Eingiering Guid
Eingiering Guid
STORAGE TANKS
TABLE OF CONTENTS
1. Scope !';" "r~.~"
8 High-PressureStorage Tanks
2. Purpose "," 8.1 Genera! Design
",0.
3. References ::: 8.2 High-PressureStorage in Spheres
8.3 High-PressureStorage in Cylindrical
4. Definitions
Vessels (Bullets)
5. Atmospheric StorageTanks -Layout and 9 Storage of Tetraethyllead and Similar
Design Antiknock Compounds
5.1 General Design Considerations 9.1 Thermal Behavior
5.2 Vertical Atmospheric Storage Tanks 9.2 Site Location and Spacing
6. Atmospheric Storage Tanks -Fire Protection 9.3 Drainage
6.1 General 9.4 "Time Available" Factors for Fire
6.2 Types of Foam Extinguishment
6.3 Foam Application Rates 9.5 Fire Protection Facilities
6.4 Subsurface Injection
6.5 Fixed Foam Chambers Appendix A -Tables and Figures -Foam System
6.6 Catenary Foam Systems
Design
6.7 Portable Monitors and Hose Nozzles
6.8 Water Supply Appendix B -Typical Subsurface Foam
6.9 Foam-Producing Materials Supply Calcu lations
7. Low-PressureStorageTanks Appendix C -Typical Catenary Foam System
7.1 GeneralDesign Arrangement
7.2 Refrigerated Storage
7.3 CryogenicService. Appendix D -Portable Foam Tower Systems
7.4 Site Location and Spacing
Appendix E -Safe Storage Temperatures and
7.5 Dike Walls -Grading and Drainage
Operating Precautions
7.6 High Level Alarms -Overfill Protection
7.7 Fire Protection Appendix F -Tank Fire Boilovers
EGE 14-8-1 Welded Steel Tanks for Oil Storage ASTM (American Society for Testing and Materials) Tests:
(Mild Steel) -Design and Construction
056 Flash Point by the Tag Closed Tester
(revised draft available)
093 Flash Point by the Pensky-Martens Closed Tester
EGE 14-8-2 Welded Steel Tanks for Oil Storage (High-
0323 Vapor Pressure of Petroleum Products
Strength Steels) -Design and Construction
EGS 14-8-6 Refrigerated Product Storage Tanks -
NFPA (National Fire Protection Association) Codes:
Design and Construction
EGE 14-S-8 Oil Storage Tanks -Foam Connections 11 Low Expansion Foam and Combined Agent System~
EGE 16-8-1 Piping -General Design 30 Flammable and Combustible Liquids Code
EGE 34-8-11 Thermal Insulation -Cold Service 58 Storage and Handling of Liquefied Petroleum Gas
EGE 34-8-15 Fireproofing -General Requirements 59A Production, Storage, and Handling of Liquefied
EGE 41-8-63 Portable Fire Extinguishers and Fire 81ankets Natura! Gas
78 Lightning Protection Code
Mobil Engineering Guides -Systems Design: 321 Basic Classification of Flammable and Combustible
EGS 622 Recommended Spacing for Refineries and Liquids
Petrochemical Plants
EGS 623 Fire Protection -Bulk Plants and Terminals 4. DEFINITIONS
EGS 629 Fire Protection and Loss Prevention -
Refineries and Petrochemical Plants Boilover -The expulsion of crude oil or certain
EGS 643 Fire Protection -Fixed Fire Water Spray other liquids from a burning tank. The light frac-
Systems tions of the crude oil distill, burn off, and produce
EGS 661 Pressure Relief and Vapor Depressuring Systems a heat wave in the residue, which on reaching a
EGS 725 Plant Drainage and Sewer Systems (revised draft water stratum results in the violent expulsion of
available). a portion of the contents of the tank. (SeeAppen-
API (American Petroleum Institute) Publications:
dix F.)
RP 520 Recommended Practice for the Design and Combustible Liquid -Any liquid having a flash
Installation of Pressure-Relieving Systems in point at or above 37.8°C (1000 F).
Refineries. Parts I and II
Std 620 Recommended Rules for Design and Fire Sea! -A means of providing a liquid trap to
Construction of Large. Welded. Low-Pressure prevent fire passage in a piping or drainage system.
Storage Tanks A fire seal provides 152 mm (6 in.) of submergence
Std 650 Welded Steel Tanks for Oil Storage below the liquid level of an inlet or outlet pipe
Std 2000 Venting Atmospheric and Low-Pressure opening. See EGS 725 for details.
Storage Tanks
Pub I 2023 Guide for the Safe Storage and Handling of Fire Stop -A closed drain section at least 9 m
Heated Petroleum-Derived Asphalt Products
and Crude Oil Residual
(30 ft) long in an open drainage ditch, with a fire )
seal at the upper end.
Std 2508 Design and Construction of Ethane and
Ethylene Installations at Marine and Pipeline Flammable Liquid -Any liquid having a flash
Terminals, Natural Gas Processing Plants. point below 37.80C (1000 F) and a vapor pressure
Refineries. Petrochemical Plants. and Tank not exceeding 276 kPa abs (40 psia) at 37.80 C
Farms
(10QoF).
Std 2510 Design and Construction of LP-Gas Installa-
tions at Marine and Pipeline Terminals, Natural
Flash Point -The temperature at which a liquid
Gas Processing Plants. Refineries, and Tank
gives off vapor sufficient to form an ignitable
Farms mixture with air near the surface of the liquid or
ASME (American Society of MechanicalEngineers) within a vessel as determined by the appropriate
Boiler and PressureVesselCode: test procedure and apparatus (see N FPA 321):
(b) The flash point of liquids having a viscosity (3) .Aluminum honeycomb sandwich panel
of 45 SUS or more at 37.8°C (100OF) and a cover
flash point 93.4°C (200OF) or higher shall be
(4) Any combustible (nonmetal) cover.
determined in accordance with ASTM 093.
(d) Covered floating roof tank -A storage
Foam -A stable aggregation of small bubbles of tank with a fixed roof and steel internal floating
lower density than oil or water, which shows roof of the single-<ieck pontoon or double-deck
tenacious qualities in covering and clinging to verti- design.
calor horizontal surfaces. Foam flows freely over
(e) Open-top floating roof tank -A storage
a burning liquid surface, forming a tough, air-
tank with a steel floating roof of the pontoon,
excluding continuous blanket to seal vo:atile com-
buoy, or double-deck design and without a fixed
bustible vapors from access to air. Foam resists
roof.
disruption due to wind and draft, or to heat and
flame attack, and is capable of resealing in case of (f) High-pressure tank -A storage vessel de-
mechanical rupture. signed as a pressure vessel; see definition (h).
5.
MOBIL ENGINEERING GUIDE
(b) Crude tanks 46 m (150 ft) or more in 152 m to 215 m (500 ft to 700 ft) intervals and
diameter: Spacing between tank shells shall be at roadway crossings to prevent the spread of
one diameter up to a maximum distance of fire. The seals shall be designed to skim the
107 m (350 ft). liquid surface to avoid trapping oil in the ditch.
(c) Hot oil tanks heated above 121°C (250°F), For fire seal design details, see EGS 725.
excluding high-flash asphalt: Minimum spacing,
5.1.4 Piping to Tankage Within Diked Areas
shell to shell, shall be equal to the diameter of
the larger tank. One of the following protection methods shall be
(d) Slop oil emulsion-breaking tanks: Minimum used to avoid potential fire exposure to piping in
spacing, shell to shell, shall be equal to the diam- ain diked
spreadarea. Otherwise,
of fire such
or possible exposure
loss of tanks.could. result
eter of the larger tank.
(a) Arrange drainage so that oil cannot collect
5.1.2 Access beneath the pipeway. Slope the diked area away
from the base of the tank.
Tankage shall be arranged so that every tank with (b) Where drainage is not possible, cover pipe-
a diameter greater than 15 m (50 ft) is directly ways within the diked area with fill, taking
accessible from a fire fighting access road on at precautions to protect pipelines from corrosion
least one side. Tanks 46 m (150 ft) in diameter or (see EGE 16-8-1).
larger shall be accessible from fire fighting access
roads on at leasttwo sides. 5.2 Vertical Atmospheric Storage Tanks
5.1.3 Pipeway Protection and Drainage 5.2.1 Floating and Fixed Roof Storage Tanks
(a) Pipeways shall not be routed through diked Floating and fixed roof storage tanks shall be
areas, except for product, utility, and foam pip- designed and installed in accordance with EGE
ing to the tank. Grade should slope away at an 14-8-1 or EGE 14-8-2 and EGE 14-5-8. Minimum
angle of one percent beneath pipeways so that requirements for tank construction shall be in
oil will not be contained in the immediate area. accordance with NFPA 30.
Sewer catch basins or drainage ditches shall not
be located beneath pipeways. When the grade is (a) Open-Top Floating Roof Tanks -Double-
relatively slight, the pipeway shall be placed over deck or pontoon open-top floating roof tanks
a berm that is on a higher elevation than the shall be used for storage of all ClassI flammable
adjacent area. liquids, such as crude oil, gasoline, and naphtha.
Their use is also required for combustible liquids
(b) Pipeways shall be protected by installation stored at or above their flash points (except
of a fire resistant ditch cover or by a fixed water asphalt and heavy oils that are heated). For
spray system at drainage ditch crossings.The fire gasoline or naphthas presently stored in cone
resistant ditch cover, which may be a concrete roof tanks, see Appendix E, Section E-5. The
culvert pipe, shall extend at least 9 m (30 ft) floating roof shall be bonded to the shell in
each side of the piping right-of-way. When a accordance with NFPA 78 to protect against a
water spray system is provided, spray nozzles rim fire caused by lightning or induced electro-
shall be located beneath the pipeway and shall static charges.
be designed to provide a density not less than An exception to NFPA 78 requirements is that
20.4 (L/min)/m2 (0.5 US gpm/ft2) of the area insulation of pantograph linkage is not required
beneath the exposed section of the pipeway. on existing tanks because bonds provide suffi-
The water spray design shall be in accordance cient protection. On tanks equipped with tube
with EGS 643. seals rather than pantograph seals, the metal
(c) Flanged or threaded joints and valves shall weathershield or secondary seal shunts provide
not be located over drainage areas that may the necessarybond. Where secondary seals are
co'ltain oil due to a spill. provided. shunts shall be located above the
secondary seal. Roof pontoons shall be main-
(d) Fire seals, or fire stops, shall be installed tained wi1hout leaks so that a flammable vapor
in drainage ditches and pipe sleeper ways at mixture will not occur within the pontoon.
MOBIL ENGINEERING GUIDE
When shunts are provided for necessary electri- same fire hazards as cone roof tanks without
cal bonding between the shell and roof, they internal coversand should be treated in the same
shall be stainless steel and installed at intervals manner.
of 3 m (10 .h), maximum, on the tank circum-
ference.
Cone roof tanks with thin-skin metallic covers
on floats have a fire loss record comparable to
Epoxy lining will not restrict normal bonding that of covered floating roof tanks. Aluminum
arrangements for the dissipation of induced honeycomb sandwich panel covers are expected
electrical charges due to lightning. Heavy, waxy to perform equally as well as, or better than,
crudes may require seal scrapers to ensure posi- metallic skin covers. Tanks with either of these
tive seal and adequate bonding. covers are subject to the same fire hazards as
covered floating roof tanks and should be
(b) Covered Floating Roof Tanks -Covered treated in the same manner.
floating roof tanks may be used for the same
type of service as open-top floating roof tanks. Depending on storage temperature and volatility
When selecting a covered floating roof tank, the of the product, the vapor space above the float-
following loss prevention considerations shall ing cover may be in the flammable zone and
apply: vulnerable to explosion. When storing volatile
products, such as gasoline, install pressure vacu-
(1) The tank diameter shall not exceed 46 m um (PV) vents or, preferably, modify the tank
(150 ft). This restriction is required because to provide ventilation in accordance with API
of possible roof hangup on the numerous Std 650, Appendix H.
columns of this type of tank and loss of seal-
ing adjacent to the columns. [In some types
of tank construction the tank diameter may 5.2.2 Dikes
exceed 46 m (150 ft), subject to Mobil ap-
proval.] Drainage and impounding or diversion dikes shall
be provided in accordance with Chapter 2 of
(2) To prevent generation of a static spark
when the space between the floating and NFPA 30. Where tank diameters are 46 m (150ft)
fixed roofs is in the explosive range, floating or more, the toe of an impounding dike shall be
roofs shall be bonded to the shell by static located a minimum of 15 m (50 ft) from the tank
wire, stainless steel shunts, or other rubbing shell. Dike walls higher than 1.8 m (6 ft) shall be
contact of suitable electrical conductivity. subject to the requirements of NFPA 30. Mini-
mum height for impounding dikes shall be 1 m
(3) Tanks shall be vented in accordance with (3 ft). Impounding dike basins shall be graded
API Std 650, Appendix H. away from tanks to fire sealed and valved drains
(4) Tanks shall not be used for storage of that extend through the dike wall. Each drain valve
products that contain hydrogen sulfide and shall be clearly labeled and located outside the dike
may from phrophoric iron scale on the roof with overflow into the plant drainage system.
and inner shell. Indicating valves shall be used.
(c) Cone (Fixed) Roof Tanks -It is preferred Unless a diversion dike system is being utilized.
that cone roof tanks be used for storage of separate impounding dike enclosures shall be pro-
Class II or Class III materials. This type of tank vided for each tank that is 46 m (150 ft) or greater
is not recommended for storage of crude oils or in diameter and stores crude oil, and for tanks in
products where the vapor space is explosive at hot oil [over 93°C (2000 F)] or slop oil service.
equilibrium storage temperatures, unless the Separate impounding dike enclosures shall be pro-
vapor space is inert gas blanketed. vided for each tank that is 61 m (200 ft) or greater
in diameter and stores Class I liquids other than
(d) Cone (Fixed) Roof Tanks with Internal crude oil. Intermediate dikes shall meet the re-
Floating Covers-Tanks with covers of the pan- quirements of NFPA 30.
type design and/or constructed of combustible ,
(nonmetallic) materials, such as plastic with or If spacing permits, a diversion dike system may be
without sheet metal enclosure, are subject to the used. Diversion dike systems shall be graded away
MOBIL ENGINEERING GUIDE
from all tanks and shall provide piping to a safe shall be used in vertical tanks. Dome roofs and
location. small-diameter cone roofs require pressure relief
devices sized in accordance with NFPA 30. Where
Main Tank Valves emergency relief is provided by a pressure relieving
device, the total venting capacity of both normal
Storage tanks shall be provided with shutoff valves and emergency vents shall be sufficient to prevent
in all lines below the liquid level. Tank valves in ruptures of the shell or bottom of vertical tanks.
lines greater than 200 mm (8 in.) in diameter, or Storage of unstable liquids shall allow for the
inaccessible under fire conditions, shall be re- effects of heat or gas, resulting from polymeri-
motely operable from a lo::ation outside the dike zation, decomposition, condensation, or self-
walls. Remotely operated main valves on tank reactivity, with vents designed in accordance with
.;ozzles shall be protected against fire exposure NFPA 30. Hot oil tanks with fixed roofs shall have
by fireproofing exposed conduit and valve opera- added venting capacity, such as venting-type roof
tors. Fireproofing shall meet the requirements of manways, to reduce the possibility of weak roof-
EGE 34-8-15. to-shell seam rupture due to small pressure surges
caused by steam or lighter products entering the
5.2.4 Piping and Fittings tank.
8
Piping and fittings connected to storage tanks shall 5.2~7 High Level Alarms -Overfill Protection
be provided in accordance with EGE 16-B-1 and
EGE 14-$-8. A high level alarm shall be installed on tanks re-
ceiving Class I or Class II materials from pipelines
Vents or marine vessels. The alarm shall sound in a
location occupied by personnel during product
A sufficient number of properly designed vents receipt, such as a control room or oil movements
shall be installed on cone roof tanks to prevent the control area. The alarm actuating device shall be
development of vacuum or pressure in excess of independent of the tank gaging instrumentation
design limitations. Maximum design pressures and shall be electrically supervised (or the equiva-
could be exceeded during tank filling and emptying lent) for circuit fault detection in accordance
operations or as a result of atmospheric tempera- with NFPA 30. Alternate overfill protection de-
ture changes. vices require Mobil approval.
Tank vents shall be sized in accordance with API 5.2.8 Low Level Alarms
Std 2000. Conservation PV vents shall be provided
on cone roof tanks unless the maximum expected A low level alarm shall be installed on tanks with
surface temperature of the liquid stored in the tank heating coils to prevent drying and overheating of
the coils. The alarm actuating device shall be inde-
is at least 13.9°C (25OF) below the closed-cup
flash point of the liquid. A conservation roof may pendent of the tank gaging instrumentation. 8
also be used. Inert gas blanketing, if utilized, may
be considered equivalent in safety to a conserva- 6. ATMOSPHERIC STORAGE TANKS-
tion roof. When PV vents are installed, flame FIRE PROTECTION
arresters are not required to prevent propagation
of flame into the vapor space of a cone roof tank. 6.1 Genera!
Tanks shall be constructed, or shall contain de- In determining what fire protection facilities are
vices, to relieve excessive internal pressure caused required, specifically those that utilize foam extin-
by fire. Required emergency venting capacities guishing equipment, the following factors should
shall be determined i" accordance with API Std be considered:
2000 and/or NFPA 30.
(a) Class 11m oils with flash points of 93°C
A floating or lifter roof, weak roof-to-shell seam, (200° F) or above do not ~ormally require pro-
or other approved pressure relieving construction tection, unless there is a possibility of being
MOBIL ENGINEERING GUIDE
heated to the flash point or above. Tank spac- originating at a fixed roof tank vent or at the seal
ing, dikage, and fire extinguishing means are of a floating roof tank represent relatively minor
relatively unimportant for unheated oils with fire exposures.
flash points of 93°C (200° F) or above. Usually,
a low cul'b and sufficient spacing for mainte- Table 1 summarizes the protection measures that
nance are satisfactory, unless other requirements should be provided for vertical atmospheric storage
are specified by local ordinance. tanks to protect them against fire risks. Depending
on the type of storage tank, these fire risks are as
(b) Tanks containing Class IlIA combustible follows:
liquids with flash points greater than 60°C
(140OF) and below 93°C (200OF) usually are (a) Cone Roof Tank -A gastight cone roof
not required to be protected by foam, unless tank, equipped with PV vents, may be subject
they are heated to or above their flash points. to internal ignition and explosion from static
Unheated product tanks in this category need discharge or from the presence of pyrophoric
not be considered when determining foam pro- iron scale when the vapor space is in the flam-
tection requirements, unless: mable range. Table E-1 and Figure E-1 of
(1) A low-flash stock is pumped into the Appendix E illustrate the flammability of the
tank for cutback and blending purposes, and vapor space in a cone roof tank based on various
the closed-cup flash point of the cutback temperatures. External ignitions such as light-
stock is less than the storage temperature. ning usually cause only a vent fire. A serious
external fire may cause the roof to relieve
(2) Hot oil streams above their flash points internal overpressure in accordance with normal
enter the tank from process units, or there is tank design, resulting in ignition of tank con-
a possibility of this occurring as a result of tents from the heat of the fire.
improper operation or process upset.
(3) Overheating occurs, resulting in storage (b) Floating Roof Tanks -Floating roof tanks
temperatures exceeding the flash point of the of open-top design are inherently fire safe, ex-
stored material. cept for the possibility of rim fires. Rim fires
on open-top floaters can result from static dis-
(4) The stored product is of exceptionally charge due to atmospheric. electrical distur-
high value or the tank is vulnerable to fires bances caused by a lightning storm, from pyro-
involving adjacent equipment or facilities. phoric iron deposits where the stored material
contains sufficient hydrogen sulfide, or from
(c) Crude oils shall be stored in floating roof
tanks to reduce vapor generation and to prevent other remotely possible external ignition causes.
However, if the roof of an open-top floater is
the development of a heat wave in the tank in a
properly bonded in accordance with NFPA 78,
fire situation. The boilover characteristics of
a rim fire attributable to static or lightning
crude oils can result in serious spread of fire if
should not occur. Rim fires are rare where open-
a heat wave reaches a tank water bottom. The
top floating roofs are properly bonded, rim seal
tanks shall have open tops unless snow loading
integrity is maintained, and pontoons are main-
is a problem.
tained leak-free.
...~
GO ~
.--
~-
'-
GJ C
CD g~
oE
.j E =~ -=~~--" "'0
m..c .ao-mm
"O~ E m-= --_c.o- :.- GO 0 0"0
GJo
'- ~
...CO
0.0
5 ~cc Eo--o~- E
GO
~
GO
GJQ)
E c
E-
CO CO
o"'~=~-g-c=
c..o.~=-
~~ --- 0-=
E -ccC ~ 0
CIJ.. "'..
m 0
-"oQ)CO
-Q)
., 0
co-
c CO
a.'"~
.c",
...
c. ...
~ ~ ~ ~ '" Q) ~ .,.
Q) ~ '"
CO
0
--"C
3-
>- >- >- >- >- >- >- >- >- >- "CE-
c--
m-
"'-
.D'S
E";;
0 - .,;
-",' Q) -~
=
= =.
0'"
>'S
--
E
C "C0 ~.- C
m"CE~o~
~m
c
=~-
c
=
muo ~
m
-
~...
.-0 =.-u
==- coO"
C CO
"C
C
"Cm_m*,'~ . -c -C'- 0" m
.-"C~ '"
>c-~"'c~
-"C *'
c~-_:>C:=~
~~=
---~-Q)~
~.-
->--
~-=ao
=c.co
.c",
E~
.c
.c
~=..=..
c C m ~ ~ 0'- O °Q)~O~.cc-
E =~- Q)
Q:.cEoEC.)~ C)=
~
c.Q.-;;;~~ c.= c. ~ 0 .~
c:;: 3
Ec ...
~o
-'"
CO"
~
--...
on
~
'" 03
...
QO ~ ~ ~ ~ '"co ~
'"Q) c> 0
CO
Q)
--c
0)
>- >- >- >- >- >- >- >- >- >- 0 ~
0 c =
~.¥
--., >
co~ m
-'... ;::c -0
oc .c
--_c -c
-..0-
,m.- c~ c
0 -c
c-
0 ~
-'"
c
m ~-;:; C:J Q)
~Eo=-=
c ca'" .- oS _:
-Qj
CUm m
Q)
-c --0
C3.:~-~~ .~ E -0
CD --~ ~
;;:E-o
.¥ .==
'" E "C
U"S '" '" co E'-OJ 0 ~
0 EE~ c . -;:: E ~ E E
Co)
co -m
-"'..¥ --.::2 C
=~
~~
E "'.:
~ 0
~m ~ ~
0_"0
C ~
-c-(.;)=~ 0 -~ ~ ~
ou..?
com
"- -co
'" -",:0: --Q)
--0 0 U
'" m GO
E£
CO .c
-
U-_U OJ
0 "- > E -
~ .-
.--0 c ~ m
'"~ '". ~ _s.§ E E
c"---
.-"-
c,~=~"-c, -
._="'-
C
-> - ~
o~
~
:=
'"Qj
-~
'"m~0
Qj
--
'"
m
'"
Et;-g
OJ >"0
-VI'- :;.
.,.
c'" :::
"C
m"-~C'c,>",-
.cc Q)
..o -C . =E 0 -0- -> ->.
>Eom ~ CO'-
-0
.-
"C
U-. .-c Co) m 0.: Co.: -"'c"'C ~
--
~~E-c=c
"-~cm.~Q.
vo 0 "---
-=--"- c
~..c
~
~ E
~m
Co)
~
~u~Co~mu=u
0
-::;
=m=~=,CmCm
__-com_Q)-
~
m_>o>o
-9- m ~ -::; ~ -::; Eoc.
m-m
0"O.c
-OJ>
.co
-)(
->
GO.,
..0.
--Q)
..0
a.
.,
..o~"-C'~c, ~ 0 ~ ---0 -0
0 )( m GO .D
=coc,-
C/Jc-"-- E
~
cn-
~ 0 o~o=u.m~=~
0.. Coo.. ~-t.) Cot.;) Co ziL:E
o.c
GO
"C
-I- 'S
'" 0
.;;; -.c
"'"C c> '"
..-co
co c.. 0"0. E
-= c.-
E -..~ v = CD v """ v a) .qo v «I °a.
",m -Q)
~
o'=c-
>co a; '" .>.
Z :a: >.¥"C
oCQ)
'"
oco"C E
-> ---co
+- 0, m-o
co...""
0
~-c:* 0' C c;- .t:
~ c;- a;oa.> ...
-"",
t::'~ ... 0 in o o
m - C1) S: ~ 0
...
N c
I N 0- ~ 0" I
S C --CO
~
0 .-0) C C
I I
-= -
c
-
Co 0 0 C'I
> :?- 00(.)
0 Q: , 0 N 0 ~ c.f:oE
t-"=m,r.
00- N in
1\ "A Q) ---CO
CO-0
~cc-
c
c
t-
ce-
.-c
C
~~~
a,a,E
V
CO)
- g.
";:;
'II
co
""" to U)
"t)
~
~'O
V
M' CO
=-
co'
§~M«+-
'1' I I
t::t::~
(.)'-'-
o..~ t::
V ...
CO) i¥.
r-
~
I
to
"""
1\
8~ V
~
i\
.
INEERING
IDE
MOBil ENGINEERING GUIDE
are methods of avoiding this limited explosion (c) Natural Gasoline Plants -Natural gasoline
hazard in the vapor space. plants are usually in remote areas.Volatile mate-
rials are generally free of hydrogen sulfide and
(c) Cone Roof Tanks with Internal Covers - are stored in floating roof tanks. Foam protec-
The use of internal coversdoes not eliminate the tion for tanks is not necessaryat most installa-
requirement for foam protection on a cone roof tions unless required by local ordinance.
tank [see Paragraph 5.2.1 (d)] .The vapor space
of a cone roof tank may be in the flammable (d) Offshore Facilities -Crude oil storage
range without an internal cover. Therefore, an tanks at producing platforms are small yet
internal cover is often used to reduce the vapor vulnerable to fire exposure becauseof the usual-
space to a lean vapor/air mixture, as well as for ly congested installations. Refer to the appro-
product conservation purposes. Where an inter- priate E&P Specifications for protection require-
nal cover is installed, acceptable results may be ments for offshore tanks.
gained for JP-4 fuel storage, for example, when
the tank is open vented. However, the use of
6.2 Types of Foam
an internal cover for more volatile materials,
such as gasoline, may only reduce the vapor/air
The requirements of this Guide are based on the
8 mixture to within the flammable range rather
than provide a lean mixture. PV vents shall be use of 3 percent, low expansion fluoroprotein
foam or aqueous film forming foam (AFFF). Basic
provided when the vapor space is expected to
be in the flammable range, unless the tank is requirements for design, installation, testing, and
ventilated in accordance with API 650, Appen- maintenance are contained in NFPA 11. The type
dix H. of foam-producing materia! determines the extent
of foam-making equipment, manpower require-
Horizontal atmospheric storage tanks, such as ments, maintenance, and fire fighting procedures.
those used at bulk plants for storage of gasoline Foam-producing materials are described briefly in
and fuel oil, do not require foam protection. the following paragraphs.
Norma! and emergency venting shall be provided
in accordance with API Std 2000 and NFPA 30. 6.2.1 Protein and Fluoroprotein Foams
Cooling streams from the plant fire water system
or municipal fire department should be provided. Protein and fluoroprotein foams are generated by
mixing foam liquid concentrate with water and
6.1.3 Basisfor Plant Foam Protection aerating the solution by inducing air in a foam
Requirements maker. Depending on concentration, the foam
liquid is proportioned in water (usually 3 percent
Each atmospheric storage tank installation shall be to 6 percent) to form a solution. There are three
evaluated for relative fire risk and associatedfoam types: low, medium, and high expansion. The low
~rotection requirements. The following rules for expansion foam recommended for use contains
"I::..,~rovidingfoam protection at a plant apply except inhibitors to reduce the amount of foam break.
where otherwise governed by local authority: down in a fire, and the solution expands eight to
ten times its volume when aerated.
(a) Refinery and Petrochemical Plant Tank-
age -Foam protection shall be sufficient for (a) Foam Concentrate Percentage -This Guide
extinguishment of the largest cone roof tank is based on the 3 percent, low expansion foam
fire. Cone roof tanks shall be protected by sub- because it requires half the liquid concentrate
surface foam systems unless the tanks contain storage requ ired by the 6 percent type. Where
polar solvents. Water and foam solution require- mutual aid is a factor, the type of foam liquid
ments for cone roof tanks are given in Appen- used by neighboring facilities should be investi.
dix A, Table A-1. Open-top floating roof tanks gated and the following factors taken into con-
shall be protected from rim fires in accordance sideration:
with Paragraph6.3.2.
(1) The 6 percent liquid concentrate is less
(b) Bulk Plants and Marine Terminals -Guide- expensive than the ~ percent, making fire
lines for bulk plant fire protection are found in extinguishment costs approximately equal on
EGS 623. a comparison of relative application rates.
MOBIL ENGINEERING GUIDE
However, more 6 percent materia! is required, ordinary foam, and the use of heated storage
so that larger containers and pumping facili- areasand ordinary foam is recommended.
ties must be provided. Therefore, the 3 per-
cent type is,usually considered more economi- It should be noted that the viscosity of the foam
cal. liquid increases at low temperatures. This can
affect the proportioning rate, reducing the per-
(2) The proportioning system used should centage of foam liquid added and thus generat-
be designed to proportion 6 percent and ing foam of poor quality. To prevent excessive
4 percent as well as 3 percent. Such a system sludging, on the other hand, foam liquid' con-
has the added advantage of permitting the centrate should not be heated above 37.8° C
generation of a stiff foam by increasing the (100OF). Therefore, it should not be stored in
proportion when using 3 percent liquid. Also, the hot sun for long periods without protection.
3 percent foam liquid concentrates should be
proportioned at 4 percent when used for sub- 6.2.2 Alcohol/Polar Solvent Resistant Foams
surface injection.
I .
(3) Foam concentrates of different types or Alcohol/polar solvent resistant foams shall be used
of the same type made by different vendors to extinguish fires due to water-soluble, polar, or
foam-destructive solvents. These foam-producing
8
may not be compatible and should not be
mixed in storage. However, different foam materials are more expensive than other types, but
solutions may be used on the same fire, and they can also be used on liquid hydrocarbon fires.
foam concentrates of the same type made For the purpose of this Guide, a 6 percent alcohol
by different vendors may be mixed together foam liquid meeting UL and Mobil requirements
imnllediately before propprtioning at' the should be used to extinguish fires involving certain
fire scene. alcohols (methyl, ethyl, isopropyl, TBA), esters
(ethyl acetate), ketones (acetone, MEK), ethers
(4) I The proportioning system may be used (isopropyl ether, diethyl ether, MTBE), aldehydes,
with foam liquid concentrate of any manu- certain amines,and other organic solvents.
facture, provided it proportions correctly.
The foam makers, where the solution is Alcohol foams are used in proportions of 6 percent
aerated, will generate foam for a 3, 4, or or greater. They are generally not effective when
6 percent foam solution. applied by subsurface injection into alcohol/polar
solvent fuels (seeParagraph6.4.1).
(b) Fbam Concentrate Requirements -Foam
liquid concentrates shall meet Underwriters 6.2.3 Aqueous Film Forming Foam(s)
Labo~tories (UL) requirements and be ap-
proved by Mobil for the use intended. The foam AF F F is a fluorinated surfactant plus foam stabil-
concen,trate must be able to produce a fire izers diluted with water to a 3 or 6 percent solu-
resistant foam of proper quality and must be tion. The foam acts as a barrier both to exclude air
sufficiently stable for long-term storage. and to develop on the fuel surface an aqueous film
capable of suppressingthe evolution of fuel vapors.
Foam liquids must contain fire resistant inhibi- AF F F is specifically recommended for process unit
tors to avoid excessive application rates. Some spill fires. When practical, Mobil recommends that
foams are corrosive and require alloy piping and AFFFs not be used for fires in depth. Testing
lined storage containers to prevent excessive has demonstrated that most AFFFs are generally
corrosipn under storage conditions. Ordinary unsuitable for these fires.
foam liquid is used when the storage tempera-
ture will not drop below -12°C {+100F) or AF F F is effectively used in a combined agent
when ~e storage area is heated. A "freeze pro- application system with dry chemica! extinguish-
tected" foam liquid may be used in colder ing agents. The speed of extinguishment, vapor-
climateS where the storage temperature may securing properties, and compatibility of AFFF
reach T200c (-4° F) and where the liquid is with dry chemicals provide extremely rapid knock-
not premixed with water in storage. However, down, extinguishment, and ,securement of flam-
"freeze protected" foam is not as effective as mable liquid spill fires. AFFF can be generated
MOBIL ENGINEERING GUIDE
MAY~986 PAGE 11 OF 67
EGS 626-1986
QUICK-OPENING VALVE
(CAR SEAL OPEN)
/, FOAM MAKER
SIAMESE FOAM
HYDRANT I- I
~ BAFFL.EPLATE
MOUNTED ON TOP
-HIGHER
- THAN UPPERMOST
POSITION OF ROOF
STAIRWAY
-
PLATFORM
[=~==~=~
~
"\: TOP
ANGLE
I~
STAIRWAY- SOmm
WINDGIRDER~ --!:..2"2.M~.-
~ ,SECONDARY
LAOOER
FOAM
d
'- DAM (1)
FOAMSOLUTION ---
STANDPIPE FLOATING ROOF
TANK SHELL
PRODUCT
NOTES:
1. No~ always reQuired. (See Paragraph C-,-'O 01
Appendix C.)
2. NPS -nominal pipe size. inches.
FIGURE 1
TYPICAL FLOATING ROOF TANK
(With Siamese Hydrant and Fixed Foam Maker
at Top of Stair~y)
f-=
MOBIL ENGINEERING GUIDE
Cone Roof Tanks Containing Polar, maximum allowable back pressure is 414 kPa gage
Oxygenated, Water-Soluble, or (60 psig) (see Figures A-11 to A-13 of this Guide).
Foam-Destructive Solvents
PHB foam makers will perform satisfactorily at
Minimum foam solution application rates for the inlet pressures of 690 to 2069 kPa gage (100 to
tan s discussed in this paragraph may be higher 300 psig), provided the system is designed so that
tha for hydrocarbon liquid fire extinguishment back pressure does not exceed 40 percent of the
be use of the characteristics of the products the inlet pressure at the desired flowrate. Also, a mini-
tan s contain. Solution rates are given for various mum of 34.5 kPa gage (5 psig) back pressure is
solv nts in NFPA 11. It is advisable to contact necessaryto maintain the proper foam characteris-
app opriate specialists within Mobil and to request tics. Depending on tank sizes, more than one foam
ven or recommendations when providing protec- maker may be required for injecting foam into the
tion for these liquids. Portable foam towers, fixed largest tank. Tests indicate that the foam solution
foa chambers, hose streams, or monitors may be rate should not exceed 12.2 (L/min)/m2 (0.3 US
emp oyed to apply the foam. Subsurface injection gpm/ft2), three times the recommended minimum
is ge erally ineffective for this use. rate.
In sub urface injection, a supply of foam liquid Subsurface foam system pressure drop shall not
concen rate is not usually required to produce exceed 40 percent of the foam maker inlet pressure
foam r foam solution to fill the volume of foam when a National Foam PHB high back pressure
feedlin s to the tank. Fire water displaces the foam maker (see Figures A-1 and A-11 to A-13) is
solutio and foam from subsurface injection lines used, or the maximum allowable pressure drop as
into th tank so that no additional foam liquid is stated by the manufacturer if a different foam
require. maker is used. The system pressure drop includes
either hose or pipe friction losses between foam
6.4.5 IFoam I njection Points maker and tank, plus static head. (See examples
in Appendix B for typical calculations; seeAppen-
A subs rface foam injection point into a tank may six A, Figures A-5 through A-1O, for hydraulic
be eith r the tank nozzle of a product line or a data.)
separat foam delivery line. The size of an injection
point s all be such that the foam generator dis- 6.4.7 Foam System Piping
charge ressure and foam velocity limitations are
not exc ded. Foam velocity at point of discharge (a) Injection Piping Methods -There are two
into a nk shall not exceed 3 m/s (10 ft/s) for methods of piping foam into a tank by fixed or
Class and IB volatile products and shall not semifixed subsurface injection (see Appendix A,
exceed m/s (20 fils) for other products. In sub- Figures A-2 to A-4, for typical designs).
surface foam injection, the minimum number of
injectio points into tanks shall be as shown in the (1) Product line connections -Fixed system
tabulati n below. piping or fire hose inlet connections are pro-
vided on product lines outside the dike wall
When or more injection points are required, or at a product manifold. Each connection
they s all be equally spaced around the tank shall be equipped with a block valve. A check
periphe .Each injection point shall be sized to valve is not required on semifixed system
deliver foam at approximately the same rate. connections because it is an integral part
Outlets for even foam distribution may be fed, of the foam maker outlet assembly (see
through a pipe manifold (spider) installed in the Figure A-1). The hose inlets, plugs, and caps
tank, b a single shell connection. Shell connec- shall be of corrosion resistant metal. This is
tions m y be made on tank manway covers rather the preferred means of injection when only
than by installing additional tank nozzles. one injection point is required.
Tank Diameter
---
Class 1A and 18
Required
Nonvolatile
8
m ft liquids Liquids
Up to 24 Up to 80
I
Over 24 to 37 Over 80 to 120 2 1
Over 37 to 43 Over 120 to 140 3 2
Over43 to 49 Over 140 to 160 4 2
Over49 to 55 Over 160 to 180 5 2
Over 55 to 61 Over 180 to 200 6 3
Over 61, add one Over 200, add one
inlet for each inlet for each
additional. .. additional. .. 465 m2 (5000 ft2) 697 m2 (7500 ft2)
of surface area of surfacearea
~~ ~
~
After the start of a fire, a foam maker inlet 6.6 Catenary Foam Systems
connection to the product line may be made
for tanks between 24 m and 37 m (80 ft and Catenary foam systems provide a means of extin-
120 ft). in diameter, depending on the liquid guishing rim fires in large, open-top floating roof
stored in the tank. In this case, product lines tanks where manual fire fighting is difficult be-
may be hot tapped, or necessaryattachments cause of the extensive rim area. Catenary foam
may be made at any existing accessibleflanged systems shall be provided in accordance with
or threaded pipe joint of suitable size. Table 1.
.
MOBIL ENGINEERING GUIDE
tween t~ Shell and roof in less than 7% minutes if hose stream to tanks containing crudes, heavy fuel
the foa is discharged under the seals or weather- oils, and similar materials that can develop a heat
Ishield w thout a foam dam. This test shall be con- wave (see Appendix F). Ground level monitors are
iducted n installation of the system and whenever not recommended for extinguishment of floating
Ithe tank al area is modified. roof rim fires because of the excessive amount of
foam delivered, the difficulty in directing the foam
~.7 PortableMonitors and HoseNozzles into the narrow annular space, and the possibility
of sinking the roof. Monitors on foam truck articu-
6.7.1 Qeneral lated booms may be advantageous, depending on
foam truck accessibility and tank size.
Portable oam monitors or foam hose streams may
~e used 0 extinquish tank fires, given the limita- 6.7.3 Advantages
1ions Ii d in NFPA 11, Chapter 6. These devices
Can be u d for protection of cylindrical or cone Despite the limitations, there are sufficient advan-
toof tan s not over 15 m (50 ft) in diameter or tages in the use of portable foam monitors to
9 m (30 ) high. Foam hose streams are effective justify consideration for tank fire extinguishment.
in extin uishing floating roof tank rim fires. In Foam trucks built to Mobil specifications are
1anks up to 40 m (130 ft) in diameter and 13 m usually equipped with a 227 m3/h (1000 US gpm)
(42 ft) h gh, foam monitors have been successful foam monitor or snorkel articulated boom with a
in extin ishing fires that involved the entire tank. 114 m3/h (500 US gpm) monitor. In addition, a
However, use of large monitors should not be 227 m3/h (1000 US gpm) wheeled monitor is
depended upon as a primary means for extinguish- recommended and can be towed behind the foam
ment of J rge cone roof tank fires. truck for use on tank or spill fires. Monitors have
the advantage of fire extinguishment without close
6.7.2 Li~itations approach, resulting in less personnel hazard. Also,
less time is required to prepare for foam applica-
When po able monitors or hose streams are used, tion, resulting in faster extinguishment, especially
low prod ct levels and intense fire may create up- for numbers of closely spaced tanks up to about
drafts du to the chimney effect. These updrafts 15 m (SO ft) in diameter. Foam mon itors are effec-
Will prev nt sufficient foam from reaching the tive in fighting large spill fires, such as those in
product urface and forming a foam blanket. tank impounding basins. However, industry ex-
Roam sh II be applied continuously and evenly perience indicates that foam monitors and foam
t~ establi h a foam blanket. Foam streams should hose streams are ineffective in fighting tank fires
be directe against the inner tank shell so that the in water-soluble materials, which require extremely
foam flo s gently onto the burning liquid surface gentle foam application.
without u due submergence. This may be difficult
to accom lish in wind conditions because,depend- 6.7.4 Application
ing on vel city and direction, wind reduces foam
S1freame ectiveness. The foam solution rate of Refinery and petrochemical plants normally have
6.5 (l/mi )/m2 (0.16 US gpm/ft2) of tank liquid 227 m3/h (1000 US gpm) foam monitors on fire
surface ar a, being 60 percent greater than fixed- trucks, as well as 114 m3/h (500 US gpm) and
system fo m rates, results in considerably higher 227 m3/h (1000 US gpm) wheeled foam monitors.
water an foam liquid requirements. Care shall The operating characteristics of these devices are
be exerci d when foam is applied by monitor or as shown in the tabulation below.
114 m3fh (500 US gpm) Monitor 227 m3/h (1000 US gpm) Monitor
Straight Stream
Nozzle Pressure Solution Flow Foam Ran""
Ba~ d on an application rate of 6.5 (L/min)/m2 easily handled containers to meet requirements for
(0.16 US gpm/ft2) of tank liquid surface, the re- foam hose streams.
qu red solution rate when using monitors can be
de ermined for the various tank sizes by multiply- Table A-5 lists pressure requirements for typical
ing by 1.6 the values given in Table A-l. foam nozzles of various types of manufacture
which are usually rated at 690 kPa gage (100 psig)
6.s1 Water Supply nozzle pressure. Normally, nozzles rated below
23 m3/h (100 US gpm) are used for 38 mm (11/2 in.)
6.81 Design Basis hose lines, while those rated at or above that f"ange
are u~d for 64 mm (21/2 in.) hose I ines. The listed
Mi imum solution application rates required for foam truck discharge pressures would also be the
con roof tanks for subsurface injection or topside foam or water hydrant outlet pressures required
foa application and foam hose streams are shown for the alternate designs. The minimum foam hose
in able A-1 on the basis of tank sizes. The flow- stream requirement is a solution rate of 11 m3/h
rate of the foam liquid concentrate shall be deter- (50 US gpm). Adjustment can be made in the num-
min d by multiplying the solution rate by 0.03 or ber of foam hose streams required when greater
0.0 , depending on the percentage of liquid used. capacity foam hose streams are provided.
Coo ing stream requirements are also shown. Thus,
6.8.3 Fire Mains and Hydrants
the otal water requirements for fighting the larg-
est one roof tank fire can be determined from
The fire water needed for foam generation in any
Tab A-1.
tank field (based on the largest cone roof tank
requiring protection) can be determined from the
6.8.~ Water PressureRequirements data contained in Paragraphs 6.8.1 and 6.8.2 and
in Table A-1. In large refinery or petrochemical
Wat r cooling streams for tank shells are usually plant tank fields or similar installations, fire water
take directly from fire hydrants. When hydrant for cooling streams shall also be considered. In
residual pressure is below 552 kPa gage (80 psig), designing the fire water system for complete tank
fire ruck booster pumps are used to supply hose protection, fire water mains shall be arranged as
strea s. For the purpose of calculation, 57 m3/h a looped or grid system to supply the design flow
(250 US gpm) cooling streams shall be utilized. at the minimum residual hydrant outlet pressure.
Such a cooling stream will reach over the curb
angl of a 23 m (75 ft) high tank from a horizontal Table A-1 lists total fire water requirements for
dista ce of 20 m (65 ft) based on 345 kPa gage foam and cooling water by tank size. The design
(50 sig) nozzle pressure when a 29 mm (11/8 in.) fire water flow for a given tank field is based on
solid stream nozzle is used. The minimum residua! the largest fire water requirement for a given tank,
hydr nt outlet pressure in the tank field shall plus cooling water for adjacent unshielded tank-
be 5 2 kPa gage (80 psig) to supply 345 kPa gage age. Depending on tank spacing, the design fire
(50 pig) nozzle pressurewith 11 m3/h (50 US gpm) water flow mayor may not be the total require-
flowi 9 through 76 m (250 ft) of 38 mm (11/2 in.) ment for the largest cone roof tank becauseof the
hose. Table A-4 in Appendix A showsthe approxi- amount that may be needed for cooling streams
mate effective range and pressurerequirements for to protect unshielded tankage. The fire water
nozzl s of various sizes when a "fair" stream is system should be designed to provide at least
provi ed. 690 kPa gage (100 psig) residual hydrant pressure
(see Paragraph 6.8.2) at design flow when cooling
Foam hose streams (see Appendix A, Table A-5) streams are used directly from the hydrants. When
are a umed to be supplied from a foam fire truck. fire truck pumpers are available to furnish cooling
When a fixed foam system is installed: foam hy- streams, the residual hydrant outlet pressure can
dran piped from the system can be used for foam be reduced to not less than 345 gage (50 psig).
hose reams. Thus, the foam hose streams may be Minimum pipe size for the fire main shall be NPS8.
suppli d from foam fire trucks or foam hydrants,
or th hose streams may be supplied with water 6.8.4 Division Valves and Fire Hydrants
from nk fieid fire hydrants and the foam nozzles
can b equipped with pickup tubes. However, there (a) Number of Valves and Hydrants -A suffi-
must hen be sufficient storage of foam liquid in cient number of division valves shall be provided
MOBIL ENGINEERING GUIDE
so t at any section of the fire main grid or loop on sleepers. Wet barrel hydrants shall be used
may be removed from service while fire water with abovegrade mains, while the self-draining
cont nues to be supplied for tank fire protec- compression type shall be used with belowgrade
tion. The system pressure drop calculations mains. Hydrants shall be at least one tank
requ red to size fire mains shall be made on the diameter from the tanks but not less than 15 m
basis of all grid sections open with parallel flow. (50 ft) from the tank shell. Hydrants should be
The umber of division valves needed for system able to protect several adjacent tanks if spacing
retia ility shall be based on no more than six permits.
hydr nts out of service as a result of a single
main break. A sufficient number of hydrants Hydrants with pumper connections shall be
shall be provided to permit fire fighting opera- placed so that a foam truck can approach within
tions regardless of wind direction. The tabu- 1.8 m (6 ft) for quick and easy connection.
latio below shows the number of hydrants Where 64 mm (2112in.) outlets are used, the
need to satisfy these requirements for various distance shall not be more than 9 m (30 ft). This
tank izes. distance permits foam truck connection with the
use of 15 m (50 ft) of fire hose. Following are
(b) ydrant Size -The hydrant size depends other recommendations in locating hydrants in
on t e water equipment and number of hose a tank field:
strea s needed. A 100 mm (4 in.) hydrant will
fumi h 114 m3fh (500 US gpm) and a 152 mm (1) Sufficient hydrants should be located so
(6 in.) hydrant 227 m3fh (1000 US gpm). A that no more than 76 m (250 ft) of 64 mm or
203 m (8 in.) hydrant is needed for high flows. 76 mm (2112in. or 3 in.) hose is required for
The 52 mm (6 in.) and 203 mm (8 in.) hydrants each connection for foam discharge from the
are e uipped with 114 mm (41/2 in.) or 127 mm truck to subsurface injection or standard pipe
(5 in. pumper outlets so that suction hose may hose inlets or inlets to foam towers (see
be u d for water supply to a foam truck. The Appendix D) erected against the tank shell.
mini um size for a hydrant in a refinery tank
field hall be 152 mm (6 in.). (2) Adequate ground coverage of the area
should be possible when using 76 m (250 ft)
(c) ydrant Arrangement -Fire mains shall of 38 mm (1112 in.) hose from truck dis-
be so located as to place hydrants outside dike charges. When this is coupled to 64 mm or
walls nd adjacent to roadways. In nonfreezing 75 mm (2112in. or 3 in.) hose, it should be
climat s the mains may be located aboveground possible to use 38 mm (1112 in.) foam hose
Hydrant
Location of Hydrant
Tank Diameter Relative to Size Outlets
m
-I ft Protected Tank* No. rom in. mm in.
*For floating roof tanks over 37 m (120 ft) and less than 61 m (200 ft) in diameter, 'only one
hydrant shall be located in each octant to provide sufficient cooling streams [see Paragraph
6.8.5 (c)].
MOBIL ENGINEERING GUIDE
streams to extinguish floating roof rim fires (2) In the amount requiied for cooling the
from the tank roof or the windgirder (see tank shell in accordance with Paragraph
Paragraph6.3.2). 6.8.5(a).
(3) H'{drant location should permit cooling (d) Floating Roof Tanks -There shall be suffi-
water to be applied to all shell portions of a cient fire water to cool the shell and extinguish
burning tank and to the shell and roof of adja- a rim fire in open-top floating roof tanks or
cent unshielded tanks when 76 m (250 ft) of covered floating roof tanks with double-deck or
64 mm or 76 mm (21/2 in. or 3 in.) hose is pontoon roofs. The numbers of cooling streams
used for cooling streams directly from hy- listed in Paragraph 6.8.5(a), Item (2) for cone
drants. roof tank shells should be sufficient. If a floating
roof is bonded against lightning as specified in
6.815 Storage Tank Fire Water Requirements NFPA 78, and there is no possibility of pyro-
phoric iron deposits due to the nature of the
() Cone Roof Tanks -A cone roof tank has stored material, the fire water requirement may
0 fire water requirements: be reduced to 182 m3/h (800 US gpm) maxi-
mum for ground fire control. For covered float-
(1) The amount needed for fixed or semi- ing roof tanks without double-deck or pontoon
fixed foam extinguishment systems at a rate floating roofs, supply fire water in accordance
of 4.1 (L/min)/m2 (0.1 US gpm/ft2) of tank with Paragraph6.8.5(a).
liquid surface area, in accordance with NFPA
11. 6.8.6 Cooling Water Requirements for
Exposed Tankage
(2) The amount needed for cooling the tank
shell to prevent it from buckling above the Calculation of fire water requirements for a poten-
liquid level and to allow the foam blanket to tial tank or sphere fire shall include cooling water
form a tight sealagainst cooled metal. Cooling streams for adjacent tankage. Allow at least two
streams for this purpose, at 57 m3/h (250 US 114 m3/h (500 US gpm) cooling streams for each
gpm) each, are estimated by tank diameter as adjacent, unshielded floating roof or cone roof
follows: tank or sphere within the following limits:
Tank Diameter
(a) Within 15 m (50 ft) of a tank of any size.
No. of Cooling
m ft Water Streams (b) Within 46 m (150 ft) of a sphere.
Up to 20 Up to 65 2
(c) Within one tank diameter and within the
tank quadrant of the exposing tank that requires
Over20 to 36 Over 65 to 118 3
the maximum amount of cooling water.
Over36 to 47 Over 118to 155 4
Over47 to 61 Over 155 to 200 5 6.9 Foam-Producing Materials Supply
Over61 Over200 6
6.9.1 Subsurface Foam Injection
(b Cone Roof Tanks Containing High-Flash
Li uids -When the product stored has a flash Sufficient foam liquid concentrate shall be pro-
po nt of 60°C (140°F) closed cup or higher, a vided to permit operation of the subsurface system
co e roof tank shall be considered relatively for the largest tank (see Table A-3), plus hose
sa .In such cases,water for foam extinguish- stream requirements (see Table A-1J, to meet the
m nt is not required if the conditions of Para- requirements of Paragraphs6.4.3(aJ and 6.4.3(bJ.
gr ph 6.1.1 (bl are met.
6.9.2 Fixed Foam Chambers or Portable
(c) Cone Roof Tanks with Internal Floating Foam Towers
C rs -Fire water should be supplied as Sufficient foam liquid concentrate shall be pro-
fo ws: vided to permit operation of fixed foam chambers
1) I n the amount requ ired for foam appl ica- or portable foam towers in accordance with Para-
ion in accordance with Paragraphs6.3.4 and graph 6.3.1 and Table A-2 of this Guide and NFPA
.8.5(a). 11,Chapter3.
..
MOBIL ENGINEERING GUIDE
ti n and to prevent flammable vapor accumula- water spray or deluge systems. Foundation erosion
ti ns. The diked enclosure shall be sized to contain may result in loss of vessel support, with sub-
at least 50 percent of the largest tank capacity. sequent failure of the tank. Fixed or portable
In locations where climatic conditions result in 114 m3fh (500 US gpm) adjustable fog-to-straight-
pr longed periods during which pressure storage stream monitors are recommended to protect this
te peratures may be below the boiling point, the type of vessel. Fire hydrants should be located
di ed enclosure shall be sized to contain 100 per- outside the dike walls, at least 15 m (50 ft) from a
ce t of the tank capacity. For refrigerated and low-pressure storage vessel, in sufficient number
c ogenic storage, secondary containment for to supply portable monitors regardless of wind
10 percent of the tank capacity shall be provided direction. Depending on the type of product
by a dike or by a double containment shell. A dike stored, foam may be used to extinguish spill fires.
siz for the maximum probable piping spill shall Dry chemica! monitors or hose streams will also
be provided if a double containment shell is used. provide excellent extinguishment. When portable
114m3fh (500 US gpm) water monitors are used,
Th ground beneath and adjacent to a low-pressure it is suggested that at least two such monitors
sto ge tank shall be sloped away from the tank to (one on each side of the installation) be provided.
pre ent accumulation of vapors or flammable When fixed monitors are used, at least four are
liq ids. Flammable liquid tanks shall be so located needed.
as 0 avoid flow of the flammable liquids into an
are adjacent to a low-pressurestorage tank. Sealed
and valved drains of adequatesize shall be provided
8. HIGH-PRESSURE STORAGE TANKS
to rain the diked enclosure. If the terrain permits,
a d version dike system may be used. It should
con ist of open channels draining to a retention 8.1 General Design
are in a safe location. The retention area may be
High-pressure storage tanks shall be designed and
of imple earthen construction. It should have a
installed in accordance with API Std 2508 and
cap city equal to the greater of the following:
API Std 2510 as applicable and with EGE 12-8-1.
() The volume of the largest diked enclosure
t at would be required for the protected tanks When spheres are not designed to withstand full
i individual diking were provided. vacuum, they shall be provided with vacuum relief
() Eighty cubic meters (500 barrels). valves sized to protect the vessel at maximum with-
drawal rates. Spheres may be designed for full
vacuum, eliminating vacuum relief valves, if the
7.6 \ High Level Alarms -, Overfill Protection vapor pressure of the stored material at storage
temperature is below or near atmospheric pressure.
Ii Lo pressure refrigerated and cryogenic storage If vacuum relief valves are used, provision shall be
.tank shall be equipped with independent high made to ensure that the vapor space remains above
~ level alarms to prevent vesseloverfilling. The alarm the flammable range; otherwise, the vapor space
actu ting device shall be independent of tank shall be inerted. For example, in freezing areas
gagi g instrumentation and shall be electrically where butane is stored, the use of vacuum relief
supe ised (or the equ.valent) for circuit fault valves permits the entrance of air, resulting in a
det tion. The alarm shall sound in a location flammable vapor mixture above the liquid level.
occu ied by personnel during product receipt, An ignition in this type of vessel could result in
such as a control room or oil movements control a detonation.
cent~r. Alternative overfill protection devices
requ~re Mobil approval. Relief valves on ASME Code vesselsshould be sized
in accordance with API RP 520 as well as ASME
requirements. When relief valves discharge directly
7.7 IFire Protection to the atmosphere, they should do so through
vertical vent stacks extending 2 m to 3 m (7 ft to
Beca~se foundation erosion can result from a high 10 ft) above the vessel.A drain should be provided
rate of cooling water application, low-pressure at the bottom of the stack, arranged to prevent
stora e tanks are not usually protected by fixed flame impingement on the vessel.
-
MOBIL ENGINEERING GUIDE
accordance with EGE 34-8-15 for a three-hour Minimum spacing requirements for cylindrical
ASTM E119 fire rating. storage vessels shall be in accordance with API Std
MOBIL ENGINEERING GUIDE
25 8 and API Std 2510 as applicable and with asphaltic cutback mastic coatings and fiberglass
E E 12-8-1. On abovegrade installations, the fabric reinforcing applied between coatings. The
m jor axis of the vesselshall be pointed away from head at one end and a short section of shell may
he ily populated areas, vital or valuable equip- be exposed, and a concrete retaining wall shall
m nt, or large-volume flammable liquid storage, contain the fill over the remainder of the vessel.
wh her located in plant or on neighboring prop- The exposed portion of the vessel shall be fire-
e .It is preferred ti"!at abovegrade vessels be proofed in accordance with EGE 34-8-15. This
10 ted downgrade and downwind from ignition permits the majority of the connections to be
so rces and arranged to prevent any possible flow made outside the fill area at the uncovered end.
of lammable liquids into the vesselarea. Grade the
are and provide drainage so that liquids will not Mounding is usually the most economical method
col ect adjacent to or under the cylindrical vessels. of fire protection where three or more large vessels
In efineries, for maximum protection against fire are involved. This is especially true when the
ex osure, either increase the minimum distance amount of fire water available is minimal, since
req irements given in API Std 2508 and API Std mounding does not require further fixed fire pro-
25 0 by 100 percent or provide specialprotection. tection facilities.
Do not locate storage vesselswithin the same diked
enc osure as atmospheric flammable liquid storage. 8.3.3 Fireproofing
a fire a~ ove certain temperatures. Tests conducted cooling water shall be used to prevent metal sur-
by Eth I and E.I. duPont de Nemours resulted in faces in the vapor spacefrom reaching temperatures
the pe inent data and precautions noted in the that would initiate surface decomposition. Com-
followi 9 paragra.phs. mercial TM L antiknock compound is ignitable at
ambient temperature in the presence of air, but it
tretraethyllead burns slowly. Water is an effective fire extinguisher
for commercial antiknock mixtures. It collects on
TE L co~ tains scavenging agents and is not classi- the surface of high-density commercial antiknock
fied as a flammable liquid because its closed-cup material, eliminating fuel supply to burning vapors
flash pint is above 930 C (2000 F). The TE L con- and preventing reflaming.
tent wi I start to decompose at about 110°C
(2300F). 9.2 Site Location and Spacing
When E L is heated above 110° C (230° F), the Blending plants and their storage facilities shall be
rate of its decomposition increases slowly as the located so as to minimize the possibility of fire
tempera ure rises. If the compound is held at tem- exposure. The preferred distance is a minimum of
peratur above 170°C (338OF), it will detonate 46 m (150 ft) from flammable liquid storage,
upon e piration of an induction period that process units, or other similar refinery equipment
shortens as the temperature rises. Detonation will and a minimum of 61 m (200 ft) from property
not occ r below 170° C (338° F), but the induction boundaries and normally occupied buildings. The
period ecreasesfrom an indefinitely long time at blending facility shall be protected from inflow
that te perature to about two minutes at approxi- of flammable liquids from other areas by suitable
mately 30° C (446° F). Tests have shown that dikes or diversion walls. Do not locate the facility
contents of the entire tank or container must be near or downgrade of cone roof tanks containing
elevated to the indicated temperatures before hydrocarbons with boilover or frothover character-
detonati n will occur. However, the detonation istics (see Appendix F).
tempera ure may decrease if the scavenging age.nts
are lost hrough vaporization. (See Paragraph9.4.) 9.3 Drainage
Tjetramethyllead and Methyl-Ethyl Weigh tank pits should be provided with a valved
~traalkYllead and sealed drain sized to prevent accumulation of
flammable liquids beneath the tank. The drain
TM L an ME L may decompose when bulk de- valve should be of the rising-stem type, easily
composit on occurs homogeneously throughout accessible and visible, and normally closed. Raise
the liqui .Decomposition may also occur in the the grade beneath storage tanks, other than weigh
vapor at the liquid/vapor interface as a result of tanks containing antiknock compounds, so that
surface aporation. Both reactions become self- drainage is away from the area beneath the tanks.
sustainin above certain threshold bulk tem- Do not provide sewer catch basins in the area
peratures Both TML and MEL and their diluted beneath the tanks. Store drums on raised concrete
composit ons, as used for commercial antiknock pads or on loading docks arranged for drainage
material, are thermally more stable with respect away from the drum storage area.
to bulk ecomposition than TE L and its diluted
composit ons. However, TM L compositions and. 9.4 "Time Available" Factors for Fire
to a lesse extent, those containing MEL are more Extinguishment
sensitive 0 surface decomposition than TE L.
The following "time available" factors, based on
The bulk temperature of TM L commercia! anti- severe exposure of TEL or TML, may be used to
knock m terial must be above 100°C (212OF) for estimate the time available for fire extinguishment
self-sustai ing surface decomposition to occur. before the heat input causescompounds to reach
Surface ecomposition, unlike bulk decompo- their decomposition temperatures. (Note that
sition, re uires initiation by an intense energy allowance must be made for any elapsedtime prior
source, s ch as a flame or hot metal surface in the to discovery of a fire.) These factors are based on a
vapor ( Paragraph9.4). Therefore, in the event compound being stored in a weigh tank, with a
of fires round tanks containing TM L or ME L, gasoline fire in the pit, vent closed, and fixed water
MOBIL ENGINEERING GUIDE
f
SP Y system not in operation. The time available guishment of small fires in accordance with EGE
is that required to start cooling water spray from 41-8-63. Provide a 38 mm (11/2 in.) live hose reel,
fi ed water spray systems or portable monitor strategically located for access and fire fighting.
fir nozzles to extinguish the fire, or to evacuate Protect tank storage or weigh tanks containing
pe nnef frbm the area. antiknock compounds with a fixed water spray
Time Available system designed in accordance with EGS 643.
Condition (Minutes) Locate strainer and control valve as remotely as
possible. If tank location is in a remote area, it "may
1. 4536 kg (10,000Ib)TELorTML TEL -15
be advisable to provide automatic operation of the
compound in tank, regardless of size TM L -13
fixed water spray system as described in EGS 643.
.11,340 kg (25,000 Ib) TE L or TM L TE L -25
compound in tank, regardless of size TM L -24
Drum storage of antiknock compounds should
.45,360 kg (100,000 Ib) TEL or TM L TEL -60
be protected by a fixed water spray system or
compound in tank, regardless of size TM L -59
fixed monitors. The system shall be designed on
OTE: If a fire that may endanger an antiknock the basis of fire intensity control with a water
mpound blending installation occurs, the nearest
density of 16.3 (L/min)/m2 (0.40 US gpm/ft2) of
mpound manufacturer's representative should be
otified immediately after initiation of plant fire horizontal area. If outdoor storage is provided and
ighting and safety procedures. fork trucks are utilized for stacking drums, adjust-
able fog-to-straight-stream fixed or portable moni-
9.51 Fire Protection Facilities tors provide more suitable protection and permit
safe, easy fork truck access. A sufficient number
A s~fficient number of 14 kg (3D Ib) dry chemica! of monitors shall be provided to cover the area,
han~ extinguishers shall be provided for extin- regardlessof wind direction.
(PAGE 26 OF 67)
MOBIL ENGINEERING GUIDE
APPENDIX A
.
MOBIL ENGINEERING GUIDE
EGS 62~ 1986 PAGE 28 OF 67 MAY 1986
E
-Co
~co =
~-
-CI)
c'C~
==~
c'5
00".:
I-~i;;-
a: E
~
Z
LI.J
~
~
~
~
~
z
~
X NNNN NNNN MMMM MMMM ~~~ ~~ ~~ ========
LI.J
LI.J
~
u..
~
Z
cx:
~
8
u..
~CM~ N~~~ MC~~ N~N~ C~~ ~~ N= ~~CN~~~~
Q ~~~~ ~~~~ C~~M ~~CM === M~ ~~ ~~~MM~~~
Q -~~- --NN NM~ ~~ ~~ =CN~~=CM
~ ~-~~-NN
LI.J
Z
Q
u 0000 0000 0000 0000 000 00 00 00000000
=~~~ =~== 0000 0000 o~= == ~= =~=~==~=
~
Q
u..
~
~ MMMM MMMM M~V ~V ~~ VV~~~V~~
Z NNNN NNNN NMM MM MM MMMMMMMM
LI.J
~
LI.J
~ NNNN ~NN~ NMM MM MM MMMMMMMM
~
d
LI.J
~
Z
0
~
~
-I ~~~~ -==~ o~~~ ~~~~ ~oo -~ =~ ~~~==~~~
Q ~~MM ~~~~ ==~- ~~~- =~= o~ ~- ~~O~O~=-
~ ~ ~M~ ~~ ~~ =O~M~=OM
~~
~
cx:
Q
u.. It) ~
=ONIt) =O~O ~OMO =000 O~O 00 00 00000000
Q ~~~~ v==W ~~~= =~O- ~~v =~ =0 ~~~=O~v~
Z ~- ~ ~~~~~~~~
cx:
~ ~~ ~ ~~=~ v~~~ ~~1t)1t) ~=~ ~= ~~ -~~~v=W~
LI.J ON~M ~~~= O~N~ ~~OM ~ON ~= ~ci ~M~~~~M~
~ ~ ~~~~ ~~~~ ~~v v~ =~ ~~~=~~~~
cx:
:::
00 -0 0 o>-m==~=-
~~ = ~ ON ~ ~""O ~N~.o -= N-mmmm~~
.0=-- --N ~~ ~ .o~~ m-- --N~ ~.o.o~~ ~
..I I I I I I I I I I I I I I I I I I I I I I I I I I
~~O- N~.oO = O~ O.o~ oom.o~ O~ -~mm~~ =
N NN~~ ~~~~ =00 N~ ~N ""N~~O~~-
N N~~~.o.o~
""""""""00"" a)
~~ ==~ ~~~ =..,. m~~oo~ ~
~N v.r-: ~ ~-: r-: mON ~mo..".~ ~ COa)OO~~""""~
I I ""N ~ ~= = -~ ~~ NN ~= ~~~~~
= I I I I I I I I I I I I I I I I I I I I I I I I
~..".=~ 00 " O~~~ .." ~= ~~~ OO~ =~ ~~""a)~ a)~
~~~~ ~NNM ~~ ~~=o N~~ ~N =~ ~~omci~N~
~ ~~~~ N~ ""'=CC=a)OO~::
~
.
MOBIL ENGINEERING GUIDE
MAY 1986 PAGE 29 OF 67 EGS 626-1986
...
0
E "'-"~
"':::'~c:
"'..
-;;;0
-~
COc:
co
...,
...
-COo. c:co co-
"tJ -o.oco- .c., ~--co 0
.r; ...
>
4'~~01--
-~.,~.co
=-
.r;e
E...
0.0
E ~
CO .r; -0) -0.- = E
t::;;"" E ':::'~
"'C:O)-coco --tf)--c: c:";
00"'-.=
., 0 =
-0
-co ..~ 11) > -; co -' ..."tJ
4'-"";-"tJ "tJ~.c- E c S
~ r;o> ., ~o"'.r; =
mo~..E- CQ",:c:-.~ "tJ
> --~ ~ ":5 M E C .,
c: ~ c: ~ '" ..0) c: E .-., "tJ
r; c:
°.- c: E E "tJ
~
",>-=",..
"> m l-
~ 0
o ""~~..0.
tJ "tJ .-"'"tJ
.r;
o.r;~o_o. C:oO" -0) ":5 C
-"'--o~
.,'"
.r.
- 0)
E .=-CQ
-" c: .,co---
"tJ-=.,.r.
.c-~"-"0
CO
0.
c:
-;
=
-"'-
"">- =.r.0) ;~.£ X c: E
~>.2'> .r;"'co C:"tJ ., ~ ~
"tJUCD..O)CQ "tJtJ..9;., "tJ '"
~COc:O).r;.r; -:'-0) -"tJ ~ >- >-
",c.-o. .. E ~.c~"tJ --'"
=co-o.~., 0" -= -~ c:
., tJ .r;
-=" ~ C ...0.= 0. CQ "'0)
C 0 -=
~ E --
..O)
="tJ".r;-
E tf)~"tJ
tJ.c c:
co 0 E
~~ I- -= -.c:§: C:"tJ -.::: 0)
"'-.. ~-"tJ -'co> co-..
Q)CQ=.
E t:-";:"tJ c: -""0
.r;-.r; ~
E .f:.
"' 0
-~ "tJ
-.-..
-o~ ",-~-
~"~CQ-
o.~CD-':::'
;;-0'"
E~'"
ca'"
., =E '"
.,
-0.
:=
0. .-'"~
>0."-'" ~o;:;co ~ ~ 0
O~ EE "'o c_.r:. "'., "-
>-
> CQ -<0
M -
-0)-10"-
.r."tJ.co
., E E =-
_c.
"""
0.,
0)
"tJ
~
.c~ "tJ
.,
'"
EI-~O>~E =o.e.s='" -"tJ ~
--'- E ..-0 tJ -.,
~ .~- "'. c:tf)- E.r. oS ~ .c
.. -_ ~ 0 ~ '.- ., ca...
0 =0. = ~'"~- -~
-5._0~'" o=>c
o .r.o--.r;c: ~.:::. -o::-~
~ -., -CQ ~
..wo 0
~.-~-;; ~ 0.-"tJ~c:- ~-.- ---'" 0 E c: E .r;
.~-0.0),,;:=;;:' N ~ 0."" 0 a;
~ tJO4'.r;- EE'" ~o.c:- ..>-
w ~~~~o?E ~:::.~.ctf)E:? t: ~
-J '8 "~~0cc.-C:0) E=>.r; ~ ..~
a1 E ---~~ "tJ- E E ~o.!!!. 2 '"
~ ~N.r... M'- Q) CO C:1O~ E ca ..
I- c: '-~O E-- -=::1:0 E -o. ca ~ ~
0
coN.r.-
-~ ..10
E o
'"
~--
0" 0
.r.C:
~-."Z-'"
o.
C)-
CQ
>
~- .-., ~ EM X E c: >- >
I- ---0>.-
"",--"'<0- ...", --=co E -0. CQ
tn g'~~2. M.~ O)~~ c ., -~ 00.-
W --co~CQO°O) .r;-CQ 0;:; o~ 0
I- tf) >-~.r;l-o_~.-;;:I-"'(.)wol-
0
Z .-N M ~ 10 CD
MOBI LEN :ING
EGS626-"S' MAY 1986
, OLt)OO OOOIr) ~ooo 000= ==0= ===
~
~
C)t'lq-Lt)
~~~ ---N
""~a>~ N~a)~
MMM~
C")V~O
V=CDa:I
~O)O)cc
0)"-('-1'0;1"
~~O)
CCO~
-C'JN
E
..I =-
=- =.- -I -MO=
'o:t"r-MCC
M'o:t"u-,u-,
""~-N
." c.r-
COCOr-c.
or-=&l')
M=MCC
NNo:t-CC
1r>v..rr--.
1r>Vr
=O1r>O
r
~MMLr)
~~~"""
,...Lr)~Lr)
CCO~
N~~
Nr-~
0>LJ..-cO
0 -;;;- -NNM M""",,,,"Lr) CCr-O")
"'~==
-~a:=
---,
CN
Q ...>-
LJ..
c..~==> -;; 0=00 ~c~~ 0Lr)Lr)0 OOLr.O Lt)Lt)Lt)U") ~Lr)~
cn
~
2
':00:
"'~=X
~(O).c
LJ..==-I
co
CI)
~
NCD=O
~~~N
N'O2"~N
NNNM
(")CCOO
~~Lr)CC
COM-a>
COr-a>O
- N-U)U")
NCCr---=
~OM
C'-.I=V
C'JC'JM
<
~
&&.
~~..-,
~N=~ N~tr}O
tr}OtCM
~o
('icc..-r- a)MMCO
mCOCON
r MMO
M~vO
c)..-o
r-r
0 ~(C(C, ~c)c)N- ccr-C)('i q-r-.q-~ CC~CCv
v- co' CO-r ' ~coc
0
..- ' ('i-
N- N~ M~ q-~ =- c~ C")~
u:
w
2
0
u
= ==0=
OvCDr-
~c~~
C)..-Na:> ~-..,.-..~
ooo~ ==00
r-MO=
===0
=ONM
==0
":t"~=
0 ..-NNN M..,...,. =tCa)C) ~'d"=r-
~~~~ ..-~~
C>":t"0")
&&.
~~II Co'---I -~ r-..O)CON ~"'c-..JC) ~N~o) cccc=cc
r-CCNC)
N=N= :t-
r-.-r
N=~
wU
m=
0)",,"0 CO MC)"'r-. M~CD~
MMr-.= M..-N
CCr-O
~Q
<0 .=
o~o
""01"0
M- ---
-===
-
M.r>COCO r-. r-. ~ O.
~
~, ~, CD, 0), -MC)u-.
N-N-M-M- -.:t-~=~ =~ CC~ r-'=~~- ~
X= C N~- ~O
UA. CoCC ~=
C&&.
-=--=~
'" ..C
--u.. .-C .-
20 ~~O
u.. .=~ ~ m= =OL&)O
CCN-::-r-
Lt)00Lt)
OM&nLt)
ccU')U')
CJ~CJ~
LnLnOO
~~r-..N
=0==
M=od"r-
==0
===
~<cnJ: ""=0. ... ~ -NNN MM~~ U')cccc~ C)ONLn ~NV~ -Q)=
MM-.:z-
<CI)~c ~
W=~ M=~ ~ ~ ~~~ ..-NNN
.oJWC Q
=~a..~
LnMr-N 'o:!"ml.nN MN-= ~~r-~ =CCv-
v~=a:>
~or-
-
cco::tOLn 'O:j"r-Ln
~CX '" NMNN ~'o:!"NN MNM=
=- =- ""'- a:>- ==M
~~cn.~
~< .~
CC~c)Q-
.-_~-
.-~ N~ C?~ r-.~ N~CCO
N-N-N-M- o::t~ aJ~
~~o::tLn
aJ~ r-~
cca>== - ..-~ 'O:j"-~-
<.oJ C
O&&. ;
&&.20'
~C
00 -=
= =occ=
r"-o:t"ccC)
Lt)Lt)OO
~C)wC)
cccc
c..-C)(O
Ir>OOIr>
OW~1r>
U')Lr)O
U')NN
&&.w '" CI) .--NNN wwr-a:. 0..-(")(0 O~cgO ~C")C")
wcn ~ ~ ('-1('-1('-1(0) C")q-U')
=<
<m I
.c
E
c N=r-.r-. mMa:lM --""0) ~ C"') Cf)-'o:t'(¥)
°--
r-..occ
~ 3 I~ ..c COOO- vM""CC =occ= =-'o:t'CC
-' -=ta:lr-m OM-
r-..r-..M
~
cn
0
-u...=",
~o
~Qm-=
C-CJ
y --' co ~ O,-,
-- C'J.M. -.,r-~- vCC~M
N~N~N~M~
r-.~ c-.,~c-.,~c-.,-
C"')-.:t~cc
=. (¥).-.=.
r-Cf)C- -- M- CC-0-
--N
w "'Q2~
c =- "'~ f-'
'< .-CJ
~ °f-'c==~
Q..o =C)==
0",","'"'0 ===
~
2 '=~o
'" .'"
~OO~
OQ:l--ot-
Ln Ln
~-'o:t"~
Ln L-")
"'"'-~o:t"
r-~~0
0000
r--OC"'lir> """=~~
M=-Lt)
===
w
U
m""m
u:("')~
NNMM M'=t"'o:t"=
~
-(0)(00)
c...Ic...IM~ v=cc
OCC'-l
2
C r od-od- ==0=M==(") 0)"-"'0) CO-":!"r- a:I=tr>
U ~r-.=..- NNM..- r-ooo ",,"~r-..
~
CO)
od-~CCN
N-
=0(")=
N~ (")~ (")~ (")~
~- 0)-..-, ~,
~",,"CCr-
---
=a:la:lCC
=- 0- --c-)-
c")<"cc
=' 0')' C")'
--<"
...
GO
-a;
E
- ~
=O~=
C")~~~
a:JONO
~==CC Lr>OOO
a)a>O~
~~
o..;t-oo
---~
NM~=
r-.t"!o.r-. CCN=.-? ~CO"'.CO"'.~ a.r5r-:c::iM
Q)~== IWONa.r5
cc~ ~~~
E O~MM .,,:.n..c>a; o-~~
~~~N ~c-.JC')C') M,",,"~~
=":!"o
":!"LnCO
GINEEF
MOBIL ENGINEERING GUIDE
TABLE A-3
FOAM LIQUID STORAGE REQUIREMENTS FOR SUBSURFACE INJECTION
PROPORTIONED AT 4% INTO CONE ROOF TANKS
BASED ON FLASH POINT OF PRODUCT
Foam Quantities Shown in L (US gal)
FlashPoints
Flash Points Below 37.8°C-93.4°C Flash Points Over Add for
37.8°C (100°F)- (100°F-200°F)- 93.4°C(200°F)- Hose
Gasolines,Naphtha, Kerosine,Fuel Oil, Lube Oils, Residuum, Stream
Tank Diameter All Crudes DieselOil HeavyFuel Oil Requirement
m, ft L US gal l US gal l US gal l
48.8 160 16,749 4,425 9,140 2,415 7,608 2,010 511 135
54.9 180 21,196 5,600 11,544 3,050 9,633 2,545 511 135
60.9 200 26,154 6,910 14,270 3,770 11,904 3,145 511 135
67.1 220 31,643 8,360 17,263 4,561 14,383 3,800 511 135
73.2 240 37,661 9,950 20,553 5,430 17,176 4,530 511 135
79.2 260 44,209 11,680 24,110 6,370 20,060 5,300 511 135
85.3 280 51,287 13,550 27,971 7,390 23,315 6,160 511 135
91.4 300 58,857 15,550 32,097 8,480 26,760 7,070 511 135
97.5 320 66,995 17,700 36,525 9,650 30,470 8,050 511 135
103.6 340 75,585 19,970 41,257 10,900 34,370 9,080 511 135
109.7 360 84,746 22,390 46,253 12,220 38,530 10,180 511 135
.
MOBIL ENGINEERING GUIDE
TABLE A-4
TYPICAL PRESSURESAND EFFECTIVE RANGES FOR WATER HOSE STREAMS
Fire Hose: 76.2 m (250 ft) Long and 63.5 mm (2Yzin.) in Diameter
Distance from
Cooling Hydrant Tank
Stream Outlet Nozzle Range 14.6 m (48 ft)
Flow Pressure Pressure -Diameter Vertical Horizontal High
~/h US kPa gage psig kPa gage pSIg mm in. ft m ft
~ 15 411 60 310 45 22.225 7/8 24 78 19 61 14 46
to 17 550 80 430 62 22.225 7/8 27 87 22 72 18 59
t5 20 720 105 550 80 22.225 7/8 30 99 25 82 22 72
.~5 2 430 70 310 46 25.4 1 24 79 20 67 15 50
~7 25~! 550 80 310 45 28.575 1'/8 24.3 80 22 72 16 54
TABLE A-5
TYPICAL PRESSURESAND EFFECTIVE RANGES FOR FOAM HOSE STREAMS
NOTES:
1. Pressure requirements for 38 mm (1'12 in.) foam nozzles are based on friction loss in
61 m (200 ft) of 38 mm (1Y2 in.) fire hose. Pressure requirements for 64 mm (2Y2 in.)
foam nozzles are based on friction loss in 76 m (250 h) of 64 mm (2Y2 in.) fire hose.
2. The minimum foam truck discharge pressure to meet the 11.4 m3/h (50 US gpm)
foam hose stream requirement is 620 kPa gage (90 psig). If the foam hose stream is
supplied from a foam or water hydrant, a residual hydrant outlet pressure of 620 kPa
gage (90 psig) is also required. I
~
MOBIL ENGINEERING GUIDE
LEGEND:
FNHT -Female National Hose Thread FNPT -Female National Pipe Thread
MNHT -Male National Hose Thread MNPT -Male National Pipe Thread
FIGURE A-1
HIGH BACK PRESSUREFOAM MAKERS
MOBIL ENGINEERING GUIDE
FIGUREA-2
SEMIPORTABLE SUBSURFACE FOAM SYSTEM
MOBIL ENGINEERING GUIDE
STORAGE
TANKS
PRODUCT
MANIFOLD
FIGURE A-3
FIXED SUBSURFACE FOAM SYSTEM
MOBil ENC:;INEERING GUIDE
./; -// // /, // // r
FIGURE A-4
TYPICAL DISCHARGE CONNECTION IN TANKS
.
MAY 1986 PAGE 37 OF 67
--
E
0
<
w
r
FIGURE A-5
STATIC HEAD CONVERSION CHART
MOBIL ENGINEERING GUIDE
-
E
0
<t
w
:I:
FIGURE A-5
STATIC HEAD CONVERSION CHART
MOBIL ENGINEERING GUIDE
FIGUREA~
FOAM VELOCITY vs NOMINAL PIPE SIZE (NPS)
(601414
I I (50) 345
~
...
is (40) 276
0
S
-;;
~
~ (30) 207
~
~l
.JI
I (20) 138
~i
Ii (10) 69
I I I ,FOAMR~TEL/S(U~9pm) I I I
13 25 38 50 63 76 88 101 114
(201"\ (400: (600) (800) (1000) (1200) (1400) (1600) (1800)
FIGURE A-7
FOAM FRICTION LOSS -NPS 2% AND NPS3 PIPE '
(4 Expansion)
MOBIL ENGINEERING GUIDE
(50) 345
-0
;!
E (40) 276
0
M
;:
E:
~ (30) 207 ,
.¥
(I)
(I)
0
...J
~ (20)138
~
u
a:
II.
(10)69
I I 1 I I I r I
FIGURE A-8
FOAM FRICTION LOSS-NPS 4 PIPE
(4 Expansion)
? (SOl 345
0
0
E 140) 276 ~!
1301207l
§ I
"3 (201138 "-
-I
~ I
~ I
NVSB
(101~r0' , , I , , I ~~ , I I
101 151 202 252 303 353 404 454 505 555
(1600) (2400) (3200) 44000) 44800) 45600) (6400) (7200) (8000) (8800)
FIGURE A-9
FOAM FRICTION LOSS -NPS 6, NPS 8, AND NPS 10 PIPE
EGS 626-1986 PAGE 40 OF 67 MAY 1986
-
-
0
0
E
0
!:!
:§:
m
~
~
(I)
(I)
0
..J
Z
0
~
~
Ir
II.
FIGURE A-10
FOAM FRICTION LOSS-NPS 12 AND NPS 14 PIPE
FIGURE A-11
PHB-10A TO 30A: SOLUTION AND FOAM CAPACITY
vs INLET PRESSURE
MOBIL ENGINEERING GUIDE
(2001 1379!
-c,
""
~ 1'80)1241~
"'/ (72)496
-~
E:
m
~
m
=
0 ,' m
~
~ I ~
(641441
~ (160)1103~
(56)386 ~
(140)96b
-u
<{
m
(1201827 (~331
-I I I (40).276
FIGURE A-12
PHB-35ATO 55A: SOLUTION AND FOAM CAPACITY
YSINLET PRESSURE
551(801
(200)1379
~
!!:
496(721 ~
~ (18011241 -=
~ co
=
Q.
= -"'
=
=
c. 441 (641
~ (16011103
oX
II:
386{56) ~
(1401965 -U
a: «
a)
Co
...
W
331(48)
~ (1201829
276(40)
30 35 40 45 50 56 61 66 71 76
(480) (560) (640) (720) (800) (880) (960) (1040) (1120) 112001
SOLUTION Lis (US gpmJ
120 140 160 180 200 222 242 262 284 304
(19201 (22401 (25401 (2880) (3200) (3520) (3840) (4160) (448QI (4800)
FOAM (4 EXPANSIONI Us (US gpmJ
FIGURE A-13
PHB-60A TO 100A: SOLUTION ANO FOAM CAPACITY
~ INLET PRESSURE
MOBIL ENGINEERING GUIDE
APPENDIX B
TYPICAL SUBSURFACE FOAM SYSTEM CALCULATIONS
EXAMPLE I
Required Data
Tank size ..., 36.6 m{120')dia.x12.2m (40') high
I
Product , Nonvolatile fuel oil (spgrO.84)
Product inlet line size. NPS 12 dia. x 91.4 (300') equiv.length
Max. allowable inlet velocity. 6.1 m/s (20 his)
Max. static head 10.7m(35')
No. hose streams required. 2 [see Par. 6.4.3{b)]
From Fig. A-10 find friction loss in NPS 12 product line from foam maker
to tanks:
273 m3/h (1200 US gpm) foam at 0.1131 kPa!m (O.5 psi!l 00')
x 91.44 m (300') = 10.34 kPa (1.5 psi)
Total pressuredrop:
76kPa (11.0psi)
~ ( 1.5 psi)
86 kPa (12.5 psi)
Because the B6 kPa (12.5 psi) is less than the maximum allowable back
pressure of 414 kPa (60 psi), the design is acceptable.
Minimum flow at 1027 m3/h (4524 US gpm) = 3.9 m/s (12.7 his)
MOBIL ENGINEERING GUIDE
EXAMPLE
n
Required Data
Product inlet line sizes (dia.: NPS 14, NPS 12, and NPS 8
.Place foam makers outside dike at least one tank diameter from nearest tank being pro-
tected. Following are the requirements in event of a fire: in tank No.6, all four foam
makers; in tank No.7, three foam makers; in tank No.8, only two foam makers. I
MOBIL ENGINEERING GUIDE
Because the largest tank is 36.6 m (120') in diameter, use four PHBi30 high
back pressure foam makers in this system.
MOBIL ENGINEERING GUIDE
Total pressuredrop:
Tank No.8 has the greatest pressure drop. Use for design 132 kPa (19.15
psi), which is lessthan the maximum allowable back pressure and is, there-
fore. accePtable.
MOBIL ENGINEERING GUIDE
Tanks No.6 and 7 are acceptable. Tank No.8 is unacceptable because the
velocity exceeds 3.05 mls (10.0 ft/s) , the maximum allowable velocity for
volatile material. Therefore, any of the following alternative methods may
be used:
(a) Install a larger inlet connection if the larger line extends at least
20 pipe diameters outside tank shell.
(b) Inside the tank attach a larger inlet line, approximately 20 pipe
diameters in length, to existing inlet.
(c) I nstall a new connection on shell near existing inlet and tie into inlet
line.
In this example we use alternative (c).
APPENDIX C
TYPICAL CATENARYFOAMSYSTEMARRANGEMENT
The foam solution piping shall be properly supported and located above-
ground to minimize external piping corrosion and allow visual inspection of
the piping. This will also ensure that proper drainage of the piping can be
provided. The piping shall run from the foam connection outside the dike
wall to the tank riser at the tank shell (see Figure C-1). To prevent damage
to the piping from exposure to fire in the diked area, the earth under the
piping shall be graded so that the piping is at the high point of the diked area
and no flammable liquid pool can collect under the piping. If the system is
semifixed, it is preferred that the foam solution siamese manifold be located
outside the diked area, a minimum of 30 m (100 ft) away from the tank,
and adjacent to the roadway. A fire hydrant should be located within 30 m
(100 ft) of the manifold.
FIGURE C-1 (
SEMIFIXED CATENARY FOAM SYSTEM -DIKED AREA AND RISER PIPING
.
MOBIL ENGINEERING GUIDE
Tank riser piping shall be suitably supported and attached to the tank to
minimize piping movement.
The swivel joint shall be on center with the ladder swivel rod to minimize
stress on the flexible hose connection.
ladder piping, which shall be securely attached to the side or bottom of the
tank roof ladder, shall be arranged so that it lines up as close as possible with
the outlet of the swivel joint. The ladder piping shall be provided with an
automatic drain at the low point of the bottom elbow (see Figure C-2).
SWIVEL.lOINT
SOLUTION SUPPL Y
FROM FOAM SYSTEM
OR FIRE OEPT ~. -
CONNECTION ---, , ':"""
."" " , , '-annc AT"",""C~T
, """-', ROOFAT HIGHEST
FLEXIBLE HOSE
'::.;:.;:--- POSITION
CONNECTION ,.-,. ---i.
C.:.
'~','-::"~::,
"
-"," '" "
~~.;',' ~ ""''II- " ""..;:,' ,
TANK SHELL :"~~ "" ""
" "
',', " '," "-'" "
I,.""
"'/,
""' ',,' ,
PIPING ATTACHED
TO THE LADOER I' ,.
II I
"..~I
~.!.__c .=============~======
PIPE SUPPORTS
-LADDER HOSE SUPPORT
CATENARY HOSE
(GOODALL) ORAIN AT ELBOW
FlxeOSOLUTION~
PIPING I
FIGURE C-2
CATENARY FOAM SYSTEM-LADDER PIPING DETAILS
..
MOBIL ENGINEERING GUIDE
FIGUREC-3
ALTERNATEFOAMMAKER LOCATIONS
A foam dam is required where foam is applied by fixed -outlets above a steel
shoe fabric seal, a tube seal weathershield, or a secondary seal; where hose
streams are used to apply foam manually over tube seals with metal weather-
FIGURE C-4
FOAM DISCHARGE ABOVE STEEL SHOE FABRIC SEAL,
WEATHERSHIELD. OR SECONDARY SEAL
MOBil ENGINEERING GUIDE
FIGURE C-5
FOAM DISCHARGE THROUGH STEEL SHOE FABRIC SEAL, METAL WEATHERSHIELD,
OR NONCOMBUSTIBLE SECONDARY SEAL
A foam dam is not required where foam is discharged below a steel shoe
fabric seal or where fixed outlets apply foam below a metal weathershield
or metal secondary seal, except where a primary tube seal is 150 mm (6 in.)
or lessfrom the roof top.
Table C-1 summarizes rim seal fire protection conditions requiring a foam
dam when a fixed or semifixed catenary foam system is installed. Foam
dams shall be designed and installed as discussed below and in accordance
with Appendix A of NFPA 11.
~
.--
~ II "C
co
0
=
-c
0
E
coc.c=-
..c
coE-E ~
-.-
cococo
co-CO
"'==
GO
z z ~
..- =~ _0 co"'co
W ct m
t--cn~ cnO...
.-~~
Q 2- =-.;
~ 0: c
a..
W
-cn
I-
ct"C ~
~ u-
..-'-
--N
--
-~~ ~ E
-' N
-ct C-
= =~
- --
W Ccn
.- ~
-C/) 2~ E
:c.
(..)
W~
-'-
~ u-
ctN
~E
cn:;::
~
>-
~
= ~
Co
=
cn -0
.~~
.:= .:=
0
~ 0
=
..-
--
=
0
-=
0
-c
=C/) 1-': ~ C
. ~E M
~ ~
o=:~
'-W-'- WE =
C/) -= ~m Eo E E E E E > .
.-1-:
~ EN
E E --::- --::- ~
~ ~
E - = 0
~ "C
C/)
>
(I)
~-
Om
w~
=C-
c=E
>-
m
N N N C'i
"C
ta Q)
"C
~ c~
~
= =.- =
=1.1- c C
0
C
Q)
0=: ~~ .-u..-
E c E
~
u E
E
Q ::~ Q..
~
.~ --I Q) 0
~ u-;:
>- . oC-
=..-
.c u
-
cn m =",("1 -Q)
> c~ c
ta -
~
~
o=:
2
C-
~c-
ct.5
c=N
.c=-
C::C/)II
~ao
-= .:::: .:::: - -
-- - .c
-c
0
w 0 ~= -= ..=:~ 0 0 0 0 0
~
Q)
Q)
~
.-=
~ = NE
=cc
~ ~ ~ ~ ~ .c
C)
ta
0=: c - E E E --
.-on
.c "C
(..) I- Co
c:: =E =
Co
E
cc
Eo C'J C'J
-
N
-E
c-.I
-E
~ c
-.c
N-=~
_taQ)
-Q) .-
c =LI,.
CO') on-
E Q).c
:§:
o-~
E Q)ta
.c Q)
U>Q)~
t;:E
'" I I '" 0
ta_on
-~ ... '" Q)=,-
-ta
"C "C
cc.
.-0 -:: -a;
_OQ)
~"C on
E
Q)
~>-
---
co-
E 0o
0
.-C
:§
-=
...
'--
:c
~
Q)Q»
.c0)~~ co
-=
GJN Q) _ta"C
en E'- "C -CO ~-
_GJ
.r=
~
"'.c
=' u
E-~
c
°
u
m
--- -.-
Q) 0
E Oc:
Q) Q)
==
-Q)
en
Q
m --E =
...COCO
>- >'"
...OC:--=0
E
oc.
~2
...
~-
_GJ
GJ~
~:c
"'-
-",
co
Q).l:J
:I
E~~
ta --
"CE:D
E CO -;:.
Q)
Q)
Co
>-
CO _co_-
0 CUCO mO
>-u;
'- ~ ~E
-0
ta°on
000-
..00-00-
='
.c
~~
..- ..."'-
.c: co~ ""-
coO m u
-com mo ~E "C~
~ 0
/(1)
w.ctao
Q)= E
~.c.c
-~
~-
~
0
~
0
~ 0
u
~ I-I-~(.J
0
Q)
cn I- I- cn Q)
cn 2- N
MOBil ENGINEERING GUIDE
cient foam to meet the design application rate for each tank, plus any foam
required for extinguishment of small dike fires (see Paragraph6.6.4). Foam
for foam hose streams may be provided from other sources if a water supply,
a means of proportioning, and foam nozzles are also provided. Tank selector
valves, which determine which tank will receive foam flow, shall be located
in an accessible area outside the tank dike areas. Tank selector valves shall
be properly labeled. Instructions for system operation shall be located in
the pumphouse.
APPENDIX 0
PORTABLE TOWER FOAM SYSTEMS
APPLICATION RATES
Up to 24 Up to 80 1
Over 24 to 35.8 Over 80 to 117.5 2
Over35.8 to 43 Over 117.5to 140 3
Over43 to 49 Over 140 to 160 4
Over49 to 55 Over 160 to 180 5
Over 55 to 67 Over 180 to 220 6
For fixed roof tanks larger than 61 m (200 ft) in diameter, at least one
additional tower shall be added for each additional 465 m2 (5000 ft2) of
tank liquid surface area. In addition, subsurface injection should be con-
sidered for supplementary application. This is necessary so that foam travel
across the burning liquid surface does not exceed 30 m (100 ft). Greater
distances result in foam destruction and failure to seal off and extinguish
the fire.
The size of a portable foam tower should be based on the foam solution
outlet rate required for the largest protected tank. When two or more towers
are provided, they shall be sized to deliver foam at the same rate. Tower
foam maker inlet pressure should be 345 kPa gage (50 psig). The capacity of
a given tower will vary approximately in proportion to the square root of the
MOBIL ENGINEERING GUIDE
APPENDIX E
SAFESTORAGETEMPERATURES
AND OPERATINGPRECAUTIONS
E-1. GENERAL
Hydrocarbons should not be stored in cone roof tanks at high or low tem-
peratures sufficient to cause liquid vapor pressures that will put the tank
vapor space in the flammable range (see Table E-1 and Figure E-1). For the
effect of solar heat on liquid surface temperatures, seeTable E-2.
TABLE E-1
FLAMMABILITY OF THE VAPOR SPACE IN CONE ROOF TANKS CONTAINING VARIOUS
FLAMMABLE LIQUIDS WITH AIRNAPOR MIXTURE IN EQUILIBRIUM
.
MOBIL ENGINEERING GUIDE
FIGURE E.1
RELATIONSHIP BETWEEN TEMPERATURE, RVP, AND FLAMMABLE LIMITS
OF PETROLEUM PRODUCTS AT SEA LEVEL
Floating roof tanks shall be used to store Class 18 and lC products having
flash points below the storage temperature. If fixed roof tanks are used for
such liquids, precautions against ignition due to static and lightning shall be
observed.
TABLE E-2
EFFECT OF SOLAR HEAT ON LIQUIO SURFACE TEMPERATURES*
Distance of liquid
surface below top angle: O.3m (1 ft) 4.6 m (15ft) 9.2m (30 ft)
Temperature Increase of
liquid Surface Above
Atmospheric Temperature
°C of °C OF °C of
White tank 0 0 0 0 0 0
Aluminum painted tank 8 15 6 10 3 5
Gray tank 11 20 8 15 6 10
Black tank 14 25 11 20 8 15
+As a result of solar heat, the liquid surface temperature in cone roof tanks is usually
warmer than the atmosphere during standing storage.
The lower temperature limit is below 100° C (212° F), which allows for a
margin of error in tank temperatures. The 121°C (250°F) upper limit
provides for the possibility of higher water boiling temperatures at the tank
bottom due to oil static head.
In summary:
(b) The storage temperatures of hot oil tanks should not exceed 232°C
(4500 F) unless special precautions are taken. These consist of keeping
below the autoignition and boiling point temperatures and avoiding hot
metal surfaces. For asphalt tanks maintained above 232°C (450OF), see
API Publication 2023. Some deposits on the underside of heated asphalt
tank roofs have been found to autoignite at 1900C (3750 F). Asphalt and
residuum tanks whose storage temperatures exceed 1770C (3500 F) shall
be inert gas blanketed. Insulation should not be retrofitted on the roof
of a heated asphalt or residuum tank unless the deposits on the underside
of the roof are completely removed or the tank is inert gas blanketed.
(c) Tanks heated and maintained below 93.4°C (2000 F) shall be pro-
vided with controls to ensure the temperature does not exceed 1000 C
(212°F). Should temperatures exceed 10QoC (2120 F), any water present
can boil and cause a frothover.
MOBIL ENGINEERING GUIDE
The vapor spaceof existing cone roof tanks used for storage of hydrocarbons
.at or near their flash points may have an equilibrium air/vapor mixture in
the explosive range. Measuresto prevent ignition sources shall include the
following:
(3) Do not use overshot (splash) filling and avoid blending operations
that may cause static buildup due to agitation.
(5) Provide a slotted gage tube that is electrically bonded to the tank
to prevent discharge of any static accumulation during gaging. If a
slotted gage tube is not provided. do not gage the tank until at least
30 minutes after the filling operation is completed.
(6) Be sure all metal parts of the tank are electrically connected.
(7) Maintain the roof vaportight, with metal thickness not less than
4.763 mm (0.1875 in.), to avoid ignition in the event of a direct light-
ning strike (see NFPA 78).
(b) Initial Filling Precautions for Covered Floating Roof Tanks and Cone
Roof Tanks with Internal Floating Covers
(1) Survey the tank and surrounding area for any potential sources
of ignition and eliminate them.
(2) Remove any rags or other sources of spontaneous combustion
from inside the tank.
(3) Removeall loose objects from the tank top.
(4) Provide an electrical bond between the tank and any loose hatches
or vent covers.
(5) limit accessto top of tank to that which is absolutely necessary.
(6) Do not attempt filling operations during periods of thunderstorm
activity. Suspend filling operations that are underway on approach of
a thunderstorm.
(7) Establish filling rates consistent with avoiding static accumulation.
Crude oil is not known to be a static accumulator, but other products
may be. [See ParagraphE-3(a), Item (2).]
MOBIL ENGINEERING GUIDE
All refined petroleum products have high electrical resistivity and are sus-
ceptible to static charge buildup. Static charges may not drain off the tank
shell without sparking through the vapor space. Experience indicates that
crude oil, because of its water content and impurities, is sufficiently con-
ductive to prevent excessive static buildup. This may also be true of some
heavy fuels or other unfinished oils. No significant charge will be retained
if the conductivity is above 5 picomhos per meter.
Sour oils that contain sufficient H2S to cause formation of pyrophoric scale
shall not be stored at temperatures that will cause the tank vapor space to
be explosive. Otherwise, the precautions listed in Paragraph E-2 should
result in reasonably safe operation. These precautions also apply to unheated
products whose flash points and vapor pressures are such that the vapor
space will be flammable at storage temperatures when the products are
stored in a cone roof tank.
Hot oil tank fires [oil storage temperature over 121°C (250OF)] and residu-
um, heavy fuel oil, and asphalt tank fires are difficult to extinguish after
initial burning because of severe slopover when cooling water or foam is
applied. Residua and heavy fuels may also have boilover characteristics simi-
lar to those of crude oils. However,. a slopover or frothover, rather than a
boilover, may occur unless the material contains a mixture of oils of vary-
ing boiling points (see Appendix F).
.
MOBIL ENGINEERING GUIDE
APPENDIX F
TANK FIRE BOllOVERS
When a fire occurs in a cone roof tank containing crude oil, the tank usually
foams or boils over unless it is extinguished before the heat wave reachesthe
water bottom. Often the expelled froth is many times the oil volume in the
tank. Thus, a tidal wave of burning froth may flow over dikes, set adjoining
tanks on fire, and destroy anything in its path. Such fires are rare since the
use of gastight cone or floating roofs instead of wood and tar paper roofs.
In fact, there is no record of a floating roof crude oil tank fire frothing or
boiling over, even with the roof submerged. The data contained herein are
based on test work accomplished on the West Coast in the late 1920s and on
practical field experience.
F-1 DEFINITIONS
At the initial stage of a crude oil tank fire, the light volatile fractions boil out
of the top surface of the crude and bum. The hot heavy residual oil that
has not volatized remains on the surface, and heat from the fire raises the
temperature of this surface layer so that heavier fractions also distill off and
bum. As burning progresses,the hot unburned residuum at 149°C to 204°C
(300° F to 400° F) forms a distinct layer remaining on top of the cold crude
below. As the hot layer interface contacts this crude, the lighter fractions
distill out of the crude top surface, bubble up through the hot layer, and
provide fuel for continued burning.
As this processcontinues, the crude is gradually consumed by the distillation
and the layer of hot residue thickens. The sharp interface between the hot
and cold oil, commonly called the "heat wave front," moves downward
toward the tank bottom as more residuum accumulates and until all the
light crude fractions are consumed. For the average crude, the heat wave
front progressesdownward at a rate of about 0.61 m to 0.91 m (2 ft to 3 ft)
per hour. When this heat wave front reaches tank bottom water, or BS&W,
the water is suddenly expanded into steam with explosive violence. Depend-
ing on such factors as the depth of the overlying hot residuum, a great
volume of froth may be thrown high into the air above the tank rim and the
burning froth wave may travel over the ground away from the tank at speeds
up to 32 km/h (20 mph).
In order to produce a distinct heat wave front, an oil must have two charac-
teristics:
(a) It must have a reasonably wide boiling range, as does crude oil.
(b) It must be sufficiently heavy to produce a relatively large amount
of undistilledlowheavy
moderately gravityends to best
is the formexample.
a top stratum of hot oil. A crude
I of
MOBIL ENGINEERING GUIDE
Refined oils such as gasoline, kerosine, diesel oil, or gas oil have a fairly
narrow boiling range and bum uniformly, leaving little residual material.
Usually, the top hot layer is about 12.5 mm to 25 mm (1/2 in. to 1 in.) thick
.at all stages of burning, and a heat wave front condition will not occur. Even
minor slopovers are not encountered in the case of tank fires involving
gasoline and distilled light oils.
Assuming the cone roof has blown free of the tank and the tank contains
about 9.14 m (30 h) of crude with boilover characteristics, the following
will result if the fire is not extinguished:
(a) One hour after ignition, there will be relatively quiet burning. The
bare shell at the top will be folded in as a result of heat. The heat wave
layer will be about 635 mm to 762 mm (25 irl. to 30 in.) deep.
8
(b) Ten hours after ignition, gasoline vapor will be bubbling up through
the 149°C to 204°C (300° F to 4000 F) heat wave layer. Approximately
2.13 m (7 ft) of product will have burned off. The heat wave front will
have settled above 6.4 m (21 ft) and will be about 2.74 m (9 ft) above the
tank bottom. Boilover can be anticipated in about 31/2 hours or less,
depending on the BS&W depth.
(3) Immediately prior to boilover, the heat wave front will contact
bottom water and the tank contents will consist almost entirely of the
149°C to 204°C (300OF to 4000 F) heat wave layer. About 3.05 m (10 ft)
of product will have burned off. There will be unusually strong burning,
with some slopping.
(d) Main boilover will occur when a column of burning froth is projected
upward with intense radiant heat. Flame height may exceed ten times the
tank diameter. Burning-froth ground fire may cover a large area, and
inertia of the froth will cause it to readily pass over the surrounding dike
walls.
When wind blows over the burning oil surface, the upwind side of a tank
on fire will be cooler than the downwind side. Flames will therefore be
more intense above the downwind side. Thus, burning will be mor~ severe
MOBil ENGINEERING GUIDE
and the heat wave layer will be deeper on the hot downwind side, so that
the heat wave front may contact the water lens or water bottom on this
side first. Becauseof this possibility I fire watches should be alert to impend-
ing slopovers or boilovers on the downwind side. Note, however, that a
localized emulsion stratum on the upwind side may froth over before a lower
stratum on the downwind side.
(b) If the tank is equipped with foam chambers, cool the shell around
and below the chambers sufficiently to prevent its folding in where the
chambers are located. (In addition, cooling the base area of the shell will
maintain its integrity and reduce fire damage.)
(c) Check all pipeline and tank valves for proper setting while they are
accessible. Start pumping oil out of the tank to salvage as much as possible
and increase outage so as to hold the frothing.
(e) Determine the oil level and the character of the crude in the tank.
A responsible person should be assigned as an observer and should place
assistant observers around the tijnk. If the crude is dry and of medium-to-
light gravity. the heat wave will settle as the tank burns quietly at a rate
of 0.61 m to 0.91 m (2 ft to 3 ft) per hour. Thus, the anticipated time of
a major boilover can be estimated. If oil is beir1!j pumped out, this time
factor will be shorter. The following table may be helpful in this res,pect.
MOBIL ENGINEERING GUIDE
(a) Cold residuum or heavy fuels. Because of high flash points, fires
involving tanks that contain such products are rare. Ignition must there-
fore be from an outside source, such as a serious surrounding ground fire.
.In one known case, a straight-run residuum reservoir boiled over violently
after burning for 19 hours. In all other instances, reports indicate that
quiet burning or some slopovers occurred.
(b) Asphalts and hot heavy fuels. Severe slopovers of burning hot fuel
oil, asphalt, and lube oil tanks have occurred when cooling water or foam
was applied. A heat wave is not a factor in these cases. Hot fuel oil tanks
at approximately 121°C (250°F) or above have frothed over when water
was present in the tank. When ignited, such froth overs have caused wide-
spread fire damage.