Combined Footing Design To BS8110: Solution

The document describes the design of a combined footing to support two columns subjected to ultimate loads of 1650 kN and 1950 kN. The footing is designed to be 6m x 2.5m x 0.65m in size with reinforcement including 3216 mm^2 of longitudinal bars and transverse bars of 1206 mm^2. Punching shear is also checked and found to be satisfactory.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (4 votes)
5K views6 pages

Combined Footing Design To BS8110: Solution

The document describes the design of a combined footing to support two columns subjected to ultimate loads of 1650 kN and 1950 kN. The footing is designed to be 6m x 2.5m x 0.65m in size with reinforcement including 3216 mm^2 of longitudinal bars and transverse bars of 1206 mm^2. Punching shear is also checked and found to be satisfactory.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Combined Footing Design to BS8110

Analyse and design the combined footing shown below when subjected to ultimate load of
1650 kN from the first column column a and 1950 kN from the second column.

The material properties are as follows:


Concrete characteristic strength: f c = 30 N / mm 2

Steel characteristic strength: f y = 460 N / mm 2

Soil bearing pressure: Psoil = 200 N / mm 2

Concrete unit weight:  Con = 24 kN / m3


Concrete cover: C = 40 mm

Assumed bar size: bar = 12 mm

Solution:
Footing size
Service axial Load: NA = 1650 /1.5 = 1100 kN
NB = 1950 /1.5 = 1300 kN
Totalservice axial, N total = 1100 + 1300 = 2400 kN
Assume self-weight is 10% of total serivce load
Footing self-weight , W = 0.1 2400 = 240kN

Area of footing required A=


(W + N ) = ( 240 + 2400 ) = 13.2 m
total 2

Soil pressure 200

Prepared by Maged Mohammed ([email protected]) Page 1


Combined Footing Design to BS8110

Try footing size of B  H  h = 6 m  2.5 m  0.65 m with area of A =15 m 2


Self-weight of concrete, W = 6  2.5  0.75  24 = 270 kN

Check service soil bearing capacity =


( N + W ) = ( 2400 + 270 ) = 178 kN/m 2  200 kN/m 2 → Ok
A 15
Arrange the centroid of load so the soil distribution pressure is uniform
 M A = 0 1300(3.4) + 2400( x) = 0  x = 1.84 m

Load analysis
N Ed 1650 + 1950
Soil pressure at ultimate load, p = = = 240 kN/m 2
A 15
Soil pressure per m width, w = 240  2.5 m = 600 kN/m
The shear force and bending moment are shown in the following page
Main Reinforcement: Longitudinal Reinforcement at Bottom
Effective depth: d x = h – c – 0.5 bar = 750 – 40 – 0.5 16 = 702 mm
Maximum Moment at column Face = 476.28 kNm
M
k=  0.156
f cu bd 2
476.28 106
k= = 0.013  0.156
30  2500  7022
 Compression reinforcement is not required
K
z = d [0.5 + (0.25 − )]
0.9
0.013
z = d [0.5 + (0.25 − )] = 0.99d x  0.95d x
0.9
z = 0.95d x = 666.9 mm
M 476.28 106
As = = = 1634 mm 2
0.95 f y Z 0.95  460  666.9
(0.13)(b)(h) (0.13)(2500)(750)
A s, min = = = 2437.5 mm 2 , As  A s, min
100 100
Then , As ,request = A s, min = 2437.5 mm 2 thus, As , prov = 3216 mm 2 (16T16 )

Prepared by Maged Mohammed ([email protected]) Page 2


Combined Footing Design to BS8110

Main Reinforcement: Longitudinal Reinforcement at Top


Maximum Moment mid span = 387.75 kNm
M 387.75  106
k=  0.156  k = = 0.01  0.156
f cu bd 2 30  2500  702 2
 Compression reinforcement is not required
K 0.01
z = d [0.5 + (0.25 − )]  z = d [0.5 + (0.25 − )] = 0.99d x  0.95d x .
0.9 0.9
Then take z = 0.95d x = 666.9 mm

Prepared by Maged Mohammed ([email protected]) Page 3


Combined Footing Design to BS8110

M 387.75 106
As = = = 1330.5 mm 2
0.95 f y Z 0.95  460  666.9
(0.13)(b)(h) (0.13)(2500)(750)
As, min = = = 2437.5 mm 2 , As  A s, min
100 100
Then , As ,request = A s, min = 2437.5mm 2 thus, As , prov = 3216 mm 2 (16T16 )

Transverse Reinforcement: Reinforcement at Bottom

Consider b = 1000 mm
Soil pressure per 1 m width, w = 240  1.0
m = 240 kN/m
1.1
M Ed = 240 1.1 = 145.2 kNm/m
2

Effective depth: d y = h – c – 1.5 bar = 750 – 40 – (1.5 16) = 686 mm


M Ed 145.2 106
k=  0.156  k = = 0.01  0.156
f cu bd 2 30  1000  6862
 Compression reinforcement is not required
K
z = d [0.5 + (0.25 − )]
0.9
0.01
z = d [0.5 + (0.25 − )] = 0.99d y  0.95d y .
0.9
Then take z = 0.95d y = 651.7 mm
M Ed 145.2 106
As = = = 510 mm 2
0.95 f y Z 0.95  460  651.7
(0.13)(b)(h) (0.13)(1000)(750)
A s, min = = = 975 mm 2 , As  A s, min
100 100
Then , As ,request = A s, min = 975 mm 2 thus, As , prov = 1206 mm 2 ( T16-175 )

Prepared by Maged Mohammed ([email protected]) Page 4


Combined Footing Design to BS8110

Vertical Shear
Maximum shear stress ,
V 1650 103
Column A : v = =
Column perimeter  d 1200  702
= 1.96 N/mm 2  0.8 f cu ok
V 1950 103
Column B : v = =
Column perimeter  d 1600  604
= 1.74 N/mm 2  0.8 f cu ok
Check the vertical shear at 1.0d from the face of
Column where 1.0d = 702 mm
0.986 1.59 0.888  954
= V = = 532.8 kN/ m width
V 954 1.59
V 532.8  103
v= = = 0.304 N/mm 2
bd 2500  702

1/3 1/4
 100 As   400 
0.79     1/3
 bd   d   f 
Vc =   cu 
m  25 
1/3
 100  3216 
1/3
 100 As 
  =  = 0.57
 bd   2500  702 
1/4 1/4
 400   400 
  =  = 0.87
 d   702 
1/3 1/3
 f cu   30 
  =  = 1.063
 25   25 
0.79  0.57  0.87
vc = 1.063 = 0.33 N/mm 2  v = 0.304 N/mm 2 → ok
1.25
Therefore no shear reinforcement is required

Prepared by Maged Mohammed ([email protected]) Page 5


Combined Footing Design to BS8110

Punching Shear
Critical shear at 1.5d from face of column:
702 + 686
Average d = = 694 mm  1.5d = 1.5  694 = 1041 mm
2
Control perimeter;
400+2(1.5d)= 400+2(1.5  694) = 2482 mm
u= 4  2482 = 9928 mm
Area within perimeter;
A = 2.4822 = 6.160 m 2

Average punching shear force at control perimeter:


V = 1950 – (240  6.16) = 471.6 kN
V 471.6 1000
Punching shear stress, v = = = 0.068 N/mm 2 → 0k
perimeter  d 9928  694
Details

Prepared by Maged Mohammed ([email protected]) Page 6