4    Isolation Rooms
4        Isolation Rooms
    4.1 General
    An isolation facility aims to control the airflow in the room so that the number of airborne infectious
    particles is reduced to a level that ensures cross-infection of other people within a healthcare
    facility is highly unlikely. This may be achieved by:
          Control of the quantity and quality of intake or exhaust air.
          Maintain different air pressures between adjacent areas.
          Designing airflow patterns for specific clinical procedures.
          Diluting infectious particles with large air volumes.
          Air filtration – HEPA filters, etc.
    Isolation facilities include the following types:
         Neutral or standard room air pressure, for example standard air conditioning, also known as
          Class S
         Positive room air pressure where an immune-compromised patient is protected from
          airborne transmission of any infection, Class P
         Negative room air pressure, where others are protected from any airborne transmission from
          a patient who may be an infection risk, Class N
         Negative room air pressure with additional barriers including an Anteroom, also known as
          Class Q for quarantine isolation.
    Isolation rooms have fairly high rates of air exchange relative to other patient areas. This applies
    to both ventilation air supply and exhaust flow rates. Potential draughts within the patient room
    can result, therefore thermal comfort of the patient needs special attention. Consideration should
    be given to installing individual thermostats in each room so that air temperature and relative
    humidity can be controlled from within the room.
    Isolation rooms do not necessarily always require the provision of an Anteroom. This should be
    determined by the proposed operational policy and be included at an early stage of the design
    process. Where an Anteroom is however a requirement, it must be provided with self-closing
    doors and be of sufficient area to allow for the donning or removal of personal protective
    equipment or clothing.
    An assessment should be made of the service requirements of the Isolation/ Anteroom in order to
    determine the practicality of sealing junctions at penetrations to ceiling and wall linings. In some
    instances, the number of service penetrations in partitions and ceilings may suggest the
    introduction of a “false” wall, or additional partition. The false wall provides a means of locating
    service points while maintaining the integrity of differential air pressures; due to the room’s
    external lining not having been penetrated. This method should achieve the best air pressure
    containment possible.
    Figure 15: Typical HEPA Filter                                     Typical HEPA filter construction
                   International
                   Health Facility Guidelines                © TAHPI           Part B: Version 5 2017     Page 19
4    Isolation Rooms
4.2 Anterooms
An Anteroom or airlock lobby, when attached to an Isolation room, functions as:
    A controlled area in which the transfer of supplies, equipment and persons can occur without
     contamination impacting on the surrounding health care areas
    A barrier against the potential loss of pressurisation
    Controls the entry or exit of contaminated air when the anteroom door is opened
    A controlled area where personal protective equipment (PPE) or clothing can be donned or
     removed prior to entry/exit of the isolated contamination area.
The Anteroom will require sufficient space to allow for storage of Personal Protective Equipment
(PPE) i.e. gowns and gloves for protective isolation. Anterooms should not be shared between
Isolation rooms.
Where an Ensuite is provided for the Isolation Room, the Ensuite entry door should not be located
within the Anteroom. The typical Anteroom plan appears below:
Figure 16: Typical Anteroom plan
The Anteroom is provided for access to the Bedroom by staff and visitors and does not need to
permit bed access. Separate entry doors to the Bedroom are provided for bed access.
The reason bed access is not required through the Anteroom includes the following principles:
    The patient Bedroom is strongly negatively pressured in relation to the adjacent corridor;
     when the door to the Bedroom is open, air from the corridor will be drawn into the Bedroom –
     there is no escape of organisms from the Bedroom into the corridor
    Similarly, the Anteroom is negatively pressured in relation to the corridor, when the door from
     the corridor to the Anteroom is opened, air is drawn from the corridor into the Anteroom
    The Bedroom is also negatively pressured in relation to the Anteroom, when the door
     between the Bedroom and Anteroom is open, air will flow into the Bedroom and not escape
     through the Anteroom
    Strongly negatively pressured rooms will prevent air from the Anteroom, Bedroom and
     Ensuite escaping into the corridor.
Negatively pressured rooms should have a pressure gauge and alarm system to advise when
pressurisation has not been achieved.
              International
              Health Facility Guidelines                © TAHPI      Part B: Version 5 2017   Page 20
4    Isolation Rooms
The flow of air for class N Isolation rooms and recommended pressure differentials is
demonstrated in the diagram below:
Figure 17: Typical Negative Pressure Isolation Room with Anteroom & Ensuite, showing airflows and relative
pressure gradients
4.3 Recommended Pressure Gradients
Where an isolation room is not provided with an Anteroom, the recommended minimum differential
pressure between the isolation room and adjacent spaces should be 15 Pa. If however an
Anteroom is provided, the recommended minimum differential pressure between isolation room
and ambient pressure should be 30 Pa. Any additional pressure gradients between successive
pressurized areas should not be less than 15 Pa.
Recommended pressure gradients are:
              International
              Health Facility Guidelines                      © TAHPI       Part B: Version 5 2017     Page 21
4       Isolation Rooms
    Type of Pressurization *                              Isolation Room               Anteroom                   Ensuite
    Class S   (Standard pressure)                                                      Not required
    Class N   (Negative Pressure)                          - 30 Pa                     - 15 Pa                    - 30 Pa
    Class P   (Positive Pressure)                          + 30 Pa                     + 15 Pa                    + 30 Pa
    Class P with negative pressure Anteroom                + 15 Pa                     - 15 Pa                    + 30 Pa
Source: Victorian Advisory Committee on Infection Control: Guidelines for the classification and design of isolation rooms in health care
facilities, 2007.
Table 4: Recommended Isolation Room Pressure gradients
Refer to Figure 17 above for a diagrammatic representation of the pressure differentials in the
Negative Pressure Isolation rooms.
4.4 Class S – Standard Pressure
A Standard Pressure room is used for patients requiring contact isolation. Normal air conditioning
in this application should be appropriate. Standard pressure Isolation rooms may be used for other
patients when not required for isolation purposes.
Recommended elements for Class S Isolation Rooms are as follows:
   A clinical handwash basin within the room
   An Ensuite shower and toilet
   A self-closing door.
A pan sanitiser located near the room is an optional element for Class S Isolation Rooms.
The room requires labelling as a standard pressure isolation room.
4.5 Class N - Negative Pressure
Negative Pressure Isolation Rooms are for patients who require airborne droplet nuclei isolation
(this includes pathogens such as measles, varicella zoster (chicken pox), legionella, tuberculosis).
The aim of placing patients in Negative Pressure rooms is to reduce the risk of infection via
airborne transmission to other persons. Negative pressure rooms can also be known as “airborne
infection isolation” rooms or “infectious isolation” facilities.
Negative pressure rooms should be located at the entry to an Inpatient Unit, so that the patient
requiring isolation does not need to pass other patient areas to access the Isolation Room.
A dedicated exhaust system should be provided to the negative pressure isolation room. To
maintain negative pressure the exhaust system removes a quantity of air greater than that of the
supply air. The exhaust air duct should be independent of the building exhaust air system to
reduce risk of contamination due to back draughts and should discharge away from staff, visitor
and patient areas. The Isolation Room Ensuite exhaust should not be connected to the building
toilet exhaust system.
The Isolation room pressure is lower than the adjoining rooms or corridor. Pressure differentials
should not be less than 15 Pa between isolation rooms and the adjacent ambient air.
An Anteroom is optional for the negative pressure Isolation Room. If an Anteroom is not provided,
a PPE bay with a hand basin should be located adjacent to the room entry.
A negative pressure Isolation Room requires the following:
    A clinical handwash basin with ‘hands free’ operation in the Isolation Room and the
     Anteroom, if provided
    An Ensuite shower and toilet
    A self closing door
    100% outside air ventilation (i.e. no return air permitted), with low level exhaust ducts
                  International
                  Health Facility Guidelines                                 © TAHPI             Part B: Version 5 2017           Page 22
4    Isolation Rooms
     approximately 150 – 300 mm above floor level to discharge vertically to the outside air
    Supply air ducts are to be independent of the building supply air system
    For immunosuppressed and infectious patients, a HEPA filtration system should be provided
     on the supply air ducting to protect the patient from unfiltered air.
    Exhaust air should be HEPA filtered
Differential air pressure instrumentation panels are required external to the isolation and Anteroom
in a prominent location. (e.g.: adjacent to the corridor entry door). It is recommended that the
isolation room controls are accessible by staff so that when required, the negative pressure
system can be switched off.
Air-conditioning systems for negative pressure Isolation Rooms should be connected to an
emergency power supply to maintain air pressurisation in the event of a power failure.
The room requires labelling as a negative pressure Isolation Room.
Figure 18: Negative Pressure Isolation room including Ensuite and Anteroom
Class Q Quarantine Isolation
Class Q Quarantine Isolation requires negative pressure isolation with additional protection for
accommodating highly infectious patients with pathogens such as haemorrhagic fever and
pneumonic plague. Class Q Isolation Rooms require the following provisions:
    Anteroom that operates as an airlock with interlocking doors; both doors must not open at
     the one time; the Anteroom must be large enough to allow for bed movement
    Alarm to be activated on loss of differential pressure; time delay may be required to permit
     entry/exit from room
    Self-closing and interlocking doors
    An Ensuite shower and toilet
    A clinical handwash basin with ‘hands free’ operation in the Isolation Room and the
     Anteroom
    100% outside air ventilation (i.e. no return air permitted), with low level exhaust ducts
     approximately 150 to 300 mm above floor level to discharge vertically to the outside air;
     exhaust air should be HEPA filtered
              International
              Health Facility Guidelines                    © TAHPI          Part B: Version 5 2017   Page 23
4    Isolation Rooms
    Supply air ducts are to be independent of the building supply air system
    For immunosuppressed and infectious patients, a HEPA filtration system should be provided
     on the supply air ducting to protect the patient from unfiltered air.
    Communication system between the room and the outside area to assist staff movement in
     and out of the room
    Pan/ utensil sanitiser.
The relationship between the Anteroom, Patient Room, Ensuite and support rooms are
demonstrated in the diagram below for an Ultra-isolation facility.
The patient is transported on a bed or trolley and enters the patient room through an Airlock. The
airlock is sized to fit the bed within the room with interlocking doors, the internal door will not open
while the external door is open, to maintain pressurisation.
Staff enter the Airlock/ Clean Utility, don PPE clothing in the Staff Change and access the Bed
Room through the Clean Utility/ Airlock. Waste is taken to the Dirty Utility, double bagged and is
removed via the Airlock, equipment is sterilised through a pass-through autoclave and is removed
via the exit Airlock. Interlocking doors are required to the Patient Bedroom, Staff Change and
Airlocks to ensure that doors are not open at the same time. Exit of staff, equipment and waste
proceeds in one direction only; staff do not re-enter the Dirty Utility or the Bedroom from the
Change Room.
Staff re-enter the suite through the Airlock/ Clean Utility and don clean PPE attire in the Staff
Change.
The Patient Bedroom should be capable of intensive care treatment with dialysis and able to
accommodate an oversized bed. Services pendant arms should be fully sealed, otherwise wall
services should be provided.
Figure 19: Typical plan of Class Q Quarantine Suite.
Legend:
             Entry for Patient and Staff
             Exit for Staff, decontaminated equipment and waste
               International
               Health Facility Guidelines                 © TAHPI       Part B: Version 5 2017    Page 24
4        Isolation Rooms
4.6 Class P - Positive Pressure
Positive pressure Isolation Rooms, relative to the ambient pressure are used to isolate immune-
compromised patients, for example oncology and some transplant patients. The intent is to reduce
the risk of airborne transmission of infection to a susceptible patient.
These rooms are also known as ‘protective isolation units’ or ‘protective environment’ rooms. (PE
rooms)
The Isolation room is provided with a higher pressure in relation to the adjoining rooms or spaces.
An Anteroom is not required. The positive pressure Isolation Rom requires the following:
    A clinical handwash basin with ‘hands free’ operation in the Isolation Room
    An Ensuite shower and toilet
    A self closing door.
Positive pressure Isolation Rooms may share a common air system, provided minimum outdoor
air requirements comply with local regulations. A HEPA filter however must be fitted to the supply
air inlet. A HEPA filter is not required to the exhaust air, as the exhaust air is not considered
infectious.
Differential air pressure instrumentation panels are required external to the Isolation Room in a
prominent location (e.g.: adjacent to the entry door)
The room requires labelling as a positive pressure Isolation Room.
4.7 Class A - Alternating Pressure
Rooms with reversible airflow mechanisms, which enable the room to have either negative or
positive pressure, should NOT be used. This is due to difficulties in configuring the appropriate
airflow, associated complex engineering, and the high risk of error during operational use for two
fundamentally different purposes. Placing a patient requiring airborne isolation requiring negative
pressure isolation in a positive pressure room could have catastrophic infection control results.
4.8 Schedule - Isolation Room Requirements
The individual components for each type of Isolation Room are identified below.
                                           Standard Pressure   Negative Pressure            Positive Pressure
    Component                              Class S             Class N and Class Q          Class P
                                                               Optional for Class N
    Anteroom                               Not required                                     Not required
                                                               Required for Class Q
    Ensuite (shower and toilet)            Yes                 Yes                          Yes
    Hand basin with hands free operation   Yes                 Yes                          Yes
                                                               Optional for Class N
    Pan Sanitiser                          Optional                                         Optional
                                                               Required for Class Q
    Self–closing door to room              Yes                 Yes                          Yes
    Grille flap to control room air flow   -                   Yes                          Yes
    Independent air supply                 -                   Yes                          -
    100% intake of fresh air               -                   Yes                          -
    Low level exhaust 150mm to 300mm
                                           -                   Yes                          Yes
    above floor level
    HEPA filter on supply air              -                   -                            Yes
    Pressure monitoring                    -                   Yes                          Yes
Table 5: Schedule of Isolation Room Requirements
                     International
                     Health Facility Guidelines                © TAHPI         Part B: Version 5 2017           Page 25
4    Isolation Rooms
Note: Type A alternating pressure Isolation is not recommended and requirements therefore have
not been included
4.9 Number of Isolation Rooms
The required number of isolation rooms should be determined by:
    Trends in disease of the general population
    Demographic trends of the population catchment area
    The health facility’s speciality services or any projected change to these services.
A minimum of 20% of the total bed complement in overnight stay Inpatient Accommodation Units
(IPUs) across the whole facility should however be provided as single Bedrooms or Class S
Rooms, (shared rooms are generally not suitable for infection prevention and control). A maximum
of 4 beds per room within medical/ surgical IPUs is recommended – dormitory style wards are
deemed no longer acceptable and should be avoided.
All IPUs providing overnight accommodation should provide at least one ‘Class S – Standard”
Isolation Room.
Facilities should provide at least one ‘Class N negative pressure’ Isolation Room per 100
overnight IPU beds. Additional ‘Class N Negative Pressure’ Isolation Rooms may be required to
meet service profile demands and model of care of the IPU or facility.
There is no set standard for the provision of positive pressure (Class P) Isolation Rooms. The
provision of Class P rooms is determined by the service profile and the model of care for the FPU
and the facility. The service profile should be based on local population requirements, including
prevalence of cancer, AIDS, cystic fibrosis, organ transplant and other conditions that may
compromise immunity within the population and an evaluation of threats from pathogens such as
aspergillosis.
Available data will inform the service profile of the facility and determine isolation room
requirements in regard to number, type and placement of isolation rooms. Data collection should
include:
     The number of patient admissions with infections known or suspected to require isolation
     The general duration of isolation required
     Seasonal variation of diseases to determine peak periods of infection
     Infection trends in the populations served by the facility
     Specialties of the health care facility.
4.10 Transport of Infectious Patients
It is recommended that transport of infectious patients is limited to movement considered
medically essential by the clinicians, e.g. for diagnostic or treatment purposes. Where infectious
patients are required to be transported to other units within the hospital or outside the following
precautions may be implemented:
      Infected or colonised areas of the patient’s body are covered:
       -    For contact isolation this may include a gown, sheets or dressings to surface wounds;
            these patients are transferred to a Standard Pressure or Protective Environment
            Isolation room
       -    For respiratory isolation the patient is dressed in a mask, gown and covered in sheets;
            these patients are accommodated in a Negative Pressure Isolation Room
       -    For quarantine isolation the patient may be transported in a fully enclosed transport cell
            or isolator with a filtered air supply and exhaust; these patients are accommodated in a
            high level quarantine isolation suite.
      The transport personnel remove existing PPE, cleanse hands and transport the patient on a
       wheelchair, bed or trolley, applying clean PPE to transport the patients and when handling
       the patient at the destination. Gown-up and gown-down rooms located at the entry to a Unit
              International
              Health Facility Guidelines                 © TAHPI       Part B: Version 5 2017   Page 26
4   Isolation Rooms
    will assist the staff to enter and exit the facility according to the strict infection control
    protocols required, thereby reducing the risk of contamination
   The destination unit should be contacted and notified prior to the transfer to ensure suitable
    accommodation on arrival.
   It is preferred that the patient is transported through staff and service corridors, not public
    access corridors During planning stages, design can assist transfer of infectious patients by
    providing service corridors and strategically placed lifts, capable of separation from other
    lifts. The nominated lift may be isolated from public and staff transit through access control
    measures and cleaned following transit of the infectious patient.
   Design may also incorporate a designated floor for horizontal bed transfers of infectious
    patients away from busy clinical areas. The designated floor may be located at mid-level in
    the hospital
   A combination of nominated lifts, corridors and a bed transfer floor would assist in the
    movement of infectious patients through the hospital and minimise the risk of spread of
    infection.
            International
            Health Facility Guidelines                 © TAHPI      Part B: Version 5 2017   Page 27