ASCE7 Example Wind 10

This document provides information for calculating wind loads on a sign structure according to the ASCE 7-02 standard. It includes details about the building geometry, occupancy classification, construction type, live loads, and wind speed/topographic factors. Calculation of partially enclosed vs open/closed structures and adjustment factors are also discussed. The purpose is to guide wind load calculations and structural design of the example sign.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
250 views5 pages

ASCE7 Example Wind 10

This document provides information for calculating wind loads on a sign structure according to the ASCE 7-02 standard. It includes details about the building geometry, occupancy classification, construction type, live loads, and wind speed/topographic factors. Calculation of partially enclosed vs open/closed structures and adjustment factors are also discussed. The purpose is to guide wind load calculations and structural design of the example sign.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Company JOB TITLE Example 10 - Sign

Address
City, State JOB NO. SHEET NO.
Phone CALCULATED BY DATE
other CHECKED BY DATE

CS09 Ver 10.01.10 www.struware.com

STRUCTURAL CALCULATIONS
FOR

Example 10 - Sign

Guide to Wind Load Procedures of ASCE 7-02


Company JOB TITLE Example 10 - Sign
Address
City, State JOB NO. SHEET NO.
Phone CALCULATED BY DATE
other CHECKED BY DATE

www.struware.com

Code Search
Code: ASCE 7 - 02

Occupancy:
Occupancy Group = B Business

Occupancy Category & Importance Factors:


Occupancy Category = I
Wind factor = 0.87
Snow factor = 0.80
Seismic factor = 1.00

Type of Construction:
Fire Rating:
Roof = 0.0 hr
Floor = 0.0 hr

Building Geometry:
Roof angle (θ) 0.00 / 12 0.0 deg
Building length (L) 2.0 ft
Least width (B) 50.0 ft
Mean Roof Ht (h) 80.0 ft
Parapet ht above grd 0.0 ft
Minimum parapet ht 0.0 ft

Live Loads:
Roof 0 to 200 sf: 20 psf
200 to 600 sf: 24 - 0.02Area, but not less than 12 psf
over 600 sf: 12 psf

Floor
Typical Floor 50 psf
Lobbies & first floor corridors 100 psf
Corridors above first floor 80 psf

Mechanical 100 psf


Stairs & Exitways 100 psf
Balcony / Deck 50 psf
Partitions 20 psf
Company JOB TITLE Example 10 - Sign
Address
City, State JOB NO. SHEET NO.
Phone CALCULATED BY DATE
other CHECKED BY DATE

Wind Loads :
Importance Factor 0.87
Basic Wind speed 90 mph
Directionality (Kd) 0.85
Exposure Category C
Enclosure Classif. Partially Enclosed
Internal pressure +/-0.55
Kh case 1 1.208
Kh case 2 1.208

Type of roof Monoslope

Topographic Factor (Kzt)


Topography Flat
Hill Height (H) 80.0 ft
Half Hill Length (Lh) 100.0 ft
Actual H/Lh = 0.80
Use H/Lh = 0.50
Modified Lh = 160.0 ft
From top of crest: x= 50.0 ft
Bldg up/down wind? downwind

H/Lh= 0.50 K1 = 0.000


x/Lh = 0.31 K2 = 0.792
z/Lh = 0.50 K3 = 1.000
At Mean Roof Ht:
Kzt = (1+K1K2K3)^2 = 1.00

Gust Effect Factor Flexible structure if natural frequency < 1 Hz (T > 1 second).
h= 80.0 ft use 20.0 However, if building h/B < 4 then probably rigid structure (rule of thumb).
B= 50.0 ft h/B = 0.40 Therefore, probably rigid structure
/z (0.6h) = 48.0 ft use 70.0

G= 1.09 Using flexible structure formula

Rigid Structure Flexible or Dynamically Sensitive Structure


/ε = 0.20 Natural Frequency (n1) = 0.7 Hz
l= 500 ft Damping ratio (β) = 0.01
zmin = 15 ft /b = 0.65
c= 0.20 /α = 0.15
gQ , gv = 3.4 Vz = 96.3
Lz = 581.1 ft N1 = 4.22
Q= 0.93 Rn = 0.056
Iz = 0.18 Rh = 0.304 η= 2.674 h= 80.0 ft
G= 0.89 use G = 0.85 RB = 0.426 η= 1.672
RL = 0.866 η= 0.224
gR = 4.104
R = 0.828
G = 1.094
Company JOB TITLE Example 10 - Sign
Address
City, State JOB NO. SHEET NO.
Phone CALCULATED BY DATE
other CHECKED BY DATE

Enclosure Classification
Test for Enclosed Building: A building that does not qualify as open or partially enclosed.

Test for Open Building: All walls are at least 80% open.
Ao ≥ 0.8Ag

Test for Partially Enclosed Building:


Input Test
Ao 0.0 sf Ao ≥ 1.1Aoi YES
Ag 0.0 sf Ao > 4' / 0.01Ag NO
Aoi 0.0 sf Aoi / Agi ≤ 0.20 NO Building is NOT Partially Enclosed.
Agi 0.0 sf

Conditions to qualify as Partially Enclosed Building. Must satisfy all of the following:
Ao >= 1.1Aoi
Ao > smaller of 4' or 0.01 Ag
Aoi / Agi <= 0.20
Where:
Ao = the total area of openings in a wall that receives positive external pressure.
Ag = the gross area of that wall in which Ao is identified.
Aoi = the sum of the areas of openings in the building envelope (walls and roof) not including Ao.
Agi = the sum of the gross surface areas of the building envelope (walls and roof) not including Ag.

Reduction Factor for large volume partially enclosed buildings (Ri) :


If the partially enclosed building contains a single room that is unpartitioned , the internal
pressure coefficient may be multiplied by the reduction factor Ri.

Total area of all wall & roof openings (Aog): 0 sf


Unpartitioned internal volume (Vi) : 0 cf
Ri = 1.00

Altitude adjustment to constant 0.00256 :


Altitude = 0 feet Average Air Density = 0.0765 lbm/ft3
Constant = 0.00256
Company JOB TITLE Example 10 - Sign
Address
City, State JOB NO. SHEET NO.
Phone CALCULATED BY DATE
other CHECKED BY DATE

Wind Loads - Other Structures:

Importance Factor = 0.87


Gust Effect Factor (G) = 1.09 Wind Speed 90 mph
Kzt = 1.00 Exposure C

A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
Height to centroid of Af (z) = 80.0 ft M = 50.00 Case A & B
Dist to sign top (h) 80.0 ft N = 20.00 ft Cf = 1.20
Height (s) 20.0 ft M/N = 2.50 ft F = qz G Cf Af = 24.3 Af
Width (B) 50.0 ft Kz = 1.208 Af = 10.0 sf
qz = 18.5 psf F = 243 lbs
Directionality (Kd) 0.85
Percent of open area
to gross area 0.0%

B. Open Signs & Lattice Frameworks (openings 30% or more of gross area)
Height to centroid of Af (z) 15.0 ft Kz = 0.849
Base pressure (qz) = 13.0 psf
Width (zero if round) 2.0 ft Either width or diameter must be zero
Diameter (zero if rect) 2.0 ft D(qz)^.5 = 7.22 F = q z G Cf A f = 0.0 Af
Percent of open area ∈ = 0.65 Solid Area: Af = 10.0 sf
to gross area 35.0% Cf = 0 F = 0 lbs
Directionality (Kd) 0.85

C. Chimneys, Tanks & Similar Structures


Height to centroid of Af (z) 15.0 ft Kz = 0.849
Cross-Section Square Base pressure (qz) = 13.8 psf
Directionality (Kd) 0.90 h/D = 15.00
Height (h) 15.0 ft
Width (D) 1.0 ft
Type of Surface N/A

Square (wind along diagonal) Square (wind normal to face)


Cf = 1.28 Cf = 1.67
F = qz G Cf Af = 19.3 Af F = q z G Cf A f = 25.1 Af
Af = sf Af = 10.0 sf
F= 0 lbs F = 251 lbs

D. Trussed Towers
Height to centroid of Af (z) 15.0 ft Kz = 0.849
∈ = 0.27 Base pressure (qz) = 15.3 psf
Tower Cross Section square
Member Shape flat Diagonal wind factor = 1.2
Directionality (Kd) 1.00 Round member factor = 1.000

Square (wind along tower diagonal) Square (wind normal to face)


Cf = 3.24 Cf = 2.70
F = qz G Cf Af = 54.3 Af F = q z G Cf A f = 45.2 Af
Solid Area: Af = 10.0 sf Solid Area: Af = 10.0 sf
F= 543 lbs F = 452 lbs