The document provides load calculations for various areas in a building including rooms, reception, common areas, dining area, kitchen, and other areas. It lists the active load, quantity, total load for each area as well as the final total load calculated as 131kW. After applying a jerk load allowance and power factor, the minimum generator rating required is calculated as 203kVA.

Uploaded by

Shankar Sanyal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
355 views2 pages

Power Load Analysis Report

The document provides load calculations for various areas in a building including rooms, reception, common areas, dining area, kitchen, and other areas. It lists the active load, quantity, total load for each area as well as the final total load calculated as 131kW. After applying a jerk load allowance and power factor, the minimum generator rating required is calculated as 203kVA.

Uploaded by

Shankar Sanyal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Area Act. Load (W) Qty Tot.

Load (kW) Area


Room 1,690 68 115
Reception 324 1 0
Common Area 1,157 1 1
Conference / Banquet - 1 -
Dining Area 1,697 1 2
Room
Kitchen 3,472 1 3
Other Areas 1,100 1 1
Other Loads 8,500 1 9

Total Load 131 kW


Jerk Load Allowance 0.80
Reception
Final Load 164 kW
PF 0.95
Total Load 173 kVA
DG Loading 85%
Min. DG Rating Reqd. 203 kVA
Common Area
Please fill the row Qty (nos)

Conference / Banquet

Dining Area

Kitchen

Other Areas

Other Loads
Item Rating (W) Qty Tot. Load (W) DF Act. Load (W) Tot. Load (W)
Room Lights 12 4 48 0.60 29
Fan 70 1 70 0.75 53
AC (1.0 ton) 1,200 0 0 0.60 -
AC (1.5 ton) 1,500 1 1500 0.60 900
TV & DTH 150 0 0 0.60 -
1,690
Charging Points 15 2 30 0.50 15
Washroom Lights 12 2 24 0.40 10
Exhaust Fan 120 1 120 0.70 84
Geyser 1,500 0 0 0.30 -
Geyser 2,000 1 2000 0.30 600
Lights 12 12 144 1.00 144
Fan 70 2 140 1.00 140
AC (2 ton) 2,000 0 0 0.75 -
324
TV & DTH 125 0 0 1.00 -
Charging Points 10 4 40 0.50 20
Printer, etc. 200 1 200 0.10 20
Lights 12 70 840 0.70 588
Fan 70 6 420 0.70 294
AC (2 ton) 2,000 0 0 0.75 -
1,157
TV & DTH 125 0 0 1.00 -
Charging Points 15 10 150 0.50 75
Appliances 200 2 400 0.50 200
Lights 12 0 0 1.00 -
Fan 70 0 0 1.00 -
AC (2 ton) 2,000 0 0 0.60 -
-
TV & DTH 150 0 0 1.00 -
Charging Points 75 0 0 0.50 -
Appliances (Heating plates) 200 0 0 0.50 -
Lights 12 40 480 0.80 384
Fan 70 8 560 0.80 448
AC (2 ton) 2,000 0 0 0.75 -
1,697
TV & DTH 150 1 150 0.60 90
Charging Points 75 10 750 0.50 375
Appliances 400 5 2000 0.20 400
Lights 12 6 72 1.00 72
Chimney 1,000 1 1000 0.70 700
Exhaust Fan 250 0 0 0.70 -
Refrigerator 200 2 400 0.50 200
Chiller 500 1 500 0.60 300
3,472
Freezer 500 1 500 0.60 300
Microwave 1,200 2 2400 0.10 240
RO & Dispenser 400 2 800 0.70 560
Appliances 500 2 1000 0.50 500
Geyser 2,000 1 2000 0.30 600
Indoor Light 12 0 0 1.00 -
External Light 50 10 500 1.00 500
1,100
External Light 100 6 600 1.00 600
Appliances 200 0 0 0.70 -
Lift 11,000 1 11000 0.70 7,700
Water Pump 2,000 1 2000 0.40 800 8,500
Pressure pump 2,000 0 0 0.50 -