Licenses ......................................................................................................................................... 6
- Programming interfaces (API) exist for all WinCC application modules and
enable data and functions to be accessed.
Uninstalling
When the access rights are transferred back from the PC to the key stick or to any
other data carrier, it is possible to prepare for transfer to another PC.
Virus scan
Virus tests can only the performed during operation with tested virus programs.
See FAQ 241 220 09.
Note It is not allowed to run WinCC in process mode without valid licenses. Neither the
name nor the attributes of the "AX NF ZZ" directory may be changed because the
transferred license keys can be irrecoverably lost.
Configurations Single-user systems are used in less complex applications and can also be used
for operating and monitoring separate sections of plant.
The configuration of the WinCC project which is always located on the server, can
also be performed on the client.
Standard client The standard client is also known as the "client without its own project".
Standard client The standard client is also known as the "client without its own project".
Redundant servers
When two WinCC stations are operating in parallel, the archives are compared
automatically during runtime or after a server fails.
The continuity of process control and operation is assured with automatic failover
of a client to the active server.
WinCC distributed system
Distributed system with multiple WinCC servers
Clients have access to up to 18 different servers or redundant server pairs.
With WinCC V7.0 only up to 12 different servers.
The required server information is imported
Individual configuration of each client (separate project)
Distribution of the tasks over several servers
Process and archive data is made available by the servers
Multi-client The multi-client is also known as a "client with its own project".
WebNavigator Option for SIMATIC WinCC for operator control and monitoring of plants via
the Internet, in-house intranet or LAN
Web server A Web server with the SIMATIC WinCC software. License is only stored
on the server. The simultaneous access of x WebClients is counted.
WebClient
Web client that allows control and monitoring of a running WinCC
project via an Internet browser with ActiveX support.
The WinCC basic system does not need to exist on the client computer.
It is also possible to use the Web client without the Microsoft Internet
Explorer.
Licensing
A license is required for using the Web server
Licenses are available for access to the Web server by 1, 3, 10, 30, 100 clients,
since WinCC V7.4 these licenses are countable
For remote diagnostics via multiple distributed Web servers with guaranteed
access, low priced Web Navigator diagnostics licenses are available
Architecture This slide displays the relationships of the individual modules within the WinCC
Explorer.
WinCC Explorer The WinCC Explorer combines all the data necessary for operating a single-user
or multi-user system and ensures hierarchically-ordered storage.
System Controller The system controller takes care of system communication between the stations.
For multi-user systems, the system controller also provides the network-wide
project view, as well as communication between the client and server. The system
controller also handles coordination through the terminal bus.
Data Manager The data manager is the start-up location for processing central tasks in a WinCC
project. The data manager exists on every station and works closely together with
the system controller. The main task is handling tag management. The
communication channels are used to access process data.
Function modules - Graphics Designer (graphics system) Graphic display and process connection
- Global scripts (script editing)
Making the project dynamic to user-specific requirements
- Alarm logging (message system)
Displaying messages and acknowledgements
- Tag logging (measured value archiving, processing and trending)
Processing measured values and their long-term storage
Processing user-oriented data and their long-term storage
- Report designer (report system) Reporting system states
Note The WinCC Explorer allows you to navigate through the WinCC applications and
their data with few operations. From its appearance and operation, the WinCC
Explorer is similar to the Explorer in Windows.
MS SQL Server Database Management System from Microsoft suitable for industry
WinCC V7.3 uses MS SQL-Server 2008 R2.
Openness This slide illustrates all system modules with opened interfaces.
You can use your own programs with Windows applications, as well as data and
functions from WinCC here.
User programs can also be started from WinCC.
Applications that run under Windows, such as Excel, Word, or Access can be
combined freely with WinCC and individual user programs.
This also makes solutions to unusual management level tasks possible.
User Routines
User routines run interpretively in WinCC. This means that a compiler is not
necessary. If an application requires many extensive user routines with a high
processing capacity, standard tools (e.g. C++) can compile these routines, and
they can be attached to the WinCC sequence.
WinCC supports
OPC Data Access 2.05a
OPC Data Access 3.00
OPC XML Data Access 1.00 (Connectivity Pack / Connectivity Station)
In the case of HardNet, the communication card has its own microprocessor and
relieves the PC processor during communication. With Ethernet, a CP 1613 for
example is used. The driver (S7 1613) requires a license.
Only a SoftNet module may be operated in the PC for the process communication.
Combinations with HARDNET communication cards are possible. The driver
software for HARDNET communication cards ships on the supplied SIMATIC NET
CDs.
SOFTNET Lean
Also uses, for example, the integrated Ethernet interface of the PC.
SOFTNET S7 Lean driver license is included in WinCC.
Max. 8 x S7 TCP/IP or Ind.Eth. or S5 TCP/IP
This makes 8 connections free of charge when using WinCC.