Installation Manual VRF ME
Installation Manual VRF ME
Air Conditioner
This air conditioner uses the refrigerant R410A.
Model No.
Outdoor Units
Type Outdoor Unit Type Nominal Capacity
72 96 120 144
ME2 2WAY VRF System U-72ME2U9 U-96ME2U9 U-120ME2U9 U-144ME2U9
U-72ME2U94 U-96ME2U94 U-120ME2U94 U-144ME2U94
Concealed Duct
F2 S-07MF2U6 S-09MF2U6 S-12MF2U6 S-15MF2U6 S-18MF2U6 S-24MF2U6 S-36MF2U6 S-48MF2U6 S-54MF2U6
- Medium Static
Concealed Duct
M2 S-07MM2U6 S-09MM2U6 S-12MM2U6 S-15MM2U6 S-18MM2U6
- Low Static
Concealed Duct
E1 S-36ME1U6 S-48ME1U6
- High Static
Concealed Floor
R1 S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6
Standing
Read through the Installation Instructions before you proceed with the installation.
In particular, you will need to read under the “IMPORTANT!” section at the top of the page.
CV6231977845
85464369760022 ACXF60-18511
WARNING
Others
Check of Density Limit If a single unit of the multi air conditioner system is to be
installed in a small room, select a suitable model and
The room in which the air conditioner is to be
installation procedure so that if the refrigerant
installed requires a design that in the event of
accidentally leaks out, its density does not reach the limit
refrigerant gas leaking out, its density will not exceed
(and in the event of an emergency, measures can be
a set limit.
made before injury can occur).
The refrigerant (R410A), which is used in the air
ASHRAE and the International Mechanical Code of the
conditioner, is safe, without the toxicity or combustibility of
ICC as well as CSA provide guidance and define
ammonia, and is not restricted by laws imposed to protect
safeguards related to the use of refrigerants, all of which
the ozone layer. However, since it contains more than air,
define a Refrigerant Concentration Level (RCL) of 400 oz
it poses the risk of suffocation if its density should rise
(11.3 kg) per 1,000 ft3 (28.3 m3) for R410A refrigerant.
excessively. Suffocation from leakage of refrigerant is
For additional guidance and precautions related to
almost non-existent. With the recent increase in the
refrigerant safety, please refer to the following documents:
number of high density buildings, however, the installation
of multi air conditioner systems is on the increase
International Mechanical Code 2012 (IMC-2012)
because of the need for effective use of floor space,
(or more recently revised)
individual control, energy conservation by curtailing heat
ASHRAE 15
and carrying power, etc.
ASHRAE 34
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to
CAUTION
CAUTION prevent dirt, moisture, or other foreign substances from entering.
These substances can result in system malfunction.
Material: O Material: O
Outer diameter Wall thickness Outer diameter Wall thickness
1/4" (6.35) 0.025 (0.635) 7/8" (22.22) 0.045 (1.143)
3/8" (9.52) 0.030 (0.762) 1-1/8" (28.58) 0.050 (1.27)
1/2" (12.7) 0.035 (0.889) 1-3/8" (34.92) 0.055 (1.397)
5/8" (15.88) 0.040 (1.016) 1-5/8" (41.28) 0.060 (1.524)
3/4" (19.05) 0.042 (1.0668) Unit: in. (mm)
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine
oil, the prevention of water and other impurities becomes more important than ever.
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Liquid
1-1. Tools Required for Installation (not supplied) 5-5. Finishing the Installation
1-7. Straight Equivalent Length of Joints 7-1. Preparing for Test Run
1-8. Additional Refrigerant Charge 7-2. Test Run Procedure
1-9. System Limitations 7-3. Main Outdoor Unit PCB Setting
1-10. Check of Limit Density 7-4. Function Switches on P.C. Board
1-11. Installing Distribution Joint 7-5. Auto Address Setting
1-12. Optional Distribution Joint Kits 7-6. Setting Test Run Remote Controller
1-13. Example of Tubing Size Selection and 7-7. Caution for Pump Down
Refrigerant Charge Amount 7-8. Self-Diagnosis Function Table and Contents of
Alarm Display
2. SELECTING THE INSTALLATION SITE. . . . . . 17
3-1. Transporting
3-2. Installing the Outdoor Unit
3-3. Routing the Tubing
3-4. Prepare the Tubing
3-5. Connect the Tubing
4. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . 28
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for
the outdoor unit and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied) 1-3. Type of Copper Tube and Insulation Material
1. Flathead screwdriver If you wish to purchase these materials separately from a local
2. Phillips head screwdriver source, you will need:
3. Knife or wire stripper
1. Deoxidized annealed copper tube for refrigerant tubing.
4. Tape measure
2. Foamed polyethylene insulation for copper tubes as
5. Level gauge
required to precise length of tubing. Wall thickness of the
6. Sabre saw or keyhole saw
insulation should be not less than 5/16" (7.94mm).
7. Hacksaw
8. Core bits 3. Use insulated copper wire for field wiring. Wire size varies
9. Hammer with the total length of wiring.
10. Drill See the section “4. Electrical Wiring” for details.
11. Tube cutter
12. Tube flaring tool Check local electrical codes and
CAUTION
CAUTION
13. Torque wrench regulations before obtaining
14. Adjustable wrench wire. Also, check any specified
15. Reamer (for deburring) instructions or limitations.
L1
H3
C L2
R410A optional distribution joint
LM CZ-P680PJ1U (for outdoor unit)
CZ-P1350PJ1U (for outdoor unit)
Balance tubing B LO A LA CZ-P160BK1U (for indoor unit)
(ø1/4" (6.35mm))
L3 CZ-P680BK1U (for indoor unit)
No.1 distribution joint for outdoor unit LC
CZ-P1350BK1U (for indoor unit)
No.1 distribution joint (for indoor unit) LD
LB H1
64
4 5 62 63
Explanation of symbols For
LF extension
Max.1.3 ft (40cm)
Distribution joint
For
(CZ: optional parts) extension
H2
Ball valve (field supply) Max.1.3 ft (40cm)
LH
T-joint (field supply) LG 3
1 2
NOTE
* Be sure to use special R410A distribution joints (CZ: optional parts) for outdoor unit connections and tubing branches.
Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
unit: ft. (m)
Item Mark Contents Length
Actual length 656 (200)*2
L1 Max. tubing length
Equivalent length 689 (210)*2
Difference between max. length and min.
L (L2 – L4) 164 (50)*4
length from the No.1 distribution joint
Allowable tubing LM Max. length of main tubing (at maximum size) - *3
length
1, 2~ 64 Max. length of each distribution tube 164 (50)*6
L1 + 1 + 2~ 63 + A Total max. tubing length including length of each distribution
3280 (1000)
+ B + LF + LG + LH tube (only liquid tubing)
Maximum tubing length from outdoor’s 1st distribution
A, B + LO, C + LO 33 (10)
joint to each outdoor unit
When outdoor unit is installed higher than indoor unit 164 (50)
H1
Allowable elevation When outdoor unit is installed lower than indoor unit 131 (40)
difference H2 Max. difference between indoor units 49 (15)*5
H3 Max. difference between outdoor units 13 (4)
Allowable length of T-joint tubing (field-supply); Max. tubing length between the L = Length
L3 6.6 (2)
joint tubing first T-joint and solidly welded-shut end point H = Height
NOTE
1: The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to
the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (90m) (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for
gas tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 1-3) on the
following page (LA table), and from the table of refrigerant tubing sizes (Table 1-9) on the second following page.)
3: If the longest main tubing length (LM) exceeds 164 ft. (50m), increase the main tube size at the portion before 164 ft. (50m) by 1
rank for the gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 164 ft. (50m), set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the tubing length marked "L" (L2 - L4) exceeds 131 ft. (40m), increase the liquid tube and gas tube by 1 rank.
5: If the total distribution tubing length exceeds 1,640ft. (500m), maximum allowable elevation difference (H2) between the indoor
units is calculated by the following formula. Make sure the indoor unit’s actual elevation difference should fall within the figure
calculated as follows.
Unit of account (feet): 49 x (2 - total tubing length(ft.) ÷ 1,640) or Unit of account (meter): 15 x (2 - total tubing length(m) ÷ 500)
6: If any of the tubing length exceeds 98ft. (30m), increase the size of the liquid and gas tubes by 1 rank.
8
Table 1-5 Outdoor Unit Tubing Connection Size ( A– C) Unit: in. (mm)
ex.) type72
BTU/h 72,000 96,000 120,000 144,000
(kW) (21.1) (28.1) (35.2) (42.2)
ø3/4" ø7/8" ø1-1/8"
Gas tubing (ø19.05) (ø22.22) (ø28.58)
Brazing connection
ø3/8" (ø9.52) ø3/8" (ø9.52) ø1/2" (ø12.7)
Liquid tubing Balance
Flare connection tube
ø1/4" (ø6.35)
Balance tubing
Flare connection Liquid tube Gas tube
Table 1-7 Indoor Unit Tubing Connection Size Unit: in. (mm)
Table 1-10-1 Necessary Amount of Additional Refrigerant Charge Per ft. (or per meter), According to Liquid Tubing Size
Table 1-10-2 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
Combination number of outdoor unit 1 2 3
Additional amount oz (g) 70.5 (2,000) 141.0 (4,000) 212 (6,000)
Necessary Amount of Additional Refrigerant Charge for All Indoor Unit Cooling Capacity
Charge a refrigerant amount calculated in the following formula according to the total amount of indoor unit cooling capacity.
Additional refrigerant amount when cooling capacity is BTU/h = Cooling capacity (BTU/h) x 1.034 x 0.001 + 10.6 (oz)
or Additional refrigerant amount when cooling capacity is kW = Cooling capacity (kW) x 1000 x 0.1 + 300 (g)
10
Max. capacity allowable connected outdoor 360,000 BTU/h Total system Number of Total system Number of
units (30 ton, 105.5 kW) tonnage indoor units tonnage indoor units
Max. connectable indoor units 64 *1 6 20 14 45
8 25 16 50
Max. allowable indoor/outdoor capacity ratio 50 – 200 % *3
10 32 18 55
*1: In the case of 18 ton (63.3kW) or smaller units, the number is
12 39 20~30 64
limited by the total capacity of the connected indoor units.
*2: Up to 3 units can be connected if the system has been extended.
*3: It is strongly recommended that you choose the unit so the load
can become between 50 and 130%.
Table 1-12 System Limitations of Total Refrigerant Amount
Combination number of outdoor unit 1 2 3
Upper limit oz (g) 1,763 (50,000) 2,821 (80,000) 3,703 (105,000)
Make sure the values calculated using the following formula should not exceed the maximum allowable values (Table 1-12).
Total refrigerant amount = Refrigerant charge amount at shipment (for outdoor unit)
+ Necessary amount of additional refrigerant charge per ft. (or per meter) according to liquid tubing size
+ Necessary amount of additional refrigerant charge per outdoor unit
+ Necessary amount of additional refrigerant charge for all indoor unit cooling capacity
CAUTION
WARNING Always check the gas density limit for the room in which the unit is installed.
11
Pay special attention to any location, such as a basement, etc., where leaking refrigerant can
CAUTION
CAUTION accumulate, since refrigerant gas is heavier than air.
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (CZ-P680PJ1U,
CZ-P1350PJ1U, CZ-P160BK1U, CZ-P680BK1U, CZ-P1350BK1U).
● When connecting a branch tubing to the indoor unit directly, it is necessary for each branch tubing to install at a positive angle
with respect to horizontal in order to prevent accumulation of refrigerant oil in stopped units. (See the below chart.)
Straight tubing
B length over
8 in. (200mm)
15∼90°
A
D 15∼90°
Straight tubing Horizontal
or Horizontal
Horizontal length over 0∼30°
Straight tubing length
8 in. (200mm) (Branch tubing
15∼90° over 8 in. (200mm)
15∼30° angle)
Vertical
Vertical Vertical Vertical
Vertical
15∼90°
15∼90° Vertical
12
1. CZ-P680PJ1U
For outdoor unit (Capacity after distribution joint is 232,000 BTU/h (68.0 kW) or less.)
Example: Gas tubing Liquid tubing
6-59/64 4-21/64
(175) (110)
5-5/16 3-13/16
(135) (97) G
C HI
2-53/64
4-31/64
(72)
C DEF
(114)
G
G
C
Distribution
H
Distribution Joint I
Joint Reducing
Insulation Joints
Reducing
Joints Insulation Unit: in. (mm)
Table 1-13 Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E Part F Part G Part H Part I
ø1-3/8" ø1-1/4" ø1-1/8" ø1" ø7/8" ø3/4" ø5/8" ø1/2" ø3/8"
in. (mm)
(ø34.92) (ø31.75) (ø28.58) (ø25.4) (ø22.22) (ø19.05) (ø15.88) (ø12.7) (ø9.52)
2. CZ-P1350PJ1U
For outdoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW).)
A
(72)
(114)
A F G
G
Distribution B
Joint Distribution
H
Joint I
Reducing
A C E Insulation Joints
D
F Reducing Unit: in. (mm)
Insulation Joints : Outside dimension
*W
ith regard to the diameter of the tube without description in Table 1-14, use a reducer (field supply) to adjust the tube diameter.
Table 1-14 Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E Part F Part G Part H Part I
ø1-3/8" ø1-1/4" ø1-1/8" ø1" ø7/8" ø3/4" ø5/8" ø1/2" ø3/8"
in. (mm)
(ø34.92) (ø31.75) (ø28.58) (ø25.4) (ø22.22) (ø19.05) (ø15.88) (ø12.7) (ø9.52)
13
2-53/64
2-53/64
B C DE
C
(72)
(72)
A B D
Distribution A Distribution
Insulation B Insulation C
Joint Joint
D
C E
Unit: in. (mm)
Table 1-15 Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E
ø3/4" ø5/8" ø1/2" ø3/8" ø1/4"
in. (mm)
(ø19.05) (ø15.88) (ø12.7) (ø9.52) (ø6.35)
4. CZ-P680BK1U U
se: For indoor unit (Capacity after distribution joint is greater than 76,400 BTU/h (22.4 kW) and no more
than 232,000 BTU/h (68.0 kW).)*
Example: 6-57/64 Gas tubing 4-21/64 Liquid tubing
(175) (110)
5-5/16
3-13/16
(135)
(97)
A
4-31/64
B CD EF E
2-53/64
F GH
(114)
DC B A GF E
(72)
E
A
Distribution Distribution
Joint Joint
B F
G
C
H
D Reducing Reducing
Insulation Joints
E Joints
Insulation F
Unit: in. (mm)
Table 1-16 Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E Part F Part G Part H
ø1-1/8" ø1" ø7/8" ø3/4" ø5/8" ø1/2" ø3/8" ø1/4"
in. (mm)
(ø28.58) (ø25.4) (ø22.22) (ø19.05) (ø15.88) (ø12.7) (ø9.52) (ø6.35)
5. CZ-P1350BK1U Use: For indoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW).)*
6-57/64 4-21/64
Example: Gas tubing Liquid tubing
(175) (110)
5-5/16 3-13/16
(135) C D (97)
A F F
B G
2-53/64
4-31/64
A G H
(72)
(114)
D C B
G
Distribution B Distribution
Joint Joint
C A H
I
D J
E Insulation
F Reducing
Reducing Joints
Insulation G Joints
H : Outside dimension Unit: in. (mm)
*W
ith regard to the diameter of the tube without description in Table 1-17, use a reducer (field supply) to adjust the tube diameter.
Table 1-17 Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E Part F Part G Part H Part I Part J
ø1-3/8" ø1-1/4" ø1-1/8" ø1" ø7/8" ø3/4" ø5/8" ø1/2" ø3/8" ø1/4"
in. (mm)
(ø34.92) (ø31.75) (ø28.58) (ø25.4) (ø22.22) (ø19.05) (ø15.88) (ø12.7) (ø9.52) (ø6.35)
In case the total capacity of indoor units connected after distribution exceeds the total capacity of the outdoor units, select the
distribution tube size for the total capacity of the outdoor units.
14
Based on the values in Tables 1-3, 4, 5, 7, 10-1 and 10-2, use the liquid tubing size and length, and calculate the amount of
additional refrigerant charge using the formula below.
(a) : Liquid tubing Total length of ø7/8" (ft.) or (m) (d) : Liquid tubing Total length of ø1/2" (ft.) or (m)
(b) : Liquid tubing Total length of ø3/4" (ft.) or (m) (e) : Liquid tubing Total length of ø3/8" (ft.) or (m)
(c) : Liquid tubing Total length of ø5/8" (ft.) or (m) (f) : Liquid tubing Total length of ø1/4" (ft.) or (m)
l Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side.
At this time, all valves must be in the “fully closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant
from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.
However, if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)
Charge with R410A refrigerant in liquid form.
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from
backing up.
l After charging is completed, turn all valves to the “fully open” position.
l Replace the tubing covers as they were before.
1. R410A additional charging absolutely must be done through liquid charging.
CAUTION
CAUTION 2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon tube is present.
(This is indicated on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in installation, it is
not possible in some cases to use the same tools for R22 and for R410A.
For type 72 For type 96 For type 120/144
Balance tube Balance tube Balance tube
Use a flathead screwdriver and Use a flathead screwdriver and Use a flathead screwdriver and
open by turning the part with the open by turning the part with the open by turning the part with the
screw groove to the right, from “–” screw groove to the right, from “–” screw groove to the right, from “–”
to “|”. to “|”. to “|”.
Liquid tube
Use a hex wrench Liquid tube Liquid tube
(width 5/32 inch (4mm)) Use a hex wrench Use a hex wrench
and turn to the left to (width 5/32 inch (4mm)) (width 5/32 inch (4mm))
open. and turn to the left to and turn to the left to
Gas tube open. open.
Use a flathead screwdriver and Gas tube Gas tube
open by turning the part with the Use a flathead screwdriver and Use a flathead screwdriver and
screw groove to the right, from “–” open by turning the part with the open by turning the part with the
to “|”. screw groove to the right, from “–” screw groove to the right, from “–”
to “|”. to “|”.
15
Therefore, the total of additional refrigerant charge amount reaches 755 oz (21,429g).
l Obtain overall refrigerant charge amount.
Overall refrigerant charge amount of the system indicates the calculated value shown above the additional charge amount in
addition to the total refrigerant charge amount (shown in the Table 1-6) at shipment in total cooling capacity of outdoor unit.
Refrigerant charge amount at shipment
(total cooling capacity of outdoor unit) : : [168,000BTU/h] 684 oz [49.2kW] (19,400g)
Total of additional refrigerant charge amount : 755 oz (21,429g)
Grand total 1,439 oz (40,829g)
Therefore, overall refrigerant charge amount of the system reaches 1,439 oz (40,829g).
Remark:
Be sure to include the values in Table 1-10-2 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit.
CAUTION Be sure to check the limit density for the room in which the indoor unit is installed.
16
* Over 2 in.
(50mm) Over 1.7ft. (500mm)
17
18
30-35/64 30-35/64
(776) (776)
29-29/64 39-31/64 39-31/64
29-29/64
(748) (1003) (1003)
27-43/64 3/64 (1) 5/64 (2) (748) 5/64 (2) 3/64 (1)
(703)
28-55/64
28-55/64
(733)
(733)
101-3/16
101-3/16
(2570)
(2570)
30-5/16 30-5/16
(770) (770)
Front view Right side view Front view Right side view
For type 120/144
Note: Can be installed so that the air direction is to the front or rear direction.
unit: in. (mm)
46-11/16
(1186) 46-11/16
45-19/32
39-31/64 (1186) 39-31/64
(1158)
3/64 (1) (1003) 5/64 (2) 45-19/32 5/64 (2) (1003) 3/64 (1)
43-13/16
(1113) (1158)
28-55/64
28-55/64
(733)
(733)101-3/16
(2570)
101-3/16
(2570)
46-29/64 46-29/64
(1180) (1180)
Front view Right side view Front view Right side view
19
Top view
(Before installing air-discharge chamber)
C : 28-47/64 (730) Installation hole pitch
J G J G J
H
E E
F
K K K
Top view
I F I 39-31/64
L L L 3/64 (1) (1003) 5/64 (2)
M M M
28-55/64
(733)101-3/16
(2570)
D D
According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.
20
34-21/64
34-21/64
(872)
(872)
30-35/64
2-29/32
(776)
(74)
57-9/16
(1462)
(1462)
25-25/32
25-25/32
18-13/16
(655)
(655)
18-13/16
(478)
(478)
30-5/16
(770) 58-5/8
68-13/64 (1489)
(1748)
Front view Right side view Front view Right side view
For type 120/144 Note: Can be installed so that the air direction is to the front or rear direction. unit: in. (mm)
42-1/4 42-1/4
(1073) (1073)
Air direction: Front direction Air direction: Rear direction
34-21/64
34-21/64
(872)
(872)
46-11/16
2-29/32
(1186)
(74)
46-11/16
45-19/32 39-31/64 (1186)
(1158) 39-31/64
3/64(1) (1003) 5/64(2) 45-19/32 (1003)
43-13/16 5/64(2) 3/64(1)
(1113) (1158)
28-55/64
(733)
57-9/16
(1462)
25-25/32
25-25/32
18-13/16
(655)
(655)
18-13/16
(478)
(478)
46-29/64
(1180) 58-5/8
84-61/64 (1489)
(2158)
Front view Right side view Front view Right side view
21
Top view
(1000)
39-3/8
(Before installing snow-proof ducting)
C : 28-47/64 (730) Installation hole pitch
B : 28-47/64 (730) Installation hole pitch downward tubing direction
A : 37-61/64 (964) Installation hole pitch forward tubing direction
H
34-21/64
34-21/64
(872)
(872)
Top view
2-29/32
2-29/32 (74)
(74)
F 39-31/64
(1003)
35/64 7-61/64 (202) 7-61/64 (202) 35/64 (14) 3/64 (1) 5/64 (2)
(14)
28-55/64
(733)
19-1/4 19-1/4 19-19/64
(489) (489) (490)
101-3/16
(2570)
57-9/16
25-25/32 (1462)
57-9/16
(1462)
57-9/16
(1462)
25-53/64
25-25/32
18-13/16
(656)
(655)
18-13/16
18-13/16
(655)
(478)
(478)
(478)
57-23/32
57-23/32
20-9/32
20-9/32
(1466)
(1466)
(515)
(515)
I
Front view Right side view
According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.
22
CAUTION
CAUTION
l When hoisting the outdoor unit, pass ropes or straps under the bottom plate
as shown in the figure at right. When hoisting, the angle between the rope
and top panel must be 70° or greater so that the rope does not come into
contact with the fan guard.
(Use 2 lengths of rope 25 ft. (approx. 7.6 m) long or more.)
l When passing the ropes through the square holes of the bottom plate:
Place the rope in the outer edge of the square holes.
l Use protective panels or padding at all locations where the rope
contacts the outer casing or other parts to prevent scratching.
In particular, use protective material (such as cloth or cardboard) Rope
A A
to prevent the edges of the top panel from being scratched.
l Be careful of the fan.
There is danger of injury if the fan starts to turn during inspection.
This is not a lifting lug.
Be sure to turn OFF the remote power switch before beginning <Do not attempt to lift the unit by one of the
inspection. Detailed legs at each corner of the unit or with hooks
drawing A or shackles attached for installing the legs.>
3-2. Installing the Outdoor Unit
(1) Use anchor bolts (15/32" or M12) or similar to securely anchor the unit in place.
(2) Make sure the rubber vibration insulator and platform extend to the inside of the legs. In addition, the washers used to anchor the
unit from the top must be larger than the installation anchor holes.
Type 120/144
D D Unit: in. (mm)
D D
(Installation hole pitch)
E E
(Installation hole pitch)
B: 28-47/64 (730)
H
A: 37-61/64 (964)
D
G E E
D D D D
F
Over 4” (100)
4” (100)
19/32 (15)
23
Air intake
Air intake
39-3/8 (1000)
39-3/8 (1000)
B
B
Air intake
Air intake
A
A
C
C
45/64 (18)
45/64 (18)
19/32 (15) 29-9/64 (740) 19/32 (15) 45-9/32 (1150)
(Installation hole pitch) (Installation hole pitch)
30-5/16 (770) 46-29/64 (1180)
A : 37-61/64 (964) [Installation hole pitch] * The tubing is routed out from the front.
B : 28-47/64 (730) [Installation hole pitch] * The tubing is routed out from the bottom.
C : 28-47/64 (730) [Installation hole pitch]
3-3. Routing the Tubing
l The tubing can be routed out either from the front or from the bottom.
l The connecting valve is contained inside the unit. Therefore, remove the front panel.
(1) If the tubing is routed out from the front, use cutting pliers or a similar tool to cut out the tubing outlet slit (part indicated by )
from the tubing cover.
For type 72/96 For type 120/144 ex.) type72/96 (208/230 V model)
Tubing cover
Remove 3 screws
Front Use cutting pliers or similar tool
Front
to cut cover out
Bottom Bottom
ex.) type 120/144 (208/230 V model)
Tubing cover
Remove 4 screws
Use cutting pliers or similar tool
to cut cover out
Tubing cover
Slit hole
(2) If the tubing is routed out from the bottom, remove the slit part ( ). Tubing cover
l Use a drill bit approximately 13/64" (5.2 mm) dia. to create holes at the
5 slit hole indentations (openings). Slit part
l Punch out the slit part ( ).
l Be careful not to damage the base plate.
Indentation (5 locations)
24
CAUTION
CAUTION Use sufficient caution during preparation of the tubing. Seal the tube ends by means of caps or
taping to prevent dust, moisture, or other foreign substances from entering the tubes.
25
26
Work method
Pressure-reducing
valve (regulator)
Nitrogen
Brazing locations Taping
1. Be sure to use nitrogen. (Oxygen, CO2, and CFC must not be used.)
CAUTION
CAUTION 2. Use a pressure-reducing valve on the nitrogen tank.
3. Do not use agents intended to prevent the formation of oxide film.
They will adversely affect the refrigeration oil, and may cause equipment failure.
4. The balance tube is not used if only 1 outdoor unit is installed.
Use the unit in the same conditions as when it was shipped from the factory.
27
4-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit Indoor unit
Time delay fuse or Time delay fuse or
Type Type
circuit capacity circuit capacity
U-72ME2U9 50 A K2 15 A
U-96ME2U9 60 A D1, U2, Y2, F2, M2, T2, P1, R1 15 A
U-120ME2U9 60 A E1 15 A
U-144ME2U9 60 A
U-72ME2U94 25 A
U-96ME2U94 25 A
U-120ME2U94 25 A
U-144ME2U94 30 A
Control wiring
(A) Inter-unit (between outdoor and (B) Remote control wiring (C) Control wiring for group control
indoor units) control wiring*
AWG #18 (0.75 mm2) AWG #18 (0.75 mm2) AWG #18 (0.75 mm2)
Max. 3,280 ft. (1,000 m) Max. 1,640 ft. (500 m) Max. 650 ft. (200 m) Total
28
Indoor
unit (No. 2) D Inter-outdoor unit control wiring
*
Power supply L1 L1
208 / 230V, 60Hz, 1-PH L2 Outdoor unit
L2 INV unit *
L1
L1 Power supply
U1
Ground L2 208 / 230V, 60Hz, 3-PH
Remote U2 L2
Controller B 1 L3 L3
WHT 1 1 R1 2
BLK 2 2 R2 Ground
A
Group control:
Indoor U-72ME2U94 / U-96ME2U94 / U-120ME2U94 / U-144ME2U94
unit (No. 3) Outdoor unit
* INV unit
Power supply L1 L1 *
208 / 230V, 60Hz, 1-PH L2 L2 L1
L1 Power supply
U1
L2
L2 460V, 60Hz, 3-PH
U1
U2
L3 L3
Ground
C U2 1
2 Ground
R1
R2
A
D Inter-outdoor unit control wiring
Outdoor unit
INV unit
Indoor *
unit (No. n) L1
L1
Power supply
* L2 460V, 60Hz, 3-PH
Power supply L1 L1
L2
L3
1 L3
208 / 230V, 60Hz, 1-PH L2 L2 2
U1 Ground
Ground
Remote U2
Controller B * Disconnect switch (Field Supply)
WHT 1 1 R1 * NOTE:
BLK 2 2 R2
Disconnect Switch may be needed by the National/Local code.
NOTE
(1) See the section “4-2. Recommended Wire Length L1 L2 L3
and Wire Diameter for Power Supply System” for the 2P terminal board (×2) 4P terminal board
explanation of “A,” “B,” “C” and “D” in the above diagram. (U-72ME2U9 / U-96ME2U9 / (U-72ME2U94 / U-96ME2U94 /
U-120ME2U9 / U-144ME2U9) U-120ME2U94 / U-144ME2U94)
(2) The basic connection diagram of the indoor unit shows
the 6P terminal board, so the terminal boards in your
equipment may differ from the diagram.
(3) Refrigerant Circuit (R.C.) address should be set before U1 U2 1 2
turning the power on.
U1 U2 1 2
(4) Regarding the R.C. address setting, See the section “7-5. Inter-unit Inter-outdoor unit
control wiring control wiring
Auto Address Setting”. Address setting can be executed Inter-unit Inter-outdoor unit
control wiring control wiring
by remote controller automatically.
Outdoor Unit
29
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN67) from all outdoor
units except any one of the outdoor units. (When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop.
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Branch point
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Outdoor unit
Outdoor unit
30
(1) Cut the wire end with cutting pliers, then strip the insulation Ring
pressure
to expose the stranded wiring approx. 3/8" (10mm) and tightly terminal
twist the wire ends.
(2) Using a Phillips head screwdriver, remove the terminal screw(s)
on the terminal board.
(3) Using a ring connector fastener or pliers, securely clamp each
stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and tighten the Special Screw
removed terminal screw using a screwdriver. washer
In this case, reconnect the wires correctly and disconnect the 2P connector (BLU, OC, CN76) on P.C. board.
Then, replace that connector with the 2P connector (BRN, EMG, CN69).
Cut out the jumper (JP11).
U-72ME2U9 / U-96ME2U9 U-120ME2U9 / U-144ME2U9
(CR-72ME2U9/A747841) (CR-144ME2U9/A747593)
Jumper Jumper
JP11 JP11
BLU BLU
FUSE3
Fuse Fuse
FUSE3 FUSE3
31
Jumper
JP11
EMG, CN69
2P connector,
BRN
Fuse
FUSE3
n Wiring sample
U-72ME2U9 / U-96ME2U9 / U-120ME2U9 / U-144ME2U9
Type 72/96 Type 120/144
Electronic component box
Inter-unit control wiring (U1, U2)
2P terminal board *1
Earth terminal *3
Tightening torque
lbs.inch N·m
*1 11 3 1.25 0.25
*2 55 2 6.2 0.2
*3 73 4 8.2 0.4
32
Earth terminal *3
Tightening torque
lbs.inch N·m
*1 11 1 1.30 0.1
*2 55 2 6.2 0.2
*3 73 4 8.2 0.4
*4 ・Hollow for jigsaw holes (Maximum allowed per hole is ø1-7/8" (ø48).)
・Be sure to use waterproof conduit for electrical wiring to the outdoor unit.
・Protective structure is necessary to avoid raindrops through wiring ports.
・Hollow to cut out openings for wiring ports on the panel with a jigsaw.
33
indoor and outdoor units. In this method, the copper tubes are
flared at each end and connected with flare nuts.
Flare tool
Before After
NOTE
When reaming, hold the tube end downward and be sure that no
copper scraps fall into the tube.
Copper
tubing
Reamer
34
(1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the
tubes before they are used.
(2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union
before connecting them together. This is effective for reducing gas leaks.
(3) For proper connection, align the union tube and flare tube straight with each other, Apply refrigerant
lubricant
then screw in the flare nut lightly at first to obtain a smooth match.
l Adjust the shape of the liquid tube using a tube bender at the installation site and
connect it to the liquid tubing side valve using a flare.
l In order to prevent damage to the flare caused by over-tightening of the flare nuts, use the table above as a guide when
tightening.
l When tightening the flare nut on the liquid tube, use an adjustable wrench with a nominal handle length of 7-7/8" (200 mm).
35
Tubing Insulation (1) At this time, the refrigerant tubes (and electrical wiring
if local codes permit) should be taped together with
l Thermal insulation must be applied to all unit tubing, including armoring tape in 1 bundle.
the distribution joint (purchased separately). To prevent the condensation from overflowing the drain
pan, keep the drain hose separate from the refrigerant
How to arrange 2 tubes (between outdoor unit and indoor unit)
tubing.
Liquid tubing Gas tubing
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall.
As you wrap the tubing, overlap half of each previous
tape turn.
Insulation
(3) Clamp the tubing bundle to the wall, using 1 clamp
approx. each ft. (m).
How to arrange 3 tubes (between outdoor units)
Cosmetic
(finishing) tape Gas tubing
Liquid tubing
Clamp
Insulated tubes Drain hose
Tube insulator
Unit side (not supplied) Tubing
insulator Heat resistant
248°F (120°C)
or above
Flare nut
Vinyl clamps (supplied)
36
Therefore, the indoor unit and tubing between the indoor and outdoor unit
must be leak tested and evacuated to remove any noncondensables and
Vacuum pump
moisture from the system.
Outlet
n Air Purging with a Vacuum Pump (for Test Run) Preparation Inlet
Check that each tube (both liquid and gas tubes) between the indoor and
outdoor units have been properly connected and all wiring for the test run has
been completed.
Remove the valve caps from all service valves on the outdoor unit.
Note that both liquid and gas tube service valves on the outdoor unit are kept
closed at this stage.
The balance tube leak test is not necessary if only 1 outdoor unit is installed.
Manifold valve
Leak test
Pressure
(1) With the service valves on the outdoor unit closed, remove the 5/16" gauge
(7.94mm) flare nut and its bonnet on the gas tube service valve.
(Save for reuse.)
(2) Attach a manifold valve (with pressure gauges) and dry nitrogen gas Charge hose
(3) Pressurize the system to no more than 484 psig (3.34MPa {33.1 kgf/cm2G})
with dry nitrogen gas and close the cylinder valve when the gauge reading
reaches 484 psig (3.34MPa {33.1 kgf/cm2G}).
Then, test for leaks with liquid soap. Open
Open
Balance
tube
Close
37
Evacuation
(1) Attach the charge hose end described in the preceding steps to the
vacuum pump to evacuate the tubing and indoor unit.
Confirm that the “Lo” knob of the manifold valve is open.
Then, run the vacuum pump. Vacuum pump
The operation time for evacuation varies with the tubing length and
capacity of the pump.
Evacuation is not necessary for the balance tube if only 1 outdoor unit
is installed. Open
Gas
NOTE tube
Close
The vacuum condition should be less than –14.7 psig (-0.1MPa)
{–755 mmHg, 5 Torr}.
Open
Outdoor unit
(2) When the desired vacuum is reached, close the “Lo” knob of the Liquid
manifold valve and turn off the vacuum pump. tube
Please confirm that the gauge pressure is under –14.7 psig (-0.1MPa) Close
{–755 mmHg, 5 Torr} after 4 to 5 minutes of vacuum pump operation.
Open
Balance
tube
Close
38
using the gas tube service valve with the system in cooling
operation mode at the time of test run. R410A
Finishing the job
(1) With a hex wrench, turn the liquid tube service valve stem Close
counter-clockwise to fully open the valve.
Gas
To avoid gas from leaking when tube
CAUTION Close
CAUTION removing the charge hose, make
sure the stem of the gas tube is
turned all the way out (“BACK
Open
SEAT” position). Outdoor unit
Liquid
(2) Turn the gas tube service valve stem counter-clockwise to tube
fully open the valve. Close
(3) Loosen the charge hose connected to the gas tube service
port (5/16" (7.94mm)) slightly to release the pressure, then Close
remove the hose.
Balance
(4) Replace the 1/4" (6.35mm) flare nut and its bonnet on the tube
gas tube service port and fasten the flare nut securely with Close
an adjustable wrench or box wrench.
This process is very important to prevent gas from leaking
from the system.
(5) Replace the valve caps at both gas and liquid service valves
and fasten them securely.
Gas
tube
Open
Close
Outdoor unit
Liquid
tube
Open
Close
Balance
tube
Open
39
(3) The protective spacers for the compressor used for the new control PCB.
ON
(6) Both the gas and liquid tube service valves are open.
If not, open them now.
Balance tube
Liquid tube Gas tube
40
*4
Are LEDs 1 and 2 on NO
Check alarm contents.
outdoor unit P.C.B OFF?
YES
Test run preparation is completed. (Do not allow short-circuited pin to remain short-circuited.)
Set the remote controller to a test run. Follow the section “7-8. Self-Diagnosis Function Table and Contents of Alarm
Display” and resolve the problem.
41
CN40
CR-72MF2U9 / A748186
SW2
COOL HEAT
A. ADD
MODE
ON ON
OFF
OFF
NO. OF I / U R. C. ADD
ON
SW5
ON
SW6 SW1
OFF OFF
O/U. ADD NO. OF O/U
SHORT OPEN
CN67
U-120ME2U9 / U-144ME2U9
SW6 SW3 SW1 CN28 CN24
Terminating resistance pin CN73 SW5 SW4 SW2 CN27 CN23 CN30
CN40
MODE
A. ADD COOL HEAT
CN34
SW4 SW2
OFF SW3 OFF SW1
CR-144MF2U9 / A748187
SHORT OPEN
CN67
42
CN34
CN33
SW5
SW6
SW4
SW3
SW2
SW1
CN24
CN23
CN40
CN30
CN28
CN27
43
l <Sample> Setting system address (Necessary when link wiring established.) (SW2, SW1)
System address (SW2)
System address (SW1)
System address number (2P Dip switch, black)
(Rotary switch, black)
1020
ON ON 1
1 system (at shipment) Both: OFF Set to 1
1 2 OFF
ON ON 1
11 systems 1: ON Set to 1
1 2 OFF
ON ON 1
21 systems 2: ON Set to 1
1 2 OFF
ON ON
0
30 systems 1 & 2: ON Set to 0
1 2 OFF
44
A.ADD pin (2P, WHT) Short circuited for over 1 second long Auto address setting starts with open-circuit.
(CN30) If short circuit lasts for over 1 second long during auto address setting, the setting is interrupted.
RC plug (3P, BLU) Connects to outdoor unit maintenance remote controller and content of alarm message will be
(CN73) checked.
STOP pin (2P, WHT) When short circuited and pulse signal is given, all indoor units stop in the same refrigerant system.
(CN28) (When short circuited, operation cannot be performed by the indoor unit's remote controller.)
45
1 2 3 OFF
(SW5) (SW5)
Number of (SW6) Unit (SW5) Unit Unit ON ON
ON ON
outdoor units ON ON number ON ON number number
(3 units setting) setting setting setting
1 2 3 OFF 1 2 3 OFF
1 2 3 OFF (unit 1) 1 2 3 OFF (unit 2) (unit 3)
3. Check the refrigerant system's Address Setting Rotary switch (SW1) on outdoor main unit control P.C. board to “1” and the Dip switch
ON ON
(SW2) to “0” (at shipment).
1 2 OFF
4. Regarding the setting of the number of indoor units connected to the outdoor unit, set the Dip switch (SW4) for setting the number of
ON ON
indoor units on outdoor main unit control P.C. board connected to the outdoor unit to “1”.
1 2 3 OFF
If the Rotary switch (SW3) set to “0”, 10 units can be prepared for operation.
6. Short circuit the A.ADD pin (CN30) on outdoor main unit control P.C. board for over 1 second long and open circuit.
Communication for auto address setting begins.
* To cancel, short circuit the A.ADD pin (CN30) again for over 1 second long and then open circuit. The LED that
indicates auto address setting goes out and the process is stopped.
Be sure to perform auto address setting again.
Auto address setting is completed when LEDs 1 and 2 on outdoor main unit control P.C. board go out.
46
3
1 2 (SW4)
OFF
ON ON
Unit 2 setting Unit 3 setting
1 2 3 OFF
Number of (SW5) (SW5)
outdoor units (SW6) Unit (SW5) Unit Unit ON
ON ON ON number ON
(3 units setting) ON number ON ON number
setting setting setting
1 2 3 (unit 1) 1 2 3 (unit 2) 1 2 3 OFF (unit 3) 1 2 3 OFF
OFF OFF
1 2 (SW4)
OFF ON ON
47
l In case of possibility of turning ON power to indoor/outdoor units for each refrigerant system:
Indoor unit address setting can be made without starting the compressor.
How to control auto address setting from outdoor unit
ON
1. Set the unit number setting switch (SW5) on unit 1 (outdoor main unit) control P.C. board to:
1 2 3
(Unit 1: This unit becomes to the outdoor main unit.)
ON
Set the unit number setting switch (SW5) on unit 2 control P.C. board to:
1 2 3
ON
Set the unit number setting switch (SW5) on unit 3 control P.C. board to:
1 2 3
2. Regarding the number of outdoor units, set the Dip switch (SW6) for setting the number of outdoor units on outdoor main unit
ON ON
control P.C. board to 3 units.
1 2 3 OFF
3. Check that the refrigerant system address Rotary switch (SW1) on outdoor main unit control P.C. board in 1 refrigerant system is
ON ON
set to “1” and the Dip switch (SW2) is set to “0” (at shipment).
1 2 OFF
4. Regarding the number of indoor units connected to the outdoor unit, set the Dip switch (SW4) for setting the number on indoor
ON ON
units on outdoor main unit control P.C. board to “1” and set the Rotary switch (SW3) to “3”.
1 2 3 OFF
Total of 13 units installation are made.
5. Turn ON power to all indoor and outdoor units in one refrigerant system.
6. Short circuit the A.ADD pin (CN30) of outdoor main unit for over 1 second long and then open circuit.
(Communication for auto address setting begins.)
* To cancel, again short circuit the A.ADD pin (CN30) for over 1 second long and then open circuit.
LEDs 1 and 2 that indicate auto address setting is in progress go out and that process is stopped.
Be sure to perform auto address setting again.
(Auto address setting is completed when the compressor stops and LEDs 1 and 2 on outdoor main unit control P.C. board go out.)
7. Turn ON power to indoor and outdoor units only for another refrigerant system and repeat steps 1 to 5 described above.
Complete auto address setting for each refrigerant system.
48
l In case of impossibility of turning ON power to indoor/outdoor units in each refrigerant system:
Indoor unit auto address setting cannot be made unless the compressor is started.
How to control automatic address from outdoor unit
1. Make all settings following the same procedure described under steps 1 to 4 in Case 2 .
5. Turn ON power to all indoor and outdoor units in all refrigerant systems.
6. If you wish to make auto address setting in heating mode , short circuit the A.ADD pin (CN30) on outdoor main unit control
P.C. board for the desired auto address setting in a refrigerant system for over 1 second long and then open circuit.
(Be sure to make settings in each refrigerant system. It is impossible to perform auto address setting in a multiple refrigerant
system simultaneously.)
(Communication for auto address setting begins and the compressor is started and auto address setting in heating mode
begins.)
(All indoor units can also be operated.)
* To cancel, again short circuit the A.ADD pin (CN30) for over 1 second long and then open circuit.
LEDs 1 and 2 that indicate auto address setting is in progress go out and that process is stopped.
Be sure to perform auto address setting again.
(Auto address setting is completed when the compressor stops and LEDs 1 and 2 on outdoor main unit control P.C. board go
out.)
7. Short circuit the A.ADD pin (CN30) on outdoor main unit in another refrigerant system for over 1 second long and then open
circuit.
49
l In case of impossibility of turning ON power to indoor/outdoor units in each refrigerant system:
The indoor unit auto address setting cannot be made unless the compressor is started.
How to control automatic address from outdoor unit
1. Make all settings following the same procedure described under steps 1 to 4 of Case 2 .
5. Turn ON power to all indoor and outdoor units in all refrigerant systems.
6. If you wish to make auto address setting in cooling mode , while short circuiting COOL side of the MODE pin (CN40) on
outdoor main unit control P.C. board for the desired auto address setting, short circuit the A.ADD pin (CN30) for over 1 second
long and then open circuit.
(Be sure to install address settings in each refrigerant system. It is impossible to perform auto address setting in a multiple
refrigerant system simultaneously.)
(Communication for auto address setting begins and the compressor starts and auto address setting in cooling mode begins.)
(All indoor units can also be operated.)
* To cancel, again short circuit the A.ADD pin (CN30) for over 1 second long and then open circuit.
LEDs 1 and 2 that indicate auto address setting is in progress go out and that process is stopped.
Be sure to perform auto address setting again.
(Auto address setting is completed when the compressor stops and LEDs 1 and 2 on outdoor main unit control P.C. board go
out.)
7. Short circuit the A.ADD pin (CN30) on outdoor main unit in another refrigerant system for over 1 second long.
Then, open circuit.
50
N OTE
● Selecting each refrigerant system individually for auto address setting
● Auto address setting for each system: Item code “A1”
1 4 CZ-RTC4
51
LED 1 2 * Do not short circuit the A.ADD pin (CN30) again during auto address setting.
LEDs 1 and 2 go out and address setting is interrupted.
* When auto address setting is normally completed, both LEDs 1 and 2 go out.
Blinks alternately In other cases, correct settings referring to the following table and perform auto address setting again.
See the section “7-8. Self-Diagnosis Function Table and Contents of Alarm Display”.
Alternating
Auto address
1
Assigning
Cancel
52
1 Keep pressing the , and buttons 3 The “Simple settings” screen appears on the LCD
simultaneously for 4 or more seconds. display.
The “Maintenance func” screen appears on the LCD Select the “Unit no.” by pressing the or
display. button for changes.
CZ-RTC5A
<If multiple indoor units are connected to 1 remote controller (group control)>
1. Press and hold the button and button for 4 Number changes
seconds or longer (simple settings mode). to indicate which
indoor unit is currently
2. “ALL” is displayed on the remote controller.
selected.
3. Next, press the button.
4. The address is displayed for 1 of the indoor units which is
Indoor unit address
connected to the remote controller. Check that the fan of that
indoor unit starts and that air is discharged.
5. Press the button again and check the address of
each indoor unit in sequence.
6. Press the again to return to normal remote controller
mode.
53
Change [ ] Confirm
N OTE 1
The outdoor units will not operate for approximately 3 minutes after the
power is turned ON and after operation is stopped.
3. If correct operation is not possible, a code is displayed on the remote
controller LCD display.
See the section “7-8. Self-Diagnosis Function Table and Contents of
Alarm Display” and correct the problem.
4. After the test run is completed, press the button again.
Check that “ ” disappears from the LCD display.
To prevent continuous test runs, this remote controller includes a timer 1 4
function that cancels the test run after 60 minutes.
* If the test run is performed using the wired remote controller, operation CZ-RTC4
is possible even if the cassette-type ceiling panel has not been
installed. (“P09” display does not occur.)
54
l This outdoor unit cannot collect more than the rated refrigerant amount as shown by the
CAUTION
CAUTION nameplate on the back.
l If the amount of refrigerant is more than that recommended, do not conduct pump down.
In this case use another refrigerant collecting system.
How to know LEDs 1 and 2 alarm display on outdoor unit control P.C. board
For example: After LED1 blinks twice, LED2 blinks 17 times. This will be repeated.
The alarm shows “P17”.
( : Blink) Connect the outdoor unit maintenance remote controller to the RC plug (3P, BLU) on outdoor main unit control
P.C. board and make confirmation.
55
• Alarm display can be checked by the outdoor maintenance remote controller. When operating, refer to the Test Run Service
Manual.
Alarm display can also be checked by number of blinking of LEDs 1 and 2 on outdoor unit control P.C. board.
See the section “How to know LEDs 1 and 2 alarm display on outdoor unit control P.C. board” under the section “7-8. Self-
Diagnosis Function Table and Contents of Alarm Display”.
Remote control display Alarm contents
E01 Indoor unit does not respond to remote controller.
E02 The remote controller is having error in sending serial communication signal.
E03 Controller does not respond to indoor unit.
E04 Oudoor unit does not respond to indoor unit.
E06 Some indoor units does not respond to outdoor unit.
E08 Indoor unit address is dupulicating.
56
57
58
59
• The parentheses of << >> used in the table of alarm display does not affect anything the operation of other indoor units.
• The parentheses of < > used in the table of alarm display implies that there are two cases: according to the content of the
symptom, some affect the operation of other indoor units and others do not affect anything.
NOTE
1. Alarm messages in << >> do not affect other indoor unit operations.
2. Alarm messages in < > sometimes affect other indoor unit operations depending on the fault.
ATTENTION!
Adjustment of terminating resistance (pin) is necessary.
Communication failure will occur unless adjustment is made correctly.
• Terminating resistance (pin) is mounted on outdoor unit control P.C. board.
• When connecting central controller, interface or peripheral equipment, adjustment of terminating resistance (pin) is necessary.
Although the connection is not made, confirmation is necessary for VRF systems.
• In the case of a refrigerant system, the terminating resistance (pin) for this inter-unit control wiring (S-LINK wiring) is one
location (See the section “7-5. Auto Address Setting”).
For 2 or more refrigerant systems, 2 locations should be valid (“SHORT” for VRF systems at shipment). See the section
“7-5. Auto Address Setting”.
In order to make 2 locations valid, let the terminating resistance (pin) of the nearest outdoor unit and the farthest outdoor unit be
valid (SHORT side) from the location of central controller.
In other refrigerant systems excepting 2 locations described above, make them invalid (OPEN side).
It is prohibited making more than 3 locations of terminating resistance valid.
• Since the use of linking the sub outdoor units of VRF systems is not connected to the inter-unit control wiring, it is not necessary
to make the terminating resistance invalid “OPEN side”.
Make final confirmation regarding the central controller or interface & inter-unit control wiring (S-LINK wiring) connected to the
peripheral equipment.
Measure the line resistance with a tester and check whether the values are in the range of 30Ω - 120Ω.
If the resistance values are out of range, check again the terminating resistance.
Megger
Nevertheless, if the values are out of range, the problem comes from wiring.
Line
• Is the connection properly made? (Wire)
60
61
62
63