SIPROTEC 7SS85

Low Impedance Centralized Busbar Protection

www.siemens.com/siprotec

Description
The SIPROTEC 7SS85 busbar protection is a selective, safe
and fast protection against busbar short circuits in medi-
um, high and extra-high voltage systems with a large
variety of busbar configurations.
Selection of the device base functionalities (significant
properties) and the modular hardware structure permit
optimum adaptation of the SIPROTEC 7SS85 to a large
variety of system configurations and functional require-
ments up to a comprehensive station protection.
Configurations
The SIPROTEC 7SS85 is suited for the following system
configurations:
• Single busbars with/without transfer busbar
• Double busbars with/without transfer busbar Busbar Protection SIPROTEC 7SS85

• Triple busbars
• Breaker-and-a-half layout method
• Dual circuit-breaker systems and one or two current Functions
transformer(s) per feeder • The table "Functions and Templates" shows all
• Truck-Type Switchgear functions that are available in the SIPROTEC 7SS85. All
functions can be configured as required with DIGSI 5
• Systems with combined busbars (alternatively
main/transfer busbar) • Using some functions requires the appropriate num-
ber of free function points to be available in the
• T circuit arrangements
device. The function point calculator in the online
• H connection arrangement with busbar coupler or configurator provides support in determining the
disconnection required number of function points for your device
• Ring busbars • The necessary function points are also shown during
project engineering with DIGSI 5
Characteristic Key Values of SIPROTEC 7SS85
• Phase-selective measurement and display
• Selective tripping of faulty bus zones
Selective and safe

• Disconnector-independent check zone as additional • Various control possibilities, such as bay out of order,
tripping criterion acquisition blocking from disconnectors and circuit
breakers, blocking of protection zones or circuit-
• Shortest tripping times (<7 ms) to ensure network
breaker failure protection, make the adaptation to op-
stability and minimize damage to the system
erationally caused special states of your system easier
• Highest stability in case of external faults, even in • Optional 1/3-pole or 3-pole circuit-breaker failure
case of transformer saturation, through stabilization protection using the integrated disconnector image to
with flowing currents trip all circuit breakers of the busbar section affected
• Operate curve with freely adjustable characteristic • Optional end-fault protection for the protection of the
curve sections section between circuit breaker and current trans-
• Additional operate curve with increased sensitivity for former for feeders and bus couplers
low current faults, for example in resistance-grounded • Direct tripping of protection zones through external
power systems signals
• Fast recognition of internal and external faults re- • Release of the tripping of a protection zone through
quires only 2 ms of saturation-free time of the current additional external signals
transformer
• Release of tripping through additional, external phase-
• Using closed iron core or linearized current transform- selective signals
ers in a plant is possible
• Optional phase/ground overcurrent protection for
• Adaptation of different current transformer ratios per each bay
parameterization
• Optional cross stabilization as additional tripping
• Three interacting methods of measurement allow release in 3-pole encapsulated gas-insulated switch-
minimum tripping times after busbar faults and en- gear
sure maximum stability in case of large short-circuit
• Optional bus coupler differential protection for fault
currents
clearing in couplers with two current transformers
• The integrated circuit-breaker failure protection rec-
ognizes circuit-breaker faults in the event of a busbar Benefits
short circuit and provides a trip signal for the circuit • Safety by measuring methods proven and reliable for
breaker at the line end. The adjacent busbar trips if a 25 years
coupling circuit breaker fails
• Simple creation and adaptation of the configuration
• There is extensive monitoring of current transformer
by the user over the entire service life
circuits, measured value acquisition and processing,
and trip circuits. This prevents the protection from • Clearly structured by fully graphical engineering and
functioning too tightly or too loosely, which reduces online plant visualization with DIGSI 5
the effort for routine checks
• Protection of up to 20 feeders with a single device

For all products using


security features of
OpenSSL, the
Siemens AG following shall apply:
Energy Management Division This product includes
Freyeslebenstraße 1 software developed
91058 Erlangen, Germany by the OpenSSL
Project for use in the
SIPROTEC 7SS85 profile E7.5.docx OpenSSL Toolkit
(www.openssl.org),
Printed in Germany | © 09.17 Siemens AG cryptographic soft-
ware written by Eric
E-Mail: [email protected] Young
Tel: +49 180 524 70 00 ([email protected])
and software devel-
oped by Bodo
Moeller.

You might also like