MTL4500/MTL5500 Series: Intrinsic Safety (IS) Isolators For Hazardous Area Interfacing
MTL4500/MTL5500 Series: Intrinsic Safety (IS) Isolators For Hazardous Area Interfacing
MTL4500/MTL5500 Series
Intrinsic safety (IS) isolators for hazardous area interfacing
MTL's latest generation of IS interfaces The reduced power consumption and in safe- and hazardous-area connectors, and
utilises an innovative "One-Core" technology high efficiency enable high signal density to a power plug which accepts a power bus; it all
to ensure the highest quality and availability be achieved together with improved freedom leads to quicker insertion, fewer wiring errors
while maintaining maximum flexibility at in cabinet layout and design. Easy integration and trouble-free, tidier installations.
lowest cost. Incorporating advanced circuit with the input/output assemblies of control
Line fault detection (LFD) facilities are
design, a common set of components and or safety instrumentation systems not only
provided across the range of I/O functions;
innovative isolating transformer construction, simplifies project engineering but also reduces
on the switch/proximity detectors, the
they achieve a significant reduction in power installation and maintenance costs.
MTL4523/5523 solenoid/alarm drivers and the
consumption while increasing channel packing
A multiway connector to the backplane isolating drivers. Analogue input units such as
densities. The compact, 16mm wide design
provides safe-area and power supply the MTL4541/5541 provide line fault detection
reduces weight and gives exceptionally high
connections, while hazardous-area connections by repeating o/c or s/c currents to the safe-
packing density. They build on the proven
plug into the front of the module, simplifing area control system.
success of the MTL2000, 3000, 4000 and
installation and maintenance and reducing time,
5000 Series to bring the benefits of new Status LEDs, configuration switches and
cost, and the risk of errors.
developments in galvanic isolation without ports are located on the top or side of
compromising the reliability of the designs The DIN-rail mounting MTL5500 Series individual modules, as appropriate, for easy
from which they have evolved. meets the needs of the IS interface market access.
for "application focussed" projects, ranging
The backplane mounting MTL4500 Both new series have been designed
from single instrument loops, through to fully
Series is designed with system vendors for compatiblity with earlier models. The
equipped cabinets, across all industries where
in mind for "project-focussed" applications MTL4500 series provides plug-replacements
hazardous areas exist.
such as Distributed Control System (DCS), for earlier MTL4000 series units, while
Emergency Shutdown Systems (ESD) and Fire The MTL5500 clips quickly onto DIN rail, the MTL5500 models can easily replace
and Gas monitoring (F&G). so it is compatible with the industry-standard MTL5000 series units. Each offer the latest
mounting system. Wiring is simplified by plug- in modern technology and efficiency without
compromise.
www.mtl-inst.com [email protected]
ISOLATOR FUNCTION SELECTOR
MTL4500 MTL5500
(Backplane) (DIN-rail) Channels Function
Digital Input
MTL4501-SR MTL5501-SR 1 fail-safe solid-state output + LFD alarm
MTL4510 MTL5510 4 switch/prox input, solid-state output
MTL4510B MTL5510B 4 multi-function switch/prox input, solid-state output
MTL4511 MTL5511 1 switch/prox input, c/o relay output
MTL4513 MTL5513 2 switch/prox input, solid-state output
MTL4514 MTL5514 1 switch/prox input, relay + LFD
MTL4516 – 2 switch/prox input, relay + LFD outputs
MTL4516C MTL5516C 2 switch/prox input, c/o relay + LFD outputs
MTL4517 MTL5517 2 switch/prox input, relay + LFD outputs
Digital Output
MTL4521 MTL5521 1 loop powered solenoid driver
MTL4521L – 1 loop powered solenoid driver, IIC
– MTL5522 1 loop powered solenoid driver, IIB
MTL4523 MTL5523 1 solenoid driver with LFD
MTL4523L – 1 loop powered solenoid driver with LFD
MTL4523R – 1 solenoid driver with reverse LFD
MTL4524 MTL5524 1 switch operated solenoid driver
MTL4524S – 1 switch operated solenoid driver, 24V override
MTL4525 MTL5525 1 switch operated solenoid driver, low power
MTL4526 MTL5526 2 switch operated relay
Pulse & Vibration
MTL4531 MTL5531 1 vibration probe interface
MTL4532 MTL5532 1 pulse isolator, digital or analogue output
MTL4533 MTL5533 2 vibration probe interface
Analogue Input
MTL4541 MTL5541 1 2/3 wire transmitter repeater
MTL4541A MTL5541A 1 transmitter repeater, passive input
MTL4541AS MTL5541AS 1 transmitter repeater, passive input, current sink
MTL4541S MTL5541S 1 2/3 wire transmitter repeater, current sink
MTL4544 MTL5544 2 2/3 wire transmitter repeater
MTL4544A MTL5544A 2 transmitter repeater, passive input
MTL4544AS MTL5544AS 2 transmitter repeater, passive input, current sink
MTL4544S MTL5544S 2 2/3 wire transmitter repeater, current sink
MTL4544D MTL5544D 1 2/3 wire transmitter repeater, dual output
Analogue Output
MTL4546 MTL5546 1 4-20mA smart isolating driver + LFD
MTL4546C – 1 4-20mA smart isolating driver + oc LFD
MTL4546Y I MTL5546Y 1 4-20mA smart isolating driver + oc LFD
MTL4549 P MTL5549 2 4-20mA smart isolating driver + LFD
MTL4549C – 2 4-20mA smart isolating driver + oc LFD
MTL4549Y MTL5549Y 2 4-20mA smart isolating driver + oc LFD
Fire & Smoke
MTL4561 MTL5561 2 loop-powered, for fire and smoke detectors
Temperature Input
MTL4575 MTL5575 1 temperature converter, THC or RTD
MTL4576-RTD MTL5576-RTD 2 temperature converter, RTD
MTL4576-THC MTL5576-THC 2 temperature converter, THC
General
MTL4599 MTL5599 – dummy module
MTL4599N – – general purpose feed-through module
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
MTL4501-SR
MTL4501-SR – MTL5501-SR Hazardous area Safe area
FAIL-SAFE SWITCH/PROXIMITY-
DETECTOR INTERFACE
Resistors must
with LFD always be fitted 6
5
12
11
for switch inputs LFD
4 10
1k4W
With the MTLx501-SR, a fail-safe switch/proximity detector 3 9
+
located in the hazardous area can control an isolated fail-safe 10kW 2 8 Failsafe
+ output
electronic output. The MTLx501-SR also provides relay alarm contacts 1 7
to signal line-fault conditions. The MTLx501-SR is for use with approved
fail-safe sensors in loops that require operation up to SIL3 according to
13 14
the functional safety standard IEC 61508. 20 to 35V dc
Vs+
Vs
SPECIFICATION
See also common specification
MTL5501-SR
Number of channels Hazardous area Safe area
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector Resistors must
always be fitted 6 7 Failsafe
Zone 0, IIC, T4–6, hazardous location 5 8 + output
for switch inputs
Div 1, Group A, hazardous location 4 9
1k4W
Voltage applied to sensor 10
3
8.6V dc max from 1k Ω +
11 LFD
10kW 2
Input/output characteristics 1 12
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx501SR Rev2 080210
MTL4510
MTL4510 – MTL5510 Hazardous area Safe area
SWITCH/ PROXIMITY
DETECTOR INTERFACE Ch D Outputs
4-channel, digital input
6 12 4
+ common
5 11
Ch C 4 10 3
The MTLx510 enables four solid-state outputs in the safe area to be
controlled by up to four switches or proximity detectors located in 3 9 2
+ 2 8 common
Ch B
a hazardous area. Each pair of output transistors shares a common 1 7 1
terminal and can switch +ve or –ve polarity signals. A range of module
configurations is available (see Table 1) through the use of selector Ch A
switches. When proximity detector modes are selected, LFD is enabled 13 14
20 to 35V dc
and the output switches to OFF if a line fault is detected. Vs+
Vs
SPECIFICATION
See also common specification MTL5510
Hazardous area Safe area
Number of channels
4, configured by switches
Location of switches
Zone 0, IIC, T6 hazardous area Ch D Outputs
Div 1, Group A hazardous location
6 7 4
+ common
Location of proximity detectors 5 8
Ch C 4 9 3
Zone 0, IIC, T4-6 hazardous area if suitably certified
Div 1, Group A, hazardous location 10
3 2
Hazardous-area inputs + 2 11 common
Ch B
1 12 1
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR) 13 Vs
Voltage applied to sensor Ch A 14 Vs+
7 to 9V dc from 1kΩ ±10% 20 to 35V dc
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal Table 1 - Mode options
Line fault detection (LFD) (when selected)
MODE o/p 1 o/p 2 o/p 3 o/p 4 i/p type
User-selectable via switches on the side of the unit.
Open-circuit alarm on if Iin < 50μA 0 chA chB chC chD
Open-circuit alarm off if Iin > 250μA 1 chA rev. chB chC chD
Short-circuit alarm on if Rin < 100Ω 2 chA chB rev. chC chD
Short-circuit alarm off if Rin > 360Ω 3 chA chB chC rev. chD
Note: Resistors must be fitted when using the LFD facility with a contact input switch
500Ω to 1kΩ in series with switch 4 chA chB chC chD rev.
20kΩ to 25kΩ in parallel with switch 5 chA rev. chB chC rev. chD
Safe-area outputs 6 chA chB rev. chC chD rev.
Floating solid-state outputs compatible with logic circuits
7 chA rev. chB rev. chC rev. chD rev.
Operating frequency: dc to 500Hz
Max. off-state voltage: ± 35V 8 chA chB chC chD
Max. off-state leakage current: ± 50μA 9 chA rev. chB chC chD
Max. on-state resistance: 25Ω 10 chA chB rev. chC chD
Max. on-state current: ± 50mA 11 chA chB chC rev. chD prox.
LED indicators detector
12 chA chB chC chD rev. + LFD
Green: power indication
13 chA rev. chB chC rev. chD
Yellow: four: on when output active
Red: LFD indication + faulty channel’s yellow LED flashes 14 chA chB rev. chC chD rev.
Maximum current consumption 15 chA rev. chB rev. chC rev. chD rev.
40mA at 24V (with all output channels energised) See Instruction Manual INM4500 for further mode information.
Power dissipation within unit
0.96W at 24V, with 10mA loads
Safety description (each channel)
Vo =10.5V Io =14mA Po =37mW Um = 253V rms or dc
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx510 Rev2 080210
MTL4510B
MTL4510B – MTL5510B Hazardous area Safe area
SWITCH/ PROXIMITY
DETECTOR INTERFACE Ch D Outputs
4-channel, multi-function, digital input
6 12 4
+ common
5 11
Ch C 4 10 3
The MTL4510B enables four solid-state outputs in the safe area to
be controlled by up to four switches or proximity detectors located in 3 9 2
+ 2 8 common
Ch B
a hazardous area. Each pair of output transistors shares a common 1 7 1
terminal and can switch +ve or –ve polarity signals. A range of module
configurations is available (see Table 1) through the use of selector Ch A
switches. These include start/stop operations and pulse output modes. 13 14
20 to 35V dc
Vs+
Vs
SPECIFICATION
See also common specification
MTL5510B
Number of channels Hazardous area Safe area
4, configured by switches
Location of switches
Zone 0, IIC, T6 hazardous area
Div 1, Group A hazardous location Ch D Outputs
Location of proximity detectors
6 7 4
+ common
Zone 0, IIC, T4-6 hazardous area if suitably certified 5 8
Ch C 4 9 3
Div 1, Group A, hazardous location
Hazardous-area inputs 10
3 2
Inputs conforming to BS EN60947–5–6:2001 standards for + 2 11 common
Ch B
1 12 1
proximity detectors (NAMUR)
Voltage applied to sensor 13 Vs
7 to 9V dc from 1kΩ ±10% Ch A 14 Vs+
Input/output characteristics 20 to 35V dc
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Table 1 - Mode options
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. MODE Function Equivalent*
Open-circuit alarm on if Iin < 50μA
Open-circuit alarm off if Iin > 250μA 0 4-ch switch input, MTLx510
Short-circuit alarm on if Rin < 100Ω 1 2-ch each channel one input, two outputs MTL4016
Short-circuit alarm off if Rin > 360Ω 2 Same as mode 1 with phase reversed MTL4016
Note: Resistors must be fitted when using the LFD facility with a contact input 3 2-ch, 2-pole changeover output
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch 4 1-ch with line fault output MTLx014
Safe-area outputs 5 As mode 4 with changeover outputs
Floating solid-state outputs compatible with logic circuits 6 1-ch with start-stop latch MTL2210B
Operating frequency: dc to 500Hz 7 4-ch switch input, MTLx510
Max. off-state voltage: ± 35V 8 4-ch switch input, MTLx510
Max. off-state leakage current: ± 50μA 9 2-ch with line fault output MTLx017
Max. on-state resistance: 25Ω 10 As mode 9 with LFD changeover
Max. on-state current: ± 50mA
11 As mode 10 with phase reversed
LED indicators
12 3-ch with normally-open LFD output
Green: power indication
Yellow: four: on when output active 13 3-ch with normally-closed LFD output
Red: LFD indication + faulty channel’s yellow LED flashes 14 2-ch monostable, pulse stretcher
Maximum current consumption 15 4-ch switch input MTLx510
40mA at 24V (with all output channels energised) * Note: that terminal connections may not be the same on these models,
Power dissipation within unit and x can mean either '4' or '5'.
0.96W at 24V, with 10mA loads See Instruction Manual INM4500 for further mode information.
Safety description (each channel)
Vo =10.5V Io =14mA Po =37mW Um = 253V rms or dc
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx510B Rev2 080210
MTL4511
MTL4511 – MTL5511 Hazardous area Safe area
SWITCH/ PROXIMITY To earth-leakage
detector *
DETECTOR INTERFACE
1-channel, with line fault detection 6
5
12
11
4 10
680W
The MTLx511 enables a safe-area load to be controlled by a switch or
3 9
proximity detector located in a hazardous-area. When selected, open +
22kW 2 8 Output
or short circuit conditions in the field wiring are detected by the line- 1 7
fault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for the channel is selected by a switch on the side of the Switch-type sensors
require resistors 13 14
module and output is provided by changeover relay contacts. if LFD is selected 20 to 35V dc
Vs+
Vs
SPECIFICATION
See also common specification
MTL5511
Number of channels Hazardous area Safe area
One
Location of switches To earth-leakage
Zone 0, IIC, T6 hazardous area detector *
Div. 1, Group A hazardous location
Location of proximity detector 6 7
Zone 0, IIC, T4–6 hazardous area if suitably certified 5 8
4 9
Div. 1, Group A hazardous location
680W
Hazardous-area inputs 3 10
+
Inputs conforming to BS EN60947–5–6:2001 standards for 2 11 Output
22kW
proximity detectors (NAMUR) 1 12
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx511 Rev2 080210
MTL4513
MTL4513 – MTL5513 Hazardous area Safe area
SWITCH/ PROXIMITY To earth-leakage
detector *
680W
DETECTOR INTERFACE
2-channel, line fault detection, phase reversal 22kW + 6 12
5 11
4 10 Outputs
The MTLx513 enables two solid-state outputs in the safe area to 680W 3 9 Ch 2
+
be controlled by two switches or proximity detectors located in the 2 8
Ch 1
hazardous area. The Ch1/Ch2 output transistors share a common 1 7
22kW
terminal and can switch +ve or -ve polarity signals. Independent output
phase reversal and line fault detection are enabled via switches for Switch-type sensors 13 14
each output. LFD indication is provided on the top of the module. require resistors 20 to 35V dc
if LFD is selected Vs+
Vs
SPECIFICATION
See also common specification
MTL5513
Number of channels Hazardous area Safe area
Two
Location of switches To earth leakage
detector *
Zone 0, IIC, T6 hazardous area 680W
Div. 1, Group A hazardous location
Location of proximity detectors 22kW + 6 7
5 8
Zone 0, IIC, T4–6 hazardous area if suitably certified 4 9 Outputs
Div. 1, Group A hazardous location
Hazardous-area inputs 680W 3 10 Ch 2
+
2 11
Inputs conforming to BS EN60947–5–6:2001 standards for 12 Ch 1
1
proximity detectors (NAMUR) 22kW
Voltage applied to sensor 13 Vs
Switch-type sensors 14 Vs+
7 to 9V dc from 1kΩ ±10%
require resistors 20 to 35V dc
Input/output characteristics
if LFD is selected
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Line fault detection (LFD) (when selected) *Signal plug HAZ1-3 is required for access to this function
User-selectable for each channel via switches on the side of the
unit. Line faults are indicated by an LED for each channel. LED indicators
Open-circuit alarm on if Iin < 50μA Green: power indication
Open-circuit alarm off if Iin > 250μA Yellow: two: channel status, on when output active
Short-circuit alarm on if Rin < 100Ω Red: two: LFD indication, on when line fault detected
Short-circuit alarm off if Rin > 360Ω Maximum current consumption
Note: Resistors must be fitted when using the LFD facility with a contact input 30mA at 24V
500Ω to 1kΩ in series with switch Power dissipation within unit
20kΩ to 25kΩ in parallel with switch 0.65W typical at 24V, with 10mA loads
Phase reversal 0.78W max. with 50mA loads
Independent for each channel, user-selectable Safety description (each channel)
Safe-area outputs Vo =10.5V Io =14mA Po =37mW Um = 253V rms or dc
Floating solid-state outputs compatible with logic circuits
Operating frequency: dc to 500Hz
Max. off-state voltage: ± 35V
Max. off-state leakage current: ± 50μA
Max. on-state resistance: 25Ω
Max. on-state current: ± 50mA
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx513 Rev2 080210
MTL4514
MTL4514 – MTL5514 Hazardous area Safe area
SWITCH/ PROXIMITY To earth-leakage
detector *
DETECTOR INTERFACE
1-channel, line fault detection, phase reversal 6
5 To earth-leakage
LFD
12
11 LFD
4 detector * 10
680W
The MTLx514 enables a safe–area load to be controlled, through a
3 9
relay, by a proximity detector or switch located in a hazardous area. +
2 8 Output
22kW
Line faults are signalled through a separate relay and indicated on the 1 7
top of the module. Switches are provided to select phase reversal and
to enable the line fault detection. Switch-type sensors
require resistors 13 14
if LFD is selected 20 to 35V dc
Vs+
SPECIFICATION Vs
See also common specification
MTL5514
Number of channels
One Hazardous area Safe area
Location of switch
Zone 0, IIC, T6 hazardous area
To earth-leakage
Div.1, Group A, hazardous location detector *
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area, if suitably certified 6 7
Div.1, Group A, hazardous location 5 LFD 8 LFD
Hazardous–area inputs 4 9
680W
Inputs conforming to BS EN60947–5–6:2001 standards for 3 10
proximity detectors (NAMUR) + 11
2 Output
22kW
Voltage applied to sensor 1 12
7 to 9V dc from 1kΩ ±10% 13 Vs
Switch-type sensors
Input/output characteristics require resistors 14 Vs+
Normal phase if LFD is selected 20 to 35V dc
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults *Signal plug HAZ1-3 is required for access to this function
are indicated by an LED. Line fault relay is energised and channel LED indicators
output relay de-energised if input line-fault detected Green: power indication
Open-circuit alarm on if Iin < 50μA Yellow: channel status, on when output energised
Open-circuit alarm off if Iin > 250μA Red: LFD indication, on when line fault detected
Short-circuit alarm on if Rin < 100Ω
Maximum current consumption
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
25mA at 24V dc
500Ω to 1kΩ in series with switch Power dissipation within unit
20kΩ to 25kΩ in parallel with switch 0.6W at 24V
Safe-area output Safety description
Channel: Single pole relay with changeover contacts Vo =10.5V Io =14mA Po =37mW Um = 253V rms or dc
LFD: Single pole relay with changeover contacts SIL capable
Note: reactive loads must be adequately suppressed These models have been assessed for use in IEC 61508 functional
Relay characteristics safety applications. See data on MTL web site.
MTL4514 MTL5514
Response time: 10ms maximum 10ms maximum
Contact rating: 10W, 0.5A, 250V ac, 2A, cosØ >0.7,
35V dc 40V dc, 2A, resistive load
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx514 Rev2 080210
MTL4516
MTL4516/C – MTL5516C Hazardous area Safe area
SWITCH/ PROXIMITY To earth-leakage
detector *
DETECTOR INTERFACE 680W
SPECIFICATION
See also common specification MTL4516C
MTL4516/C MTL5516C
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx516/C Rev2 300310
MTL4517
MTL4517 – MTL5517 Hazardous area Safe area
SWITCH/ PROXIMITY To earth leakage
detector *
DETECTOR INTERFACE 680W
+ 6
12
2-channel, line fault detection, phase reversal 22kW
5
LFD 11 LFD
4 10
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx517 Rev2 080210
MTL4521
Number of channels
MTL5521
One
Location of load Hazardous area Safe area
Zone 0, IIC, T4–-6 hazardous area if suitably certified
Div. 1, Group A hazardous location
To earth leakage
Minimum output voltage Equivalent output circuit detector *
Solenoid, alarm or 13
Output current (mA) 48 Current limit: 48mA other IS device 14
Input voltage
20 to 35V dc
Hazardous-area output
Minimum output voltage: 12.8V at 48mA
Maximum output voltage: 24V from 180Ω *Signal plug HAZ1-3 is required for access to this function
Current limit: 48mA LED indicator
Output ripple Yellow: output status, on when output active
< 0.5% of maximum output, peak to peak Maximum current consumption
Response time 90mA at 24V
Output within 10% of final value within 100ms Power dissipation within unit
1.4W at 24V
Safety description
Vo =25V Io =147mA Po =919mW Um = 253V rms or dc
SIL capable
These models have been assessed for use in IEC 61508 functional
safety applications. See data on MTL web site.
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx521 Rev2 080210
MTL4521L
Number of channels
One *Signal plug HAZ1-3 is required for access to this function
Location of load LED indicator
Zone 0, IIC, T4–-6 hazardous area if suitably certified Yellow: output status, on when output active
Div. 1, Group A hazardous location Maximum current consumption
Minimum output voltage Equivalent output circuit 90mA at 24V
232W maximum
Maximum inrush current
21.4
200mA
Power dissipation within unit
1.4W at 24V
10.3
Output 21.4V minimum Safety description
voltage Vo = 25V Io = 108mA Po = 675mW Um = 253V rms or dc
(V)
Input voltage
20 to 35V dc
Hazardous-area output
Minimum output voltage: 10.3V at 48mA
Maximum output voltage: 24V from 232Ω
Current limit: 48mA
Output ripple
< 0.5% of maximum output, peak to peak
Response time
Output within 10% of final value within 100ms
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS4521L Rev1 250310
MTL5522
SPECIFICATION
See also common specification
Number of channels *Signal plug HAZ1-3 is required for access to this function
One LED indicator
Location of load Yellow: output status, on when output active
Zone 0, IIB, T4–6 hazardous area if suitably certified Maximum current consumption
Div. 1, Group C hazardous location 125mA (typ.) at 24V
Minimum output voltage Equivalent output circuit Power dissipation within unit
21.4 158W maximum 1.4W at 24V
Safety description
Vo =25V Io =166mA Po =1.04W Um = 253V rms or dc
SIL capable
9.9
21.4V minimum These models have been assessed for use in IEC 61508 functional
Output
voltage safety applications. See data on MTL web site.
(V)
Input voltage
20 to 35V dc
Hazardous-area output
Minimum output voltage: 9.9V at 70mA
Maximum output voltage: 24V from 158Ω
Current limit: 70mA
Output ripple
< 0.5% of maximum output, peak to peak
Response time
Output within 10% of final value within 100ms
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx522 Rev2 080210
MTL4523/R
6 12
5 11
4 10
+
With the MTLx523 interface, an on/off device in a hazardous area can
be controlled by a voltage signal in the safe area. It is suitable for driving 3 9
+
2 8
loads such as solenoids. Line fault detection (LFD), which operates LFD
7
irrespective of the output state, is signalled by a safe-area solid-state 1 +
Solenoid, alarm or MTL4523R
switch which de-energises MTLx523, or energises MTL4523R, if a field LFD phase reversed
other IS device
line is open or short–circuited. Earth fault detection can be provided by 13 14
20 to 35V dc
connecting an MTL4220 earth leakage detector to terminal 3. Vs+
Vs
SPECIFICATION
See also common specification MTL5523
Output current (mA) 48 Current limit: 48mA link to reverse output phase
Hazardous-area output
Minimum output voltage: 12.8V at 48mA
*Signal plug HAZ1-3 is required for access to this function
Maximum output voltage: 24V from 180Ω
Current limit: 48mA LED indicators
Output ripple Green: power indication
< 0.5% of maximum output, peak to peak Yellow: output status, on when output active
Control input Red: LFD indication, on when line fault detected
Suitable for switch contacts, an open collector transistor or logic Maximum current consumption
drive 100mA at 24V dc
Output turns on if input switch closed, transistor on or Power dissipation within unit
< 1.4V applied across terminals 11 & 12 1.2W with typical solenoid valve, output on
Output turns off if input switch open, transistor off or 2.0W worst case
> 4.5V applied across terminals 11 & 12 Safety description
Response time Vo =25V Io =147mA Po =919mW Um = 253V rms or dc
Output within 10% of final value within 100ms SIL capable
Line fault detection (LFD) These models have been assessed for use in IEC 61508 functional
Open or short circuit in field cabling de-energises solid state safety applications. See data on MTL web site.
line-fault signal.
LFD transistor is switched on, provided that the field circuit
impedance is > 55Ω and < 6k5Ω.
Line fault signal characteristics
Maximum off-state voltage: 35V
Maximum off-state leakage current: 10μA
Maximum on-state voltage drop: 2V
Maximum on-state current: 50mA
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx523/R Rev2 080210
MTL4523L
SPECIFICATION
See also common specification
*Signal plug HAZ1-3 is required for access to this function
Number of channels LED indicators
One Yellow: output status, on when output active
Location of load Red: LFD indication, on when line fault detected
Zone 0, IIC, T4–6 hazardous area if suitably certified Maximum current consumption
Div. 1, Group A, hazardous location 100mA at 24V dc
Minimum output voltage Equivalent output circuit Power dissipation within unit
1.2W with typical solenoid valve, output on
21.4 180W maximum
Safety description
Vo =25V Io =147mA Po =919mW Um = 253V rms or dc
12.8 SIL capable
Output 21.4V minimum These models have been assessed for use in IEC 61508 functional
voltage safety applications. See data on MTL web site.
(V)
Input voltage
20 to 35V dc
Hazardous-area output
Minimum output voltage: 12.8V at 48mA
Maximum output voltage: 24V from 180Ω
Current limit: 48mA
Output ripple
< 0.5% of maximum output, peak to peak
Response time
Output within 10% of final value within 100ms
Line fault detection (LFD)
Open or short circuit in field cabling energises solid state line
fault signal
LFD transistor is switched on, provided that the field circuit
impedance is > 55Ω and < 6k5Ω.
Line fault signal characteristics
Maximum off-state voltage: 35V
Maximum off-state leakage current: 10μA
Maximum on-state voltage drop: 2V
Maximum on-state current: 50mA
Note: LFD signal is Zener-diode protected against inductive loads
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS4523L Rev2 080210
MTL4524
Number of channels 6 7
One 5 8
4 9 Control
Location of load
Zone 0, IIC, T4–6 hazardous area if suitably certified 3 10
+ 11
Div.1, Group A, hazardous location 2 +
12
Minimum output voltage Equivalent output circuit 1
Solenoid, alarm or 13 Vs
21.4 180W maximum other IS device 14 Vs+
20 to 35V dc
12.8 use link to reverse phase
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx524 Rev2 080210
MTL4524S
To earth leakage
SOLENOID/ALARM DRIVER detector *
Control
switch operated with 24V override, IIC 12
6
5 11
4 10
+
The MTL4524S enables an on/off device in a hazardous area to be 3 9
+
controlled by a volt-free contact or a floating logic signal in the safe 2 8
+ 24V
7
area. It can drive loads such as solenoids, alarms, LEDs and other low 1
power devices that are certified as intrinsically safe or are classified Solenoid, alarm or Override
as non-energy storing simple apparatus. By connecting a second other IS device
13 14
safe-area voltage, the output can be disabled to permit, for example, a 20 to 35V dc
Vs+
safety system to override a control signal.
Vs
SPECIFICATION
See also common specification *Signal plug HAZ1-3 is required for access to this function
LED indicators
Number of channels
Green: power indication
One
Yellow: output status, on when output active
Location of load
Maximum current consumption
Zone 0, IIC, T4–6 hazardous area if suitably certified
100mA at 24V dc
Div.1, Group A, hazardous location
Power dissipation within unit
Minimum output voltage Equivalent output circuit
1.3W with typical solenoid valve, output on
21.4 180W maximum
1.9W worst case
Safety description
Vo =25V Io =147mA Po =919mW Um = 253V rms or dc
12.8
Hazardous-area output
Minimum output voltage: 12.8V at 48mA
Maximum output voltage: 24V from 180Ω
Current limit: 48mA
Output ripple
< 0.5% of maximum output, peak-to-peak
Control input (must be fully-floating)
Suitable for switch contacts or an opto-isolator
0 = input switch closed, transistor on or < 1.4V applied
1 = input switch open, transistor off or > 4.5V applied
Override input
A 24V logic signal applied across the terminals allows the
solenoid/alarm to be operated by the control input. If it is
disconnected, the solenoid/alarm is off.
0 = < 2.0V applied across terminals 8 & 9
1 = > 9.0V applied across terminals 8 & 9
(nominal switching point 4.5V)
Control and override inputs
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS4524S Rev2 080210
MTL4525
To earth leakage
SOLENOID/ALARM DRIVER detector *
Control
switch operated with override, IIC, low power 12
6
5 11
4 10
+
The MTLx525 enables an on/off device in a hazardous area to be 9
+
3
+
controlled by a volt-free contact or logic signal in the safe area. It can 2 8
7
drive loads such as solenoids, alarms, LEDs and other low power 1
devices that are certified as intrinsically safe or are classified as non- Solenoid, alarm or Override
energy storing simple apparatus. other IS device
13 14
20 to 35V dc
The MTL4525 allows a second safe-area switch or logic signal to Vs+
be connected that enables the output to be disabled to permit, for Vs
example, a safety system to override a control signal.
MTL5525
SPECIFICATION
See also common specification Hazardous area Safe area
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx525 Rev2 080210
MTL4526
Contact/Logic 2 ch Off On On On
Input 1in2out On On On On
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx526 Rev2 080210
MTL4531
VIBRATION TRANSDUCER
INTERFACE 6 12
5 11
4 10
The MTLx531 repeats a signal from a vibration sensor in a hazardous 0V
3- Vibration 3 9 ve
area, providing an output for a monitoring system in the safe area.
wire transducer 2 8 Monitor
The interface is compatible with 3-wire eddy-current probes and 1 7
0V
accelerometers or 2-wire current sensors; the selection is made by a 3
2- Vibration
switch on the side of the module. wire transducer 2
1 13 14
20 to 35V dc
Vs+
SPECIFICATION Vs
See also common specification
350W 24V
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx531 Rev2 080210
MTL4532
5
PULSE ISOLATOR Current
pulse
Configuration
socket
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx532 Rev2 080210
MTL4533
MTL4533 – MTL5533 Hazardous area Safe area
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx533 Rev2 080210
MTL4541/S
I +
9
The MTLx541 provides a fully-floating dc supply for energising a +3 4/20mA
2 I 8 +
conventional 2- or 3-wire 4/20mA transmitter, which is located in a 1 7 +
4/20mA Load Load
hazardous area, and repeats the current in another floating circuit to
drive a safe-area load. For HART 2-wire transmitters, the unit allows
13 14
bi-directional communications signals superimposed on the 4/20mA 20 to 35V dc
loop current. Alternatively, the MTLx541S acts as a current sink for a Vs+
safe-area connection rather than driving a current into the load. Vs
SPECIFICATION
See also common specification MTL5541/S
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx541/S Rev2 080210
MTL4541A/AS
CURRENT REPEATER
4/20mA passive i/p for HART transmitters ®
6 12
5 11
4 10
MTL4541A MTL4541AS
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx541A/AS Rev2 080210
MTL4544/S
MTL4544/S – MTL5544/S Hazardous area Safe area
Ch 2 + Ch 2
transmitters + 6 I 12
4/20mA
5 11
4 I 10
+
4/20mA Load Load
The MTLx544 provides fully-floating dc supplies for energising two +
I 9
conventional 2-wire or 3-wire 4/20mA or HART transmitters located in +3 4/20mA
2 8
1 I 7
+
a hazardous area, and repeats the current in other circuits to drive two 4/20mA Load Load
Ch 1
safe-area loads. For smart transmitters, the unit allows bi-directional Ch 1
transmission of digital communication signals superimposed on the 13 14
4/20mA loop current. Alternatively, the MTLx544S acts as a current 20 to 35V dc
Vs+
sink for a safe-area connection rather than driving a current into the
Vs
load.
SPECIFICATION MTL5544/S
See also common specification Hazardous area Safe area
Number of channels
Two
Location of transmitter MTL5544 MTL5544S
Zone 0, IIC, T4–6 hazardous area if suitably certified Ch 2 Load
Div. 1, Group A hazardous location + 6 I 7
+
5 8
4 I 9
4/20mA
Safe-area output 4/20mA + Load
Signal range: 4 to 20mA Ch 1 Load
I 10
Under/over-range: 0 to 24mA + 3 11 +
2
1 I 12
4/20mA
Safe-area load resistance (MTLx 544) 4/20mA + Load
@ 24mA: 0 to 360Ω 13 Vs
@ 20mA: 0 to 450Ω 14 Vs+
Safe-area load (MTLx544S) 20 to 35V dc
Current sink: 600Ω max.
Maximum voltage source: 24V dc
Safe-area circuit output resistance: > 1MΩ
Safe-area circuit ripple
< 50μA peak-to-peak LED indicator
Hazardous-area input Green: power indication
Signal range: 0 to 24mA (including over-range) Maximum current consumption (with 20mA signals)
Transmitter voltage: 16.5V at 20mA 96mA at 24V dc
Transfer accuracy at 20°C Power dissipation within unit (with 20mA signals)
Better than 15μA MTLx544 1.4W @ 24V dc
Temperature drift MTLx544S 1.9W @ 24V dc
< 0.8μA/°C Safety description (each channel)
Response time Terminals 2 to 1 and 3, and 5 to 4 and 6:
Settles to within 10% of final value within 50μs Vo =28V Io =93mA Po =651mW Um = 253V rms or dc
Communications supported Terminals 1 to 3 and 4 to 6:
HART (terminals 1 & 2 and 4 & 5 only) Simple apparatus ≤1.5V, ≤0.1A and ≤25mW; can be connected
without further certification into any IS loop with an open-circuit
voltage <28V
SIL capable
These models have been assessed for use in IEC 61508 functional
safety applications. See data on MTL web site.
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx544/S Rev2 080210
MTL4544A/AS
SPECIFICATION
See also common specification MTL5544A/AS
Safe-area output
Signal range: 4 to 20mA
Under/over-range: 1.0 to 21.5mA
Safe-area load resistance (MTL5544A)
Conventional transmitters: 0 to 360Ω LED indicator
Smart transmitters: 250Ω ±10% Green: power indication
Safe-area load (MTL5544AS) Power requirement (with 20mA signal)
Current sink: 600Ω max. 70mA at 24V
Maximum voltage source: 24V DC 85mA at 20V
Safe-area circuit output resistance: > 1MΩ 50mA at 35V
Safe–area circuit ripple Power dissipation within unit (with 20mA signals)
< 50μA peak-to-peak up to 80kHz MTLx544A 1.5W @ 24V dc
Transfer accuracy at 20°C MTLx544AS 2.0W @ 24V dc
Better than 20μA Safety description
Temperature drift Terminals 1 to 2 and 4 to 5:
< 1μA/°C Um = 253V rms or dc.
Response time 8.6V (diode). This voltage must be considered when calculating
Settles within 200μA of final value after 20ms the load capacitance.
Communications supported Non-energy-storing apparatus ≤1.5V, ≤0.1A and ≤25mW; can be
HART connected without further certification into any IS loop with an
open-circuit voltage < 28V
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx544A/AS Rev2 080210
MTL4544D
MTL4544D – MTL5544D Hazardous area Safe area
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx544D Rev2 080210
MTL4546/C/Y
MTL4546/C/Y – MTL5546/Y Hazardous area Safe area
ISOLATING DRIVER
for 4–20mA HART® valve positioners
+
with line fault detection 6
5
12
4/20mA
11
4 10
I 9
The MTLx546 accepts a 4/20mA floating signal from a safe-area controller + 3
to drive a current/pressure converter (or any other load up to 800Ω) in a P 4/20mA
2 8
I 7
hazardous area. For HART valve positioners, the module also permits I 1
bi-directional transmission of digital communication signals. Process
controllers with a readback facility can detect open or short circuits in 13 14
20 to 35V dc
the field wiring: if these occur, the current taken into the terminals drops Vs+
to a preset level. The MTL4546C and the MTLx546Y are very similar Vs
to the MTLx546 except that they provide open circuit detection only
(i.e. no short-circuit detection).
MTL5546/Y
SPECIFICATION Hazardous area Safe area
See also common specification
Number of channels
One
Location of I/P converter 6 7
Zone 0, IIC, T4–6 hazardous area if suitably certified 5 8
4 9
Div. 1, Group A, hazardous location
Working range I 10
4 to 20mA + 3 11
P 4/20mA
2 4/20mA
I 12
Digital signal bandwidth I 1 +
500Hz to 10kHz 13 Vs
Maximum load resistance 14 Vs+
800Ω (16V at 20mA) 20 to 35V dc
Minimum load resistance
90Ω (short-circuit detection at < 50Ω)
Output resistance
> 1MΩ
LED indicator
Under/over range capability Green: power indication
Under range = 1mA
Maximum current consumption (with 20mA signals into 250Ω load)
Over range = 24mA (load ≤ 520Ω)
35mA at 24V dc
Input and output circuit ripple
Power dissipation within unit (with 20mA signals into 250Ω load)
< 40μA peak-to-peak
0.8W at 24V
Transfer accuracy at 20°C
Safety description
Better than 20μA
Vo =28V Io =93mA Po =651mW Um = 253V rms or dc
Temperature drift
SIL capable
< 1.0μA/°C
These models have been assessed for use in IEC 61508 functional
Input characteristics
safety applications. See data on MTL web site.
Field wiring state MTLx546 MTL4546C MTLx546Y
Normal < 6.0V < 6.0V < 6.0V
Open-circuit < 0.9mA < 0.9mA < 0.5mA
Short-circuit < 0.9mA N.A. N.A.
Response time
Settles within 200μA of final value within 100ms
Communications supported
HART
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx546/C/Y Rev2 080210
MTL4549/C/Y
MTL4549/C/Y - MTL5549/Y Hazardous area Safe area
ISOLATING DRIVER
two-channel, for 4–20mA, HART® Ch 2
Ch 2 +
valve positioners with line fault detection P
+ 6
5
I 12
4/20mA
11
4/20mA
I 4 I 10 Ch 1
+
9
The MTLx549 accepts 4/20mA floating signals from safe-area controllers + 3 I
4/20mA
P 4/20mA
2 8
to drive 2 current/pressure converters (or any other load up to 800Ω) in 1 I 7
I
a hazardous area. For HART valve positioners, the module also permits
Ch 1
bi-directional transmission of digital communication signals. Process
controllers with a readback facility can detect open or short circuits 13 14
20 to 35V dc
in the field wiring: if these occur, the current taken into the terminals Vs+
drops to a preset level. The MTL4549C and MTLx549Y are very similar Vs
to the MTLx549 except that they provide open circuit detection only
(i.e. no short-circuit detection).
MTL5549/Y
SPECIFICATION Hazardous area Safe area
See also common specification
Number of channels
Two
Ch 2 Ch 2
Location of I/P converter + 6 I 7
P 5 8
Zone 0, IIC, T4–6 hazardous area if suitably certified 4/20mA 4/20mA
Div. 1, Group A, hazardous location
I 4 I 9
+
Ch 1
Working range 10
+ 3 I
11
4 to 20mA P 4/20mA
2
I 1 I 12 4/20mA
Digital signal bandwidth +
500Hz to 10kHz Ch 1 13 Vs
Maximum load resistance 14 Vs+
20 to 35V dc
800Ω (16V at 20mA)
Minimum load resistance
90Ω (short-circuit detection at < 50Ω)
Output resistance
> 1MΩ LED indicator
Under/over range capability Green: power indication
Under range = 1mA Maximum current consumption (with 20mA signals into 250Ω load)
Over range = 24mA (load ≤ 520Ω) 70mA at 24V dc
Input and output circuit ripple Power dissipation within unit (with 20mA signals into 250Ω load)
<40μA peak-to-peak 1.6W at 24V
Communications supported Safety description (each channel)
HART Vo=28V Io=93mA Po=0.65W Um = 253V rms or dc
Transfer accuracy at 20°C SIL capable
Better than 20μA These models have been assessed for use in IEC 61508 functional
Temperature drift safety applications. See data on MTL web site.
< 1.0μA/°C
Input characteristics
Field wiring state MTL4549 MTL4549C MTL4549Y
Normal < 6.0V < 6.0V < 6.0V
Open-circuit < 0.9mA < 0.9mA < 0.5mA
Short-circuit < 0.9mA N.A. N.A.
Response time
Settles within 200μA of final value within 100ms
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx549/C/Y Rev2 080210
MTL4561
MTL4561 – MTL5561 Hazardous area Safe area
FIRE AND SMOKE To earth leakage
detector *
DETECTOR INTERFACE Ch 2
2-channel +
+ 6 I 12
Ch 2
5 11
4 I 10
The MTLx561 is a loop-powered 2–channel interface for use with Fire
detectors +
conventional fire and smoke detectors located in hazardous areas. + 3 I 9
Ch 1
In operation, the triggering of a detector causes a corresponding 2 8
1 I 7
change in the safe–area current. The unit features reverse input
polarity protection, while ‘no-fail’ earth fault detection on either line
can be provided by connecting an earth leakage detector to terminal Ch 1
13 14
3 and/or 6. To earth leakage
detector *
SPECIFICATION
MTL5561
See also common specification
Hazardous area Safe area
Number of channels
Two, fully floating, loop powered To earth leakage
detector *
Location of fire and smoke detectors
Zone 0, IIC, T4–6 hazardous area if suitably certified Ch 2
Div. 1, Group A, hazardous area
+ 6 I 7
Input voltage 5 8
Ch 2
6 to 30V dc 4 I 9
+
Fire
Current range detectors 10
1 to 40mA, nominal + 3 I
11
2
I 12 Ch 1
Quiescent safe–area current at 20°C 1 +
(hazardous–area terminals open circuit)
13
< 400μA at Vin = 24V per channel Ch 1 14
Integral input polarity protection To earth leakage
Input circuit protected against reverse polarity detector *
‘No-fail’ earth fault protection
Enabled by connecting terminals 3 and/or 6 to an earth leakage
detector (see notes) *Signal plug HAZ1-3 is required for access to this function
Fault on either line of each channel proclaimed: unit continues
worki ng
Notes:
1. To maintain isolation between the two channels, separate earth leakage
detectors are needed.
2. The earth leakage detectors introduce a 100μA, 1Hz ripple to the field circuit.
Minimum output voltage Vout at 20°C
For Vin ≤ 25V: Vout = Vin – (0.38 x current in mA) – 2V
For Vin > 25V: Vout = 22.5V – (0.35 x current in mA)
Maximum output voltage
28V from 300Ω
Transfer accuracy at 20°C
Better than 400μA
Temperature drift
< 4μA/°C ( 0°C to 60°C)
< 15μA/°C (–20°C to 0°C)
Response time to step input
Settles to within 5% of final value within 1.5ms
Power dissipation within unit
0.7W maximum at 24V with 40mA signal (each channel)
0.9W maximum at 30V with 40mA signal (each channel)
Safety description for each channel
Vo=28V Io=93mA Po=0.65W Um = 253V rms or dc
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx561 Rev2 080210
MTL4575
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx575 Rev2 240510
MTL4576-RTD
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx576R Rev2 080210
MTL4576-THC
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx576T Rev2 080210
MTL4599
Hazardous area Safe area
MTL4599 - MTL5599
DUMMY ISOLATOR
6 12
5 11
Unused 4 10 Unused
The primary function of the MTLx599, which can be used with all other hazardous- safe-area
area cores 3 9 cores
MTLx500 Series units, is to provide termination and earthing facilities 2 8
for unused cable cores from hazardous areas. 1 7
SPECIFICATION 13 14
See also common specification
Unused safe-area cores
Weight
60g
MTL5599
Hazardous area Safe area
6 7
5 8
4 9
Unused
hazardous- Unused
3 10
area cores safe-area
2 11
12
cores
1
13
14
MTL4599N
GENERAL PURPOSE
FEED-THROUGH MODULE 12 12
11 11
10 10
SPECIFICATION
See also common specification
Weight
60g
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx599/N Rev2 080210
DIMENSIONS (MM)
PWR
OPA
OPB
OPC
OPD
FLT
regarding safety approvals, certificates and entity parameters.
104.8 15.8
Connectors
Each unit is supplied with signal connectors, as applicable. HAZ
When using crimp ferrules for the hazardous or non-hazardous
(safe) signal connectors the metal tube length should be 12mm
and the wire trim length 14mm.
Isolation
250V rms, tested at 1500V rms minimum, between safe- and
hazardous-area terminals.
121.8
50V between safe-area circuits and power supply
Supply voltage
20 – 35V dc
Location of units
Safe area
Terminals
2
Accepts conductors of up to 2.5mm stranded or single-core
Mounting
MTL4500
MTL4500 series backplanes
MTL5500
T-section 35mm DIN rail (7.5 or 15mm) to EN 50022 MTL5500
Ambient temperature limits
–20 to +60°C (–6 to +140°F) operating Optional TH5000 tag holder for individual
isolator identification.
–40 to +80°C (–40 to +176°F) storage
Accepts tag label 25 x 12.5 ±0.5mm, 0.2mm thick
Humidity
5 to 95% relative humidity
Weight MTL5510
OPA
OPB
OPC
OPD
FLT
MTL4500 140g
MTL5500 150g 109.8 16.0mm PITCH
104.8 15.8
HART® is a registered trademark of HART Communication Foundation HAZ SAFE
118.8
123.6
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPSx5CS Rev2 080210
MPA5500 PCS45/PCL45USB
A.C. POWER ADAPTOR CONFIGURATOR
FOR MTL CONVERTERS
The MPA5500 enables any MTL5500 Series module that is normally The PCS45/PCL45USB configurator allows MTL converters to be
powered from a nominal 24V DC supply (i.e. those that are not loop- configured from a standard PC running a Microsoft® Windows®
powered) to be powered from a high-voltage AC supply. operating system. It comprises PC software, provided on a CD (PCS45),
and an ATEX certified interfacing link (PCL45USB). Converters can be
It plugs into the power socket (terminals 13 and 14) of an MTL5500 configured from the safe area, while on-line, and configurations can be
module and clips securely onto the module housing. The 25V DC saved to disk and printed out when required. It is suitable for use with
power output from the adaptor is sufficient to supply a single module MTL4000, MTL4500, MTL5000 and MTL5500 series products.
and can be connected to any normal AC power source.
Safe area
AC inputs USB
15.8 connector
133 20 MTL5500
MTL4500
3-pole
jack plug
3.5mm
PCS45
software CD
MTL5073
MTL5074
118.8
Interfacing link
MTL4073
MTL4075 PCL45USB PC LINK
11 cable provided
MTL Instruments GmbH S/N: 1201
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
MTL5991 MTL5500 SERIES
24V DC POWER SUPPLY POWERBUS KITS
PB - 8T,16T,24T,32T
A DIN-rail mounted unit for locations where a dc supply is not A quick and easy way to distribute DC power to MTL5500 Series
readily available. The wide input power supply range makes this unit modules. Each powerbus kit includes 4 single ferrules, 4 twin ferrules
universally applicable and the 24V dc , 2A output will drive a useful and 2 insulation displacement connectors (Scotchlok).
number of MTL5000 and MTL5500 series modules.
Safe area
+
4
+ 1 x2
5
2
6 Optional insulation
3 displacement
7 connectors
8
SPECIFICATION
Power supply
85 to 264V ac 47 to 63Hz
Power dissipation within unit
7.2W @ 2A
Mounting
35mm DIN (top hat) rail
Output voltage
24V dc nom (23.64 min/24.36 max)
Output current SPECIFICATION
2A maximum (1.7A with <105V ac input) Available in 4 different lengths:
LED indicators PB - 8T = 8 connectors and loops
Green: Power indication PB - 16T = 16 connectors and loops
Weight PB - 24T = 24 connectors and loops
310g PB - 32T = 32 connectors and loops
Ambient temperature Insulation material :
Operating temperature –10°C to +50°C PVC
Storage temperature –40°C to +85°C Conductor :
2
Terminals 24 strands of 0.2mm dia (0.75mm ) standard copper
2
Cage clamp type accommodating conductors up to 2.5mm , Insulation thickness :
stranded or single-core 0.5 to 0.8 mm
Note: Segregation between hazardous and safe area wiring must be maintained. Current rating :
12A max
Operating temperature range :
4 5 6 7 8
1 2 3
- 20ºC to +60ºC
Max voltage drop on 32 modules drawing 130mA max :
0.5V
38 (1.5)
90 (3.54)
Note: To reduce the risk of excessive voltage drop or overcurrent do not connect
powerbuses in series.
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
125 Ø 5.5 131 (inside)
MTL5500 SERIES
ENCLOSURES
187
157
175
70
107 150
DIMENSIONS (mm) AND MOUNTING 137 DX070
80
102
270
305
249
395
339
360
430
80
170
102
520 Ø 7.2
576
249
305
DX430
DX170
147 (inside)
147 (inside)
184
184
SPECIFICATION
Note: N. America/Canada - Enclosures are rated NEMA 4X so can
Construction
be used in Class 1, Division 2 (gases) location, but check with local
Glass reinforced polycarbonate base - DX070
requirements and ensure all cable entries also conform. Additional
Glass reinforced polyester base - DX170, DX430
warning label will be required on or near the enclosure, see installation
Transparent polycarbonate lid
details. Not suitable for Class II or III, Division 2 hazardous locations.
Protection
Dust-tight and water-jet proof to IEC529:IP65 Approximate capacities (on DIN rail between earth terminals)
Lid fixing
* Use these figures when IMB57 mounting blocks for tagging/earth are included.
Captive fixing screws
Weight (excluding barriers/isolators) kg Number of MTL5500 isolators
DX070 0.8
DX070 4 (2)*
DX170 2.6
DX430 4.1 DX170 10 (8)*
Items provided DX430 26 (24)*
DIN rail - fitted
ETL7000 Earth terminals (2 x) - fitted Ambient temperature limits
"Take care IS" front adhesive label Dependent on units fitted. See instruction manual INM5500.
Cable trunking (except DX070)
Note: Isolators are not included.
Mounting
Wall fixing lugs provided. For further details refer to INM5500.
Tagging and earth rail
Accommodates MTL5500 Series accessories.
Permitted location
Safe (non-hazardous) area
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
ERB57S Earth-rail bracket, straight
Nickel-plated; supplied with two push fasteners, one (14mm,
MTL5500 SERIES 2 2
35mm ) earth-rail clamp and one (10mm, 16mm ) earth clamp.
ACCESSORIES 3mm
150mm
10mm
MTL5500 Series isolators mount quickly and easily onto standard DIN 16mm2 35mm2 16mm2 35mm2
rail. A comprehensive range of accessories simplifies earthing and
tagging arrangements.
THR2
10mm 10mm
14mm 14mm
10mm
ETM7 TH5000
HAZ1-3 TGL57
HAZ4-6
TAG57 5.5
mm 7mm
31mm
Grey spacer, one required between each MTL5995 and any
adjacent module on a DIN rail, to provide 10mm air-circulation
space between modules
CONNECTORS
Each MTL5500 unit is supplied with signal and power connectors, as
135mm
applicable.
Spares replacement connectors are available separately; see ordering
82mm
information.
28mm
See also
‘MTL5500 Series powerbus kits'
66mm 15mm
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
CUSTOM, STANDARD AND
UNIVERSAL BACKPLANES
FOR EASY DCS INTEGRATION
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
CPS BACKPLANE dimensions (mm)
157 285
28.5
72 28.5 96 112 112
59
B B
38 B B
32 38
B B
B
1 2 3 4 5 6 7 8
B 1 2 3 4 5 6 7 8 9 1 0 11 12 13 14 15 16
A A A A A
A A
1 2 3 4
CPS16
BPS16
CPS08
BPS08
175
175
113
CPS16-CC
BPS16-CC
170
CPS08-CC
BPS08-CC
113
132
A A A A A
C C
A A C C C C
C C
CPS08 CPS16
CPS04
446
10 143 139 143
B B
23
A A A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
B B
CPS24
BPS24
100
CPS24-CC
BPS24-CC
140
A A A A
CPS24
Power requirements, Vs
21V dc to 35V dc through plug-in connectors
Safe–area connections
2
CPS: 2.5mm screw-clamp terminals – 6 positions per module
Power sense
Through separate plug-in crimp connector
Weight (without modules or accessories)
CPS04: 96g
CPS08: 225g
CPS16: 419g
CPS24: 592g
Earth terminals
Earth rail Tagging
strip
483mm
Fuses
132.5mm
(3U)
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310
ORDERING INFORMATION
Please go to our website at www.mtl-inst.com for the latest information regarding safety approvals, certificates and entity parameters.
The given data is only intended as a product description and should not be regarded as a legal warranty of proper-
ties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 487 7887
[email protected] [email protected] [email protected] EPS45/5500 Rev3 250310