Power Stations Best Practices and Health Monitoring
Power Stations Best Practices and Health Monitoring
Pradip Chanda
Suparna Mukhopaddhyay
Operation and
Maintenance of
Thermal Power
Stations
Best Practices and Health Monitoring
123
Energy Systems in Electrical Engineering
Series editor
Muhammad H. Rashid, Pensacola, USA
More information about this series at http://www.springer.com/series/13509
Pradip Chanda Suparna Mukhopaddhyay
•
123
Pradip Chanda Suparna Mukhopaddhyay
Power Management Institute Power Management Institute
Noida, Uttar Pradesh Noida, Uttar Pradesh
India India
vii
viii Preface
million tons of coal and, finally, savings of Indian Rupee (INR) 220 crore
(approximately 32 million USD).
Residual life assessment of plant components hover around two different
approaches, one using data analysis based on operational history and the other
based on a periodic examination of critical components. Operation beyond the
limiting range can cause fatigue to the equipment and reduce its effective lifespan.
Creep damage occurs when the component is operated above the grain recovery
temperature characteristic of a material. Creep fatigue results in plastic deformation
of the material. Low-cycle fatigue is the fatigue of a component as a result of cyclic
loading beyond the strain limit. Each cycle in the resulting stress (load cycle) leads
to utilization of the low-cycle fatigue resistance (low-cycle fatigue) and thus finally
to stress cracking at the most highly loaded point.
Since 2001, the EN12952 code is being followed in many countries for design
service loading combination. A boiler manufacturer will generally design the boiler
so that there is some reserve with regard to the design service loading combination.
It is a reality that a power plant is initially operated in base load operation due to its
favorable efficiency compared with other available power plants. With increasing
age, it will be deployed more and more in cycling duty or as a peaking plant. This
different operating mode compared with the design of the components results in a
different anticipated service life for the power plant equipment.
A load cycle is a closed hysteresis loop in the stress/strain diagram. The stress in
the material is calculated from the pressure and temperature gradient, while the
numbers of cycles to crack initiation are material properties. Continuous fatigue
monitoring is the responsibility of the power plant operator (not the manufacturer)
and to be performed for the most highly-loaded components.
Strong corrosion occurs at the furnace wall of coal-fired boilers by flame
impingement. When coal containing a lot of sulfur content is used as fuel, the area
in the neighborhood of the burner zone becomes an atmosphere of low oxygen
partial pressure containing hydrogen sulfide (H2S), creating a severe corrosive
environment. Increase in the oxygen partial pressure on the piping surface by filling
boundary air (to create an air curtain along the water wall piping) over the water
wall piping surface, is considered effective.
Water is a major component used as a working fluid as well as a cooling
medium. At high pressure, the solubility of water comes down and chemicals get
deposited inside the vessel. Boiler tube failure due to corrosion and chemical
deposition is a common phenomenon and a nightmare for all thermal plant oper-
ators. Due to bad management of water chemistry, carry-over silica at the low
pressure (LP) stage of a turbine may disturb the dynamic balance of the turbine
blade, cause rise in vibration, and finally, failure of the blades. More than 45 %
of the energy input into turbine gets lost in the condenser. Untreated cooling water
produces scaling and algae inside the condenser tube, causing heat transfer and
thereby reducing turbine output and cycle efficiency. Therefore, managing water
chemistry for cycle water as well as cooling water is a major challenge to power
station managers. In addition to water, the chemical analysis of lubricating oil,
transformer oil, etc. predicts the condition of different equipment. Chemical
Preface ix
analysis of flue gas predicts the efficiency of combustion. Considering all these
facts, this book makes a special emphasis on thermal power plant chemistry.
The task and timing of major equipment maintenance is determined by predictive
maintenance or reliability-centered maintenance focused on the engineering side of
maintenance. As financial constraints are placed on maintenance resources, there is
an increasing need for determining the timing of maintenance taking into consid-
eration the financial expenditure and impacts. Risk Evaluation and Prioritization
(REAP) provides the plant management quantified assessments of financial invest-
ment decisions of maintenance. Different maintenance strategies are deployed to
avoid breakdowns, premature equipment malfunctions, and to increase response
times to recover from failure, in order to effect improvements in overall plant
availability. This book also covers details on the planning part of maintenance.
A large number of forced outages occur per year due to human error which not
only affects the industry in terms of financial losses, but also in terms of its repu-
tation among its customers as a reliable power producer. The root causes of these
human errors have been discussed in detail for better outage management.
Best practices are not just benchmarking parameters. Implementation of these
practices creates long-term sustainability. Best practices have many dimensions
starting from maximizing efficiency to maximizing life span. The chapter dedicated
to best practices in this book has covered many dimensions of good practices to
minimize resource utilization, better environment management, knowledge man-
agement with maximizing growth, and life span.
The huge operating experience of National Thermal Power Corporation (NTPC)
shared in a different forum has made it possible for me to write this book. Borrowed
from erstwhile Central Electricity Generation Board (CEGB), different operating
and management practices have been indigenized by NTPC to suit the weather and
ambience of the country the plant belongs to. Many operating practices over time
have been documented through instruction and directives, but many are still a tacit
knowledge. Moreover, the instructions and directives do not speak about the
knowledge and reasoning. Through this book I try to bare the knowledge of the
different processes involved in thermal power plant operation and maintenance so
that future engineers are not mandated to follow the instructions blindly, but are
able to upgrade and make independent decisions for managing a power station.
I am thankful to my senior colleagues and fellow engineers at NTPC who have held
my hand during the process of learning. I am thankful to Dr. Suparna Mukhopaddhyay
for encouraging me to write down my experience. Finally, I wish to profoundly thank
my wife Nibedita, son Arnab, and daughter Debarati for their constant encouragement
and support which helped me immensely in writing this book.
xi
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Understanding Operation Practices . . . . . . . . . . . . . . . . . . . . . 2
1.2 Understanding Maintenance Practices . . . . . . . . . . . . . . . . . . . 4
2 Performance Parameters of Power Stations
of Global/Indian Scenario. . . . . . . . . . . . . . . . . . . . . . . . ....... 7
2.1 Impact of Performance Parameter on Economics
of Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2 Impact of Performance Parameter on the Environment . . . . . . . 16
2.2.1 Environment Impact on Water . . . . . . . . . . . . . . . . . . 16
2.2.2 Impact on Air Quality. . . . . . . . . . . . . . . . . . . . . . . . 17
2.2.3 Impact on Land . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3 Residual Life Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1 Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4 Coal-Fired Unit Operation Guidelines. . . . . . . . . . . . . . . . . . . . . . 25
4.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3 Cold and Hot Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.4 Fire Prevention and Fire Fighting. . . . . . . . . . . . . . . . . . . . . . 45
4.5 Abnormal and Unsafe Operation . . . . . . . . . . . . . . . . . . . . . . 45
4.6 Abnormal Operation Case Study . . . . . . . . . . . . . . . . . . . . . . 48
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5 Managing Thermal Stress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.1 Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.2 Turbine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
xiii
xiv Contents
5.3 Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.4 Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6 Chemical Health of Thermal Power Unit . . . . . . . . . . . . . . . . ... 59
6.1 Role of Chemistry in Thermal Power Unit . . . . . . . . . . . . ... 59
6.2 Effect of Processes Chemistry on Power Plant
Equipments and Performance. . . . . . . . . . . . . . . . . . . . . . . . . 60
6.3 Fuel Chemistry and Combustion . . . . . . . . . . . . . . . . . . . . . . 62
6.4 Effect of Fuel Quality on Combustion . . . . . . . . . . . . . . . . . . 66
6.4.1 Moisture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.4.2 Ash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.4.3 Coal Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.4.4 Some Important Points of Combustion Control . . . . . . 67
6.5 Managing Water and Steam Quality . . . . . . . . . . . . . . . . . . . . 68
6.5.1 Treatment of Water . . . . . . . . . . . . . . . . . . . . . . . . . 69
6.5.2 Water Quality at Different Stages of the
Demineralization Process (For Drum Type Boiler) . ... 74
6.5.3 Water Chemistry for Super Critical Unit . . . . . . . . ... 76
6.5.4 Cycle Chemistry Core Monitoring Parameters
for Conventional Fossil Units . . . . . . . . . . . . . . . ... 80
6.5.5 Treatment for Once-Through and Supercritical
Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
6.6 Managing Cooling Water . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
6.6.1 Strategies to Minimum Water Consumption. . . . . . . . . 84
6.6.2 Cooling Water-Associated Problems . . . . . . . . . . . . . . 85
6.7 Managing Lube Oil Quality. . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.8 Monitoring Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
6.8.1 Ambient Air Quality Measurements . . . . . . . . . . . . . . 92
6.8.2 Water Pollution and Control . . . . . . . . . . . . . . . . . . . 92
6.9 Indication of Abnormality . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
7 Maintenance Practice . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...... 97
7.1 Types of Maintenance . . . . . . . . . . . . . . . . . . . . . . . ...... 97
7.1.1 Preventive Maintenance . . . . . . . . . . . . . . . . ...... 98
7.1.2 Predictive Maintenance/Condition-Based
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7.1.3 Risk Evaluation and Prioritization (REAP) . . . . . . . . . 101
7.1.4 Interrelationship Among RCM, Overhaul, and
Activity-Based Budgeting . . . . . . . . . . . . . . . . . . . . . 101
7.1.5 Corrective Maintenance . . . . . . . . . . . . . . . . . . . . . . 102
7.2 Permit to Work System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2.1 Work Order System . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2.2 Clearance Permit System. . . . . . . . . . . . . . . . . . . . . . 104
Contents xv
xvii
xviii About the Authors
Good operating and maintenance practices help in maintaining the health of the
equipment and adds life to any thermal power station. This book covers many
dimensions of good practices to minimize resource utilization, better environment
management, knowledge management with maximizing growth, and life span. The
discussions in this book are distinctly divided in two parts, namely ‘Operation
practices for sustenance’ and ‘Maintenance practices for long term reliability’. Its
goal is to help the readers develop their own practices and technical guidelines
suitable for the plant concerned in a structured way.
Keywords Thermal plant Reliability Residual life Operation practices
Maintenance practices Performance parameter Water chemistry Best practices
xix
Chapter 1
Introduction
Electricity is a key enabler to the gross domestic product growth of the country.
Thermal power station is an industrial facility for generating electric power from
fossil fuel. Being a highly capital-intensive industry, it needs to operate at a high
utilization factor during the whole plant life cycle to justify its investment.
First-rate operating and maintenance practices assist in maintaining optimization
of equipment and add life to any thermal power station. With an installed capacity
of approximately 267 GW, the national load factor of thermal power was
approximately 65.55 % during 2013–2014, and compared with 2012–2013, the
figure was reduced by 4.38 %. While availability of fuel is one of the factors
responsible for the drooping trend, unplanned outages of systems and equipment
played a major role in on bar availability. This was also reflected in the down trend
of the plant load factor. It is observed that, while some of the older power stations
that have crossed their normative life cycles are operating with high availability,
some new plants are operated with very low availability. It is because the stations
that have adopted operating practices aligned with enhancing the life cycle of
equipment, get sustainable availability of any system. Omission minus commis-
sioning, maintaining process chemistry meticulously throughout the life cycle of the
plant, maintaining process parameter within prescribed norms, predicting mainte-
nance, etc. are the success stories of a healthy power stations.
Equipment manufacturers generally provide specific operation and maintenance
instructions for the equipment supplied by them. A thermal power generating unit is
built up by integrating different equipment, namely the boiler, turbine, generator,
and many other auxiliaries forming different systems such as the ‘air and gas
system’, ‘fuel firing system’, ‘feed water system’, etc. These systems operate in
coordination to generate power with sustained reliability. Hence, operating and
maintaining a thermal power generating unit requires understanding of system level
dynamics which is different from the individual equipment level
operating/maintenance procedures.
Furthermore, to maintain reliable and efficient operation of a generating unit
throughout its lifecycle and beyond its lifecycle, it requires specific care in
© Springer India 2016 1
P. Chanda and S. Mukhopaddhyay, Operation and Maintenance
of Thermal Power Stations, Energy Systems in Electrical Engineering,
DOI 10.1007/978-81-322-2722-9_1
2 1 Introduction
control the above input sources and work on a real-time basis. Then where is the
role for operation engineer for bench marking practices? To understand the role we
need to understand what happened when these inputs goes to the system and what
are the limitations of auto loops in general used in modern power stations.
What happens when fresh pulverized coal reaches the burning furnace zone? It
gets burned, releases energy, and produces flame. But the flame temperature,
velocity of the flame, and emissivity of the flame depend on the constituent and size
of the pulverized fuel input and its rate of entry in the furnace. Flame temperature as
a function of constituent can be expressed as
P
_
mð146:58C þ 568:78H þ 29:4S 6:58A 51:53ðO þ NÞÞ þ ðti tref Þ _ p ÞR
ðmC
tf ¼ P þ tref
_ p ÞP
ðmC
The capital equipment of thermal power units is very expensive. Good maintenance
practices can sustain efficiency and the life cycle of the equipment. Although
manufacturers provide maintenance instructions for the equipment supplied by
them, in reality similar types of equipment behave differently, and maintaining them
with their unique behavior calls for a different approach. The maintenance practices
discussed in this book are not guided by manufacturer instructions, but rather
practice needs to be adopted for managing the equipment for a sustained long life
and efficiency.
The maintenance practices of a thermal power station are different from tradi-
tional maintenance practices in the sense that
1. Power plants require being run continuously. Maintenance causes outages of
equipment/system. Duration of outage for maintenance is restricted by market
demand (even under regulated condition). Hence, the maintenance philosophy
appropriate to the market demand pattern with a short-term, medium-term, and
long-term approach is required for preserving the deterioration or damage of
equipment.
2. Being an energy conversion industry, the maintenance practices not only need to
address the equipment health conditions, but also to plug losses.
Elaborating further, the thermal power generator’s commercial earning is
dependent on its availability to grid and its operating efficiency. The availability is
guided by redundancy and reliability. Power plant equipment is very costly,
therefore, redundancy is limited. Various philosophies such as time base mainte-
nance with analytical hierarchy principle, predictive maintenance, condition-based
maintenance, or mixed up methods are generally adopted for enhancing reliability.
The overall strategy is to enhance the availability at the lowest maintenance cost.
In thermal power generation, energy is converted from one form to another and
the process is less efficient. Therefore, any waste/dilution of primary energy during
conversion requires attention to maintenance to plug in the fault. Interestingly, this
type of fault does not reflect on the physical performance of the equipment such as
change in vibration/noise/drawing over current, etc., but is understandable to the
operating engineer through reflection in operating parameters. For example, leakage
through seals of an air pre heater (APH) does not create any vibration/noise, but it
gets reflected in oxygen concentration in the flue gas at the inlet and the outlet of the
APH. Therefore, maintenance in a thermal power station is also operation centric.
Over and above, the thermal plant maintenance practices also need to address
reduction of consumables such as chemicals and lubricants. For example, due to
damage of sealing arrangement of the coal mill gearbox, a considerable amount of
fine coal dust may enter the gearbox and contaminate the oil. This contamination
can lead to high consumption of oil and necessary handling of hazardous waste oil.
Data pertaining to an Indian thermal power station (shown below) indicate
reduction of usage of lubricating oil after adopting advance maintenance practices
1.2 Understanding Maintenance Practices 5
The actual life of the equipment differs from the expected life of the equipment.
Considering the fact that the quality of the equipment was absolutely normal during
delivery, the difference in its life span arises from its actual working circumstances.
It is difficult to avoid being exposed to an abominable circumstance at some
stochastic period of time throughout the life cycle of the equipment. A good
maintenance practice needs to capture the total history of abnormal situations
through which the equipment/system of equipment has gone through.
Maintenance practice to cover the residual life assessment and adopt process of
stress reliving/replacement as dimmed fit for enhancing the life of the thermal unit
as a whole. This book will focus on the maintenance practices of enhancing the life
of the equipment while at the same time sustaining its performance.
Since its inception in 1975, National Thermal Power Corporation of India has
tried to adopt and benchmark its operation and maintenance practices globally. The
journey yields the result. The first unit of NTPC at Singrauli commissioned during
1982 is still operating with 100 % availability and so are the other units. The author
started his career as commissioning and operation engineer with NTPC in 1980 and
for 35 years has moved through many technical and strategic positions within the
company.
This book is a humble endeavor to detail the good operating practices of a
thermal power station which can help the future operation and maintenance engi-
neers sustaining the availability of a thermal plant beyond its perceived life cycle.
Chapter 2
Performance Parameters of Power
Stations of Global/Indian Scenario
Heat rate (kcal/kWh) indicates how much heat is used for generation of one unit
of electricity.
860
Efficiency ¼ 100
Heat rate
Fossil fuel contains carbon which combines with oxygen in the air during
combustion and produces carbon dioxide. The parameter is expressed as million
ton.
Nitrogen oxide or NOx is formed when combustion flame temperature reaches
approximately 1400 °C. SOx is generated as a result of the presence of sulphur in
the fuel and its combination with oxygen during combustion. Both NOx and SOx
are expressed as parts per billion (PPB) in the ambient air. SMP is the presence of
fly ash particle in the air expressed in PPM.
Global Scenario
Since 1990, the electricity sector across the globe began changing its focus from a
regulated environment to a market-driven approach. The environmental mandates
has further driven the sector to technology adoption, change in usage pattern, and
change in the classical concept of performance. This has presented a new challenge
as to how the performance can be benchmarked against improving reliability,
mitigating environmental requirements, while adding value in the service to the
customer. The best practices for performance measurement across the different
power generation assets globally has concentrated its focus on the value of the
generation as a composite benefit delivered to the grid (regulated environment) or
benefit delivered to the owners (de-regulated environment). In its 2010 report on
‘Generating Plant Performance’ the World Energy Council (WEC) had suggested a
diverse matrix of performance indicator (World Energy Council Report 2010) as
shown in Fig. 2.1.
Electricity generating plant performance, which was until now primarily focused on
effective heat energy utilization only, is replaced by a metrics consisting of availability,
efficiency, emissions, cost, and others. This ensures that only the best possible perfor-
mance can be attained with “perfect” operations and maintenance (O&M) management
practices when equipment failure rate and repair time is minimized. In reality, the actual
achieved performance for each generating plant around the world is far below its
theoretically best achievable values. The Performance Generating Plant Committee
report by the WEC estimated that 80 % of the gap in performance is due to “less than
perfect” O&M management practices. Revisiting a plant’s O&M management prac-
tices, along with replacement of inadequate or worn-out components to increase its
availability and reliability to its theoretical best achievable limits, can substantially
reduce its performance gap. The four core (primary) performance indicators according
to the WEC’s 2010 Generation Performance Report are
1. Energy availability factor (EAF)
2. Load factor (LF)
3. Planned capacity loss factor (PCLF)
4. Unplanned capability loss factor (UCLF)
As per Institute of Electrical and Electronics Engineers (IEEE) standard 762-2006,
the aforesaid indices of performance definition is given below (IEEE Std 762™-
2006).
EAF—The energy availability factor is the ratio of the potential amount of
energy that could be produced by any utility after all planned and unplanned losses
are considered to that of theoretical availability and is measured in percentage
potential. It is a fact that not all available energy can be generated. However, EAF
identifies what percentage of power during a given period could be generated.
Factors beyond management control are included in the EAF. EAF is considered to
be as given by the IEEE 762 weighted equivalent availability factor (WEAF) which
includes outside management control outages or derating, if any. WEAF can be
expressed as
Pn
½ðAHi NMCi Þ ðEUNDHi þ ESDHi Þ NMCi
WEAF ¼ i¼1 Pn 100
i¼1 ðPHi NMCi Þ
Pn
½ðFOHi þ EFDHi þ MOHi þ EMDHi Þ NMCi
WEUOF ¼ i¼1 Pn 100
i¼1 ðPHi NMCi Þ
Where FOH- Forced Outage Hours, EFDH- Equivalent Forced Derated Hours,
MOH- Maintenance Outage Hours and EMDH- Equivalent Maintenance Derated
Hours. PCLF—The planned capability loss factor is the ratio of maximum energy
generation that a plant is not capable of supplying to the electric grid because of
planned energy losses to that of maximum energy available expressed in percentage.
The planned capability loss includes annual maintenance shutdowns. An outage is
considered to be planned if it is scheduled at least 4 weeks in advance. PCLF is equal
to IEEE 762 weighted equivalent planned outage factor (WEPOF) and is expressed as
Pn
½ðPOHi þ EPDHi Þ NMCi
WEPOF ¼ i¼1 Pn 100
i¼1 ðPHi NMCi Þ
Where POH- Forced Outage Hours and EPDH- Equivalent Planned Derated
Hours. LF—The load factor is the ratio of the maximum energy the unit actually
produced to that of EAF expressed in percentage. LF is equal to IEEE 762 net
capacity factor (NCF) and is expressed as
NAAG
NCF ¼ 100
NMG
Where NAAG- Net Actual Generation and NMG- Net Maximum Generation.
With increase in population growth surpassing 7 billion, it has become a challenge
to meet the necessary energy requirements. Installed capacity across the globe is
given in Fig. 2.2 as of 2013.
The International Energy Statistics report of the International Energy Agency
(IEA) shows the trend of energy generation growth from fossil fuel across the globe
(Fig. 2.3).
The above trend shows that EAF is high but the generation growth is showing a
negative trend indicating less demand from fossil fired plant for coal-fired units. This
may be because many older units have been discarded and to reduce CO2 emission,
coal as a fuel has taken a back seat to make way for gas and renewable energy sources.
While the availability factor, and reliability enhances commercial compliance of
a utility, the efficiency enhancement of generation reduces fossil fuel consumption
and thereby reduces production of CO2.
As per IEA World Energy Outlook 2009 (IEA 2010), efficiency of coal-fired
utility across the globe is shown in Figs. 2.4 and 2.5.
As per the IEA report, there is enough scope of improvement in efficiency
through adaptation of efficient technology and good operation practices. India needs
to adopt high-efficiency supercritical units to enhance the gross efficiency.
Indian Scenario
India has enough coal reserve, and therefore the primary source of electricity is
coal. The energy availability position of the country (CEA 2010–11) as per CEA
report for the past decades is shown in Fig. 2.6.
12 2 Performance Parameters of Power Stations …
Source: IEA
Fig. 2.5 Relation between net plant efficiency and specific CO2 emission is shown
The energy shortage shows a negative trend over the past 5 years and indicates
that the gap is reducing.
Although the demand is there, the loading factor for fossil-fired power as per
CEA report is being reduced (CEA 2010–11) as shown in Fig. 2.7.
Scarcity of domestic fuel in conjunction with price volatility of international fuel
is one of the major cause of such a downtrend.
2 Performance Parameters of Power Stations … 13
Fig. 2.7 Loading factor trend for fossil fuel generators in India
Nine supercritical units were synchronized to the grid during the 2011–2012
financial year. Planned maintenance accounted for was 5.93 %. This is an increase
as compared with 5.83 % during the 2009–2010 financial year. Increase in
unscheduled capital maintenance along with unscheduled R&M activity of some
units were the main reason for the percentage increase in planned maintenance.
Similarly, during the 2011–2012 financial year, the loss of generation due to forced
outages of thermal units increased to 11.46 % as compared with 10.32 % during the
2009–2010 financial year. Increased forced shutdown of units due to a coal supply
problem was one of the major reasons. Transmission constraints and equipment
problems also added to the value.
Currently, India is going through adaptation of supercritical technology. The
forced outage of supercritical units is high, indicating that the technology has not
yet stabilized with Indian coal and atmospheric conditions. The O&M practices are
being reviewed under Indian context.
Heat conversion at high temperature is always efficient, but the temperature
limitation of turbine metal restricts high temperature conversion. With research for
developing high temperature material for turbine ultra-supercritical units with steam
temperature, approximately 700 °C is expected to substantially enhance the effi-
ciency of a thermal unit (Fig. 2.8).
Fig. 2.9 Temperature correction factor for a typical 500 MW set. Source CIPECH14
2.1 Impact of Performance Parameter on Economics of Generation 15
TG HR (kW)
210 MW 500 MW
Change in HPT efficiency by 1 % 0.3 % 0.3 %
Change in IPT efficiency by 1 % 0.16 % 0.16 %
Change in LPT efficiency by 1 % 0.5 % 0.5 %
Ash pond discharge contains harmful heavy metals such as B, As, Hg which can
leach out over a period of time. As a result, the ground water may become polluted
and be unsuitable for domestic use.
1 kg of Indian coal produces on average 0.4 kg of ash. Out of that, 0.38 kg goes to
air with flue gas. Coal burning at thermal power plants produces mainly CO2, SOx,
NOx, CFCs, and other trace gases. It also produces airborne inorganic particulates
such as fly ash and suspended particulate matter (SPM). CO2, NOx, and CFCs are
greenhouse gases (GHGs) (Shamshad et al. 2012).
A large amount of land for the main plant and ash pond is required for a coal-based
thermal power plant. The specific land requirement (per MW of installed capacity)
for coal, gas, and hydroelectric power plants is 0.1–4.7, 0.26, and 6.6 ha, respec-
tively. Plant-generated effluents create change in natural soil properties, causing it to
become more alkaline due to the alkaline nature of fly ash. The quantity of effluent
production from coal burning for 1 kWh of electricity production is given below:
• 0.65 kg coal is burnt
• 990 gm CO2 is produced
• 7.6 gm SOx is produced
• 3.5 gm NOx is produced
• 0.061 gm soot is produced
• 2.3 gm SPM is produced.
In addition to mitigating the environment impact through technology, heat rate
improvement reduces coal consumption and thus reduces the adverse impact on
weather.
References
3.1 Definition
The equipment in a thermal plant has the operating range defined by the manu-
facturer. Often the equipment is subjected to operating beyond its operating range
due to (a) variation in interconnected grid demand, (b) start ups and shut downs,
(c) malfunctioning of controls, etc. This type of abnormal operation adversely
affects the material properties of various equipment through a material damage
mechanism such as creep, fatigue, corrosion, etc., and thereby reduces the life of the
equipment. Residual life assessment (RLA) is a method by which the type of
degradation of equipment and its materials are determined to ascertain the
remaining life of the equipment (Bhavnani 2007). The essential steps involved in
RLA are studying the historic operating data of the equipment and failure history
and estimating the material degradation. Mainly two different approaches are
adopted for RLA of power plant components. As a continuous process, some
manufacturers approach RLA using data analysis based on operational history. As a
discrete process, some approach RLA based on a periodic examination of critical
components. Data analysis is based on operation history and knowledge of the
operational stress-temperature data. Operation beyond the limiting range causes
fatigue to the equipment and reduces its effective lifespan. The most common types
of fatigue for thermal plant equipment are:
1. Creep fatigue: The allowable service life of component depends on the exposure
of the component beyond limiting load and the temperature such that the service
life is limited at a constant load and decreases with increasing temperature.
Creep damage occurs when the component is operated above the grain recovery
temperature characterizing of a material. Creep fatigue results in plastic defor-
mation of the material.
2. Low-cycle fatigue: Low-cycle fatigue is the fatigue of a component resulting
from cyclic loading beyond the strain limit. Cyclic strain loading occurs when
the part is subjected to pressure changes and/or fluctuating fluid temperature
3.2 Methods
Since 2001, code EN12952 is being followed in many countries for design service
loading combination. A boiler manufacturer will generally design the boiler so that
there is some reserve with regard to the design service loading combination. In
reality, it is that a power plant is initially operated in base load operation due to the
favorable efficiency compared with the other available power plants. With increasing
age, it will be deployed more and more in cycling duty or as a peaking plant. This
different operating mode compared with the design of the component results in a
different anticipated service life of power plant equipment (Kunze and Raab 2012).
Calculation of creep fatigue Dc is based on a comparison of the exposure time
Top of a component at specific levels of pressure and temperature with the theo-
P P T
retical service life Tal of the component at these conditions: Dc ¼ i k Top;i;k al;i;k
.
The theoretical service life is calculated from the creep resistance (material
property), the operating temperature, and the membrane stress (or pressure). For a
quick overview of the operating mode of the power plant, it is expedient to cate-
gorize pressure and temperature in classes, with the classification assigned by
experts. The background is to define small intervals for normal operation values and
wider.
Low-cycle fatigue Df is determined by comparing the actual load cycles (n) the
equipment has subjected to with the number of cycles to crack initiation N of the
component for specific values of the stress range 2f and temperature t on which the
P P n
load cycle is based: Df ¼ i k Ni;ki;k .
A load cycle is defined by code EN 12952-4 as a closed hysteresis loop in the
stress/strain diagram. The stress in the material is calculated from the pressure and
temperature gradient, while the numbers of cycles to crack initiation are material
properties.
Continuous fatigue monitoring is the responsibility of the power plant operator
(not the manufacturer) and should be performed for the most highly loaded
components.
Heavily loaded components which are continuously monitored with regard to
creep fatigue and low-cycle fatigue are as follows:
• Headers
• Drums
• Separators
3.2 Methods 21
• Spray attemperators
• Piping (pipe bends)
Drums and separators are generally monitored for low-cycle fatigue (not creep
fatigue) because these components are operated in temperature ranges for which no
creep of the material occurs (below the grain recovery temperature).
Operating parameters (measured values) are required for each component to be
monitored for calculation of the service life:
• Creep fatigue:
– Mean wall temperature tmw and
– Internal pressure p
• Low-cycle fatigue:
– Inner wall temperature tim
– Mean wall temperature tmw
– Internal pressure p
The other methods of periodic examination of equipments involve (Padole and
Joshi 2002):
A. Application of NDE techniques for detection of cracks, assessing the extent of
corrosion/erosion etc. Use of ultrasonic thickness gauging, ultrasonic flaw
detector, dye Penetration testing, fluorescent magnetic particle testing for
detection of cracks, assessment of hydrogen damage by ultrasonic testing,
steam side oxide scaling is assessed by in situ ultrasonic boroscopic inspection
of rotors, eddy current tests for rotor blades and root, and video probe of critical
components.
B. Assessing the condition of material through in situ metallography applying
replica method, in situ chemical analysis with the help of spectroscope/X-ray
fluorescence, in situ hardness measurement etc.
C. Grouping of component specimens for a specific type of NDT.
It is essential to select suitable NDE techniques for critical areas where failures
are likely to occur (Table 3.1) and detection of such failures. Based on design
conditions, past experience and previous failure information, suitable inspec-
tion technique is adopted.
The actual service life of plant equipment differs from its nominal design life and
it is significantly dependent on good or poor operation and maintenance. With
respect to thermal power plants, for the purpose of keeping their function and
performance at an established level, the scope of inspection, method, and frequency
are defined on an equipment-by-equipment basis as a standard, and patrols, routine
checks, periodic inspections, service, and maintenance (repair, replacement, etc.)
are performed according to such standards.
Precise inspection and remaining life assessment for plants whose cumulative
operation time has exceeded 100,000 h is shown in Table 3.2.
Table 3.1 Typical failure mechanisms and the associated inspection technique (Benesch et al. 2010)
22
1. Rotor X X X X
2. Retaining rings X X X X X
Condenser and heat X X X X X X X X
Exchanger
X Applicable; HTT High temperature tensile failure; VT Visual inspection and dimensional check; UTG Ultrasonic thickness gauging; UTF Ultrasonic flaw
detection; PT Penetrant testing; MT Magnetic particle inspection; ET Eddy current testing; HT Hardness measurement; REP In situ replica metallography; FOT
Fiberoptic examination; DT Destructive tests on samples; CA Chemical analysis in situ; SPL Special Test Methods
a
Oxide scale measurement by special Ultrasonic technique
b
Hydrogen damage assessment by special Ultrasonic technique
c
Boresonic Inspection
d
Special Eddy Current Test of Roots
23
24 3 Residual Life Assessment
References
Benesch WA, Hay M, Verghese JT (2010) The high available and efficient coal fired power
station. POWER-GEN India & Central Asia 2010
Bhavnani PC (2007) Residual Life assessment, uprating, R&M of old power plants. Conference
proceedings on Thermal Power India 2- Present Status, Technology Development, Future
Prospects & Strategies, IndiaCore
Kunze U, Raab S (2012) Assessment of remaining useful life of power plant steam generators—a
standardized industrial application. In: European conference of prognostics and health
management society 2012
Padole PM, Joshi MM (2002) Application and implementation of residual life assessment
techniques for coal handling plant. NDE2002 predict. Assure. improve. National Seminar of
ISNT, Chennai, 5. Accessed Dec 7 2002
Chapter 4
Coal-Fired Unit Operation Guidelines
4.1 Introduction
4.2 Commissioning
After the plant is erected, all the equipment is subjected to trial operation before it is
taken into the specific subsystem. When the subsystems are proved reliable with
trial operation, the major capital equipment boiler and turbine are taken through the
process of chemical cleaning. Boiler tubes are processed through with chemical
treatment for building up protective layers inside the tubes. Steam blowing is done
for cleaning the boiler tubes free of any debris. Turbine systems are cleaned with
detergent and thereafter oil flushing is done on the lubricating oil system for further
cleaning. Setting of safety valves and testing of interlocks and protection of
Water
CEP BFP Economizer
Water
Water and steam path
Air preheater
Flue gas path
ESP
ID Fan
To Chimney
Fig. 4.1 Flow diagram of air, gas, water, and steam in a power boiler
equipment and subsystems are done before making the plant ready for synchro-
nization with the grid. All these activities that are required to make the plant ready
are known as commissioning. The regulatory life of a power plant is 25 years.
A well-commissioned plant can run efficiently beyond its regulatory life, and
hence the importance of commissioning guidelines. The guidelines need to cover
the followings:
1. Formation of a commissioning team with experienced representation from the
Mechanical, Electrical, Chemistry, and Control and Instrumentation disciplines.
2. Well-documented formats for pre-checks, trial run checks, and post operation
checks including safe operating limits of equipment and systems.
3. Documentation of omissions.
4. Human safety precaution to be taken during commissioning.
The commissioning team to be formed as a three-tier structure:
a. Steering committee
b. Commissioning panel
c. Working party.
The purpose of the steering committee is to provide policy and priorities, ensure
adequate resources, and approve the work program. The steering committee formed
with plant in-charge, members from the core commissioning team, and a com-
missioning team from equipment erector/suppliers. The commissioning panel
controls day-to-day commissioning activities and coordinates between different
working parties and teams. It is normally chaired by heads of O&M, the test team
4.2 Commissioning 27
leader, and the erection department. The working party and the test team carry out
commissioning activities and hand over equipment from the erection state to the
operation state.
Major committees are formed much before the schedule commissioning.
Identifying the operation and maintenance team, setting up an O&M organization,
procurement of regular consumable spares (such as electrical fuses of different
ratings, different types of bearings for rotating equipment, etc.) to be completed so
that commissioning activities continues without interruption and a smooth transition
from the commissioning phase to the operating phase is ensured.
Various documentation is prepared during the commissioning stage. Mainly five
types of documentation are done: (1) paper of principle, for setting out the principle
and objectives; (2) testing and commissioning schedule, covering details of the
testing procedure, responsibilities, and result; (3) standard checklists, checking for
correct erection, limit of operations, testing instrument schedule, etc.; (4) design
change notification for recording intermediate design change if any; and (5) test
report for documenting the test results and trial run.
Every piece of equipment and system in a plant has unique deviation from its
design characteristics. The condition of the equipment/systems in long run is
compared with its unique initial characteristics. Therefore, keeping the record
of initial test results are vital for maintaining a long life of equipment and systems.
Some of the major commissioning activities on which the life span of a plant
depends are chemical cleaning of boiler tubes and turbine pipelines, preservation of
the boiler after cleaning, oil flushing of lubrication and control oil system, and
maintaining chemical parameters within limits during commissioning. Generally,
commissioning procedure for individual equipment follows the guidelines given by
the respective manufacturer. However, that does not take care of the requirement of
a system commissioning. Therefore, the plant must have its own standard of system
for commissioning. For example, commissioning of an ID fan/FD fan needs to
follow the procedure given by the fan manufacturer, but while commissioning the
air and gas system, setting the operating regime of a secondary air damper or
tertiary air damper should be done as per site condition. Necessary guidelines for
system commissioning to be developed by the plant engineer on the basis of site
condition in conjunction with manufacturer recommendations.
The chemical cleaning process for the water and steam path of steam generators
at fossil fuel fired stations was in itially developed during the latter half of the
twentieth century. Development in technology and experience in field application
subsequently led to a number of changes in the process. Removal of iron oxides
from tube surface is generally accomplished with solvents of iron oxide. However,
the choice of solvent depends on philosophy of approach for cleaning by different
manufacturers. The common solvents are:
• Hydrochloric acid (HCl)
• Hydrofluoric acid (HF)
28 4 Coal-Fired Unit Operation Guidelines
A schematic drawing of the open circuit technique used with once through boiler
for acid cleaning is shown in Fig. 4.2.
Once the chemical analysis of the boiler indicates that the boiler is clean, the
next activity is the passivation step. In the case of HCl, passivation is preceded by
rinses and neutralization of any remaining acid in the boiler. In the case of EDTA,
passivation occurs after cooling the boiler to 160 °F and after the pH of the solvent
is raised with ammonia (for diammonium EDTA) when oxygen is added.
The degree to which the boiler tube surfaces are truly passivated is a function of
the solvent, the procedure, and the time and temperature at which the passivation is
performed. The passivation step at the end of the chemical cleaning is generally
neither long enough nor at a high enough temperature to create a robust protective
layer. It is often difficult to ensure that the boiler gets really dry after the cleaning or
can be laid-up properly in a wet condition. The super heater is always back-filled
during cleaning to minimize the risk of contamination. The important thing is to
make sure all deposits have been removed during the cleaning and that the
chemistry has stabilized. A comparison of deposit removal capability of different
solvents is shown in Table 4.2.
Oil flushing is done to clean the oil piping system by removing dirt, welding
slag, etc., after completion of piping erection. This is ensured by creating conditions
30 4 Coal-Fired Unit Operation Guidelines
similar to the machine in operation by adopting a thermal shock process. Before oil
flushing, all the pipes should be acid cleaned (soaking through 5 % HCl with
appropriate inhibitor, passivation through sodium nitrite [2 %] and liquid ammonia
[5 %] and then drying via dry compressed air). For conducting the oil flushing
effectively, the oil system is flushed in loops, namely (1) lube oil system flushing,
(2) jacking oil system flushing, (3) control oil system and purification system
flushing, and 4) seal oil system flushing. While flushing is done in different stages
for inclusion and exclusion of different equipment, thermal shock is done for
effective cleaning. One cooler is used for heating the oil while another cooler is
used for cooling. It should be noted however that raising the temperature of oil
should be slow but cooling should be rapid (from around 75 °C to approximately
30 °C). During cooling the pipelines are softly hammered with wooden buttons for
loosening stuck debris, if any. The differential level meter of the main oil tank
4.2 Commissioning 31
(MOT) indicates the filter cleaning requirement. Generally, if the difference shown
in differential level meter becomes 200 mm, then flushing stops to clean the MOT
filter. The lube oil filters are cleaned based on differential pressure (DP) across the
filter (>0.7 Ksc). The pipeline should be considered cleaned when DP across the
filter is stabilized and does not increase beyond 0.1 to 0.2 Ksc for more than 8 h of
continuous flushing operation. Mechanical impurities should be less than 100 ppm
for three consecutive readings at an interval of 4 h. On completion of flushing, a
hydraulic test is conducted for the entire system (in general lube oil lines at 12 kg,
control oil lines at 20/32 kg and jacking oil lines 225 bar). The MOT is drained,
cleaned, and inspected before restoration of the system. All bearing pedestals are
cleaned thoroughly before being boxed up. Schematics for flushing of different oil
systems are given in Figs. 4.3, 4.4 and 4.5.
During erection of high pressure pipelines, welding slag, loose foreign material,
etc. are inadvertently left inside the pipe. These loose materials can damage turbine
blades if they get carried over to turbine. Although there are strainers before entry to
the turbine, the high speed debris will damage the strainer and will cause outages of
the plant. In order to remove these welding slags, loose foreign materials, iron
pieces, rust, etc. from the system, steam blowing of MS lines, CRH, HRH, SH, RH,
32 4 Coal-Fired Unit Operation Guidelines
HP, and LP bypass pipe lines of turbine is carried. Effect of steam blowing depends
on thermal shock and the cleaning force of the steam. ‘Cleaning force ratio’ is
defined as the ratio of velocity of steam during steam blowing to that of steam
velocity at MCR (maximum continuous rating) and generally denoted as ‘K’. It can
be expressed as
Recommended value K > 1.25 (between 1.25 and 1.4). Blowing mass flow can
pffiffiffiffiffiffiffiffiffi pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
be expressed as Qflow ¼ 1:25 QMCR VMCR =Vblow : Steam flow can be
measured by net feed water flow.
Steam blowing can be done through either the puffing method or the continuous
method. In both, the method boiler pressure is raised approximately 40–60 kg/cm2,
and steam is suddenly allowed to pass through the pipes under the blowing process
and escape to the atmosphere. In the puffing technique the boiler fire is killed, and
pressure drop inside the drum is limited to change in saturation temperature by
40 °C. In the continuous technique, boiler fire is not killed and steam blowing takes
place virtually at a constant pressure.
Steam blowing is done in number of stages depending on the convenience of
taking different pipe line circuits and temporary pipe line erection. However aux-
iliary pipelines are generally blown through using the continuous method.
Stainless steel target plates are put just before the end of the temporary pipeline
where steam is allowed to escape to the atmosphere. Steam blowing is complete
when the orifice granularity on the target plate is not more than 08 nos and size less
than 0.8 mm for two successive blowings. Boiler expansion is checked during
steam blowing.
Certificates are issued in different stages of commissioning. They are: (1) safety
clearance certificate-issued prior to excitation of the plant/equipment, (2) record of
initial operation-issued after initial operation, (3) initial taken over certificate-issued
for taking over the plant in accordance with the condition of contract, (4) final
internal contract clearance certificate-issued after completion of guarantee period,
(5) plant completion report-after performance guarantee test of the entire plant.
Tube failure is a major contributor to boiler downtime. Analysis reveals that a
major percentage of tube failure during commissioning/initial operation is due to
blockage in the tubes. The thermal flow test of the boiler tubes detects any
blockage. The thermal flow meter works on the principle that the rate of cooling of
a tube is proportional to the flow of fluid inside the tube. The accuracy of a flow
meter is good for a fluid velocity of 0.15 to 3.0 m/s. Tubes are heated to approx-
imately 100 °C and the rate of cooling is observed until the temperature drops to
10 °C above the ambient temperature. The cooling period is compared among all
the tubes. The rate of cooling will be lower in case any blockage. The ideal period
of testing of the water wall will be just after acid cleaning. The ideal period for
testing of super heaters will be just after steam blowing.
34 4 Coal-Fired Unit Operation Guidelines
(continued)
Activity Detail procedure to be followed
Charging of equipment cooling water • No work permits pending
system • Adequate level in DM water cooling tank and
pumps are lined up
• Ensure gland sealing
• Start ECW pumps
• Charge various auxiliary coolers
Charging of auxiliary steam header • No work permit pending on auxiliary steam
supply system, SCAPH, atomizing steam, oil
heater
• Drain from auxiliary steam header is opened, all
downstream CVs and manual isolating valves are
closed
• Service air and instrument air is charged
• Charge auxiliary steam header by first opening
bypass of inlet isolation valve
• Allow draining of the header for any water
condensation and ensure that steam is flowing
through the drain (by observing drain line metal
temperature)
• Close the drain and open isolation valve
completely
Charging of fuel oil system • No work permits pending
• Oil trip v/v operation and protection checked
• Charge auxiliary steam for line heating
• Line up fuel oil station at firing floor of the boiler
• Open short recirculation v/v and charge the
system
Charging of LP ash water system • No work permits pending on LP ash water
system, furnace trough seal and bottom ash
hopper
• Line up and start p/p
• Check water flow through overflow lines
Filling hotwell. Startup of condensate • No work permit pending in condensate system,
system LP heaters, deaerator
• Instrument air in service
• ECW water to CEP motor coolers and bearing oil
cooler is lined up
• Open DM water inlet v/v to hot well. Fill hot well
to normal level
• Condenser spill valve bypass and common
isolation valve to exhaust hood spray are closed
• Line up hot well and deaerator level controller,
LP heaters and deaerator
• Start CEP and fill deaerator
• Add hydrazine and ammonia as recommended by
chemist
(continued)
4.3 Cold and Hot Startup 37
(continued)
Activity Detail procedure to be followed
Startup of feed water system and boiler • No permit is pending on feed water system, HP
filling heaters, deaerator, etc.
• Ensure ECW flow to working and lubricate
• Ensure seal quenching pressure more than
recommended value
• Ensure emergency seal quenching pump is lined
up
• Start auxiliary oil p/p of boiler feed pump (BFP)
• Ensure HP heaters are bypassed
• Start BFP in recirculation mode
• Ensure all low point drains are closed
• Drum vents are open
• Open economizer inlet and recirculation valve
• Open low range feed control valve
• LP dosing pumps lined up and taken in service
• Control feed water flow as per rate of flow to
deaerator
• Slowly close recirculation of BFP pump
• Observe drum/separator level (depending on
drum type/once through boiler)
Line up for turbine lubricating oil • No work permits pending
system and taking in service • Lubricating oil coolers are lined up. Supply
valves to bearings are opened
• Thrust bearing filter is lined up
• Adequate oil level in MOT
• Open the oil temperature controller manually to
30 %
• Start oil vapor extractor
• Start one auxiliary oil pump and check local
pressure and flow
• Take temperature controller on auto
Line up for control fluid • Line up control fluid coolers
• Start control fluid tank vapor extractor
• Start one control fluid pump and observe flow
and pressure
Lining up generator seal oil system and • No work permits pending
putting in service • Seal oil tank, seal oil pumps, thrust oil lined up
• Seal oil system is lined up
• Line up seal oil coolers and start seal oil pump
Hydrogen filling in generator • CO2 is entered through bottom of the generator
and air purged through top. Lining up done
accordingly
• Hydrogen is entered through bottom and CO2
purged from bottom
• Check hydrogen purity for >97 % and pressure as
recommended
(continued)
38 4 Coal-Fired Unit Operation Guidelines
(continued)
Activity Detail procedure to be followed
TG on barring • Turbine lubricating oil system and seal oil system
in service
• Start jacking oil pump and check pressure
• Open gate gearing valve from control panel
• Observe turbine speed, bearing temperature and
vibration
Line up of air and flue gas system • No work permits on furnace, APH, fans, ESP and
interconnected ducts and dampers in the boiler
• Unit equipment cooling system in running
condition with all coolers in SG side charged
• APH fire sensing device and soot blowers
available
• All the wall blowers and LRSB are in retracted
condition
• Boiler slag bath, trough seal, economizer and air
pre-heater hoppers are filled with water
• Bottom ash equipment is lined up
• All peep holes and man holes in the boiler closed
• All inlet and outlet dampers of the entire ESP
pass are opened
• APH air motor availability checked
• After closing inlet outlet dampers APH start
command given
• Outlet secondary air damper of APH is opened
followed by opening of inlet dampers
• Flue gas outlet damper is opened followed by
inlet damper
Startup of ID fan • No work permits pending on fans
• Adequate oil in lubricating oil tank
• One hydraulic coupling cooler and one lubricated
oil cooler water is charged
• Fan Inlet vane in minimum position, inlet and
outlet damper closed
• Start lubricating oil pump. Adequate pressure and
oil flow in bearings to be checked
• Give ID fan start command. Initially starting
current will be high and then comes down to no
load value
• Inlet and outlet damper opens automatically after
some time
• Do not load ID fan without running FD fan
Startup of FD fan • No work permit is pending on fans
• At least one ID fan is running
• Secondary air damper (SADC) operation is
checked
• Adequate lubricating oil in lubricating oil tank
• Start lubricating oil pump. Adequate pressure and
oil flow through bearings is checked
(continued)
4.3 Cold and Hot Startup 39
(continued)
Activity Detail procedure to be followed
• Fan blade pitch in minimum position and
inlet/outlet damper in closed condition
• Give FD fan start command. Wait till current
comes down to no load value. Inlet/outlet damper
opens automatically
• Load FD fan by opening blade bitch control
• Load ID fan by opening vane control
• Put ID fan on auto. Adjust set point of ID to
maintain a negative draft of around (–) 10 mm of
water column
• Load FD fan to maintain air flow slightly above
40 % of full load flow
SCAPH (steam coil air preheater) in • No work permit on SCAPH
service • One set of ID and FD fan running
• Drain valves down streams of SCAPH are open
to IBD
• Charge the steam line
• Crack open SAPH cold end temperature
controller for worming up
• After worming up close the drains and open
control valve to maintain require cold end
temperature
Line up for boiler light up • Oil guns and igniters checked. SADC checked.
Scanner air fan in service. Bottom ash evacuation
system taken in service. At least one set of ID
and FD fans, both air heaters, all flushing
apparatus are in service. All drains are closed
• Drum is filled with water
• Drum and super heater vents are open
Boiler light up Conditions for purge permissive
• Maintaining air flow between 30 and 40 % of full
load air flow
• Drum water level normal
• Burner tilt horizontal (corner fired boiler)
• All PA fans, pulverizers and feeders off
• All hot air gates closed
• All nozzle valves closed
• No boiler trip command persisting
• All scanner sensing no flame
• Oil tip valve (HOTV) closed
“Purge ready” signal will indicate the compliance
of conditions
• Press “purge start”. After stipulated time elapsed,
“purge completed” signal will glow
• Open long recirculation v/v for oil heating as well
as the HOTV
• Wait until oil temperature at boiler front is
approximately 110 °C
(continued)
40 4 Coal-Fired Unit Operation Guidelines
(continued)
Activity Detail procedure to be followed
• Give light up command to one pair of guns at
bottommost elevation
• Igniter at one corner will advance and start
sparking. HO nozzle v/v will open. Atomized
steam oil mixture will spray out. If scanner does
not sense fire within preset time interval, the
corresponding gun will retract automatically
• After flame is established, adjust fuel oil pressure
and combustion air so that flame is stable and no
black soot is visible in exhaust gas
• When oil gun is in service, air heater soot blower
needs to be operated at least once every 8 h
• CBD opening per chemist recommendation
• Maintain rate of rise of drum metal temperature
less than 2 °C per minute and that of main steam
temperature less than 5 °C per minute by
controlling oil firing
• At 2 kg/cm2 drum pressure, close drum vents
• Super heater header startup vents remain open
• Maintain furnace temperature within allowable
metal temperature of re-heater (because no steam
is flowing through re-heater). Check with furnace
temperature probe
• Drum top bottom metal temperature difference to
be maintained within 50 °C
• Maintain water level in the drum through low
range feed control and emergency blow down
Vacuum pulling • Open drain of gland steam supply and charge
gland steam header for warming up
• Start gland seal condenser extractor fan
• Open seal steam pressure controller and maintain
a pressure of 0.1 kg/cm2 or recommended
pressure. Maintain seal temperature at
approximately 150–160 °C
• Line up vacuum p/p. Close vacuum breaker and
start vacuum pump in hogging mode
• Check the vacuum build up at recommended
value
• Open air ejector v/v and close by pass v/v to keep
the vacuum p/p in hold position
• Close drain of gland seal supply line
Main steam line warming and charging • No work permit on main steam line
• Boiler is steaming and pressure is around
6–8 kg/cm2
• Condenser vacuum is pulled
• All drain v/vs of steam line and strainers are
opened
(continued)
4.3 Cold and Hot Startup 41
(continued)
Activity Detail procedure to be followed
• First open by pass v/v of main steam stop valve
and begin heating of the pipe until pure steam
continue to come through drains
• Close the drain and open main steam (MS) stop
valve
HP/LP bypass charging • No work permit on HP/LP bypass system
• ECW cooling water is lined up for gland cooling
of HP bypass v/vs
• All drains of MS are line up to TG flash tank
• HP BP downstream drains open
• HP bypass v/v pressure set-point initially set to
around 12 kg/cm2 and temperature around
220 °C
• Set LP bypass v/v pressure set point to about
4 kg/cm2 and keep in auto
• Water spray pressure controller in manual mode
• Open manual isolation v/v for exhaust hood spray
• Injection water pressure switch and low vacuum
protection switch in LP BP rack is kept in
operating mode
• Control fluid line to all v/v and injection water is
lined up
• Temperature dependent solenoid v/vs are in reset
condition in LP BP rack.
• Open both bypass v/v manually to around 5 %.
Check downstream temperature rising
• LP BP v/v will automatically open and hold
approximately 25 % until the actual hot re-heat
pressure reaches to preset value
• Put HP BP in auto. Increase boiler firing. Pressure
set point increased gradually to around 40 kg for
attaining turbine rolling parameter
• HP BP will force close if downstream
temperature is higher than 380 °C or vacuum
becomes less than 0.8 kg/cm2. In case HP BP
gets forced closed, spray v/v should be closed
immediately to prevent water entry
• After synchronization the HP BP set point should
be kept in higher value than operating pressure
and temperature to avoid unnecessary operation
of HP BP
• LP BP stop and control v/v gets force closed if a
condenser vacuum is less than 0.6 kg/cm2 or
injection water presser becomes low or condenser
wall temperature increases beyond 90 °C
• After synchronization, LP BP set point is a
function of turbine first stage pressure
(continued)
42 4 Coal-Fired Unit Operation Guidelines
(continued)
Activity Detail procedure to be followed
Line up and start of turbine rolling • Main steam pressure is around 40 kg/cm2 and
temperature is around 350 °C
• Open all drain v/vs of HP and IP control v/vs.
Open ESV seat drain.
• Take generator primary water system with temp
controller in service
• Generator lockout relay is reset
• Switch on the tracking device from console and
TSE effect
• Reduce the starting device to zero position,
Check building up of Trip oil pressure and
start-up oil pressure
• Raise the speeder gear position to 100 %. Load
limiter set to block load limit
• Raise the starting device slowly (fast opening will
collapse the startup oil pressure fast and may not
be able to open the stop valves). At around 40 %
when HP stop v/v starts opening, hold starting
device. After HP stop v/v opened fully raise
starting device further. The IPCV starts open.
After all the v/vs opened, raise the starting device
fully
• Let all the stop v/vs heated uniformly (by
observing temperature at 50 % depth and 100 %
depth from TSE). Keep warm up controller on
• Raise speeder gear to initial soaking speed
(reference speed will be as per the manufacturer
of the turbine. In general the reference is around
600 rpm)
• Turbine will start speeding up till soaking speed
achieved. Jacking oil pump should cut-off
automatically
• Check that all the bearing temperature, thrust
bearing temperature, bearing vibration and
differential expansion are within limit
Pulverizer line up and starting • Cooling water system is charged and oil coolers
are lined up. Lubricating oil level is ok
• PA fan lub oil system is lined up. Check auto
interlock for standby lube oil pump
• Instrument air is charged to all cold and hot air
dampers
• Secondary air temperature is adequate (>200 °C)
• Coal Feeder is lined up and put it on remote
• All permissive for PA fan is available on Control
desk
• Start one PA fan on no load. After stabilization
load it
• Put seal air fan on auto and start
(continued)
4.3 Cold and Hot Startup 43
(continued)
Activity Detail procedure to be followed
• All pulverizer permissives are available on
control desk
• Start pulverizer. Cold air damper opens
automatically
• Open hot air damper. Maintain recommended air
flow to the pulverizer through primary air flow
controller
• Start feeder. Load slowly and maintained
pulverizer outlet temperature around 80 °C
• Adjust opening of fuel air damper as per feeder
speed
• Scanner should sense flame and flame failure
protection gets armed
Turbine rolling and synchronisation • Line up switchyard bay by closing line side and
bus side isolators
• Adequate margin in TSE is available for rolling
further
• Raise the speed reference to synchronous speed
in one stroke. Turbine speeds up to synchronous
speed
• Auxiliary oil pump will automatically cut off
• Allow for soaking till IP shaft attains temperature
as per rolling curve. TSE margin will indicate
further allowance
• Switch on excitation to generator. Raise AVR set
point to build voltage as recommended. Match
auto and manual set point of AVR and put AVR
on auto
• Switch on synchroscope. Adjust AVR so that
generator terminal voltage and grid voltage are
same
• Adjust turbine speed so that difference between
generator and grid speed is minimized with
generator speed in higher side. (Synchroscope
needle rotates slowly clockwise)
• Close generator breaker when permissive lamps
glow
• Immediately increase speed reference in turbine
to pick up some block load (otherwise generator
may trip on reverse power protection)
• Close HP/LP bypass v/v. Close all drains opened
during rolling. Close warm up drain. Switch off
synchroscope
• Adjust load controller slowly so that turbine
control switches over to load controller
• Raise the starting device to 100 % and turn
tracking device on. Increase load limiter value
• Increase HP/LP by pass set point to full load
pressure
(continued)
44 4 Coal-Fired Unit Operation Guidelines
(continued)
Activity Detail procedure to be followed
LP heater charging • Inlet outlet condensate v/vs are opened and their
after bypass v/vs are closed
• Drain v/vs are put on control mode
• Heater vent v/vs are opened
• Level controllers lined up
• Extraction steam isolating v/vs are opened
• NRV solenoids are deenergized
• Observe increase in condensate temperature
• Close all heater vent v/vs
A temperature in service • Line up SH spray circuit by opening isolating
v/vs
• Line up RH spray circuit by opening isolating
v/vs
• Set both SH and RH temperature controller to
auto with recommended set point
Changing over to unit auxiliary • Unit is synchronized with load more than
transformer auxiliary requirement
• Put UAT breakers in racked in condition. Control
supply turned on
• Put UAT-A incomer synchronizing switch in
check mode and check for permissive
• Switch on the breaker of UAT-A
• Switch off the station supply breaker to BUS-A
• Switch off UAT-A incomer synchronizing switch
• Repeat same for taking UAT-B in service
Load raising and HP heater charging • Move pulverizers to another elevation one by one
and remove oil gun when pulverizers are more
than 50 % loaded
• Raise load through load controller
• Put FD fan control, combustion control on auto
• With unit load more than 50 %, ensure HP
heaters water side charging with bypass v/v
closed
• Keep heaters vent v/v open. Extraction drain v/v
open
• Drip v/v put in normal
• Extraction isolation v/v are opened
• FC NRV deenergized
• Observe heater level and feed water temperature
• Close extraction line drain v/vs and heater vent
v/vs
Warm and hot startup is subset of cold startup. When unit is tripped while
running and the cause of tripping is removed very quickly, then hot startup is
restored. The care to be taken during hot startup is:
1. Boiler is purged properly before starting.
2. All drain valves of steam pipes are opened to avoid any accumulation of
condensation.
4.3 Cold and Hot Startup 45
3. Rate of rise of temperature and pressure is within the limit given by manufacturer.
4. Boiler out steam temperature is more than turbine and stop valve metal tem-
perature, so that rotor is not getting cooled down.
The thermal power station has many materials that are prone to fire such as cables,
oils, lubricants, coal, etc. Standard guidelines of the NFPA are generally adopted
for providing fire protection devices for combatting fire. But why do fires start in
thermal power units? It may be due to leakage of hot air, leakage of inflammable
oil, or possibly accumulation of coal dust.
Good maintenance and regular checking of safety equipment prevents fires.
Therefore, a good maintenance guideline is a must for a power station. The
guideline should cover:
1. Identification of vulnerable hazardous areas.
2. Daily reporting format of cleanliness for identified hazardous area.
3. Schedule checking of mulsifire, extinguishers, and safety equipment.
4. Reporting of leakage of inflammable material and hot air. Monitoring of the
leakage and its maintenance.
5. Issuance of hot permit.
6. Specific guideline for main plant and offsite areas.
A fire can catch in many types of equipment such as the power transformer,
cable gallery, coal conveyor, oil pipeline, oil storage tank, etc., and they require
different extinguishing methods. Oil fires require a foam extinguisher, electrical
fires require carbon dioxide, transformers are protected with mulsifire, and some
require high pressure water. During a fire, toxic gas is produced. Therefore, in
addition to fire protection, use of protective gas masks is also essential.
Regular firefighting training of all operation and maintenance staff is must.
Station HR should maintain a record of training.
Case I
Abnormal condition Each occurrence was existing both in the +ve side of 220 V DC
prevailing: source 1 as well as in –ve side of 220 V DC source 2 of switchyard
Happenings 400 kV main and tie breaker (X352 & X252) were tripped. Master
trip relay was found picked up on both 400 and 132 kV protection
panel of tie transformer without any other protection relay operation.
This resulted with a loss of supply to both 132 and 11 kV station
buses. CW pumps 1C and 2C also tripped /because they are on the
station bus. Unit 2 tripped within 4 s of IBT 1 tripping. Unit 2
tripped on actuation of Gr I protection relay. UPS inverter was
tripped within 3–4 s of unit 2 tripping. CW pump 2B also tripped
along with unit 2 trip whose supply was from unit 2 unit bus. At that
time only CW pump 1A remained in service which was from unit
bus of unit 1. Unit 1 tripped at 21:17:20 h (within 55 s of IBT 1 trip)
on low vacuum protection
Root cause On the basis of the switchyard event log and unit 1 SOE, it was
concluded that due to earth fault on both DC sources of the
switchyard has resulted in malfunctioned operation of the master trip
relays of IBT1 and unit 2 generator breakers
Case II
Abnormal condition Generator was running at synchronous speed with full voltage build
prevailing up with bus side isolator closed and generator breaker open condition
due to hold up for a last minute electrical check up
Happenings 400 kV bus tripped on bus bar protection. All units that were
connected to the bus tripped
Root cause analysis The capacitor across the breaker contact was punctured causing LBB
(local breaker back up protection) to operate resulting bus bar
differential protection actuation. This might be due to the fact that at
some instance the voltage phasor of generator became opposite to
bus voltage causing twice the system voltage across the capacitor of
the generator breaker and the capacitor could not sustain that for
considerable time
Case III
Abnormal condition Plant running on full load. Deaerator level controller was
prevailing malfunctioning and hence was kept on manual operation. Hot well
makeup was closed
Happenings All CEPs tripped on hot well level were very low. Subsequently all
BFP tripped on seal water pressure became very low
Root cause analysis D/A controller in manual did not modulate to respond to the hot well
level. Operator did not notice that hot well makeup was closed and
hot well level going down
References 49
References
Operating parameters of a power plant are dynamic, and in general, vary within a
band of designed limits. However, often due to variation in fuel quality, failure of
controllers, or disturbance in the interconnected power system, the operating
parameters vary beyond their operating limit resulting with thermal stress to the
component and equipments. First we need to understand how this occurs, and only
then can corrective measures be taken.
Adiabatic flame temperature Tfl in the furnace can be calculated by striking the
heat balance between fuel and air on one hand and combustion products on the
other hand, and can be expressed as
m_ gas Cgas ðTfl Tamb Þ ¼ m_ air Cair ðTair Tamb Þ þ m_ fuel Cfuel ðTfuel Tamb Þ þ m_ fuel Hfuel
where m_ is the mass flow, C is the specific heat and H is the heat content of the
relevant component. It is clear from above that with change in fuel heat content or
quantity of fuel, the temperature of the flame changes. Heat absorbed by the water
wall Q_ ww is a function of flame temperature and water wall temperature Tww (a
function of drum pressure only) and can be expressed as
Q_ ww ¼ efur Aww r Tfl4 Tww
4
. The resultant exit gas temperature Tgexit is again a
m_ g Cg ðTfl Ta Þ Q_ ww
function of flame temperature Tgexit ¼ m_ g Cg . As the flame temperature
increases, the components of the boiler become exposed to high flue gas temper-
ature, and prolong exposure resulting in thermal fatigue failure.
Thermal fatigue, corrosion fatigue, and creep damage account for 83 % of the
causes of total damage (Okrajni 2009). As measures are taken to improve the
reliability of thermal power generation plants, it is important to prevent such fati-
gue, corrosion fatigue, and creep damage from occurring to such pressure-retaining
components.
Thermal fatigue occurs by the repeated effects of high thermal stress that is
generated by the temperature differences among the member materials. The thermal
fatigue generated by the start/stop operation of boiler equipment or by load fluc-
tuation is in general a type of low-cycle fatigue. The causes generating thermal
stress vary depending on the structure of each component of the boiler equipment.
The types of damage generally experienced with the pressure-retaining components
of the boiler equipment are shown in Fig. 5.1.
5.1 Boiler
As the number of start ups and shut downs increases, many cracks on the boiler
tube and leakages begin to appear in all areas of the boiler, and, for this reason,
inspection and repair result in longer time and higher cost. In particular, heavy
damage is found in the metallic substance weld zone of furnace pipe walls, furnace
headers, and nozzle weld zones at the reheater header due to fatigue and creep, and
fundamental measures become necessary.
54 5 Managing Thermal Stress
Although the strength of a boiler’s pressure part used under high temperature
and high pressure is designed on the basis of 100,000-h creep rupture strength, in
reality, different pressure parts of the boiler before reaching the cumulative oper-
ation hours of 100,000 h have been found to be developed with cracks. This is due
to an increase in cyclic creep and thermal stress.
From the early 1960s, inspection and assessment technology for remaining life
assessment coping with deterioration phenomena became obvious with time and
has been developed and became operational. At the present time, the focus of its
development has shifted to reducing manual labor, adopting automation, broader
use of robots, etc. In addition, development and practical use of operation
supervisory/diagnosis technology for the purposes of strengthening and enhancing
the operation supervisory aspect is being pushed forward.
The Thermal and Nuclear Power Engineering Society (Kanto affiliate) conducted
a survey on the renewal status of plant equipment for thermal power plants
(commercial thermal, joint thermal, and private thermal) whose cumulative oper-
ating hours exceeded 100,000 h in 1991 on a nationwide scale, and the results of
that survey have been summarized in the “Report of a fact-finding survey on the
renewal of thermal plants (January 1993).” As extracted from the report, the fol-
lowing are the measures to be taken for renewal of the equipment of a thermal plant,
renewal rate and equipment whose renewal due to “deterioration and damage”
exceeds 20 % (Oesterlin and Maier 2013).
Boiler-plant related
1. Furnace tube
Renewal rate About 36 %
Renewal time From less than 40,000–200,000 h. The renewal peak falls within the range
of 100,000–200,000 h
2. Superheater 1st
Renewal rate About 25 %
Renewal time From less than 40,000–200,000 h or more. The renewal peak falls within
the range of 120,000–140,000 h
Reason for Conceivable reasons for renewal are creep damage, external
renewal high-temperature corrosion, and ash erosion
3. Superheater 2nd to 4th
Renewal rate About 56 %, 3rd about 66 %, 4th about 70 %
Renewal time 2nd: From less than 40,000 h to 200,000 h or more
The renewal peak falls within the range of 100,000–120,000 h.
3rd and 4th: From 60,000 h to 160,000 h
The renewal peak falls within the range of 80,000–100,000 h
Reasons for As there are many renewals for those whose main steam temperature is
renewal 550 °C or more, for those for WSS (weekly start up and shut down)
operation and for heavy oil-fired ones, conceivable reasons for renewal are
creep damage and high temperature corrosion
(continued)
5.1 Boiler 55
(continued)
4. Superheater weld joint with dissimilar materials
Renewal rate About 47 %
Renewal time From less than 40,000–180,000 h. The renewal peak falls within the range
of 80,000–160,000 h
Reason for As there are many renewals for those whose main steam temperature is high
renewal and for heavy oil-fired ones, conceivable reasons for renewal are creep
damage, thermal stress fatigue, and high-temperature corrosion
5. Reheater 1st and 2nd
Renewal rate 1st about 60 % 2nd about 62 %
Renewal time Renewals are distributed widely at 60,000 h or more
The renewal peak falls within the range of 120,000–160,000 h for the 1st
superheater and within the range of 100,000–120,000 h for the 2nd
superheater
Reasons for From the viewpoint of the number of start ups, steam temperature,
renewal conceivable reasons for renewal are creep and thermal stress fatigue
6. Reheater weld joint with dissimilar materials
Renewal rate About 60 %
Renewal time 1st from 60,000 to 180,000 h The renewal peak falls within the range of
100,000 to 120,000 h. 2nd from 60,000 to 120,000 h the renewal peak falls
within the range of 80,000 to 120,000 h
Reasons for From the fact that there are many renewals of those whose steam pressure is
renewal high for both the 1st and 2nd reheater, and in the case of the 1st reheater, a
conceivable reason for renewal is thermal stress fatigue
5.2 Turbine
The actual service life of plant equipment differs from its nominal design life and it
is significantly dependent on good or poor operation and maintenance. The inlet
temperature of a steam turbine is as high as 500 °C or higher, and the steam at the
final stage where it finishes its expansion is in the wet condition at a temperature of
about 33 °C and at a wetness fraction of about 10 %.
Various types of deterioration occur due to the difference in operating condi-
tions. The stage of a turbine near the dry-wet alternating area that becomes wet with
a heavy load and dries with a light load is an area where corrosion must be
particularly observed. In such an area, a phenomenon occurs where traces of cor-
rosive substances dissolved in water droplets sometimes condense as a result of the
alternation between a wet condition and a dry condition caused by load fluctuation
or by starting and stopping.
Corrosion and pitting occur more or less in a steam turbine that has been
operated for a long period of time because when the steam turbine stops, steam
56 5 Managing Thermal Stress
turns into droplets that attach to the metal surface even near the last stage where wet
steam flows and in the higher stage where the temperature is higher. Corrosion
fatigue occurs when corrosion and repeated stress exist concurrently. The necessary
strength and ductility of the materials used for the parts exposed to high temperature
are maintained by heat treatment. However, various mechanical properties related
to the strength deteriorate due to the effects of temperature and stress caused by
operation under high temperature for a long period of time. One of these phe-
nomena is softening. The higher the temperature and the stress, the more con-
spicuous is the softening.
A different mode of age deterioration of a turbine is shown below in Fig. 5.2.
Among the above-mentioned deterioration modes, softening and creep are
caused mainly by temperature-related factors. The high-pressure turbine,
intermediate-pressure turbine, and associated valves are assessed. A model of this
complexity is needed to accurately describe cyclic plasticity in addition to
time-dependent effects such as primary and secondary creep and stress relaxation.
Due to long-term scale in power plants, load change effects can play an important
role in the resulting mechanical response of the component and hence the estimated
damage from creep fatigue.
Because low-cycle fatigue occurs due to repeated thermal stress and centrifugal
force caused by the starting and stopping of the operation at the power plant, the
corner portions where stress concentration occurs are assessed for the
high-temperature and high-pressure or rotating parts of the equipment.
5.3 Generator 57
5.3 Generator
The causes of deterioration of the stator coil insulation are generally classified as
follows: (1) heat, (2) electricity, (3) machine, and (4) environment.
Because the impregnated resin of natural resin has plastic elasticity, heat dete-
rioration such as softening, flow-out, and sublimation progress, resulting in voiding
and peeling. It generally leads to dielectric breakdown due to partial discharge. The
following are the measures to be taken for renewal of the generator and generator
auxiliaries of a thermal plant.
5.4 Fans
Changes in stress occur at the impeller caused by the change in RPM due to
start/stop of operations. Low-cycle fatigue occurs due to repeated thermal expan-
sion caused by temperature particularly with a GRF (gas recirculation fan). If a
GRF begins at room temperature, the temperature of the intake gas rapidly changes
the temperature of the fan impeller and the vibration becomes great until it comes
back to stable, steady operation. This is an effect of the difference in thermal
expansion caused by the temperature difference among the components of the
impeller. In particular, when a riveted joint is used in the structure, this phe-
nomenon appears frequently. Therefore, if a riveted structure has been used for the
impeller, it is recommended to change it to a welded structure and remodel the
connection of the impeller to the shaft/hub to a reaming bolt connection structure
from the rivet-fixed type.
References
Forde J, Fernandes J, Sibli A (2009) Damage to power plant due to cyclic operations and
guidelines for best practices. European Technology Development (ETD) report, April 2009
Kumar A, Mathuriya S, Silpi S (2014) Detection of creep damage and fatigue failure in thermal
power plants and pipelines by non-destructive testing techniques. A review. Int J Eng Res
Technol (IJERT), 3(11)
Oesterlin H, Maier G (2013) Numerical assessment of power plant components by use of
mechanism-based material models for deformation and lifetime. In: 39th MPA-seminar
October 8 and 9, 2013 in Stuttgart. Fraunhofer Institute for Mechanics of Materials IWM,
Freiburg
Okrajni J (2009) Thermo-mechanical fatigue conditions of power plant components. J Achiev
Mater Manuf Eng 33(1)
Sanders R, Hu X (2011) Thermal fatigue of power plant components. In: CEED Seminar
Proceedings 2011
Chapter 6
Chemical Health of Thermal Power Unit
The role of chemistry in a thermal power unit can be broadly classified as follows:
• Production of DM water for cycle water in boiler—Cycle water is the
working medium of the boiler. Although cycle water operates on closed loop,
the average make-up requirement is 3–4 %. As an example, for a 1000 MW
subcritical thermal plant, average make-up water requirement is around
2100 MT/day. Bearing oil coolers of major equipment such as ID fans, FD fans,
PA fans, etc. are supplied with DM water.
• Production of clarified water for equipment cooling and other purposes—
Clarified water is produced from raw water through filtration and flocculation. It
is input for production of DM water. In addition, air conditioners and com-
pressor coolers are supplied with clarified water. This water is also used for
drinking purpose.
• Analysis of coal/oil for determination of calorific value and fuel component
analysis—Cost of fuel is dependent on effective heat content of the fuel. An
analysis of fuel is done for determination of its effective heat value, ash, and
moisture content.
• Analysis of flue gas for ascertaining effluents in flue gas—Flue gas contains
suspended particulate matter and green house gases. Environment norms
specified the acceptable limits of effluent in ambient air. Analysis of flue gas is
done to estimate the effluent concentration in the air and thereby taking cor-
rective measures, if any.
• Analysis of mill fineness, unburnt carbon, and flue gas oxygen and carbon
monoxide for effective combustion—Efficiency of the plant is reduced without
the proper combustion. Negative mill fineness adversely affects the combustion.
Similarly, less air affects combustion and produces carbon monoxide. A flue gas
analysis should be done before taking corrective measures.
A thermal power plant has a number of chemical and physical processes associated
with it. Fuel is converted to heat energy and produces flue gas as a by-product. The
flue gas contains many toxic components and needs effluent control. Heat energy
from the fuel is converted to water and produces super-heated steam, which runs the
6.2 Effect of Processes Chemistry on Power Plant Equipments and Performance 61
turbine. Lubricants keep the high-speed turbine bearing cool. The generator is
equipped with a high-quality hydrogen cooling and water cooling.
Water is a major component and is used as working fluid as well as a cooling
medium. Because it is a universal solvent, water carries a number of chemicals
dissolved in it, including gases. At high pressure, the solubility of water drops and
chemicals are deposited inside the vessel. Deposited chemicals cause (a) corrosion
to the tubes and (b) prevent heat transfer. Corrosion damages the base material.
Prevention of heat transfer causes localized heating leading to failure of base
material. Boiler tube failure is due to corrosion and chemical deposition is a
common phenomenon and a nightmare for all thermal plant operators. Furthermore,
with the advancement in cycle efficiency through super critical and
ultra-supercritical technology, the cycle pressure and temperature threshold is
increasing, making water chemistry more vulnerable. Keeping water free from
chemicals and developing methods to reduce tube corrosion is still a major subject
of research and development to the power plant researcher.
Under high pressure and high temperature, silica becomes dissolved in steam
and carries over to the turbine. At a later stage of the turbine, when temperature and
pressure are reduced, solubility of silica drops and is deposited on the turbine blade
which disturbs the dynamic balance of the turbine blade, causing a rise in vibration,
and finally blade failure.
More than 45 % of the energy input to turbine gets lost in the condenser. A huge
amount of cooling water is required to extract heat from the condenser. Untreated
cooling water produces scaling and algae inside the condenser tube, affecting heat
transfer and thereby reducing turbine output and cycle efficiency. With an increase
in the number of power plants to meet the ever-rising demand, availability of water
is reduced and we are resorting to close cycle cooling. Close cycle cooling requires
more chemical treatment to keep it suitable for the condenser tube. Tube leakage in
the condenser causes major outage to the plant. Deposits in cooling tower fills
deteriorates cooling efficiency and directly affects heat rate of the unit.
Lubrication oil and control oil are two vital fluids in a turbine. It is an absolute
must for oil lubrication of the turbine to be free from debris, free from moisture, free
from any deposition. Daily chemical analysis keeps the lubrication system healthy.
Defective lubricant causes costly damages and plant outages. With the introduction
of fire-resistant fluid (FRF) for turbine control, keeping FRF free from moisture is
necessary, otherwise acidic property develops causing damage to the sophisticated
control equipment. Lubrication also plays a vital role in all rotating equipment.
Many rotating equipment is pressure lubricated. Poor chemical condition of the
lubrication oil causes non-availability of the equipment.
Coal and oil are the main resources for generating power. A boiler is designed
within a narrow range of coal characteristics. The efficiency of the boiler changes
with diversity of coal composition. Formation of slag and erosion due to abra-
siveness damages boiler parts. Regular chemical analysis of coal gives an idea to
operator for optimum loading of mills, heat rate of the unit, and prescribes blending
(in case a facility for blending is available). The quality of the coal plays a major
62 6 Chemical Health of Thermal Power Unit
role in combustion and efficiency. The power station chemistry group also identifies
the pulverizer responsible for producing bad quality.
The power transformer transforms electric energy for transmission. Outage of
the generator transformer stops the plant. Health of the transformer is identified
through chemical analysis of transformer oil and predicts the condition of the
transformer long before it reaches the failure stage, thereby allowing preventive
maintenance can be done. Similarly, chemical analysis of oil filled measuring
transformers (CT and PT) prevents catastrophic failure of the electrical system.
Environment norms are becoming more stringent. As a whistle blower, chem-
istry plays a vital role to appraise everybody about the effluent release in the
environment and thereby forced O&M to take corrective measures.
Boiler furnace design is based on the rate of heat release by the input fuel. Heat
release from the fuel depends on its component. Combustion of coal particles takes
place in different phases as shown in Fig. 6.1 (Shen 2009).
Starting of char burning and total time required for complete combustion
changes the heat transfer pattern of the boiler. Stages of char combustion are shown
in Fig. 6.2.
Typical proximate and ultimate analysis of coal of different countries are given
in Tables 6.1 and 6.2.
Adding oxygen involvement to the above equations and deducting the oxygen
presence in the fuel totals the theoretical volume of oxygen required for
combustion.
VO2 ¼ ð1:866C þ 5:56H þ 0:7S 0:7OÞ Nm3 kg
For calculation of theoretical dry air on a mass basis, the following formula can
be used:
In practice, more air than the theoretical calculated amount is supplied in order to
obtain complete combustion. The air above the theoretical values supplied for a
combustion process is known as “excess air”. It is necessary to determine the
amount of excess air to exercise control over combustion. This may be accom-
plished by chemical analysis of flue gas. It is possible to assess the quantity of air
taken part in the combustion through flue gas analysis as shown in the table above.
The table indicates how the quantity of excess air supplied in the combustion
process is generally found either by the presence of carbon dioxide or oxygen
percentage in the flue gases. In the case of combustion of a single fuel, a satisfactory
index of excess air can be assessed from the carbon dioxide content of flue gas only.
This is because combustion of 1 lb. of carbon produces 3.67 lb. of carbon dioxide,
only under normal atmospheric condition.
6.3 Fuel Chemistry and Combustion 65
In case a large amount of air is used, the concentration of CO2 will be diluted
and thus the percentage composition will be lowered. Conversely, in case a small
amount of excess air is used, dilution will be less and the percentage concentration
of CO2 will be relatively high. In a given percentage of excess air, higher carbon
hydrogen ratio fuels will experience a higher percentage of CO2 in the flue gas in
comparison to the fuels with lower percentage of excess air. When fuel oil is
burned, the flue gas formed will have a lower percentage of carbon dioxide. Oxygen
percentage in flue gas provides an accurate excess air measurement when either
single or multiple fuels are used. Excess oxygen in flue gas represents the portion
which presents during the combustion, but did not combine as a combustible ele-
ment in the fuel. This additional oxygen in the flue gas and the nitrogen with which
it was mixed are considered as the excess air. The theoretical oxygen and thus the
theoretical air requirement are approximately proportional to the heat content of the
fuel even with variation of the carbon-hydrogen ratio. For a given percentage of
oxygen, the excess air is the same for either coal or fuel oil. A table indicating the
percentage of excess air, carbon dioxide, and oxygen for bituminous coal and fuel
oil is given below:
The percentage of excess air over the theoretical air requirement formulas can be
calculated as follows (Basu et al. 2000):
O2 1=2CO
Percentage of excess air ¼ 100
0:263N2 þ 1=2CO O2
O2
Percentage of excess air ¼ 100
0:263N2 O2
Now air contents some moisture. If X m is the percentage of moisture in the air,
then the actual wet air requirement will be Mwa ¼ Mda ½1 þ Xm
66 6 Chemical Health of Thermal Power Unit
6.4.1 Moisture
If the moisture content in coal is high, it will cause trouble for the mill. Hot primary
air supplied to the mills has two purposes. First, to dry up the coal so that it can
properly grind, and second, to carry coal dust to the burners. If the coal is not dry,
higher particles will form by sticking together from finer particles and air will not be
able to carry them freely and efficiently. As a result, the mill will begin to overload
and consequently the milling capacity will be reduced and therefore, the load on the
boiler will be reduced. Additionally, the fuel/air mixture temperature will be low
causing an evolution of volatiles which will retard the combustion process. If efforts
are made to take the same output from the mills, more hot air must be supplied to
dry the coal sufficiently and to carry the coal to the burners. This will cause excess
air to be supplied to the boiler and will lengthen the flame and affect the com-
bustion. There will also be heat loss due to excess air.
6.4.2 Ash
Although ash has nothing to do with the combustion directly, on the whole it affects
performance of the boiler. Moist ash content forms the basis of gradation of coal
(i.e. higher ash means reduction in combustible percentage therefore lower the
calorific value). Coal with a high ash content causes increased wear and tear of the
mills, piping, and ducts. If the boiler has been designed for high ash coal, it will
take care of the poor quality of coal while maintaining furnace stability and load.
But if a boiler has been designed for superior coal low in ash content, feeding of
inferior coal will definitely affect the furnace stability and the rate of heat release
may not be sufficient to complete the combustion with the furnace. It may either
cause fires in the super heater zone or wastage of combustibles.
6.4 Effect of Fuel Quality on Combustion 67
The furnace is designed for burning a particular size of coal so that its combustion
may be complete by the time it leaves the furnace. Therefore, if coarser coal dust is
fed, combustion will not be complete in the furnace and after-fires may occur. This
will also reduce the output and efficiency of the boiler. Coarse particles can also fall
down to the lower zones of the furnace and may get entrapped in the slag, resulting
in loss of combustibles. If coal quality is increased by changing the classifier vane
position, even the particle of correct size may not pass through the classifier and
return to the mill for further grinding, thus reducing the milling capacity.
Fuel costs consume approximately 80 % of the total cost of power generation.
The evaluated calorific value of the fuel in a chemistry lab proposes a theoretical
coal requirement for a particular level of generation. Comparing the evaluated value
with the actual consumption of coal drives operation engineers to find fault with the
equipment.
Three types of water are used in any thermal plant, namely (a) demineralized
(DM) water, (b) clarified water, and (c) raw water. DM water is used for cycle water
and cooling of bearing lube oil of important rotating machines. Clarified water is the
main input to DM water and is also used for cooling and drinking water purposes.
Raw water in huge quantities is used as cooling water for condensing steam in the
condenser, as cooling water for DM-DM coolers, and as input to the clarifier.
Mineral-free water is preferred as working fluid for generating thermal power.
High-quality demineralized water free from chemical ions is processed through
filtration and ion exchange. Raw water contains soluble carbonates and oxides. Any
salt which dissolves in water that is subjected to hydrolysis and breaks into cations
and anion. These charged particles permit the water to conduct electricity. These
types of salt are called electrolytes. Calcium, magnesium, sodium, and iron are
some of the most common cations in water. Anions such as bicarbonate, carbonate
hydroxide, sulfates, and chlorides are common in water. Soluble carbonate or oxide
at high temperature gets deposited on the inner surface of the tubes causing bad heat
transfer. This further leads to overheating of the tubes and subsequent failure.
Another troublesome impurity is dissolved silica. At very high temperature and
pressure, when fed to boilers, silica is carried away with steam and is deposited at
the low pressure stage of the turbine causing damage to the turbine blades. Further
presence of carbon dioxide and oxygen in natural water causes many corrosion
problems. A DM plant does the chemical treatment to make the water free from
minerals.
Corrosion is the wasting of material due to formation of metallic
oxide/hydroxide when the metal is in contact with water. Metallic iron in contact
with water goes into the solution as ferrous ions leaving negative charged electrons
free to react (Mookherji and Kapur 1971):
M ! Mþ þ e ð6:1Þ
The positively charged metallic ions react with negative (OH)− ions to form the
hydroxide:
The ferrous hydroxide formed is oxidized to ferric form by the oxygen present in
water in the dissolved state. The electrons released in the reaction (6.1) are neu-
tralized by an equivalent amount of hydrogen ions from water to the neutral state:
eþH ! H
The neutral H formed reacts with the dissolved oxygen present in water to
form H2O:
6.5 Managing Water and Steam Quality 69
2H þ 1=2 O2 ! H2 0
1. Clarification
2. Demineralization
Clarification process encompasses:
1. Mixing of chemicals with water-Various chemicals, namely aluminum sulfate,
iron sulfate, sodium aluminates, iron sulfate, polyaluminium chloride, etc. are
used for coagulation. Chlorine is added for disinfection. The water mixed with
chemicals is churned slowly so that colloids come out of suspension and are
precipitated. Clear water is allowed to overflow from the clariflocculator.
A schematic of clarification is shown in Fig. 6.3.
2. Filtration-The water is allowed to pass through a pressure filter and a gravity
filter. Filtration is the removal of the solid particles from water by passing it
through a filtering medium. Filtration is usually a mechanical process that does
70 6 Chemical Health of Thermal Power Unit
not remove dissolved solids. Various layers of gravity sand filter are shown in
Fig. 6.4.
Clarified water is used for:
1. Feed water to DM plant
2. Feed water to Softening Plant
3. Drinking water–township and plant
4. Service water–as cooling water for A/C and compressors
Demineralization: Filter water is processed through a cation and an ion
exchanger to produce DM water. Synthetic ion-exchange resins are used to remove
6.5 Managing Water and Steam Quality 71
all the ionizable salts and the quality of water thus produced is as pure as that
obtained by distillation. The schematic is shown in the Fig. 6.5.
The strongly acidic cation-exchange resins exchanges hydrogen ions for other
cations. The result is that neutral salts are converted to their corresponding acids, a
process known as salt splitting. The strongly basic ion-exchange resins exchanges
other ions for hydroxyl ions (OH). Therefore, the water after treatment in a cation
exchanger is further treated in an ion exchanger and thus the salts originally present
are converted to water. The mixed bed unit is single column or unit containing both
cation and ion exchange resins intimately mixed together. When water is passed
through such as unit it comes into contact alternately with grains of cation and
anion resin, so that the water is subject to an almost infinite number of deminer-
alization stages. In operation it behaves like a large number of two-stage dem-
ineralizers in series, with the result that it will produce final water which is neutral
and has very low residual dissolved solids content.
During the process of demineralization, the ion exchanger becomes weak and
hence after eight hours of service (or as recommended by DM plant provider),
regeneration of an ion, cation, and mixed bed is done for revival of capability of the
ion exchanger. Ion exchange reactions during service and regeneration are as follows:
chosen ensures that, with a raw water having a TDS of several hundred ppm,
virtually complete demineralization results.
A water treatment plant for a 2000 MW station will have a through-put of about
45,000 gal/h and units to handle this through-put with perhaps two complete dem-
ineralization streams operating in parallel can be designed to acceptable dimensions.
Mixed bed units, or sometimes cation-exchange units are used to remove traces of
contaminants (metal corrosion products silica and cooling water leaks) from feed
water particularly in feed systems associated with once-through boilers. This is one
method of “condensate polishing”. The condensate polishing ion-exchange units
form an integral part of the feed system and handle 100 % of the feed water flow.
Typical Back Wash Flow Rates
Cation
Back Wash flow rate—40 m3/h (1/2 of the normal flow rate).
Duration—5 min
Type of water—filtered water
Anion
Back Wash flow rate—20 m3/h (1/3 of the normal flow rate).
Duration—5 min
Type of water—filtered water
Mixed Bed
Mixed bed differs from that of the single resin bed primarily with regard to the
regeneration step. The key to the process is backwash, which serves for classing the
two resin components the lighter anion resin forming at the top, the heavier cation
resins remains at the bottom; when done properly, a clear and level interfacing is
formed between two layers. An interface collector is incorporated at this point.
Back sash flow rate—18 m3/h
Duration—3 min
Type of water—DM water
If 1 ppm of dissolved solids enters in each 1,000,000 lb. of feed water, 1 lb. of
dissolved material enters the boiler each hour. Since 999,000 of that water is
removed as steam (pure water vapor), one pound of solids is left behind in the boiler
in each hour of operation. Obviously, if we continue to operate in this way, the solid
content of the boiler water would keep on increasing. Carbon dioxide and oxygen
gases get dissolved in the feed water due to unavoidable contact with the atmo-
sphere and form corrosive substances causing damage to boiler tubes. An efficient
deaerator can reduce the concentration of dissolved oxygen in the feed water to
<0.005 mg kg–1.
Modern practice is to use hydrazine (N2H4) and it reacts as follows:
N2 H4 þ O2 ! N2 þ 2H2 O
From the above chemical equation we can see that no solids are produced, in
fact, the nitrogen and water are completely harmless. Hydrazine, therefore, is the
ideal chemical for removing oxygen and its only disadvantage is that it is expen-
sive. Any surplus hydrazine that remains after removing the oxygen will decom-
pose to release ammonia (an alkaline gas) and nitrogen.
3N2 H4 ! 4NH3 þ N2
Hydrazine Ammonia Nitrogen
ðliquidÞ ðgasÞ ðgasÞ
Boiler feed water in a supercritical unit has to be of extremely high levels of purity.
Because supercritical boilers are not provided with a steam drum, if the entering
feed water is not free from mineral oxides, the impurities may deposit in the boiler
and carryover of impurities can result in turbine blade deposits.
Make-up water quality at the DM outlet:
• Sp. conductivity < 0.1 µS/cm, with
• Chlorides, sulfates, and sodium < 3 ppb
• Silica < 10 ppb
• TOC < 300 ppb
Therefore, feed water chemistry is critical to the overall reliability and sustain-
ability of fossil-fuel-fired plants. Corrosion products are generated during the pro-
cess, flow along the cycle and are deposited in the various boiler areas. The
deposition at different areas acts as the initiating center for most of the major failure,
and therefore need chemical cleaning for removal.
Reducing, AVT(R)—Reducing agent (N2H4) is added at CEP discharge. pH is
maintained by using ammonia. Here the ORP (oxidation-reduction potential) is in
the range of 300–350 mV.
• Elevated pH of 9.0–9.3.
• Cation conductivity of <0.20 µS/cm.
• Minimum air in-leakage to ensure <10 ppb dissolved oxygen at CPD.
• Addition of reducing agent (N2H4) to the feed water to ensure reducing ORP
(−300 to −350 mv).
6.5 Managing Water and Steam Quality 77
NH3
O2 0 ppb 30–150 ppb 0 ppb
(injected)
Conductivity <0.5 µs/cm ≥0.2 µs/cm
There are four action levels that have been developed based on the following
criteria:
1. Normal—Different parameters are consistent over a long period of operation.
A safety limit has been provided to prevent concentration of impurities at sur-
faces and under surface deposits.
2. Action Level 1—The limit indicates that there is a possibility of accumulation
of impurities susceptible for corrosion. The parameters are to be normalized
within 1 week.
3. Action Level 2—The limit indicates that accumulation of impurities and cor-
rosion will occur. Parameters to be brought back to normal level within 24 h.
4. Action Level 3—Rapid corrosion can occur. Shut down the unit within 4 h.
• Immediate shutdown: Rapid boiler tube damage by low boiler water pH.
Immediate shutdown is required.
• Action Level 1 value: 2 × (Normal target value)
• Action level 2 value: Twice the action level 1 value
• Action level 3 value: > Limit of action level 2
• Immediate shutdown: Boiler water pH (drum units) indicates a serious
acidic contamination and the unit should be shut down in an orderly fashion.
Various monitoring points and limits are given in Tables 6.7, 6.8, 6.9, 6.10, and 6.11.
When water is converted to steam in a boiler, a small proportion of any impu-
rities in the water will be carried forward with the steam and deposited in the super
heater or on the turbine blades by one of two mechanisms. These are:
(a) Physical carryover whereby small droplets of impure water escape through the
steam scrubbers.
(b) Some impurities become more soluble and are carried forward as the satura-
tion temperature of the steam increases with pressure.
Table 6.10 Main steam and Targets Cumulative hours per year
RH steam limit
N (Normal) –
1 (Action level 1) 336 (2 weeks)
2 (Action level 2) 48 (2 days)
3 (Action level 3) 8
Immediate shutdown 1
One of the soluble impurities carried forward in the steam is silica (SiO2). Silica
is more soluble in steam than other impurities and when it deposits on the turbine
blades it is extremely difficult to remove. This effect is so pronounced that special
precautions must be taken. The figure shows these plotted against different boiler
pressures. These limits are controlled (a) by preventing dust particularly entering
parts of the unit when opened up during survey or inspection and (b) monitoring
82 6 Chemical Health of Thermal Power Unit
and controlling silica at the outlet from the demineralization plant. Should the silica
limits be reached, they must be reduced by lowering the boiler pressure and
blowing down.
The boiler water quality control for the once-through boiler differs in comparison
with conventional drum-type boilers because of the following:
1. The quality of the water in a drum-type boiler can be monitored and controlled
through sampling and adding chemicals at the drum. The concentrations of
impurities are controlled by blowing down part of the water to waste and adding
fresh water in the drum. Once-through and supercritical boilers do not have any
drum. Therefore, sampling and controlling of the boiler water is not possible.
The only option to maintain water quality is to analyze and control the feed
water at the boiler inlet.
2. The tube wall surfaces of a drum boiler are usually wet. If dry spots occur then
formation of high concentrations of salts at the periphery takes place. Whereas
in a once-through boiler, dry and wet walls at different regions exist by design.
Any impurities will cause salt concentration at dry wall regions. Therefore, the
feed water quality to such boilers must be of exceptionally high standard.
3. Concentrations of normally safe materials in subcritical boilers must be elimi-
nated in the once-through boiler with no blow down. Everything entering will
either deposit or pass out with the steam to the turbine. In the case of the
supercritical boiler, the problems of feed water treatment are accentuated by the
fact that at critical pressure the solubility of dissolved salts is the same in the
steam as in the water. There is no physical separation and impurities in the water
may again pass through with the steam to be deposited in the super heater and
on the turbine blades. If deposition occurs, it can result in an increased pressure
drop across the boiler. This will reduce output efficiency and affect heat transfer
necessitating shutdown to chemically clean the plant. Additionally, solutions of
6.5 Managing Water and Steam Quality 83
other, possibly corrosive, materials will concentrate and corrode the boiler. If
these are carried forward to the turbine they can deposit and lead to loss of
efficiency or possibly cause cracking of the special alloy steels used in turbine
rotors. For once-through boilers, only volatile additives can be used for feed
water dosing. These are normally ammonia and hydrazine. This is known as
zero solids treatment or AVT. In order to achieve the high quality feed water
required for once-through boilers, it is necessary to continuously polish the
whole of the condensate. This is particularly important at sea water stations
where the ingress of salt from condenser leakage would cause rapid boiler
corrosion.
The power sector is a dominant consumer of industrial water. Cooling water con-
sumes more than 50 % of the water requirement in thermal power units. Specific
consumption of water with open cycle cooling is about 5 m3/MW. The scarcity of
water and the increasing cost of water mandates for close-cycle cooling. With
close-cycle cooling specific consumption of water can be brought down to about
3 m3/MW.
In close-cycle cooling, the major consumption is evaporation loss (around 75 %)
and blow-down (around 23 %). Around 2 % is drift loss.
Evaporation: Amount of evaporation that occurs in a cooling tower can be
calculated using the following formula.
Drift (W): Drift is a form of blow down that occurs due to entrainment of water
droplets in the air leaving the cooling tower. Drift typically ranges from about 0.05
to 0.3 % of the recirculation rate depending upon the type and efficiency of the
cooling tower.
Make-up (MU): To replace water lost from the system by evaporation, drift,
blown down, etc., fresh water known as make-up is added to the circulating water
system.
84 6 Chemical Health of Thermal Power Unit
E
BD þ W ¼
COC 1
MU ¼ E þ BD þ W
Due to water’s ability to dissolve most of the substances to some extent, and its
ability to support biological life, every cooling water system is subjected to
potential operational problems. These are:
1. Deposit formation–scaling
2. Fouling-general fouling and microbiological fouling
3. Corrosion
4. Biological deposition
In general, chemical water treatment involves addition of corrosion inhibitor and
periodically analyzing for the residual. However, modern chemical treatment also
includes the control of scale and biological growth as shown in Fig. 6.12.
Controlling the three sides of the water triangle judicially, the effectiveness of water
treatment increases. On the other hand, failure to control any one component of the
triangle adversely affects the water quality leading to damage of valuable capital
equipment.
To prevent formation of calcium scale in the cooling water system, three basic
methods are normally adopted.
1. Removing the calcium oxides/carbonate and scaling minerals from the water
during water treatment.
2. Converting scale forming constituents soluble in water.
3. Converting the impurity as a removable sludge rather than as a hard deposit.
Based upon these basic methods scale control may be done in the following
manner:
1. Limiting COC
2. Softening of make-up water
3. pH adjustment of cooling water
4. Polyphosphate dosing
5. Organophosphonates/various organic polymer dosing
6. Scale inhibitors
7. Control of fouling
8. Control of biofouling
9. Periodic cleaning
• Mechanical cleaning
• High-pressure water jet cleaning
For water TDS < 10000 mg/l, different index are used to denote the potential of
scaling and corrosion for calcium carbonate.
1. Langlier (or saturation) index
LSI ¼ pH pHs
pHs ¼ ð9:3 þ A þ BÞ ðC þ DÞ
RSI ¼ 2pHs pH
S&DSI ¼ pH pHs
pHs ¼ pCa þ pAlk þ K
pCa ¼ 0:4343 logðCaÞ þ 5 pAlk ¼ 0:45 logðAlkÞ þ 4:8
Anodic Cathodic
Chromate Polyphosphate
Orthophosphate Zinc
Molybdate Polysilicate
Nitrite Phosphonates
Orthosilicate
For example, when phosphate is added to the system in the presence of calcium
hardness it will form a cathodic inhibitor.
6.6 Managing Cooling Water 89
Chemical Residuals
1. Inorganic phosphate as PO4 2–3 ppm
2. Organic phosphate as PO4 1.5–2.0 ppm
3. Zinc as Zn 0.5–1.0 ppm
4. Molybdate as MoO4 0.5–1.0 ppm
5. Dispersant as polymer 1.0–2.0 ppm
6. Biocides chlorine 0.2–0.5 ppm
CIO2 (continuous) 0.05–0.1 ppm
Once daily 0.2–0.5 ppm
The treatment program is suitable for a pH range from 7.5–8.3 and alkalinity up
to 300 ppm. The upper limit of alkalinity is 300 ppm, beyond that sulfuric acid
dosing would be required to maintain the alkalinity ≤300 ppm as per the following
formula:
If the surfaces are separated by a fluid, the friction between them is considerably
reduced and lubricating oil is normally used for this purpose. Good lubrication aims
at retaining the oil film between the moving surfaces. Friction produces heat and so
90 6 Chemical Health of Thermal Power Unit
a lubricating oil is not only required to prevent the surfaces from coming into direct
contact, but also to dissipate the heat from the parts being lubricated. In the case of a
turbine plant, the heat transmitted along the shafts from the steam cylinders must
also be removed and this is another purpose for the lubricating oil. It is essential that
a lubricating oil allows trouble-free operation of the plant in which it is used.
Deterioration of the oil inhibitors may cause rusting in oilways with debris being
carried forward into journals and bearings. Shafts can be attacked by acids formed
in the oil, or the lubricating properties of the oil can be impaired by emulsification
which can result in damage to shafts and bearings. Regular examination of the oil
can indicate its rate of deterioration. Thus the sampling and analysis of lubricating
oils ensures that they are satisfactory for continued service. If an oil beings to
deteriorate, it can be either changed or reconditioned (sometimes at the site) at a
time suited to the operation of the plant, rather than waiting until deterioration
makes the oil change essential at an inconvenient time. A lubricating oil may
deteriorate for several reasons (Sander 2012):
1. Increase or decrease in viscosity
2. Oxidation
3. Become contaminated with water
4. Lose its rust inhibitor
5. Foam
6. Emulsification
7. Become acidic
8. Become contaminated by dirt or metallic particles
If the viscosity decreases, the oil film between the moving surfaces could
become so thin that the surfaces actually touch each other. Grades of different
lubricating oils are given in Table 6.13.
Oil becomes oxidized when the various compounds which make up the oil
combine with oxygen. Additives called oxidation inhibitors are added to lubricating
oils to stabilize them against oxidation. As an oil becomes oxidized, its acidity
increases. It is better to anticipate any oxidation that might occur rather than wait
until the acidity has increased, or sludge has formed. Oxidation stability tests should
be carried out every 6 months.
Thermal power plants generate effluents in the form of gas and liquid. Burning of
coal generates huge amounts of CO2 and toxic gases such as nitrogen oxides and
oxides of sulfur. The ash contains many heavy metals and toxic metals. Open-cycle
cooling water enhances the temperature of the source and thereby becomes the
destroyer of aquatic life. Environment norms differ from place to place. The
chemistry department is to monitor the chemical parameters in the effluents.
Various pollutants emitted by flue gas from coal-fired and lignite-based thermal
power plants are namely CO2, NOx, SOx, along with inorganic particles such as fly
ash, soot, suspended particulate matter (SPM), and traces of other gases. Types of
pollutants and emission from thermal power plants depend on the composition of
the fuel, furnace temperature, quantity of air used, and any technology used to
control the emissions. To calculate the impact of burning of fuel inside the furnace,
mass emission for CO2, SO2, and nitric oxide (NO) are computed based on the
input data. Mass of CO2, SO2, NO, and H2O are calculated by mass balance as:
CO2 ¼ C 44=12
SO2 ¼ S 64=32
H2 O ¼ H 18=2
O þ N2 ¼ NO þ N
N þ O2 ¼ NO þ O
N þ OH ¼ NO þ H
• Sufficient setting time is allowed in the ash pond before the supernatant water is
released into water bodies. This ensures that the suspended solids in the effluent
are well below the prescribed limits.
• The pH of the effluent is monitored. If this is not within allowable limits,
provisions of neutralizations of the effluent made.
From an environmental point of view, bottom ash is fairly inert and, therefore,
relatively safe. However, fly ash is rather reactive. Due to the presence of various
acid and base metals, ash water mixtures exhibit a wide range of pH.
Ash transport water normally picks up dissolved solids from ash. In addition,
depending on the design and operator of the ash pond, large quantities of suspended
solids may be present. Wide variations in pH of the ash transport water have also
been observed. The range of concentrations of the various parameters of ash
transport waters, monitored by the National Thermal Power Corporation at its
operating stations is presented in Table 6.14.
The demineralization system waste is drained to a flow equalization and holding
tank for temporary storage. The holding tank is sized to hold the waste generated by
one complete cycle of boiler clearing for one unit. From the holding tank the waste
Any abnormality in the chemical parameter indicates problems in the system. Some
examples are given below.
1. Increase in chloride concentration in feed water: The main contributing factor
for increment of chloride concentration in boiler water is condenser tube leak-
age. It is often possible to identify small leakage in the condenser tube before
any rise in feed water conductivity. The normal limit of chloride in boiler water
for a drum-type boiler is <50 ppb and for supercritical boiler it is <3 ppb.
2. Increase in silica concentration in feed water: An anionic exchanger in the water
treatment plant removes silica. Increase in silica concentration in make-up water
indicates anionic bed exhaustion. Taking heaters in services after maintenance
also increases silica in boiler water. Limit of silica in make-up of a drum-type
boiler is <20 ppb and for a supercritical boiler it is <10 ppb.
3. Increase of O2 at air heater outlet: Excess air is required for complete com-
bustion. Air heater seal leakage causes air ingress in flue gas. Therefore, an
increased oxygen measurement at the air heater outlet indicates air heater seal
leakage. Normally in flue gas, 3–5 % of excess oxygen is maintained.
4. Increase of CO in flue gas: Perfect combustion converts all carbon monoxide to
carbon dioxide. In the boiler, the air fuel mixture is not homogeneous at all
points due to turbulence and therefore traces of CO are always there in flue gas.
Again, imperfect combustion causes CO production which may convert to CO2
after the furnace zone. CO formation at various zones can be measured with the
help of high-velocity thermocouple (HVT) along with a gas analyzer. There is
no acceptable limit of CO in flue gas (it should be minimum). However, as per
ambient air quality standard in industrial areas, an acceptable limit is around
5 mg/Nm3 measured every 8 h, on average.
5. Increase of CO in mill: Presence of CO indicates combustion of fossil fuel.
A trace of CO in the mill indicates mill fire. Immediate measures should be
taken for quenching of fire in the mill.
6. Increase of unburned carbon in bottom ash: Burning of coal particle in a PF
boiler depends on the 3Ts (temperature, turbulence, and time) and size of the
coal particles. While the 3Ts are taken into consideration in designing the fur-
nace, unburned in bottom ash is mainly caused by mill quality. Lower coal
quality increases unburned in bottom ash. The acceptable particle size is 75 %
of pulverized coal should pass through 200 mesh.
6.9 Indication of Abnormality 95
7. Increase of wear debris in lubrication oil: Wear debris analysis is done for
understanding the condition of bearings. The limits are expressed in mg/kg.
A general acceptable limit is 10–30 mg/kg. An increasing trend indicates
damage of bearings.
8. Increase in acidity in control oil: In the power generation industry, phosphate
ester fluid is generally used in electrohydraulic turbine governing control
(EHC) systems of steam turbines because of its good stability, exceptional fire
retardant, and lubricating properties. Phosphate ester is a delicate fluid and in the
presence of high water content (>1500 ppm) and high temperatures, it is sus-
ceptible to hydrolytic breakdown and therefore needs special attention.
Breakdown of phosphate ester fluid results in the formation of acidic com-
pounds. To overcome this, conditioning chemicals are used to maintain the acid
environment (acid number) within acceptable limits. In general, fuller’s earth,
activated alumina, and ion exchange resins are used to absorb acidic compounds
formed in the fluid. IEC 60978 and ISO 7745 guidelines should be followed.
The limit in acid number is <0.1 mg KOH/gm.
9. Increase in dissolved gas analysis: Condition of oil-filled power transformer is
diagnosed from dissolved gas analysis (DGA) of oil samples. Presence of the
following gases are examined:
• Pure gases: H2, N2 and O2
• Oxides of carbon: CO and CO2
• Hydrocarbons: acetylene (C2H2), ethylene (C2H4), methane (CH4) and
ethane (C2H6)
Overheating damages the organic structure of the insulation. In this case, DGA
indicates high levels of carbon monoxide and carbon dioxide. If the damage is
severe, DGA shows methane and ethylene at high levels.
Overheating of oil breaks down the organic structure and formation of methane,
ethane, and ethylene.
Partial discharge is detected in a DGA by increase in hydrogen levels.
Formation of arc is a severe condition in a transformer and indicated by detection
of acetylene.
IEC standard 60599 and the ANSI IEEE standard C57.104 give guidelines for
the assessment of transformer condition based on DGA, and the volumetric ratios of
pairs of gases.
10. Decrease in hydrogen purity: Hydrogen purity inside the generator is required
to be maintained above 97 %. When purity decreases, it indicates mixing with
oxygen or other gases. Only seal oil comes in contact with hydrogen as well as
the ambient atmosphere. Seal oil absorbs oxygen from the air. A decrease in
hydrogen purity indicates trouble in the exhauster system. Additionally, pres-
ence of moisture and other gases due to high temperature in the winding slot
may also be the reason for the decrease in hydrogen purity.
96 6 Chemical Health of Thermal Power Unit
References
Basu P, Kefa, Justin (2000) Fuels and combustion calculation, Chapter 3, Boilers and
Burners-Design and Theory, Springer
Madan HC, Chauhan SS, Garg D (2013) Chemical cleaning of boilers with EDTA. BHEL,
Technical service. http://www.slideshare.net
Mookherji SN, Kapur JC (1971) Some problems of corrosion in thermal plants. ACC-Vikers
Babcock Limited, Durgapur. Proceedings of Short Course on “Corrosion Control in Water and
Waste Water Engineering”, Feb. 24th–27th, 1971, NML
Shen X (2009) Coal combustion and combustion product. Coal, Oil Shale, Natural Bitumen,
Heavy oil and peat vol-I, 2009 - eolss.net
Sander J (2012) Steam turbine oil challenges. LE White paper, 2012 Lubrication Engineers, Inc.
Tsubakizaki S et al. (2013) Water quality control technology for thermal power plants. Mitsubishi
Heavy Indus Tech Rev 50(3)
Chapter 7
Maintenance Practice
The actual service life of plant equipment differs from its nominal design life and it
is significantly dependent on good or poor operation and maintenance. Precise
inspection for the pressure part of the boiler, turbine rotor, casing, major valves and
rotor of generator, remaining life assessment, renewal of deteriorated equipment
and portions, addition of equipment, strengthening and enhancement of durability
are all planned simultaneously.
Maintenance is perceived as an opportunity to improve reliability and avail-
ability of the equipment and of the unit as a whole. The Power Generation Industry
in India, by and large adopts the philosophy of preventive maintenance at fixed
intervals and predictive maintenance (PdM) of selected equipment occasionally, on
the basis of condition monitoring. Scientific tools such as the reliability centered
maintenance (RCM) with risk evaluation and prioritization (REAP) are now being
introduced in some plants and are in the very early stages of implementation.
Maintenance can be defined as the set of activities that keeps an operating system in
good condition and also brings back the system to working condition if it fails. The
set of activities includes inspections, identification of faults, procurement of spares
and its preservation, repairs, overhauls, etc. carried out on an operating system to
restore it to its original performance, avoid the causes of failure, and ensure its
productivity.
In-production plant, maintenance plays a major role in determining the delivery
schedule, quality of the product, and its cost. The real impact of maintenance can
only be seen when maintenance activities for each piece of equipment are opti-
mized. It has been observed over the past few decades that considerable interest has
been placed and research done in the field of maintenance modeling and opti-
mization. Maintenance affects the cost of production. It also determines whether the
system will be operated economically or not.
The RCM provides the base work for scope identification of overhaul and pre-
ventive maintenance. The condition indicators (PdM measurements) are also
defined based on failure modes in the RCM. The frequency of these tasks (number
of times in a year and interval) are also determined through RCM. RCM thus
provides the input for ‘engineering declaration’ which is an essential document for
102 7 Maintenance Practice
All work order requests are automatically routed for approval to the planner(s) of
the equipment on which the problem was observed. When a planner logs into the
system, all the work order requests created for equipment associated with their
location is displayed for either approval or rejection.
All preventive maintenance work orders are automatically generated by pre-
ventive maintenance schedules defined in the system. Once a work order is created,
it goes through the planning and execution stage, ending with closure of the work
order to complete the cycle. The planning phase consists of scheduling/rescheduling
the work order by taking into consideration the availability of spare parts and
resources to execute the work order as well as feedback from operation on
equipment availability. A clearance permit for isolating the equipment for main-
tenance is also generated when the work order is scheduled. When a work order is
scheduled, it is ready for execution and the actual hours spent by the
employees/resources, the actual duration of the work order/task, the quantity of
spare parts used, details of root cause of failure, and equipment downtime details
can be entered into the system while execution of the work order is in progress.
When the work order is closed, the actual details entered for the work order are
posted to the equipment history for future review/analysis.
generated and scheduled automatically every week, when maintenance periods are
opened. When equipment is not in use and when the preventive maintenance tasks
identified for that equipment are not to be performed for a temporary period of time,
the equipment can be flagged as off-line for that period. A sample preventive
maintenance work order is shown in Appendix 1.
All resources such as spares, consumables, and contract manpower can be specified
during scheduling of the work order. The material can be issued directly against the
work order and the balance of the material can also be returned. Similarly, the
contract manpower can be booked against the work order. This assists in daily
monitoring of the maintenance costs through the equipment and defect level.
Planning is the most critical for proper maintenance of equipment and systems.
Absence of proper planning may result in unnecessary loss in equipment avail-
ability leading to loss of system availability and hence, overall plant availability
(Wei et al. 2004).
Planning is done to address the following:
• Equipment wise history cards
• Making spares available at the appropriate time
• Skilled manpower planning for maintenance activities
• Preparing PM schedules for time based on manufacturer’s recommendation or
historical performance as well as based on condition
• Preparing maintenance schedules based on reliability using RCM tools such as
REAP
• Inventory management
• Focus on zero failures, reduction in maintenance cost
• Prepare maintenance budgets based on activities to be carried out and resources
to be mobilized
• Reduction in MTTR
• Preparing network diagrams for all maintenance activities
• Preparing sub-assemblies to be ready for final assembly to save down time of
the machine
• Preparing a checklist to be followed before and during maintenance
• Improvement of skills of maintenance staff through appropriate training
106 7 Maintenance Practice
The concept of the overhauling preparedness index (OPI), initiated in the year 2005
across all NTPC stations, ensures overhaul preparedness of forthcoming overhauls
through various attributes. The OPI score is monitored for the 24 months prior to
the actual overhauling of the unit. Attributes monitored are namely formation of an
outage committee, identification of the scope of work, plant betterment action plans,
incorporation of recommendations of knowledge team/modifications/trip commit-
tee, resources preparation in terms of material and contracts, quality plans,
re-commissioning checks sheets, PERT/BAR chart preparation, etc. The pre-
paredness index is handy in deciding which efforts need to be applied for carrying
out overhaul activities smoothly and in a time-efficient way. The following points
describe OPI and its utility:
• An overhauling schedule is prepared well in advance (8-year rolling plan) and
stations preparedness for overhauling is measured through OPI.
• Monitoring of the OPI is begun 24 months before actual overhauling.
• This index is a measure of preparedness in terms of
– Formation of an outage committee
– Engineering declaration submission
– Outage period and duration: Justification of outage duration and time period
– Equipment and scope of work for overhaul. Standard Scope of work:
Boiler and auxiliary
Steam turbine and auxiliary
Turbo generator and electrical
Control and instrumentation
Miscellaneous
Gas turbine and auxiliary
– Plant betterment action plan (AI/RI/EI/TO/LF) Examples
BTL reduction plan
APH efficiency revival plan
108 7 Maintenance Practice
Appendix 1
References 109
References
Training Strategy
• Identifying training needs.
• Imparting skill-based training and refresher courses.
• Training as a part of KPA for the operating staff as well as their reporting officer.
Strategy for Inexperienced Manpower
• Manpower mix needs to be balanced.
• More experienced personnel at lateral level to be increased.
• Experienced manpower may be retained after retirement.
Strategy for Adhering to Standard Procedure
• Working executives can access all the standard procedures easily.
• Involvement of working executives to be increased in procedure development
for new set of activities.
• In case of critical activities, time pressure should be eased to avoid any lapse in
following standard procedures.
Any process is dynamic and hence susceptible to change in parameter value over an
acceptable range. The economic operation of any power plant calls for consistent
supervision of the process states and the form of major equipment (Pliska et al. 2010).
Further, there is a wide range of problems connected with measurement inac-
curacies and thereby estimating expected power and efficiency. It is humanly
impossible to notice deviation of all the parameters in a definite time frame. To do
these jobs, artificial intelligence systems are adopted. Under varying conditions and
different steady-state operating modes, process simulation is used to calculate
detailed of expected or desirable performance values (pressures, temperatures,
flows, etc.). In modern power plant, dynamic simuletor is used for prediction and
auto corection of parameters for safe operation. Comparison of expected perfor-
mance and actual performance also helps in early detection of any equipment
degradation or/and incorrect adjustment of the process parameters.
This also aids in improving operation and predictive maintenance so that plant
operation and maintenance costs can be reduced. An example of finding deviation is
shown in Fig. 8.5.
Performance analysis diagnostic and optimization (PADO) is a widely used
system for finding parameter deviation. Different modules of PADO are shown in
Fig. 8.6 (PADO 2016).
8.2 Minimizing Process Parameter Deviation 115
Although the number of forced outages has been reduced considerably over
the past several years, there is still a long way to go to achieve ‘zero forced
outage’.
116 8 Outage Minimization
References
Conversion of fossil fuel energy into electricity is a very poor process. A major
portion of the energy in fossil fuel gets lost at different components or processes:
• Losses in boiler
• Losses in condenser
• Losses in turbine
‘Heat rate’ is the measurement of how much heat is being utilized for production
of one unit of electricity. Efficiency can be calculated through a direct method of
ratio of energy generation to that of energy input from fuel or indirect method of
(input energy losses) to the ratio of input energy. In general loss method is con-
sidered to be the more accurate method because every component of loss can be
ascertained and accordingly corrected steps can be taken for minimizing the loss.
56% (49%)
Cycle
Boiler
13%
Unit Auxiliaries
8%(3%)
100% Heat
input
• Loss due to wasted heat in ash: Ash exits the furnace as bottom ash with high
temperature. Loss related to the sensible heat of ash can be calculated as
½Mass of BA CBA ðTBA Ta Þ þ Mass of FA CFA ðTFA Ta Þ
100
GCV of fuel
• Radiation and unaccounted loss: Any hot body radiates heat energy, similar to
the boiler. Sufficient insulation is provided on external surface of the boiler to
minimize this loss. Generally, for large boilers, this loss is considered to be
0.4–1.0 %. However, if boiler surface area and surface temperature is known,
h i
this can also be calculated as 0:548 ðTs =55:55Þ4 ðTa =55:55Þ4 þ 1:957
rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
1:25 ½196:85Vm þ 68:9
ð Ts T a Þ where Vm is the wind velocity and Ts is the
68:9
surface temperature.
Components of boiler loss (Bureau of Energy Efficiency 2014) are shown in
Fig. 9.1.
The following parameters should be monitored for boiler loss:
• APH gas inlet temperature
• APH gas outlet temperature
• APH air inlet temperature
• APH air outlet temperature
• Oxygen and carbon dioxide at APH gas inlet and gas outlet
• Ambient air temperature and humidity
• Coal sample and analysis for GCV and ultimate analysis
• Bottom ash and fly ash sample for unburned carbon analysis.
120 9 Managing Efficiency
The condenser converts steam to water. In the thermal cycle of a power plant
condenser is the element where approximately 47 % of the total heat energy is
exhausted and has not been added to the output. The major losses in the condenser
occur due to:
• Poor condenser back pressure: Consider the rankine cycle for power generation
shown in Fig. 9.2, available energy for work depends on the exhaust pressure at
which the adiabatic expansion is taking place (point number 7). Available energy
is reduced when exhaust pressure increases due to bad vacuum.
The following reasons can be attributed to poor vacuum:
• High CW inlet temperature: Low pressure turbine (LPT) exhaust temperature is
the saturation temperature at back pressure. The higher the cooling water tem-
perature the lower the rate of steam condensation taking place, with the quantity
of cooling water flow remaining constant. This results in deterioration in back
pressure. High CW inlet temperature restricts loading of turbine.
• Tube fouling/scaling: Cooling water in the condenser is taken from the raw
water source. Formation of algae and other inorganic growth causes fouling.
Presence of insoluble mineral salts results in scale formation. Fouling and
scaling reduces both heat transfer and flow through the condenser tubes. Poor
heat extraction from the LPT exhaust cause reduction in back pressure.
• LPT exhaust temperature: The turbine consumes heat to convert steam energy to
mechanical energy. Due to leakage in the interstage seals, or any other reason,
pressure drop across LPT can change and will result in high LPT exhaust
temperature. This will cause an increase in hot well temperature and thereby
saturation pressure.
• Air ingress: The condenser is maintained under vacuum. Continuous evacuation
of noncondensable gas from the LPT exhaust steam is done through the vacuum
pump or ejector. The hot well is connected to the LPT exhaust through an
9.1 Efficiency Losses in a Coal-Fired Power Station 121
HP 86 %
IP 90 %
LP 88 %
Fig. 9.8 Heat balance diagram of a 800 MW advanced ultra super-critical unit
The following parameters are measured, for computation of boiler efficiency and
performance test (International Energy Agency 2010).
(a) Flue gas analysis
1. CO2 or O2 percentage in flue gas
2. CO percentage in flue gas
3. Flue gas temperature
(b) Flow meter measurements for
1. Fuel flow
2. Steam flow
3. Feed water flow
4. Condensate water flow
5. Combustion air flow
126 9 Managing Efficiency
Measurement Instrument/method
CO2, O2, and CO High-velocity thermocouple (HVT) probe with
portable gas analyzers
Flue gas temperature, combustion air HVT probe with digital temperature recorder/optical
temperature pyrometer, RTD
Boiler surface temperature RTD
Steam temperature Thermocouple
Fuel temperature RTD, liquid in glass
Furnace draft Differential manometer
Steam flow, water flow, air flow Flow meter as applicable
Fuel flow Calibrated gravimetric feeder
The combustion efficiency test does not cover the auxiliary power consumption
by fans, pumps, etc.
Flue gas concentration and temperature can both be stratified due to turbulent
flow in the furnace. An HVT probe can be traversed throughout the width of the
boiler and thereby can collect samples at different points over the cross section for a
representative sample. Flow of flue gas and water is measured either through an
on-line instrument or inserting a differential manometer. Steam flow is measured
from the first stage pressure of the turbine. Rate of fuel flow is estimated from the
gravimetric feeder speed.
Readings should be recorded only after steady boiler conditions are attained.
Steady stack temperature, fuel input, steam pressure, and excess O2 are the indi-
cations that boiler operating condition is stabilized. During the test the following
conditions are maintained:
9.3 Boiler Efficiency Test 127
• Emergency blow down and soot blowing is not carried out during the test
period.
• Mill combination is maintained throughout the test period.
• Drum, deaerator and hot well maintained at a fairly constant level during the
test.
• All controlling parameter variations kept within the permissible limits.
• Duration of the test generally lasts for 4–8 h.
• Fly ash/bottom ash, raw coal, and flue gas sampling are taken at intervals of
15 min.
For calculation purposes, all the readings are averaged for the entire period.
Ultimate analysis of the coal is done for estimating the percentage of different
components.
The object of the heat consumption test is to determine the required heat input to the
turbine for an output of one kilowatt-hour at particular loadings (Gill 1984). The
required heat input for one unit of electricity is known as ‘heat rate’ and its unit is
kcal/kWh.
Prior to the test, the plant should be held on a steady loading at the test load for
at least 1 h to ensure that everything is thoroughly ‘heat-soaked’.
The following parameters are determined during the heat consumption test:
1. Steam flow to HP turbine and its enthalpy at inlet and outlet
2. RH spray flow and its inlet and outlet enthalpy
3. Feed water flow and its enthalpy at a different point
4. Bleed steam flow to heaters and its enthalpy
5. HP gland leak off flow and its enthalpy
6. Steam flow to IP turbine and inlet enthalpy
7. Condenser vacuum
8. Electrical output.
A result is obtained and recorded in a table such as this:
Test No. 1 2 3 4 5 6 7 8 9 10 11
Load (MW)
Heat (kcal/h)
When plotted on a graph of heat consumption versus load, the trend lies in a
straight line called a ‘Willians line’ as shown as Fig. 9.9.
128 9 Managing Efficiency
The line has intercepted the heat consumption axis at h0 which is the fixed heat
consumption at any load. At lower loads the heat rate increases and therefore, the
thermal efficiency worsens.
This is because the fixed heat component represents an increasing proportion of
the total heat consumption.
LPT ENTRY
HPT EXIT
TSV 200 MW
HPH 5
LPT 1
Pressure in Kg/cm2
140 MW
LPT ENTRY
HPT EXIT
TSV 140 MW
HPH 5
LPT 1
Actual
Pressure in Kg/cm2
140 MW
Reference
TSV 140 MW
HPH 5
LPT 1
Actual
Pressure in Kg/cm2
140 MW
Reference
simultaneously to ensure that readings are taken at the same loading conditions.
During the pressure survey all the heaters should be in service, otherwise there will
be discontinuity in the best line through the points.
130 9 Managing Efficiency
Coal mills are the major auxiliary equipment used for feeding coal to a coal-fired
power plant. Therefore, performance of the milling system is of utmost importance.
One useful technique used to diagnose milling system performance is known as the
“operating window” (Subba Rao 2011). The operating window (Gill 1984)
describes the limits/operating regime of a mill based on different input parameters
as shown in Fig. 9.14. This helps in avoiding the usual problems such as mill skids,
duct erosion, explosion, and fires in pulverized coal-air ducts or inside the mill. As
shown in Fig. 9.14, the mill operating window is drawn within coal flow–air flow
coordinates, representing the mill performance limits. The following are the limits
considered for developing the operating window:
(1) Limit in flame stability.
(2) Capacity limit of the mill.
(3) Fuel fall out limit of the mill.
(4) Erosion limit.
(5) Tempering limit.
(6) Drying limit.
A typical mill operating window is shown in Fig. 9.14.
In the operating limits related to coal flow is drawn between milling capacity
limit and flame stability limit (1 and 2), the air flow operating regime is drawn
between coal transport limit and erosion limit (3 and 4), Operating regime of
pulverized coal-air temperature is drawn between the drying limit and tempering
limit (5 and 6). Plotting these limits defines a suitable “working area”. This working
132 9 Managing Efficiency
area is bound by upper limits (2, 4, and 6) and lower limits (1, 3, and 5). The
pulverizer should operate into this working area, to avoid performance problems.
Milling capacity is the upper limit for coal flow. If coal flow crosses the milling
capacity limit, mill choking may occur. Thus, mill capacity is given by the mill
manufacturer. The turndown ratio of the burner determines the lower coal flow limit
to maintain flame stability. A typical turndown value is half of the maximum
nominal milling capacity (Gill 1984).
If air flow is less, pulverized coal can settle in the ducts and may cause fire or
explosion. The coal-air mixture should have a minimum velocity of 18–20 m/s to
avoid any settlement. On the other hand, if air flow is too high, there is the
possibility of wearing on ducts, valves, and bends. In general, maximum air flow
should be within 1.5 times the minimum air flow value (Gill 1984).
Drying capacity is determined by mass flow of air through the mill and tem-
perature of the air to the mill. The tempering limit ensures outflow coal-air mixture
at a reasonable temperature, but low enough to avoid spontaneous combustion.
Currently, mill performance is not only judged by the limits of operation. The
quality of grinding, equal distribution of coal in all the mill discharge pipes, is a
major factor for combustion. Distribution of coal-air flow is normally checked by
dirty pitot tubes. A mill fineness check is done through high accuracy mill fineness
sampler.
9.8 Fan Performance Test 133
line leak-off is measured to assess the condition of the hydraulic clearances within
the pump.
Pressure and temperature measurement
While pressure is measured using a pressure transducer, temperature is usually
measured through a thermocouple. For noncontact type measurement, portable
infrared instruments provide sufficient accuracy and can be used for temperature
measurement.
Brakes horsepower measurement
Brakes horsepower of a pump driven by an electric motor can be reasonably cal-
culated by its motor current and voltage.
References
Bellman DK (2007) Power plant efficiency outlook. Working Document of the NPC Global Oil &
Gas Study, July 2007
Bureau of Energy Efficiency (2014) Energy performance assessment of boilers
Gill AB (1984) Power Plant Performance. Butterworth and Co (Publisher) Ltd
International Energy Agency (2010) Power generation from coal-measuring and reporting
efficiency performance and CO2 emissions
Jochem E (2007) Realizing the potential of energy efficiency. Expert Report, UNF
Subba Rao PMV (2011) Performance analysis of coal mills
Chapter 10
Best Practices
The Indian power generation sector has been developed with a mixed ownership by
the central government, state government, independent power producers, and
captive power plants. Having diversified motivation for ownership, the operating
practices of these power plants are not always consistent, and often are not per-
formed with the best possible effectiveness and efficiency. This is further affected
by lack of experience; technical knowhow, lack in research facility which results in
an increasing gap between well-performing units and less-developed ones.
Best practice is a relative term. It should not be misunderstood as benchmarking
parameters and a way to achieve it. To the contrary, it gives the capability of
everlasting sustainability. Best practice has many dimensions for a thermal power
generator. This chapter discusses some of the good practices that give sustainability
rather than a rank in overall performance. The practice covers the following areas:
• Longevity and efficient operation beyond the regulatory period
• Maximizing availability
• Knowledge management
• Growth planning for sustainability
• Environment management.
Deposition not only changes the heat consumption pattern of the cylinder, but
changes the natural frequency of the blade and results in high vibration.
Maintaining steam chemistry as recommendation is the best practice to avoid
deposition (see Chap. 6 on recommended values). This can be done during
major overhauling of the turbine.
– Bad performance of condenser: Bad performance of condenser can occur as
a result of many issues as explained in Chap. 9. Scaling and corrosion in
condenser tubes is nonreversible if appropriate actions are not taken in time.
Managing cooling water chemistry is one of the best practices for long life of
condenser tubes. DP across the condenser indicates tube choking, fouling,
and scale formation. Reversing of condenser cooling water flow, cleaning
through balls/concho system is adopted for removal of soft scales. A point
worth mentioning is that that during reversal of cooling water flow, loading
on turbine should be reduced appropriately. In case of permanent scaling, a
chemical cleaning method should be adopted for removal of scales.
Monitoring total condition of condenser is the best practice for sustainable
condenser performance (as explained in Chap. 9).
• Capacity degradation of generator can occur as a result of:
– Scaling in generator stator conductor: High-capacity stator conductors are
water cooled. Deviation in chemical parameter of stator water may lead to
scaling inside the conductor and is nonreversible. Monitoring chemical
parameter once every 8-h shift and taking corrective measures is the best
practice for long life of the generator.
– Bad performance of generator coolers: DM water is used for generator
hydrogen coolers. Scaling, if any, reduces performance of cooling. Water
chemistry is a vital factor for long life of coolers.
• Competing with advanced efficient machines: With passing of time, technology
advancement is taking place. Efficiency of an old boiler, heat rate of old turbine
not able to compete with more efficient advanced class of machines. However,
efficiency of old machines can improve to some extent by retrofitting them with
new technology. The best practice is to engage a dedicated R&M group for
studying retrofitting possibilities in old plants.
• Unavailability of spares: Technology is changing fast. Unavailability of spares
leads to capacity degradation. Developing spare parts through vendor devel-
opment is one of the best practices for sustaining longevity of the plant, but
requires a long drawn out process. The maintenance planning group of the plant
should initiate before the spares became unavailable.
• Obsolesce of controls: Control systems and data acquisition systems become
obsolete very fast. The best practice is to plan and implement retrofitting of new
controls before the old become obsolete.
140 10 Best Practices
Plant availability becomes affected due to forced plant outage or partial outage of its
auxiliaries and availability of fuel (Ahmad et al. 2012) and water. The major
challenges faced are:
• Minimizing forced outages: Forced outages occurs as a result of system dis-
turbance and human error. System disturbance can occur internally due to
equipment or control failure or externally from an interconnected power system.
While internal forced outage probability can be theoretically brought down to
‘zero’ through the approach of total productive maintenance (TPM), an efficient
good islanding scheme can prevent plant outage from an interconnected power
system. Human error can be prevented through training. Increasing acidity in
Turbine control fluied is a common phenonmenon for outage of Turbine
(Bhattacharyya and Ghosh 2013). Documenting all types of forced outages,
discussing the root cause and mitigating measures to all the operating staff on a
common platform is considered to be a best practice. Discussing outages
through video conference across the organization at NTPC is a unique practice.
• Availability of auxiliaries: Partial outage of auxiliaries occurs because of failure
of any given component of the equipment. Preventive and predictive mainte-
nance needs to be taken to such a level that equipment outage is ‘zero’. To truly
enhance the quality of maintenance, one must look beyond preventive and
predictive maintenance philosophies and adopt best practices such as TPM,
which brings in a cultural transformation through a true partnership of the
Operations and Maintenance Departments.
to share and the quality of the input needs to be monitored. The second best practice
is determining how to encourage employees to share and acquire. The mechanism
of reward does not work indefinitely. When an employee benefits directly from the
knowledge, the process sustains. It requires a thorough study on the type of
knowledge employees are seeking and easy access to that knowledge. That
knowledge must be developed by relevant domain experts. All these require a
dedicated team for KM. A training/employee development center can act as a
change agent. The mandate should be:
• Creating a platform for collaborative knowledge sharing and capturing tacit
knowledge
• Building organization-wide and unit-specific intellectual capital
• Internal branding
• Creating a culture of knowledge sharing.
Auraiya is one of the NTPC gas stations. Due to low schedule from beneficiaries,
the operating performance of the station was deteriorating. The knowledge team
invoked brain storming. The reason attribute was the cost of generation. Details
activity required for reducing the cost of generation worked out. All the concern
departments were aligned to the requirement. Auriya became the 3rd best in gen-
eration cost among the seven NTPC gas stations.
142 10 Best Practices
An organization does not grow if the road ahead is not clear. Only proper planning
can bring that clarity. Planning starts with the vision of the organization/department.
Change in business environment, new opportunities, diversification requirement
forces the organization to change its vision. For example, NTPC, a reputable power
utility company in India has revisited its visions and objectives a number of times
since its first corporate planning session in 1985.
The 1985 objective statement stipulated:
• To establish thermal power capacity and associated transmission systems within
the prescribed time schedule, cost, and reliability level and conforming to the
National Energy Plan.
• To operate its power stations at base load with maximum performance efficiency
and plant reliability.
• To build in-house capabilities so as to be self-reliant in respect to technical
expertise and develop a cadre of skilled manpower with a knowledge of the
latest technology.
• To manage the financial operations of the company in accordance with sound
commercial utility practices and to generate returns as per government
guidelines.
• To develop and implement a well-knit personnel policy and a comprehensive
personnel program that will be result-oriented and to develop an organizational,
culture which will motivate employees to contribute their best toward the
achievement of organizational objectives.
• To function as a responsible public sector undertaking, bearing in mind its
commitment to the society.
Over a period, the vision changed, and in 2007 its vision statement changed to
“A world class integrated power majority, powering India’s growth, with increasing
global presence.”
While a vision keeps changing over time, the process of planning roams around
the four basic questions:
• Where does the organization want to go?
• When does it want to achieve the goal?
• Where does the organization stand now?
• How should the organization reach the destination?
The answers to these questions depends on the change in business scenario, the
strength and weaknesses of the organization, and what the opportunities and threats
are. An organization can appraise the answer internally or externally. The best
practice is to internally judge the goal but appraise the strength/weaknesses and
opportunities/threats from the outside. How the external environment perceives the
organization on the above-mentioned fronts gives an accurate representation.
A regular growth plan is a best practice for an organization.
10.6 Environment Management 143
The second best practice is reducing land usage. Many power utility companies
use fly ash for brick and manufacturing. Back filling of a mine with ash is also an
option for ash utilization. Ash utilization via various methods reduces environment
burden.
SOx emission is controlled by treating flue gas with lime. It can also be con-
trolled by blending high sulfur coal with low sulfur coal. Optimization of coal
blending is a dynamic process and is considered to be a good practice. NOx
emission is dependent on flame temperature. Low NOx burner design or blanketing
the flame over a fire air supply reduces NOx emission. The best practice is to
monitor these two gases online and continuously take corrective measures.
One of the best practices followed by good power utilities is operation and main-
tenance guidelines specific to the unit/station (Confederation of Indian Industry
2010). The guidelines can be drilled down to system level/equipment level
operation and maintenance instruction. These guidelines are used for development
of local management instructions (LMI) suitable for a particular plant. LMIs are
written by experienced engineers associated with a particular plant and aid in
maintaining health of the units in the long run.
The guidelines can be of the following categories:
(1) Operation directives
(2) Operation guidance notes
(3) Operation information notes
(4) LMIs.
Operation directives are issued by the highest authority of the plant operation
and maintenance (O&M), the implementation of which is mandatory for all power
stations.
Operation guidance notes are documents conveying advice and broad guidance
issued under the highest authority of O&M, the implementation of which would be
mandatory to the extent applicable to the particular station.
Operation information notes (OINs) are issued under the authority of the Head of
Operation Services to provide information to power stations relating to technical
matters. The information contained in OINs is to assist station authorities and to be
acted upon at the discretion of the station head.
LMIs are management instructions produced and issued at locations which are
derived from directives, guidance notes or information notes, and authorized by the
station head to instruct the staff on station policy. Additionally, the station head may
want to include other matters of station policy within his LMI system which he or
10.7 Important Operational Guidelines/Operation Directives 145
she desires to introduce and which allows effective discharge of the managerial
responsibilities. LMIs are by definition site-specific, mandatory documents.
As a sample, three guidelines/directives used at NTPC are given in the
Appendices A, B, and C.
References
Ahmad W, Prasad MSK, Javed Bhat, Thangapandian V (2012) Coal accident analysis, risk
quantification and Suggestive scheme improvements in coal bunkers of Thermal power plants.
IJIERD 3(2), 18–25
Bhattacharyya B, Ghosh SK (2013) Use and maintenance of phosphate ester hydraulic fluids in
steam turbine governor system-A case study. In: NTPC O&M conference IPS 2013
Confederation of Indian Industry (2010) Manuel on best practices in Indian thermal power
generating units
Appendix A
The Operational and Safety Aspects
of Chemical Cleaning of Thermal
Power Plants
such cases, only one copper removal process needs to be utilized and it is
advantageous to use it after iron removal. Furthermore, it may be possible
to divide in half the chemical concentrations of sodium bromate and citric
acid, the pH still, however, being adjusted to 9.5. Work has shown that
sodium nitrite is a less acceptable alternative to sodium bromate for the
oxidizing agent in copper removal, despite its apparent advantage for the
secondary purpose of short-term passivation. If gas-induced circulation is
being used, air is an acceptable medium during copper removal, but does
not obviate the need for sodium bromate.
1.5.4.7 Passivation After Cleaning
To minimize deterioration of the active surfaces produced by acid cleaning,
a final passivation stage is an essential part of the overall cleaning process.
Details are included in Appendices 1A, 1D, 1E and supplementary notes
are given in Sect. 1.8, ‘Protection of Plant After Cleaning’.
1.5.4.8 Protection of Plant When the Cleaning Process is Interrupted
Special situation could arise if it were necessary at any stage to curtail
or suspend a cleaning. Guidance on the available courses of action in
such circumstances is given in Appendix 1G.
1.6 Practical Considerations
1.6.1 Planning
1.6.1.1 Coordination
Experience has shown the need for full consultation between the
Engineering, Design and Construction, Plant Engineering, and
Operation Services before carrying out pre-operational chemical
cleaning.
1.6.1.2 Operational Water Requirements
During cleaning, there is a requirement for very large quantities of
clarified and DM water. Careful programming of the installation and
commissioning of the water treatment plant and water storage tanks is,
therefore, required before commencing pre-commissioning cleaning.
For post-operational cleaning, application of the complete Appendix 1D
may use up to 12 boiler volumes of DM water.
1.6.1.3 Effluents
It is essential that all statutory requirements covering effluent disposal
from the station are established and met. In some circumstances, citric
acid waste can be disposed of by burning in an adjacent boiler.
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 153
dictate that both pre- and post-operational cleaning are carried out with
most of the drum internals in place.
1.6.3.6 Stagnant Areas
Particular attention must be given to stagnant areas, instrument
connections, and similar items to ensure that they are properly cleaned
and flushed. Temperature measurement points should be installed to
show uniformity of circulation, although an infra-red TV camera is
preferable for this purpose. Adequate sampling facilities should be
available to check reagent strength and circulation.
1.6.3.7 Water-Plugging of Super heaters
To prevent cleaning solutions entering the super heater while only the
boiler circuit is being cleaned, the super heater shall be water-plugged
before any circulation of cleaning solution commences and
back-flushed between the various stages of the process. Care must be
taken to ensure that the super heater can be adequately back-flushed. In
addition, as discussed in Appendix 1H, a constant head overflow device
shall be fitted to the boiler drum, and suitable arrangements made to
indicate drum level during cleaning. Make-up water should be adjusted
to a Ph OF 8.8–9.2, and ammonia should be used for this purpose.
1.6.3.8 Venting
While chemical cleaning operations are in progress, venting of the
boiler, including the vent from the constant head overflow, should be to
the outside of the building into an area inaccessible to personnel.
1.6.3.9 Inspection
Thorough inspection of the plant, as far as practicable, shall be carried
out at the end of the cleaning process, giving due regard to the
precautions given in Sect. 5, ‘Safety Aspects’.
1.6.4 Chemical Aspects
Given that there have been problems of degradation of inhibitors in
storage, it would be advisable to check the age and batch number of the
chemical used. Apply the inhibitor efficiency test before use.
1.6.4.1 Chemical Requirements
As some cleanings require additional amounts of chemicals (principally
for iron removal), a sufficient reserve should be available locally to
minimize delay to the program. This is particularly important for the
first cleaning in a boiler’s history or after a change of operating regime
(e.g. from base-load to two-shifting).
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 155
Notes:
1. This procedure may be unsuitable for large vessels (e.g., DC heaters) because
of weight support limitations.
2. After water flushing has been completed, the plant shall either be dried out or
put in wet storage, unless the flushing immediately precedes a further stage of
cleaning.
3. Water flushing shall be carried out using deionized water if austenitic
components are present or for once-through boilers. If any other plant is given
a preliminary flush with filtered water, it shall be thoroughly flushed out
afterward with deionized water, except where it is to be followed by a chemical
cleaning process.
1.8 Protection of the Plant After Cleaning
1.8.1 The Need for Passivation
After the steel surfaces have been chemically cleaned, they are very
‘active’ and subject to rapid rusting. It is, therefore, necessary to passivate
the cleaned metal surfaces to prevent their deterioration. Operation
immediately after passivation is the best means of establishing the
protective oxide film.
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 157
Notes:
1. Experience shows that provided the system has been lagged, the temperature
should not have fallen below 75 °C before cleaning has been completed, when
using ammoniated citric acid, or 50 °C with hydrofluoric acid/hydrochloric
acid.
2. The reasons for raising pH above 5.0 are:
(i) To minimize corrosion of the plant after cleaning, but before displace-
ment of acid.
(ii) To avoid corrosion in discharge points and culverts.
160 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
1A-III. 1.4 Citric acid rinse is carried out using 0.1 % W/W citric acid with
a of pH 3.5–4.0. The second rinse with citric acid is done at a
temperature of 65 °C. This step is to ensure a more thorough
iron removal.
1A-III. 1.5 Drain the citric acid solution under nitrogen capping.
1A-III. 1.6 Carry out neutralization using a neutralizing solution contain-
ing 8000 ppm of trisodium phosphate, (Na3PO4 12H2O) and
4100 ppm of disodium phosphate (Na2HPO4 7H2O) at a
pressure of 7 kg/cm2. Hold the pressure for about 2 h
Neutralization can also be done using 1 % soda ash solution at
85–90 °C for about 6 h.
1A-III. 1.7 Switch off the fires. Allow boiler to cool gradually. Open the
drum vents when the drum pressure drops to 1–2 kg/cm2. Drain
the boiler when the drum temperature drops to below 100 °C.
full load steam flow. ASME PTC 4.1/BS-2885 gives a method for
calculating sizes of pipework, and pressure and temperature
conditions necessary for steam purging the super heater, reheater,
and steam pipework together with the necessary chart. Because
there is now a computer program available for carrying out the
required calculations, practical guidance, based on experience on
steam purging at many stations, is also included.
1B-2 During steam blowing, there is an increased risk of water carryover
because the pressure drop which occurs is higher than during
normal operation. To minimize the risk of stress corrosion, sodium
hydroxide must not be added to the boiler water during steam
blowing. The boiler is initially filled with 50 mg/kg hydrazine and
50 mg/kg ammonia. No further additions of hydrazine are required,
but 50 mg/kg hydrazine and 50 mg/kg ammonia should be added to
the make-up water to the boiler to react with dissolved oxygen.
Before commencing the steam blowing process, it must be proved
that all cleaning chemicals have been thoroughly flushed from the
boiler water circuit. The boiler water should not contain more than
0.1 mg/kg chloride (as Cl−) or 0.2 mg/kg sodium (as Na+).
2.4.1.3 In the on-load method, the pH of the cooling water entering the
condenser is decreased by acid dosage to about 2–2.5. The buffering
capacity of the cooling water, together with the large volume of the
system restrict the change of pH elsewhere in the circuit.
2.4.2 Choice of Acid
While in principle any of a large number of acids may be used to
remove the scales found in condensers, hydrochloric and sulfuric acids
are recommended because in addition to being inexpensive and readily
available, they were used satisfactorily in investigational studies of this
subject. Of these two, hydrochloric acid is recommended only when the
whole condenser is isolated, (i.e., in an off-load cleaning). Where there
is any possibility of contamination of the feed water by the cleaning
solution, as in reduced-load or on-load methods, then only sulfuric acid
is to be used. For SS tubes, sulphamic acid, although costly, is also
being used.
2.4.3 Inhibition
2.4.3.1 The three basic methods of cleaning impose quite different requirements
for inhibition and these are influenced by the materials of construction
of the plant and by the estimated long-term frequency of cleaning. By
the use of inhibitors, acceptable conditions can be achieved in respect of
the corrosion of water boxes and tubes, as well as restraint of galvanic
attack and copper deposition and dezincification. The use of either
recommended inhibitors. Armohib 28 or Armohib 533 or equivalent
suppresses copper deposition in the water box and also counteracts
galvanic corrosion. Recommendations for inhibitor requirements are
given in Appendix 2D.
2.4.3.2 The degree of risk to condenser integrity is related to the frequency of
cleaning.
2.4.4 Selection of Cleaning Processes
To aid in the selection of a suitable cleaning process, logic is given in
Appendix 2E.
2.4.5 Practical Considerations
2.4.5.1 Terminal Points
Suitable terminal points can be made as branch connections, so that
rigging can be carried out on-load and subsequent flushing can take
place without delay.
2.4.5.2 Circuitry
Where appropriate, the water boxes should be connected in series into a
circuit containing a tank and pump, the water box vents being fitted
with temporary connections back to the chemical mixing tank.
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 173
2.5.3.3 Experience to date has shown that a solution containing Na4EDTA and
0.7 % oxalic acid has sufficient capacity to cope with most of the
condenser steam side deposits encountered. If oil is present, 10 % v/v
degreasant and 1 % v/v ethomeen S25 has been found to be adequate.
2.5.4 Exclusion of Oxygen
2.5.4.1 Corrosion inhibitors are unnecessary provided air (oxygen) is excluded
from the cleaning circuit.
2.5.5 Practical Considerations
Experience has shown the need for full consultation between cleaning
contractors, stations and if appropriate, specialist advice should be
sought prior to cleaning. Among the factors to be considered are:
2.5.5.1 Water Requirements
2.5.5.1.1 During the cleaning, there will be a requirement for large quantities of
high quality demineralized water for preparing solutions and rinsing.
Water containing a significant concentration of calcium must not be
used, as this would cause a precipitation of calcium oxalate and a
subsequent rise in solution pH.
2.5.5.1.2 Although the clean is carried out at ambient temperatures, if possible, a
supply of high quality hot water (e.g., blow-down) should be available
to facilitate more rapid dissolution of oxalic acid crystals when the
cleaning solution is being prepared.
2.5.5.2 Temporary Holding Tanks
Sufficient temporary holding tanks must be provided to hold the
pre-mixed solution prior to transferring it to the condenser, and to hold
the effluent when the cleaning is completed.
2.5.5.3 Mixing Procedure
2.5.5.3.1 Prior to mixing is necessary to prepare a concentrated (approx. 10 %
v/v) solution of oxalic acid and to add the surfactant to the degreasant.
To save process time, both these procedures may be carried out off site
by the cleaning contractor prior to the cleaning.
2.5.5.3.2 If the degreasant/surfactant mix is prepared on site, this mixture must be
continuously agitated prior to use to ensure complete dispersal of the
much denser surfactant.
2.5.5.3.3 Mixing shall be carried out in the following order:
1. Dilute Na4EDTA concentrate.
2. Carefully add, with further dilution, concentrated oxalic acid
solution.
176 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
The system is refilled with raw water and circulated at 4–5 kg/cm2
pump pressure and drained. Mass flushing is finally done with CW
pumps in service.
4.2.5 Fluoride
Determine using a fluoride ion selective electrode and an epoxy bodied
reference electrode.
4.2.6 Alkalinity
Take a 100-mL sample, add pH 4.5 indicator and titrate with 0.1 M nitric
acid.
g/kg NaOH = Titre × 0.4.
4.2.7 Sodium
Sodium may be measured flame photometrically. Instruments giving a
full scale deflection for 5 mg/kg or less of sodium will be satisfactory, and
should be operated in accordance with the manufacturer’s instruction.
4.2.8 Total Iron in Citric Acid, Hydrochloric Acid, or Hydrofluoric Acid
4.2.8.1 Dilute the sample to give a final iron concentration in the range
0–60 mg/kg (3 % citric acid saturated with iron will have an approximate
iron concentration of 8500 mg/kg). For most analysis, a hundred-fold
dilution will be adequate. With hydrofluoric acid, dilute with 2 % boric
acid to protect glassware.
4.2.8.2 Determine the total iron by atomic absorption directly on the diluted
sample or take 50 mL of the diluted sample, add 0.5 thioglycollic acid
and 5 mL excess of 0.880 ammonia. Make up to 100 mL. Measure the
colour using a 10 mm cuvette and a 605 filter. Read off the total iron
concentration from a calibration graph prepared under identical
conditions
Total iron and total copper may also be determined by titration method.
For iron 5 mL of filtered sample and dilute with 25 mL of DM water.
Add 2 % KMnO4 solution dropwise till permanent pink colour appears.
Add 15 % hydrazine sulphate solution dropwise till pink colour
disappears. Add 2 drops in excess. Add 5 g of KI crystals and stopper
the flask. Allow to stand for 5 min. Titrate the liberated iodine with 0.1 N
sodium thiosulphate solution using starch indicator.
The method for copper determination is same as for iron except that
before the addition of KI crystals 5 g of ammonium bifluoride is to be
added and mixed well.
4.2.9 Ferric Iron in Citric Acid or Hydrochloric Acid
4.2.9.1 Take 25 mL sample and adjust the pH to 2.5 with approximately normal
Na2C03 solution
4.2.9.2 Dilute the solution to 100 mL and add five drops of 5 % sulphosalicylic
acid solution. Titrate with 0.1 M EDTA until the pink colour just
188 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
disappears. Add a further five drops of indicator and continue the titration
until the pink color disappears
g/kg Fe 3+ = Titre × 223.
4.2.10 Nickel
Place 2 mL of the sample in a separating funnel, add four drops of 10 %
hydrogen peroxide solution, and two drops of phenolphthalein solution.
Then, add 5 mL of 10 % sodium potassium tartrate and mix the contents.
Add 2.5 N sodium hydroxide solution drop-wise until the phenolph-
thalein just turns pink and then add 0.1 N hydrochloric acid drop-wise
until the colour is just discharged. Add 5 mL of 0.15 %
furil-alpha-dioxime followed by 25 mL of 2 N ammonia solution. Swirl
the contents of the flask to mix, and add 15 mL of the chloroform through
a filter paper and measure the absorbance in a suitable size cuvette.
Determine the nickel content from a calibration curve.
4.3 Methods of Analysis to be Used During the Post-operational Cleaning
of Condensers
The iron, copper, zinc, and nickel content of samples of the chemical
cleaning liquor can be determined by atomic absorption
spectrophotometry/suitable equipment available at site using standard
instrument operating conditions.
4.3.1 Instrument Calibration
4.3.1.1 Prepare separate series of calibration standards by appropriate dilution of
1000 mg/kg stock containing:
(i) Iron: 0, 10, 20, 30, 40 and 50 mg/kg Fe
(ii) Copper: 0, 5, 10, 20, 30 and 40 mg/kg Cu
(iii) Zinc: 0, 0.5, 1, 2, 3 and 4 mg/kg Zn
(iv) Nickel: 0, 2, 4, 6, 8 and 10 mg/kg Ni
in 2 % v/v ‘AR’ nitric acid
4.3.1.2 Measure the absorbance of each standard, using the manufacturer’s
recommended instrument conditions, at the following wave lengths:
(i) Fe: 372.0 nm
(ii) Cu: 217.9 nm
(iii) Zn: 213.9 nm
(iv) Ni: 232.0 nm
and construct calibration curves for reference purposes.
4.3.1.3 When used in conjunction with the following analytical procedure, the
above concentrations will correspond to 0–2500 mg/kg Fe; 0–2000 mg/kg
Cu; 0–200 mg/kg Zn, and 0–500 mg/kg Ni in the original cleaning liquor.
Two procedures are available, one for determining total metal removed in
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 189
a clean and the other for following the progress during the chemical
cleaning operation
4.3.2 Determination of the Total Amount of Iron, Copper, Zinc, and Nickel
Removal in a Cleaning
Mix the final cleaning liquor sample well. Transfer 5 mL of the sample to
clean dry 50 mL conical flask. Add 5 mL concentrated nitric acid (AR).
Heat to boiling on a moderate hot plate and gently reflux for 15 min with
occasional swirling of the flask. Allow to cool and add approximately
30 mL deionized water. Warm the solution on a hot plate and transfer the
contents of the flask quantitatively to a clean 250 mL graduated flask.
Dilute to the mark with deionized water and mix the solution well.
Determine the Fe, Cu, Zn, and Ni content solution by atomic absorption
spectrophotometry using the instrument operating conditions and cali-
bration procedure previously described.
4.3.3 Rapid Method for Following the Progress of the Chemical Cleaning
Operation
Transfer 5 mL of the chemical cleaning liquor (free from suspended
matter) to a clean 250 mL graduated flask. Add 5 mL ‘AR’ concentrated
nitric acid, dilute to the mark with deionized water and mix well.
Determine the Fe, Cu, Zn, and Ni content of the sample by atomic
absorption using the instrument conditions and calibration procedure
described above.
(continued)
Determinant Solution Method
Armohib 28 Acid cleaning Colorimetric
Bromate/copper Alkali cleaning Titration
Nitrite Copper stripping Colorimetric
Nitrite Flushing Colorimetric
Copper Alkali cleaning Colorimetric
Trisodium phosphate Alkali boil-out Titration
Phosphate Cleaning Colorimetric
Phosphate Alkali boil-out Colorimetric
Hydrazine Water Colorimetric
consult with the medical service (normally the Nursing Officer) with
respect to first-aid facilities. Supervision of the required safety precau-
tions by the Station Chemist shall also include supervising the chemical
cleaning contractor’s employees and any failure to comply with the safety
requirements shall be notified immediately to the Project Site Manager or
Location Manager as appropriate. The Supervising Officer or his deputy
shall be present at the scene of operation whenever chemicals are being
received or are in the cleaning system or during subsequent inspection
5.2.1.2 The Station Chemist shall ensure that chemicals are introduced in the
correct manner to the cleaning circuit and that the ventilation and
temperature requirements before entry into the plant for inspection or
working have been complied with (see 5.2.6)
5.2.2 General Philosophy
5.2.2.1 The manual handling of chemicals should be avoided as far as practicable
and wherever possible, mechanical methods should be used for
transporting, dispensing, and transferring chemicals
5.2.2.2 Protective clothing for skin and eye protection must be worn and if not
adequately ventilated, breathing apparatus must be worn when:
(i) Mixing chemicals
(ii) Dealing with leaks, spillages, splashes and
accumulated vapors
(iii) Approaching the plant
(iv) Post-cleaning inspection is carried out
5.2.3 General Precautions and Personal Hygiene
Wherever and whenever there is danger of contact with chemicals, all
personnel must:
(i) Be warned of the nature of the potential hazards and the necessary
precautions and be instructed in the correct use of protective
clothing and equipment by the Supervising Officer
(ii) Observe a high standard of personal hygiene avoiding contact with
chemicals, their vapors or contaminated residues
(iii) Not eat, drink, or smoke
(iv) Avoid wiping nose, eyes or face other than with clean paper tissues
(v) Place all debris and chemical residues removed from the plant in
clearly labeled polythene bags for subsequent disposal
(vi) On leaving the plant, remove their protective clothing for cleaning
before re-use, and clean themselves and their equipment, using
disposable materials
(vii) Wash thoroughly as soon as possible after leaving the operational
area (see 5.2.8)
192 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
5.2.5.3 Whilst chemical cleaning operations are in progress, venting of the boiler,
including the vent from the constant head overflow, must be to the outside
of the building, inaccessible to personnel and well away from other vents
or intakes to avoid the possibility of vapor reentering the building
5.2.6 Approach to the Plant (Excluding Bodily Entry) After any Stage of
the Cleaning Process
5.2.6.1 When the plant is to be opened up after the passivation stage or after any
acid stage during the process, the precautions given in 5.2.6.2–5.2.6.6
shall be observed
5.2.6.2 The chemical cleaning circuits must be drained to the approved disposal
point taking care to minimize spillage, splashing of solutions or
accumulation of vapor. If chemicals are drained into a holding vessel,
care must be taken that mixing of chemicals from different stages does not
occur in the vessel. It is particularly important to avoid acidifying
solutions containing nitrite or bromate, or mixing strong acids and alkalis
or strong oxidizing and reducing agents
5.2.6.3 Vapors issuing from plant openings should be dispersed by blowing clean
air through the access point using the best possible ventilation to obtain a
high dilution rapidly. The breaking open of access points should be
carried out by personnel wearing an approved type of overall and gloves
and breathing apparatus incorporating a hood to give a full protection to
the head. Suitable equipment is given in Appendix 5B. Contact with
surfaces which are or have been wetted by chemicals should be avoided
as far as is reasonably practicable
5.2.6.4 Components which are contaminated with chemicals should be placed on
impervious sheets for cleaning prior to replacement
5.2.6.5 Personnel should not expose themselves to risk by making a quick
observation of the plant interior (without bodily entry) when the access
points are first opened
5.2.7 Entry of Personnel into Plant That has been Chemically Cleaned
5.2.7.1 The precautions given in 5.2.7.2–5.2.7.5 are necessary if entry is to be
made into the plant after any acid cleaning or passivation stage in the
process
5.2.7.2 Entry to the plant shall be restricted to the minimum number of people
necessary. During the time that personnel are inside the plant, a stand-by
man must be positioned at the point of entry
5.2.7.3 Before entering the plant after chemical cleaning, either after the
passivation stage at the end of the process, or after any acid stage during
the process, or to carry out reinstatement work such as the removal of
flow restrictors, there must be an absolute minimum delay of 3 h after
194 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
opening all entry points, unless full protective clothing is worn and an
air-line breathing apparatus is used. During this period, ventilation of the
plant should be carried out at a rate of at least ten air changes/h using a
filtered air supply. It is essential that this 3-h delay period is observed,
even if a higher ventilation rate is adopted. Ventilation of the plant at a
rate of at least 10 air changes per hour should be continued while
personnel are in the plant for inspection or to carry out reinstatement work
such as removal of flow restrictors
5.2.7.4 Additionally before personnel enter plant, the temperature should be
ambient temperature. If the conditions above in 5.2.2 and 5.2.5 have been
fully complied with personnel can enter the plant wearing coveralls,
gloves, and carefully fitted eye-goggles as detailed in Appendix 5B.
Where such conditions have not been fully complied with, personnel
entering the plant must wear overalls, PVC gloves, rubber boots, a
breathing apparatus, and hood attachment giving full protection to the
head as detailed in Appendix 5B
5.2.7.5 Removal of debris or chemical residues from the plant must be carried out
by personnel wearing full protective equipment and in such a manner as
to avoid contamination of external surfaces. The residues should be
extracted into impervious containers which are then passed to persons
wearing gloves and goggles, as detailed in Appendix 5B
5.2.8 Exit of Personnel and Materials from Plant Containing Hazardous
Residues After Chemical Cleaning
5.2.8.1 The personnel collecting debris and chemical residues must place them in
clearly labeled polythene bags within the plant
5.2.8.2 For disposal, debris and chemical residues must be washed into a system
where considerable dilution can be achieved. Equipment used for
handling chemicals and the inhibitor must also be cleaned after use by
washing into a disposal system where considerable dilution can be
achieved (see 5.2.9)
5.2.8.3 The same personal clothing should be used until the end of the work
period on which a particular operator is engaged and then thoroughly
cleaned. Upon leaving the plant, the operator should remove the
protective clothing for subsequent cleaning before re-use and proceed
directly to the showers, paying particular attention to washing the hands
and face
5.2.9 Disposal of Chemical Waste
Disposal of all surplus solutions and chemical waste must be by an
approved route. The appropriate waste disposal and water authorities
should be consulted.
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 195
Notes:
1. Where Emergency Action is Required For Dealing With Spillage Or
Escape Of Chemicals, Maximum Ventilation and Water-Washing
Facilities Must Be Used
2. Personnel using self-contained and air-line breathing apparatus must
be properly trained and experienced in the use of such apparatus
3. The standard procedure outlined in documents with regard to the
removal of protective clothing must be strictly observed
4. Particular care must be exercised when opening drums of 0.880
ammonia solution, particularly where these have been in a warm
atmosphere, because the contents are likely to be under pressure
5.3 Boilers, Super Heaters, Reheaters, and Feed Systems
Where there is a choice, preference should be given in using inhibitors
having a lower perceived risk.
5.3.1 In addition to the safety considerations given for all items of plant, the
following specific provisions apply to the chemical cleaning of boilers,
super heaters, reheaters, and feed systems
5.3.2 The substituted thio-ureas present in some inhibitors specified in
Appendix IF can lead to the formation of carbodiimides, which cause
temporary blindness and sensitivity to light. To minimize the risk of eye
toxicity, it is essential to adhere to the recommendations in Sect. 5.2, ‘All
Items of Plant’, particularly regarding the addition of the inhibitor to the
cleaning solution (5.2.5) and approach and entry into the plant (5.2.6 and
5.2.7). The recommendations on supervision (5.2.1) handling, storage,
and disposal of chemicals (5.2.2, 5.2.4, 5.2.5 and 5.2.9) must be strictly
observed
5.4 Condensers
5.4.1 Cooling Water Side
5.4.1.1 The provisions given in Sect. 5.2 also apply to the chemical cleaning of
the CW of the condensers
5.4.1.2 While it is believed that eye toxicity due to carbodiimide is not possible
with the inhibitors currently specified for condensers in Appendices 2D
and 2E, it is nevertheless essential to flush out all traces of inhibitor using
the full flow of the main CW pumps for at least 3 h before entering the
plant. The precautions during cleaning (5.2.5) and the approach and entry
into the plant (5.2.6 and 5.2.7) must be strictly applied
196 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
5.4.1.3 The health precautions stated in the IS Safety Code of Practice on the
maintenance of cooling water and other auxiliary water must be followed
to minimize the risk of infection from Legionella
5.4.2 Steam Side
Inhibitors are not used in current practice for cleaning the steam side of
condensers, therefore, no special precautions are required in this respect.
5.4.2.2 However, large volumes of acid cleaning liquids and solvents are used
and the provisions given for supervision (5.2.1). Handling storage and
disposal of chemicals (5.2.2, 5.2.4 and 5.2.9) must be applied. Some
solvents are flammable and/or toxic, and precautions must be taken to
ensure that no explosion hazard or toxicity risk can arise. Ventilation
equipment should be selected and positioned taking into account risks to
personnel and explosion risks in accordance with ‘National Power Safety
Rules Code of Practice in Confined Spaces’
5.5 Feed Heaters
The provisions given for supervision (5.2.1); the addition of inhibitors to
the cleaning solutions (5.2.5); approach and entry into the plant (5.2.6 and
5.2.7), and the handling, storage, and disposal of chemicals (5.2.2, 5.2.4
and 5.2.9) must be strictly observed. Solvents are also used and
precautions must be taken to ensure that no explosion hazard can arise
and that the plant is suitably ventilated to prevent risks to personnel (see
5.4.2.2).
(continued)
Chemicals OEL (note 1) Main hazards Special storage
requirements
Citric acid Powder and solution can cause eye Store away from
injury oxidizing agent
Chromic acid 0.05 mg/m3 Can cause severe burns Store away from
(as Cr) Can cause violent oxidizing agents and
explosion in contact with reducing any fire risk
agents
Dipotassium hydrogen Produces toxic, irritant fumes when
phosphate heated
Disodium hydrogen Produces toxic, irritant fumes when
phosphate heated
Ethomean S25 – Skin and eye irritant (See Supplier's
data sheet)
Formic acid 5 ppm Corrosive. Can cause severe burns Store in a
well-ventilated area
Inhibitors (Armohib 28, Can cause skin and eye irritation –
Hibron armohib 533, (some severe). Some combus-
Stannine LTP, Dodigen Tible/toxic/corrosive
95, etc.) Rodine, Lith
solvent, coronil. etc.
Hydrazine 0.1 ppm Strongly caustic. Irritant Store separately. See
May cause damage to liver and national safety code of
kidneys practice GS-C1 0.15
Hydrochloric acid 5 ppm Corrosive and irritant. Store in a
well-ventilated area
Hydrogen peroxide 1 ppm Oxidizing and corrosive Store separately, and
Can cause severe damage to eyes away from all
and skin combustible materials in
May explode in contact with dust a cool area
Hydrofluoric acid 3 ppm Toxic and corrosive. Can cause Store in a
severe burns well-ventilated area
Nitric acid 2 ppm Oxidizing and corrosive can cause Store away from acetic
severe burns acid, ammonia and
combustible materials
Oxalic acid 1 mg/m3 Corrosive. Avoid breathing dust or Store away from
vapor oxidizing agents
Potassium hydroxide 2 mg/m3 Highly corrosive. Irritant. Inhalation Severe store away from
(caustic potash) (Note 2) of dust or mist causes intense acids
irritation
Potassium or sodium – Eye/skin irritant, with acid solutions Store away from acids
dichromate toxic gases can be produced and combustible
materials
Possible explosion hazard on contact
with organic materials
(continued)
198 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
(continued)
Chemicals OEL (note 1) Main hazards Special storage
requirements
Potassium or sodium – Oxidizing agent. Eye/skin irritant. Store away from acids,
bromate With acid solutions toxic gases are combustible materials
produced and ammonia
Possible explosion hazard with
ammonia and contact with organic
materials
Potassium or sodium – Eye/skin irritant. With acid solutions Store away from acids
chromate toxic gases can be produced. and combustible
Possible explosion hazard on contact materials
with organic materials
Potassium or sodium Eye skin irritant with acid solutions Store away from acids
nitrite nitrons fumes are produced. Possible and combustible
explosion hazard on contact with materials
organic materials
Sodium carbonate (soda Skin irritant. Dust or mist, irritating Store away from acids
ash) to upper respiratory tract
Sodium fluoride 2.5 mg/m3 If heated or in contact with acids, Store away from acids
(as F) emits highly toxic fumes and combustible
materials
Sodium hydroxide 2 mg/m3 Highly corrosive. (note 2) irritant. Severe store away from
(caustic soda) Dust acids
or mist can cause irritation to upper
respiratory tract
Sulphamic acid – Emits toxic fumes when heated. Store away from heat
Irritant
Sulphuric acid 1 mg/m3 Extremely irritant and corrosive. Store away from alkalis
Cause severe burns
Tetra sodium ethylene – Concentrated solution is caustic. Store away from acids
diamine tetra Skin
acetate and eye irritant
Tripotassium phosphate – Skin irritant. If heated highly toxic –
fumes
Trisodium phosphate – Skin irritant. If heated emits highly –
toxic fumes.
Wetting agents – May cause eye and skin irritation –
(Dissapol, Teepol, etc.)
Notes
1. OEL—Occupational Exposure Limit (8-h TWA value)
2. Confirm by reference to the most recent HSE Guidance Note eH 4016
Appendix A: The Operational and Safety Aspects of Chemical Cleaning … 199
(continued)
Conditions Protective equipment
5B-3 (i) For entry into plant after chemical a. Compressed air-line breathing apparatus
cleaning in which the requirements for b. One-piece cotton/polyester overall with
inhibitor additions and ventilation and hood or one-piece disposable PE-coated
temperature have been fully complied with tyrek
c. PVC gloves
d. Rubber boots (molded)
(ii) When breaking open access points a. Compressed air-line breathing apparatus
after chemical cleaning (if entry also required).
b. Open-circuit self contained breathing
apparatus (if entry not required)
c. One-piece cotton/polyester overall with
hood or one-piece disposable Tyrek
d. PVC gloves
e. Rubber boots (molded)
(iii) Where contact with vapor and As per 5B.3 (ii)
merging from drains or vents during a
chemical process is unavoidable
(iv) Where severe spillage or escape of the a. Open-circuit self-contained breathing
following chemicals has taken place: apparatus
Sodium bromate, Nitrous fumes, b. Compressed air-line breathing
Stannine LTP and Armohib 28
c. PVC gloves
d. Rubber boots (molded)
e. One-piece cotton/Polyester coverall
with hood or one-piece disposable overall
in PE-coated tyrek (alternatively, PVC
chemical splash suit)
5D-2.3.3 Place the test vessel in a constant temperature bath and allow it to
equilibrate to the test temperature.
5D-2.3.4 Weigh the coupon to the nearest tenth of a milligram. The coupon
should not be added to the test vessel containing the solution until
the solution reaches the test temperature. Totally immerse the
coupon in the test solution. Any supports or hangers used should
be electrically nonconductive material.
5D-2.3.5 The duration of test should be 6 h.
5D-2.3.6 Duplicate tests must be performed to confirm results and to
minimize the possibility of random errors. Duplicate tests should
be conducted separately so that any errors made in one test will not
be repeated in duplicate.
5D-2.3.7 After completion of the test, rinse the coupons in DM water and
then rinse them with acetone or methanol to remove the inhibitor
film. Scrub the test coupons using a nylon brush and soap solution.
Rinse with DM water and follow with an acetone or alcohol rinse
to replace the water and dried in oven at a temperature of about
105 °C for about 15 min. Store the coupons in a desiccator for a
minimum period of 1 h prior to re-weighing.
5D-2.3.8 Calculation of Corrosion Rate
After cleaning, the coupon should be re-weighed to the nearest
tenth of a milligram. The corrosion rate, as on average penetration,
based on weight loss should then be calculated in the units of
mg/cm2/h.
5D-2.3.9 Criteria for Acceptance
The weight loss should not be more than 0.1 mg/cm2/hr at 65 °C
for carbon steel and mild steel sample.
5D-3 Field Test Method
A small ball of steel wool (about 0.1 gm) is degreased with
acetone and added to a sample of inhibited acid solution in the acid
tank solution during cleaning process.
5D-3.1 Criteria
Inhibitor efficiency is judged to be adequate if the wire wool ball
does not float after 1 min in ammoniated citric acid or after 2 min
in hydrochloric acid.
204 Appendix A: The Operational and Safety Aspects of Chemical Cleaning …
5D-4 Notes:
1. The expiration date of the inhibitor is to be checked before
starting use.
2. In the event that the test fails, the test is to be conducted at a
higher concentration so as to conclude at what concentration
the efficiency is acceptable and accordingly concentration of
inhibitor in acid cleaning procedure is to be adopted.
Appendix B
Fire Protection of Power Stations
1.0 Introduction
Plant is exposed to onerous operating conditions and the combinations of
flammable material in large quantities and ignition sources which can lead to
the incidence of fires. This Guidance Note applies the principles and gives
specific recommendations to achieve a satisfactory level of protection,
methods to prevent fires, and routine checks/maintenance jobs for operational
station at risk from fire.
2.0 Any previous Guidelines
Nil
3.0 Scope
This Guidance Note is specifically geared at fixed fire detection and
protection systems. The provision and use of portable equipment, such as
hose pipes/reels and extinguishers by a fire fighting team is covered by the
TAC/CISF Fire Manual.
Recommendations are made for prevention/detection/protection against fire,
for inspection, for testing and maintenance, and for operational needs
pertaining to the fire detection and protection equipment.
4.0 Fire Hazards and Prevention
The various hazards in a power station and the methods to prevent these are
given in the following table.
(continued)
S. No. Area Fire hazard Fire prevention
4.4 Coal bunkers 1. Feeding of hot coal from 1. Residual, compacted coal should
stockyard, which may be about be avoided in bunkers and bunkers
to burn should be emptied and cleaned
2. Residual coal sticking to thoroughly during overhaul of unit
bunker walls for a long periods 2. Bunker gates to be maintained to
resulting in self-ignition ensure that they close properly
3. Any draught of air through when bunker is not in use
the coal in bunkers, particularly 3. Hot coal should not be fed into
compressed air from air blast the bunkers from stockyard
equipment 4. System of hot work permit to be
4. Low bunker level coupled followed during welding/cutting job
with unsatisfactory isolation in bunker floor
from feeder/mill with 5. Availability of bunker level
subsequent pressurization of indication along with annunciation
furnace causing hot gases to for low bunker level to be ensured
pass through the bunker
5. Bunker conveyor fires
4.5 Coal feeders 1. Hot or burning coal passing 1. Routine cleaning of feeder from
from coal bunkers inside to reduce extent of residual
2. Fires in mills particularly coal left compacted in dead spaces
during start-up or shut-down within the feeder
periods 2. Bunker gates and mill dampers to
3. Friction due to mechanical be maintained to prevent passage of
failure combustion products from fires into
4. Welding/gas cutting etc. the feeders or elsewhere in the
5. Residual coal in pockets of system
feeder 3. The system of hot work permit to
be strictly followed during
welding/gas cutting jobs
4. Periodic checking of feeder
protection on “No coal on belt” to
be ensured
4.6 Coal mills and P. 1. High mill outlet temperature 1. Appropriate fire detection system
F. piping due to coal flow interruption to be maintained in both running
2. Low level of coal in ball and standby mills
mills 2. Instrumentation of
measuring/maintaining level of coal
in ball mills and of measuring
sound level to be maintained
3. Proper start-up and shut-down
procedures to be maintained
4. Mill inerting system to always be
kept in service
5. Auto closing of HAG from mill
outlet temperature high protection
is to be kept in service
(continued)
208 Appendix B: Fire Protection of Power Stations
(continued)
S. No. Area Fire hazard Fire prevention
4.7 Boiler burner 1. Ignition of preheated fuel oil 1. Steam pipes for oil atomization
fronts on hot boiler casing/steam pipes are to be thoroughly insulated
2. Rupture of flexible hoses 2. Prompt attention to defects on
3. Leakage of PF pipes burner connecting hoses and pipe
4. Faulty ignitors coupled with work
leaking oil 3. No spillage of oil around burner
area during removal of burner
carrier for tip cleaning. In case of
oil leakage, soaked insulation to be
removed and re-insulation to be
completed
4. Minimum electrical
equipment/cables/junction boxes
near burners to be located
5. Ignitor faults to be immediately
attended
6. Oil waste, rag, and combustible
materials should not to be allowed
to accumulate
7. Periodic checking of igniter
effectiveness to be done
4.8 Fuel oil storage 1. Greater risk during venting, 1. Precautions to be taken during
tanks gassing, and filling operations tank emptying, cleaning, tank
of light fuel oil inspections, vent inspections, and
2. Leakage of tank other maintenance work (including
3. Dry grass around tanks electrical/lighting work).
4. Oil spillage Welding/cutting to be avoided. If
5. Unclean surroundings carried out, all precautions must be
6. Soaked insulation taken
7. Electrical tracing 2. Entry to bunded area to be
restricted to authorized persons
only
3. Filling lines to be purged and
road tanker connections should be
kept secure when not in use
4. Recycled oil to be cooled to
below the flash point before
returning to storage tanks
5. Excess temperature safety
systems and alarms to be installed
on heater banks
6. All areas within the bund walls
must be free of vegetation and other
combustible materials
(continued)
Appendix B: Fire Protection of Power Stations 209
(continued)
S. No. Area Fire hazard Fire prevention
4.9 Fuel Oil unloading 1. Oil spillage or leakage due to 1. There should be adequate
and transfer pump failure of joints or of venting ventilation in the enclosed pump
house due to overheating or house to keep the concentration of
restrictions in system oil vapors within safe levels
2. Heaters 2. Proper smoke vents and
3. Loosely laid electrical adjustable louvers at high and low
cables/welding cables level
4. Drain oil stagnant in 3. Proper earthing of all electrical
unloading pipe trenches and systems
surface drains 4. Use of flame proof
lighting/electrical appliances only
in the pump house
5. Trenches to be filled with sand
and PCC on top to prevent
contamination with oil
6. Oil waste, rag, other combustible
materials not to be allowed to
accumulate
7. No spillage of oil
8. Prompt attention to defects on oil
pipes and heaters etc.
9. If used, oil absorbing granules
should be removed immediately
after use. Wood dust not to be used
as it is an oil-absorbing medium
4.10 Naphtha tanks and 1. Leak in the system, whether 1. Gas leak detection system to be
piping from bulk storage, the kept operational
distribution network, control 2. Entry to storage areas should be
valves, or naphtha pipelines at restricted to authorized persons
combustion chambers only
2. Venting or leaking Naphtha 3. Areas around tanks to be kept
gas getting ignition due to free of vegetation and any other
discharge of static electricity combustible materials
during tank filling 4. Earthing of tanks, other
equipment to be checked regularly
5. Filling lines to be purged and
road tanker connections to be kept
secure when not in use
6. Prompt attention to leakage
defects
4.11 Regenerative Air 1. Carry over of unburnt liquid 1. Frequent inspection and water
Heaters fuel onto the internal heat washing of air heater
exchanger surfaces during cold 2. Soot blowing of air heaters
start-up specially during start-up
2. Slow build-up of deposits of immediately after bringing boiler
unburnt fuel in the absence of into service and cleaning regularly
soot blowing for a period of at least once per shift at a minimum
time 3. Oil to be burnt with maximum
attainable efficiency in the furnace
by appropriate cleaning and
adjustment of burners to minimize
the quantity of unburnt particles,
elimination of tramp air, and
consequent chilling of the flame and
(continued)
210 Appendix B: Fire Protection of Power Stations
(continued)
S. No. Area Fire hazard Fire prevention
by ensuring that combustion
chambers are gas tight
4. Air heaters can be put under
observation during light up with the
help of digital camera
5. Regular cleaning, maintenance
and testing of oil burners
6. Thermo-couple type fire
detection system which has been
found to be more reliable to be kept
in service for monitoring air heater
temperatures
7. Infra-red fire detection system,
wherever provided, also to be
maintained for prompt hot spot
detection
8. Burner flushing and testing for
their sprayer leakage and
atomization to be done
4.12 Turbine-generator 1. Minor leakage of lubricating 1. Oil leaks, if any, should be
and control fluids into collected nearest to the leak
inaccessible areas, lagging, 2. Prompt attention to oil leakages
drain trenches and coming in 3. Good housekeeping.
contact with hot surfaces Accumulation of rubbish should be
2. Heavy oil leakage in the form avoided
of spray onto bare hot metal 4. Dispensing point of flammable
caused by bursting of liquid to be kept away from turbine
pipe/flange hall
3. Leakage of hydrogen to 5. Seepage of oil into insulation
atmosphere should be avoided
4. Leakage of hydrogen into 6. Any increase in consumption of
bus duct coupled with choking hydrogen to be thoroughly
of vents of bus duct investigated and rectified
5. Cables laid near hot 7. Adequate ventilation of TG hall
equipment 8. Any welding/gas cutting work to
6. Looseness of current carrying be done only after issue of hot work
bolts, carbon brushes permit
9. Steam pipes to be thoroughly
insulated
10. In case of oil leakage, soaked
insulation to be removed and
re-insulation to be done
4.13 Mineral oil filled 1. Electrical faults inside the 1. Oil leakages to be promptly
transformers transformers including tap attended to
changer failures 2. Vegetation, rags, etc. should not
2. Oil leakage from be allowed around transformer
transformers 3. Routine checking of cooling fans
3. Bushing failure and pumps, operational parameters
4. Rupture of transformer tank 4. Soaking pit to be inspected
body caused by internal faults regularly and cleared as necessary
so as to avoid saturation
5. DGA (dissolved gas analysis) to
be done regularly for transformers,
(continued)
Appendix B: Fire Protection of Power Stations 211
(continued)
S. No. Area Fire hazard Fire prevention
and any defect indicated should be
attended to as early as practicable
6. Condition monitoring of
transformers by thermo-vision
cameras, acoustics methods should
be done
4.14 Cable 1. Overheating of cables/cable 1. Cable galleries/vaults to be kept
(a) galleries/vaults joints up to temperature clean and free of all extraneous
conditions high enough to bring combustible materials and not to be
the plasticizers of PVC used as storage and office areas
compound into a volatile state Regular inspection of cable
2. Short-circuit creating galleries
sufficient heat 2. Access to cable galleries to be
3. Accumulation of coal dust, restricted
flammable debris, cardboard 3. Proper ventilation to be provided.
packages, fuel and lubricating 4. All cable entry points to cable
oils gallery to be fire sealed
4. Welding/cutting inside cable 5. Fire barrier walls to be provided
gallery between cable tunnels of units and
5. Heating during installation of fire doors to be kept closed
heat-shrinkable cable joints 6. Loosely laid wires to be avoided
7. Lighting fittings, lighting wires to
be inspected regularly
8. No welding work to be done in
cable galleries
9. Any leakage of fuel/lubricating
oil into cable gallery to be
immediately attended
10. Ingress of coal dust from boiler
side must be avoided
11. Any overheated joint should be
repaired at the earliest
12. Proper illumination in the cable
gallery to be maintained
4.14 Cables in trays in 1. Accumulation of coal dust, 1. Cable trays to be covered with
(b) boiler area flammable debris, cardboard aluminum sheet from top
packages, fuel, and lubricating 2. Cable trays to be regularly
oils inspected and cleaned
2. Welding/cutting inside cable 3. Loosely laid wires to be avoided
gallery 4. Care to be taken during gas
3. Hot flue gas/ash from boiler cutting/welding near/above cable
furnace during furnace trays
pressurization 5. Any leakage of fuel
4. Heat radiation/high oil/lubricating oil on cables to be
temperature due to vicinity of immediately attended
furnace, p.c. pipes, hot air ducts
(continued)
212 Appendix B: Fire Protection of Power Stations
(continued)
S. No. Area Fire hazard Fire prevention
4.14 Cables in trays 1. Accumulation of coal dust, 1. Cable trays to be covered with
(c) near bottom ash flammable debris, cardboard aluminum sheet from top
hoppers packages, fuel, and lubricating 2. Cable trays to be regularly
oils inspected and cleaned
2. Welding/cutting inside cable 3. Loosely laid wires to be avoided
gallery 4. Care to be taken during gas
3. Hot flue gas/ash from boiler cutting/welding near/above cable
furnace during furnace trays
pressurization 5. Any leakage of fuel
4. Heat radiation/high oil/lubricating oil on cables to be
temperature due to vicinity of immediately attended
furnace, p.c. pipes, hot air ducts 6. Cables trays can be insulated
5. Hot bottom ash falling on with refractory material for limited
cables during abnormal lengths keeping in view derating
operation factors as per cable manufacturers
(Cables may have to be replaced by
higher size)
4.15 Switch-gears 1. Insulating oil of circuit 1. Switchgear rooms to be kept
breakers clean and free of flammable debris
2. PVC cables, epoxy resin 2. Regular inspection of switchgear
based and paxolin/melamine rooms to be done
insulating material, PVC 3. Switchgear rooms not to be used
wiring, solenoids, and plastic as storage areas or office space
encased relays 4. Proper maintenance of
switchgears and regular testing of
protection relays
5. Proper ventilation of switchgear
rooms
4.16 Gas turbines 1. Leakage of gas, Naphtha 1. Gas leak detectors to be kept in
from joints, covers etc. service always and to be regularly
2.Improper burning of liquid tested
fuel leading to its accumulation 2. Gas/liquid fuel leak should be
in the duct promptly given attention
3.Leakage of 3. Lubricating oil/jacking oil leak
lubricating/jacking oil should be attended at the earliest
possible time
4. No flammable materials should
be allowed to be stored in the
turbine hall
5. Liquid fuel should be fired to
maximum attainable efficiency
6. Good housekeeping.
Accumulation of rubbish to be
avoided
7. Dispensing point of flammable
liquid to be kept away from turbine
hall
8. Any welding/gas cutting work to
be done only after issue of hot work
permit
9. Seepage of oil into insulation to
be avoided
10. Adequate ventilation of TG hall
(continued)
Appendix B: Fire Protection of Power Stations 213
(continued)
S. No. Area Fire hazard Fire prevention
4.17 Diesel Generators 1. Leakage of fuel oil 1. Permanent natural ventilation
and Diesel 2. Lubricating oil getting should be provided in the diesel
Engines Driven overheated and leaked engine room at high and low levels
Fire Pumps 3. NRV of diesel return line to to disperse vapors and fumes
tank not working 2. Exhaust pipes should be suitably
insulated to prevent ignition of
flammable materials
3. Fuel, lubricating oil leakages
should be immediately attended to
4. Fuel tanks should preferably be
positioned outside the building
5. Instrumentation and controls of
diesel engine to be regularly
checked and maintained
6. Overloading should be avoided
7. NRV of diesel return line to tank
to be checked regularly
8. Engine oil sample to be tested
regularly
9. Battery and diesel tank should be
sufficiently apart
(continued)
SN Area Detection system Protection system Remarks
c. (i) Unit Turbine lube oil Quartzoid bulb type Automatic HVW
tanks, coolers, and heat detectors (with spray system and fire
purifiers hydraulic detection extinguishers
(ii) Turbine lube oil tank pipe network)
assembly in auxiliary
compartment of gas
turbines (design without
GT enclosure)
d. Central lube oil tanks - do - - do -
assembly and purifiers
e. Turbine lube oil pipes (in - do - (optional) Automatic HVW Feasibility to be
oil canal) spray system checked as per
(optional) layout for each
project
f. Lube oil system (tanks, - do - Automatic HVW
piping if any) of TD- spray system and fire
boiler feed pump extinguishers
g. Generator seal oil system - do - - do -
h. Cable galleries/cable vault (a) Linear heat (a) Automatic MVW (b) Not being
sensing cable type spray system and fire provided in new
heat detectors; extinguishers projects
ionization and (b) TES type water
photoelectric type spray system
smoke detectors
(b) - do - plus TES
type
sprinkler bulbs (for
local/auto spray)
i. Cable vault (above false Linear heat sensing Fire extinguishers; Indicator of the
roof and below false cable type heat automatic carbon photo-electric
flooring of unit control detectors; ionization dioxide gas and ionization
rooms) and photoelectric extinguishing system type smoke
type smoke detectors or automatic inert gas detectors to be
extinguishing system mounted at false
roof
j. Battery rooms (C&I and Electrical spot type Fire extinguishers
electrical) heat detector and
ionization type
smoke detectors
k. Steam turbine bearing (a) Quartzoid bulb (a) Manual HVW To be provided in
housing, turbine type heat detectors spray system and fire consultation with
enclosure (with hydraulic extinguishers manufacturer
detection pipe (optional)
network) (optional) (b) Automatic inert
(b) Flame detectors, gas extinguishing
gas detectors system
(continued)
Appendix B: Fire Protection of Power Stations 215
(continued)
SN Area Detection system Protection system Remarks
l. All MCC and Switchgear Ionization type Fire extinguishers
rooms (LT/HT) smoke detectors
m. UCB and its adjoining Ionization and photo Automatic Inert gas
office space, Control electric type smoke (‘INERGEN’ or
equipment rooms, UPS, detectors ‘ARGONITE’)
inverter rooms, extinguishing system;
marshalling cabinet area automatic inert
system
n. SWAS rooms – Fire extinguishers
o. Service building/facilities Smoke detection Sprinkler system, fire
building system extinguishers
p. Along the periphery – Hydrant system Hydrant valves
and individual
hose boxes/hose
reels
q. Stair cases – Hydrant system and Landing valves
fire extinguishers and individual
hose boxes
5.2 Main plant boiler/WH RB block
a. Electro-static-precipitator – Hydrant system, Landing valves
water monitors and individual
around ESPs and hose boxes, hose
WHRB reels
b. Gas turbine fuel syst. Quartzoid bulb type Automatic HVW
skids heat detectors (with spray system and fire
(gas/Naphtha/NGS/HSD) hydraulic detection extinguishers
for metering/filtering etc. pipe network)
c. Boiler burner front Quartzoid bulb type Automatic HVW
heat detectors (with spray system and fire
pneumatic detection extinguishers
pipe network) or
electrical spot type
detector
d. All control rooms, MCC Ionization type Fire extinguishers
and switchgear rooms smoke detectors
(ESP/VFD, ash handling
plant and other buildings)
e. Cable galleries (ESP and Linear heat sensing Automatic MVW
VFD building) cable type heat spray system and fire
detectors; ionization extinguishers
and photoelectric
type smoke detectors
f. Boiler staircases – Hydrant system, Landing valves
water monitors on and individual
either side of boilers hose boxes
and fire extinguishers
(continued)
216 Appendix B: Fire Protection of Power Stations
(continued)
SN Area Detection system Protection system Remarks
g. Coal Bunkers – Bunker inerting by
CO2/inert gas/steam
(optional)
h. Along the periphery – Hydrant system Hydrant valves
and individual
hose boxes
5.3 Transformer yard area
a. All transformers Quartzoid bulb type Automatic HVW Hydrant valves
heat detectors (with spray system hydrant and individual
hydraulic/pneumatic system and fire hose boxes
detection pipe extinguishers
network)
b. Along the periphery – Hydrant system Hydrant valves
and individual
hose boxes
c. DG set/black start DG Quartzoid bulb type Automatic MVW
area heat detectors (with spray system and fire
hydraulic detection extinguishers
pipe network)
d. All control rooms, MCC Ionization type Fire extinguishers
and switchgear rooms smoke detectors
(compressor house, DG
set area or any other local
MCC/switchgear rooms)
5.4 Coal handling plant
a. Coal Conveyors (a) - (a) Hydrants/monitors Hoses to be
(b) LHS cable type (b) (i) Sprinkler provided in
heats detectors and system central hose
infrared type heat (ii) Solenoid operated houses
detectors automatic MVW
(c) Linear heat spray system and
sensing cable type hydrant system
heat detectors, (c) Automatic MVW
quartzoid bulb type spray system and
heat detectors (with hydrant system
hydraulic/pneumatic
detection pipe
network) and
infra-red type heat
detectors
b. Transfer points and Quartzoid bulb type (a) Automatic MVW
crusher houses heat detectors spray/sprinkler
system and hydrant
system (landing
valves and/or water
monitors)
(b) Hydrants
(continued)
Appendix B: Fire Protection of Power Stations 217
(continued)
SN Area Detection system Protection system Remarks
c. Coal handling plant Ionization type (a) Fire extinguishers
control rooms, MCC and smoke detectors (b) Hydrants (outside)
switchgear rooms
d. Cable galleries in CHP Linear heat sensing (a) Automatic MVW
control/switchgear rooms cable type heat spray system and fire
(if any) detectors; ionization extinguishers
and photoelectric (b) Hydrants (outside)
type smoke detectors
e. Transformers of rating 10 Quartzoid bulb type Automatic HVW Hoses to be
MVA and above within heat detectors (with spray system and fire provided in
the plant premises hydraulic detector extinguishers hydrant central hose
pipe network) system houses
5.5 Fuel oil handling
a. Fuel oil tanks Linear heat sensing Foam injection
(NAPTHA/NGL/HSD) cable type heat system and
HFO/LDO detectors, quartzoid automatic/manual
bulb type (with MVW spray system
pneumatic detection (for uninsulated
pipe network) heat tanks)
detectors
b. Fuel oil dyke – Hydrant system Hoses to be
(hydrants and water provided in
monitors); central hose
foam water houses
hydrants/monitors
c. Fuel oil pump house ‘Quartzoid bulb’ (a) Automatic
equipment type heat detectors MVW/foam spray
(with hydraulic system
detector pipe (b) Fire extinguishers,
network) foam hydrants
d. Control rooms, Ionization type Fire extinguishers
MCC/switchgear rooms if smoke detectors
any
e. Transformers of rating Quartzoid bulb type Automatic HVW Hoses to be
10 MVA heat detectors (with spray system and fire provided in
hydraulic detector extinguishers hydrant central hose
pipe network) system houses
5.6 All Other off site area
a. All pump – Hydrant system Hoses to be
houses/permanent (hydrants and/or provided in
structure such as WTP, water monitors) fire central hose
PT Plant etc. (other than extinguishers houses
cooling towers)
(continued)
218 Appendix B: Fire Protection of Power Stations
(continued)
SN Area Detection system Protection system Remarks
b. Miscellaneous Ionization type Hydrant system
switchgear/MCC and smoke detectors (hydrants and/or
control rooms water monitors) and
fire extinguishers
c. Transformers of rating 10 Quartzoid bulb type Automatic HVW Hoses to be
MVA and above within heat detectors (With spray system, hydrant provided in
the plant premises hydraulic detector system and fire central hose
pipe network) extinguishers houses
d. Administration building – Hydrant system Hydrant valves
(periphery) and individual
hose boxes
e. Administration building – Hydrant system and Landing valves
(staircases) rire extinguishers and individual
hose boxes
f. Communication Ionization type Fire extinguishers
building/SATCOM smoke detectors
building if any switchgear
room, control/cubicle
room
g. Communication – Hydrant system Hydrant valves
building/SATCOM and individual
building (periphery) hose boxes
(continued)
Frequency Checks
Weekly 1. All hydrant valves and monitors to be examined systematically to ensure that
all valves and spring catches are maintained in good condition along with
hand-wheels, couplings, lugs, etc.
2. Inspect hydrants for any obstruction of approach to these due to vehicles, etc.
3. Open randomly selected valves one by one and observe flow of water for a
short time. Close the valves. The whole operation of valves should be smooth
and there should not be any leakage
4. Inspect all hose boxes to ensure that these contain the required number of
hoses, branch pipes, and nozzles
5. Open air release valves on the main pipes in order to expel trapped air
6. Inspect hose reel installations and ensure that their isolating valves are closed
7. Inspect isolating valves for valve position and for any leakage
8. Check valve pit for proper cleanliness and ensure that it is not flooded and is
in good repair, readily operable condition
Frequency Checks
9. Check level and specific gravity of electrolyte in the batteries of diesel
engines
10. Check that automatic start sequence of diesel engine-driven pump is
operative. Run each diesel engine for about 30 min under load (not less than
60 % operating load) until the time operating parameters such as exhaust
temperature, closed circuit water temperature, lubricating oil temperature,
lubricating oil pressure, etc. are stabilized. Check whether operating parameters
are within recommended range
Check exhaust pipes of each diesel engine for leakage, chokage, and
overheating when the pump is running
11. Check battery charger panels for proper functioning
12. Check fire pumps control-cum-annunciation panel for proper functioning
and alarm/annunciation
13. Check temperature of pump house
14. Check all auxiliary equipment such as battery charger, compressor, water
pumps, and diesel fuel level
15. Carry out flow test as detailed below:
(a) Select hydraulically most remote hydrant and place a pressure gauge
mounted on a blank cap adjacent to it
(b) Connect two or more hose pipes with nozzles each 30 m long at
hydraulically most remote hydrant and adjacent valves
(c) With a pump running at its maximum pressure, with other hydrant valves
closed, flow water through the hose reels with valves fully open. Note down
readings of pressure gauges mounted adjacent to hydraulically most remote
hydrant valve and in the pump house. The running pressure should be between
3.5–5 kg/cm2. This test should be repeated with different pump next week by
rotation. (Alternatively, the pressure gauge can be mounted at the hydraulically
most remote hydrant also instead of adjacent one). Test should be rotated for
different locations which are hydraulically far or are hazardous
16. Change over to other pumps as per ‘Change Over Schedule’
(continued)
220 Appendix B: Fire Protection of Power Stations
(continued)
Frequency Checks
Monthly 1. Clean strainers of spray pumps (in case of clarified fire water site may change
the frequency of cleaning the strainers)
2. Check that connectors of battery are clean and free from corrosion and
properly connected. Smear a little petroleum jelly on them and on the battery
terminals
3. Top up cells with distilled water, if required
4. Carry out monthly maintenance of diesel engine as per manufacturer’s
recommendation
5. Measure vibrations of pumps and gear boxes
Quarterly 1. Clean and examine pump coupling for signs of wear, general damage,
looseness, and misalignment
2. Carry out quarterly maintenance of pump and motor and diesel engine as per
manufacturer’s recommendations
3. Inspect fan belts of diesel engine for slackness and wear. Adjust/replace if
necessary
4. Clean crankcase breather (use clean fuel for cleaning) by using air
Frequency Checks
5. Remove air filter element and shake out excess dirt by gently tapping on a flat
clean surface
6. Inspect exhaust pipe work for any damage, leakage, or choking and clean it
thoroughly.
7. Check and clean terminals of electric motors. Tighten connections, if required
8. Reassemble air compressors using new gaskets
9. Inspect compressor delivery filter
10. Carry out quarterly maintenance of air compressors as per manufacturer’s
recommendations
11. Adjust the gland assembly by tightening the gland adjusting nuts on either
side of split gland collar. Replace gland packing if it has hardened
Yearly 1. Overhauling of pump and motor to be performed per manufacturer’s
recommendation
2. Yearly maintenance of diesel engine to be done per manufacturer’s
recommendations including:
(a) Inspection and cleaning of fuel injectors
(b) Thorough checking of diesel engine cooling system for leaks, blockages
(flushing, if required, to be done with clean water)
(c) Inspection of starter motor and replacement of carbon brushes, if necessary
(d) Inspection and cleaning of engine exhaust manifolds and pipes and
replacement, wherever necessary
(e) Inspection of air filter and replacement of air filter element, if required
3. Painting of stand posts, overground pipes, and risers is recommended
4. Carry out hydraulic test of pipelines to detect leakages
5. Remove suction filter, cylinder head and valve plate assembly of air
compressors and clean. Inspect valve plates and counter plates. Replace, if
necessary
Every 2 1. All isolating valves to be dismantled and thoroughly overhauled
years 2. Various pressure/temperature switches/gauges to be calibrated
Every 5 Drain, clean, repair, and return to service all pump suction tanks for the systems
years
Appendix B: Fire Protection of Power Stations 221
(continued)
Frequency Checks
Monthly 1. Check for proper functioning of solenoid valves for
remote/manual operation and local/manual operation by energizing
solenoid valves but not allowing spray to take place
2. Check quartzoid bulbs and spray nozzles for proper
positioning/orientation
Quarterly (in addition to 1. Check that water supply arrangements (including back-up
weekly requirements) supplies) are in order and operate valves and carry out a valve
discharge test
2. Operate main stop and zone isolating valves over full range.
A non-hardening packing should be used in valve glands. Restart
valves. Trip and reset deluge valves
3. Test the deluge system by doing actual spray. Where plant
operations prevent routine testing of fixed water sprays,
consideration should be given to conducting a trial of the equipment
during a plant overhaul
4. Check back-pressure valves for correct function. Inspect all
sprays and nozzles for freedom from corrosion and correct
orientation. Painted detector heads should be replaced
5. Examine piping to ensure that it is corrosion free, is properly
supported and is painted
6. All electrical and hydraulic alarms and their initiation devices
should be checked
7. Check spray nozzles for proper orientation
8. Operate water spray system by releasing pressure from detection
line after taking precautionary measures. Observe the spray
coverage and nozzles for any choking, wrong directional mounting
In the case of spray system of transformers, check that the top of
spray cones are below turret of bushings. Reset deluge valve
9. Clean strainers after the spray
Annually 1. Overhaul all control valves, isolating valves and deluge valves
2. Alarm valves, isolating valves to be dismantled and overhauled
3. Various pressure/temperature switches/gauges to be calibrated
4. Flush detection and spray lines and clean all nozzles
5. Carry out hydraulic test of pipelines to detect leakages
Every statutory outage 1. Pressure vessels should be examined internally and the
opportunity taken to repaint with rust-resisting paint
2. Test the deluge system by doing actual spray. Where plant
operations prevent routine testing of fixed water sprays,
consideration should be given to conducting a trial of the equipment
during a plant overhaul
3. Carry out a full flow pump test for a minimum of 6 h
4. Adequate steps should be taken to prevent vulnerable items
suffering damage from water ingress and to ensure that spray
pipework is completely drained afterward
Every 15 years Drain, clean, repair and return to service to service all pump suction
tanks for the system
Appendix B: Fire Protection of Power Stations 223
1.0 Purpose
The directive specifies the system for modifications in plant/equipment at
the power station.
2.0 Scope
2.1 This directive shall be applicable to all modifications (or design change)
to plant/equipment/systems/components of existing power stations after
the date of issue of the directive. For modifications made prior to issue of
this revision, procedure described at clause no 5.7 should be followed
2.2 In the case of power stations set up after the date of issue of this directive,
the directive shall apply from the date the PG test is conducted or date of
completion of warranty of the contractor, whichever is later
2.3 The directive shall not be applicable to modifications/design change to be
carried out under contractual obligations of the contractor under the
contract irrespective of the period when such modification is carried out.
However, in such cases where modification is necessary to be carried out
before expiry of the warranty period or before PG Test, whichever is later,
written consent of the contractor for such proposed modification should
be obtained before carrying out the modification. In all such cases, an
approval from the Engineering Department must be obtained, which shall
be routed through Operation Services (OS)
2.4 The reference design or datum for each plant/equipment/system/
component of the power station shall be as per the last document
approved by Engineering or the original design drawings
2.5 The directive shall not be applicable to ‘defects’ or ‘repairs’ which require
equipment to be reinstated to the original condition
2.6 For the purpose of this directive, system, or component shall also include
load-bearing structures
Station Code:
Purpose of Modification
Component / System: (State justification)
Manufacturer :
Any identified safety hazard / Environment impact on account of the Plant Modifications
Date
232 Appendix C: System for Plant Modifications
3. APPROVALS
4. IMPLEMENTATION
(After work has been completed, record the means by
which modification has been achieved. State Contract Signature:
Number, etc.) Concerned Dept. I/C
Date:
5. COMMISSIONING
Note:
1. This Directive applies only to modifications; it does not apply to `defects' or
repairs which require equipment to be reinstated to the original condition.
2. Section 2 `Categorization'-The selection of Assessment Category is the
responsibility of the Appropriate authority.
Appendix C: System for Plant Modifications 233