Joint Inspection Report - Raceways/Trays

This document provides a joint inspection report for raceways and trays for the Line 7 metro project in Mumbai. It details the inspection of materials by representatives from MMRDA, AICA GC, and Sterling & Wilson. Parameters like size, thickness, coating thickness, and source of materials were checked for items like raceways, junction boxes, cable trays, and accessories to ensure compliance with project specifications. Test reports, certificates, and documents were also reviewed. The inspection found the materials to be in accordance with defined BOQ and code parameters.

Uploaded by

sachin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
91 views10 pages

Joint Inspection Report - Raceways/Trays

This document provides a joint inspection report for raceways and trays for the Line 7 metro project in Mumbai. It details the inspection of materials by representatives from MMRDA, AICA GC, and Sterling & Wilson. Parameters like size, thickness, coating thickness, and source of materials were checked for items like raceways, junction boxes, cable trays, and accessories to ensure compliance with project specifications. Test reports, certificates, and documents were also reviewed. The inspection found the materials to be in accordance with defined BOQ and code parameters.

Uploaded by

sachin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

JOINT INSPECTION REPORT - Raceways/Tr

PROJECT : LINE 7 (ANDHERI TO DAHISAR EAST


MRTS CORRIDOR)
CLIENT : MUMBAI METROPOLITAN REGION DEVELOPMENT AUTHORITY (MMRDA)

CONSULANTS : AICA GC

E&M Contractor- M/S Sterling & Wilson

Inspection by

Name of the Saff / representative Designation

2 Mr. Paresh Pawar

3 Mr. Musa Ashraf

4 Mr. Sachin Kharat


5 Mr. Rohit Poojary

Check findings
Sr. No. Parameters to check Parameter defined in
BOQ/Specification/codal
provisions

Applicable codes :IS 277: 2003, IS 2629

1 Raceway

Check whether the sample(material) is


in line with BOQ parameters defined in
the contract.
A size 200 X 50 mm
a Thickness 2 mm
b Micron/ GSM min 18 micron/minimum 260 GSM
B size 100 X 50 mm
a Thickness 2 mm
b Micron/ GSM min 18 micron/minimum 260 GSM
Check the Source of Material is Bharati,
C selectedd from the vendor list specified Unitech,Steelways,MEM,BEC,Profa
from the appendix F(Indicative vendor b,Indiana RK Engg and equivalent
list)
cadmium plates brass screw conter
D
Screw for removable cover sunk type
Check Invoice/recieving Challan of should be submitted at the time of
E
Material. material receive at site

2 Raceway junction box

Check whether the sample(material) is


in line with BOQ parameters defined in
the contract.

A size 150 X 150 mm

a Thickness
2 mm

b Micron/ GSM
min 18 micron/minimum 260 GSM

B size 250 X 250 mm

a Thickness
2 mm

b Micron/ GSM
min 18 micron/minimum 260 GSM
Check the Source of Material is selected Bharati,
C from the vendor list specified from the Unitech,Steelways,MEM,BEC,Profa
appendix F(Indicative vendor list) b,Indiana RK Engg and equivalent
Check Invoice/recieving Challan of should be submitted at the time of
D
Material. material receive at site

3 PERFORATED CABLE TRAY

Check whether the sample(material) is


in line with BOQ parameters defined in
the contract.

A size 300mm X 40 mm

a Thickness
2 mm

b Micron/ GSM
min 40 micron/minimum 450 GSM

c Type of tray flange


doubleed bend type

B Vertical Inside Bend 45D angular type


300mm X 40 mm

a Thickness
2 mm

b Micron/ GSM
min 40 micron/minimum 450 GSM
c Type of tray flange
doubleed bend type

d Radius of Bend should be 12 times the diameter of


largest LV cable

C Vertical outside Bend 45D angular type


300mm X 40 mm

a Thickness
2 mm

b Micron/ GSM
min 40 micron/minimum 450 GSM

c Type of tray flange


doubleed bend type

d Radius of Bend should be 12 times the diameter of


largest LV cable

D Bend 90D angular type


300mm X 40 mm

a Thickness
2 mm

b Micron/ GSM
min 40 micron/minimum 450 GSM

c Type of tray flange


doubleed bend type

d Radius of Bend should be 12 times the diameter of


largest LV cable

E Equal Tee
300mm X 40 mm

a Thickness
2 mm

b Micron/ GSM
min 40 micron/minimum 450 GSM

c Type of tray flange


doubleed bend type

Bharati,
F Check the Source of Material is selected Unitech,Steelways,MEM,BEC,Profa
from the vendor list specified from the b,Indiana RK Engg and equivalent
appendix F(Indicative vendor list)
Check Invoice/recieving Challan of should be submitted at the time of
G
Material. material receive at site

4 Ladder Type cable Tray

Check whether the sample(material) is


in line with BOQ parameters defined in
the contract.
A size 300mm X 40 mm

a Thickness
2 mm
b Micron/ GSM
min 40 micron/minimum 450 GSM

c Runner
20x75x20x2.5mm

d Rungs 20x30x20x2.5mm 250mm center to


centre

Bharati,
B Check the Source of Material is selected Unitech,Steelways,MEM,BEC,Profa
from the vendor list specified from the b,Indiana RK Engg and equivalent
appendix F(Indicative vendor list)
Check Invoice/recieving Challan of should be submitted at the time of
C
Material. material receive at site
5 Physical appearance
a Shape machine bends
b Coating It should be rust proof
6 Documents of measuring instruments
Micrometer, Vernier
a Name:
Calliper,Elcometer

b Caliberation certificate: sholud be submitted with instrument


7 Accessories
A GI slotted Angle
Size- ISA 35 X 35X 5 mm ISA 40 X 40 X 5 mm
Hot dip galvanized/ powder
a Material coated/pre galvanized / stainless
steel
c Dimension as per BOQ/TS/ code ISA 40 X 40 X 5 mm
(i) Thickness 5mm
(ii) micron 100
B GI Threaded Rod
Size- 12 mm 12 mm
Hot dip galvanized/ powder
a Material coated/pre galvanized / stainless
steel
c Dimension as per BOQ/TS/ code 12 mm
(i) Thickness 5mm
(ii) micron 100

Documents submitted/available if any


8 with sample (for major items only)
should be submitted at time of
a Test certificate of source of material
material receive on site
b GTP should be submitted with TDS
c MTP
d Third Party test report should be perform for major items
e FAT should be perform for major items
f SAT should be perform for major items
Approval/performance certificate issued by
g Atleast 2 metro projects
other metro projects
h supporting PO copies Atleast 3 projects PO copies
i ISO certificate Valid and renewed
j BIS certificates Valid and renewed
k Company financial documents As per GCC
l Trademark certificates
m Quality certificate
n Company Profile
o Incorporation certificate

E&M Contractor AICA-GC


Name: Name:
N REPORT - Raceways/Trays

Doc. No. MEP/ML7/SA/003

THORITY (MMRDA) Date of inspection -15/05/2019

Organization

MMRDA

AICA-GC

AICA-GC
Sterling& Wilson Ltd.

heck findings
contractor
Accetance criteria
Actual measured submission
value/compliances

200 X 50 mm
2.04; 2.01; 2.3 mm
19.4; 17.9; 16.7 micron
100 X 50 mm
2.01; 2.00; 2.06 mm
19.5; 18.5; 18micron

Profab

S/S &GI counter sunk


type
150mmx150mmx68mm

2.17,2.21,2.25 mm

22,16.6,17.5

not meaured

not meaured

not meaured

profab

300mm X 40 mm

2.5,2.25,2.44

43,47,39

doubleed bend type

300mm X 40 mm

1.68; 1.84; 1.68

57; 52; 63
doubleed bend type

not measured

300mm X 40 mm

2.31; 2.62;

70; 60; 66

doubleed bend type

not measured

300mm X 40 mm

1.75; 2.30

78; 54; 49

doubleed bend type

not measured

300mm X 40 mm

2.3; 2.9; 2.10

54; 70; 50

doubleed bend type

profab

300mm X 40 mm

2.54,2.30,2.19
14.4,11.7,12.5

20x75x20x2.5mm

20x30x20x2.5mm

profab

bends are equivalent


no rust on material

Vernier Calliper,
Elcometer
Calibration certificate
Available submitted

ISA 35 X 35X 5 mm

Hot dip galvanised GI


ISA 35 X 35X 5 mm
5.71; 5.7; 5.94 mm
124; 131; 137

12 mm

Hot dip galvanised GI


12 mm
5.71; 5.7; 5.94 mm
124; 131; 137
MMRDA
Name:

You might also like