Experimental Research On Power Quality Improvement Using Capacitor Bank For 500 kVA Three Phase Transformer
Experimental Research On Power Quality Improvement Using Capacitor Bank For 500 kVA Three Phase Transformer
Volume 3 Issue 5, August 2019 Available Online: www.ijtsrd.com e-ISSN: 2456 – 6470
Copyright © 2019 by author(s) and KEYWORDS: Power quality; Power factor; Capacitor bank; Reactive power
International Journal of Trend in Scientific compensation; apparent power
Research and Development Journal. This INTRODUCTION
is an Open Access article distributed Power quality has always been a major concern in any electrical power system
under the terms of design. Power Factor (PF) is one of the measures of the overall power quality
the Creative and must be considered in a system that has a large amount of capacitive and
Commons Attribution inductive loads which can cause poor power factor such as leading and lagging
License (CC BY 4.0) power factors. In electrical engineering, power factor is only related to AC
(http://creativecommons.org/licenses/by circuits. There is no power factor in DC circuits due to zero frequency.
/4.0)
The power factor of a system is composed of two elements, electrical systems design concepts as well as advancements
active power and apparent power. Active power is the useful in power electronic technologies may shift the design
power. Apparent power is the aggregate of active power and philosophy for implementing PF correction.
reactive power. This ratio is also equal to the cosine of the
angle between the voltage and the current of the system. POWER FACTOR CORRECTION TECHNIQUES
When the overall power factor of a generating station’s load If reactive power compensator is supplied near the load, the
is low, the system is inefficient and the cost of electricity line current, power losses can be reduced or minimized and
corresponding high [1]. To overcome this, and at the same voltage regulation can also be improved at the load
time ensure that the generators and cables are not loaded terminals. The reactive power elements which can control
with the wattles current, the supply authorities often the reactive power distribution and flows are [5][6][7]:
impulse penalties for low power factor [2] [3].
1. Synchronous condenser
Depending on load, power factor can be classified as lagging 2. Shunt capacitor
power factor, leading power factor and unity power factor. 3. Series capacitor
Poor PF like lagging power factor and leading power factor
can lead to excessive current requirements and may also 4. Shunt reactor
cause operating issues with electric generators, motors, 5. Static Var compensator
transformers, the generation and the distribution systems. It
6. Saturable transformer
makes the electrical system less efficient, and has the
potential to damage the machines. To accommodate these 7. Tap-staggered transformer
issues, various devices are used to balance the reactive
power being provided or absorbed. Today, the most common Among these types, reactive power compensation can be
way to improve a poor “lagging” PF in any plant due to implemented with the capacitor bank connected in parallel
inductive loads is to install “PF improvement capacitors”[4]. or in series with the load simply and effectively. Moreover,
This method is a time proven means for correction provided two types of capacitor bank can be classified as follow [7]:
at a reasonable cost and with typically good reliability when 1. Fixed type capacitor bank
there were not many non-linear loads. However, modern 2. Automatic type capacitor bank
@ IJTSRD | Unique Paper ID – IJTSRD26637 | Volume – 3 | Issue – 5 | July - August 2019 Page 1202
International Journal of Trend in Scientific Research and Development (IJTSRD) @ www.ijtsrd.com eISSN: 2456-6470
A. Fixed Type Capacitor Bank (or)
The reactive power supplied by the fixed capacitor bank is Reactive Power = (ApparentPower)2 (Real Power)2 (7)
constant irrespective of any variations in the power factor
and the load of the receivers. These capacitor banks are (or)
switched on either manually by a remote-controlled
contactor. Q= (S) 2 (P) 2 (8)
This type of capacitor bank can be used in the following S= P + j Q (where j is the imaginary unit) (9)
application:
1. Where the load factor is reasonably constant. Capacitor Rating = Multiplying Power Factor kW Demand
2. Electrical installations with constant load operating 24 (10)
hours a day (or)
3. Reactive compensation of transformers
4. Individual compensation of the motors Capacitor Rating = kVAR – kVAR (11)
5. Where the kVAR rating of the capacitors is less than, or (Uncorrected) (Corrected)
equal to 15% of the supply transformer rating, a fixed
value of compensation is appropriate. 2
6. Size of Fixed Capacitor bank Qc ≤ 15% kVA transformer % Line Current Reduction = 100 1 PresentPowerFactor
ImprovedPowerFactor (12)
B. Automatic Type Capacitor Bank
The reactive power supplied by the capacitor bank can be 2
adjusted according to variations in the power factor and the % Power Losses = 100 Present Power Factor (13)
Improved Power Factor
load of the receivers. The equipment is applied at points in
an installation where the active-power or reactive power
variations are relatively large, for example:
% Loss Reduction=100 1 Present Power Factor
2
@ IJTSRD | Unique Paper ID – IJTSRD26637 | Volume – 3 | Issue – 5 | July - August 2019 Page 1203
International Journal of Trend in Scientific Research and Development (IJTSRD) @ www.ijtsrd.com eISSN: 2456-6470
TABLE1. SURVEY OF TU (MANDALAY) LOAD PATTERN = 137.6 kVAR
IN JUNE, 2018 =150kVAR (Around)
Real Reactiv Apparen Power
Time Power e Power t Power Factor Actually, 0.95 power factor is reasonable for application but
(kW) (kVAR) (kVA) (P.F) 0.99 power factor is considered for future load expansion.
1:00 AM 30.55 18.04 36.56 0.85 So, 150kVAR automatic shunt type capacitor bank is
2:00 AM 32.23 20.11 37.72 0.83 installed at the secondary side of the transformer.
3:00 PM 31.45 25.12 40.11 0.81
4:00 PM 45.23 34.04 55.43 0.8 EXPERIMENTAL SET-UP
5:00 PM 43.16 40.02 58.01 0.75 To correct entire University's loads, 150kVAR (5 × 30 kVAR)
6:00 AM 71.33 110.34 129.75 0.55 automatic capacitor bank are installed at the secondary side
7:00 AM 75.76 98.11 123.42 0.60 of the transformer. The system maintains the power factor at
8:00 AM 76.3 109.00 131.78 0.58 0.99 with considering the future load demand as that
9:00 AM 97.76 102.10 140.56 0.7 university. It eliminates too much kVAR at light-load periods
and undesirable over-voltages.
10:00 AM 95.78 96.88 136.22 0.7
11:00 AM 97.76 145.70 175.00 0.56
12:00 PM 99.63 108.00 145.11 0.7
1:00 PM 90.67 93.45 130.55 0.69
2:00 PM 100.24 106.90 146.03 0.7
3:00 PM 100.20 106.02 143.77 0.69
4:00 PM 100.08 138.47 169.47 0.55
5:00 PM 43.1 59.00 72.88 0.6
6:00 PM 65.67 100.01 116.99 0.57
7:00 PM 74.22 82.91 110.71 0.68
8:00 PM 73.34 77.79 104.79 0.7
9:00 PM 60.78 62.90 88.90 0.69
10:00 PM 51.42 50.82 73.99 0.7 Fig.2 Connection Diagram of 150kVAR Capacitor Bank
11:00 PM 45.77 45.71 63.66 0.7
12:00 PM 30.15 32.09 43.09 0.7 TU (Mandalay) has variable load conditions and inductive
loads. So, automatic capacitor banks are used for power
factor correction of this university. The following figures
3(a), (b) and (c) are complete installation diagrams of five
numbers of 30 kVAR ( 30kVAR×5=150kVAR) automatic
capacitor bank for power factor correction. Figure 2 shows
the connection diagram of 150kVAR capacitor bank for 500
kVA three-phase transformer for TU (Mandalay).
Therefore,
Capacitor Rating =Multiplying Factor × kW Demand
= 1.376 × 100 (b)
@ IJTSRD | Unique Paper ID – IJTSRD26637 | Volume – 3 | Issue – 5 | July - August 2019 Page 1204
International Journal of Trend in Scientific Research and Development (IJTSRD) @ www.ijtsrd.com eISSN: 2456-6470
C. Experiment 3
When all of 30kVAR (5×30kVAR=150kVAR) automatic
capacitor are on in the experiment 3, the following
experimental and calculation results shown in table 4 are
obtained. Experimental Result for 0.99 of power
improvement is also illustrated in figure 4.
A. Experiment 1
In the experiment 1, three numbers of 30kVAR (90kVAR)
automatic capacitor are on and the remaining two capacitors
are off. Under this condition, the following experiment
results are obtained. Table 2 shows not only the experiment
but also the calculation results using equations 1 to 15.
B. Experiment 2
In the experiment 2, four numbers of 30kVAR (120 kVAR)
Fig. 4 Experimental Result for 0.99 of Power Improvement
automatic capacitor are on and the remaining one capacitors
are off. The experiment and calculation results are shown in
COMPARISON RESULTS FOR WITH AND WITHOUT
table 3.
CAPACITOR BANK
The table below is to illustrate some variables obtained from
TABLE3. EXPERIMENTAL AND CALCULATION RESULTS
power factor changes. Capacitor rating added to improve
OF EXPERIMENT 2
power factor can be determined. Capacitor rating is the
Experiment Results
difference between kVAR ratings of original power factor
Capacitor Bank (kVAR) 120 and desired power factor. From Table 5, 120 kVAR capacitor
Power factor 0.95 bank is needed to improve power factor from 55 % to 95 %.
Qremain(kVAR) 21.05
P (kW) 100 The higher the power factor improves, the less the
S (kVA) 101.93 transformer loading. Consequently, load amperes drop. In
Calculation Results turn, the lower the power factor, the more the transformer
% Line Current Reduction 17.73 loading. Thus, load currents increase. In this paper, load
% Power Losses 33.52 variables with constant load 100 kW at 95 % power factor
% Loss Reduction 66.48 are 101.93 kVA and 21.05 kVAR.
@ IJTSRD | Unique Paper ID – IJTSRD26637 | Volume – 3 | Issue – 5 | July - August 2019 Page 1205
International Journal of Trend in Scientific Research and Development (IJTSRD) @ www.ijtsrd.com eISSN: 2456-6470
TABLE5. COMPARISON RESULTS FOR WITH AND From the figures 5, 6 and 7, the %power lossess, reactive
WITHOUT CAPACITOR BANK power and apparent power are directly proportional to the
Specification
Without
With CB
power factor. The power factor approaches to 1, the net
CB apparent power is nearly equal to real power.
0.85
Power factor 0.55 (Penalty 0.95 0.99 In the international policy, the electricity bill payment
PF)
system is based on the apparent power, S(kVA). By
Capacitor
- 90 120 150 improving the quality of power factor, the consumer based
Bank (kVAR)
Qremain(kVAR) 138.47 49.71 21.05 0.75 on international policy will reduce the electricity bill
P (kW) 100 100.09 103.42 101.14 significantly. The formula including active power, apparent
S (kVA) 169.47 113.17 101.93 101.93 power and power factor is P= S cosϕ. The apparent power is
% Line inversely proportional to the power factor. The magnitude of
Current - 12.47 17.73 19.75 the current flowing through the device is less on the
Reduction electrical devices. So, users can get the better life time of the
% Power
- 41.87 33.52 30.86
electrical devices.
Losses
% Loss In Myanmar, the electricity bill payment system is based on
- 58.13 66.48 69.14
Reduction the real power, P(kW). Although the consumers improve the
power factor quality, the users will not be reduced the
Reactive Power (kVAR) electricity bill significantly. By installing Capacitor Bank, the
150 reactive power, Q(kVAR) and the apparent power, S(kVA),
will be decreased. By improving power factor, it is better for
100 electrical appliances and can improve the lifetime of the
electrical devices.
@ IJTSRD | Unique Paper ID – IJTSRD26637 | Volume – 3 | Issue – 5 | July - August 2019 Page 1206
International Journal of Trend in Scientific Research and Development (IJTSRD) @ www.ijtsrd.com eISSN: 2456-6470
APPENDIX
REFERENCES
[1] Juan Dixon (SM), “Reactive Power Compensation [6] Oshima K., “Recent Development of Power Capacitor
Technologies” State-of-the-Art Review (Invited Paper), Review” Nissan Electric Review, (2003)
1957
[7] Stangland, G.: The Economic Limit of Capacitor
[2] Miller T. J. E., “Reactive Power Control in Electrical Application for Load Relief, Power Engineering, pp. 78-
System”, Corporate research and development center, 80, November 1950
General Electric Company, Schemectamy, New York.,
[8] Marbury, R. E.: Power Capacitors, Westinghouse
John Wiley & sons Press, (1982)
Electric Corporation, February, 1949
[3] Samiran Choudhuri, S. P. Choudhury, R. K.
[9] Cuttino, W. H.: Extending the Use of Shunt Capacitors by
Mukhopashyay and T. Choudhury, 1990., “Reactive
means of Automatic Switching, AIEE Summer Meeting,
Power Compensation inIndustrial power Distribution
St. Louis, Missouri, June 26-30, (1944)
System”, Power System for the Year 2000 and Beyond,
Bombay, India. [10] Marija LLic, “Handbook of Electric Power Calculations”
McGraw-Hill, Inc, (2000)
[4] Marbury, R. E.: Power Factor Correction Releases Plant
Capacity, Electrical South, March 1942 [11] Nagrath I. J.,“Power System Engineering” Tata Mc Graw-
Hill Publishing Company Limited, (2000)
[5] G. Brunello, B. Kasztenny ,C. Wester, “Shunt Capacitor
Bank Fundamentals and Protection” Conference for [12] Ma Marlar Thein Oo, 'Design and Construction of
Protective Relay Engineers –Texas A&M University, Capacitor Bank for Industrial Plant', JULY, 2008
(2003).
@ IJTSRD | Unique Paper ID – IJTSRD26637 | Volume – 3 | Issue – 5 | July - August 2019 Page 1207