Model KSS: Automatic Transfer Switches Standard Specific-Breaker Rated
Model KSS: Automatic Transfer Switches Standard Specific-Breaker Rated
Ratings
Model Current Voltage, Frequency
KSS 40--600 amps 208--600 VAC, 50/60 Hz
800--1000 amps 208--480 VAC, 50/60 Hz
Contact Ratings
Motor Load
Resistive Load Inductive Load NC NO
Engine Start Contacts 2 A @ 30 VDC N/A N/A N/A
Auxiliary Contacts, (40--600A) ] 15 A @ 250 VAC N/A N/A N/A
Auxiliary Contacts, (800--1000A) ] 15 A @ 480 VAC 15 A @ 250 VAC; 5 A @ 125 VAC; 2.5 A @ 125 VAC;
6 A @ 500 VAC 3 A @ 250 VAC; 1.5 A @ 250 VAC;
1.5 A @ 500 VAC 0.75 A @ 500 VAC
] Auxiliary position-indicating contacts, one set Normal and one set Emergency
- Digital Meter (with MPAC 1200 only) - Surge Protection Device (SPD)
D Measure and display voltage, current, frequency, and D Surge protection reduces transient voltages to harmless
power for both sources levels
D Programmable visual alarms for high voltage, low voltage, D Protection modes: L-L / L-N / L-G / N-G
and high current D Replaceable phase and neutral cartridges for service
D Three digital outputs D Frequency: 50--60 Hz
D Serial port for optional network connections D Operating Temperature Range: --40 to 176_F
D Password-protected programming menus (--40 to 80_C)
D Joystick operation D Remote contacts for customer-supplied status indicators:
Contacts: 1 NO, 1 NC
D Factory-installed
Min Load: 12VDC / 10 mA
D Three digital outputs Max. Load: 250 VAC / 1 A
D Joystick operation Wire Size (max.): 16AWG
D Fuse protection: 30 amps / 600 V
- Extended Limited Warranties
D UL 1449, 3rd Edition for Type 2 applications
D 2-year basic
D IEC 61-643-1, 2nd Edition T2/11
D 5-year basic
D See additional specifications below
D 5-year comprehensive
D 10-year major components
Additional Controller Accessories
- Export Packaging See the controller spec sheet for more information.
- Heater, Anti-Condensation - Accessory Modules (with MPAC 1200 only)
D Hygrostat-controlled 120 VAC strip heater D Alarm Module
(customer-supplied voltage source required)
D External Battery Supply Module
D 100 or 250 watts (sized for enclosure)
D Input/Output Module
D Protective 15 amp circuit breaker
D High-Power Input/Output Module
- Literature Kits
- Controller Disconnect Switch
D Production literature kit
(one kit is included with each transfer switch) - Ethernet Communications
D Overhaul literature kit
- Current Sensing Kit (with MPAC 1200 only)
- Neutral Assembly
- Line-to-Neutral Voltage Monitoring
D Available as loose kit for open units (with MPAC 1200 only)
- RSA III Remote Serial Annunciator - Padlockable User Interface Cover
D Monitors the generator set
D Monitors Normal and Emergency source status and - Supervised Transfer Control Switch
connection (with MPAC 1200 only)
D Monitors ATS common alarm
D Allows remote testing of the ATS
For more information, see specification sheet G6--139.
SPD Specifications
Max. Limiting Voltage, (L-N/N-G/L-G) Maximum
Nominal Discharge UL VPR 3rd Ed (kV) Short Circuit Continuous
Voltage Current (L-N/N-G/L-G) Withstand Operating
(V ±15%) (kA) Phase Poles (kV) at 3kA at 10kA Current (kA) Voltage (VAC)
240 / 120 40 Split 3 0.6 / 1.2 / 0.7 0.6 / 0.4 / 0.6 0.8 / 0.7 / 0.8 200 175 / 350
208 / 120 40 Wye 4 0.6 / 1.2 / 0.7 0.6 / 0.4 / 0.6 0.8 / 0.7 / 0.8 200 175 / 350
480 / 277 40 Wye 4 1.0 / 1.2 / 1.1 1.0 / 0.4 / 1.0 1.2 / 0.7 / 1.2 200 320 / 460
240 / 120 40 HLD 4 1.0 / 1.2 / 1.1 1.0 / 0.4 / 1.0 1.2 / 0.7 / 1.2 200 320 / 460
600 / 347 40 Wye 4 1.3 / 1.2 / 1.4 1.3 / 0.4 / 1.3 1.5 / 0.7 / 1.5 200 440 / 880
Model Designation
Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Miscellaneous
Record the transfer switch model designation in the boxes. The transfer switch model designation defines
characteristics and ratings as explained below.