Inspection PDF
Inspection PDF
Nozzles
• Severe deterioration
IGV bushings
• Wear
Bearings/seals
• Scoring/wear
Compressor blades
• Corrosion/erosion
• Rubs/FOD
Rotor inspection
Compressor discharge case Cracks Repair or monitoring
Turbine shell Cracks Repair or monitoring
Compressor and compressor Wear Repair
discharge case hooks
Cases – exterior and interior Cracks Repair or monitoring
Exhaust diffuser Cracks Weld repair
Exhaust diffuser insulation Loose/missing parts Replace/tighton parts
Forward diffuser flex seal Wear/cracked parts Replace seals
30
Major Inspection
Hot Gas Path
Inspection
Combustion
Inspection
• Visually inspect the exhaust diffuser for any cracks in flow path five days, could take weeks. GE will provide recommendations
surfaces. Inspect insulated surfaces for loose or missing regarding the types and quantities of spare parts needed; however,
insulation and/or attachment hardware in internal and external it is up to the owner to purchase these spare parts on a planned
locations. In E-class machines, inspect the insulation on the basis allowing adequate lead times.
radial diffuser and inside the exhaust plenum as well.
Early identification of spare parts requirements ensures their
• Inspect exhaust frame flex seals, L-seals, and horizontal joint availability at the time the planned inspections are performed.
gaskets for any signs of wear or damage. Inspect steam gland Refer to the Reference Drawing Manual provided as part of the
seals for wear and oxidation. comprehensive set of O&M Manuals to aid in identification and
ordering of gas turbine parts.
• Check torque values for steam gland bolts and re-torque to
full values. Additional benefits available from the renewal parts catalog data
system are the capability to prepare recommended spare parts
• Check alignment – gas turbine to generator/gas turbine to
lists for the combustion, hot gas path and major inspections as
accessory gear.
well as capital and operational spares.
Comprehensive inspection and maintenance guidelines have been
Typical expectations for estimated repair cycles for some of the
developed by GE and are provided in the O&M Manual to assist
major components are shown in Appendix D. These tables assume
users in performing each of the inspections previously described.
that operation of the unit has been in accordance with all of the
Parts Planning manufacturer’s specifications and instructions.
Lack of adequate on-site spares can have a major effect on plant Maintenance inspections and repairs are also assumed to be
availability; therefore, prior to a scheduled disassembly type of done in accordance with the manufacturer’s specifications and
inspection, adequate spares should be on-site. A planned outage instructions. The actual repair and replacement cycles for any
such as a combustion inspection, which should only take two to particular gas turbine should be based on the user’s operating
New Nozzle
Acceptance Standards
Severe Deterioration
Operating Hours
Figure 43. First-stage nozzle wear-preventive maintenance: gas fired – continuous dry – base load
32
Factored Hours/Factored Starts
Type of Inspection Combustion System MS3002K MS5001PA/MS5002C, D MS6B MS7E/EA MS9E
Combustion Non-DLN 24000/400 12000/800 (1) (3) 12000/1200 (2) (3) 8000/900 (3) 8000/900 (3)
Hot Gas Path 24000/900 24000/900 24000/900 24000/900 24000/900 24000/900 24000/900 24000/900
Factors that can reduce maintenance intervals: 1. Units with Lean Head End liners have Note: Factored Hours/Starts intervals include an
• Fuel • Trips a 400-starts combustion inspection interval. allowance for nominal trip maintenance
2. Machines with 6581 and 6BeV combustion factor effects.
• Load setting • Start cycle
hardware have a 12000/600 combustion Hours/Starts intervals for Major Inspection
• Steam/water injection • Hardware design inspection interval. are quoted in Actual Hours and Actual Starts.
• Peak load firing 3. Multiple Non-DLN configurations exist Repair/replace cycles reflect current
operation (Standard, MNQC, IGCC). The typical case production hardware, unless otherwise
is shown; however, different quoting limits noted, and operation in accordance with
may exist on a machine and hardware basis. manufacturer specifications. They represent
Contact a GE Energy representative for initial recommended intervals in the absence
further information. of operating and condition experience.
Figure 44. Base line recommended inspection intervals: base load – gas fuel – dry
34
Rotor Inspection Interval start classification is key. Additionally, equivalent starts for trips
Like HGP components, the unit rotor has a maintenance interval from load are added. The total equivalent starts are divided by
involving removal, disassembly and thorough inspection. This the actual number of starts to yield the maintenance factor. The
interval indicates the serviceable life of the rotor and is generally rotor starts-based maintenance interval for a specific application
considered to be the teardown inspection and repair/replacement is determined by dividing the baseline rotor maintenance interval
interval for the rotor. These intervals are traditionally concurrent of 5000 starts by the calculated maintenance factor. As indicated
with hot gas path and major inspections, however, it should be in Figure 47, the baseline rotor maintenance interval is also the
noted that the maintenance factors for rotor maintenance intervals maximum interval, since calculated maintenance factors less
are distinct and different from those of combustion and hot gas than one are not considered.
path components. As such, the calculation of consumed life on
Figure 48 describes the procedure to determine the hours-based
the rotor may vary from that of combustion and hot gas path
maintenance criterion. Peak load operation is the primary
components. Customers should contact GE when their rotor has
maintenance factor for the F class rotor and will act to increase
reached the end of its serviceable life for technical advisement.
the hours-based maintenance factor and to reduce the rotor
The starts-based rotor maintenance interval is determined from the maintenance interval.
equation given in Figure 47. Adjustments to the rotor maintenance
When the rotor reaches the limiting inspection interval determined
interval are determined from rotor-based operating factors as were
from the equations described in Figures 47 and 48, a refurbishment
described previously. In the calculation for the starts-based rotor
of the rotor is required so that a complete inspection of the rotor
maintenance interval, equivalent starts are determined for cold,
components in both the compressor and turbine can be performed.
warm, and hot starts over a defined time period by multiplying
It should be expected that some rotor components will either have
the appropriate cold, warm and hot start operating factors by the
reached the end of their serviceable life or will have a minimal
number of cold, warm and hot starts respectively. In this calculation,
Start Factors
Fh = Hot start factor (Down 1-4 hr)*
Fw1 = Warm1 start factor (Down 4-20 hr)
Fw2 = Warm2 start factor (Down 20-40 hr)
Fc = Cold start factor (Down >40 hr)
Ft = Trip from load factor
(1) F class
Note: Start factors for 7/9 FA+e machines are tabulated in Figure 23.
For other F Class machines, refer to applicable TILs.
amount of residual life remaining and will require replacement at An hours-based combustion maintenance factor can be
this inspection point. Depending on the extent of refurbishment determined from the equations given in Figure 49 as the ratio
and part replacement, subsequent inspections may be required of factored-hours to actual operating hours. Factored-hours
at a reduced interval. considers the effects of fuel type, load setting and steam or
water injection. Maintenance factors greater than one reduce
As with major inspections, the rotor repair interval should include
recommended combustion inspection intervals from those shown
thorough dovetail inspections for wear and cracking. The baseline
in Figure 44 representing baseline operating conditions. To obtain
rotor life is predicated upon sound inspection results at the majors.
a recommended inspection interval for a specific application, the
The baseline intervals of 144,000 hours and 5000 starts in Figures
maintenance factor is divided into the recommended base line
47 and 48 pertain to F class rotors. For rotors other than F class,
inspection interval.
(1) Af = 10 for DLN 1 extended lean-lean, DLN 2.0 lean-lean and DLN 2+ in extended sub-piloted
and extended piloted premixed operating modes.
36
Maintenance Factor = (Factored starts)/(Actual Starts)
Factored Starts = ∑ (Ki x Afi x Ati x Api x Asi x Ni), i = 1 to n Start/Stop Cycles
Actual Starts = ∑ (Ni), i = 1 to n Start/Stop Cycles
Where:
i = Discrete Start/Stop Cycle (or Operating Practice)
Ni = Start/Stop Cycles in a Given Operating Mode
Asi = Start Type Severity Factor
As = 1.0 for Normal Start
As = 1.2 for Start with Fast Load
As = 3.0 for Emergency Start
Api = Load Severity Factor
Ap = 1.0 up to Base Load
Ap = exp(0.009 x Peak Firing Temp Adder in deg F) for Peak Load
Ati = Trip Severity Factor
At = 0.5 + exp(0.0125*%Load) for Trip
Afi = Fuel Severity Factor (Dry, at Load)
Af = 1.0 for Gas Fuel
Af = 1.25 for Non-DLN (or 1.5 for DLN) for Distillate Fuel
Af = 2.0 for Crude (Non-DLN)
Af = 3.0 for Residual (Non-DLN)
Ki = Water/Steam Injection Severity Factor
(% Steam Referenced to Compressor Inlet Air Flow, w/f = Water to Fuel Ratio)
K = Max(1.0, exp(0.34(%Steam – 1.00%))) for Steam, Dry Control Curve
K = Max(1.0, exp(0.34(%Steam – 0.50%))) for Steam, Wet Control Curve
K = Max(1.0, exp(1.80(w/f – 0.40))) for Water, Dry Control Curve
K = Max(1.0, exp(1.80(w/f – 0.20))) for Water, Wet Control Curve
A starts-based combustion maintenance factor can be determined Inspection frequencies and the amount of downtime varies
from the equations given in Figure 50 and considers the effect within the gas turbine fleet due to different duty cycles and
of fuel type, load setting, emergency starts, fast loading rates, the economic need for a unit to be in a state of operational
trips and steam or water injection. An application specific readiness. It can be demonstrated that an 8000-hour interval
recommended inspection interval can be determined from the for a combustion inspection with minimum downtime can be
baseline inspection interval in Figure 44 and the maintenance achievable based on the above factors. Contact your local GE
factor from Figure 50. Appendix B shows six example maintenance Energy representative for the specific man-hours and
factor calculations using the above hours and starts maintenance recommended crew size for your specific unit.
factors equations.
Depending upon the extent of work to be done during each
maintenance task, a cooldown period of 4 to 24 hours may
Manpower Planning
be required before service may be performed. This time can be
It is essential that advanced manpower planning be conducted
utilized productively for job move-in, correct tagging and locking
prior to an outage. It should be understood that a wide range of
equipment out-of-service and general work preparations. At the
experience, productivity and working conditions exist around the
conclusion of the maintenance work and systems check out,
world. However, based upon maintenance inspection man-hour
a turning gear time of two to eight hours is normally allocated
assumptions, such as the use of an average crew of workers in the
prior to starting the unit. This time can be used for job clean-up
United States with trade skill (but not necessarily direct gas turbine
and preparing for start.
experience), with all needed tools and replacement parts (no repair
time) available, an estimate can be made. These estimated craft Local GE field service representatives are available to help plan
labor man-hours should include controls and accessories and the your maintenance work to reduce downtime and labor costs.
generator. In addition to the craft labor, additional resources are This planned approach will outline the renewal parts that may
needed for technical direction of the craft labor force, specialized be needed and the projected work scope, showing which tasks
tooling, engineering reports, and site mobilization/demobilization. can be accomplished in parallel and which tasks must be sequential.
cost and availability is vital to the user. A rigorous maintenance GER-3569F, “Advanced Gas Turbine Materials and Coatings.”
program will minimize overall costs, keep outage downtimes to
GEK-32568, “Lubricating Oil Recommendations for Gas Turbines
a minimum, improve starting and running reliability and provide
with Bearing Ambients Above 500°F (260°C).”
increased availability and revenue earning ability for GE gas
turbine users. GEK-110483, “Cleanliness Requirements for Power Plant
Installation, Commissioning and Maintenance.”
38
Appendix From Figure 45, at a steam injection rate of 2.4%, the
value of “M” is .18, and “K” is .6.
A.1) Example 1 – Hot Gas Path Maintenance
Interval Calculation From the hours-based criteria, the maintenance factor is
determined from Figure 45.
An MS7001EA user has accumulated operating data since the last
hot gas path inspection and would like to estimate when the next MF = [K + M(I)] x [G + 1.5(D) + Af(H) + AP x P]
one should be scheduled. The user is aware from GE publications (G + D + H + P)
that the normal HGP interval is 24,000 hours if operating on
Annual hours on peak load at +100 deg F firing temperature
natural gas, with no water or steam injection, and at base load.
It is also understood that the nominal starts interval is 1200, P = 120 hr/yr
based on normal startups, no trips, no emergency starts. The AP = 6
actual operation of the unit since the last hot gas path inspection
is much different from the GE “baseline case.” MF = [.6 + .18(2.4)] x [3200 + 1.5(350) + 0 + 6(120)]
(3200 + 350 + 0 + 120)
Annual hours on natural gas, base load
= G = 3200 hr/yr MF = 1.25
Annual hours on light distillate The hours-based adjusted inspection interval is therefore,
NA + N B + N P
T= 20 Starts with trips from base load
(a Ti = 8) MF = 0.5(40)+(127)+1.3(0)+20(2)+2(5)+(8–1)20
40+127+0
For this particular unit, the second and third-stage nozzles are
FSX-414 material. The unit operates on “dry control curve.” MF = 2
S = 600 starts [Note, since the total annual number of starts is 2 ended in a trip from full load
167, the estimated time to reach 600 starts is 1 ended in a normal shutdown
600/167 = 3.6 years.]
4 Fast loads:
In this case, the starts-based maintenance factor is greater than
1 tripped during loading at 50% load
the hours maintenance factor and therefore the inspection interval
is set by starts. The hot gas path inspection interval is 600 starts 3 achieved base load and ended in
FS = 0.5(NA)+(NB)+1.3(NP)+20(E)+2(F)+ Σ(a
i=1
TI – 1) Ti
FS = 0.5(41)+(66)+1.3(50)+20(3)+2(4)+[(6.5–1)6+
(8–1)37+(10–1)10]=601.50
AS = 41 + 66 + 50 = 157
601.5
MF = = 3.8
157
40
B) Examples – Combustion Maintenance Interval
Calculations (reference Figures 49 and 50)
DLN 1 Peaking Duty with Power Augmentation Standard Combustor Baseload on Crude Oil
+50F Tfire Increase Gas Fuel No Tfire Increase Crude Oil Fuel
3.5% Steam Augmentation 6 Hours/Start 1.0 Water/Fuel Ratio 220 Hours/Start
Start with Fast Load Wet Control Curve Normal Start and Load Dry Control Curve
Normal Shutdown (No Trip) Normal Shutdown (No Trip)
Factored Hours = Ki * Afi * Api * ti = 34.5 Hours Factored Hours = Ki * Afi * Api * ti = 788.3 Hours
Hours Maintenance Factor = (34.5/6) 5.8 Hours Maintenance Factor = (788.3/220) 3.6
Where Ki = 2.34 Max(1.0, exp(0.34(3.50-1.00))) Wet Where Ki = 1.43 Max(1.0, exp(1.80(1.00-0.80))) Dry
Afi = 1.00 Gas Fuel Afi = 2.50 Crude Oil, Std (Non-DLN)
Api = 2.46 exp(0.018(50)) Peaking Api = 1.00 Baseload
ti = 6.0 Hours/Start ti = 220.0 Hours/Start
Factored Starts = Ki * Afi * Ati * Api * Asi * Ni = 5.2 Starts Factored Starts = Ki * Afi * Ati * Api * Asi * Ni = 5.9 Starts
Starts Maintenance Factor = (5.2/1) 5.2 Starts Maintenance Factor = (5.9/1) 5.9
Where Ki = 2.77 Max(1.0, exp(0.34(3.50-0.50))) Wet Where Ki = 2.94 Max(1.0, exp(1.80(1.00-0.40))) Dry
Afi = 1.00 Gas Fuel Afi = 2.00 Crude Oil, Std (Non-DLN)
Ati = 1.00 No Trip at Load Ati = 1.00 No Trip at Load
Api = 1.57 exp(0.009(50)) Peaking Api = 1.00 Baseload
Asi = 1.20 Start with Fast Load Asi = 1.00 Normal Start
Ni = 1.0 Considering Each Start Ni = 1.0 Considering Each Start
DLN 2.6 Baseload on Distillate DLN 2.6 Baseload on Gas with Trip @ Load
No Tfire Increase Distillate Fuel No Tfire Increase Gas Fuel
1.1 Water/Fuel Ratio 220 Hours/Start No Steam/Water Injection 168 Hours/Start
Normal Start Dry Control Curve Normal Start and Load Dry Control Curve
Normal Shutdown (No Trip) Trip @ 60% Load
Factored Hours = Ki * Afi * Api * ti = 943.8 Hours Factored Hours = Ki * Afi * Api * ti = 168.0 Hours
Hours Maintenance Factor = (943.8/220) 4.3 Hours Maintenance Factor = (168.0/168) 1.0
Where Ki = 1.72 Max(1.0, exp(1.80(1.10-0.80))) Dry Where Ki = 1.00 No Injection
Afi = 2.50 Distillate Fuel, DLN Afi = 1.00 Gas Fuel
Api = 1.00 Baseload Api = 1.00 Baseload
ti = 220.0 Hours/Start ti = 168.0 Hours/Start
Factored Starts = Ki * Afi * Ati * Api * Asi * Ni = 5.3 Starts Factored Starts = Ki * Afi * Ati * Api * Asi * Ni = 2.6 Starts
Starts Maintenance Factor = (5.3/1) 5.3 Starts Maintenance Factor = (2.6/1) 2.6
Where Ki = 3.53 Max(1.0, exp(1.80(1.10-0.40))) Dry Where Ki = 1.00 No Injection
Afi = 1.50 Distillate Fuel, DLN Afi = 1.00 Gas Fuel
Ati = 1.00 No Trip at Load Ati = 2.62 0.5+exp(0.0125*60) for Trip
Api = 1.00 Baseload Api = 1.00 Baseload
Asi = 1.00 Normal Start Asi = 1.00 Normal Start
Ni = 1.0 Considering Each Start Ni = 1.0 Considering Each Start
DLN 1 Combustor Baseload on Distillate DLN 2.6 Peak Load on Gas with Emergency Starts
No Tfire Increase Distillate Fuel +35F Tfire Increase Gas Fuel
0.9 Water/Fuel Ratio 500 Hours/Start 3.5% Steam Augmentation 4 Hours/Start
Normal Start Dry Control Curve Emergency Start Dry Control Curve
Normal Shutdown (No Trip) Normal Shutdown (No Trip)
Factored Hours = Ki * Afi * Api * ti = 1496.5 Hours Factored Hours = Ki * Afi * Api * ti = 12.5Hours
Hours Maintenance Factor = (1496.5/500) 3.0 Hours Maintenance Factor = (12.5/4) 3.1
Where Ki = 1.20 Max(1.0, exp(1.80(0.90-0.80))) Dry Where Ki = 1.67 Max(1.0, exp(0.34(3.50-2.00)))
Afi = 2.50 Distillate Fuel, DLN 1 Afi = 1.00 Gas Fuel
Api = 1.00 Partload Api = 1.88 exp(0.018(35)) Peaking
ti = 500.0 Hours/Start ti = 4.0 Hours/Start
Factored Starts = Ki * Afi * Ati * Api * Asi * Ni = 3.7 Starts Factored Starts = Ki * Afi * Ati * Api * Asi * Ni = 9.6 Starts
Starts Maintenance Factor = (3.7/1) 3.7 Starts Maintenance Factor = (9.6/1) 9.6
Where Ki = 2.46 Max(1.0, exp(1.80(0.90-0.40))) Dry Where Ki = 2.34 Max(1.0, exp(0.34(3.50-1.00))) Dry
Afi = 1.50 Distillate Fuel, DLN Afi = 1.00 Gas Fuel
Ati = 1.00 No Trip at Load Ati = 1.00 No Trip at Load
Api = 1.00 Part Load Api = 1.37 exp(0.009(35)) Peaking
Asi = 1.00 Normal Start Asi = 3.00 Emergency Start
Ni = 1.0 Considering Each Start Ni = 1.0 Considering Each Start
Equivalent Availability =
Reliability = (1-FOH/PH) (100)
FOH = total forced outage hours GT UH HRSG UH ST UH
[1 – +B + x 100 ]
PH = period hours GT PH GT PH ST PH
contribution to plant output – units are %. FO = Forced Outage Events from a Running
(On-line) Condition
Equivalent Reliability =
GT FOH HRSG FOH ST FOH Service Factor: Measure of operational use, usually
[1 – +B + x 100 ] expressed on an annual basis – units are %.
GT PH B PH ST PH
SF = SH/PH x 100
GT FOH = Gas Turbine Forced Outage Hours SH = Service Hours on an annual basis
GT PH = Gas Turbine Period Hours PH = Period Hours (8760 hours per year)
42
D) Repair and Replacement Cycles (Natural Gas Only)
44
PG7211(F): 7F.01 / PG9301(F): 9F.01 Parts PG7231(FA): 7FA.02 Parts
Repair Interval Replace Interval (Hours) Replace Interval (Starts) Repair Interval Replace Interval (Hours) Replace Interval (Starts)
Combustion Liners Cl 6 (Cl) 5 (Cl) Combustion Liners Cl 6 (Cl) 5 (Cl)
Caps Cl 6 (Cl) 5 (Cl) Caps Cl 6 (Cl) 5 (Cl)
Transition Pieces Cl 6 (Cl) 5 (Cl) Transition Pieces Cl 6 (Cl) 5 (Cl)
Fuel Nozzles Cl 3 (Cl) 3 (Cl) Fuel Nozzles Cl 3 (Cl) 3 (Cl)
Crossfire Tubes Cl 1 (Cl) 1 (Cl) Crossfire Tubes Cl 1 (Cl) 1 (Cl)
Crossfire Tube CI 1 (CI) 1 (CI) Crossfire Tube CI 1 (CI) 1 (CI)
Retaining Clips Retaining Clips
End Covers CI 6 (Cl) 3 (Cl) End Covers CI 6 (Cl) 3 (Cl)
Stage 1 Nozzles HGPI 3 (HGPI) 3 (HGPI) Stage 1 Nozzles HGPI 2 (HGPI) 2 (HGPI)
Stage 2 Nozzles HGPI 3 (HGPI) 3 (HGPI) Stage 2 Nozzles HGPI 2 (HGPI) 2 (HGPI)
Stage 3 Nozzles HGPI 3 (HGPI) 3 (HGPI) Stage 3 Nozzles HGPI 3 (HGPI) 3 (HGPI)
Stage 1 Shrouds HGPI 2 (HGPI) 2 (HGPI) Stage 1 Shrouds HGPI 2 (HGPI) 2 (HGPI)
Stage 2 Shrouds HGPI 2 (HGPI) 2 (HGPI) Stage 2 Shrouds HGPI 2 (HGPI) 2 (HGPI)
Stage 3 Shrouds HGPI 3 (HGPI) 3 (HGPI) Stage 3 Shrouds HGPI 3 (HGPI) 3 (HGPI)
Stage 1 Bucket HGPI 2 (HGPI) 2 (HGPI) Stage 1 Bucket HGPI 2 (HGPI) 2 (HGPI)(1)
Stage 2 Bucket HGPI 3 (HGPI)(1) 3 (HGPI)(1) Stage 2 Bucket HGPI 1 (HGPI)(2) 3 (HGPI)(3)
Stage 3 Bucket HGPI 3 (HGPI)(1) 3 (HGPI)(1) Stage 3 Bucket HGPI 3 (HGPI) 3 (HGPI)
Note: Repair/replace cycles reflect current production hardware, unless otherwise noted, and operation in Note: Repair/replace cycles reflect current production hardware, unless otherwise noted, and operation in
accordance with manufacturer specifications. They represent initial recommended intervals in the absence of accordance with manufacturer specifications. They represent initial recommended intervals in the absence of
operating and condition experience. For factored hours and starts of the repair intervals, refer to Figure 44. operating and condition experience. For factored hours and starts of the repair intervals, refer to Figure 44.
Cl = Combustion Inspection Interval Cl = Combustion Inspection Interval
HGPI = Hot Gas Path Inspection Interval HGPI = Hot Gas Path Inspection Interval
(1) With welded hardface on shroud, recoating at 1st HGPI is required to achieve replacement life. (1) Periodic inspections are recommended within each HGPI. GE approved repair operations may be needed
to meet 2 (HGPI) replacement. Consult your GE Energy representative for details on both.
Figure D-8. Estimated repair and replacement cycles (2) Interval can be increased to 2 (HGPI) by performing a repair operation. Consult your GE Energy
representative for details.
(3) Recoating at 1st HGPI may be required to achieve 3 HGPI replacement life.
PG7221(FA): 7FA.01 / PG9311(FA): 9FA.01 Parts Figure D-10. Estimated repair and replacement cycles
46
PG9371(FB): 9FB.01 Parts
Repair Interval Replace Interval (Hours) Replace Interval (Starts)
Combustion Liners CI 4 (CI) 4 (CI)
Caps CI 4 (CI) 4 (CI)
Transition Pieces CI 4 (CI) 4 (CI)
Fuel Nozzles CI 2 (Cl)(1) 2 (CI)(1)
Crossfire Tubes CI 1 (Cl) 1 (Cl)
Crossfire Tube CI 1 (CI) 1 (CI)
Retaining Clips
End Covers CI 4 (CI) 4 (CI)
Stage 1 Nozzles HGPI 1 (HGPI)(2) 1 (HGPI)(2)
Stage 2 Nozzles HGPI 2 (HGPI) 2 (HGPI)
Stage 3 Nozzles HGPI 3 (HGPI) 3 (HGPI)
Stage 1 Shrouds HGPI 2 (HGPI) 2 (HGPI)
Stage 2 Shrouds HGPI 2 (HGPI) 2 (HGPI)
Stage 3 Shrouds HGPI 3 (HGPI) 3 (HGPI)
Stage 1 Buckets HGPI 1 (HGPI)(2) 1 (HGPI)(2)
Stage 2 Buckets HGPI 1 (HGPI)(2) 1 (HGPI)(2)
Stage 3 Buckets HGPI 1 (HGPI)(2) 1 (HGPI)(2)
Note: Repair/replace cycles reflect current production hardware, unless otherwise noted, and operation in
accordance with manufacturer specifications. They represent initial recommended intervals in the absence of
operating and condition experience. For factored hours and starts of the repair intervals, refer to Figure 44.
CI = Combustion Inspection Interval
HGPI = Hot Gas Path Inspection Interval
(1) Blank and liquid fuel cartridges to be replaced at each CI
(2) 1 HGPI replacement interval for currently shipping units. Older units may have extended lives.
Consult your GE Energy Services representative for unit specific recommendations.
48
F) Turning Gear/Ratchet Running Guidelines
Case A.1 – Normal. Restart anticipated for >48 hours Until wheelspace temperatures <150F.(1) Rotor classified as
unbowed. Minimum 24 hours.(2)
Case A.2 – Normal. Restart anticipated for <48 hours Continuously until restart. Rotor unbowed.
Case B – Immediate rotor stop necessary. (Stop >20 minutes) None. Classified as bowed.
Suspected rotating hardware damage or unit malfunction
Before Startup:
Case C – Hot rotor, <20 minutes after rotor stop 0–1 hour(3)
Case D – Warm rotor, >20 minutes & <6 hours after rotor stop 4 hours
50
Figure 41. Gas turbine major inspection – key elements
Figure 42. Major inspection work scope
Figure 43. First-stage nozzle wear-preventive maintenance: gas fired – continuous dry – base load
Figure 44. Base line recommended inspection intervals: base load – gas fuel – dry
Figure 45. Hot gas path inspection: hours-based criterion
Figure 46. Hot gas path inspection: starts-based criterion
Figure 47. F Class rotor maintenance factor: starts-based criterion
Figure 48. F Class rotor maintenance factor: hours-based criterion
Figure 49. Combustion inspection hours-based maintenance factors
Figure 50. Combustion inspection starts-based maintenance factors
Figure B-1. Combustion maintenance interval calculations
Figure D-1. Estimated repair and replacement cycles
Figure D-2. Estimated repair and replacement cycles
Figure D-3. Estimated repair and replacement cycles
Figure D-4. Estimated repair and replacement cycles
Figure D-5. Estimated repair and replacement cycles
Figure D-6. Estimated repair and replacement cycles
Figure D-7. Estimated repair and replacement cycles
Figure D-8. Estimated repair and replacement cycles
Figure D-9. Estimated repair and replacement cycles
Figure D-10. Estimated repair and replacement cycles
Figure D-11. Estimated repair and replacement cycles
Figure D-12. Estimated repair and replacement cycles
Figure D-13. Estimated repair and replacement cycles
Figure D-14. Estimated repair and replacement cycles
Figure E-1. Borescope inspection access locations for 6F machines
Figure E-2. Borescope inspection access locations for 7/9F machines
Figure F-1. Turning Gear Guidelines
• Steam/Water Injection section added • Procedural clarifications for HGP inspection added
• Cyclic Effects section added • Added inspections for galling/fretting in turbine dovetails to major
inspection scope
5/96 Rev D
• HGP factored starts calculation updated for application of trip
• Estimated Repair and Replacement Cycles added for F/FA factors
• Estimated Repair and Replace Cycles added for FA+E • HGP factored starts example added
• Starts and hours-based rotor maintenance interval equations • F-class borescope inspection access locations added
added
• Various HGP parts replacement cycles updated and additional
6B table added
9/00 Rev G
• Revision History added
11/02 Rev H
11/09 Rev L
• Estimated Repair and Replace Cycles updated and moved to
Appendix D • Updated text throughout
52
GE Energy | GER-3620L (11/09) 53
54
GTD-222, GTD-241, GTD-450, and GECC-1 are trademarks of the General Electric Company.