CT/PT Selection Chart: Applicable Standard (A) (V) CT's Qty PT PT's Part # PT's Qty Service Size CT CT's Part # Phase

This document provides a chart detailing CT and PT selection guidelines for various service sizes and phases. It includes the applicable CT and PT models, quantities required, and applicable standards for residential, commercial, central metering, and primary metering applications up to 27.6kV. Selections are provided for single phase 120/240V, three phase 208V, 347/600V, and Delta systems from 400A up to 4000A.

Uploaded by

Prabakar P
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
494 views

CT/PT Selection Chart: Applicable Standard (A) (V) CT's Qty PT PT's Part # PT's Qty Service Size CT CT's Part # Phase

This document provides a chart detailing CT and PT selection guidelines for various service sizes and phases. It includes the applicable CT and PT models, quantities required, and applicable standards for residential, commercial, central metering, and primary metering applications up to 27.6kV. Selections are provided for single phase 120/240V, three phase 208V, 347/600V, and Delta systems from 400A up to 4000A.

Uploaded by

Prabakar P
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CT/PT Selection Chart

Updated on 9 / 20 / 2017

Service Size CT's PT's Part PT's Applicable Standard


Phase CT CT's Part # PT
[A] [V] Qty # Qty Visit: HorizonUtilities.com/Metering
1ph
400A 120/240 CT 200:5 M8122 1 - - - 27-05
Residential
CT 300:5 or M8124 or or
1ph 400A 120/240 M8125 1 - - -
Commercial CT 400:5 check load 27-06
demand
1ph
400A 120/240 CT 300:5 M8170 1 - - - 27-08
Central
Sec.wire distance max. 15ft
Metering

3 400A - 600A 208 CT 300:5 M8170 3 - - - 27-09-208V


Sec.wire distance max. 15ft
ALECTRA (formerly HORIZON) SECONDARY METERING

3 400A - 600A Delta 600V CT 300:5 M8170 2 PT 600/120 M9005 2 27-09-Delta


Sec.wire distance max. 15ft

3 400A - 600A 347/600 CT 300:5 M8170 3 PT 360/120 M9002 3 27-09-347/600V


Sec.wire distance max. 15ft

3 800A only 208 CT 300:5 M8170 3 - - - 27-11-208V - Switchboard


Sec.wire distance max. 15ft

3 1000A - 3000A 208 CT 1000/2000A:5 M8209 3 - - - 27-11-208V - Switchboard


up to 2000A Wire CT on 1000:5
above 2000A Wire CT on 2000:5

3 3000A - 4000A 208 CT 1000/2000A:5 M8209 3 - - - 27-11-208V - Switchboard


Wire only 2000:5

3 up to 800A 347/600 CT 300:5 M8170 3 PT 360/120 M9002 3 27-11-347/600V - Switchboard


Sec.wire distance max. 15ft

3 1000A - 3000A 347/600 CT 1000/2000A:5 M8209 3 PT 360/120 M9002 3 27-11-347/600V - Switchboard


up to 2000A Wire CT on 1000:5
above 2000A Wire CT on 2000:5

3 3000A - 4000A 347/600 CT 1000/2000A:5 M8209 3 PT 360/120 M9002 3 27-11-347/600V - Switchboard


Wire only on: 2000:5

3 max 800A 347/600 CT 300:5 M8170 3 PT 360/120 M9002 4 28-50


Sec.wire distance max. 15ft
HORIZON PRIMARY METERING

8kV
8kV

13.8kV
13.8kV

16kV
16kV

27.6kV
27.6kV