PERFORMANCE DATA flowbar
Redefine your comfort zone. ™ | www.titus-hvac.com
FL-30 - 2-SLOT, HIGHTHROW WITH TITUS PLENUM
Airflow, cfm 80 180 280 380 480 580 680
Total Pressure 0.006 0.032 0.077 0.141 0.226 0.329 0.453
2 ft. Static Pressure 0.005 0.025 0.060 0.111 0.177 0.259 0.356
NC (Noise Criteria) <10 <10 <10 20 31 39 46
Throw 1-3-10 7-11-19 12-17-24 16-20-28 18-22-32 20-24-35 22-27-38
Airflow, cfm 150 300 450 600 750 900 1050
2 Slot 10” Inlet
3.0” Total Pressure 0.009 0.036 0.081 0.145 0.226 0.326 0.444
Slot 4 ft. Static Pressure 0.004 0.017 0.039 0.069 0.108 0.156 0.212
Width NC (Noise Criteria) <10 <10 <10 22 32 41 48
Throw 2-4-13 7-13-25 13-20-31 18-25-35 22-28-39 25-31-43 27-33-47
Airflow, cfm 180 350 520 690 860 1030 1200
Total Pressure 0.011 0.041 0.090 0.159 0.246 0.353 0.480
5 ft. Static Pressure 0.004 0.015 0.033 0.059 0.091 0.131 0.177
NC (Noise Criteria) <10 <10 10 23 33 41 48
Throw 2-4-14 7-14-27 14-21-33 18-27-38 23-30-42 27-33-46 29-35-50
Airflow, cfm 80 180 280 380 480 580 680
Total Pressure 0.006 0.028 0.068 0.126 0.201 0.293 0.403
2 ft. Static Pressure 0.005 0.025 0.060 0.111 0.177 0.259 0.356
NC (Noise Criteria) <10 <10 <10 16 26 35 42
Throw 1-3-10 7-11-19 12-17-24 16-20-28 18-22-32 20-24-35 22-27-38
Airflow, cfm 150 310 470 630 790 950 1110
2 Slot 12” Inlet
3.0” Total Pressure 0.007 0.028 0.065 0.117 0.183 0.265 0.362
Slot 4 ft. Static Pressure 0.004 0.018 0.043 0.076 0.120 0.174 0.237
Width NC (Noise Criteria) <10 <10 <10 19 30 38 45
Throw 2-4-13 8-14-25 14-21-31 19-26-36 23-29-40 26-31-44 28-34-48
Airflow, cfm 180 360 540 720 900 1080 1260
Total Pressure 0.007 0.029 0.065 0.116 0.182 0.262 0.356
C
5 ft. Static Pressure 0.004 0.016 0.036 0.064 0.100 0.144 0.195
NC (Noise Criteria) <10 <10 <10 20 30 38 45
Throw 2-4-14 7-14-27 14-21-33 19-27-39 24-31-43 27-33-47 29-36-51
• All pressures are in inches of water • Plenums not provided by Titus may demonstrate performance
• Isothermal throw values given are for terminal velocities of 150, 100 variations from data published by Titus. Titus can not guarantee
and 50 fpm performance if a factory engineered plenum is not provided.
• Each NC value represents the noise criteria that will not be exceeded • Throw values for HighThrow units are based on a one-way discharge
by the sound pressure in any of the octave bands, 2 through 7, with from the slot
a room absorption of 10dB, re 10-12 watts • Throws listed are for one-way air pattern. For divided airflow, select
• The tests were conducted with the FlowBar and plenums as a the airflow in each direction according to the number of slots aimed
composite assembly in that direction, with the total airflow apportioned between slots.
• Data obtained from tests conducted in accordance with ASHRAE See section Engineering Guidelines and the topic ‘Procedure to
Standard 70-2006 “Method of Testing for Rating the Performance of Obtain Catalog Throw Data’ for throw information.
Air Outlets and Inlets” • For continuous lengths it is recommended that maximum active
lengths are no longer than 10 feet
MODUFLOW 24 X 24 INCHES 1-SLOT DATA
PERFORMANCE DATA
(BASED ON MF10 MODEL)
Neck Velocity, (fpm) 300 400 500 600 700 750 800 850 900
Velocity Pressure, (In. WG) 0.006 0.010 0.016 0.022 0.031 0.035 0.040 0.045 0.051
Airflow, cfm 59 79 98 118 137 147 157 167 177
6” Dia Total Pressure, (In. WG) 0.015 0.027 0.043 0.062 0.084 0.096 0.110 0.124 0.139
Inlet NC (Noise Criteria) - - 12 18 22 24 26 28 30
Throw feet 0-1-4 1-2-6 1-3-8 2-4-9 2-5-10 3-6-11 3-6-11 3-7-12 4-7-12
1” Airflow, cfm 105 140 175 209 244 262 279 297 314
Slot 8” Dia Total Pressure, (In. WG) 0.027 0.048 0.075 0.108 0.148 0.169 0.193 0.218 0.244
Width Inlet NC (Noise Criteria) - 17 24 29 34 36 38 40 42
Throw feet 1-3-8 2-5-11 4-7-12 5-8-13 6-10-14 7-10-14 7-11-15 8-11-15 8-11-16
Airflow, cfm 164 218 273 327 382 409 436 464 491
10” Dia Total Pressure, (In. WG) 0.042 0.075 0.116 0.168 0.228 0.262 0.298 0.336 0.377
Inlet NC (Noise Criteria) 18 26 33 39 43 45 47 49 51
Throw feet 3-6-11 6-9-13 7-10-15 9-11-16 10-12-17 10-13-18 11-13-19 11-14-19 11-14-20
• All data based on tests • Throw based on Isothermal air, at 150, • NC based on a 10 dB reduction
conducted in accordance with 100 and 50 fpm terminal velocities in discharge sound in all octave
C42 ASHRAE Standard 70-2006 bands for room absorption