Area Act. Load (W) Qty Tot.
Load (kW) Area
Room 1,690 68 115
Reception 324 1 0
Common Area 1,157 1 1
Conference / Banquet - 1 -
Dining Area 1,697 1 2
Room
Kitchen 3,472 1 3
Other Areas 1,100 1 1
Other Loads 8,500 1 9
Total Load 131 kW
Jerk Load Allowance 0.80
Reception
Final Load 164 kW
PF 0.95
Total Load 173 kVA
DG Loading 85%
Min. DG Rating Reqd. 203 kVA
Common Area
Please fill the row Qty (nos)
Conference / Banquet
Dining Area
Kitchen
Other Areas
Other Loads
Item Rating (W) Qty Tot. Load (W) DF Act. Load (W) Tot. Load (W)
Room Lights 12 4 48 0.60 29
Fan 70 1 70 0.75 53
AC (1.0 ton) 1,200 0 0 0.60 -
AC (1.5 ton) 1,500 1 1500 0.60 900
TV & DTH 150 0 0 0.60 -
1,690
Charging Points 15 2 30 0.50 15
Washroom Lights 12 2 24 0.40 10
Exhaust Fan 120 1 120 0.70 84
Geyser 1,500 0 0 0.30 -
Geyser 2,000 1 2000 0.30 600
Lights 12 12 144 1.00 144
Fan 70 2 140 1.00 140
AC (2 ton) 2,000 0 0 0.75 -
324
TV & DTH 125 0 0 1.00 -
Charging Points 10 4 40 0.50 20
Printer, etc. 200 1 200 0.10 20
Lights 12 70 840 0.70 588
Fan 70 6 420 0.70 294
AC (2 ton) 2,000 0 0 0.75 -
1,157
TV & DTH 125 0 0 1.00 -
Charging Points 15 10 150 0.50 75
Appliances 200 2 400 0.50 200
Lights 12 0 0 1.00 -
Fan 70 0 0 1.00 -
AC (2 ton) 2,000 0 0 0.60 -
-
TV & DTH 150 0 0 1.00 -
Charging Points 75 0 0 0.50 -
Appliances (Heating plates) 200 0 0 0.50 -
Lights 12 40 480 0.80 384
Fan 70 8 560 0.80 448
AC (2 ton) 2,000 0 0 0.75 -
1,697
TV & DTH 150 1 150 0.60 90
Charging Points 75 10 750 0.50 375
Appliances 400 5 2000 0.20 400
Lights 12 6 72 1.00 72
Chimney 1,000 1 1000 0.70 700
Exhaust Fan 250 0 0 0.70 -
Refrigerator 200 2 400 0.50 200
Chiller 500 1 500 0.60 300
3,472
Freezer 500 1 500 0.60 300
Microwave 1,200 2 2400 0.10 240
RO & Dispenser 400 2 800 0.70 560
Appliances 500 2 1000 0.50 500
Geyser 2,000 1 2000 0.30 600
Indoor Light 12 0 0 1.00 -
External Light 50 10 500 1.00 500
1,100
External Light 100 6 600 1.00 600
Appliances 200 0 0 0.70 -
Lift 11,000 1 11000 0.70 7,700
Water Pump 2,000 1 2000 0.40 800 8,500
Pressure pump 2,000 0 0 0.50 -