Page 1 of 10 Field Inspection and Test Record Transformer Protective Relay

The document provides a summary of field inspection and testing of transformer protective relays at the Pattaya Tai Substation. Key points tested include: 1. The relays' behavior under different time synchronization loss conditions. 2. The relays' operation in test and normal modes with different configurations of the secondary devices and intertrip signals. 3. The operation of GOOSE and shared variable alarms between devices when secondary devices lose power. The tests confirmed the correct operation of the protective relay functions and signaling during different conditions. Representatives from the project company and provincial authority witnessed and confirmed the test results.

Uploaded by

Noptana Tummasit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views10 pages

Page 1 of 10 Field Inspection and Test Record Transformer Protective Relay

The document provides a summary of field inspection and testing of transformer protective relays at the Pattaya Tai Substation. Key points tested include: 1. The relays' behavior under different time synchronization loss conditions. 2. The relays' operation in test and normal modes with different configurations of the secondary devices and intertrip signals. 3. The operation of GOOSE and shared variable alarms between devices when secondary devices lose power. The tests confirmed the correct operation of the protective relay functions and signaling during different conditions. Representatives from the project company and provincial authority witnessed and confirmed the test results.

Uploaded by

Noptana Tummasit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

Page 1 of 10

FIELD INSPECTION AND TEST RECORD

TRANSFORMER PROTECTIVE RELAY


SUBSTATION : PATTAYA TAI SUBSTATION LOCATION : 115kV ST & MU PANEL
PROJECT : โครงการพพัฒนาโครงขข่ายไฟฟฟ้าอพัจฉรริ ยะ (Smart Grid) PANEL : =TCPP2 & TCPP2SM
CONTRACT NO. : จ.281/2560 DEVICE NO. : TCPP2 & TCPP2SM

1. TIME SYNCHRONIZATION FAIL CONDITION


Time Syn Loss < 10 Min Time Syn Loss > 10 Min
No. DEVICE NAME FUNCTION MU
SHOULD BE RESULT SHOULD BE
1 TCPP2Main (CSC-326) 87T, 50BF SM1,2, INCSM TRIP NOT TRIP
2 TCPP2 Backup1 (CSC-211) 50/51N, 50BF SM2 TRIP TRIP
3 TCPP2 Backup2 (CSC-211) 51GB SM3 TRIP TRIP
Noted : Pull out IRIG-B cable at MU and Relay

2. TEST MODE AND NORMAL MODE CONDITION


2.1 TCPP2Main
DEVICE MODE RESULT
NO. SM1 BO SM2 BO SM3 BO INC02SM RELAY
TCPP2Main TCPP2SM1 TCPP2SM2 TCPP2SM3 INC02SM
MAKE MAKE MAKE BO MAKE TRIP

1 TEST TEST TEST TEST TEST TRIP TRIP X TRIP 87T TRIP
2 TEST TEST NORMAL NORMAL TEST TRIP X X TRIP 87T TRIP

2.2 TCPP2 Backup 1


DEVICE MODE RESULT
NO. TCPP2 SM1 BO SM2 BO SM3 BO INC02SM RELAY
TCPP2SM1 TCPP2SM2 TCPP2SM3 INC02SM
Backup1 MAKE MAKE MAKE BO MAKE TRIP
50/51N
1 TEST TEST TEST TEST TEST TRIP TRIP X TRIP
TRIP
50/51N
2 TEST NORMAL TEST NORMAL NORMAL X TRIP X X
TRIP

2.2 TCPP2 Backup 2


DEVICE MODE RESULT
NO. TCPP2 SM1 BO SM2 BO SM3 BO INC02SM RELAY
TCPP2SM1 TCPP2SM2 TCPP2SM3 INC02SM
Backup2 MAKE MAKE MAKE BO MAKE TRIP
51GB
1 TEST TEST TEST TEST TEST TRIP TRIP X TRIP
TRIP
51GB
2 TEST NORMAL NORMAL TEST NORMAL X X X X
TRIP
3 NORMAL NORMAL NOMAL TEST NORMAL X X X X X
51GB
4 NORMAL NORMAL NOMAL NORMAL TEST TRIP TRIP X X
TRIP
Page 2 of 10

FIELD INSPECTION AND TEST RECORD

TRANSFORMER PROTECTIVE RELAY


SUBSTATION : PATTAYA TAI SUBSTATION LOCATION : 115kV ST & MU PANEL
PROJECT : โครงการพพัฒนาโครงขข่ายไฟฟฟ้าอพัจฉรริ ยะ (Smart Grid) PANEL : =TCPP2 & TCPP2SM
CONTRACT NO. : จ.281/2560 DEVICE NO. : TCPP2 & TCPP2SM

RESPONSIBILITY TESTED BY CONFIRMED BY WITHESSED BY

COMPANY ITALTHAI ENGINEERING ITALTHAI ENGINEERING PROVINCIAL ELECTRICITY AUTH


SIGNATURE
NAME
DATE
Page 3 of 10

115kV ST & MU PANEL


=TCPP2 & TCPP2SM
TCPP2 & TCPP2SM

Time Syn Loss > 10 Min


RESULT

RESULT
RELAY RELAY RECIEVE
TRIP CURRENT
87T TRIP RECIEVE
87T TRIP RECIEVE

RESULT
RELAY RELAY RECIEVE
TRIP CURRENT
50/51N
RECIEVE
TRIP
50/51N
RECIEVE
TRIP

RESULT
RELAY RELAY RECIEVE
TRIP CURRENT
51GB
RECIEVE
TRIP
51GB
RECIEVE
TRIP
X RECIEVE
51GB
RECIEVE
TRIP
Page 4 of 10

115kV ST & MU PANEL


=TCPP2 & TCPP2SM
TCPP2 & TCPP2SM

WITHESSED BY

PROVINCIAL ELECTRICITY AUTHORITY


GOOSE/SV A
1. TCPP2Main

GOOSE/SV Alarm
NO. Condition

TCPP2Main TCPP2SM1 TCPP2SM2


1 TCPP2SM1 Power Off GOOSE/SV Alarm Normal
2 INC02SM Power Off SV Alarm GOOSE Alarm GOOSE Alarm
3 TCPP2SM2 Power Off Normal Normal
4 TCPP2SM3 Power Off SV Alarm GOOSE Alarm Normal
5 BZPMain1 Power Off Normal GOOSE Alarm GOOSE Alarm
6 TCPP2Main Power Off GOOSE Alarm GOOSE Alarm

2.TCPP2 Backup1

GOOSE/SV Alarm
NO. Condition

TCPP2 Backup1 TCPP2SM1 TCPP2SM2


1 TCPP2SM2 Power Off GOOSE/SV Alarm Normal
2 TCPP2 Backup2 Power Off GOOSE Alarm GOOSE Alarm GOOSE Alarm
3 TCPP2 Backup1 Power Off GOOSE Alarm GOOSE Alarm
3.TCPP2 Backup2

GOOSE/SV Alarm
NO. Condition

TCPP2 Backup2 TCPP2SM1 TCPP2SM2


1 TCPP2SM3 Power Off GOOSE/SV Alarm Normal Normal
2 TCPP2SM2 Power Off GOOSE Alarm Normal
OOSE/SV ALARM CONDITION

Result (Relay&SM)
OSE/SV Alarm
Relay Trip SM1 SM2
87T Make BO Make BO
PP2SM2 TCPP2SM3 INC02SM
Normal Normal no no no
Normal no no no
Normal Normal yes yes no
Normal yes yes yes
Normal Normal yes yes yes
GOOSE Alarm GOOSE Alarm no no no

Result (Relay&SM)
OSE/SV Alarm
Relay Trip SM1 SM2
50/51N Make BO Make BO
PP2SM2 TCPP2SM3 INC02SM
Normal Normal no no no
Normal GOOSE Alarm yes yes yes
GOOSE Alarm GOOSE Alarm no no no
Result (Relay&SM)
OSE/SV Alarm
Relay Trip SM1 SM2
51GB Make BO Make BO
PP2SM2 TCPP2SM3 INC02SM
Normal no no no
Normal Normal yes yes yes
y&SM) Result (HMI)

INC02SM
Control Status
Make BO

no yes yes
no yes yes
yes no no
yes yes yes
yes yes yes
no yes yes

y&SM) Result (HMI)

INC02SM
Control Status
Make BO

no no no
yes yes yes
no yes yes
y&SM) Result (HMI)

INC02SM
Control Status
Make BO

no yes yes
yes no no