs on phase B. The
corresponding phasor diagram is shown in the Fig. 11.8(b). The capacitive currents Iy
and ly flow through the healthy lines. The fault current not only depends on the zero
sequence impedance of the source but also on the resistance in the earth circuit, This
fault current can be resolved into two components one inphase with the faulty phase
lation resulting in itsProtection and Switchgear 11-8 Power System Earthing
voltage and other lagging the faulty phase voltage by 90°. This lagging component of
current is in phase opposition to capacitive current and it changes with change in
value of earthing resistance. Thus the value of this resistance is designed in such a
way that during fault on any phase, a current equal to full load current of largest
alternator ot transformer flows in earth resistance which will keep the overvoltages
within limits. With fault current lagging component equal to capacitive current the
system operation is similar to solidly earth system and no transients occur due to
arcing ground,
Earthing
resistance:
(a) Circuit representation (b) Phasor diagram
Fig. 14.8
With high value of earthing resistance and low value of reactive current than the
capacitive current then system conditions approach to that of ungrounded system with
chances of transient over voltages to occur. The line to earth voltage of the healthy
phases at the time of fault is little more than line to earth voltage of the solidly
grounded system operating under similar conditions. The duration of this voltage can
be reduced by using suitable protective switchgears to avoid any harmful effect that
may be caused.
The value of resistance to be inserted in earth cireuit is given by,
Ve
R= wh
V1
where Vi. = Line to Line voltage
I
The advantages of this system are as follows,
1) The discriminative type of switchgears may be used for protection.
Full load current of largest alternator or transformer
2) The hazards due to arcing grounds are minimized.
3) The influence on neighbouring communication circuits is minimized due to
lower value of fault current flowing ‘through earth as compared to that in case
of solidly grounded system.Protection and Switchgear 44-10 Power System Earthing
isolated neutral system along with reduced possibility of arcing grounds and
numerous other advantages.
It consists of a coil called Peterson coil or Ground fault neutralizer or are
supression coil whose function is to make arcing earth faults self extinguishing and in
the case of sustained faults to reduce the earth current to low value so that system can
supply power with one line earthed.
is system works on the principle that when inductance and capacitance are
ted in parallel, resonance takes place between them and because of the
s of resonance, the fault current is reduced or can be neutralized
conne
characteristi
The 5
phasor diagram is shown in the Fig, 11.10 (b)
em with fault on phase B is shown in the Fig. 11.10(a). The corresponding
{b) Phasor diagram
Fig, 11.10 Resonant grounding
An are supression coil is an iton-cored reactor similar to oil immersed transformer
connected between neutral of system and earth, This coil is provided with number of
tappings so that it can be tuned with the capacitance which may vary due to varying
operational conditions.
As the system operation is similar to isolated neutral system, the phase to earth
voltage of healthy phase is J3 times the normal phase voltage and the resultant
capacitive current is 3 times the normal charging current of one phase. The resultant
capacitive current lead by 90° with faulty phase voltage while the fault current
lags by 90" with faulty phase voltage.
Now we have, Ip = Ic at resonance
oe Moe ye 3Mem
Pe 7% EEKProtection and Switchg
eit Power System Earthing
There is one problem with the above method, As the operating conditions vary,
the capacitance of the network also vary. This can be overcome by using a tapped coil,
The appropriate tapping is required to be tised for each of the change in the network
conditions. The current rating of the coil is given by,
3pm
's Xe
The time rating of coils used in systems where earth faults are located and
removed is around ten minutes, In other systems continuous time rated coils are used.
The are supression coil is shown in the Fig. 11.11
Earth faut
20
ge [er Tas
Normaly
‘open
raul
breaker
supercon BJF
coil (DC supply
for pong
L ‘creut
Fig. 14.14
The coil is tapped in order to select the reactance depending upon the length of
transmission line and the capacitance to be neutralized. The arc supression coil is
connected between neutral and ground.
1
The reactance of the coil can be evaluated by using the expression L = =
janProtection and Switchgear 44-12 Power System Earthing
The rating of the coil is continuous and equal to the maximum earth fault current.
If a double phase to ground fault or another ground fault occurs, the curtent flowing
through the coil is more. This can be prohibited with closing of a circuit breaker after
certain time lag, The earth fault current flows through the parallel circuit by passing
the arc supression coil. Here the circuit breaker is normally open and closes after the
closure of relay tripping circuit by passing arc supression coil
This method of neutral grounding is used in medium voltage overhead
transmission line which are connected to system generators through intermediate
power transformers. This is because the higher insulation requirement on the
apparatus associated with arc supression coil grounding system is easily incorporated
in power transformers than in generators. Also the overhead lines are usually
subjected to earth faults due to lightning. Hence protection is required.
11.8 Voltage Transformer Earthing
In this system of earthing, the neutral point is earthed through a single phase
voltage transformer. The system thus acts as an insulated neutral system. A very high
reactance earthing is provided due to the voltage transformer,
The connection diagram is shown in the Fig. 11.12,
Surge
Divertor
HIKE wer
i
voltage
transformer
Fig. 11.42
‘The voltage transformer shown in the above figure measures the voltage so that
earth fault on the system is indicated. The travelling waves passing through the
machine winding are reflected through voltage transformer. A surge divertor is used
between neutral and earth to avoid the rise of voltage.
The voltage transformer is used normally in generator circuits which are directly
connected to step up transformers. The generator circuits are physically isolated from
the main distribution system. The electrostatic capacity of the circuit is negligible as
the interconnecting cables between the generator and transformer windings are
normally short. The risk of overvoltage conditions arising due to arcing ground is
eliminated.Protection and Switchgear 14-13 Power System Earthing
11.9 Earthing Transformer
When the transformers or generators are delta connected or if the neutral points
are not accessible then artificially the neutral earthing point can be created with the
use of star connected earthing transformer. Such transformer has no secondary, Each
phase of primary has two equal parts. There are three limbs and each limb has two
windings providing opposite flux during normal condition. Such a transformer is
shown in the Fig. 11.13.
R y 8
(a) Winding of an earthing transformer (b) Schematic arrangement of
winding of an interconnected star
connected earthing transformer
Fig, 11.13
One set of windings are connected in star providing the neutral point. The other
ends of this set of windings are connected to the second set of windings as shown in
the Fig. 11.13, The directions of the currents in the two windings on each limb are
opposite to cach other. The small exciting current is circulated in the windings during
normal operation. Under faulty condition, the transformer offers-a low impedance
path to the flow of zero phase sequence currents. The value of fault current is limited
in some cases by the use of a resistor in series with the neutral earthing connection.
This is necessary in systems with operating voltage between 22 kV and 3.3 kV.
‘These transformers are of short time ratings in the range of 10 seconds to 1 minute
Hence the size of these transformers is small as compared to power transformers of
same rating. If the earthing transformer is not available then a star-delta transformer is
usedProtection and Switchgear, 41-46 Power System Earthing
11.10 Resistance of Grounding Systems
The ground resistance of an electrode system is nothing but the resistance between
the system of electrodes and other infinitely large electrode in the ground at infinite
spacing. The ground resistance is also decided by soil resistivity which is
electro-physical property, The soil resistivity depends on various factors such as type
of soil, moisture content, dissolved salt etc. It is also affected by grain size and its
distribution. The temperature and pressure are the other factors which have influence
on soil resistivity.
In practice it is not possible to have homogeneous soil. The apparent resistivity is
hence defined for an equivalent homogeneous soil.
‘The moisture content in the soil is also a variable factor which changes with
seasons. With increase in moisture content, resistivity of soil reduces. To overcome this
difficulty, the grounding systems may be installed near to the permanent water level
so that the change in resistivity due to change in seasons is minimized.
With decrease in temperature, the soil resistivity increases and the discontinuity is
observed at freezing point. The quantity of salt dissolved in the moisture reduces the
resistivity appreciably. Various salts have different effects on the soil resistivity. With
finer graining, the resistivity of soil reduces while the large value of pressure
decreases soil resistivity
The variation of soil resistivity with moisture and salt content is shown in the
Fig. 7.14 (a) and (b)
t
Resistivity]
(=m)
Moisture: Percentage,
4) of salt
content
(2) Co)
Fig. 11.14 Variation of soil resistivity with moisture and salt contentProtection and Switchgear 11-45 Power System Earthing
Resistance of Grounding Point Electrode
Consider a hemispherical electrode buried in the soil as shown in the Fig. 11.15 (a)
which is simplest possible form of electrode.
(a) )
Fig. 11.15
The total resistance in this case can be divided into three parts which are viz
i} resistance of conductor ii) contact resistance between the surface of electrode and
main body of earth which is negligible iii) resistance of body of earth surrounding the
electrode which is the main part.
Let I be the current dissipated by the electrode. This current spreads out radically
in the earth. Ata distance x from the centre of hemisphere the current density is given
by,
I
2ax?
The electric field strength e due to current dens
_ pl
ee PO dex?
‘The line integral of the field strength e from the surface of sphere of radius R to
the distance x gives the voltage V.
elfi 1
anc x
The variation of e, V and i with respect to distance x is shown in the Fig. 11.15 (b)
‘The voltage between the hemispherical electrode and a point at infinity ie, x = ©
s given by,
veProtection and Switchgear 11-16, rower System Earthing
‘The earth resistance is therefore given by,
= Voie
R= T 2nC
11.10.1 Generalised Equation
‘Consider a system with two electrodes having their potentials as V, and V;. Let V
be the potential at any point in the medium having resistivity as p. Let y be
electrostatic potential.
18¥
The current flow normal to surface at any point of the electrode is >
Total flow of current from the electrode in the outward direction is,
1ppeY a. _ lew
ala ® olan ds
Here ds is an element of the electrode surface.
If Q is the charge on this electrode then by Gauss theorem
oy _
-fj¥-as = 420
The total flow of current is given by,
p= 4Q
P
If is the capacitance between the electrodes in air then
Wire = M-¥=8
R is the resistance between the electrodes which is given by,
Suppose C is the capacitance of the single electrode with the return electrode at
infinity then R is the resistance of earth for single electrode.
If we consider a sphere of radius $ then the capacitance of sphere in air is equal to
radius 5.
=
R-Gs
If this eleerode is hemispherical and buried with its lower half in the earth then
the resistance is given by,Protection and Switchgear 14.47 ower System Earthing
In general the equation for any electrode is given by,
=
R= >,
2aC
where C is the electrostatic capacity of the electrode along with its image above
the surface of the earth. The combined electrode is considered as in air.
11.11 Resistance of Driven Rods
]
The most simple and cheap form of
electrodes is nothing but driven rod. It is shown
in the Fig. 11.16 with its length as [and diameter
d with its image, It can be considered equivalent
to an ellipsoid of revolution with a major axis
very much large a8 compared to minor axis.
The capacity of rod and its image is
2
c=
amit init
The earthing resistance of driven rod is given by
df
I R= Ri n®
Fig. 11.16 al od
For the cylindrical rod with hemisphere end
the above expression becomes,
p 2
R= my
An alternative expression for the resistance of driven rod is obtained by using
uniform current dissipation method and is given by,
PL ina
R=
add
From the expression far resistance of driven rods, it can be seen that, the earthing
resistance is inversely proportional to length [.
Generally resistance of single rod is not sufficient. Hence number of rods are
connected in parallel. It is necessary to minimize the overlap among the areas of
influence of the rods. This is possible by keeping large distance between the rods, It is
difficult to achieve this in practice and approximate method is used.Protection and Switchgear 414-18 Power System Earthing
In this method, a rod is replaced by hemispheric electrode having same resistance,
If n tods are connected in parallel then their resistance is greater than (2 } of that of a
single driven rod due to the mutual screening.
The screening, coefficient for n electrodes in parallel is defined as,
Resistance of one electrode
(Resistance of n electrodes in parallel) x n
=
11.12 Grounding Grids.
‘The low ground resistance in case of high voltage substations can be obtained with
the use of interconnected ground grids. In a typical grounding grid system, a number
‘of interconnected bare solid copper conductors are buried at a depth of 0.3 to 0.6 m
and spaced in a grid pattern. It provides common earth for all devices and metallic
structures in the substation.
‘At each of the junction point, the conduetors are bonded together. This system is
usually supported by a number of vertical rods about 3 m long at some joints
If a is cross-sectional area of copper, in circular miles, t is the fault duration in
seconds, T,, is the maximum allowable temperature and TT, is the ambient temperature
then the size of grid conductors required which prevents fusing under the fault
current is given as,
asl Tot
© oy [AT
234+Ts
If the grid depth is less than 0.25 m then the earthing resistance of the grid is
given by,
p
R= 2
4
Here R = Grid resistance in ohms
a = Ground area occupied by grid in m?
L = Total length of buried conductors in m
But when the grid depth is greater than 0.25 m then earthing resistance is given
by,Protection and Switchgear 11-19 Power System Earthing
The effective grounding of the equipment is possible through the grid. Also the
voltage gradiant at the surface of the earth can be controlled at safe value for human
contacts with the addition of ground rods, the ground resistance further reduces when
soil resistivity in the upper layer is more than the soil underneath,
11.13 Design Principles of Substation Grounding System
The most important factor in the substation is its grounding. The system neutral is
connected to the ground through grounding. The discharge path for surge arrestors
and safety of operating personnels can also be achieved through grounding.
The grounding gives low resistance path to earth and reduces rise in ground
potential which is dependent on magnitude of fault current and resistance of
grounding system. The low resistance for substation ground can not be obtained in
deserts and rocky areas.
The convenient way for getting proper ground connection is through If the
ground rods are used in addition then it reduces the ground resistance. Depending on
the size of the substation, nature of soil and the grounding resistance required, the
size of grid and number along with length of driven rods can be determined
Under the fault condition, the potential of earth and its gradient over the surface
out fram the electrode is dependent on the ground resistance. The systems with higher
values for maximum ground fault current, it is not possible to have lower values for
ground resistance so as to have rise in grounding system potential to safe value.
The practical solution for grounding at substation yards is through grid or mat.
The grid consists of a number of meshes and connected to several earth electrodes
driven at intervals.
The total number of electrodes required is determined by using the expression
Maximum Fault Current
Number of electrodes = 0
The grounding resistance for a grounding grid or mat is calculated from the
following expression,
= Be
Rea
Here p, ity of soil in Q-m, L is total length of buried conductor in metres
and r is radius of circular plate in metres.
The size of grounding conductor should be appropriate so as to have thermal
stability for ground fault current and it should be mechanically strong. The minimum
cross section for the grounding conductor having required thermal stability is
determined from the following expression,Protection and Switchgear 41-20 Power System Earthing
Amin = Tp vt
Cc
where Ip is fault current in amperes while t is time in seconds for the operation of
protective relays including circuit breaker tripping time. C is a constant, Its value is 70
for steel having temperature rise of 400°C while for copper with temperature rise of
300°C, its value is 165.
The minimum
required for proper mechanical strength in case of steel is
61 mm®, For copper it is 107.2 mm? while in case of aluminium it is 195 mm?,
In case of grounding conductors made up of steel, its size should be checked for
corrosion. If the soil is moderately or severely corrosive then the steel strip of
minimum thickness 6 mm and minimum cross section area should be 200 mm?.
The earthing grid system is normally extended over the total substation yard and
in few cases, several metres beyond it. The grounding conductors should have low
impedance. They should be able to carry prospective fault current without getting,
fused or damaged. They must take account the future expansion of connected power
system.
Examples with Solutions
iim Example 11.1 : Determine the inductance of Peterson coil to be connected between the
neutral and ground to neutralize the charging current of overhead line having the line
ta ground capacitance of 0.15 uF. If the supply frequency is 50 Hz and the operating
voltage is 132 kV, Find the KVA rating of the coil,
Solution ; In case of Peterson coil we have,
1
oe
3a°C
= 2af=2x ex 50 = 100% x = 314159 t/s
C = 0.15 pF = 0.15 x 10°°F
1
Inductance, Los ——________
nductance, 3x (314.159)? x(0.15 x10)
Ls
v2
ph
KVA rating of coil = —2Protection and Switehgear Power System Earthing
_ __(76210.23)?
© 359% 3231
= 821.29
KVA rating of coil
iim Example 11.2 : In @ 50 Hz overhead Hine, the eapacitance of one line to earth was
16yE, It was decided to use am earth fault neutralizer. Calculate the reactance to
neutralize the capacitance of i) 100% of the length of line ii) 90% of the length: of the
line iii) 95% of the length of the line.
Solution : w= 2 nf =2 mx 50 = 100 n= 314.159 r/s
C = 16pF= 16% 10°F
i) For 100% length of the line
We have inductance of Peterson coil given by,
1 1
L= -— 1 lai
302” 3(314.159? (16x10)
The inductance required to neutralize is 2.11 H
Reactance X= 2nfl sob = (314.159) @1)
x, = 663.140
ii) Capacitance for 90% of the length of the line is
16409 = 144 UP = 144 x 10-¢
1 1
Indi le:
inductance, Fore ~ Hald.159? Gadx lo)
L = 234H
Inductive Reactance, X;, = L = (314159) (2.34) = 736.82 0
Capacitance for 95% of the length of the line is,
16% 0.95 = 152 pF = 152 x 10°
1 1
Inductance, L-—. 2220
nenceance Bor 3G14.1597 (152x104)
L = 22H
Inductive Reactance, X, = L = (314.159) (2.22) = 698.04. 0Protection and Switchgear 44-22 Power System Earthing
Review Questions
1
2
3
4
5
Explain in brief isolated neutral system
What ore the advantages of neutral earthing ?
State the methods nioptest for nonceffectively grosended systems,
What do you acum by effectively grounded and non-effectively grounded systems ?
Write a note on soled grounding.
Explain resistance earthing.
What are the advantages of resistance earthing ?
How reacties earthing & achiewed ?
Write @ note on resonant grounding
Derive the expression for the renctance of the Peterson coi.
Explain the working of arc supressiom coil.
Write short notes on i) collage transformer earthing is) Earthing transformer.
What ore the various factors on iwhich soil resistivity depends ?
write
Note on grounding grids
Explain tae principles of design of substation grounding.
A33-KV, 3 phase, 50° Hz overlucad Tine 50 kam long his capacitance earth dine eqpeal to 0.019 WF
per kom,
Determine tite inductance and VA rating of the arc suepression coil (6.75 H, 169.3 kVA)
rhcad line, the capacitance of one line to earth wns: 1.5 jF. It tos decided to wse an
cr. Calculate the reactance ta neutralize the capacitance of 11 100% of the
igti of the Hine it!) 95% of the lenge of the line
(4) 2.25 H Gi) 25 H (ii) 237 BD
bn a 50 Hf
cearth fonelt netted
length of the Tine if) 80% of the
Determine the value of reactance to be connected in the neutral connection to nentralize the
capacitance current of a everkend tine to ground capacitance of each linw equal to 015 uF. The
frequency is 50 He (226K)
Q00Protection Against Overvoltage
12.1 Introduction
The voltage waves having magnitude more than its normal value and which
remains for a very short duration are called overvoltage surges or transient
overvoltages. For any electrical equipment, its insulation requirements are decided by
these transient overvoltages.
The overvoltages in the system occur due to various reasons such as lighting
surges, switching surges, faults and travelling waves, There is high rate of rise and
high peak value in transient overvoltages which is dangerous for the insulation and
hence protection is required against these overvoltages
12.2 Lightning Phenomenon
A. lightning stroke on any overhead line or on outdoor equipment causes
lightning surges. Before studying the protection against these lightning surges, let us
study the mechanism of lightning.
An electrical discharge in the air between clouds, between the separate charge
centres in the same cloud or between cloud and the earth is nothing but lightning. It
produces the large spark accompanied by the light. This discharge of electricity
through the air from the clouds under turbulent conditions is always abrupt and
discontinuous. The serious hazards may take place sometimes if this discharge
terminate on the earth.
There are various theories which explain the potentials required for lightning
strokes, are built up. However we will assume that because of some process taking
place in the atmosphere under the turbulent conditions there is accumulation of
charges in the clouds. With the dielectric medium as the air the cloud and the ground
form plates of a capacitor. If the lower part of the cloud is negatively charged, the
earth is positively charged by induction.
For lightning discharge to take place, it requires hreakdown of air between the
dloud and the earth. With increase in the charge, the potential between the cloud and
the earth increases. As a result of this the potential gradient in the air increases. The
(12-4)Protection and Switchgear 42-2 Protection Against Overvolta,
potential gradient required for the breakdown of air is 30 kV/cm peak. But there is
large moisture content in the air and because of lower pressure at high altitude, the
breakdown of air takes place at 10 kV/em. The process of lightning discharge is
shown in the Fig, 12.1
o © ©
Fig. 12.4
When charge increases there is difference in potential between cloud and earth
which also increases resulting in increase of potential gradient of air which is
non-uniformly distributed. The potential gradient is more at the centre of charge in the
cloud. This gradient appears across some part of the ait and when it is more than
breakdown strength of air, this air breaks down. A streamer called pilot streamer or
leader streamer starts from cloud towards the earth and carries the charge with it as
shown in the Fig. 12.1 (a). Till the time the cloud through which this stream is
initiated supplies enough charge to maintain the potential gradient at the tip of the
leader streamer above the breakdown strength of air, the leader streamer continues to
travel towards the earth. With the loss of this gradient, the streamer stops without
reaching to the earth, The charge dissipated without forming the complete stroke. The
lightning stroke may start with the potentials of the order of 5x 10° V to 20x 10° V
between cloud and earth while the current of the leader streamer is low, typically less
than 100 A and its propagation velocity is 0.05 % of that of velocity of lightProtection and Switchgear 12-3 Protection Against Overvoltage
Many times the streamer travels towards the earth until it is reached to the earth
or some object on earth, As the initial streamer moves towards earth, it is
accompanied by points of luminescence which travel in jumps giving rise to stepped
leaders. In one step the distance travelled is about 50 m while the velacity of stepped
leader exceeds one sixth of that of light. The stepped leaders results in first visual
phenomenon of discharge.
The electrostatic field and potential gradient at earth’s surface is high as this
streamer reaches to the earth, When it becomes sufficiently large then a short upward
streamer called retum streamer rises form the earth as shown in the Fig. 121 ()
When the contact of leader is made with the earth then a sudden spark may be
appeared, This contact is similar to closing of a switch between two opposite charges,
the downward leader with negative charge and upward streamer with positive charge
Due to this sudden sparks appearing which causes the most neutralisation of negative
charges on the cloud. This is called lightning. Any further discharge from the cloud
must be originated form other portion of it
When lightning occurs then it is associated with high current followed by lower
current for significant duration as the charge in the cloud is neutralised. The upward
streamer carries high current with a speed of propagation of about 30 m/sec which
is faster than the speed of the leader streamer. The current rises sharply within
microseconds and then decays slowly compared to its rise. This is similar to discharge
of a capacitor through a circuit but it is not periodic, The experiments conducted in
the laboratories show that when the charge in the channel is near exhaustion, there is
smooth transition in current into its low value which is associated with the remaining
charge in the cloud.
When the streamer reaches the earth and much of charge in the cloud fram which
it was originated, is neutralised then potential pertaining to point of charge centre
reduces, But there may exist high potential between this original charge centre and
other charge centres, Due to this, there may be discharge from other charge centres
into the region where the leader streamer was originated. Thus subsequent discharges
takes place alongwith the original stroke to the earth, Many strokes can be observed
which contains more than one current peak which are called multiple or repetitive.
Separate peaks are termed as components.
In summary we can say that lightning is a phenomenon of breakdown of air and
discharge which can be seen by eye as a single flash but contains number of separate
strokes that travels with same path practically. The variation of time interval between
them is from 0.5 msec to 500 msec. 87 % of the lightning strokes originate from
negatively charged clouds while remaining 13 % originate from positively charged
clouds. Lightning discharge current magnitude lies in the range of 10 kA to 90 kA.Protection and Switchgear 12-4 Protection Against Overvoltage
Some values for the lightning stroke are given below in the Table 12.1 for the
information:
Voltage 200 MY (peak )
Current 40 to 90 kA { discharge )
Duration 10 psec
Power 8x10? KW
Energy 22 kWh
Table 12.1
We should also consider the case of statically induced charges and various
lightning strokes. When a charged clouds come above the conductor, the charges are
statically induced on the conductor which are released by travelling either side in the
form of travelling waves when clouds go away from their place, These surges are not
prevented by earthwire.
It can also be seen that the paths travelled by lighining strokes are unpredictable
in certain cases. Usually these strokes try to travel and reach to the earth, ‘These
strokes are interrupted by lightning rods, trees, tall structures etc. But sometimes
these strokes does not obey any rule and travels horizontally in all sorts of haphazard
fashion,
B type strokes originate due to sudden change in charge between two clouds. As a
result of this there is sudden change in charge in other (third cloud in its vicinity)
cloud which discharges to the earth. This B type stroke does not hit lightning rod or
earth wire, Thus overhead lines can not be protected against such strokes
12.2.1, Waveform of Lightning Current
A generalized waveform for
t lightning current is shown in the
Current Fig. 12:2.
ere | Crest .
Tt consists of a peak value
called crest. The time taken by
the wave to reach this peak is
called front time. The time span
from origin to a point where is
the voltage or current has
decayed to one half of its peak
value is represented by T,Protection and Switchgear 12-5 Protection Against Qvervoltage
Time T, varies from 1 to 10 psec while T; varies from 10 to 100 psec. 25 % of the
lightning strokes carry current less than 10 KA, 86% strokes are with currents less
than 50 KA. In case of 11% strokes the current lies in between 50 and 100 KA.
While 2 % strokes carry current in between 100 and 150 kA. Only 0.5 % strokes carry
currents more than 150 kA whereas the measured highest value is 400 kA. The total
duration of lightning in some strokes may be up to 1 second.
12.3 Types of Lightning Strokes
There are two main types of lightning strokes that appear on various equipments
in the power system. They are viz. Direct Stroke and Indirect Stroke. Direct stroke
may appear on line conductor, on tower top or on the ground wire indirect stroke
may appear on overhead line conductors.
12.3.1 Direct Stroke on Overhead Conductors
These strokes are most dangerous as their effects are most severe and harmful, In
this type of stroke, the discharge or the current path is directly from the cloud to the
overhead line. From the line, the current path may be over the insulators down the
pole to the ground, The voltage set up is in millions which can cause flash over and
puncture of insula The insulators may get shattered till the surge is sufficiently
dissipated and it travels to both sides. The wave may reach to the substation and
damage the equipments because of excessive stress produced,
If a overhead line conductor is struck by lightning then the rise in voltage at the
point is given by,
Yoel «
= aie *F
where, lage = Current in the lightning stroke
%, = surge impedance of the line.
The term = is used in the above expression as the charge on the conductor flows
2
to the both sides of the conductor in the form of travelling waves.
If we consider Z,= 1000 Q , Inge 40 KA as representative figures then voltage
developed will be,
20% 10° = 2%107 volts
= (420° 22
This is the amount of voltage that is produced during a stroke. If this lightning
stroke appears at a point away from a substation or generating station then this
overvoltage and the current flows along the line in both the directions shattering theProtection and Switchgear 12-6 Protection Against Overvoltage
insulators and even wrecking poles until the energy present is dissipated completely
in the paths towards earth. If it occurs near a plant or substation then the damage is
sure. But these types of direct strokes are not frequent in occurrence.
Due to this lightning stroke, neighbouring lines are also subjected to overveltages
due to electromagnetic coupling. These high voltages may cause flash over in case of
insulators,
All high voltage overhead lines are protected from lightning strokes by use of
earth conductors, With the use of overhead network of earth conductors, the outdoor
switchyards are protected,
A direct stroke is shown in the Fig. 12.3.
Overhead line
Earth
Fig. 123
The cloud will induce opposite charge on the overhead line by induction. When.
the potential between the cloud and line is more than breakdown strength of air, the
lightning discharge takes place between cloud and the line.
There may be other type of direct stroke that may occur on the overhead line
which is illustrated in the Fig. 12.4.
This type of stroke is produced because of sudden change in charge conditions in
the clouds, Consider, for example, three clouds viz. cloud 1, cloud 2 and cloud 3
having positive, negative and positive charges respectively. If cloud 1 is shifted
towards cloud 2 then discharge may take place between them and charge on them
will be neutralised. Thus charge on clouds 1 and 2 may be disappeared quickly. As a
result charge on cloud 3 is suddenly free as its bonding with cloud 2 has been broken.
Due to this, rapid discharge from cloud 3 may take place to the earth ignoring tall
objects. Thus protection against these strokes is difficult while protection against oth
type of direct stroke is possible as the direct stroke we have discussed above will
occur on tall objectsProtection and Switchgear 12-7 Protection Against Overvoltage
Direct stroke
‘Overhead line
Earth
Fig. 12.4
12.3.1.1 Director Stroke on Tower
If there is a direct lightning stroke on the tower then its voltage is increased. Its
value is given by
ai
Varwie = Ly a+ Ry i
where Varste = Voltage surge between top of tower and earth
Ly = Inductance of tower
Ry = Resistance of tower
i = current flowing through tower because of stroke.
For example if we consider R = 10.0, i = 30 kA, 2 = 10kA/ps
L = 10nH
Veeroke = (10) (10) + (10) (30) = 400 kV
‘This is the voltage that will appear between top of tower and earth. If this voltage
is more than impulse flash over level then flash over may occur between tower and
line conductor.
Due to this travelling waves may also be formed in both the directions of
conductor which may reach to substation equipments to cause their damage. A direct
stroke on the ground wire in its middle span may also cause a flash over between line
conductor and earthwire or line conductor and tower.Protection and Switchge:
12.3.2 Indirect Strokes
The effect of indirect strokes is similar to that of direct strokes. Their effect is
more severe in case of distribution lines than in case of high voltage lines. These
strokes are due to electrostatically induced charges on the conductors due to presence
of charged clouds. Sometimes currents may be induced electromagnetically due to
lightning discharge in the immediate vicinity of line which results in indirect stroke, It
Protection Agi
is shown in the Fig. 12
Earth
Fig. 12.5
Consider that a positively charged cloud is above the line. It induces negative
charge on the line by electromagnetic induction which is present in that portion of the
line which is under the cloud while the other portions of line are positively charged as
shown in the Fig. 12.5. The induced positive charges slowly leak to the earth through
the insulators, Whenever there is discharge from the cloud to earth or to another
cloud, the negative charge on the wire is isolated as it can not move quickly to the
earth over the insulators. Due to this, negative charge goes along the line in both
directions in the form of travelling waves. Maximum surges in a transmission line are
caused by indirect lightning strokes. The same action may take place but with
opposite charges if the cloud is negatively charged.
12.4 Effects of Lightning
Because of direct or indirect type of lightning strokes, a steep fronted voltage wave
is produced on the line. Its peak value may reach to about 2000 kV in about 1 sec
while it decays to half its peak value in about 5 jisec. Because of this voltage,
travelling waves are initiated along the line in both the directions. The velocity of
these travelling waves depend upon the inductance (L) and capacitance (C) of the
mine. ‘The harmful effects of lightning are discussed below.
transmProtection and Switchgear 12-9 Protection Against Overvoltage
i) The travelling waves which are generated on account of lightning surges
shatter the insulators and may even wreck poles.
ii) If these traveling waves reach towards the windings of generator or the
alternator then it may cause its appreciable damage. The inductance associated
with the windings opposes the sudden change in charge through it. Because
of this, excessive pressure may be developed between the windings which also
cause insulation breakdown. After insulation breakdown, the line voltage may
be sufficient to maintain the are which is produced resulting in ultimate
damage to machine,
iii) When the arc is initiated due to lightning stroke then it will set up disturbing
illations in the line. Due to this other equipments connected to the system
may be damaged.
12.5 Protection Against Lightning
Proper protection must be provided to the power stations, substations, overhead
transmission lines from the direct lightning strokes while the electrical apparatus must
be protected from indirect strokes in the form of travelling waves, Already we have
seen that the lightning strokes can cause severe damage than other types of switching
surges or transients. Hence protection against lightning strokes is an important
consideration in the system design.
Commonly used equipments for protection against lightning strokes are as given
below.
1. Farthing screen
2. Overhead ground wires
3. Lightning arresters or surge diverters,
To protect the generating stations and the substations from direct strokes, earthing,
screen is used. Overhead ground wires protect the overhead transmission line from
direct lightning strokes. The protection against both kinds of strokes direct and
indirect in the form of travelling waves is provided with the help of lightning
arresters.
Sometimes lightning or earth rods are mounted on tall buildings. These rods are
connected to the earth. On the sharp points of this rod, positive charges are
accumulated which attracts the lightning strokes. The earth wire placed above the
caverhead line is grounded at every tower and positive charges are accumulated on
this wire, The negatively charged strokes are attracted by earth wire. If this wire is
not present, there would be flash over in the line as lightning strokes will strike
directly on the lineProtection and Si
hgear 42-40 Protection Against Overvoltage
The earth wire does not provide 100 % protection as weak strokes and B type of
strokes are not attracted by this wire. The earth wire is a good solution for the most
dangerous ditect strokes, It has a shielding angle which is the angle made by
outermost conductor in the at the ground wire, This angle should be as lower as
possible to give more protection. Whatever line conductors come under the shielded
vone are well protected against direct strokes. This angle is normally between
3°to4(P. Its typical satisfactory and economical value is 35
12.6 Protection of Generating Stations and Substations Against Direct
Strokes
Generally the generating, stations are housed in big. buildings while the substations
are housed in switchyard ot outdoor, To protect these structures from direct strokes,
three important requirements viz. interception, conduction and dissipation must be
fullilled. It requires an object in good electrical connection with the earth having low
impedance path to attract the leader stroke. It also requires a low resistance
connection with the body of the earth.
For having a goad electrical connection, the upper portion of metal structure may
be used, Instead of this, a separate metallic system called shield mounted on the
structure or near to it may be used. The total switchyard is provided with earthed
overhead shielding screen.
The earthing sereen consists of a network of copper conductors mounted all over
the electrical equipment in the plant or substation. This shield is appropriately
connected to the earth on atleast two points with the help of low impedance: path
Occurrence of any direct stroke is directly diverted to the earth as the shield provides
low resistance path. Thus the costly station equipments are protected from damage.
This is designed in such a way that out of 1000 strokes, 999 will be diverted to earth
through this shield while only 1 stroke may strike on the protected equipment which
is called 0.1 % exposure
‘Transmission line conductors are protected with the help of overhead earthed
shield. A vertical line if drawn from the earth wire and angle a is plotted on its both
sides then this angle a is called shielding angle while envelope within angle 2a is
called zone of protection. The clearance between line conductor and overhead
shielding should be more than minimum clearance between phase and earth
Lighting mast is an independent structure which is installed at specific locations
the switchyard.
In outdoor switchyards, lightning masts are preferred up to 33 KV. With increase
in voltage, it becomes tall and uneconomical. In this case, overhead shielding wires are
employed as height of the structure required is less.Protection and Switchgear 12-11 Protection Against Overvoltage
12.7 Protection of Transmission Lines Against Direct Strokes
The transmission lines are effectively protected against direct lightning strokes
with the use of ground wires. The ground wire is a conductor which runs in parallel
with the line conductor. It is placed at the top of tower structure. For horizontal
configuration of line conductors there are two ground wires whereas for vertical
configuration there is only one ground wire.
The ground wire is made up of galvanised steel or recently ACSR conductor of the
same size as that of line conductor is used. The material and size of conductor
required for ground wire needs more mechanical considerations in its design rather
than the electrical. With the help of simple and economical methods, the effective
resistance of the ground wire can be decreased,
‘The use of ground wire is to provide shielding of line conductors against direct
lightning strokes. Also whenever a stroke appears on a tower, the ground on
both sides of tower provide paralle! paths for stroke reducing effective impedance and
the potential at tower top is comparatively less. As the ground wire and power line
conductors are coupled electrically and magnetically, chances of failure of insulation
are significantly reduced.
For the sake of simplicity and understanding, one ground wire and one conductor
is shown in the Fig. 126.
Overhead ground wire
Fig. 12.6Protection and Switchgear 42-12 Protection Against Overvoltage
The height of ground wire is such that practically all the lightning strokes are
intercepted by them. These ground wires are earthed at every tower or pole through.
low resistance.
Whenever any stroke strikes on the line, it will be taken up by ground wire. The
heavy current flows to the ground from the ground wire. The extent to which
protection is provided by the ground wire depends on footing resistance of the tower,
Let us consider this resistance as say R, and the lightning stroke current is say [pcuer
then potential of the tower top Vyoue With respect to earth is given by,
Veit = Eaeoke “Ra
This is the approximate voltage between tower and line conductor which also
appears across string, of insulators present on the tower. If this voltage is less than
that required for insulator flash aver then no damage or harmful effects can be
observed. But if its value is greater then insulator flash over may take place resulting
in its damage. Hence the footing resistance of the tower should be kept as low as
possible to limit the value of voltage which will avoid flash over of insulator.
It is important to consider that the voltage to which the tower is raised during
lightning stroke, is not dependent on the system voltage. Hence the design of
transmission line against lightning for specific performance has nothing to do with the
system voltage.
12.7.1 Requirements of Ground Wire
‘The requirements for the design of the line against lighting strokes are given
below.
i) The ground wires used for protection of transmission line should be
mechanically strong and should be suitably located to provide the protection,
ii) There must be sufficient clearance between power line conductors and ground
wire for the given system voltage.
ili) The footing resistance of the tower should be as low as possible and
economically justifiable.
The first requirement is met by use of galvanised steel wire or ACSR wire and the
protective angle or shielding angle decides the location of ground wire for effective
shielding. Protective angle is the angle between the vertical line passing through the
ground wire and the line passing through the outermost line conductor. It is shown
in the Fig. 12.7.Protection and Switchgear 12-13 Protection Against Overvoltage
Ground
Power
‘conductor
fy
Fig. 12.7
If two or more than two ground wires are used then the protective zone between
the two adjacent wires can be taken as semi-circle with diameter as a line joining the
two ground wires. Experiments by research scientists show that a single wire
provides effective shielding to a line conductor that lies below a quarter circle with its
centre at the height of ground wire and radius equal to height of ground wire from
the groundlevel. The proved shielding angle for adequate protection is about 30° for
plain areas while it decreases by an amount of slope of hill in case of hilly regions.
‘The second requirement of sufficient clearance between tower and conductor is
met by suitable design of cross arm in such a way that when a string of insulators is
given a swing of about 30° towards the tower structure then the air gap between the
conductor and tower structure should be in such a way as to withstand the switching
voltage (normally four times line to ground voltage) that may appear on the system.
The clearances between conductors can also be adjusted by adjusting the sag in such a
way as to avoid the midspan flash overs.
The third requirement is already discussed earlier. For 66 kV line, the standard
acceptable value of footing resistance is nearly 10.2. It increases as the system voltage
rises.. For a line with operating voltage of 400 kV, its typical value is 80.2. The tower
footing resistance is its value when measured at a frequency of supply which is 50 Hz
in our country. The performance of the line in context with lightning stroke depends
on impulse value of ance which is a function of resistivity, critical
breakdown gradient of soil, length and type of driven grounds and magnitude of
stroke current.Protection and Switchgear 12-15 Protection Against Overvoltage
Tower
structure
a“ fa) Single paraitel continuous:
Leg ‘arrangement
‘of tower
(b} Double parattel continuous
arrangement
{c) Radial arrangement
(4) Radial and continuous arrangement
Fig. 12.9 Various counterpoises arrangements
The ground wire in addition to
give protection against direct
strokes also provides electrostatic
sercening by reducing the voltage
induced in the conductors by
discharge of a neighbouring cloud
Consider Cy as capacitance of 6,
cloud to line while Cy as
capacitance of line to ground as
shown in the Fig. 12.10
‘The voltage across the line and Fig. 12.10
the ground is ( \v. Vis
the cloud voltage. As the ground wire is above the line conductor, there will be
appreciable increase in Cy which results in reduction of line induced voltage.Protection and Switchgear 12-16
With a single ground wire the induced voltage is reduced to half of that without
ground wire. With two ground wires, this reduction is about one third while for three
ground wires, it is one fourth. These results are at favourable conditions of good
earths and low impedance of earth connection as obtained by conducting experiments
in the laboratory. The ground wire is also helpful in attenuating any travelling waves
which may set up in the lines by acting short circuited secondary of line conductors,
12.7.4 Advantages of Ground Wire
i) Direct lightning strokes on the transmission line are well protected by ground
wire.
ii) There is damping effect of the ground wire on the disturbance travelling along
the line as it acts as a short circuited secondary.
iii) For external fields, it provides electrostatic shields to certain extent which
reduces the voltage induced in the line conductors due to discharge of a
neighbouring cloud
12.7.5 Disadvantages of Ground Wire
i) It requires extra cost.
ii) It may be possible that due to breaking of ground wire and falling on the line
conductors can cause a direct short-circuit fault. But this situation is rare to
occur as mechanically strong galvanized steel stranded conductors are used.
Due to this the ground wires bear sufficient strength.
12.7.6 Use of Ground Wire
Ground wires are extensively used for protection against direct lightning strokes
for voltages ranging from 110 kV to 500 kV. They are used on all the important
transmission lines and on all sections of transmission lines running through regions
which subject to frequent lightning storms.
12.8 Protection of Transmission Line by Auxiliary Devices.
‘The alternative way of protecting transmission line against lightning is by making
use of auxiliary devices. In these
Crossarm y
‘ways of protection, discharge path
sing i controlled and some device is
ofinsuiators used to extinguish the arc so
‘Supporing formed. The most commonly used
Line conductor
structure ee device is protector tube which
Protector
tube consists of fibre tube with an
electrode in each end, It is shown
in the Fig. 12.11,
Fig. 12.11Protection and Switehgear 12-17 Protection Against Overveltage
It is mounted below each line in such a way that the upper electrode is connected
to hom which is are shaped at appropriate distance below the line forming a series
gap with it. The lower electrode is effectively grounded
With the appearance of the surge on the line the series gap is spanned. An arc is
formed between the electrodes in the tube. Some of the fibre of tube walls is
vapourized due to heat in the are, The natural gas from this reaction violently enters
into the arc to deionize it which prevents restriking of the arc after first zero point of
the current
12.9 Protection of Electrical Apparatus. Against Travelling Waves.
(indirect Strokes)
The earthing screen and the ground wire discussed earlier provide protection
against direct lightning strokes but does not provide any protection against travelling
waves which may teach the electrical apparatus. The lightning arresters or the surge
arresters are the one whe provide protection against the travelling waves.
There are basically two main sources of causing overvoltages viz. external
overvoltages mainly due to lightning and internal overvoltages due to switching
operations. The protection against external overveltages due to lightning can be
provided by methods which are known as shielding methods.
The shielding methods do not allow an are path to form between line and ground
thus giving protection in line design. For protection against internal overvoltages
no}
shielding methods are employed which allow an arc path between line and
ground. There is special provision of extinction of arc in these methods.
Use of ground wire for protection that has been described earlier is a shielding
method while use of spark gaps and lightning arresters are non-shielding methods,
Sometimes the non-shielding methods are also used fer giving protection against
external overvoltages.
The non shielding methods are based on the principle of insulation breakdown
When the overvoltage is incident on protective device, a part of energy content in it is
discharged to ground through the protective device.
The breakdown of insulation is function of voltage as well as time of its
application alongwith shape and size of the electrodes used. More steeper is the
voltage wave, the larger will be magnitude of voltage required for breakdown as
expenditure of energy is required for breakdown of dielectric in any form requires
time. This energy criterion for different insulators can be compared with the help of
term called Impulse ratio which is defined as the ratio of breakdown voltage due to
impulse of specified shape to the breakdown voltage at power frequency. For sphereProtection and Switchgear 12-19 Protection Against Overvoltage
The most commonly
employed protective device
against travelling waves is a
surge diverter. which is
connected between line and
Residual earth at the substation. The
voage travelling waves are diverted to
the earth with this diverter.
The travelling voltage wave
after reaching near the diverter
> sparks over at a certain
prefixed voltage. It is shown in
the Fig. 1213 (a) and (by
respectively.
This provides a conducting
path of low impedance between
line and earth. The residual or
discharge voltage will be
controlled to a safe value which
could be withstood by
insulation by the flow of
Fig. 12.43 current to earth through surge
impedance of the line.
(b) i
It is clear that the path of low impedance exists only when overvoltage occurs in
case of surge diverter while it comes to normal state immediately to offer high
impedance for normal working system voltage,
12.10 Requirements of Surge Diverter
The ideal surge diverter has following requirements.
i) It should not carry any current at normal system voltage i.e. its breakdown
voltage should be above any normal or abnormal fundamental frequency
voltage that may occur on the system.
ii) The transient voltage wave whose peak value is greater than the spark over or
breakdown voltage of surge diverter should breakdown as fast as possible to
provide path for surge to earth.
iii) After the breakd
discharge current without damage to it and the voltage should not be more
than its breakdown value.
mm, the surge diverts stould be capable of carrving12-20
Protection Agai
iv) When the transient voltage reduces below its breakdown value, the power
frequency current flowing through the diverter should be interrupted as
quickly as possible
12.11 Operation of a Typical Surge Diverter (Lightning Arrester)
Power
ine
i ! Spark
! ' gap
\ | Noningar
Lightning | +-+-—Nonines
eee '
Fig. 12.14 (a)
The basic form of any type of surge
diverter is shown in the Fig, 12.14 (a)
It consists of a spark gap which is in
series with a non linear resistor. The
terminal of the protected equipment is
connected on end of the diverter. The other
end of the diverter is solidly grounded
through non-linear resistor.
The length of a spark gap is set in such
a way that the normal system voltage is not
sufficient to initiate arc across the gap while
very high voltage will cause break down of
air insulation and are is initiated
The non-linear resistor bears a property
of decrease in its resistance as the voltage
increases and vice versa. The volt-amp
characteristics for a non linear resistor is shown in the Fig. 12.14 (b).
Fig. 12.14 (b)
Under normal condition, the diverter
is off without conducting any current or
very small negligible current due to
capacitive effect (Non-linear resistor
offers very high resistance to this current
hence it is negligible) Hence the gap is
not conducting.
Whenever high voltage occurs, there
is breakdown of air insulation initiating
the arc, Thus a low resistance path is
offered for the surge to the earth
Excess charge on the line because of
surge is conducted to the earth through
the arrester which prevents the surge
being sent back on line.Protection and Switchg 42
41 Protection Against Overvoltage
As there is breakdown of spark gap due to over voltage, the arc would be short
circuit on the system and may cause power follow current in the diverter. After the
surge iS over, the resistor offers very high resistance to prevent the effect of short
circuit which makes the spark gap non-conducting:
It should be observed that the are in the gap should immediately cease after the
surge is over to avoid the current flowing through gap and resistor which would be
damaged otherwise. The voltage drop across the arrester should be less than the
breakdown strength of the insulation of the equipment to be protected.
Presently following types of surge arresters are commonly used.
1. Valve type or gapped silicon-carbide surge arresters consisting of silicon
carbide discs in series with spark gap units.
Zine oxide gapless arresters or metal oxide arresters. These are gapless and
consisting of ZnO (Zine Oxide) discs in series. ‘These arresters are having
good volt-amp characteristics. The energy absorption level is also high and
these arresters are preferred for EHV and HVDC installations,
12.12 Classification of Surge Arresters
Based on current, voltage and energy capability the surge arresters are classified as
follows,
}) Station type surge arresters :
This type of arrester has the highest capacity for energy dissipation w lowest
level of protection. The peak discharge current that can carry is 10 kA while its
voltage range for operation is 3.3 kV to 245 kV (rms). They are employed normally in
large power stations and substations
2) Line type surge arresters +
‘These arresters are mainly used for protection of large transformers, intermediate
sub stations and medium and large power stations. They are smaller than station
transformers, ‘The standard discharge current carried safely by them is about 5 kA
while the working voltage range is 3.3 kV to 123 kV (rms).
3) Distribution type and secondary type surge arresters :
These type of arresters are used for protection of distribution transformers in
distribution circuits mounted on poles. The standard peak discharge current for its
operation is 25 kA and 15 kA. While its voltage range is up to 3.3 kV (rms).
There are three general types of surge diverters with each having its field of
application. They are
1) the rod gap
li) the protector tube or Expulsion type lightning arresterProtection and Switchgear 1
22 Protection Against Overvolta
iii) the conventional valve type lightning arrester
12.13 Terms and Specifications used in Surge Arresters
Following terms and specifications are generally used in reference with surge
arrester,
i) Non-linear resistor :
‘This is a part of arrester offering low resistance to the flow of discharge current of
the surge limiting, the voltage across arrester terminals while offering high resistance
to the flow of power frequency currents (inoperative for normal power frequency
voltage)
ii) Rated voltage of the arrester :
It is defined as the maximum permissible power frequency RMS voltage between
the line terminal and earth terminal of the arrester as specified by the manufacturer at
which surge arrester can perform its rated duty. Generally for all other equipments
rated voltage is between phase to phase while for surge arresiers it is between phase
and ground
ii} Follow current :
It is defined as the current that flows from connected power source through
lightning, arrester following the passage of the discharge current.
iv) Normal discharge current :
It is defined as that current which is flowing through the surge arrester after the
spark over, It is expressed as crest or peak value for a specified wave. These values
are given for various types of lightning arresters described in previous section.
v) Discharge current :
‘The surge current which flows through the arrester after the spark over is called
discharge current
vi) Power frequency spark over voltage :
It is defined as the rms value of power frequency voltage that is applied between
ling and earth terminals of the arrester causing the spark over of the series gap.
vii) Impulse spark over voltage :
‘The highest value of the voltage attained during an impulse of given polarity of
specified wave shape applied between line terminal and earth terminal of an arrester
before the flow of discharge current is called impulse spark over voltage.
viii) Re:
It is defined as the voltage which appears across line and earth terminal during
the flow or passage of discharge current.
jual or discharge voltage =Protection and Switchgear 12-23 Protection Against Overvoltage
ix) Rated current :
It is the maximum impulse current at which the peak discharge residual voltage is
determined.
x) Co-efficient of Earthing :
It is defined as the ratio of highest rms voltage of healthy phase to earth to the
phase to phase normal voltage. Mathematically it is given by,
Highest rms voltage of healthy phase to earth
Phase to phase normal rms voltage
Coefficient of earthing 100
12.14 Horn Gap Arrester
This type of arrester has two horn shaped metal rods separated by a small
distance. One end is connected to the line while the other is connected to the
earth, It is shown in the Fig. 12.15,
To tne Choke
apparatus
tobe protected
Hom
o
Fig. 12.15 Horn gap arrester
The horns are constructed in such manner that the distance between them
gradually increases towards the top. The horns are mounted on porcelain insulators.
The resistance R limits the follow current to a small value. The choke connected
between equipment to be protected and horn gap is designed in such a way as to
‘offer small reactance at normal power frequency while high reactance at transient
frequency. Hence the choke does not allow any transients to enter the apparatus to be
protected. By using the choke the steepness of the wave incident on the equipment to
be protected is reduced, While the choke also reflects the voltage surge back on to the
hom. The gap between the homs is adjusted in such a way that normal supply
voltage will not be sufficient to initiate arc across the gap.Protection and Switchgear 12-24 Protection Against Overvoltage
Under normal conditions, the gap is non-conducting whenever there is an
overvoltage in the system and its value is more then breakdown value of gap, spark
over takes place across small gap, The arc formed may be maintained by the normal
voltage also, The heated air around the are and the magnetic effect of the are cause it
to move up in the gap. The are acts like a flexible conductor, The arc moves
gradually through positions a, b, ¢ respectively. At some position (say c), lengthening
of are takes place as distance between the horns is too large. Thus the voltage is not
enough to maintain the are and it is extinguished. The excessive charge on the line is
therefore travelled to the earth through the arrester.
12.14,1 Advantages
1. After the surge is over, this type of arrester does not cause
the system as the arc is cleared by itself.
ort circuiting of
2. The follow current is maintained to a small value with the help of series
resistance,
12.14.2 Disadvantages
L. If the gap is bridged due to some external factors (such as birds) the device
will not work properly.
2. The setting of horn gap is required to be changed due to corrosion and pitting
which can affect its performance.
3. The time required for its operation is relatively more (about 3 seconds) than
recent fast operating devices.
4. It is harmful to employ this type of arrester on isolated neutral system.
Due to above limitations, the hom gap arrester is rarely used in practice. Also it
has low reliability and hence used as secondary protection.
12.15 Rod Gap Arrester or Spark Gap Arrester
It is the simplest, cheapest and most rugged form of surge diverter used for
protection of insulators in line, equipments and bushings. It is shown in the Fig. 12.16.
Please refer Fig. 12.16 on next page.
The conducting reds are provided between the line terminal and earthed terminal
of the insulator with an adjustable gap. The medium present in the gap is air. The
rods are either square or round with diameter approximately 12 mm and bent at right
angles. One rod is connected to the line circuit while the other rod is connected to
the earth, The gap between the rods may be in the form of horns or arcing rings.Protection and Switchgear 12-26 Protection Against Overvoltage
Under normal operating
conditions the = gap_— is
t non-conducting. When the high
Voltage voltage surge occurs on the line,
ink there is spark over in the gap and
current in surge is diverted to the
carth. Thus excessive charge on
the line is passed to the earth
through this. arrester. The
—+ — volt-time characteristics for a rod
gap is shown in the Fig. 12.17
Time in
microseconds
With the given gap and the
wave shape of the voltage, the
time required for the breakdown varies inversely with the voltage. The time for flash
over for positive polarity is less than that for negative polarity. Upto certain extent
the flash over voltage depends on the length of grounded rod, There is considerable
difference between positive and negative flash over voltages for low values of this
length. If the length is about 1.5 to 2 times the gap spacing then it is sufficient to
reduce this difference applicably. The gap setting is in such a way that its breakdown
voltage should be more than 30% below the voltage level of the equipment to be
protected that it can withstand.
Fig. 12.17
12.15.41 Limitat
Following are limitations of rod gap arrester.
ns
1. Precise protection is not achieved and is not reliable so it can not be used as
main protection against surge in high voltage systems. But as it is cheap it can
be a good choice for second line of defence.
2. It gives protection against waves with comparatively small sloping front. Also
the breakdown voltage varies with polarity, steepness and waveshape. The
performance is affected by polarity of surge.
3. The rods may get damaged due to excess heat produced by arc. This is an
important consideration in high voltage systems.
4. The performance is affected adversely due to climatic conditions such as
humidity, temperature pressure.
5. The power frequency follow current is not interrupted by this type of arrester
and it continues, to flow even after the high voltage surge is over. This creates
a line to ground (or earth fault) fault which is to be interrupted by circuit
breaker, Thus the operation of rod gap results in interruption of supply and
breakers must operate to de-energize the circuit to clear the flash over. TheProtection and Switchgear 12-27 Protection Against Overvoltage
are set up across the gap due to surge current ionizes the surrounding air
which affects the insulation strength of the gap. Also sufficient time must be
provided for deionization of are path before the reclosure of circuit breaker for
restoring supply. Hence it is generally used as back up protection,
‘There are some improvements in rod gap such as fused gap and control gap
which are also used in practice sometimes. The fused gap is simply a red gap along
with a fuse in series with it to cut the power follow current. But it requires
replacement and maintenance of fuse. Also for its effective operation it requires
proper co-ordination between blowing of fuse and adjacent relay timing.
‘The control gap consists of a double gap arrangement to get sphere gap
characteristics. Compared to rod gap its volt-time characteristics are better. It can be
used with or without fuses and used as a back up or secondary protection,
12.16 Multigap Arrester
It consists of a series of metallic cylinders
Line made up of alloy of zine generally insulated
from one another and separated by small air
gaps as shown in the Fig. 12.18.
oO Cylinder 1 is connected in series with the
line While cylinder 3 is connected to earth
r-—O through a series resistance. The series resistance
limits the arc, The protection against travelling
O waves is reduced due to series resistance. To
overcome this difficulty shunt resistance is
included in some of the gaps.
Shunt
resistance
Under normal operating conditions, cylinder
Series 2 is at earth potential and it is not possible to
resistance breakdown the series gaps by normal voltage.
When overvoltage occurs, there is
breakdown of the gap between 1 and 2. The
large current will pass through the gaps instead
Fig. 12:18 of choosing an altemate path through shunt
resistance and will divert to the earth.
After the surge is over, there is no are in between 2 and 3, the power follow
current is limited by shunt and series resistances as they are now in series. The
current is not enough te maintain arc in the gap between 1 and 2 and normal
conditions are restored. These arresters are used for system voltages upto 33 kVProtection and Switchgear 12-29 Protection Against Overvoltage
iii) The internal gap inside the tube.
iv) It has an open vent at the bottom for releasing the gases.
It consists of a series gap in series with internal gap inside a fibre tube. This gap
in the fibre tube is made up of two electrodes. The upper electrode is connected to
the series gap while the lower electrode is connected to the earth. One such arrester is
placed under each line conductor. It is required that the breakdown voltage of the
tube should be less than that of the insulation for which it is used.
Whenever Over voltage occurs on the line, there is breakdown in the series gap
and arc is formed between the electrodes in the tube. Thus providing a low
impedance path for lightning current to earth.
The heat produced by the arc vapourizes some of the organic material in the tube.
The resulting natural gas builds up high pressure in short ame and expelled out
through the bottom vent after producing lot of turbulance in the tube. After the gas
leaving from the tube violently, it carries ionized air around the arc
Due to this strong de-ionizing effect, the arc is extinguished without restriking
making current zero. The arc extinction time is about one or two half cycles which is
very short interval for protective relays to act. Hence circuit breakers remain closed
and line is kept in operation. After the expelling of gases and arc suppression, the
tube is ready for new operation, The power follow current is safely interrupted by
this type of arrester.
With each operation of
the tube the diameter of the
fibre tube is increased as
{ some part of fibre lining is
Positve a4Ky vapourized every time which
come Sone lowers insulation
vatage 23K characteristics of tube. The
13.8kv volt-time characteristics are
better than rod gap type and
are shown in the Fig. 12.20,
Excessive current flowing
neg through the tube may cause
its bursting while a small
current will be insufficient
Fig. 12.20
for producing necessary pressure to extinguish the are, Also as the gas producing
‘material is utilized each time when arrester operates, there is limitation of number of
operations which can be safely carried by this arrester. Since there is gaseous
discharge, it is not suitable for mounting, near other equipments.Protection and Switchgear 12-30 Protection Against Overvoltage
12.17.1 Advantages.
1) They are cheaper and can be installed easily,
2) They are capable of interrupting power follow current immediately after the
surge is over,
12.17.2 Disadvantages
1) The volt-amp characteristics for this arrester is poor and hence can not be used
for protection of expensive station equipment
2) It can not be mounted in an. enclased equipment because of discharge of gas
during its operation.
3) It can perform limited number of operations as some of the fibre is used in
every operation to produce gas for extinguishing the arc.
These type of lightning arresters are used on transmission towers near to the
stations in certain cases to make the station lightning arrester free from its duty to
certain extent by reducing the magnitude of surges coming on the line.
They are also used for protection against surges for transformers in rural areas as
they are cheap than valve type arresters, These arresters are also employed in some
special cases such as transmission towers with more height wherein there are more
chances of lightening strokes
Expulsion type arresters are either transmission type used for transmission line
insulators of distribution type for the protection of distribution transformer and
similar apparatus on distribution networks
12.18 Valve Type Lightning Arrester
It is an expensive surge diverter also known as non-linear surge diverter. The
details of this arrester are shown in the Fig. 1221. (See Fig. 12.21 on next page)
As shown in the figure, there are two assemblies viz.
i) series spark gaps
ii) non linear resistor disc’ made up of material such as thyrite or matrosil in
series.
‘The non linear elements are in series with the gap. Both these assemblies are
contained in tight porcelain container for reliable protection against moisture, humidity
and condensation.Protection and Switchgoai
‘The interrupting capacity of the spark gaps unit can be increased with the help of
grading resistors. Under normal working conditions, the leakage current is always
less than 0.1 mA approximately which flow through the resistors, This is sufficient to
maintain the enclosures at specified temperature above ambient so as to prevent the
effect of moisture into enclosure.
12.18.2 Non Linear Resistors.
The non-linear resistors are made of an inorganic compound viz. Thyrite or
Metrosil, These discs are in series to form a block. With the increase in applied voltage
and current, the resistance decreases quickly, The residual voltage is hence maintained
though current is high within limit. The non-linear resistors have the property of
providing high resistance to current flow of normal system voltage but low resistance
to flow of high surge currents ie, its resistance decreases with increase in current and
vice versa. Hence the power follow current after the surge is over can he easily
interrupted with the help of resistor blocks by spark gaps at first current zero.
12.18.3 Working
Under normal operating conditions, the system voltage is not enough to cause
breakdown of air gap assembly. Under the condition of over voltage, there is
breakdown of series spark gaps and the surge current quickly reaches to ground
through non linear resistors. The non-linear resistors will offer very small resistance
to the flow of surge current whose magnitude is large. Thus the surge is prevented
from sending back over the line. After the surge is over, the resistor blocks. offers
high
Alter approaching towards the equipment to be protected , the surge takes around
0.25 psec to reach to the arrester
and the whole operation of
sistance to the flow of power follow current and the current is interrupted.
arrester takes place in a very short
state interval of time in about 20 to 30
usec. The are is extinguished at
Voltage
first current zero by cooling and
lengthening of arc and also. the
voltage and current are almost in
phase
Dynamic
characteristics
The volt-ampere characteristics
® type lightning arrester is
‘ig. 12.22.
Curent —>
‘arent of vab
Fig. 12.22
shown in theProtection and Switchgear 12-33 Protect
n Against Overvoltage
‘The closed curve represents the dynamic characteristics corresponding te
application of voltage surge while the dotted line showing static characteristics. The
horizontal tangent drawn to the dynamic characteristics gives the voltage known as
residual voltage and is the peak voltage during discharge of surge current.
Depending upon the type of the arrester ie, either line type or station type
discharge voltage varies from 3 kV to 6 kV. This voltage is also affected by
magnitude and waveshape of discharge current.
The impulse ratio of unity is obtained for this arrester according to design of spark
gaps. Hence high values of surge currents can not be interrupted. The impulse
breakdown strength is smaller than residual voltage which decides the protection level
for insulation co-ordination.
The voltcurrent relationship for ene type of thyrite disc (nonlinear resistor) is
given by,
Vek
Resistance of the arrester = — Kit
Typical values of K and f are 4650 and 0.72.
With N number of thyrite discs,
NK
r
RI = NK = constant
Resistance, R = NKI*
12.18.4 Advantages
i) The operation of this arrester is very fast wit
ction of second.
a fr
ii) They are suitable for effective protection of transformers and cables against
surges.
12.18.5 Disadvantages
i) Very steep wave front type of surges are not being protected by these
arresters. Fortunately the lightning surges on the transmission system are
attenuated as they travel over the line towards the substations and they are
within the reach of protection circuits in the substations. But proper care
should be taken to prevent surges of severe intensity and efficient form of
shielding should be used.
ii) The performance of this type of arrester may be affected if there is entry of
moisture in the enclosure. This problem can be solved by sealing the container
herm
cally or enclosures are filled by inert gas and contain some form ofProtection and Switchgear 12-34 Protection Against Overvoltage
de-humidifier or allowing the leakage current to pass to maintain the
temperature within limits.
12.18.6 Applications
The valve type arrester is classified in following types.
i) Station type =
These arresters are efficient and expensive which are used for protection of
important equipments with rating from 2.2 kV to 400 kV and higher, It has highest
capability for dissipation of energy.
) Line type
The term “Line” is misleading as these arresters are not used for protection of
lines. Unlike station type, these are also used for protection of plants and substations
which are comparatively less important and economy is to be achieved. They are used
upto 66 kV except in some cases beyond it. They are smaller in cross section, weight
and cost than station type. ‘They provide protection against higher surge voltages than
station type but have less surge current capacity. Typical ratings of these arresters are
upto 5 kA to use in large transformers and intermediate substations.
i) Atrester for protecting Rotating Machines :
These are specially used for protection of generators and motors with voltage
range from 2,2, kV to 22 kV.
iv) Distribution type arrester :
These are generally used for protection of pole mounted distribution substations
and are available in the voltage range from 2.2 kV to 15 kV.
v) Secondary arresters :
These are used for protection of low voltage apparatus with the range of 120 V to
0
12.19 Metal Oxide Lightning Arresters
This is a new type of lightning arrester developed and used. It consists of
non-linear resistor block and main element of the arrester is metal oxide or normally
zine oxide (ZnO) which is economical compared to thyrite arresters. There are no
gap and its degree of non-linearity is more than that of thyrite arrester
The ZnO type of arrester provides better surge protection with more stable
protection characteristics and has simple construction similar to valve type but the
valve element is a dense ceramic body made up ef ZnO and other metallic oxides.Protection and Switchgear 12-35 Protection Against Overvoltage
12.20 Location of Lightning Arresters
‘The lightning arresters are normally located near the equipment to be protected.
Because of this, the chances of surges te enter the circuit between the protective
equipment (arrester) and the equipment to be protected are reduced. Secondly if there
is distance between arrester and protected equipment then a steep fronted wave after
being incident on lightning arresters, after spark over at the appropriate sparkover
voltage, enters the transformer after travelling over the lead between two and suffers
reflection at the terminal. The total voltage at the terminal of transformer is sum of
incident and reflected voltage which is approximately twice the incident voltage. If the
arrester is not at correct location then transformer may experience a surge of twice the
magnitude that on arrester. With L as the inductance of the lead between arrester and
equipment, the voltage incident at transformer terminal is given by,
where, Rate of change of surge current
If a capacitor is connected at the terminals of protected equipment then steepness
‘of wave is reduced which decreases rate di/dt which results in less distribution of
stress on winding of protected equipment.
The location of an arrester
in a substation depends on
what is the probability of
flashover on the line per one
hundred kilometers in a span
t of one year. The typical
Probability probability curve of peak
impulse current is shown. in
the Fig. 12.23.
The crest or peak value of
Peak surge and the characteristics
Impulse of arresters are also important.
It will not be economical and
necessary also to install one
arrester near to each equipment in the substation. The optimum use of arrester to
serve the intended purpose is to install it at the entry of incoming line.
Fig. 12.23
For indoor substations, the requirement of lightning arrester is comparatively less
as equipments there are connected by cables which attenuate the surges. Hence theProtection and Switchgear 12-36 Protection Against Overvoltage
duty of arrester in case of medium voltage range indoor substation is reduced
considerably.
12.21 Rating of Lightning Arrester
The discharge current in the surge is very large which is passed through the
arrester. But the time of discharge is less hence the energy dissipated is small. Hence
the important factor in selection of lightning arrester is the line to ground voltage that
the arrester is subjected during operation for any condition
Generally 5 % allowance is taken to consider the no-load condition of the line and.
sudden loss of load on generators. Thus. an arrester of 105% rating is used on a
system where line to ground voltage may reach line to line value during ground fault.
The rated voltage is maximum permissible rms value of power frequency voltage
while. still
carrying out effectively and without damage the automatic extinction of follow up
which is supported by the arrester across its line and earth terminal
current.
The voltage rating of the arrester must be greater than normal phase to ground
voltage to avoid high current flowing through arrester causing, terminal overloading,
In order to get the maximum voltage which can occur on system phases and ground
during fault on one of the phases, it is required to know system highest voliage and
co-efficient of earthing:
The highest voltage of the system is normally taken as 110 % of nominal system
voltage.
Highest rms voltage of healthy p'
Now, Coeff
mw Coe Phase to phase ni
jent of earthing =
Voltage rating of arrester = Highest phase to phase rms voltage
x coefficient of earthing
Voltage rating of arrester = 11x Phase to phase rms voltage
x coefficient of earthing
For effectively earthed system, the ¢o-efficient of earthing is 0.8.
If system vottage is 400 kV,
Rating of arrester = 1.1 x 400 x 0.8 = 352 KY
For non-effectively earthed systems, isolated or unearthed neutral system, arresters
are rated at 100 % of system highest voltage.
If phase to phase rms voltage = 400 kV with isolated or unearthed neutral system
Rating of arrester = 1.1 x 400 = 440 kVProtection and Switchgear 12-37 Protection Against Overvoltage
The nominal discharge current must have specific wave shape and crest value to
classify arrester with reference to its durability and protection characteristics. Different
ratings are tabulated as below. The wave shape for these ratings is 8/20 ps,
Application
Current Rating (kA)
Protection of important and main power and
substations in areas which are prone to lightning
Strokes more frequently with system voltages
above 66 kV.
2 5 Protection of other power and substations with
system voltages above 66 kV
3 25 Protaction of smail substations where divertars of
higher ratings are uneconomical with system
voltages unto 22 kV
4 18 Protection of rural distribution system where i is
necessary to install diverters more frequently for
protecting small transformers with systemn voltages:
‘ot more than 22 KV
Table 12.3
‘As per American practice, the wave shape is specified as 10/20 ps.
The power frequency spark over voltage should be 1.4 times the rated voltage of
arrester to avoid frequent sparking over of arrester due to internal over voltages of
insufficient magnitude. The maximum impulse spark over voltage is the magnitude of
1/50 psec voltage wave on which the arrester sparks over 5 times out of 5. The
residual or discharge voltage depends , for type and nominal voltage of arrester, on
waveform gradient (di/dt) and. magnitude of current. For determining this voltage, it
is recommended to use a current wave denoted by 8/20 psec. The discharge voltages
are fixed for a current of 5 kA or 10 kA. Maximum discharge current is referred to a
wave shape given by 5/20 yssec,
12.22 Tests on Lightning Arrester
Various. tests are performed on lightning arresters to evaluate its performance.
Some of the tests are listed below
1/50 impulse spark over test
Wave front impulse spark over test
Peak discharge residual voltage at rated diverter current
Impulse current withstand test
Switching impulse voltage test
aurepe
Peak discharge residual voltage at low currentProtection and Switchgear 12-38 Protection Against Overveltage
7, Discharge capacity of durability
8. Transmission line discharge test
9. Low current long duration test
10. Power duty cycle test
11. Pressure relief test
12.23 Surge Absorber
The steepness of wave front of travelling waves can cause damage to the
apparatus in addition to magnitude of wave. More steeper is the travelling wave, the
damage to the apparatus is more. Thus to reduce the steepness of wave front of the
surge, surge absorber is used.
‘The surge absorber is a protective device which can reduce the steepness of wave
front of a surge and absorbs energy contained in travelling wave. Though surge
diverter and surge absorber eliminate the surge, the way in which it is done is
different in two devices. The surge diverter diverts the surge to the earth while surge
absorber absorbs energy contained in the surge.
‘A capacitor connected between line and earth can reduce the steepness of wave
front. Similarly as the impedance of capacitor is inversely proportional to its
frequency, it gives protection against low voltage high frequency waves. Thus it can
be considered that the lines are connected to the earth so far as discharge at high
frequency is considered.
‘The capacitor is used for the protection of transformer winding to make it free
from very high stresses that may be set up in the tums. A pure capacitor can not
dissipate the energy in wave front or in high frequency discharge but it just reflects
the energy away from the equipment to be protected while the energy is dissipated in
the resistance of line conductors and earthing resistances. With a series combination of
resistor and capacitor, a part of energy is dissipated in the series combination in
addition to prevent it from approaching to the equipment, The arrangement is shown
in the Fig. 12.24 (i) and (ii), At normal power frequency, the reactance of capacitor is
high and practically no current flows to the ground.
‘The surge absorber may also be in the form similar to air cored transformer with
low inductance primary and single turn short circuited secondary to act for energy
dissipation, When the travelling wave is incident on the absorber, a part of energy is
dissipated as heat due to transformer action and by eddy currents. Because of series
inductances, the wave front steepness is reduced,Protection and Switchgear 12-39 Protection Against Overvoltage
Line ——»——— Transformer Line Transformer
® “
Fig. 12.24 Surge absorber using capacitor
In another type of surge absorber, a parallel combination of resistance and
inductance is used as shown in the Fig, 12.25 . This combination is placed in series
with the line steep wave fronts or high frequency discharges to find the inductive
path to have more reactance and are forced through resistance where they are
dissipated. The power frequency currents find inductive path of minimum impedance
(X, =2afLie X, = f) and pass through it without much loss.
‘The Ferranti surge absorber consists of
inductive coil magnetically coupled but
not electrically to a metal shield and the
steel tank containing it. The coil is
eylindteal and currents are induced in
metal shield. The absorber is enclosed
cylindrical boiler plate tank and is vacuum
Fig. 12.25 impregnated. It is similar to transformer
with short circuited secondary. The
inductor is primary while metallic shield acts as short circuited secondary dissipator.
‘The energy is dissipated as heat generated in a dissipator due to transformer action. It
is used for the protection of transformer. It is shown in the Fig. 12.26.
Due to filter effect, the high frequency currents are prevented from passing freely
through the absorber, The energy transferred through mutual induction is dissipated
in the form of heat in the dissipator.ist Overvoltage
Protection and Switchgear 12-40 Protection Ag
Meta! shiets Metal shield
Ling o——$— FT ITT ——an mn Line rT
a a,
Fig. 12.26 Ferranti surge absorber
12.24 Summary of Protective Devices Against Lightning Surges
Sr, No. Device Field of application
1 Rod gap type Bushing insulator, Support Insulator, Across insulator
String
2 | Overhead earthed ground | Above overhead transmission lines. , in the substation
wires, awa
3 | verticat masts ‘Substations
Earthed lightning rods Above tall buildings or structures
5 | Ughtning or surge arresters| Incoming lines in substations, Near terminals of
transformers and generators, Pole mounted distibution
systems
6 | Surge absorbers Near rotating machines or switchgear, Across series
reactors
Table 12.3
Review Questions
1. Explain the phontamenom of lightning discharge.
2, What are carious types of lightning strakes ? Explain tem ix detail
3. What are He haditiful effects of lightning strokes ont sidbstation cquipments ?
4. What are various methods of protection against lightning strokes ?
nsf direct lighting strokes
ter? Hh
5. How do earthing screen and ground wires provide protection a
are they
ree
What is a surge déveeter ? What is baske principle of operation of
classified?
2. Write short mates on the following types of arresters
1) Horm gap arrester 8) Rod gup arrester ili} Multigap arrester
fo Expulsion type arrester 2) Valoe type arresterProtection and Switchgear 12-44 Protection Against Overvoltage
& Explain clearly how rating of lightning arrester is selected. How the location of lightning arrester
is decided ?
9. Explain te following terms related to the ligheninrg arrester
4) Rate voltage) Follow exerreat 6) Discharge current
A) Power frequency spark dter toltage €) Impulse spark ater toltage
JP Residual voltage g) Rated current
10. What és tower footing resistance ? What are the methods to reduce this resistance ?
11, What & a grounud wire ? Discuss its location with respect Fo the Fine conductors,
12, Explain the operation of various types of surge absorbers
13, Whit do yo rican by coefficient af earthing ?
14, What are the basic ecqtirements of a good ligitning arrester ?
qoo2