Low Pressure Gas Piping Pressure Loss Calculation

This document calculates the pressure loss for gas piping from a microturbine generator based on pipe diameter, length, flow rate, and number of elbows. It determines that a 6-inch pipe is required for the first section and a 3-inch pipe for the second section to maintain over 4 inches of water column pressure at the generator. The total pressure drop is calculated to be 0.88 inches, leaving over 6 inches of pressure from the gas supply.

Uploaded by

John A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
216 views1 page

Low Pressure Gas Piping Pressure Loss Calculation

This document calculates the pressure loss for gas piping from a microturbine generator based on pipe diameter, length, flow rate, and number of elbows. It determines that a 6-inch pipe is required for the first section and a 3-inch pipe for the second section to maintain over 4 inches of water column pressure at the generator. The total pressure drop is calculated to be 0.88 inches, leaving over 6 inches of pressure from the gas supply.

Uploaded by

John A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Microturbine GAS PIPING PRESSURE LOSS CALCULATION

Pipe sizing shall be based on equation 4-1 of Section 402.4 of the 2006 International Fuel & Gas Code.
Nominal Pipe Size Actual ID
0.381 10 10.02
Q
D 0.206
8 7.981
 H  6 6.065
19.17  

4 4.026
 Cr * L  3
2.5
3.068
2.469
2 2.067
D = Inside diameter of the pipe, inches. 1.5 1.61
Q = Input rate of the appliance(s), CFH. 1.25 1.38
L = Equivalent length of pipe, feet. 1 1.049
delta H = Pressure drop, in. of water column. 0.75 0.824
Cr = 0.6094

Generator 100% Cap. (Required Gas Pressure: 4"-7" w.c.)


Pipe Section Equiv. Length (ft.) Gas Load (CFH) Actual PD (in.of H2O) Req. Pipe Size (in.) Actual Pipe Size
A-B 44 11800 0.085682025 6.07 6.065
B-C 158 3300 0.796903734 3.07 3.068

Leaving Pressure from Gas Co. Regulator (in. of H2O): 6.9


Total Pressure Drop to Appliance (in. of H2O): 0.882585759
Delivered Gas Pressure to Appliance (in. of H2O): 6.017414241

A-B (Assumes 20 lf with (3) 90's at 8 equiv. lf/ea)


B-C (Assumes 130 lf with (7) 90's at 4 equiv. lf/ea)